relion 670 series transformer protection ret670 pre ......1. application ret670 provides fast and...

102
Relion ® 670 series Transformer protection RET670 Pre-configured Product Guide

Upload: others

Post on 27-Jan-2021

12 views

Category:

Documents


0 download

TRANSCRIPT

  • Relion® 670 series

    Transformer protection RET670Pre-configuredProduct Guide

  • Contents

    1. Application...........................................................3

    2. Available functions...............................................8

    4. Functionality.......................................................12

    5. Hardware description.........................................27

    6. Connection diagrams.........................................29

    7. Technical data....................................................41

    8. Ordering.............................................................89

    Disclaimer

    The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumesno responsibility for any errors that may appear in this document.

    © Copyright 2010 ABB AB.

    All rights reserved.

    Trademarks

    ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks orregistered trademarks of their respective holders.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    2 ABB

  • 1. Application

    RET670 provides fast and selectiveprotection, monitoring and control for two-and three-winding transformers,autotransformers, generator-transformer unitsand shunt reactors. The transformer IED isdesigned to operate correctly over a widefrequency range in order to accommodatepower system frequency variations duringdisturbances and generator start-up and shut-down.

    A very fast differential protection function,with automatic CT ratio matching and vectorgroup compensation, makes this IED theideal solution even for the most demandingapplications. RET670 has very lowrequirements on the main CTs, nointerposing CTs are required. It is suitable fordifferential applications with multi-breakerarrangements with up to six restraint CTinputs. The differential protection function isprovided with 2nd harmonic and wave-blockrestraint features to avoid tripping formagnetizing inrush, and 5th harmonicrestraint to avoid tripping for overexcitation.

    The differential function offers a highsensitivity for low-level internal faults.RET670 unique and innovative sensitivedifferential protection feature, based on well-known theory of symmetrical componentsprovide best possible coverage for windinginternal turn-to-turn faults.

    Low impedance restricted earth-faultprotection functions are available ascomplimentary sensitive and fast mainprotection against winding earth faults. Thisfunction includes a directional zero-sequencecurrent criterion for additional security.

    Additionally a high impedance differentialfunction is available. It can be used asrestricted earth fault or, as three functions areincluded, also as differential protection onautotransformers, as differential protectionfor a tertiary connected reactor, as T-differential protection for the transformer

    feeder in a mesh-corner or ring arrangement,as tertiary bus protection and so on.

    Tripping from Pressure relief / Buchholz andtemperature devices can be done through thetransformer IED where pulsing, lock-outcontact output and so on, is performed. Thebinary inputs are heavily stabilized againstdisturbance to prevent incorrect operations atfor example, dc system capacitive dischargesor dc earth faults.

    Distance protection functionality for phase-to-phase and/or phase-to-earth faults is availableas back-up protection for faults within thetransformer and in the connected powersystem.

    Versatile phase, earth, positive and zerosequence overcurrent functions, which canoptionally be made directional and/or voltagecontrolled, provide further alternative backupprotection. Thermal overload with two time-constants, volts per hertz, over/under voltageand over/under frequency protectionfunctions are also available.

    Built-in disturbance and event recorderprovides valuable data to the user aboutstatus and operation for post-faultdisturbance analysis.

    Breaker failure protection for eachtransformer breaker allows high speed back-up tripping of surrounding breakers.

    The transformer IED can also be providedwith a full control and interlockingfunctionality including Synchrocheck functionto allow integration of the main and/or alocal back-up control.

    The advanced logic capability, where userlogic is prepared with a graphical tool, allowsspecial applications such as automaticopening of disconnectors in multi-breakerarrangements, closing of breaker rings, loadtransfer logic and so on. The graphical

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010Pre-configured Revision: B

    ABB 3

  • configuration tool ensures simple and fasttesting and commissioning.

    Serial data communication is via opticalconnections to ensure immunity againstdisturbances.

    The wide application flexibility makes thisproduct an excellent choice for both newinstallations and the refurbishment of existinginstallations.

    Four packages has been defined for followingapplications:

    • Two winding transformer in singlebreaker arrangements (A30)

    • Two winding transformer in multibreaker arrangements (B30)

    • Three winding transformer in singlebreaker arrangements (A40)

    • Three winding transformer in multibreaker arrangements (B40)

    The packages are configured and ready fordirect use. Optional functions are notconfigured but a maximum configurationwith all optional functions are available astemplate in the graphical configuration tool.An alternative for Autotransformers is alsoavailable as a configuration template. Analogand tripping IO has been pre-defined forbasic use on the, as standard supplied onebinary input module and one binary outputmodule. Add binary I/O as required for yourapplication at ordering. Other signals need tobe applied as required for each application.

    For details on included basic functions, referto chapter ""

    The applications are shown in figures 1, 2, 3and 4 for single resp. multi-breakerarrangement.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    4 ABB

  • IN>44

    3U>22

    3U<22

    I->O

    51/67

    51N/67N

    59

    27

    94/86

    87T

    3Id/I>

    IdN/I>

    87N

    IdN/I>

    87N

    3I>50BF

    3I>44

    IN>44

    51N/67N

    SC/VC

    25

    51/67

    3I>50BF

    3I>44

    I->O

    94/86

    TRIP BUSBAR

    TRIP BUSBAR

    CB2

    TRIP CB2

    CB1TRIP CB1

    en05000272.vsdIEC05000272 V1 EN

    Figure 1. A typical protection application for a two winding transformer in single breakerarrangements is shown on the figure. The system earthing principle and connectiongroup will vary which gives different detailed arrangements for each application.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 5

  • IN>44

    3U>22

    3U<22

    I->O

    51/67

    51N/67N

    59

    27

    94/86

    87T

    3Id/I>

    IdN/I>

    87N

    IdN/I>

    87N

    3I>50BF

    3I>44

    IN>44

    51N/67N

    SC/VC

    25

    51/67

    3I>50BF

    3I>44

    I->O

    94/86

    TRIP BUSBAR&CB2

    TRIP BUSBAR&CB1/2

    CB3

    TRIP CB3

    CB1

    TRIP CB1

    CB2

    S3I>

    50BF

    TRIP CB1/3

    I->O

    94/86TRIP CB2

    en05000273.vsdIEC05000273 V1 EN

    Figure 2. A typical protection application for a two winding transformer in multi breakerarrangements is shown on the figure. The system earthing principle and connectiongroup will vary which gives different detailed arrangements for each application.Breaker failure function is here provided for each breaker.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    6 ABB

  • IN>44

    3U>22

    3U<22

    I->O

    51/67

    51N/67N

    59

    27

    94/86

    87T

    3Id/I>

    IdN/I>

    87N

    IdN/I>

    87N

    3I>50BF

    3I>44

    IN>44

    51N/67N

    SC/VC

    25

    51/67

    3I>50BF

    3I>44

    I->O

    94/86

    TRIP BUSBAR

    TRIP BUSBAR&CB1/2/3

    CB2

    TRIP CB2

    CB1TRIP CB1

    CB3

    3I>44

    3I>50BFTRIP BUSBAR

    &CB1/2

    UN>22

    59N

    t2

    TRIPI->O

    94/86

    en05000274.vsdIEC05000274 V1 EN

    Figure 3. A typical protection application for a three winding transformer in single breakerarrangements is shown on the figure. The system earthing principle and connectiongroup will vary which gives different detailed arrangements for each application.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 7

  • IN>44

    3U>22

    3U<22

    I->O

    51/67

    51N/67N

    59

    27

    94/86

    87T

    3Id/I>

    IdN/I>

    87N

    IdN/I>

    87N

    3I>50BF

    3I>44

    IN>44

    51N/67N

    SC/VC

    25

    51/67

    3I>50BF

    3I>44

    I->O

    94/86

    TRIP BUSBAR&CB2/3/4

    TRIP BUSBAR&CB1/2/4

    CB3

    TRIP CB3

    CB1

    TRIP CB1

    CB2

    S3I>

    50BFTRIP CB1/3/4/X

    I->O

    94/86TRIP CB2

    CB4

    3I>44

    3I>50BFTRIP BUSBAR

    &CB1/2/3

    TRIP

    UN>22

    59N

    t2

    I->O

    94/86

    en05000275.vsdIEC05000275 V1 EN

    Figure 4. A typical protection application for a three winding transformer in multi breakerarrangements is shown on the figure. The system earthing principle and connectiongroup will vary which gives different detailed arrangements for each application.Breaker failure function is here provided for each breaker.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    8 ABB

  • 2. Available functions

    Function description Transformerback-upprotection(A10)

    Voltagecontrol(A25)

    Singlebreaker, 2winding(A30)

    Multibreaker, 2winding(B30)

    Singlebreaker, 3winding(A40)

    Multibreaker, 3winding(B40)

    AN

    SI

    Bas

    ic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign)

    Differential protection

    87T Transformer differentialprotection, two winding(T2WPDIF)

    - - - - 1 - 1 - - - - -

    87T Transformer differentialprotection, three winding(T3WPDIF)

    - - - - - - - - 1 - 1 -

    87 1 phase High impedancedifferential protection(HZPDIF)

    1 - - - - 3/A02 - 3/A02 - 3/A02 - 3/A02

    87N Restricted earth faultprotection, low impedance(REFPDIF)

    1 - - - 2 - 2 - 2 1/A01 2 1/A01

    Impedance protection

    21 Distance protection zone,quadrilateral characteristic(ZMQPDIS/ZMQAPDIS)

    - - - - - 4/B02 - 4/B02 - 4/B02 - 4/B02

    Directional impedancequadrilateral (ZDRDIR)

    - - - - - 2/B02 - 2/B02 - 2/B02 - 2/B02

    21 Full-scheme distanceprotection, mhocharacteristic (ZMHPDIS)

    - - - - - 4/B08 - 4/B08 - 4/B08 - 4/B08

    Full-scheme distanceprotection, quadrilateral formho (ZMMPDIS)

