Remote control and monitoring server PCS200 User manual Version 1.1 TERRA

Upload: others

Post on 10-Mar-2020

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

Remote control

and monitoring server

PCS200

User manualVersion 1.1

TERRA

Page 2: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

www.terraelectronics.com

C O N T E N T S

1 Product description _______________________________ 32 Safety instructions _______________________________ 33 Parameters _____________________________________ 3

3.1 Features ___________________________________ 34 External view and operating control _________________ 45 PCS200 control interface __________________________ 5

5.1 USB control ________________________________ 55.2 LCD display ________________________________ 55.3 Keypad ____________________________________ 55.4 “Addressed” indicator _______________________ 55.5 “Status” indicator ___________________________ 5

5.5 5.6 “Ground” clamp_____________________________ 55.7 230V~ 50 Hz power supply unit ________________ 55.8 Cooling fan _________________________________ 55.9 “Terra Bus” data bus connectors _______________ 55.10 UPS communication port ______________________ 65.11 Digital opto-isolated inputs ____________________ 65.12 Digital relay outputs _________________________ 75.13 Temperature sensor _________________________ 75.14 Ethernet port _______________________________ 75.15 Secondary Ethernet port (optional) _____________ 75.16 Console port RS232 (debug)___________________ 7

6 Connecting to the network _________________________ 87 Default settings __________________________________ 88 PCS200 web control ______________________________ 8

8.1 Front page access ___________________________ 88.2 System management _________________________ 98.3 Video monitor ______________________________ 108.4 Status ____________________________________ 128.5 I/O control ________________________________ 138.6 View configuration __________________________ 138.7 Headend description ________________________ 148.8 Time/Date ________________________________ 148.9 Network __________________________________ 158.10 Users ____________________________________ 168.11 View logs _________________________________ 168.12 Firmware update ___________________________ 178.13 Restart ___________________________________ 178.14 LOGOUT _________________________________ 17

9 APPENDIX ____________________________________ 189.1 Networking over GSM cellular data network ____ 18

Page 3: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

Remote control and monitoring server PCS200

1 Product descriptionCMH WEB server is an optional device for Terra Bus managed devices monitoring and control.Unit is considered as a master device on Terra Bus network as web-based frontend. Through the web server it is

possible to:- monitor up to 255 devices connected to the data bus;- view and change parameters on the individual devices;- view device specific diagnostic information;- operate advanced mode in terminal enabled devices;- upgrade device firmware.Unit is intended to be used together with MMH3000, CMH3000 and RMH3000 headends.The product is intended for indoor usage only.It is strictly recommended to feed AC power using UPS.

2 Safety instructionsThe server is powered from mains 230 V~. This voltage is dangerous to life.Any repairs must be done by a qualified personnel.To avoid the electric shock follow these instructions:Do not remove the cover, without isolating the unit from the mains supply.Do not plug the server into the mains supply if the power cord or plug are damaged.Do not plug the server into the mains supply until all cables have been connected correctly.To disconnect the server, disconnect plug from mains socket.The mains socket must be easily accessible.The server shall not be exposed to dripping or splashing water and no objects filled with liquids, such as vases,

shall be placed on it.Avoid placing server next to central heating components and in areas of high humidity.No naked flame sources, such as lighted candles, should be placed on server.If the server has been kept in cold conditions for a long time, keep it in a warm room no less than 2 hours before

plugging into the mains.The ventilation should not be impeded by covering the ventilation openings with items, such as newspapers,

table-cloths, curtains.

3 ParametersPower consumption: 198...250V~ 50Hz 3.5WWorking temperature 00C...500CHumidity ≤ 80%

3.1 Features:Remote control for CMH3000, MMH3000 and RMH3000 headends;Management from anywhere using a web browser;Server and module software upgrade via HTTP;Controls up to 255 modules;Custom access levels for multiple users;Integrated LCD and keyboard for configuration;I/O control for external devices.

