RESIDENTIAL REPORT
1234 Main St.Fresno, Ca 93705
Buyer Name02/03/2020 9:00AM
InspectorJesse Newton
InterNachi Certified5594923091
AgentAgent Name555-555-5555
2345
121516171921242526333639
Table of Contents
Table of ContentsSUMMARY1: INSPECTION DETAILS2: ROOF3: EXTERIOR4: BASEMENT, FOUNDATION, CRAWLSPACE & STRUCTURE5: HEATING6: COOLING7: PLUMBING8: ELECTRICAL9: FIREPLACE10: ATTIC, INSULATION & VENTILATION11: DOORS, WINDOWS & INTERIOR12: MISC. ITEMS.13: APPLIANCESSTANDARDS OF PRACTICE
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 2 of 42
2.1.1 Roof - Coverings: Edge tile Missing
2.1.2 Roof - Coverings: Tiles Cracked/Broken
2.1.3 Roof - Coverings: Under-Driven Nails
2.1.4 Roof - Coverings: Moss growing on tile roof
2.2.1 Roof - Roof Drainage Systems: Debris
2.2.2 Roof - Roof Drainage Systems: Downspouts Drain Near House
2.2.3 Roof - Roof Drainage Systems: Gutters Missing
2.3.1 Roof - Flashings: Missing
2.4.1 Roof - Skylights, Chimneys & Other Roof Penetrations: Chimney cap needs secured.
2.4.2 Roof - Skylights, Chimneys & Other Roof Penetrations: Other penetrations ie vent pipes
3.1.1 Exterior - Siding, Flashing & Trim: Cracking - Minor
3.3.1 Exterior - Walkways, Patios & Driveways: Driveway Cracking - Minor
3.3.2 Exterior - Walkways, Patios & Driveways: Patio Cracking - Minor
6.1.1 Cooling - Cooling Equipment: Air Flow Restricted
8.4.1 Electrical - Lighting Fixtures, Switches & Receptacles: Cover Plates Damaged
8.4.2 Electrical - Lighting Fixtures, Switches & Receptacles: Open Ground Receptacle
8.4.3 Electrical - Lighting Fixtures, Switches & Receptacles: Arcing switch
11.1.1 Doors, Windows & Interior - Doors: Door Doesn't Latch
11.1.2 Doors, Windows & Interior - Doors: Noticeable Gap
11.2.1 Doors, Windows & Interior - Windows: Failed Seal
11.4.1 Doors, Windows & Interior - Walls: Poor Patching
11.7.1 Doors, Windows & Interior - Countertops & Cabinets: Cabinet Hinge Loose
11.7.2 Doors, Windows & Interior - Countertops & Cabinets: Countertop Cracked/Chipped
11.7.3 Doors, Windows & Interior - Countertops & Cabinets: Grout Deteriorating
11.8.1 Doors, Windows & Interior - Garage door for automobiles: Weather stripping
SUMMARY
3MAINTENANCE ITEM
20RECOMMENDATION
2SAFETY HAZARD
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 3 of 42
In AttendanceClient's Agent
OccupancyVacant, Garage was full ofbelongings
StyleRanch
Temperature (approximate)66 Fahrenheit (F)
Type of BuildingSingle Family
Weather ConditionsClear
Overall Impression By InspectorAbout The Home
2019-12-06Inspector Jesse Newton CPIMy overall impression about this home is that it is good shape for its age and location. I found mostly normalwear and tear items that are found in most homes. Stucco cracks are small and normal. I found minimal crack indriveway which is extremely good. That means concrete was done correctly and I trust foundation is same. Alldoors and windows are in good working order. With the exception of two in the master bedroom. They appear tohave lost the gas from in between the panes. This happens all the time. keeping the blinds open to allow heat onthem will help keep moisture out, or you may be able to have them repaired. The HVAC system is in goodcondition . It is a value unit and should be fairly reasonable in operating costs. I did notice that a lot of sprayfoam was used in the corners where one roof meets another. I find this odd and have personally never seen thatbefore. I am assuming since there are no signs of any leaks that it has sealed everything and will probably last along time. I recommend keeping an eye on it in the future or having a roofer evaluate it for any type of repair.Inside the home has some cosmetic issues such as texture not matching and some drywall patches. These arecommon in a house of this age and are purely cosmetic and does not affect the integrity of the home. There isalso a couple electrical issues that are shown in the report. But All In All I find this home to be safe and verylivable. It does have some after construction add ons like the Insta Hot water in the kitchen and the whole housewater filter in garage. These items have waterlines that are not hidden in the walls. The main line in the garage isok however as noted in my report the Instant Hot water lines coming in from outside should be completelyinsulated. While we do live in sunny California there is always that 1 in 100 chance of temperatures falling belowfreezing at which point an uninsulated water line could freeze and burst. So in my opinion this, the two plugreceptacles in bedroom 1 and the light switch in living room should be addressed. My only otherrecommendation is to add a carbon monoxide detector closer to hot water heater.I wish you well and hope you enjoy your new home. Thank you for allowing me to be part of this adventure withyou.