    - - - - - 4/B08 - 4/B08 - 4/B08 - 4/B08

    Directional impedanceelement for mhocharacteristic (ZDARDIR)

    - - - - - 2/B08 - 2/B08 - 2/B08 - 2/B08

    Additional distanceprotection directionalfunction for earth faults(ZDARDIR)

    - - - - - 1/B08 - 1/B08 - 1/B08 - 1/B08

    Mho impedancesupervision logic(ZSMGAPC)

    - - - - - 1/B08 1/B08 1/B08 1/B08

    78 Power Swing detection(ZMRPSB)

    - - - - - 1/B02/B08

    - 1/B02/B08

    - 1/B02/B08

    - 1/B02/B08

    Current protection

    50 Instantaneous phaseovercurrent protection(PHPIOC)

    3 - - 2/C14 2 - 2 - 3 - 3 -

    51/67

    Four step phaseovercurrent protection(OC4PTOC)

    3 - - 2/C14 2 - 2 - 3 - 3 -

    50N Instantaneous residualovercurrent protection(EFPIOC)

    3 - - 2/C14 2 - 2 - 3 - 3 -

    51N/67N

    Four step residualovercurrent protection(EF4PTOC)

    3 - - 2/C14 2 - 2 - 3 - 3 -

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 9

  • Function description Transformerback-upprotection(A10)

    Voltagecontrol(A25)

    Singlebreaker, 2winding(A30)

    Multibreaker, 2winding(B30)

    Singlebreaker, 3winding(A40)

    Multibreaker, 3winding(B40)

    AN

    SI

    B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign)

    67N Sensitive directionalresidual overcurrent andpower protection(SDEPSDE)

    1 - - 1/C16 - 1/C16 - 1/C16 - 1/C16 - 1/C16

    49 Thermal overloadprotection, two timeconstants (LPPTTR)

    1 - - - 1 1/C05 1 1/C05 2 1/C05 2 1/C05

    50BF

    Breaker failure protection(CCRBRF)

    3 - - - 2 - 4 - 3 - 6 -

    52PD

    Pole-discordanceprotection (CCRPLD)

    - - - - 1 - 2 - 1 - 2 -

    37 Directional underpowerprotection (GUPPDUP)

    - - - - - 1/C17 - 1/C17 - 1/C17 - 1/C17

    32 Directional overcurrentprotection (GOPPDOP)

    - - - - - 1/C17 - 1/C17 - 1/C17 - 1/C17

    46 Broken conductor check(BRCPTOC)

    1 - 1 - 1 - 1 - 1 - 1 -

    Voltage protection

    27 Two step undervoltageprotection (UV2PTUV)

    - 1/D01 - 2/D02 1 1/D01 1 1/D01 1 2/D02 1 2/D02

    59 Two step overvoltageprotection (OV2PTOV)

    - 1/D01 - 2/D02 1 1/D01 1 1/D01 1 2/D02 1 2/D02

    59N Two step residualovervoltage protection(ROV2PTOV)

    - 1/D01 - 2/D02 1 1/D01 1 1/D01 1 2/D02 1 2/D02

    24 Overexcitation protection(OEXPVPH)

    - - - - - 1/D03 - 1/D03 - 2/D04 - 2/D04

    60 Voltage differentialprotection (VDCPTOV)

    2 - 2 - 2 - 2 - 2 - 2 -

    27 Loss of voltage check(LOVPTUV)

    1 - 1 - 1 - 1 - 1 - 1 -

    Frequency protection

    81 Underfrequency protection(SAPTUF)

    - 6/E01 - - - 6/E01 - 6/E01 - 6/E01 - 6/E01

    81 Overfrequency protection(SAPPTOF)

    - 6/E01 - - - 6/E01 - 6/E01 - 6/E01 - 6/E01

    81 Rate-of-change frequencyprotection (SAPFRC)

    - 6/E01 - - - 6/E01 - 6/E01 - 6/E01 - 6/E01

    Multipurpose protection

    General current andvoltage protection(CVGAPC)

    - - - - - 6/F02 - 6/F02 - 6/F02 - 6/F02

    Secondary system supervision

    Current circuit supervision(CCSRDIF)

    - - 4 - 2 - 3 - 3 - 5 -

    Fuse failure supervision(SDDRFUF)

    1 - - - 3 - 3 - 3 - 3 -

    Control

    25 Synchrocheck, energizingcheck and synchronizing(SESRSYN)

    1 - - - 1 - 1 2/H01 1 3/H02 1 4/H03

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    10 ABB

  • Function description Transformerback-upprotection(A10)

    Voltagecontrol(A25)

    Singlebreaker, 2winding(A30)

    Multibreaker, 2winding(B30)

    Singlebreaker, 3winding(A40)

    Multibreaker, 3winding(B40)

    AN

    SI

    Bas

    ic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign)

    Apparatus control for up to6 bays, max 30 apparatusesincl. interlocking (APC30)

    - - - - - 1/H09 - 1/H09 - 1/H09 - 1/H09

    90 Automatic voltage controlfor tapchanger, singlecontrol (TR1ATCC)

    - - 2 2/H16 - 1/H11 - 1/H11 - 1/H112/H16

    - 1/H112/H16

    90 Automatic voltage controlfor tapchanger, parallelcontrol (TR8ATCC)

    - - 2 2/H18 - 1/H15 - 1/H15 - 1/H152/H18

    - 1/H152/H18

    84 Tap changer control andsupervision, 6 binaryinputs (TCMYLTC)

    - - 4 - 4 - 4 - 4 - 4 -

    84 Tap changer control andsupervision, 32 binaryinputs (TCLYLTC)

    - - 4 - 4 - 4 - 4 - 4 -

    Logic rotating switch forfunction selection andLHMI presentation(SLGGIO)

    15 - 15 - 15 - 15 - 15 - 15 -

    Selector mini switchextension (VSGGIO)

    20 - 20 - 20 - 20 - 20 - 20 -

    Scheme communication

    85 Scheme communicationlogic for residualovercurrent protection(ECPSCH)

    - - - - 1 - 1 - 1 - 1 -

    85 Current reversal and weak-end infeed logic forresidual overcurrentprotection (ECRWPSCH)

    - - - - 1 - 1 - 1 - 1 -

    Logic

    94 Tripping logic (SMPPTRC) 3 - 2 - 2 - 3 - 5 - 6 -

    Trip matrix logic(TMAGGIO)

    12 - 12 - 12 - 12 - 12 - 12 -

    Monitoring

    Measurements (CVMMXU) 6/10/6

    - 6/10/6

    - 6/10/6

    - 6/10/6

    - 6/10/6

    - 6/10/6

    -

    Event counter (CNTGGIO) 5 - 5 - 5 - 5 - 5 - 5 -

    Disturbance report(DRPRDRE)

    1 - 1 - 1 - 1 - 1 - 1 -

    IEC61850 genericcommunication I/Ofunctions (SPGGIO)

    64 - 64 - 64 - 64 - 64 - 64 -

    Measured value expanderblock (RANGE_XP)

    66 - 66 - 66 - 66 - 66 - 66 -

    Metering

    Pulse counter logic(PCGGIO)

    16 - 16 - 16 - 16 - 16 - 16 -

    Function for energycalculation and demandhandling (ETPMMTR)

    6 - 6 - 6 - 6 - 6 - 6 -

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 11

  • Function description Transformerback-upprotection(A10)

    Voltagecontrol(A25)

    Singlebreaker, 2winding(A30)

    Multibreaker, 2winding(B30)

    Singlebreaker, 3winding(A40)

    Multibreaker, 3winding(B40)

    AN

    SI

    B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign) B

    asic

    Option(Qty/optiondesign)

    Station communication

    IEC61850-8-1Communication *)

    1 - 1 - 1 - 1 - 1 - 1 -

    LON communicationprotocol *)

    1 - 1 - 1 - 1 - 1 - 1 -

    SPA communicationprotocol *)

    1 - 1 - 1 - 1 - 1 - 1 -

    IEC60870-5-103communication protocol *)

    1 - 1 - 1 - 1 - 1 - 1 -

    DNP3.0 for TCP/IP andEIA-485 communicationprotocol

    1 - 1 - 1 - 1 - 1 - 1 -

    Single command, 16 signals 4 - 4 - 4 - 4 - 4 - 4 -

    Multiple command andtransmit

    60/10

    - 60/10

    - 60/10

    - 60/10

    - 60/10

    - 60/10

    -

    Remote communication

    Binary signal transfer 6 - 6 - 6 - 6 - 6 - 6 -

    *) In order to utilize it, an appropriate optional hardware port must be ordered.

    4. Functionality

    Differential protection

    Transformer differential protectionT2WPDIF/T3WPDIF

    The functions Transformer differentialprotection, two-winding (T2WPDIF) andTransformer differential protection, three-winding (T3WPDIF) are provided withinternal CT ratio matching and vector groupcompensation and when required zerosequence current elimination is also madeinternally in the software.

    The function can be provided with up to sixthree phase sets of current inputs. All currentinputs are provided with percentage biasrestraint features, making the IED suitable fortwo- or three-winding transformers in multi-breaker station arrangements.

