MI002056-E ENGLISH 1/8 Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - Modbus connection rules - DIP-switches Settings - Digital Inputs - Frontal Panel Leds Signalling’s - Factory Settings - Module Layout - Decomissioning and Disposal SENECA s.r.l. Via Austria, 26 – 35127 – PADOVA – ITALY Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287 For manuals and configuration software, see www.seneca.it SENECA S This document is property of SENECA srl. Duplication and reprodution are forbidden, if not authorized. Contents of the present documentation refers to products and technologies described in it. All technical data contained in the document may be modified without prior notice Content of this documentation is subject to periodical revision. Z-PC Line Z-PC Line RS485 Modbus Module 5 Digital Inputs RS485 Modbus Module 5 Digital Inputs EN EN Z-D-IN Z-D-IN Installation Manual Installation Manual

Upload: others

Post on 25-Oct-2021

19 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RS485 Modbus Module 5 Digital Inputs

MI002056-E ENGLISH 1/8

Contents:- General Specifications- Technical Specifications- Installation Rules- Electrical connections- Modbus connection rules- DIP-switches Settings- Digital Inputs- Frontal Panel Leds Signalling’s- Factory Settings- Module Layout- Decomissioning and Disposal

SENECA s.r.l.Via Austria, 26 – 35127 – PADOVA – ITALYTel. +39.049.8705355 - 8705359 - Fax +39.049.8706287For manuals and configuration software, see www.seneca.it

SENECAS

This document is property of SENECA srl. Duplication and reprodution are forbidden, if not authorized. Contents of the present documentation refers to products and technologies described in it. All technical data contained in the document may be modified without prior notice Content of this documentation is subject to periodical revision.

Z-PC LineZ-PC Line

RS485 Modbus Module5 Digital Inputs

RS485 Modbus Module5 Digital Inputs

ENEN Z-D-INZ-D-IN

InstallationManual

InstallationManual

Page 2: RS485 Modbus Module 5 Digital Inputs

MI002056-E ENGLISH 2/8

General Specifications

5 digital inputs with self-powered 16 V shared negative pole.2

Removable terminals with section of 2.5 mm Input protection by 600 W/ms TVS transient current suppressors. 5 inputs with 16 bit totalizer with 100 Hz max. frequency, with settable filter. Possibility to set the input n° 5 to 32 bit fast totalizer, max frequency 10 kHz. Possibility of ON-LINE configuration. RS485 serial communication with Modbus-Rtu protocol, maximum 32 nodes. 1500 V input insulation with respect to the remaining low voltage circuits. Power supply and serial connection wiring facilitated by means of a bus that can be housed in the DIN guide. Insertion and extraction from bus without: interruption to communication or system power supply Communication times below 10 ms (@ 38400 Baud). Connection distance up to 1200 m. DIP-Switch settings for Modbus speed and address, and for RS485 line termination. All the totalizers are saved in non-volatile memory (Fe-RAM).

Technical SpecificationsInputs

Input type Reed, Contact, Proximity PNP, NPN (with external resistor) etc...

Number of Channels 5 (4+1)

Maximum Totalizers Frequency 10 kHz only for channel 5 (if configured)

UL (state OFF) 0 – 10 V , I < 2 mA

UH (state ON) 12 – 30 V, I > 3 mA

Absorbed Current 3 mA (for each input)

Power SupplyVoltage 10 – 40 V;19 - 28 V 50 – 60 Hz

Consumption Typical: 1,5 W , Max: 2,5 W @ 24V

Environmental ConditionTemperature -10 – +65°C (-10 – +55 °C UL)

Humidity 30 – 90% a 40°C non condening

Altitude Fino a 2000 m a.s.l.

Storage Temperature -20 – +85°C

Protection degree IP20

Page 3: RS485 Modbus Module 5 Digital Inputs

MI002056-E ENGLISH 3/8

Connections

Removable 3-way screw terminals, 5 mm pitch

Rear IDC10 connector for DIN 46277 rail

Dimensions / BoxDimensions L: 100 mm; H: 112 mm; W: 17,5 mm

Box PA6, Black

The module complies with the following standards:

EN61000-6-4 (electromagnetic emission, industrial environment).

EN61000-6-2 (electromagnetic immunity, industrial environment).

EN61010-1 (safety).

RS485.

Alimentazione

IngressiDigitali.

IDC10

2

..

11

IDC10

1500V

Installation RulesThe module is designed to be installed in vertical position on a DIN 46277 rail. In order to ensure optimum performance and the longest working life, the module(s) must be supplied adequate ventilation and no raceways or other objects that obstruct the ventilation slots. Never install modules above sources of heat; we recommend installation in the lower part of the control cabinet.

