required capacitor banks sizing calculation

2
CAPACITOR BANKS SIZING CALCULATION FOR SKPPL SITE CONSTRUCTION POWER 1 1150 kW P 906.54 kW cosθ1 0.4 cosθ2 0.99 KVAR θ1 66.45551 tanθ₁ 2.291288 θ2 8.113728 tanθ₂ 0.142492 KW Multiplying Factor Total Required KVAR Total No. of capacitor banks req. 500 KVAR - 2 Nos. 300 KVAR - 2 Nos. 200 KVAR - 2 Nos. 2 580 kW P 520 kW cosθ1 0.4 cosθ2 0.99 KVAR θ1 66.45551 tanθ₁ 2.291288 θ2 8.113728 tanθ₂ 0.142492 KW Multiplying Factor Total Required KVAR Total No. of capacitor banks req. 300 KVAR - 2 Nos. 250 KVAR - 2 Nos. Required KVAR obtained from multiplying factor PF without Capacitors Running load Desired PF will be Required KVAR P(tanθ₁ - tanθ₂) 1117.373694 Required KVAR obtained from multiplying factor Calculation for required Capacitor Bank Running Connecting load PF without Capacitors Desired PF will be Formula for KVAR calculation: Required capacitive KVAR Required KVAR For Transformer no-02 (Adit-2) 600 KVA For Transformer - 01 (Near Adit-1) 1250 KVA Calculation for required Capacitor Bank Required capacitive KVAR P(tanθ₁ - tanθ₂) 1947.969131 Formula for KVAR calculation: Connected Load Connected Load 906.54 2.1487956 2000 520 2.1487956 1100

Upload: usharaniy

Post on 24-Nov-2015

61 views

Category:

Documents


9 download

DESCRIPTION

Capacitor Calculation

TRANSCRIPT

  • CAPACITOR BANKS SIZING CALCULATION FOR SKPPL SITE CONSTRUCTION POWER

    1

    1150 kWP 906.54 kWcos1 0.4cos2 0.99

    KVAR

    1 66.45551 tan 2.2912882 8.113728 tan 0.142492

    KWMultiplying

    Factor

    Total Required

    KVAR

    Total No. of capacitor banks req.

    500 KVAR - 2 Nos.300 KVAR - 2 Nos.200 KVAR - 2 Nos.

    2

    580 kWP 520 kWcos1 0.4cos2 0.99

    KVAR

    1 66.45551 tan 2.2912882 8.113728 tan 0.142492

    KWMultiplying

    Factor

    Total Required

    KVAR

    Total No. of capacitor banks req.

    300 KVAR - 2 Nos. 250 KVAR - 2 Nos.

    Required KVAR obtained from multiplying factor

    PF without Capacitors Running load

    Desired PF will be

    Required KVAR

    P(tan - tan)1117.373694

    Required KVAR obtained from multiplying factor

    Calculation for required Capacitor Bank

    Running Connecting loadPF without Capacitors

    Desired PF will be

    Formula for KVAR calculation:Required capacitive KVAR

    Required KVAR

    For Transformer no-02 (Adit-2) 600 KVA

    For Transformer - 01 (Near Adit-1) 1250 KVA

    Calculation for required Capacitor Bank

    Required capacitive KVAR P(tan - tan)1947.969131

    Formula for KVAR calculation:

    Connected Load

    Connected Load

    906.54 2.1487956 2000

    520 2.1487956 1100