    Two-winding applications

    xx05000048.vsd

    IEC05000048 V1 EN

    two-windingpowertransformer

    xx05000049.vsd

    IEC05000049 V1 EN

    two-windingpowertransformer withunconnecteddelta tertiarywinding

    xx05000050.vsd

    IEC05000050 V1 EN

    two-windingpowertransformer withtwo circuitbreakers on oneside

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    12 ABB

  • xx05000051.vsd

    IEC05000051 V1 EN

    two-windingpowertransformer withtwo circuitbreakers and twoCT-sets on bothsides

    Three-winding applications

    xx05000052.vsd

    IEC05000052 V1 EN

    three-windingpowertransformer withall threewindingsconnected

    xx05000053.vsd

    IEC05000053 V1 EN

    three-windingpowertransformer withtwo circuitbreakers and twoCT-sets on oneside

    xx05000057.vsd

    IEC05000057 V1 EN

    Autotransformerwith two circuitbreakers and twoCT-sets on twoout of three sides

    Figure 5. CT group arrangement fordifferential protection andother protections

    The setting facilities cover for applications ofthe differential protection to all types ofpower transformers and autotransformerswith or without load tap changer as well asfor shunt reactors or and local feeders withinthe station. An adaptive stabilizing feature isincluded for heavy through-faults. Byintroducing the load tap changer position, thedifferential protection pick-up can be set tooptimum sensitivity thus covering internalfaults with low fault level.

    Stabilization is included for inrush currentsrespectively for overexcitation condition.Adaptive stabilization is also included forsystem recovery inrush and CT saturation forexternal faults. A fast high set unrestraineddifferential current protection is included forvery high speed tripping at high internal faultcurrents.

    Innovative sensitive differential protectionfeature, based on the theory of symmetricalcomponents, offers best possible coverage forpower transformer windings turn-to-turnfaults.

    1Ph High impedance differentialprotection HZPDIF

    The 1Ph High impedance differentialprotection HZPDIF function can be usedwhen the involved CT cores have the sameturn ratio and similar magnetizingcharacteristic. It utilizes an externalsummation of the phases and neutral currentand a series resistor and a voltage dependentresistor externally to the IED.

    Restricted earth fault protection (PDIF,87N)

    Restricted earth-fault protection, lowimpedance function (REFPDIF) can be usedon all directly or low impedance earthedwindings. REFPDIF function can providehigher sensitivity (down to 5%) and higherspeed as it measures individually on eachwinding and thus do not need inrushstabilization.

    The low impedance function is a percentagebiased function with an additional zerosequence current directional comparisoncriteria. This gives excellent sensitivity andstability for through faults. The functionallows use of different CT ratios andmagnetizing characteristics on the phase andneutral CT cores and mixing with otherfunctions and protection IEDs on the samecores.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 13

  • xx05000058.vsd

    IEC05000058 V1 EN

    Figure 6. Autotransformer low impedance REF

    Impedance protection

    Distance measuring zone, quadrilateralcharacteristic ZMQPDIS, ZMQAPDIS

    The line distance protection is a four zonefull scheme protection with three fault loopsfor phase-to-phase faults and three faultloops for phase-to-earth fault for each of theindependent zones. Individual settings foreach zone in resistive and reactive reachgives flexibility for use as back-up protectionfor transformer connected to overhead linesand cables of different types and lengths.

    ZMQPDIS together with Phase selection withload encroachment FDPSPDIS hasfunctionality for load encroachment, whichincreases the possibility to detect highresistive faults on heavily loaded lines.

    The distance protection zones can operateindependently of each other in directional(forward or reverse) or non-directional mode.

    Full-scheme distance measuring, Mhocharacteristic ZMHPDIS

    The numerical mho line distance protection isafour zone full scheme protection for back-updetection of short circuit and earth faults. Thefour zones have fully independent measuringand settings, which gives high flexibility forall types of lines.

    The function can be used as underimpedance back-up protection fortransformers and generators.

    Phase selection, quadrilateralcharacteristic with fixed angle FDPSPDIS

    The operation of transmission networkstoday is in many cases close to the stability

    limit. Due to environmental considerations,the rate of expansion and reinforcement ofthe power system is reduced, for example,difficulties to get permission to build newpower lines. The ability to accurately andreliably classify the different types of fault, sothat single pole tripping and autoreclosingcan be used plays an important role in thismatter. Phase selection, quadrilateralcharacteristic with fixed angle FDPSPDIS isdesigned to accurately select the proper faultloop in the distance function dependent onthe fault type.

    The heavy load transfer that is common inmany transmission networks may make faultresistance coverage difficult to achieve.Therefore, FDPSPDIS has a built-in algorithmfor load encroachment, which gives thepossibility to enlarge the resistive setting ofboth the phase selection and the measuringzones without interfering with the load.

    The extensive output signals from the phaseselection gives also important informationabout faulty phase(s), which can be used forfault analysis.

    Full-scheme distance protection,quadrilateral for earth faults ZMMPDIS,ZMMAPDIS

    The distance protection is a four zoneprotection with three fault loops for phase-to-earth fault for each of the independent zones.Individual settings for each zone resistive andreactive reach give flexibility for use onoverhead lines and cables of different typesand lengths.

    The Full-scheme distance protection,quadrilateral for earth faults functionsZMMDPIS and ZMMAPDIS have functionalityfor load encroachment, which increases thepossibility to detect high resistive faults onheavily loaded lines .

    The independent measurement of impedancefor each fault loop together with a sensitiveand reliable built in phase selection makesthe function suitable in applications withsingle phase auto-reclosing.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    14 ABB

  • The distance protection zones can operate,independent of each other, in directional(forward or reverse) or non-directional mode.This makes them suitable, together withdifferent communication schemes, for theprotection of power lines and cables incomplex network configurations, such asparallel lines, multi-terminal lines.

    Directional impedance element for Mhocharacteristic ZDMRDIR

    The phase-to-earth impedance elements canbe optionally supervised by a phaseunselective directional function (phaseunselective, because it is based onsymmetrical components).

    Faulty phase identification with loadencroachment FMPSPDIS

    The operation of transmission networkstoday is in many cases close to the stabilitylimit. Due to environmental considerationsthe rate of expansion and reinforcement ofthe power system is reduced, for exampledifficulties to get permission to build newpower lines. The ability to accurate andreliable classifying the different types of faultso that single phase tripping andautoreclosing can be used plays an importantroll in this matter.

    The phase selection function is design toaccurate select the proper fault loop in thedistance function dependent on the fault type.

    The heavy load transfer that is common inmany transmission networks may in somecases interfere with the distance protectionzone reach and cause unwanted operation.Therefore the function has a built inalgorithm for load encroachment, which givesthe possibility to enlarge the resistive settingof the measuring zones without interferingwith the load.

    The output signals from the phase selectionfunction produce important informationabout faulty phase(s), which can be used forfault analysis as well.

    Power swing detection ZMRPSB

    Power swings may occur after disconnectionof heavy loads or trip of big generation plants.

    Power swing detection function (ZMRPSB) isused to detect power swings and initiateblock of selected distance protection zones.Occurrence of earth-fault currents during apower swing can block ZMRPSB function toallow fault clearance.

    Power swing logic ZMRPSL

    Additional logic is available to secure trippingfor faults during power swings and preventtripping at power swings started by a fault inthe network.

    Current protection

    Instantaneous phase overcurrentprotection PHPIOC

    The instantaneous three phase overcurrentfunction has a low transient overreach andshort tripping time to allow use as a high setshort-circuit protection function.

    Four step phase overcurrent protectionOC4PTOC

    The four step phase overcurrent protectionfunction OC4PTOC has an inverse or definitetime delay independent for each stepseparately.

    All IEC and ANSI time delayed characteristicsare available together with an optional userdefined time characteristic.

    The directional function is voltage polarizedwith memory. The function can be set to bedirectional or non-directional independentlyfor each of the steps.

    A 2nd harmonic blocking can be setindividually for each step.

    Instantaneous residual overcurrentprotection EFPIOC

    The Instantaneous residual overcurrentprotection EFPIOC has a low transientoverreach and short tripping times to allowuse for instantaneous earth-fault protection,

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 15

  • with the reach limited to less than typicaleighty percent of the transformer impedanceat minimum source impedance. EFPIOC canbe configured to measure the residual currentfrom the three-phase current inputs or thecurrent from a separate current input.EFPIOC can be blocked by activating theinput BLOCK.

    Four step residual overcurrent protectionEF4PTOC

    The four step residual overcurrent protectionEF4PTOC has an inverse or definite timedelay independent for each step separately.

    All IEC and ANSI time delayed characteristicsare available together with an optional userdefined characteristic.

    The directional function is voltage polarized,current polarized or dual polarized.

    EF4PTOC can be set directional or non-directional independently for each of the steps.

    A second harmonic blocking can be setindividually for each step.

    EF4PTOC can be configured to measure theresidual current from the three-phase currentinputs or the current from a separate currentinput.

    Sensitive directional residual overcurrentand power protection SDEPSDE

    In isolated networks or in networks withhigh impedance earthing, the earth faultcurrent is significantly smaller than the shortcircuit currents. In addition to this, themagnitude of the fault current is almostindependent on the fault location in thenetwork. The protection can be selected touse either the residual current or residualpower component 3U0·3I0·cos j, foroperating quantity with maintained shortcircuit capacity. There is also available onenondirectional 3I0 step and one 3U0overvoltage tripping step.

    Thermal overload protection, two timeconstant TRPTTR

    If the temperature of a power transformer/generator reaches very high values the

    equipment might be damaged. The insulationwithin the transformer/generator will haveforced ageing. As a consequence of this therisk of internal phase-to-phase or phase-to-earth faults will increase. High temperaturewill degrade the quality of the transformer/generator oil.

    The thermal overload protection estimatesthe internal heat content of the transformer/generator (temperature) continuously. Thisestimation is made by using a thermal modelof the transformer/generator with two timeconstants, which is based on currentmeasurement.

    Two warning levels are available. Thisenables actions in the power system to bedone before dangerous temperatures arereached. If the temperature continues toincrease to the trip value, the protectioninitiates trip of the protected transformer/generator.

    Breaker failure protection CCRBRF

    Breaker failure protection (CCRBRF) ensuresfast back-up tripping of surrounding breakersin case of own breaker failure to open.CCRBRF can be current based, contact based,or adaptive combination between these twoprinciples.

    A current check with extremely short resettime is used as check criteria to achieve ahigh security against unnecessary operation.