1: INSPECTION DETAILS
Information
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 4 of 42
Inspection MethodBinoculars, Ground, Ladder, Roof
Roof Type/StyleGable, Hip
Roof Drainage Systems: GutterMaterial
Vinyl
Flashings: MaterialAluminum, Missing?
Crack repairs. Several places on roof
Missing edge piece back of house Gap in stucco at roof on East side ofhouse in back
Coverings: MaterialSlateSee comments on pictures. I recommend a roofer come and repair loose tiles/slate and see if foam can beremoved
2: ROOFIN NI NP D
2.1 Coverings X X2.2 Roof Drainage Systems X X2.3 Flashings X X2.4 Skylights, Chimneys & Other Roof Penetrations X X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 5 of 42
Flashing bent up catching wind maycause tile to crack
Broken piece couldn’t find fromwhere
Spray foam in several places.Inspector does not know why
Cracked tiles above garage east side
Deficiencies
2.1.1 CoveringsEDGE TILE MISSINGObserved areas that was missing a tile piece oneve/edge. Recommend qualified roofing contractor evaluate &repair.
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 6 of 42
Missing tile . Possible place formoisture intursion
2.1.2 CoveringsTILES CRACKED/BROKENRoof had cracked/broken tiles. Recommend a qualified roof contractor repair or replace to preventmoisture intrusion and/or mold.
RecommendationContact a qualified roofing professional.
Broken piece
Recommendation
2.1.3 CoveringsUNDER-DRIVEN NAILSObserved one or more under-driven nails/fasteners. Recommend a qualified roofing contractor evaluateand repair.
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 7 of 42
Loose nails Loose tile, nails worked loose Loose nails
2.1.4 CoveringsMOSS GROWING ON TILE ROOFRecommend pressure washing the moss off the roof. Moss candamage tiles and thus allow moisture intrusion.
RecommendationContact a qualified cleaning service.
Maintenance Item
2.2.1 Roof Drainage SystemsDEBRISDebris has accumulated in the gutters. Recommend cleaning to facilitate water flow.Here is a DIY resource for cleaning your gutters.
Front of house
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 8 of 42
2.2.2 Roof Drainage SystemsDOWNSPOUTS DRAIN NEAR HOUSEOne or more downspouts drain too close to the home's foundation. This can result in excessive moisture inthe soil at the foundation, which can lead to foundation/structural movement. Recommend a qualifiedcontractor adjust downspout extensions to drain at least 6 feet from the foundation. Here is a helpful DIY link and video on draining water flow away from your house.
Gutter drains next to front dooron porch
Recommendation
2.2.3 Roof Drainage SystemsGUTTERS MISSINGThere are no gutters present on the structure. Gutters arerecommended because they collect rain water from the roof anddirect it away form the building.
No gutter. Rain water comes off roofin front of door
Recommendation
2.3.1 FlashingsMISSINGFlashings were missing at time of inspection. Flashings provide protection against moisture intrusion.Recommend a qualified roofing contractor evaluate and remedy.
RecommendationContact a qualified roofing professional.
Maintenance Item
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 9 of 42
Arrow loose fascia. Circle roofand flashing missing
Missing flashing/stucco abovefront porch right side
Flashing diverting water undertiles
Area of concern other photostaken here
2.4.1 Skylights, Chimneys & Other Roof PenetrationsCHIMNEY CAP NEEDS SECURED.Chimney/fireplace exhaust vent cap not secure. Could potentially lift off with wind or kids playing.Recommend securing with screws.
RecommendationContact a handyman or DIY project
Lifts right off Cap
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 10 of 42
2.4.2 Skylights, Chimneys & Other Roof PenetrationsOTHER PENETRATIONS IE VENT PIPESRoof jacks need sealed or replaced. Sealing them would be the best route at this time. Recommend anactual silicone or tar sealer not tape. All roof jacks and vent pipes need repaired to avoid moistureintrusion
RecommendationContact a handyman or DIY project
Tape can leak reseal or replace Tape can leak. Reseal or replace
Maintenance Item
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 11 of 42
Inspection MethodVisual
Siding, Flashing & Trim: SidingMaterial
Stucco
Siding, Flashing & Trim: SidingStyle
Lath
Exterior Doors: Exterior EntryDoor
Steel
Walkways, Patios & Driveways:Driveway Material
Concrete
Decks, Balconies, Porches &Steps: Appurtenance
Covered Porch, Front Porch,Patio
Decks, Balconies, Porches &Steps: Material
Concrete
broken piece of wood
Vegetation, Grading, Drainage, Retaining Walls & Fences/Gates: GateGate has broken piece of wood on bottom. Doesn't affect performance. Gate also catches on opening andclosing. Recommend fence contractor to adjust repair gate for easy opening and to prevent further damage.
