Page 1 of 13 Version: 1 Owner: Initial Approved by: University H&S Committee Date of approval: Review Date DSEAR-Classification of Hazardous Areas (Zoning) and Selection of Equipment Contents Overview ................................................................................................................................................. 2 Assessing the risk .................................................................................................................................... 3 The Hazardous properties of dangerous substances. ......................................................................... 3 Relationship between fires and explosions ............................................................................................ 5 Maintenance ........................................................................................................................................... 5 Equipment in hazardous areas ............................................................................................................... 5 Marking of equipment ............................................................................................................................ 6 Selection of equipment ........................................................................................................................... 6 Classifying hazardous areas into zones ................................................................................................... 7 Gases, vapours and mists ........................................................................................................................ 8 Dusts ....................................................................................................................................................... 8 Equipment categories and zones ............................................................................................................ 8 OHSS: Classification of Hazardous areas (Zoning) and selection of equipment Guidance 202 <title>

Upload: vuongkhuong

Post on 11-May-2018

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

DSEAR-Classification of Hazardous Areas (Zoning) and Selection of Equipment

Contents Overview ................................................................................................................................................. 2

Assessing the risk .................................................................................................................................... 3

The Hazardous properties of dangerous substances. ......................................................................... 3

Relationship between fires and explosions ............................................................................................ 5

Maintenance ........................................................................................................................................... 5

Equipment in hazardous areas ............................................................................................................... 5

Marking of equipment ............................................................................................................................ 6

Selection of equipment ........................................................................................................................... 6

Classifying hazardous areas into zones ................................................................................................... 7

Gases, vapours and mists ........................................................................................................................ 8

Dusts ....................................................................................................................................................... 8

Equipment categories and zones ............................................................................................................ 8

OHSS: Classification of Hazardous areas (Zoning) and selection of equipment Guidance

202

<title>

Page 2 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

Flammable liquids ................................................................................................................................. 10

Larger scale laboratory work ................................................................................................................ 10

Instruments with internal flames.......................................................................................................... 11

Fume Cupboards ................................................................................................................................... 11

Liquefied flammable gases ................................................................................................................... 11

Flammable gases ................................................................................................................................... 12

Releases into enclosed spaces .............................................................................................................. 12

Conclusions ........................................................................................................................................... 12

Overview Gases, vapours, mists and dusts can all form explosive atmospheres with air. Hazardous area

classification is used to identify places where, because of the potential for an explosive atmosphere,

special precautions over sources of ignition are needed to prevent fires and explosions.

Hazardous area classification should be carried out as an integral part of the risk assessment to

identify places (or areas) where controls over ignition sources are needed (hazardous places) and

also those places where they are not (non-hazardous places). Hazardous places are further classified

in Zones which distinguish between places that have a high chance of an explosive atmosphere

occurring and those places where an explosive atmosphere may only occur occasionally or in

abnormal circumstances. The definitions of the Zones (which are included in DSEAR) also recognise

that the chance of a fire or explosion depends on the likelihood of an explosive atmosphere

occurring at the same time as an ignition source becomes active.

DSEAR defines a place where an explosive atmosphere may occur in quantities that require special

precautions to protect the health and safety of workers as hazardous. A place where an explosive

atmosphere is not expected to occur in quantities that require such special precautions is deemed to

be non-hazardous. For these purposes “special precautions” means precautions to control potential

ignition sources within a hazardous area, particularly in relation to the construction, installation and

use of equipment.

The term “not expected to occur in such quantities” means that employers should consider the

likelihood of releases of explosive atmospheres as well as the potential quantity of such releases

when considering area classification. So if a release is extremely unlikely to occur and/or if the

quantities released are small, it may not be necessary to classify the area as hazardous.

For example, if a dangerous substance is being carried through a seamless pipe, and that pipe has

been properly installed and maintained, it is extremely unlikely that the substance will be released.