    A contact check criteria can be used wherethe fault current through the breaker is small.

    CCRBRF can be single- or three-phaseinitiated to allow use with single phasetripping applications. For the three-phaseversion of CCRBRF the current criteria can beset to operate only if two out of four forexample, two phases or one phase plus theresidual current start. This gives a highersecurity to the back-up trip command.

    CCRBRF function can be programmed to givea single- or three-phase re-trip of the ownbreaker to avoid unnecessary tripping ofsurrounding breakers at an incorrectinitiation due to mistakes during testing.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    16 ABB

  • Pole discordance protection CCRPLD

    Single pole operated circuit breakers can dueto electrical or mechanical failures end upwith the different poles in different positions(close-open). This can cause negative andzero sequence currents which gives thermalstress on rotating machines and can causeunwanted operation of zero sequence ornegative sequence current functions.

    Normally the own breaker is tripped tocorrect such a situation. If the situationpersists the surrounding breaker should betripped to clear the unsymmetrical loadsituation.

    The Polediscordance protection functionCCRPLD operates based on information fromauxiliary contacts of the circuit breaker forthe three phases with additional criteria fromunsymmetrical phase current when required.

    Directional over/underpower protectionGOPPDOP/GUPPDUP

    The directional over-/under-power protection(GOPPDOP/GUPPDUP) can be usedwherever a high/low active, reactive orapparent power protection or alarming isrequired. The functions can alternatively beused to check the direction of active orreactive power flow in the power system.There are number of applications where suchfunctionality is needed. Some of them are:

    • detection of reversed active power flow• detection of high reactive power flow

    Each function has two steps with definitetime delay. Reset times for every step can beset as well.

    Broken conductor check BRCPTOC

    The main purpose of the function Brokenconductor check (BRCPTOC) is the detectionof broken conductors on protected powerlines and cables (series faults). Detection canbe used to give alarm only or trip the linebreaker.

    Voltage protection

    Two step undervoltage protectionUV2PTUV

    Undervoltages can occur in the power systemduring faults or abnormal conditions. Twostep undervoltage protection (UV2PTUV)function can be used to open circuit breakersto prepare for system restoration at poweroutages or as long-time delayed back-up toprimary protection.

    UV2PTUV has two voltage steps, each withinverse or definite time delay.

    Two step overvoltage protection OV2PTOV

    Overvoltages may occur in the power systemduring abnormal conditions, such as, suddenpower loss, tap changer regulating failures,open line ends on long lines.

    Two step overvoltage protection OV2PTOVcan be used as open line end detector,normally then combined with directionalreactive over-power function or as systemvoltage supervision, normally then givingalarm only or switching in reactors or switchout capacitor banks to control the voltage.

    OV2PTOV has two voltage steps, each ofthem with inverse or definite time delayed.

    OV2PTOV has an extremely high reset ratioto allow setting close to system service voltage.

    Two step residual overvoltage protectionROV2PTOV

    Residual voltages may occur in the powersystem during earth faults.

    Two step residual overvoltage protectionROV2PTOV calculates the residual voltagefrom the three-phase voltage inputtransformers or from a single-phase voltageinput transformer fed from an open delta orneutral point voltage transformer.

    ROV2PTOV has two voltage steps, each withinverse or definite time delayed.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 17

  • Overexcitation protection OEXPVPH

    When the laminated core of a powertransformer or generator is subjected to amagnetic flux density beyond its designlimits, stray flux will flow into non-laminatedcomponents not designed to carry flux andcause eddy currents to flow. The eddycurrents can cause excessive heating andsevere damage to insulation and adjacentparts in a relatively short time. Overexcitationprotection OEXPVPH has settable inverseoperating curve and independent alarm stage.

    Voltage differential protection VDCPTOV

    A voltage differential monitoring function isavailable. It compares the voltages from twothree phase sets of voltage transformers andhas one sensitive alarm step and one tripstep. It can be used to supervise the voltagefrom two fuse groups or two different voltagetransformers fuses as a fuse/MCB supervisionfunction.

    Frequency protection

    Underfrequency protection SAPTUF

    Underfrequency occurs as a result of lack ofgeneration in the network.

    Underfrequency protection SAPTUF is usedfor load shedding systems, remedial actionschemes, gas turbine startup and so on.

    SAPTUF is provided with an under voltageblocking.

    The operation may be based on single-phase,phase-to-phase or positive-sequence voltagemeasurement.

    Overfrequency protection SAPTOF

    Overfrequency protection function SAPTOF isapplicable in all situations, where reliabledetection of high fundamental power systemfrequency is needed.

    Overfrequency occurs at sudden load dropsor shunt faults in the power network. Closeto the generating plant, generator governorproblems can also cause over frequency.

    SAPTOF is used mainly for generationshedding and remedial action schemes. It isalso used as a frequency stage initiating loadrestoring.

    SAPTOF is provided with an undervoltageblocking. The operation is based on single-phase, phase-to-phase or positive-sequencevoltage measurement.

    Rate-of-change frequency protectionSAPFRC

    Rate-of-change frequency protection function(SAPFRC) gives an early indication of a maindisturbance in the system. SAPFRC can beused for generation shedding, load shedding,remedial action schemes. SAPFRC candiscriminate between positive or negativechange of frequency.

    SAPFRC is provided with an undervoltageblocking. The operation may be based onsingle-phase, phase-to-phase or positive-sequence voltage measurement.

    Multipurpose protection

    General current and voltage protectionCVGAPC

    The protection module is recommended as ageneral backup protection with manypossible application areas due to its flexiblemeasuring and setting facilities.

    The built-in overcurrent protection featurehas two settable current levels. Both of themcan be used either with definite time orinverse time characteristic. The overcurrentprotection steps can be made directional withselectable voltage polarizing quantity.Additionally they can be voltage and/orcurrent controlled/restrained. 2nd harmonicrestraining facility is available as well. At toolow polarizing voltage the overcurrent featurecan be either blocked, made non directionalor ordered to use voltage memory inaccordance with a parameter setting.

    Additionally two overvoltage and twoundervoltage steps, either with definite timeor inverse time characteristic, are availablewithin each function.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    18 ABB

  • The general function suits applications withunderimpedance and voltage controlledovercurrent solutions. The general functioncan also be utilized for generator transformerprotection applications where positive,negative or zero sequence components ofcurrent and voltage quantities are typicallyrequired.

    Secondary system supervision

    Current circuit supervision CCSRDIF

    Open or short circuited current transformercores can cause unwanted operation of manyprotection functions such as differential,earth-fault current and negative-sequencecurrent functions.

    It must be remembered that a blocking ofprotection functions at an occurrence of openCT circuit will mean that the situation willremain and extremely high voltages willstress the secondary circuit.

    Current circuit supervision (CCSRDIF)compares the residual current from a threephase set of current transformer cores withthe neutral point current on a separate inputtaken from another set of cores on thecurrent transformer.

    A detection of a difference indicates a fault inthe circuit and is used as alarm or to blockprotection functions expected to giveunwanted tripping.

    Fuse failure supervision (RFUF)

    Failures in the secondary circuits of thevoltage transformer can cause unwantedoperation of distance protection,undervoltage protection, neutral point voltageprotection, energizing function (synchronismcheck) etc. The fuse failure supervisionfunction prevents such unwanted operations.

    There are three methods to detect fuse failures.

    The method based on detection of zerosequence voltage without any zero sequencecurrent. This is a useful principle in a directlyearthed system and can detect one or twophase fuse failures.

    The method based on detection of negativesequence voltage without any negativesequence current. This is a useful principle ina non-directly earthed system and can detectone or two phase fuse failures.

    The method based on detection of du/dt-di/dt where a change of the voltage is comparedto a change in the current. Only voltagechanges means a voltage transformer fault.This principle can detect one, two or threephase fuse failures.

    Control

    Synchronizing, synchrocheck andenergizing check SESRSYN

    The Synchronizing function allows closing ofasynchronous networks at the correctmoment including the breaker closing time.The systems can thus be reconnected after anautoreclose or manual closing, whichimproves the network stability.

    Synchrocheck, energizing check (SESRSYN)function checks that the voltages on bothsides of the circuit breaker are insynchronism, or with at least one side deadto ensure that closing can be done safely.

    SESRSYN function includes a built-in voltageselection scheme for double bus and 1½breaker or ring busbar arrangements.

    Manual closing as well as automatic reclosingcan be checked by the function and can havedifferent settings.

    For systems which are running asynchronousa synchronizing function is provided. Themain purpose of the synchronizing functionis to provide controlled closing of circuitbreakers when two asynchronous systems aregoing to be connected. It is used for slipfrequencies that are larger than those forsynchrocheck and lower than a set maximumlevel for the synchronizing function.

    Apparatus control APC

    The apparatus control is a function forcontrol and supervision of circuit breakers,disconnectors and earthing switches within abay. Permission to operate is given after

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 19

  • evaluation of conditions from other functionssuch as interlocking, synchrocheck, operatorplace selection and external or internalblockings.

    Features in the apparatus control function:

    • Select-Execute principle to give highreliability

    • Selection function to prevent simultaneousoperation

    • Selection and supervision of operator place• Command supervision• Block/deblock of operation• Block/deblock of updating of position

    indications• Substitution of position indications• Overriding of interlocking functions• Overriding of synchrocheck• Operation counter• Suppression of Mid position

    Two types of command models can be used:

    • Direct with normal security• SBO (Select-Before-Operate) with enhanced

    security

    Normal security means that only thecommand is evaluated and the resultingposition is not supervised. Enhanced securitymeans that the command is evaluated with anadditional supervision of the status value ofthe control object. The command securitywith enhanced security is always terminatedby a CommandTermination service primitive.

    Control operation can be performed from thelocal HMI under authority control if so defined.