3: EXTERIORIN NI NP D
3.1 Siding, Flashing & Trim X X3.2 Exterior Doors X3.3 Walkways, Patios & Driveways X X3.4 Decks, Balconies, Porches & Steps X3.5 Eaves, Soffits & Fascia X3.6 Vegetation, Grading, Drainage, Retaining Walls & Fences/Gates X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
Deficiencies
3.1.1 Siding, Flashing & TrimCRACKING - MINORStucco showed cracking in one or more places. This is a result of temperature changes, and typical ashomes with stucco age. Recommend monitoring.
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 12 of 42
Cracking from corners of doorsand windows is normal
Crack
3.3.1 Walkways, Patios & DrivewaysDRIVEWAY CRACKING - MINORMinor cosmetic cracks observed, which may indicate movement inthe soil. Recommend monitor and/or have concrete contractorpatch/seal.
Bu sidewalk front driveway
Recommendation
3.3.2 Walkways, Patios & DrivewaysPATIO CRACKING - MINORNormal settling & cracking observed. Recommend monitor and/orpatch/seal.
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 13 of 42
Patio back yard
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 14 of 42
Inspection MethodVisual
Foundation: MaterialConcrete, Slab on Grade
Floor Structure:Basement/Crawlspace Floor
N/A
Floor Structure: MaterialConcrete, Slab
Floor Structure: Sub-floorN/A
Wall Structure: Wood frame
Walls covered withstucco/drywall.
Ceiling Structure: Ceiling joistbuilt in trusses
Normal
4: BASEMENT, FOUNDATION, CRAWLSPACE &STRUCTURE
IN NI NP D4.1 Foundation X4.2 Basements & Crawlspaces X4.3 Floor Structure X4.4 Wall Structure X4.5 Ceiling Structure X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
Limitations
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 15 of 42
Value Series by Lennox
Equipment: BrandAttic
Lennox
Equipment: Energy SourceGas
Equipment: Heat TypeAttic
Forced Air
Distribution Systems: DuctworkInsulated
Distribution Systems: Return air ventFilter minimumA clean return air filter helps unit run more efficiently and use less power. It also helps minimize bad air particlesand cleans the air that you breath. I recommend changing out every thirty days for optimum performance. WhileHEPA Filters remove 98% of the particles in the air they also clog faster and need to be changed more. A dirtyfilter reduces the life of the unit.
5: HEATINGIN NI NP D
5.1 Equipment X5.2 Normal Operating Controls X5.3 Distribution Systems X5.4 Presence of Installed Heat Source in Each Room X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 16 of 42
Cooling Equipment: EnergySource/Type
Electric, Central Air Conditioner
Cooling Equipment: LocationExterior East
Distribution System:Configuration
Central
Presence of Installed CoolingSource in Each Room: central air
vents in every room
Cooling Equipment: BrandOutside
LennoxCompressor unit for A/C needs cleaning. A clean unit produces cooler air, runs more efficient and uses lesselectricity.
6: COOLINGIN NI NP D
6.1 Cooling Equipment X X6.2 Normal Operating Controls X6.3 Distribution System X6.4 Presence of Installed Cooling Source in Each Room X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
Deficiencies
6.1.1 Cooling EquipmentAIR FLOW RESTRICTED
Air flow to the air conditioner condenser was restricted. This may
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 17 of 42
Air flow to the air conditioner condenser was restricted. This mayresult in inefficient operation. Recommend cleaning dirt and/ordebris from unit. They have a condenser coil cleaning spray thatworks really well. Spray it on and rinse off.
RecommendationContact a handyman or DIY project
Needs cleaning.
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 18 of 42
FiltersSediment Filter, Whole houseconditioner
Water SourcePublic
Main Water Shut-off Device:Location
Garage at water heater
Drain, Waste, & Vent Systems:Drain Size
1 1/2", 2"
Drain, Waste, & Vent Systems:Material
ABS, PVC
Water Supply, DistributionSystems & Fixtures: DistributionMaterial
Copper, Pex
Water Supply, DistributionSystems & Fixtures: WaterSupply Material
Copper
Hot Water Systems, Controls,Flues & Vents: Capacity
40 gallons
Hot Water Systems, Controls,Flues & Vents: Location
Garage
Hot Water Systems, Controls,Flues & Vents: PowerSource/Type
Gas
Water Heater installed around 2007 Flame cover off. Recommend re-installing
Hot Water Systems, Controls, Flues & Vents: Manufacturergarage
AO SmithI recommend flushing & servicing your water heater tank annually for optimal performance. Water temperatureshould be set to at least 120 degrees F to kill microbes and no higher than 130 degrees F to prevent scalding. Here is a nice maintenance guide from Lowe's to help. This water heater appears to have been installed in 2007. House was built in 1997.