An explosive atmosphere would not be expected to occur from this source and the area surrounding

the pipe would be non-hazardous.

Page 3 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

A spillage from a small bottle of solvent would release so little flammable material that no special

precautions are needed other than the general control of ignition sources (for example, no smoking)

and cleaning and disposing of the spillage. It would not be classified as a hazardous area. When

considering whether hazardous area classification is necessary for “small” quantities of dangerous

substances the actual circumstances of use and any specific industry guidance should also be taken

into account.

Dangerous substances in small pre-packaged containers for sale, display, etc. in retail premises

would not normally ("normal" is intended to ensure that atypical situations such as a poorly

ventilated basement in a Shop etc. where aerosols or other flammables are present remains subject

to a hazardous area classification study) require the area to be classified as hazardous. However we

would expect a hazardous area classification to be carried out for pre-packaged containers held in

large quantities e.g. in warehouses. Procedures to clean up and dispose of any spillage/release and

to control ignition sources in the event of such a release would be needed.

Assessing the risk Identifying hazardous or non-hazardous areas should be carried out in a systematic way. Risk

assessment should be used to determine if hazardous areas exist and to then assign zones to those

areas. The assessment should consider such matters as:

the hazardous properties of the dangerous substances involved;

the amount of dangerous substances involved;

the work processes, and their interactions, including any cleaning, repair or maintenance

activities that will be carried out;

the temperatures and pressures at which the dangerous substances will be handled;

the containment system and controls provided to prevent liquids, gases, vapours or dusts

escaping into the general atmosphere of the workplace;

any explosive atmosphere formed within an enclosed plant or storage vessel; and,

any measures provided to ensure that any explosive atmosphere does not persist for an

extended time, e.g. ventilation.

Taken together these factors are the starting point for hazardous area classification, and should

allow for the identification of any zoned areas. The following paragraphs give further information on

what to consider during an assessment.

The Hazardous properties of dangerous substances. The properties of a dangerous substance that need to be known include the boiling point and flash

point of any flammable liquid, and whether any flammable gas or vapour that may be evolved is

lighter or heavier than air. For dusts, information on particle size and density will be needed, once it

has been shown that a particular dust can form an explosive atmosphere. Often, relevant

information is contained on a safety data sheet provided with the product.

The size of potential releases

Page 4 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

Some potential sources of release may be so small that there is no need to specify a hazardous area.

This will be the case if the consequence of an ignition following a release is unlikely to cause danger

to people in the vicinity. However, in the wrong circumstances ignition of quite small quantities of

flammable gas/vapour mixed with air can cause danger to anyone in the immediate vicinity. Where

this is the case, as in a relatively confined location, from which rapid escape would be difficult, area

classification may be needed even where quite small quantities of dangerous substance are present.

The size of any potential explosive atmosphere is, in part, related to the amount of dangerous

substances present. Industry specific codes have been published by a variety of organizations to

provide guidance on the quantities of various dangerous substances that should be stored. For

example, the “Code of Practice on Storage of Full and Empty LPG Cylinders and Cartridge.

Temperatures and pressures

Additional information relating to the process that involve the dangerous substances should also be

taken into account, including the temperatures and pressures used in the process, as this will

influence the nature and extent of any release, and the extent of any subsequent hazardous areas.

Some substances do not form explosive atmospheres unless they are heated, and some liquids if

released under pressure will form a fine mist that can explode even if there is insufficient vapour.

Ventilation

Ventilation, either natural, or mechanically (e.g. produced by fans), can both dilute sources of

release, and remove dangerous substances from an enclosed area. As a result there is a close link

between the ventilation at any given location, and the classification and extent of a zone around a

potential source of release. Well-designed ventilation may prevent the need for any zoned area, or

reduce it so it has a negligible extent.