    Voltage control TR1ATCC, TR8ATCC,TCMYLTC and TCLYLTC

    The voltage control functions, Automaticvoltage control for tap changer, single control(TR1ATCC,), Automatic voltage control fortap changer, parallel control (TR8ATCC,) andTap changer control and supervision, 6binary inputs (TCMYLTC,) as well as Tapchanger control and supervision, 32 binaryinputs TCLYLTC are used for control ofpower transformers with a motor driven loadtap changer. The function provides automatic

    regulation of the voltage on the secondaryside of transformers or alternatively on a loadpoint further out in the network.

    Control of a single transformer, as well ascontrol of up to eight transformers in parallelis possible. For parallel control of powertransformers, three alternative methods areavailable, the master-follower method, thecirculating current method and the reversereactance method. The two former methodsrequire exchange of information between theparallel transformers and this is provided forwithin IEC61850-8-1.

    Voltage control includes many extra featuressuch as possibility of to avoid simultaneoustapping of parallel transformers, hot stand byregulation of a transformer in a group whichregulates it to a correct tap position eventhough the LV CB is open, compensation fora possible capacitor bank on the LV side bayof a transformer, extensive tap changermonitoring including contact wear andhunting detection, monitoring of the powerflow in the transformer so that for example,the voltage control can be blocked if thepower reverses etc.

    Logic rotating switch for functionselection and LHMI presentation SLGGIO

    The logic rotating switch for functionselection and LHMI presentation function(SLGGIO) (or the selector switch functionblock) is used to get a selector switchfunctionality similar with the one provided bya hardware selector switch. Hardwareselector switches are used extensively byutilities, in order to have different functionsoperating on pre-set values. Hardwareswitches are however sources formaintenance issues, lower system reliabilityand extended purchase portfolio. The virtualselector switches eliminate all these problems.

    Selector mini switch VSGGIO

    Selector mini switch (VSGGIO) functionblock is a multipurpose function used in theconfiguration tool in PCM600 for a variety ofapplications, as a general purpose switch.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    20 ABB

  • VSGGIO can be controlled from the menu orfrom a symbol on the single line diagram(SLD) on the local HMI.

    Single point generic control 8 signalsSPC8GGIO

    The Single point generic control 8 signals(SPC8GGIO) function block is a collection of8 single point commands, designed to bringin commands from REMOTE (SCADA) tothose parts of the logic configuration that donot need complicated function blocks thathave the capability to receive commands (forexample, SCSWI). In this way, simplecommands can be sent directly to the IEDoutputs, without confirmation. Confirmation(status) of the result of the commands issupposed to be achieved by other means,such as binary inputs and SPGGIO functionblocks.

    Scheme communication

    Scheme communication logic for residualovercurrent protection ECPSCH

    To achieve fast fault clearance of earth faultson the part of the line not covered by theinstantaneous step of the residual overcurrentprotection, the directional residualovercurrent protection can be supported witha logic that uses communication channels.

    In the directional scheme, information of thefault current direction must be transmitted tothe other line end. With directionalcomparison, a short operates time of theprotection including a channel transmissiontime, can be achieved. This short operatetime enables rapid autoreclosing functionafter the fault clearance.

    The communication logic module fordirectional residual current protectionenables blocking as well as permissive under/overreaching schemes. The logic can also besupported by additional logic for weak-endinfeed and current reversal, included inCurrent reversal and weak-end infeed logicfor residual overcurrent protection Currentreversal and weak-end infeed logic for

    residual overcurrent protection (ECRWPSCH)function.

    Current reversal and weak-end infeed logicfor residual overcurrent protectionECRWPSCH

    The Current reversal and weak-end infeedlogic for residual overcurrent protectionECRWPSCH is a supplement to Schemecommunication logic for residual overcurrentprotection ECPSCH.

    To achieve fast fault clearing for all earthfaults on the line, the directional earth-faultprotection function can be supported withlogic that uses communication channels.

    The 670 series IEDs have for this reasonavailable additions to scheme communicationlogic.

    If parallel lines are connected to commonbusbars at both terminals, overreachingpermissive communication schemes can tripunselectively due to fault current reversal.This unwanted tripping affects the healthyline when a fault is cleared on the other line.This lack of security can result in a total lossof interconnection between the two buses. Toavoid this type of disturbance, a fault currentreversal logic (transient blocking logic) canbe used.

    Permissive communication schemes forresidual overcurrent protection, can basicallyoperate only when the protection in theremote terminal can detect the fault. Thedetection requires a sufficient minimumresidual fault current, out from this terminal.The fault current can be too low due to anopened breaker or high positive and/or zerosequence source impedance behind thisterminal. To overcome these conditions,weak end infeed (WEI) echo logic is used.

    Logic

    Tripping logic SMPPTRC

    A function block for protection tripping isprovided for each circuit breaker involved inthe tripping of the fault. It provides the pulseprolongation to ensure a trip pulse of

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 21

  • sufficient length, as well as all functionalitynecessary for correct co-operation withautoreclosing functions.

    The trip function block includes functionalityfor evolving faults and breaker lock-out.

    Trip matrix logic TMAGGIO

    Trip matrix logic (TMAGGIO) function isused to route trip signals and/or other logicaloutput signals to different output contacts onthe IED.

    TMAGGIO output signals and the physicaloutputs are available in PCM600 and thisallows the user to adapt the signals to thephysical tripping outputs according to thespecific application needs.

    Configurable logic blocks

    A number of logic blocks and timers areavailable for user to adapt the configurationto the specific application needs.

    • OR function block.

    • INVERTER function blocks that inverts theinput signal.

    • PULSETIMER function block can be used,for example, for pulse extensions orlimiting of operation of outputs.

    • GATE function block is used for controllingif a signal should be able to pass from theinput to the output or not depending on asetting.

    • XOR function block.

    • LOOPDELAY function block used to delaythe output signal one execution cycle.

    • TIMERSET function has pick-up and drop-out delayed outputs related to the inputsignal. The timer has a settable time delay.

    • AND function block.

    • SRMEMORY function block is a flip-flopthat can set or reset an output from twoinputs respectively. Each block has two

    outputs where one is inverted. The memorysetting controls if the block after a powerinterruption should return to the statebefore the interruption, or be reset. Setinput has priority.

    • RSMEMORY function block is a flip-flopthat can reset or set an output from twoinputs respectively. Each block has twooutputs where one is inverted. The memorysetting controls if the block after a powerinterruption should return to the statebefore the interruption, or be reset. Resetinput has priority.

    Fixed signal function block

    The Fixed signals function (FXDSIGN)generates a number of pre-set (fixed) signalsthat can be used in the configuration of anIED, either for forcing the unused inputs inother function blocks to a certain level/value,or for creating a certain logic.

    Monitoring

    Measurements

    The service value function is used to get on-line information from the IED. These servicevalues makes it possible to display on-lineinformation on the local HMI and on theSubstation automation system about:

    • measured voltages, currents, frequency,active, reactive and apparent power andpower factor

    • the primary and secondary phasors• differential currents, bias currents• positive, negative and zero sequence

    currents and voltages• mA, input currents• pulse counters• event counters• measured values and other information

    of the different parameters for includedfunctions

    • logical values of all binary in- andoutputs and

    • general IED information.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    22 ABB

  • Supervision of mA input signals (MVGGIO)

    The main purpose of the function is tomeasure and process signals from differentmeasuring transducers. Many devices used inprocess control represent various parameterssuch as frequency, temperature and DCbattery voltage as low current values, usuallyin the range 4-20 mA or 0-20 mA.

    Alarm limits can be set and used as triggers,e.g. to generate trip or alarm signals.

    The function requires that the IED isequipped with the mA input module.

    Event counter CNTGGIO

    Event counter (CNTGGIO) has six counterswhich are used for storing the number oftimes each counter input has been activated.

    Disturbance report DRPRDRE

    Complete and reliable information aboutdisturbances in the primary and/or in thesecondary system together with continuousevent-logging is accomplished by thedisturbance report functionality.

    Disturbance report DRPRDRE, alwaysincluded in the IED, acquires sampled data ofall selected analog input and binary signalsconnected to the function block that is,maximum 40 analog and 96 binary signals.

    Disturbance report functionality is a commonname for several functions:

    • Event list• Indications• Event recorder• Trip value recorder• Disturbance recorder

    Disturbance report function is characterizedby great flexibility regarding configuration,starting conditions, recording times and largestorage capacity.

    A disturbance is defined as an activation ofan input in the AxRADR or BxRBDR functionblocks, which is set to trigger the disturbancerecorder. All signals from start of pre-fault

    time to the end of post-fault time will beincluded in the recording.

    Every disturbance report recording is savedin the IED in the standard Comtrade format.The same applies to all events, which arecontinuously saved in a ring-buffer. The localHMI is used to get information about therecordings, but the disturbance report filesmay be uploaded to PCM600 and furtheranalysis using the disturbance handling tool.

    Event list DRPRDRE

    Continuous event-logging is useful formonitoring of the system from an overviewperspective and is a complement to specificdisturbance recorder functions.

    The event list logs all binary input signalsconnected to the Disturbance report function.The list may contain of up to 1000 time-tagged events stored in a ring-buffer.

    Indications DRPRDRE

    To get fast, condensed and reliableinformation about disturbances in theprimary and/or in the secondary system it isimportant to know, for example binarysignals that have changed status during adisturbance. This information is used in theshort perspective to get information via thelocal HMI in a straightforward way.

    There are three LEDs on the local HMI(green, yellow and red), which will displaystatus information about the IED and theDisturbance report function (trigged).

    The Indication list function shows all selectedbinary input signals connected to theDisturbance report function that havechanged status during a disturbance.

    Event recorder DRPRDRE

    Quick, complete and reliable informationabout disturbances in the primary and/or inthe secondary system is vital, for example,time tagged events logged duringdisturbances. This information is used fordifferent purposes in the short term (forexample corrective actions) and in the longterm (for example Functional Analysis).