7: PLUMBINGIN NI NP D
7.1 Main Water Shut-off Device X7.2 Drain, Waste, & Vent Systems X7.3 Water Supply, Distribution Systems & Fixtures X7.4 Hot Water Systems, Controls, Flues & Vents X7.5 Fuel Storage & Distribution Systems X7.6 Sump Pump X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 19 of 42
Limitations
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 20 of 42
Service Entrance Conductors:Electrical Service Conductors
Below Ground, 220 Volts, 120Volts, Copper
Main & Subpanels, Service &Grounding, Main OvercurrentDevice: Main Panel Location
Right, Back
Main & Subpanels, Service &Grounding, Main OvercurrentDevice: Panel Capacity
200 AMP
Main & Subpanels, Service &Grounding, Main OvercurrentDevice: Panel Manufacturer
Westinghouse
Main & Subpanels, Service &Grounding, Main OvercurrentDevice: Panel Type
Circuit Breaker
Branch Wiring Circuits, Breakers& Fuses: Branch Wire 15 and 20AMP
Copper
Branch Wiring Circuits, Breakers& Fuses: Wiring Method
Romex, Not Visible
Standard smoke detector
Smoke Detectors: Standard detectorsLocations living room, hallway and each bedroom. Checked and all work and tied together . One goes off they allgo off
8: ELECTRICALIN NI NP D
8.1 Service Entrance Conductors X8.2 Main & Subpanels, Service & Grounding, Main Overcurrent Device X8.3 Branch Wiring Circuits, Breakers & Fuses X8.4 Lighting Fixtures, Switches & Receptacles X X8.5 GFCI & AFCI X8.6 Smoke Detectors X8.7 Carbon Monoxide Detectors X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 21 of 42
Carbon monoxide detector in hallway
Carbon Monoxide Detectors: Carbon monoxideOne in hallway. Tested and works fine . Recommend installing another closet to garage maybe laundry room. Hotwater heater in garage. Also maybe in master bedroom closet or in attic. Furnace is in attic
Deficiencies
8.4.1 Lighting Fixtures, Switches & ReceptaclesCOVER PLATES DAMAGEDOne or more receptacles have a damaged cover plate. Recommendreplacement.
Hallway
Recommendation
8.4.2 Lighting Fixtures, Switches & ReceptaclesOPEN GROUND RECEPTACLEFIRST BEDROOM
One or more receptacles have open ground . To eliminate safety hazards, all receptacles should begrounded.
RecommendationContact a qualified electrical contractor.
Safety Hazard
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 22 of 42
Bedroom
Bedroom
8.4.3 Lighting Fixtures, Switches & ReceptaclesARCING SWITCHLight switch by front door. Can hear arcing when turning on/off. Recommend Electrician repair/replaceswitch
RecommendationContact a qualified electrical contractor.
BAd switch
Switch arcing
Safety Hazard
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 23 of 42
TypeGas
9: FIREPLACEIN NI NP D
9.1 Vents, Flues & Chimneys X9.2 Lintels X9.3 Damper Doors X9.4 Cleanout Doors & Frames X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
Limitations
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 24 of 42
Dryer Power Source220 Electric
Dryer VentMetal
Flooring InsulationNone
Attic Insulation: Insulation TypeBlown, Fiberglass, Loose-fill
Attic Insulation: R-value30
Ventilation: Ventilation TypeGable Vents, Soffit Vents
Exhaust Systems: Exhaust FansFan Only
main house has blown in and batinsulation
Garage attic not insulated
Attic/insulation/trussesFYI of attic
10: ATTIC, INSULATION & VENTILATIONIN NI NP D
10.1 Attic Insulation X10.2 Vapor Retarders (Crawlspace or Basement) X10.3 Ventilation X10.4 Exhaust Systems X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
Limitations
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 25 of 42
Windows: Window ManufacturerUnknown
Walls: Wall MaterialDrywall
Ceilings: Ceiling MaterialDrywall
Countertops & Cabinets:Cabinetry
Wood
Countertops & Cabinets:Countertop Material
Tile
11: DOORS, WINDOWS & INTERIORIN NI NP D
11.1 Doors X X11.2 Windows X X11.3 Floors X11.4 Walls X X11.5 Ceilings X11.6 Steps, Stairways & Railings X11.7 Countertops & Cabinets X X11.8 Garage door for automobiles X X
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 26 of 42
Mstr bdrm window fogged
Mstr bedroom windows fogged Screen torn mstr bdrm
Nail in screen mstr bdrm
Windows: Window TypeSlidersAll windows are good and operate as they should. Two in master bedroom have dogged up in between Toppanes. I recommend a window professional look at them and possibly repair and put new gas in between panes.