Extent of hazardous areas

The assessment needs to identify areas within a workplace that are connected to places where an

explosive atmosphere may occur. This will provide information on any areas away from the source of

the hazard to which an explosive atmosphere may spread, for example through ducts. Such areas

should be included in the classification system for places where explosive atmospheres may occur.

An approach to assessing this risk is described in BS EN 60079/10. A technique for preventing this

risk is described in BS EN 50016, on pressurisation of enclosures or rooms containing electrical

equipment.

Other considerations

When considering the potential for explosive atmospheres, it is important to consider all dangerous

substances that may be present at the workplace, including waste products, residues, materials used

for cleaning or maintenance, and any used only as a fuel. Also some combinations of dangerous

substances may react together, forming an ignition source, or in combination may form an explosive

atmosphere, where singly this does not occur.

Some repeated activities involve the introduction of potential sources of ignition into an area where

a spill is possible, and which would meet the description of a hazardous area. In these

Page 5 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

circumstances, safety can be achieved by isolating power sources while a transfer is taking place,

and making suitable checks before and after a transfer, before moving equipment into or out of a

hazardous area.

Activities, such as maintenance, may incur risks not covered by the normal area classification of the

area where the activity is taking place, for instance the introduction of sources of ignition into a

hazardous area. Sometimes the dangerous substance can be removed before the maintenance work

activity starts. Sometimes, special control measures can be taken to prevent the release of any

dangerous substance during the work. In such cases the additional risks associated with the activity

should be assessed before work starts.

Relationship between fires and explosions In many cases where an explosive atmosphere can form, any ignition will cause a fire rather than an

explosion. Both fire and explosion cause dangers to workers, and in many cases the precautions

required to prevent an ignition are the same. The overall package of precautions required will

depend on the possible consequences of a fire or explosion.

Many factors influence the risks from a fire involving dangerous substances. In particular, employers

should consider whether a fire could lead to an explosion, how fast a fire might grow, what other

materials might be rapidly involved, any dangers from smoke and toxic gases given off, and whether

those in the vicinity would be able to escape.

Maintenance During a period when maintenance is being carried out the normal area classification drawings may

not be applicable. If dangerous substances have been removed, it may be possible to treat areas

normally classified as hazardous as non-hazardous. Alternatively, if the maintenance creates the

larger than normal risk of a release of a dangerous substance, larger areas may need to be treated as

hazardous. It is not normally necessary to create new area classification drawings for the duration of

the maintenance work.

Equipment in hazardous areas Special precautions need to be taken in hazardous areas to prevent equipment from being a source

of ignition. In situations where an explosive atmosphere has a high likelihood of occurring, reliance is

placed on using equipment with a low probability of creating a source of ignition. Where the

likelihood of an explosive atmosphere occurring is reduced, equipment constructed to a less

rigorous standard may be used. Equipment is categorised (1, 2 or 3) depending on the level of zone

where it is intended to be used.

A number of ways of constructing equipment to prevent ignition risks have been published as

harmonised European Standards, and in some cases, additional requirements are set out in the

Standards relating to installation and use.

Page 6 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

Marking of equipment A standardised marking scheme is applied to identify equipment suitable for a specific location.

Equipment built to the requirements of EPS will carry the explosion protection symbol “Ex” in a

hexagon, the equipment category number (1, 2, or 3), the letter G and/or D depending on whether it

is intended for use in gas or dust atmospheres, and other essential safety information. In many cases

this will include a temperature rating expressed as a “T” marking, and sometimes a gas group. These

indicate limitations to safe use. Employers and those installing equipment should consider the

marking and documentation provided with “Ex” equipment when it is being installed.

Selection of equipment DSEAR requires that new equipment and protective systems used in a hazardous area must be

selected on the basis of the requirements set out in the DTI’s Equipment and Protective Systems for

Use in Potentially Explosive Atmospheres Regulations 1996 (as amended) (EPS) unless the risk

assessment finds otherwise.