3

Page 4: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

4 External view and operating control

Front view

5

4

1 USB control 2 LCD display 3 Keypad 4 “Addressed” indicator

5 “Status” indicator

6 “Ground” clamp 10 UPS communication port 14 Ethernet port

7 230V~ 50 Hz power supply input 11 Digital opto-isolated inputs 15 Secondary Ethernet port (optional)

8 Cooling fan 12 Digital relay outputs 16 Console port RS232 (debug)

9 “Terra bus” data bus connectors 13 Temperature sensor 17 Antenna port (not used)

Back view

Page 5: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

5 PCS200 control interfaceSee “External view and operating control” section 4 for visual interface control locations.

5.1 USB controlTerra Bus data bus can be managed using front panel USB port along with proper PC software (e.g. Terra Link,

CMH Master). During USB control mode LCD panels shows system status: “USB CONTROL”, “ADDRESSED”LED turns green and web server activity is suspended.

Note: To use USB port the driver must be installed. See supplied CD for more information.

5.2 LCD DisplayAlphanumeric LCD display shows current server status as well as network settings.

5.3 KeypadBasic network configuratin can be setup using onboard keypad. To move inside menu, press “>” or “<” buttons.

To activate selected submenu press “Enter”. “ESC” cancels any actions and returns to the default location (“Systemstatus”).

Menu structure:

System Status > IP adress > Netmask > Gateway > Primary DNS > Secondary DNS > Reboot

To change digital value press “Enter” and increase or decrease number above the marked using “>” or “<”buttons. Selection is confirmed by pressing “Enter”.

Repeat this sequence untill the last number is set. After finishing the configuration select “Reboot” and press“Enter”. System will reboot by indicating “System busy” in the “System status” screen. After changing status to “Ok”system is running with new network settings.

5.4 “Addressed” indicatorGreen “Addressed” indicator turns on when USB cable is connected.

5.5 “Status” indicatorGreen“Status” indicator stays on as long as PCS200 server is powered up. Note that for PCS200 units with

firmware version below 2.00, “Status” LED could be red.

5.6 “Ground” clampIt is highly recommended to have “Earth” safety terminal connected to “Ground” clamp to improve electrical

safety and EMI immunity.

5.7 230V ~50 Hz power supply input

5.8 Cooling fanPCS200 has internal temperature sensor built in. Cooling fan is automatically started keeping device operating

safely if internal temperature gets above threshold limit.

5.9 “Terra Bus” data bus connectors“Terra Bus” data bus is based on robust and industry standard RS485 bus specifications. Two parallel connectors

provided for user installation convenience. 4P4C “Terra Bus” cable is included in the package.PCS200 “Terra Bus” cables must be unplugged if another master (PC or handheld) is used on the data bus.

192.168.0.99

5

Page 6: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

5.10 UPS communication portThis port has two inputs used to monitor and report UPS status.Recommended mating terminal block connector:

Tyco Electronicsp/n 284507-4 or p/n 284509-4

Pin-out:pin 1 – 0V(logic ground)pin 2 – PCS200 Input #4 (Battery Low)pin 3 – 0V (logic ground)pin 4 – PCS200 input #3 (Power Failure)

Input #3 and #4 status and log can be viewed with web interface by clicking on “I/O Control” link.

Most smart UPS devices have standard serial port (female D-SUB 9) with status information.See connection table for PCS200 interfacing to smart UPS serial port.

PCS200 UPS COMM. UPS serial port Notespins (female D-SUB 9)

1 4 0V (logic ground)2 5 Battery Low, open-collector output from UPS.

Normally low (0V), goes high when low battery.3 4 0V (logic ground)4 2 Power Failure, RS232 level output from UPS.

Normally RS232 low level (-12V), goes toRS232 high level (+12V) when line power failure.

5.11 Digital opto-isolated inputsThere are two general purpose inputs.Recommended mating terminal block connector:

Tyco Electronicsp/n 284507-4 or p/n 284509-4

Pin-out:Pin 1 – Input #2 Low-sidePin 2 – Input #2 High-sidePin 3 – Input #1 Low-sidePin 4 – Input #1 High-side

Nominal input port voltage difference is +12V (operational from +5V to +20V).Input #1 and #2 status and log can be viewed with web interface by clicking on “I/O Control” link.See sample interface diagram below.