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 27 of 42
Laminate flooring
Flooring missing in hall closet
Carpet in bedrooms
Laundry floor drain, needs drainscreen
Floors: Floor CoveringsLaminate, Carpet
Limitations
Deficiencies
11.1.1 DoorsDOOR DOESN'T LATCHDoor doesn't latch properly. Catch part is ripping out of doorframe
RecommendationContact a handyman or DIY project
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 28 of 42
11.1.2 DoorsNOTICEABLE GAPBACK SCREEN DOOR
One or more gaps could result in energy loss. Recommend handyman or door contractor evaluate.
RecommendationContact a handyman or DIY project
Gap. Door installed incorrectly Gap
Recommendation
11.2.1 WindowsFAILED SEALObserved condensation between the window panes, which indicates a failed seal. Recommend qualifiedwindow contractor evaluate & repair or replace
RecommendationContact a qualified window repair/installation contractor.
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 29 of 42
11.4.1 WallsPOOR PATCHINGSub-standard drywall patching observed at time of inspection. Does not affect home other than cosmetics.
RecommendationContact a handyman or DIY project
Texture/patchwork does notmatch
Indents Paint doesn’t match
Can see tape line from patchwork Texture does not match
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 30 of 42
Arrow cover plate away fromwall.square texture mismatch
Wire coming through wall in livingroom
11.7.1 Countertops & CabinetsCABINET HINGE LOOSEOne or more cabinet hinges were loose. Recommend a qualified handyman or cabinet contractor repair. Here is a helpful DIY article on cabinet repairs.
RecommendationContact a handyman or DIY project
Recommendation
11.7.2 Countertops & CabinetsCOUNTERTOP CRACKED/CHIPPEDCountertop had one or more cracks or chips. Recommend qualifiedcountertop contractor evaluate and repair. Here is a helpful article on repairing cracks, chips & fissures.
RecommendationContact a qualified tile contractor
Kitchen counter
Recommendation
11.7.3 Countertops & CabinetsGROUT DETERIORATINGGrout lines were cracked or deteriorated. Recommend a qualifiedcontractor repair or replace grout.
RecommendationContact a handyman or DIY project
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 31 of 42
Mstr bath
11.8.1 Garage door for automobilesWEATHER STRIPPINGBottom of garage door weather stripping is torn and let’s light in on the edges. Could potentially let waterin and or rodents. Recommend new weatherstrip
RecommendationContact a qualified garage door contractor.
Left side Right side
Recommendation
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 32 of 42
Whole House Water Filter 1/2 garage ceiling is drywalled 1/2 isnot
Holes behind water heater needcovered up.
Sprinkler control in garage
Misc. Items FoundIn House
These Items have no particular place. But when conducting the inspection I felt these should be noted. If Videosdon't play let me know. Major ones are master bath toilet is loose and shower valve shut off is wrong and hard toturn off.
12: MISC. ITEMS.IN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
VIDEO
VIDEO
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 33 of 42
Screen door catch broke out needsrepaired
Green insulated water line. Red un-insulated but should be
All penetrations on house should besealed to prevent termite and
moisture intrusion
Kitchen sink has chips in it
VIDEO VIDEO
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 34 of 42
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 35 of 42
RefrigeratorNone
Disposalbrand unknown
Disposal works
DishwasherKenmoreRan through normal cycle. No issues and no leaks
13: APPLIANCESIN NI NP D
IN = Inspected NI = Not Inspected NP = Not Present D = Deficiencies
Information
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 36 of 42
Inside oven
RangeGEAll burners work. Did not test oven as it was dirty. Needs cleaning
MicrowavewhirlpoolAbove stove. Has light and fan. Both work on low and high settings. Microwave worked heating water
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 37 of 42
Instant hot waterEco SmartWorks temp setting 48°Celsius equals to 118.4° Fahrenheit
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 38 of 42
STANDARDS OF PRACTICE
RoofI. The inspector shall inspect from ground level or the eaves: A. the roof-covering materials; B. the gutters; C. thedownspouts; D. the vents, flashing, skylights, chimney, and other roof penetrations; and E. the general structure ofthe roof from the readily accessible panels, doors or stairs. II. The inspector shall describe: A. the type of roof-covering materials. III. The inspector shall report as in need of correction: A. observed indications of active roofleaks. IV. The inspector is not required to: A. walk on any roof surface. B. predict the service life expectancy. C.inspect underground downspout diverter drainage pipes. D. remove snow, ice, debris or other conditions thatprohibit the observation of the roof surfaces. E. move insulation. F. inspect antennae, satellite dishes, lightningarresters, de-icing equipment, or similar attachments. G. walk on any roof areas that appear, in the inspectorsopinion, to be unsafe. H. walk on any roof areas if doing so might, in the inspector's opinion, cause damage. I.perform a water test. J. warrant or certify the roof. K. confirm proper fastening or installation of any roof-coveringmaterial.