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 23

  • The event recorder logs all selected binaryinput signals connected to the Disturbancereport function. Each recording can containup to 150 time-tagged events.

    The event recorder information is availablefor the disturbances locally in the IED.

    The event recording information is anintegrated part of the disturbance record(Comtrade file).

    Trip value recorder DRPRDRE

    Information about the pre-fault and faultvalues for currents and voltages are vital forthe disturbance evaluation.

    The Trip value recorder calculates the valuesof all selected analog input signals connectedto the Disturbance report function. The resultis magnitude and phase angle before andduring the fault for each analog input signal.

    The trip value recorder information isavailable for the disturbances locally in theIED.

    The trip value recorder information is anintegrated part of the disturbance record(Comtrade file).

    Disturbance recorder DRPRDRE

    The Disturbance recorder function suppliesfast, complete and reliable information aboutdisturbances in the power system. Itfacilitates understanding system behavior andrelated primary and secondary equipmentduring and after a disturbance. Recordedinformation is used for different purposes inthe short perspective (for example correctiveactions) and long perspective (for exampleFunctional Analysis).

    The Disturbance recorder acquires sampleddata from all selected analog input andbinary signals connected to the Disturbancereport function (maximum 40 analog and 96binary signals). The binary signals are thesame signals as available under the eventrecorder function.

    The function is characterized by greatflexibility and is not dependent on the

    operation of protection functions. It canrecord disturbances not detected byprotection functions.

    The disturbance recorder information for thelast 100 disturbances are saved in the IEDand the local HMI is used to view the list ofrecordings.

    Event function

    When using a Substation Automation systemwith LON or SPA communication, time-tagged events can be sent at change orcyclically from the IED to the station level.These events are created from any availablesignal in the IED that is connected to theEvent function (EVENT). The event functionblock is used for LON and SPAcommunication.

    Analog and double indication values are alsotransferred through EVENT function.

    Measured value expander block RANGE_XP

    The current and voltage measurementsfunctions (CVMMXU, CMMXU, VMMXU andVNMMXU), current and voltage sequencemeasurement functions (CMSQI and VMSQI)and IEC 61850 generic communication I/Ofunctions (MVGGIO) are provided withmeasurement supervision functionality. Allmeasured values can be supervised with foursettable limits that is low-low limit, low limit,high limit and high-high limit. The measurevalue expander block (RANGE_XP) has beenintroduced to be able to translate the integeroutput signal from the measuring functions to5 binary signals that is below low-low limit,below low limit, normal, above high-highlimit or above high limit. The output signalscan be used as conditions in the configurablelogic.

    Metering

    Pulse counter logic PCGGIO

    Pulse counter (PCGGIO) function countsexternally generated binary pulses, forinstance pulses coming from an externalenergy meter, for calculation of energyconsumption values. The pulses are captured

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    24 ABB

  • by the binary input module and then read bythe pulse counter function. A scaled servicevalue is available over the station bus. Thespecial Binary input module with enhancedpulse counting capabilities must be orderedto achieve this functionality.

    Function for energy calculation anddemand handling ETPMMTR

    Outputs from Measurements (CVMMXU)function can be used to calculate energy.Active as well as reactive values arecalculated in import and export direction.Values can be read or generated as pulses.Maximum demand power values are alsocalculated by the function.

    Basic IED functions

    Time synchronization

    Use the time synchronization source selectorto select a common source of absolute timefor the IED when it is a part of a protectionsystem. This makes comparison of events anddisturbance data between all IEDs in a stationautomation system possible.

    Human machine interface

    The local HMI is divided into zones withdifferent functionality.

    • Status indication LEDs.• Alarm indication LEDs, which consist of

    15 LEDs (6 red and 9 yellow) with userprintable label. All LEDs are configurablefrom PCM600.

    • Liquid crystal display (LCD).• Keypad with push buttons for control

    and navigation purposes, switch forselection between local and remotecontrol and reset.

    • Isolated RJ45 communication port.

    IEC05000056-LITEN V1 EN

    Figure 7. Medium graphic HMI, 15controllable objects

    Station communication

    Overview

    Each IED is provided with a communicationinterface, enabling it to connect to one ormany substation level systems or equipment,either on the Substation Automation (SA) busor Substation Monitoring (SM) bus.

    Following communication protocols areavailable:

    • IEC 61850-8-1 communication protocol• LON communication protocol• SPA or IEC 60870-5-103 communication

    protocol• DNP3.0 communication protocol

    Theoretically, several protocols can becombined in the same IED.

    IEC 61850-8-1 communication protocol

    The IED is equipped with single or doubleoptical Ethernet rear ports (order dependent)for the new substation communicationstandard IEC 61850-8-1 for the station bus.IEC 61850-8-1 communication is also possiblefrom the optical Ethernet front port. IEC

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 25

  • 61850-8-1 protocol allows intelligent devices(IEDs) from different vendors to exchangeinformation and simplifies systemengineering. Peer-to-peer communicationaccording to GOOSE is part of the standard.Disturbance files uploading is provided.

    Serial communication, LON

    Existing stations with ABB station bus LONcan be extended with use of the optical LONinterface. This allows full SA functionalityincluding peer-to-peer messaging andcooperation between existing ABB IED's andthe new IED 670.

    SPA communication protocol

    A single glass or plastic port is provided forthe ABB SPA protocol. This allows extensionsof simple substation automation systems butthe main use is for Substation MonitoringSystems SMS.

    IEC 60870-5-103 communication protocol

    A single glass or plastic port is provided forthe IEC60870-5-103 standard. This allowsdesign of simple substation automationsystems including equipment from differentvendors. Disturbance files uploading isprovided.

    DNP3.0 communication protocol

    An electrical RS485 and an optical Ethernetport is available for the DNP3.0communication. DNP3.0 Level 2communication with unsolicited events, timesynchronizing and disturbance reporting isprovided for communication to RTUs,Gateways or HMI systems.

    Single command, 16 signals

    The IEDs can receive commands either froma substation automation system or from thelocal HMI. The command function block hasoutputs that can be used, for example, tocontrol high voltage apparatuses or for otheruser defined functionality.

    Multiple command and transmit

    When 670 IED's are used in SubstationAutomation systems with LON, SPA orIEC60870-5-103 communication protocols theEvent and Multiple Command function blocksare used as the communication interface forvertical communication to station HMI andgateway and as interface for horizontal peer-to-peer communication (over LON only).

    Remote communication

    Analog and binary signal transfer toremote end

    Three analog and eight binary signals can beexchanged between two IEDs. Thisfunctionality is mainly used for the linedifferential protection. However it can beused in other products as well. An IED cancommunicate with up to 4 remote IEDs.

    Binary signal transfer to remote end, 192signals

    If the communication channel is used fortransfer of binary signals only, up to 192binary signals can be exchanged betweentwo IEDs. For example, this functionality canbe used to send information such as status ofprimary switchgear apparatus or intertrippingsignals to the remote IED. An IED cancommunicate with up to 4 remote IEDs.

    Line data communication module, shortand medium range LDCM

    The line data communication module (LDCM)is used for communication between the IEDssituated at distances

  • kbit/s resp 2Mbit/s operation. The converteris delivered with 19” rack mountingaccessories.

    5. Hardware description

    Hardware modules

    Power supply module PSM

    The power supply module is used to providethe correct internal voltages and full isolationbetween the terminal and the battery system.An internal fail alarm output is available.

    Binary input module BIM

    The binary input module has 16 opticallyisolated inputs and is available in twoversions, one standard and one withenhanced pulse counting capabilities on theinputs to be used with the pulse counterfunction. The binary inputs are freelyprogrammable and can be used for the inputof logical signals to any of the functions.They can also be included in the disturbancerecording and event-recording functions. Thisenables extensive monitoring and evaluationof operation of the IED and for all associatedelectrical circuits.

    Binary output module BOM

    The binary output module has 24independent output relays and is used fortrip output or any signaling purpose.

    Static binary output module SOM

    The static binary output module has six faststatic outputs and six change over outputrelays for use in applications with high speedrequirements.

    Binary input/output module (IOM)

    The binary input/output module is usedwhen only a few input and output channelsare needed. The ten standard output channelsare used for trip output or any signallingpurpose. The two high speed signal output

    channels are used for applications whereshort operating time is essential. Eightoptically isolated binary inputs cater forrequired binary input information.

    mA input module MIM

    The milli-ampere input module is used tointerface transducer signals in the –20 to +20mA range from for example OLTC position,temperature or pressure transducers. Themodule has six independent, galvanicallyseparated channels.

    Optical ethernet module OEM

    The optical fast-ethernet module is used toconnect an IED to the communication buses(like the station bus) that use the IEC61850-8-1 protocol (port A, B). The modulehas one or two optical ports with STconnectors.

    Serial SPA/IEC 60870-5-103 and LONcommunication module SLM

    The optical serial channel and LON channelmodule is used to connect an IED to thecommunication that use SPA, LON, orIEC60870–5–103. The module has two opticalports for plastic/plastic, plastic/glass, or glass/glass. One port is used for SPA and IEC60870-5-103 one port is used for LON.

    Line data communication module LDCM

    Each module has one optical port, one foreach remote end to which the IEDcommunicates.

    Alternative cards for Medium range (1310 nmsingle mode) and Short range (850 nm multimode) are available.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 27

  • Galvanic RS485 serial communicationmodule

    The galvanic RS485 serial communicationmodule is used as an alternative for DNP3.0communication.

    GPS time synchronization module GSM

    This module includes the GPS receiver usedfor time synchronization. The GPS has oneSMA contact for connection to an antenna.

    IRIG-B Time synchronizing module

    The IRIG-B time synchronizing module isused for accurate time synchronizing of theIED from a station clock.

    Electrical (BNC) and optical connection (ST)for 0XX and 12X IRIG-B support.