For much electrical equipment, employers will notice comparatively little change from the situation

now, except in the details of the marking on equipment. The EPS regulations, however, also apply to

mechanical equipment that is a potential ignition source. This is a new requirement, and until

recently there has been no mechanical equipment that has been certified for use in a hazardous

area.

A harmonised European standard for category 3 mechanical equipment is now available as BS EN

13463 part 1.

DSEAR recognises that there might be circumstances where the risk assessment finds that the

selection criteria for equipment is inappropriate, or unnecessarily restrictive. A degree of flexibility

has been introduced into Schedule 3 of the Regulations -by allowing employers to use equipment

that does not conform to the requirements in the DTI’s Regulations, where the employer’s risk

assessment finds otherwise.

It is important to understand, however, that it would normally be expected that equipment used in

zoned areas would comply with the requirements in the DTI Regulations and that equipment of a

higher or lower category than that usually required would only be present in special circumstances.

For example:

during maintenance operations where alternative effective precautions are provided to

control the risk;

where workers can be excluded from the hazardous area, and will not be at risk from any

ignition of an explosive atmosphere.

where equipment of the required category is simply not available, but a lower category can

be used in combination with other protective measures to achieve the purposes of these

regulations.

Page 7 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

Where employers intend to use the flexibility provided in DSEAR, their decision must be fully

justified in their assessment of risk. It should also be considered in the context of other requirements

placed on employers by these Regulations.

The flexibility in DSEAR does not effect in any way the duties placed on manufactures, suppliers,

importers and other “responsible persons” under the EPS Regulations 1996. Equipment they place

on the market must comply with the requirements of EPS. In many cases however, manufacturers

will have a choice to make, whether they build to category 2 or 3 standards. Their decision will

depend on the needs of the customers.

DSEAR should not be used:

To allow equipment imported from outside the EU, built to other standards, to be used

without complying with the EPS Regulations;

To justify explosion protected equipment built to lower standards than that specified by EPS.

Employers who manufacture equipment for their own use, or who import directly from outside the

EU are considered to be a “responsible person” under EPS and take on the full responsibility for

complying with those Regulations when putting that equipment into the EEA.

Classifying hazardous areas into zones Hazardous area classification is a technique for assessing the probability of formation of a flammable

atmosphere and its likely duration. No lower threshold for quantities of materials or risk for this is

given. Instead, the requirement to designate a hazardous area relates to places where special

precautions are needed to protect the safety of employees. 'Special precautions ' are taken to be

design features of electrical and other equipment that prevent it creating an ignition source. The

same principles may be extended to control the use of mobile equipment and other sources of

ignition that may be introduced into the area (for example, matches and lighters) and the risks from

electrostatic discharges.

For most laboratory operations there is no tradition of hazardous area classification or using

ignition-protected equipment. In many cases there are health risks associated with exposure to

gases and vapours and laboratory work will be designed to minimize releases and control

concentrations in the air people breathe. The concentrations needed to control the health risk i.e.

Workplace Exposure Limits (WEL’s)are far below the levels at which an explosive atmosphere can

form, so precautions designed to protect the health of laboratory workers may also help prevent the

need to designate any zoned areas. If precautions already used are adequate to prevent fire and

explosion risks to laboratory workers, then there is no need for zoning and ‘special precautions' in

terms of the ignition risk from equipment will not be necessary.

Area classification studies usually take the form of drawings identifying the hazardous areas and

zones. Additional text gives information about the dangerous substances that will be present, the

work activities that have been considered, and other assumptions made by the study. Whenever

such drawings and documents have been produced, they should be included in the risk assessment

Page 8 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

record required by DSEAR. These documents should be considered whenever new equipment is to

be introduced into a zoned area.

Gases, vapours and mists For gases, vapours and mists the zone classifications are:

Zone 0 A place in which an explosive atmosphere consisting of a mixture with air of dangerous

substances in the form of gas, vapour or mist is present continuously or for long periods or

frequently.