ExteriorI. The inspector shall inspect: A. the exterior wall-covering materials, flashing and trim; B. all exterior doors; C.adjacent walkways and driveways; D. stairs, steps, stoops, stairways and ramps; E. porches, patios, decks, balconiesand carports; F. railings, guards and handrails; G. the eaves, soffits and fascia; H. a representative number ofwindows; and I. vegetation, surface drainage, retaining walls and grading of the property, where they may adverselyaffect the structure due to moisture intrusion. II. The inspector shall describe: A. the type of exterior wall-coveringmaterials. III. The inspector shall report as in need of correction: A. any improper spacing between intermediatebalusters, spindles and rails. IV. The inspector is not required to: A. inspect or operate screens, storm windows,shutters, awnings, fences, outbuildings, or exterior accent lighting. B. inspect items that are not visible or readilyaccessible from the ground, including window and door flashing. C. inspect or identify geological, geotechnical,hydrological or soil conditions. D. inspect recreational facilities or playground equipment. E. inspect seawalls,breakwalls or docks. F. inspect erosion-control or earth-stabilization measures. G. inspect for safety-type glass. H.inspect underground utilities. I. inspect underground items. J. inspect wells or springs. K. inspect solar, wind orgeothermal systems. L. inspect swimming pools or spas. M. inspect wastewater treatment systems, septic systemsor cesspools. N. inspect irrigation or sprinkler systems. O. inspect drainfields or dry wells. P. determine the integrityof multiple-pane window glazing or thermal window seals.
Basement, Foundation, Crawlspace & StructureI. The inspector shall inspect: A. the foundation; B. the basement; C. the crawlspace; and D. structural components.II. The inspector shall describe: A. the type of foundation; and B. the location of the access to the under-floor space.III. The inspector shall report as in need of correction: A. observed indications of wood in contact with or near soil;B. observed indications of active water penetration; C. observed indications of possible foundation movement, suchas sheetrock cracks, brick cracks, out-of-square door frames, and unlevel floors; and D. any observed cutting,notching and boring of framing members that may, in the inspector's opinion, present a structural or safetyconcern. IV. The inspector is not required to: A. enter any crawlspace that is not readily accessible, or where entrycould cause damage or pose a hazard to him/herself. B. move stored items or debris. C. operate sump pumps withinaccessible floats. D. identify the size, spacing, span or location or determine the adequacy of foundation bolting,bracing, joists, joist spans or support systems. E. provide any engineering or architectural service. F. report on theadequacy of any structural system or component.
HeatingI. The inspector shall inspect: A. the heating system, using normal operating controls. II. The inspector shall describe:A. the location of the thermostat for the heating system; B. the energy source; and C. the heating method. III. Theinspector shall report as in need of correction: A. any heating system that did not operate; and B. if the heatingsystem was deemed inaccessible. IV. The inspector is not required to: A. inspect or evaluate the interior of flues orchimneys, fire chambers, heat exchangers, combustion air systems, fresh-air intakes, humidifiers, dehumidifiers,electronic air filters, geothermal systems, or solar heating systems. B. inspect fuel tanks or underground orconcealed fuel supply systems. C. determine the uniformity, temperature, flow, balance, distribution, size, capacity,BTU, or supply adequacy of the heating system. D. light or ignite pilot flames. E. activate heating, heat pumpsystems, or other heating systems when ambient temperatures or other circumstances are not conducive to safeoperation or may damage the equipment. F. override electronic thermostats. G. evaluate fuel quality. H. verifythermostat calibration, heat anticipation, or automatic setbacks, timers, programs or clocks.
CoolingI. The inspector shall inspect: A. the cooling system, using normal operating controls. II. The inspector shall describe:A. the location of the thermostat for the cooling system; and B. the cooling method. III. The inspector shall report as
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 39 of 42
in need of correction: A. any cooling system that did not operate; and B. if the cooling system was deemedinaccessible. IV. The inspector is not required to: A. determine the uniformity, temperature, flow, balance,distribution, size, capacity, BTU, or supply adequacy of the cooling system. B. inspect portable window units,through-wall units, or electronic air filters. C. operate equipment or systems if the exterior temperature is below 65Fahrenheit, or when other circumstances are not conducive to safe operation or may damage the equipment. D.inspect or determine thermostat calibration, cooling anticipation, or automatic setbacks or clocks. E. examineelectrical current, coolant fluids or gases, or coolant leakage.
