Description: These HDA 4400 intrinsically safe versions of pressure transmitters are specially developed for use with the medium hydrogen and in hazardeous areas. There design is based on the HDA 4000 series. The dual approval in accordance with ATEX and IECEx enables universal, almost world-wide utilisation of the devices in potentially explosive atmospheres. As with the industry model, the HDA 4400 has a stainless steel measuring cell with thin-film strain gauge. The main fields of application are hydrogen fuelling stations. Due to the specially selected material, these HDA 4400 are suited for the use in hydrogen applications. Protection types and applications:
ATEX I M1 Ex ia I Ma
II 1G Ex ia IIC T6, T5 Ga II 1/2 G Ex ia IIC T6, T5 Ga/Gb II 2 G Ex ia IIC T6, T5 Gb II 1D Ex ia IIIC T85 °C Da
II 3G Ex nA IIC T6, T5, T4 Gc II 3G Ex ic IIC T6, T5, T4 Gc II 3D Ex ic IIIC T80/T90/T100 °C Dc
IECEx Ex ia I Ma
Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia IIC T6, T5 Gb Ex ia IIIC T85 °C Da Ex nA IIC T6, T5, T4 Gc Ex ic IIC T6, T5, T4 Gc Ex ic IIIC T80/T90/T100 °C Dc
Status: 2017-08-04
Pressure Transmitter HDA 4400 Ex Applications Intrinsically safe, non sparking ATEX / IECEx, dual approval for medium hydrogen
Technical Data Input data
Measuring range bar 16 25 40 200 250 400 500 600 1050
Overload range bar 50 50 80 500 500 800 1000 1000 1400
Burst pressure bar 125 125 200 1250 1250 2000 3000 3000 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm for measuring range ≤ 600 bar) (20 Nm for measuring range 1050 bar) G 1/4 B DIN EN 837 (20 Nm for measuring range ≤ 600 bar) (40 Nm for measuring range 1050 bar)
Parts in contact with fluid Stainless steel 1.4435 (Ni content ≥ 13 %) Measuring cell: gold-plated Seal: Copper (Cu-DHP) (G 1/4 B)
Output data
Output signal, 4 .. 20 mA, 2 conductor
permitted resistance RLmax = (UB - 12 V) / 20 mA [kΩ]
Accuracy acc. to DIN 16086
at limit setting
≤ ± 0.5 % FS typ.
≤ ± 1.0 % FS max.
Accuracy at minimum setting
(B.F.S.L)
≤ ± 0.25 % FS typ.
≤ ± 0.5 % FS max.
Temperature compensation
zero point
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Temperature compensation
over range
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Non-linearity at max. setting
acc. to DIN 16086
≤ ± 0.3 % FS max.
Hysteresis ≤ ± 0.4 % FS max.
Repeatability ≤ ± 0.1 % FS
Rise time ≤ 2 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range -25 .. +85 °C
Operating / ambient / fluid temperature range
T6, T80/T85 °C Ta = -25 .. 60 °C T5, T90 °C Ta = -25 .. 70 °C T100 °C Ta = -25 .. 80 °C T4 Ta = -25 .. 85 °C
Storage temperature range -40 .. +100 °C
- mark EN 61000-6-1 / 2 / 3 / 4
EN 60079-0 / 11 / 15 / 26
EN 50303
Vibration resistance acc. to DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 20 g
Ingress protection acc. to DIN EN 60529 1) IP 67
Relevant data for Ex applications Ex ia, ic Ex nA
Supply voltage 12 .. 28 V DC 12 .. 28 V DC
Max. input current Ii = 100 mA
Maximum input power Pi = 1 W max. power consumption ≤ 1 W
Connection capacitance of the sensor Ci ≤ 22 nF
Inductance of the sensor Li = 0 mH
Insulation voltage 50 V AC, with integrated overvoltage protection acc. to EN 61000-6-2
Other data
Residual ripple of supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 1 million cycles (0 .. 100 % FS)
Weight 150 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override, and short circuit protection are provided. FS = Full Scale = relative to the full measuring range
B.F.S.L.= Best Fit Straight Line 1) With mounted female connector having the corresponding protection class.