6

1 2 3 4 1 2 3 4 1 2 3 4

11111 222223333344444

Page 7: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

5.12 Digital relay outputsThere are two digital relay outputs. They could be used to control module power relays. This way user could

remotely restart station modules.Recommended mating terminal block connector:

Tyco Electronicsp/n 284507-4 or p/n 284509-4

Pin-out:Pin 1 – Output #1 contact 1Pin 2 – Output #1 contact 2Pin 3 – Output #2 contact 1Pin 4 – Output #2 contact 2

Relay output contacts electrical rating: 30VDC, 2A.When power is off and while system is booting, both relay output contacts are NORMALLY CLOSED. This way

using relay outputs to control system module power relays, system modules remain operational when PCS200 isrestarting.

When PCS200 has booted, outputs can be controlled by web interface (“I/O Control” link). Pressing “ON”makes contacts closed, “OFF” - contacts open.

5.13 Temperature sensorThis interface allows to connect external temperature sensor (1-Wire compatible).

Pin-out:Pin 1 - +5V power (supplied by PCS200)Pin 2 - not usedPin 3 - 1-Wire data busPin 4 - 0V (logic ground)

Temperature sensors can be supplied as an option, please contact manufacturer for further information.

5.14 Ethernet portThis Ethernet port is used to connected PCS200 to the network. PCS200 supports 10/100Mbps Ethernet.If PCS200 is placed behind a firewall or a router, make sure certain ports are open/forwarded (see “Connecting

to the network” section 6 for more details).

5.15 Secondary Ethernet port (optional)This feature is enabled with PCS200 firmware versions 1.20 and above.Secondary 10/100Mbps Ethernet port can be used to connect an IP streaming device like IP camera or video

server. Additional video/audio stream (TCP or UDP) ports needs to be open/forwarded if PCS200 is locatedbehind firewall/router. See “Video monitor” section 8.3 for more details.

5.16 Console port RS232 (debug)This RS232 serial port (115200bps, 8-N-1) outputs some debug boot messages, and can be ignored by the user.

7

Page 8: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

6 Connecting to the networkTo operate basic functions of PCS200 Ethernet and Data Bus cables must be connected.

• PCS200 can be operated using direct connection or pluged into Ethernet network. Ethernet socket[14] is located on the back of PCS200.

• PCS200 must be the only master device on the Terra Bus. Two parallel Data Bus sockets [9] arelocated on the back of PCS200. No other handheld, USB-Terra Bus, Ethernet-Terra Bus devicecan be used together. 4P4C cable is included in the package.

• If PCS200 is located behind a Firewall or router, following ports must be open or forwarded:1. HTTP port 80 (TCP)2. Extended HTML mode ports: 81 (TCP) and 1000 (TCP)3. Advanced terminal mode: 2300 (TCP)4. Other TCP or UDP ports if “Video monitor” feature is used. See “Video monitor” section 8.3 formore information.

• If remote location with TerraBus managed devices and PCS200 server doesn’t have access to theInternet, then GSM data networking option could be used as alternative solution. See Appendix –“Networking over GSM cellular data network” section 9.1 for more details.

7 Default settings

IP: 192.168.0.99Netmask: 255.255.255.0Gateway: 192.168.0.1User: terraPassword terraSubrack count 2

8 PCS200 web control

8.1 Front page accessDevice is shipped with default user “terra” and password “terra”. Administrator can enable and disable

access by adding users in web page “Users”.

8

Page 9: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

8.2 System managementTop of the webpage shows currently logged in user, PCS200 serial number and PCS200 firmware version.If some modules aren’t visible or module firmware upgrade has been just performed, pressing “Rescan” link will

trigger PCS200 to scan all subrack addresses and update list of modules in System management page.Terra Bus enabled modules are shown on the “SYSTEM MANAGEMENT” page:

Number of visible Terra Bus subracks can be set in “View configuration” page.By pressing on the existing device, it is possible to view and change device’s parameters.After selecting desired settings, press button “Apply Changes” to activate configuration.

“Set Default Parameters” and “Firmware upgrade” options are only available in PCS200 with firmwareversion of 1.20 and above.