StandardsIsolations

ADDITIONAL NOTES :.Use in Pollution Degree 2 Environment

Power Supply must be Class 2.A max 2.5 A rated fuse shall be installed near the module.

Page 4: RS485 Modbus Module 5 Digital Inputs

MI002056-E ENGLISH 4/8

19 - 28 V 10 - 40 V

2

3

Electrical ConnectionsPower Supply and MODBUS Interface

Power Supply and Modbus interface are available by using the bus for the Seneca DIN rail, by the rear IDC10 connector or by Z-PC-DINAL1-17.5 accessory.

Z-PC-DINAL2-17.5 Accessory Use

When Z-PC-DINAL2-17.5 accessory isused the signals are provided by terminal blocks. The figure shows the meaning of the terminals and the position of the DIP-switch (present on each DIN rail supports listed on Accessories list) for network termination (not used in case of Modbus network). GNDSHLD: Shield to protect the connecting cables signal against interference (recommended).

RS485 GND

RS485 A

RS485 B

Power Supply AC / +

Power Supply AC / -

IDC 10 1

Power SupplyAs an alternative to the bus connection by Z-PC-Dinx it is also possible use the terminals 2-3 to provide power supply to the module. The upper limits must not be exceeded, to avoid serious damage to the module. If the power source is not protected against overload, then a safety fuse with a maximum value of 0.5 A must be installed in the power supply line.

Inserting on the DIN rail

As illustrated in the next figure:1) Insert the rear IDC10 connector on a DINrail free slot (the insertion is univocal becausethe connectors are polarized).2) Tighten the two locks placed at the sides ofthe rear IDC10 connector to fix the module.

Rear Connector (IDC10)

The figure show the meaning of the IDC10 connector pins, when the signals are provided directly through this connector.

Page 5: RS485 Modbus Module 5 Digital Inputs

MI002056-E ENGLISH 5/8

DIGITAL INPUTS

REED, PROXIMITY PNP, NPN, and contact-type sensor can be connected to the input terminals. The terminal 12 (+16V) is able to deliver the power supply directly for this sensors. All the inputs are connected in shared connection to terminal 1 GND.The flowing current through a closed input is approx. 3 mA.

Modbus connection rules

1) Install the modules on the DIN rail (max 120).2) Connect the remote modules using cables of proper length.Data about the cable lengths are provided on the following table:-Bus Length: Modbus network Maximum length as a function of the Baud Rate. Is the cable length to connect the two modules with bus terminators (see Scheme 1).-Derivation Length: Derivation line Maximum length as a function of the Baud Rate (see Scheme 1).

Bus length Derivation length

1200 m 2 m

Input #1: 0 – 100 HzInput #2: 0 – 100 HzInput #3: 0 – 100 HzInput #4: 0 – 100 HzInput #5: 0 – 100 Hz

input #5: 0 – 10 kHz

5

6

4GNDB(-)A(+)

MODBUS RS485

RS485 communication connection with the Modbus master system as an alternative to the Z-PC-DINx bus.Note: the indication of the RS485 connection polarity isn'tstandardised and in some masters may be reversed.

Scheme 1

Bus Length

DL = Derivation Length

DLTerminator Terminator

Module2Module1

Module3Module4

Module5

1

11

12

7

8

9

10

#1

#2

#3

#4

#5

+

Z-D-IN-1

16V

1

11

12

7

8

9

10

1

11

12

7

8

9

10

PNP NPN#1

#2

#3

#4

#5

#1

#2

#3

#4

#5

R=1k5

1k5

1k5

1k5

1k5

Page 6: RS485 Modbus Module 5 Digital Inputs

MI002056-E

For the best performances, the use of special shielded cables is suggested (BELDEN 9841 cable for example).

DIP-switches settingsThe DIP-switches positions define the module Modbus communication parameters:address and Baud Rate. In the following table the Baud Rate and the address values arelisted as a function of the DIP-switches positions:

DIP-Switches Status

POSITION BAUDRATE

POSITION ADDRESS

POSITION TERMI-NATOR 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10

x x x x x x x x 9600 x x x x # 1 x x x x x x x x x Disabilitato

x x x x x x x x 19200 x x x x # 2 x x x x x x x x x Enabled

x x x x x x x x 38400 x x . . . . . . x x # . . .

x x x x x x x x 57600 x x x x # 63

x x x x FromEEPRO

x x x x FromEEPROM

Note: when switches from 3 to 8 are in OFF, comunication settings are taken from the EEprom.