Zone 1 A place in which an explosive atmosphere consisting of a mixture with air of dangerous

substances in the form of gas, vapour or mist is likely to occur in normal operation occasionally.

Zone 2 A place in which an explosive atmosphere consisting of a mixture with air of dangerous

substances in the form of gas, vapour or mist is not likely to occur in normal operation but, if it does

occur, will persist for a short period only.

Dusts For dusts the zone classifications are:

Zone 20 A place in which an explosive atmosphere in the form of a cloud of combustible dust in air is

present continuously, or for long periods or frequently.

Zone 21 A place in which an explosive atmosphere in the form of a cloud of combustible dust in air is

likely to occur in normal operation occasionally.

Zone 22 A place in which an explosive atmosphere in the form of a cloud of combustible dust in air is

not likely to occur in normal operation but, if it does occur, will persist for a short period only.

Notes:

1. Layers, deposits and heaps of combustible dust must be considered as any other source

which can form an explosive atmosphere.

2. "Normal operation" means the situation when installations are used within their design

parameters.

Equipment categories and zones The hazardous area zone classification and corresponding equipment categories are:

Zone 0 or zone 20 -category 1 equipment

Zone 1 or zone 21 -category 2 equipment

Zone 2 or zone 22 -category 3 equipment

Page 9 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

Note. Category 1 equipment can also be used in zones 1 and 21 and category 1 and 2 equipment can

be used in zones 2 and 22.

Basic principles

Area classification analyses the sources of gas and vapour release, looking at those that arise in

normal operation , (primary sources) and those which only occur as a result of some foreseeable

equipment failure or operator error (secondary sources). Clearly, not all laboratory hazards will be

covered by such an analysis, but it should be part of any overall risk assessment. The aim should

always be to minimise releases into the general atmosphere of the laboratory.

On a laboratory scale, a primary source might be the vapour released when a volatile solvent is

poured from one container to another, while someone knocking the container off the bench to the

floor creates a secondary source. Primary sources should normally be so small they can easily be

controlled by adequate ventilation, and the extent of any explosive atmosphere is negligible.

Strictly, area classification takes no account of the consequences of a release, whether this is a fire

or explosion, but selection of the necessary precautions must take the consequence factor into

account and this approach is recognised in DSEAR.

For laboratory work, it is helpful to consider separately releases which occur suddenly, but where

the maximum release quantity can be specified, e.g. the fracture of a glass flask; and those where

the release once started will continue until some correctiv e action is taken to shut off the release,

e.g. closing a valve following failure of a plastic or rubber hose from a gas cylinder or mains supply.

The volatility of the product is also an important factor, but this must be considered in the context of

the temperature at which it will be used. So if you are pouring a solvent from one open container to

another at a temperature below its flash point, there should be no hazardous area, because too little

vapour is present. If you then distil the same solvent and the condenser cooling fails, vapour will be

released, and the risk is much greater. Consequently, the comments on flammable liquids apply

whenever they are used or stored above their flash point.

The degree of supervision of any continuous process should be considered. Would someone be

constantly available to take action, if cooling water flow failed, a flask cracked, or a process boiled

over? Would it be possible to isolate all electrical equipment quickly from a safe place? Turning off

switches that are in the immediate vicinity of a release might create the spark that we need to avoid.

Familiarity with an operation carried out many times should not be the basis for leaving the

equipment unsupervised, if some simple problem could create a risk to others.

Training is also relevant to assessing the risk. Students and other young people may not have the

experience in laboratory work that fully experienced staff have, but they can and should be given

training in the actions that should be taken to prevent foreseeable problems, like small spills, and

the action needed where simple problems arise. Most laboratories have good general ventilation,

but this is not primarily intended to limit the extent of any explosive atmospheres that may form.

More localised extraction is needed for this.