“Set Default Parameters” button sets default module parameters. After operation completes, “SYSTEMMANAGEMENT” page will load automatically. Please select same module to check its parameters again. If errormessages are shown in Diagnostics window, press “Reset module” following by “Refresh data” to update moduleparameter view. 9

Page 10: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

“Firmware upgrade” button allows user to upgrade module firmware remotely. User must select module firmwarefile(s) based on given format (e.g. firmware file 530XX_1_142.hex would fit in shown case).

Please note that module firmware upgrade might take several minutes and must not be interrupteduntil it is complete otherwise module might get corrupted and unusable.

Both buttons “Set Default Parameters” and “Firmware upgrade” require ‘Administrator’ access level to operate(see “Users” section 8.10 for more details).

8.3 Video monitorThis option is only available in PCS200 with firmware version of 1.20 and above.“Video monitor” link allows to view video stream of an IP streaming device (IP camera, video server) connected

to a secondary Ethernet port [5.15].IP streaming device must be configured with the following manual/static network settings before connecting to

PCS200 server:IP address: 192.168.99.2Subnet Mask: 255.255.255.0Gateway: 192.168.99.1

Also check IP streaming device manufacturer documentation or configuration settings to find out which ports andwhich protocols (TCP and/or UDP) are used for video/audio/control streams.

These ports must be open/forwarded in your firewall or router along with other PCS200 ports (see [6] “Connectingto the network”).

Same streaming ports must be configured in PCS200 server internal firewall too. By default PCS200 has followinginternal ports open:

80 TCP5001 TCP, UDP5002 TCP, UDP5003 TCP, UDP

PCS200 server internal firewall ports are listed at the bottom of “Video monitor” page.

10

Page 11: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

In order to modify existing ports press “FireWall Ports” link. Following page will be displayed:

To add a new port or modify existing port and protocol, enter port number, select TCP, UDP or both protocolsand press CHANGE. To delete non-needed port, just enter port number, leave TCP and UDP selections blank andpress CHANGE.

Once all needed ports have been modified, press DONE to save new internal firewall configurations. And press“Video monitor” link again.

Internal IP streaming device web interface should open up in the main frame. It is very likely that IP streamingdevice will have some default login prompt, again check IP streaming device manufacturer documentation for loginuser name and password.

11

Page 12: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

12

8.4 StatusStatus submenu allows to automatically generate and send e-mail messages if temperature gets outside specified

limits or one of the inputs change. User can tick which parameters should be monitored and reported.For this feature to work, email settings must be correctly set in “Network” page.PCS200 has internal temperature sensor. External temperature is monitored only if external temperature sensor is

connected to connector [11]. Digital inputs are located in connector [9].

Page 13: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

13

8.5 I/O controlI/O control submenu display status of 2 relay outputs, 2 general purpose digital inputs and UPS state. Relay

outputs can control external devices.To modify I/O description:

• Enter brief description in the text input area located near corresponding input/output.• Press “Comment” button to save the information.

Events log will display:• A relay state change by user.• Digital input trigered by external device.• Power line status change is reported by UPS.

8.6 View configurationView configuration submenu allows user to choose number of subracks to be shown in “SYSTEM

MANAGEMENT” page. This parameter defines how many devices should be scanned by Terra Bus.Recommendation: use only groups which are actually connected to the data bus. This improves scan time and

performance.

Page 14: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

14

8.7 Headend descriptionUser may save any information related to connected headend. A three files can be uploaded for the future disposal.

File size is limitted up to 5 MB each.To upload file:• Press “Browse” button.• Locate file on the computer.• Press “Send” button.Upload time depends on file size and network conditions. System displays confirmation message if file is uploaded successfully.To download file:• Press in the button named “Description #<1-3> <FILE>”.• Confirm file download.

8.8 Time/DatePCS200 internal battery-backed system clock can by adjusted by synchronizing with PC time in “Time/Date”

submenu page by pressing button: “SYNC”.

Page 15: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

15

8.9 NetworkTo access web server it must be configured with proper TCP/IP settings. It can be done by:• changing settings with onboard LCD panel• filling up required values on the web page “Network”Device is shipped with settings:

IP address: 192.168.0.99Netmask: 255.255.255.0

If device is used not in the same subnet as the user’s workstation, “Gateway” IP address is also required(e.g. 192.168.0.1). At least one DNS address should be supplied.