Digital Inputs

MODBUS registers: Holding registers

Register Name Description40002 INPUT,

OVERFLOWThe status of the inputs is available in the bits:input 1: 40002.0input 2: 40002.1input 3: 40002.2input 4: 40002.3input 5: 40002.4The bits from 40002.8 to 40002.12 indicate overflow of the respectivetotalizers. NOTE: The overflow bits MUST be reset from master.

40003 TOTAL 1 16 bits totalizer of input 1. The overflow is available at bit 40002.8.

40004 TOTAL 2 16 bits totalizer of input 2. The overflow is available at bit 40002.9

40005 TOTAL 3 16 bits totalizer of input 3. The overflow is available at bit 40002.10

40006 TOTAL 4 16 bits totalizer of input The overflow is available at bit 40002.114.

40007 TOTAL 5 16 bits totalizer of input The overflow is available at bit 40002.125.

ENGLISH 6/8

Page 7: RS485 Modbus Module 5 Digital Inputs

MI002056-E ENGLISH 7/8

Register Name Description40014 INPUT,

OVERFLOWThe status of the inputs is available in the bits:input 1: 40002.0input 2: 40002.1input 3: 40002.2input 4: 40002.3input 5: 40002.4The bits from 40002.8 to 40002.12 indicate overflow of the respectivetotalizers. NOTE: The overflow bits MUST be reset from master.

40015 TOTAL 1 16 bits totalizer of input 1. The overflow is available at bit 40002.8.

40016 TOTAL 2 16 bits totalizer of input 2. The overflow is available at bit 40002.9

40017 TOTAL 3 16 bits totalizer of input 3. The overflow is available at bit 40002.10

40018 TOTAL 4 16 bits totalizer of input The overflow is available at bit 40002.114.

40019 TOTAL 5Lower part

Less significant part for the input 5.of the 32 bit (Unsigned) totalizer

40020 TOTAL 5Upper part

Most significant part for the input 5.of the 32 bit (Unsigned) totalizer

MODBUS Registers: Coil registers

Register Name Description00017 OFTOTAL 1 Input 1 overflow totalizer.

00018 OFTOTAL 2 Input 2 overflow totalizer.

00019 OFTOTAL 3 Input 3 overflow totalizer.

00020 OFTOTAL 4 Input 4 overflow totalizer.

00021 OFTOTAL 5 Input 5 overflow totalizer.

MODBUS Registers: Input status

Register Name Description10001 INPUT 1 Active status input 1. See bit 40009.0

10002 INPUT 2 Active status input 2. See bit 40009.1

10003 INPUT 3 Active status input 3. See bit 40009.2

10004 INPUT 4 Active status input 4. See bit 40009.3

10005 INPUT 5 Active status input 5. See bit 40009.4

Frontal Panel LEDs SignallingsLED STATUS Meaning of LEDs

PWR Green On Power supply presence.

FAIL Yellow Blinking Error setting.

FAIL Yellow On Fault or Failure.

RX Red Blinking Receiving data from RS485.

RX Red On Verifying the connection.

TX Red Blinking Transmitting data to RS485.

TX Red On Verifying the connection.

Page 8: RS485 Modbus Module 5 Digital Inputs

Variation of standard parameters are possible by using configuration software (see: )www.seneca.itFor more information about a list of all register and their function refer to the USER manual.

MI002056-E ENGLISH 8/8

Decommisioning and DisposalDisposal of Electrical & Electronic Equipment (Applicable throughout the European Union and other European countries with separate collections programs). This symbol, found on your producr or on its packaging, indicates that this product should not be treated as household waste when you wish to dispose of it. Instead, it should be handed over to an applicable collection point for the recycling of electrical & electronic equipment. By ensuring this product is didposed of correctly, you will help prevent potential negative consequences to the environment and human health, which could otherwise be caused by inappropriate disposal of this product. The recycling of materials will help to conserve natural resources. For more detailed information about the recycling of the product, please contact your local city office, waste disposal service of the retail store where you purchased this product.

Default ConditionModule factory settings parameters

All DIP-Switches position: OFF = setting from EEPROM

MODBUS Protocol Communication parameters: 38400 8,N,1 Addr. 1

Reversed input status: DISABLED

Digital filter: 3 ms

Totalizer: UP counter

10 KHz on Channel 5: DISABLED

MODBUS latency time: 5 ms

Module LayoutMODULE DIMENSIONS FRONTAL PANEL

112 m

m

17,5 mm

100,0 mm

PWR

1 2

3 4

5

FAIL

RX TX

x x

x x

x x

x

x

x

Z-D-IN