OFFICE BUILDING NIGHT COOLING POTENTIAL IN BALTIC REGION. Riga Technical University Institute of Heat, Gas and Water technology. RENARS MILLERS, ALEKSANDRS ZAJACS, ARTA USELONOKA. General information: Location – 56.97 ° N, 24.07° E (Riga), Site – outside city centre, - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/1.jpg)
Riga Technical UniversityInstitute of Heat, Gas and Water technology
OFFICE BUILDING NIGHT COOLING POTENTIAL IN BALTIC REGION
RENARS MILLERS, ALEKSANDRS ZAJACS, ARTA USELONOKA.
![Page 2: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/2.jpg)
General information:
Location – 56.97° N, 24.07° E(Riga),
Site– outside city centre, surrounding agglomeration 2-4 storey buildings
Model ground area - 662m2 Volume – 14214m3 Height – 6 storeys, 24m
Envelope/volume ratio (Net) – 0.24m2/m3 Envelope/volume ratio (Gross) – 0.25m2/m3 Window/envelope ratio – 32%
Solar protection – standard glazing + shading devices
Cooling technique – Mechanical cooling + night cooling
![Page 3: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/3.jpg)
The lowest possible area/volume ratioCan be expressed as - 3/r
A/V ratio of a sphere with the same volume – 0.2
Starting point – the form
Sphere
If h=D then A/V ratio can be expressed as - 3/r
A/V ratio of a sphere with the same volume – 0.22
Cylinder
A/V ratio – 0.25
![Page 4: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/4.jpg)
Window description:
•U - value - 1.2W/m²K;•G - value - 0.62;•Tsolar - 0.54;•Tvisible - 0.8;
Description of external constructions:
•External wall - 0.14W/m²K;•Roof - 0.12Wm²K;•External floor - 0.33W/m²K;•Air tightness - 0.6ACH at 50Pa; Concrete building body and
slabs help to achieve greater thermal mass for accumulating heat during occupied hours.
Building envelope
![Page 5: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/5.jpg)
Night cooling – predicted air movement
Predicted air exchange rate – 5 ACH
![Page 6: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/6.jpg)
Simulated air exchange rate – 7.9 ACH, Indoor/Outdoor temperature difference – 10K, No wind present
Night cooling – simulated air movement
![Page 7: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/7.jpg)
The benefits of night cooling
Mechanical cooling
Mechanical cooling + night cooling
Absolute reduction
Relative reduction
Annual energy consumption for cooling, kWh/m²
17 8 -9 -53%
Peak load, kW 247 217 -30 -12%
![Page 8: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/8.jpg)
Simple shading design
No external shading devices With external shading devices
![Page 9: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/9.jpg)
Mechanical cooling Mechanical cooling + shading devices
Absolute reduction
Relative reduction
Annual energy consumption for cooling, kWh/m²
17 12 -5 -29%
Peak load, kW 247 197 -50 -20%
Benefits of shading devices
![Page 10: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/10.jpg)
Heat balance of typical room on the south side
No shading, no night cooling
Shading, night cooling
![Page 11: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/11.jpg)
Shading devices in combination with night cooling as passive cooling approach
Mechanical cooling
Mechanical cooling + night cooling
Mechanical cooling + shading devices
Mechanical cooling + shading
devices + night cooling
Absolute reduction
Relative reduction
Annual energy consumption for cooling, kWh/m²
17 8 12 4 -13 -76%
Peak load, kW 247 217 197 138 -109 -44%
Reduction from night cooling – 30kW
Reduction from shading devices – 50kW 80kW
![Page 12: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/12.jpg)
Conclusions:• Stack effect can boost air exchange rate during night cooling in multi-
storey building• Night cooling in this case is more effective for reducing energy
consumption – 53%• Shading devices are more effective to reduce peak load – 20%• Significant reduction of pike load – 44% can be achieved when using both
– night cooling and shading design in combination.
![Page 13: Riga Technical University Institute of Heat, Gas and Water technology](https://reader036.vdocuments.mx/reader036/viewer/2022062305/5681625c550346895dd2ae0a/html5/thumbnails/13.jpg)
Thank you for your attention!