    Transformer input module TRM

    The transformer input module is used togalvanically separate and transform the

    secondary currents and voltages generated bythe measuring transformers. The module hastwelve inputs in different combinations ofcurrents and voltage inputs.

    Alternative connectors of Ring lug orCompression type can be ordered.

    High impedance resistor unit

    The high impedance resistor unit, withresistors for pick-up value setting and avoltage dependent resistor, is available in asingle phase unit and a three phase unit.Both are mounted on a 1/1 19 inch apparatusplate with compression type termnals.

    Layout and dimensions

    Dimensions

    xx05000003.vsd

    CB

    E

    F

    A

    D

    IEC05000003 V1 EN

    Figure 8. 1/2 x 19” case with rear cover

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    28 ABB

  • xx05000004.vsd

    IEC05000004 V1 EN

    Figure 9. Side-by-side mounting

    Case size A B C D E F

    6U, 1/2 x 19” 265.9 223.7 201.1 242.1 252.9 205.7

    6U, 3/4 x 19” 265.9 336.0 201.1 242.1 252.9 318.0

    6U, 1/1 x 19” 265.9 448.1 201.1 242.1 252.9 430.3

    (mm)

    Mounting alternatives

    Following mounting alternatives (IP40protection from the front) are available:

    • 19” rack mounting kit• Flush mounting kit with cut-out

    dimensions:

    ▪ 1/2 case size (h) 254.3 mm (w) 210.1mm

    ▪ 3/4 case size (h) 254.3 mm (w) 322.4mm

    ▪ 1/1 case size (h) 254.3 mm (w) 434.7mm

    • Wall mounting kit

    See ordering for details about availablemounting alternatives.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 29

  • 6. Connection diagrams

    Table 1. Designations for 1/2 x 19” casing with 1 TRM slot

    IEC08000471 BG V1 EN

    Module Rear Positions

    PSM X11

    BIM, BOM, SOM or IOM X31 and X32 etc. to X51and X52

    BIM, BOM, SOM, IOM orGSM

    X51, X52

    SLM X301:A, B, C, D

    IRIG-B 1) X302

    OEM X311:A, B, C, D

    RS485 or LDCM 2) 3) X312

    LDCM 2) X313

    TRM X401

    1) IRIG-B installation, when included in seat P30:22) LDCM installation sequence: P31:2 or P31:33) RS485 installation, when included in seat P31:2Note!1 One LDCM can be included depending of availabilityof IRIG-B respective RS485 modules.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    30 ABB

  • Table 2. Designations for 3/4 x 19” casing with 2 TRM slot

    IEC08000473 BG V1 EN

    Module Rear Positions

    PSM X11

    BIM, BOM, SOM, IOM orMIM

    X31 and X32 etc. to X71 andX72

    BIM, BOM, SOM, IOM,MIM or GSM

    X71, X72

    SLM X301:A, B, C, D

    IRIG-B or LDCM 1,2) X302

    LDCM 2) X303

    OEM 4) X311:A, B, C, D

    RS485 or LDCM 2) 3) X312

    LDCM 2) X313

    LDCM 2) X322

    LDCM 2) X323

    TRM 1 X401

    TRM 2 X411

    1) IRIG-B installation, when included in seat P30:22) LDCM installation sequence: P31:2, P31:3, P32:2, P32:3,P30:2 and P30:33) RS485 installation, when included in seat P31:2, P31:3,P32:2 or P32:34) OEM X311:A, B (IEC 61850-8-1). (X311:C, D IEC61850-8-1)Note!2-4 LDCM can be included depending of availability of IRIG-B respective RS485 modules.When IRIG-B, RS485 and 4 pc of LDCM are in use, needsa second ADM.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 31

  • Table 3. Designations for 1/1 x 19” casing with 2 TRM slots

    IEC08000475 BG V1 EN

    Module Rear Positions

    PSM X11

    BIM, BOM, SOM,IOM or MIM

    X31 and X32 etc. to X131and X132

    BIM, BOM, SOM,IOM, MIM orGSM

    X131, X132

    SLM X301:A, B, C, D

    IRIG-B or LDCM1,2)

    X302

    LDCM 2) X303

    OEM 4) X311:A, B, C, D

    RS485 or LDCM2) 3)

    X312

    LDCM 2) X313

    LDCM 2) X322

    LDCM 2) X323

    TRM 1 X401

    TRM 2 X411

    1) IRIG-B installation, when included in seatP30:22) LDCM installation sequence: P31:2, P31:3,P32:2, P32:3, P30:2 and P30:33) RS485 installation, when included in seatP31:2, P31:3, P32:2 or P32:44) OEM X311:A, B (IEC 61850-8-1). OEMX311:C, DNote!2-4 LDCM can be included depending ofavailability of IRIG-B respective RS485 modules.When IRIG-B, RS485 and 4 pc of LDCM are inuse, needs a second ADM.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    32 ABB

  • IEC08000479 BG V1 EN

    Figure 10. Transformer input module (TRM)

    ■ Indicates high polarity

    CT/VT-input designation according to figure 10

    Curr

    ent/

    volt

    age

    confi

    gura

    tion

    (50/

    60 H

    z)

    AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12

    12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A

    12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A

    9I+3U,1A

    1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V

    9I+3U,5A

    5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V

    5I, 1A+4I, 5A+3U

    1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V

    7I+5U,1A

    1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V

    7I+5U,5A

    5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V

    6I+6U,1A

    1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V

    6I+6U,5A

    5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V

    6I, 1A 1A 1A 1A 1A 1A 1A - - - - - -

    6I, 5A 5A 5A 5A 5A 5A 5A - - - - - -

    Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-processing function blocks.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 33

  • IEC08000480 BG V1 EN

    Figure 11. Binary input module (BIM). Inputcontacts named XA corresponds torear position X31, X41, and so on,and input contacts named XB torear position X32, X42, and so on.

    IEC08000484 BG V1 EN

    Figure 12. mA input module (MIM)

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    34 ABB

  • IEC08000477 BG V1 EN

    Figure 13. Communication interfaces (OEM, LDCM, SLM and HMI)

    Note to figure 13

    1) Rear communication port SPA/IEC 61850-5-103, ST-connector for glass alt. HFBR Snap-in connector forplastic as ordered

    2) Rear communication port LON, ST connector for glass alt. HFBR Snap-in connector for plastic as ordered

    3) Rear communication port RS485, terminal block

    4) Time synchronization port IRIG-B, BNC-connector

    5) Time synchronization port PPS or Optical IRIG-B, ST-connector

    6) Rear communication port IEC 61850-8-1 for X311:A, B, ST-connector

    7) Rear communication port C37.94, ST-connector

    8) Front communication port Ethernet, RJ45 connector

    9) Rear communication port 15-pole female micro D-sub, 1.27 mm (0.050") pitch

    10) Rear communication port, terminal block

    IEC08000476 BG V1 EN

    Figure 14. Power supply module (PSM)

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 35

  • IEC08000478 BG V1 EN

    Figure 15. GPS time synchronization module (GSM)

    IEC08000481 BG V1 EN

    Figure 16. Binary output module (BOM). Output contacts named XA corresponds to rearposition X31, X41, and so on, and output contacts named XB to rear positionX32, X42, and so on.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    36 ABB

  • IEC08000482 BG V1 EN

    Figure 17. Static output module (SOM)

    IEC08000483 BG V1 EN

    Figure 18. Binary in/out module (IOM). Input contacts named XA corresponds to rear positionX31, X41, and so on, and output contacts named XB to rear position X32, X42,and so on.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 37

  • CC

    TCTC

    P1

    -QB1-QB2

    -QA1

    -BI1

    QB1-OPENQB1-CL

    QB2-OPENQB2-CL

    QA1-OPENQA1-CL

    QA1-SPR UNCH

    CLOSE QA1

    TRIP QA1

    MAIN 2 TRIP

    BUS ABUS B

    QA1-OPENQA1-CL

    BBP-TRIP

    ST BFP 3PH

    BUCH TRIP

    SUDDEN P

    MAN SC OK

    FAU

    LTSI

    GN

    ALLI

    NG

    TO MAIN 2 RELAY

    TO BUS PROT

    MCB ORFUSE

    MCB-OK

    - +IRF

    WT WARN

    HV BUSBAR TRIP

    TRIP Reinf

    CLOSE Reinf

    TRM1:1-3

    TRM1:11-12

    TRM1:7

    TRM1:8

    CC

    TCTC

    -QA1SPR UNCH

    TRM1:4-6

    TO BUS PROT

    TO MAIN 2 RELAY

    MCB OK

    TRM1:10

    OT TRIP

    WT TRIP

    OT WARN

    OIL LOW

    GAS ALARM

    TC RAISETC LOWER

    TC IN LOC.

    TC IN MAN

    TC IN AUTO

    MV BUSBAR TRIP

    = TAP POS

    CLOSE QA1

    TRIP QA1

    TRIP Reinf

    CLOSE Reinf

    MIM1:1

    QW

    QO-T1

    -BU1

    -BI1

    -BU1

    P1

    -N.BI1

    -N.BI1

    BLOCK LW 3I>BBP STEP

    en05000262.vsd

    IEC05000262 V1 EN

    Figure 19. Typical connection diagram for two winding transformer in a single breakerarrangement. Note! Including IO for control option.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    38 ABB

  • CC

    TCTC

    P1

    -QB1

    -QB62

    -QA1

    -BI1

    QB1-OPENQB1-CL

    QB6-OPENQB6-CL

    =1-QA1-OPEN

    =1-QA1-CL

    =1-QA1-SPR UNCH

    CLOSE QA1

    TRIP QA1

    MAIN 2 TRIP

    BUS A

    QA1-OPENQA1-CL

    BBP-TRIP

    ST BFP 3PH

    BUCH TRIP

    SUDDEN P

    MAN SC OK

    FAU

    LTSI

    GN

    ALLI

    NG

    TO MAIN 2

    TO BB PROT

    MCB ORFUSE

    MCB-OK

    - +IRF

    WT WARN

    HV BUSBAR TRIP

    TRIP Reinf

    CLOSE Reinf

    TRM1:10-12

    TRM2:4

    TRM2:5

    CC

    TCTC

    -QA1SPR UNCH

    TRM2:1-3

    TO BUS PROT

    TO MAIN 2 RELAY

    MCB OK

    TRM2:10

    OT TRIP

    WT TRIP

    OT WARN

    OIL LOW

    GAS ALARM

    TC RAISETC LOWER

    TC IN LOC.