Page 10 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

Flammable liquids

Small scale operations

Looking first at operations with flammable liquids, at the very smallest scale of operations, the

consequences of a spill may well be trivial. Quantities up to about 50mls can be mopped up or

sometimes flushed away, and if they ignite, so long as the fire does not quickly spread, they may well

bum out before anyone is at risk, or before a laboratory worker could take any action to extinguish a

fire. If these are the conclusions of a risk assessment, formal zoning is clearly inappropriate, though

it may well be appropriate to avoid the use of naked flames and other powerful or constant ignition

sources in the immediate vicinity. Where the evaporation of a solvent is deliberately intended, e.g.

from a coated surface, the operation may need to be carried out in a fume cupboard. In these cases,

if the health risks under COSHH are proper ly controlled, there may well be no need for additional

precautions to control the fire and explosion risk.

It is expected that most work by students or pupils in schools will be at this scale.

Medium scale operations

Where quantities are larger but still manipulated on the open bench, for example up to 2.51, in a

Winchester bottle, the risks are more significant. The actual extent of a flammable atmosphere

following a spill may well be a radius of up to a metre, but only a very small height above the liquid

level. Any ignition of a spreading pool will produce a fire that quickly extends to the whole area of

the spill, and could cause a risk to laboratory staff. Particular dangers arise if the spill enters the

drains, as an explosive atmosphere could then form in an enclosed space.

Direct heating by Bunsen burners and other obvious continuous ignition sources should be avoided,

but the greatest risk probably comes from electrical equipment in use as part of the operation.

Much of this cannot be avoided, and may well not be available in ignition-protected form, e.g. hot

plates, heating mantles, stirrer controllers.

Precautions are likely to include: good handling techniques to minimise spills, sills or other liquid

retaining methods to minimise liquid spread, proper support for glass equipment, placing electrical

equipment where it will not be splashed as a result of a spill as far as practicable, and constant

supervision by trained staff, so that electrical equipment can be rapidly isolated, others warned of

any dangers, and if safe to do so, first aid fire fighting started. Most importantly, the risk that a fire

following a spill will rapidly involve other containers of flammable liquids or other dangerous

chemicals should be considered. Any necessary improvements to the storage arrangements for such

chemicals should then be implemented.

Where these and similar precautions have been adopted, the risk assessment may conclude that

there is no need for hazardous areas to be specified.

Larger scale laboratory work Laboratory work involving equipment above a 2 litre scale, and pilot scale plants need more careful

consideration. Pilot scale is taken to mean equipment with a capacity of 50-I 00 litres or more. ·

Page 11 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

Particular risks come from the use of all glass equipment that may be fractured by impact, thermal

shock, overpressure, assembly technique, and poor handling with open containers, use of temporary

hoses for flammable or other hazardous materials.

Perhaps the most useful approach to controlling the ignition risks, is to limit the extent of any

flammable atmosphere formed as a result of a release , by a combination of semi-enclosure, forced

ventilation, and then to place all electrical equipment outside the enclosure , so far as possible. This

may allow a hazardous area study to conclude that any zones are of very small or even negligible

extent. Direct heat sources, like an electric mantle may nevertheless need to be used, and could be

exposed to flammable vapours following a major failure of a glass vessel. In this case the risk

assessment should consider if the laboratory worker and any others nearby could be expected to

escape safely, and how any subsequent fire could be prevented from spreading to affect other

people and facilities.

Instruments with internal flames Some types of instrumentation use very small internal gas flames, and in principle could ignite any

surrounding explosive atmosphere, if for instance there was a release of vapour from some

operation nearby. In addition, an explosive atmosphere could form from a leak in the fuel line to the

flame, or in some cases from flammable liquids in the instrument. Such instrumentation needs

specific consideration in the risk assessment. If the maximum size of leak is very small, any release

will form an explosive atmosphere of negligible extent.