PlumbingI. The inspector shall inspect: A. the main water supply shut-off valve; B. the main fuel supply shut-off valve; C. thewater heating equipment, including the energy source, venting connections, temperature/pressure-relief (TPR)valves, Watts 210 valves, and seismic bracing; D. interior water supply, including all fixtures and faucets, by runningthe water; E. all toilets for proper operation by flushing; F. all sinks, tubs and showers for functional drainage; G. thedrain, waste and vent system; and H. drainage sump pumps with accessible floats. II. The inspector shall describe:A. whether the water supply is public or private based upon observed evidence; B. the location of the main watersupply shut-off valve; C. the location of the main fuel supply shut-off valve; D. the location of any observed fuel-storage system; and E. the capacity of the water heating equipment, if labeled. III. The inspector shall report as inneed of correction: A. deficiencies in the water supply by viewing the functional flow in two fixtures operatedsimultaneously; B. deficiencies in the installation of hot and cold water faucets; C. mechanical drain stops that weremissing or did not operate if installed in sinks, lavatories and tubs; and D. toilets that were damaged, had looseconnections to the floor, were leaking, or had tank components that did not operate. IV. The inspector is notrequired to: A. light or ignite pilot flames. B. measure the capacity, temperature, age, life expectancy or adequacy ofthe water heater. C. inspect the interior of flues or chimneys, combustion air systems, water softener or filteringsystems, well pumps or tanks, safety or shut-off valves, floor drains, lawn sprinkler systems, or fire sprinklersystems. D. determine the exact flow rate, volume, pressure, temperature or adequacy of the water supply. E.determine the water quality, potability or reliability of the water supply or source. F. open sealed plumbing accesspanels. G. inspect clothes washing machines or their connections. H. operate any valve. I. test shower pans, tub andshower surrounds or enclosures for leakage or functional overflow protection. J. evaluate the compliance withconservation, energy or building standards, or the proper design or sizing of any water, waste or ventingcomponents, fixtures or piping. K. determine the effectiveness of anti-siphon, backflow prevention or drain-stopdevices. L. determine whether there are sufficient cleanouts for effective cleaning of drains. M. evaluate fuelstorage tanks or supply systems. N. inspect wastewater treatment systems. O. inspect water treatment systems orwater filters. P. inspect water storage tanks, pressure pumps, or bladder tanks. Q. evaluate wait time to obtain hotwater at fixtures, or perform testing of any kind to water heater elements. R. evaluate or determine the adequacy ofcombustion air. S. test, operate, open or close: safety controls, manual stop valves, temperature/pressure-reliefvalves, control valves, or check valves. T. examine ancillary or auxiliary systems or components, such as, but notlimited to, those related to solar water heating and hot water circulation. U. determine the existence or condition ofpolybutylene plumbing. V. inspect or test for gas or fuel leaks, or indications thereof.
ElectricalI. The inspector shall inspect: A. the service drop; B. the overhead service conductors and attachment point; C. theservice head, gooseneck and drip loops; D. the service mast, service conduit and raceway; E. the electric meter andbase; F. service-entrance conductors; G. the main service disconnect; H. panelboards and over-current protectiondevices (circuit breakers and fuses); I. service grounding and bonding; J. a representative number of switches,lighting fixtures and receptacles, including receptacles observed and deemed to be arc-fault circuit interrupter(AFCI)-protected using the AFCI test button, where possible; K. all ground-fault circuit interrupter receptacles andcircuit breakers observed and deemed to be GFCIs using a GFCI tester, where possible; and L. smoke and carbon-monoxide detectors. II. The inspector shall describe: A. the main service disconnect's amperage rating, if labeled;and B. the type of wiring observed. III. The inspector shall report as in need of correction: A. deficiencies in theintegrity of the serviceentrance conductors insulation, drip loop, and vertical clearances from grade and roofs; B.any unused circuit-breaker panel opening that was not filled; C. the presence of solid conductor aluminum branch-circuit wiring, if readily visible; D. any tested receptacle in which power was not present, polarity was incorrect, thecover was not in place, the GFCI devices were not properly installed or did not operate properly, evidence of arcingor excessive heat, and where the receptacle was not grounded or was not secured to the wall; and E. the absence ofsmoke detectors. IV. The inspector is not required to: A. insert any tool, probe or device into the main panelboard,sub-panels, distribution panelboards, or electrical fixtures. B. operate electrical systems that are shut down. C.remove panelboard cabinet covers or dead fronts. D. operate or re-set over-current protection devices or overloaddevices. E. operate or test smoke or carbon-monoxide detectors or alarms F. inspect, operate or test any security,fire or alarms systems or components, or other warning or signaling systems. G. measure or determine theamperage or voltage of the main service equipment, if not visibly labeled. H. inspect ancillary wiring or remote-control devices. I. activate any electrical systems or branch circuits that are not energized. J. inspect low-voltagesystems, electrical de-icing tapes, swimming pool wiring, or any timecontrolled devices. K. verify the service ground.L. inspect private or emergency electrical supply sources, including, but not limited to: generators, windmills,photovoltaic solar collectors, or battery or electrical storage facility. M. inspect spark or lightning arrestors. N.inspect or test de-icing equipment. O. conduct voltage-drop calculations. P. determine the accuracy of labeling. Q.inspect exterior lighting.