    TC IN MAN

    TC IN AUTO

    MV BUSBAR TRIP

    CLOSE QA1

    TRIP QA1TRIP Reinf

    CLOSE Reinf

    CLOSE QA1

    TRIP QA1

    TRIP Reinf

    CLOSE Reinf

    CC

    TCTC

    -QA1

    MAIN 2 TRIP

    TRM1:1-3

    -QB6 -QB61

    TO MAIN 2

    -QB9

    TRM1:4-6P1

    QB6-OPENQB6-CL

    QB61-OPENQB61-CL

    QB9-OPENQB9-CL

    =2-Q0-OPEN=2-Q0-CL

    =2-Q0-SPR UNCH

    TRIP Reinf

    = TAP POS

    BBP-TRIP

    MIM1:1

    QW

    QO

    -BI1

    -BU1

    -BI1

    P1

    -T1

    -BU1

    BLOCK LW 3I>BBP STEP

    en05000263.vsd

    IEC05000263 V1 EN

    Figure 20. Typical connection diagram for two winding transformer in a multi breakerarrangement. Note! Including IO for control option.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 39

  • CC

    TCTC

    P1

    -QB1-QB2

    -QA1

    -BI1

    QB1-CL

    QB2-CL

    QA1-OPENQA1-CL

    QA1-SPR UNCH

    CLOSE QA1

    TRIP QA1

    MAIN 2 TRIP

    BUS ABUS B

    QA1-OPENQA1-CL

    BBP-TRIP

    ST BFP3PH

    BUCH TRIP

    SUDDEN P

    MAN SC OK

    FAU

    LTSI

    GN

    ALLI

    NG

    TO MAIN 2 RELAY

    TO BUS PROT

    MCB ORFUSE

    MCB-OK

    - +IRF

    WT WARN

    HV BUSBAR TRIP

    TRIP Reinf

    CLOSE Reinf

    TRM1:1-3

    TRM2:7-9

    TRM1:7

    TRM1:8

    CC

    TCTC

    -QA1SPR UNCH

    TRM2:1-3

    TO BUS PROT

    TO MAIN 2 RELAY

    MCB OK

    TRM1:11

    OT TRIP

    WT TRIP

    OT WARN

    OIL LOW

    GAS ALARM

    TC RAISETC LOWER

    TC IN LOC.

    TC IN MAN

    TC IN AUTO

    MV BUSBAR TRIP

    CCTCTC

    -QA1TRM2:4-6

    CLOSE QA1

    TRIP QA1TRIP Reinf

    CLOSE Reinf

    CLOSE QA1

    TRIP QA1TRIP Reinf

    CLOSE Reinf

    = TAP POSMIM1:1

    QW

    QO

    QA1-OPENQA1-CL

    SPR UNCH

    P1

    -BI1 -BI1

    P1

    -BU1

    -BU1

    BLOCK TW 3I>BBP STEP

    TRM1:12 Res. for Bus 2VT

    -BU1

    QB1-OPEN

    QB2-OPEN

    en05000265.vsd

    IEC05000265 V1 EN

    Figure 21. Typical connection diagram for three winding transformer in a single breakerarrangement. Note! Including IO for control option.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    40 ABB

  • CC

    TC

    TC

    P1

    -QB1

    -QB62

    -QA1

    -BI1

    QB1-OPENQB1-CL

    QB62-OPENQB62-CL

    =1-Q0-OPEN=1-Q0-CL

    =1-Q0-SPR UNCH

    CLOSE QA1

    TRIP QA1

    MAIN 2 TRIP

    BUS A

    QA1-OPENQA1-CL

    BBP-TRIP

    ST BFP 3PH

    BUCH TRIP

    SUDDEN P

    MAN SC OK

    FAU

    LTSI

    GN

    ALLI

    NG

    TO MAIN 2

    TO BB PROT

    MCB ORFUSEMCB-OK

    - +IRF

    WT WARN

    HV BUSBAR TRIP

    TRIP Reinf

    CLOSE Reinf

    TRM2:7-9

    TRM1:7

    TRM1:8

    CC

    TC

    TC

    -QA1SPR UNCH

    TRM2:1-3

    TO BUS PROT

    TO MAIN 2 RELAY

    MCB OK

    TRM1:11

    OT TRIP

    WT TRIP

    OT WARN

    OIL LOW

    GAS ALARM

    TC RAISETC LOWER

    TC IN LOC.

    TC IN MAN

    TC IN AUTO

    MV BUSBAR TRIP

    CC

    TC

    TC

    -QA1TRM2:4-6

    CLOSE QA1

    TRIP QA1TRIP Reinf

    CLOSE Reinf

    CLOSE QA1

    TRIP QA1TRIP Reinf

    CLOSE Reinf

    CC

    TC

    TC

    -QA1

    MAIN 2 TRIP

    TRM1:1-3

    -QB6 -QB61

    TO MAIN 2

    -Q9

    TRM1:4-36P1

    QB6-OPENQB6-CLQB61-OPENQB61-CLQ9-OPENQ9-CL

    =2-Q0-OPEN=2-Q0-CL

    =2-Q0-SPR UNCH

    CLOSE QA1

    TRIP QA1TRIP Reinf

    CLOSE Reinf

    = TAP POS

    QA1-OPENQA1-CL

    SPR UNCH

    QW

    QO

    -BI1

    -T1

    -BU1

    -BI1

    -BU1

    -BI1

    P1

    P1

    TO SECOND BAY

    BLOCK TW 3I>BBP STEP

    TRM1:12 Res. for Bus 2VT

    -BU1

    en05000259.vsd

    IEC05000259 V1 EN

    Figure 22. Typical connection diagram for three winding transformer in a multi breakerarrangement. Note! Including IO for control option.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 41

  • 7. Technical data

    General

    Definitions

    Referencevalue

    The specified value of an influencing factor to which are referred thecharacteristics of the equipment

    Nominalrange

    The range of values of an influencing quantity (factor) within which, underspecified conditions, the equipment meets the specified requirements

    Operativerange

    The range of values of a given energizing quantity for which the equipment,under specified conditions, is able to perform its intended functionsaccording to the specified requirements

    Energizing quantities, rated valuesand limits

    Analog inputs

    Table 4. TRM - Energizing quantities, rated values and limits

    Quantity Rated value Nominal range

    Current Ir = 1 or 5 A (0.2-40) × Ir

    Operative range (0-100) x Ir

    Permissive overload 4 × Ir cont.

    100 × Ir for 1 s *)

    Burden < 150 mVA at Ir = 5 A

    < 20 mVA at Ir = 1 A

    Ac voltage Ur = 110 V 0.5–288 V

    Operative range (0–340) V

    Permissive overload 420 V cont.450 V 10 s

    Burden < 20 mVA at 110 V

    Frequency fr = 50/60 Hz ± 5%

    *) max. 350 A for 1 s when COMBITEST test switch is included.

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    42 ABB

  • Table 5. MIM - mA input module

    Quantity: Rated value: Nominal range:

    Input resistance Rin = 194 Ohm -

    Input range ± 5, ± 10, ± 20mA0-5, 0-10, 0-20, 4-20mA

    -

    Power consumptioneach mA-boardeach mA input

    £ 4 W£ 0.1 W

    -

    Table 6. OEM - Optical ethernet module

    Quantity Rated value

    Number of channels 1 or 2

    Standard IEEE 802.3u 100BASE-FX

    Type of fiber 62.5/125 mm multimode fibre

    Wave length 1300 nm

    Optical connector Type ST

    Communication speed Fast Ethernet 100 MB

    Auxiliary DC voltage

    Table 7. PSM - Power supply module

    Quantity Rated value Nominal range

    Auxiliary dc voltage, EL (input) EL = (24 - 60) VEL = (90 - 250) V

    EL ± 20%EL ± 20%

    Power consumption 50 W typically -

    Auxiliary DC power in-rush < 5 A during 0.1 s -

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    ABB 43

  • Binary inputs and outputs

    Table 8. BIM - Binary input module

    Quantity Rated value Nominal range

    Binary inputs 16 -

    DC voltage, RL 24/40 V48/60 V110/125 V220/250 V

    RL ± 20%RL ± 20%RL ± 20%RL ± 20%

    Power consumption24/40 V48/60 V110/125 V220/250 V

    max. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input

    -

    Counter input frequency 10 pulses/s max -

    Oscillating signal discriminator Blocking settable 1–40 HzRelease settable 1–30 Hz

    Table 9. BIM - Binary input module with enhanced pulse counting capabilities

    Quantity Rated value Nominal range

    Binary inputs 16 -

    DC voltage, RL 24/40 V48/60 V110/125 V220/250 V

    RL ± 20%RL ± 20%RL ± 20%RL ± 20%

    Power consumption24/40 V48/60 V110/125 V220/250 V

    max. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input

    -

    Counter input frequency 10 pulses/s max -

    Balanced counter input frequency 40 pulses/s max -

    Oscillating signal discriminator Blocking settable 1–40 HzRelease settable 1–30 Hz

    Transformer protection RET670 1MRK 504 091-BEN BPre-configuredProduct version: 1.1 Issued: June 2010

    44 ABB

  • Table 10. IOM - Binary input/output module

    Quantity Rated value Nominal range

    Binary inputs 8 -

    DC voltage, RL 24/40 V