Fume Cupboards Some work at this scale may be done in a fume cupboard, and this will allow the sash to be closed to

give some protection if a fire should start. The work should be arranged so that any foreseeable

release of gas or vapour will be rapidly diluted below the explosive limit, by the airflow through the

cupboard. Precautions may still be needed to reduce the fire risk, such as retaining sills at the front

edge, and extraction ductwork kept free from flammable residues. In particular fume cupboards

should not be used as storage facilities for toxic or flammable chemicals while they are also being

used for experimental work. Rapid failure of stored bottles in a small fire could produce sufficient

vapour to prevent the extract fan diluting vapours sufficiently.

Liquefied flammable gases These may be handled either under pressure, or in refrigerated form. A small release of liquid is

likely to vaporise immediately, creating a substantial size of explosive gas/ air mixture. Pressurised

systems need to be robustly constructed, and checks provided to ensure they are leak tight. Where

liquids are handled in refrigerated form, the risks from loss of cooling or loss of insulation should be

considered. Good ventilation around the apparatus will always be needed, but there may also be a

need to designate a zone 2 area. This will depend on the foreseeability of a release of liquid, how

rapidly it might be detected, and the ability of the ventilation to disperse it quickly.

Page 12 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

Flammable gases Leaks that continue until some corrective action is taken are possible from some piped gas sources.

Low pressure mains gas pipes in domestic and similar premises are not considered to give rise to

hazardous areas although explosions caused by gas escapes in private houses do occur from time to

time. Laboratory work presents a wider range of hazards:

Many gases used are not odorised; some may be lighter than air, while others are heavier.

Gas pressures often are significantly higher than the 75mbar pressure typical of mains gas.

Many temporary connections are made using flexible rubber or plastic hose which can fail with age,

or from unsuitable connection methods or attack from propane, butane or solvents. Equipment

could fail from overpressure, if a regulator is wrongly adjusted. Some types of gas taps on open

benches can easily be knocked open inadvertently.

Releases into enclosed spaces Where vapours or gases may escape into an enclosed space like an oven, or refrigerator, the

consequence of an ignition is more likely to be an explosion than a fire. Refrigerators have exploded

in laboratories, where the light switch or thermocouple sparked when opening or closing. This risk

can be avoided by buying a unit designed for this purpose , with any spark-producing electrical

equipment sealed from contact with the internal atmosphere, rather than a designation of the inside

of unit as zone 1 or 2. In the case of an oven, it may be possible to keep heating elements below the

ignition temperature of any vapour likely to be used, or to provide adequate ventilation to prevent

the build-up of vapours, but some risks will remain unless close control is maintained over products

and quantities that can be placed inside.

The risk assessment needs to consider the ventilation provided, its reliability and the size of leak that

could be controlled in this way; what can be done to minimise the risk of a gas leak, and how any

such a leak would be identified promptly, so that appropriate action could be taken. Particular

account should be taken of the out- of­ hours risk if ventilation is shut down, or systems have to be

left under pressure.

Small leaks may well be dispersed safely by good ventilation, but the consequences of a release that

builds up and then finds a source of ignition are likely to be severe.

Conclusions Where flammable liquids or gases are handled in laboratories, it is always necessary to consider

sources of ignition in any risk assessment, and control these closely, even if there are no formally

designated hazardous areas.

Whether work is done on the open bench, in a fume cupboard or a dedicated facility for larger scale

work, a decision in a written risk assessment not to zone the laboratory must justify this on the

basis that any incident will be of limited scale and could be safely and quickly controlled by those

Page 13 of 13 Version: 1 Owner: Initial Approved by: University H&S

Committee Date of approval: Review Date

present; or that they could escape very quickly without leaving others in the building at risk. A high

standard of controls of the type described above will help justify this assessment.

There are circumstances, in particular at the pilot scale, where hazardous area classification, and the

associated use of explosion protected (Ex) equipment should be adopted. In all cases, the design of

the facility should aim to minimise the extent of any hazardous area if it cannot be avoided

completely.