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 40 of 42
FireplaceI. The inspector shall inspect:
readily accessible and visible portions of the fireplaces and chimneys;
lintels above the fireplace openings;
damper doors by opening and closing them, if readily accessible and manually operable; and
cleanout doors and frames.
II. The inspector shall describe:
the type of fireplace.
III. The inspector shall report as in need of correction:
evidence of joint separation, damage or deterioration of the hearth, hearth extension or chambers;
manually operated dampers that did not open and close;
the lack of a smoke detector in the same room as the fireplace;
the lack of a carbon-monoxide detector in the same room as the fireplace; and
cleanouts not made of metal, pre-cast cement, or other non-combustible material.
IV. The inspector is not required to:
inspect the flue or vent system.
inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets, or mantels.
determine the need for a chimney sweep.
operate gas fireplace inserts.
light pilot flames.
determine the appropriateness of any installation.
inspect automatic fuel-fed devices.
inspect combustion and/or make-up air devices.
inspect heat-distribution assists, whether gravity-controlled or fan-assisted.
ignite or extinguish fires.
determine the adequacy of drafts or draft characteristics.
move fireplace inserts, stoves or firebox contents.
perform a smoke test.
dismantle or remove any component.
perform a National Fire Protection Association (NFPA)-style inspection.
perform a Phase I fireplace and chimney inspection.
Attic, Insulation & VentilationI. The inspector shall inspect: A. insulation in unfinished spaces, including attics, crawlspaces and foundation areas;B. ventilation of unfinished spaces, including attics, crawlspaces and foundation areas; and C. mechanical exhaustsystems in the kitchen, bathrooms and laundry area. II. The inspector shall describe: A. the type of insulationobserved; and B. the approximate average depth of insulation observed at the unfinished attic floor area or roofstructure. III. The inspector shall report as in need of correction: A. the general absence of insulation or ventilationin unfinished spaces. IV. The inspector is not required to: A. enter the attic or any unfinished spaces that are notreadily accessible, or where entry could cause damage or, in the inspector's opinion, pose a safety hazard. B. move,touch or disturb insulation. C. move, touch or disturb vapor retarders. D. break or otherwise damage the surfacefinish or weather seal on or around access panels or covers. E. identify the composition or R-value of insulationmaterial. F. activate thermostatically operated fans. G. determine the types of materials used in insulation orwrapping of pipes, ducts, jackets, boilers or wiring. H. determine the adequacy of ventilation.
1234 Main St. Buyer Name
All Types Of Home Inspections Ltd Page 41 of 42
Doors, Windows & InteriorI. The inspector shall inspect: A. a representative number of doors and windows by opening and closing them; B.floors, walls and ceilings; C. stairs, steps, landings, stairways and ramps; D. railings, guards and handrails; and E.garage vehicle doors and the operation of garage vehicle door openers, using normal operating controls. II. Theinspector shall describe: A. a garage vehicle door as manually-operated or installed with a garage door opener. III.The inspector shall report as in need of correction: A. improper spacing between intermediate balusters, spindlesand rails for steps, stairways, guards and railings; B. photo-electric safety sensors that did not operate properly; andC. any window that was obviously fogged or displayed other evidence of broken seals. IV. The inspector is notrequired to: A. inspect paint, wallpaper, window treatments or finish treatments. B. inspect floor coverings orcarpeting. C. inspect central vacuum systems. D. inspect for safety glazing. E. inspect security systems orcomponents. F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures. G. move furniture,stored items, or any coverings, such as carpets or rugs, in order to inspect the concealed floor structure. H. movesuspended-ceiling tiles. I. inspect or move any household appliances. J. inspect or operate equipment housed in thegarage, except as otherwise noted. K. verify or certify the proper operation of any pressure-activated auto-reverseor related safety feature of a garage door. L. operate or evaluate any security bar release and opening mechanisms,whether interior or exterior, including their compliance with local, state or federal standards. M. operate anysystem, appliance or component that requires the use of special keys, codes, combinations or devices. N. operateor evaluate self-cleaning oven cycles, tilt guards/latches, or signal lights. O. inspect microwave ovens or test leakagefrom microwave ovens. P. operate or examine any sauna, steamgenerating equipment, kiln, toaster, ice maker,coffee maker, can opener, bread warmer, blender, instant hot-water dispenser, or other small, ancillary appliancesor devices. Q. inspect elevators. R. inspect remote controls. S. inspect appliances. T. inspect items not permanentlyinstalled. U. discover firewall compromises. V. inspect pools, spas or fountains. W. determine the adequacy ofwhirlpool or spa jets, water force, or bubble effects. X. determine the structural integrity or leakage of pools or spas.