If email status reports are required (see “Status” page), then SMTP server and email addresses must be supplied.

Page 16: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

16

8.10 UsersAdministrator can setup new accounts by supplying new user name, password and the access level. Any user who

has lower access level than administrator is unable to create new users.There are two user access levels, ‘Administrator’ and ‘User’. ‘User’ access level is prevented from accessing

following functions:• Upgrade module firmware• Set default module parameters• Add/delete/modify users• View logs• Upgrade PCS200 server firmware

8.11 View logsAny successful or unsuccessful login of existing user will be show in the log file. Login time and remote user’s IP

address are saved. Administrator can clear access log by pressing “Clear ALL history”.

Page 17: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

17

8.12 Firmware updateFirmware update allows user to upload and upgrade PCS200 server firmware supplied by manufacturer.PCS200 firmware version is printed on top of each page after serial number.

8.13 RestartReboots PCS200 server.

8.14 LOGOUTAllows user to log out.

Page 18: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

9 APPENDIX

9.1 Networking over GSM cellular data networkSome remote locations where Terra Bus managed devices and PCS200 server is installed might not have Internet

access. Then GSM data networking option could be used as alternative as long as remote location is covered with3G/EDGE/GPRS data service by the cellular provider. It’s recommended to use 3G or EDGE service to allow highenough data rates for comfortable PCS200 control.

The user needs to obtain a SIM card with static IP address from local cellular operator. It might also be possibleto use SIM card with dynamic IP address, then dynamic DNS service (e.g. www.dyndns.org) could be used toprovide symbolic domain name. But it’s important that cellular network provider SIM card ISP public IP wouldmatch ISP local IP address, otherwise GSM router and PCS200 will not be visible and accessible from the Internet.In some cases this could be requested as extra service from cellular network provider. It is recommended to consultlocal network operator before ordering a SIM card or service.

If user is located in the area without internet access, then similarly 3G/EDGE router could be used to accessInternet and therefore gain access to PCS200.

18

Page 19: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

No additional PCS200 configurations are necessary, it can be left with default network settings:IP: 192.168.0.99Netmask: 255.255.255.0Gateway: 192.168.0.1

Following parameters must be configured in 3G/EDGE router:• APN (Access Point Name) and phone number (*99#), this information is supplied by GSM network

provider• Router static WAN IP address, supplied by GSM network provider• Router LAN settings:

o IP: 192.168.0.1o Subnet: 255.255.255.0

• Router Ports forwarding to IP 192.168.0.99o 80 TCPo 81 TCPo 1000 TCPo 2300 TCPo possibly additional IP streaming ports if “Video Monitor” feature is used (not recommended

because of high amount of network traffic and limited speed)

Internal tests and step by step procedure is based on using RUT100 - 3G Mobile Router manufactured byTeltonika (http://www.teltonika.lt). Although any other 3G/EDGE router with similar characteristics could be usedtoo.

RUT100 by default comes with LAN IP address of 192.168.0.1 and DHCP enabled. Connect your PC toRUT100 for configuration, and login (default user: admin, password: admin01).

Go to “CONFIGURATION” and enter APN and phone number. This information should be supplied by cellularnetwork provider when you purchase a SIM card.

19

Page 20: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

Then enter network settings as shown:

Next add following ports to forward to IP 192.168.0.99:• 80 TCP• 81 TCP• 1000 TCP• 2300 TCP

20

Page 21: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

Save all settings and reboot RUT100 router. Then connect RUT100 LAN port to PCS200 Ethernet port [14].Enter provided static IP address (or dynamic DNS domain name) in the Internet Explorer address bar, and youshould see PCS200 server startup screen.

21

Page 22: Remote control and monitoring server PCS200h24-files.s3.amazonaws.com/83431/228499-LexxL.pdf · Remote control and monitoring server PCS200 1 Product description CMH WEB server is

TERRA UAB

Draugystes str. 22, LT-51256 Kaunas, LithuaniaTel.: +370 37 - 31 34 44, fax: +370 37 - 31 35 55

E-mail: [email protected]://www.terraelectronics.com