Relative pressure Accuracy 0.5 %
Applications: Code used in Model Code
1 9 C
ATEX KEMA 05 ATEX 1016X
I M1 Ex ia I Ma
II 1G Ex ia IIC T6 Ga II 1/2G Ex ia IIC T6 Ga/Gb II 1D Ex ia lIIC T85 °C Da
II 2G Ex ia IIC T6 Gb
II 3G Ex nA llC T6,T5 Gc II 3G Ex ic llC T6,T5 Gc ll 3D Ex ic lllC T80/T90°C Dc
IECEx KEM 08.0014X
Ex ia I Ma
Ex ia IIC T6 Ga Ex ia IIC T6 Ga/Gb Ex ia lIIC T85 °C Da
Ex ia IIC T6 Gb
Ex nA llC T6,T5 Gc Ex ic llC T6,T5 Gc Ex ic lllC T80/T90°C Dc
Application fields Mining Protection class: intrinsically safe ia with barrier
Gases / conductive dust Protection class: intrinsically safe ia with barrier
Gases Protection class: intrinsically safe ia with barrier
Gases Protection class: Non sparking nA
Gases / conductive dust Protection class: intrinsically safe ic with barrier
Model Code: HDA 4 4 X 6 – A – XXXX – E N X – H00 Mechanical connection C = SF250CX20, Autoclave (7/16-20 UNF 2B) G = G1/4 B DIN EN 837
Electrical connection 6 = M12x1, 4 pole, male (mating connector not included)
Output signal A = 4 .. 20 mA, 2 conductor
Measuring ranges in bar 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Approval E = ATEX / IECEx
Insulation voltage N = 50 V AC to housing
Types of protection and application areas ATEX IECEx
1 = I M1 Ex ia I Ma II 1G Ex ia IIC T6 Ga II 1/2 G Ex ia IIC T6 Ga/Gb II 2 G Ex ia IIC T6 Gb II 1D Ex ia IIIC T85 °C Da
Ex ia I Ma Ex ia IIC T6 Ga Ex ia IIC T6 Ga/Gb Ex ia IIC T6 Gb Ex ia IIIC T85 °C Da
9 = II 3G Ex nA IIC T6, T5 Gc Ex nA IIC T6, T5 Gc Only in conjunction with electrical connection „6“ and with the impact
protection metal safety sleeve (see instrument dimensions)
C = II 3G Ex ic IIC T6, T5 Gc II 3D Ex ic IIIC T80/T90°C Dc
Ex ic IIC T6, T5 Gc Ex ic IIIC T80/T90°C Dc
Modification number H00 = for hydrogen applications
Dimensions:
With impact protection metal safety sleeve: Types of protection and application areas: 9
The impact protected metal safety sleeve is included. A straight female connector is required for electrical connection; e.g. female connector M12x1, 4 pole, straight, with 3m shielded cable: ZBE 06S-03, Mat. Nr. 6098243
Pin connections: M12x1 connector
Pin HDA 44X6-A
1 + Sig
2 n.c.
3 - Sig 2
4 n.c.
Note:
The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described please contact the relevant technical department. All technical details are subject to change without notice. HYDAC ELECTRONIC GmbH Hauptstrasse 27, D-66128 Saarbrücken Telephone +49 (0)6897 509-01 Fax +49 (0)6897 509-1726 E-mail: [email protected] Internet: www.hydac.com
Description: This intrinsically safe version of the pressure transmitter HDA 4400 has been specially developed for the use in hydrogen applications and potentially explosive atmospheres and it is based on the HDA 4000 series. The approval complying with CSA enables the utilisation of the devices meeting the requirements of the North American market for potentially explosive atmospheres. As with the industry model, the HDA 4400 has a stainless steel measurement cell with thin-film strain gauge. The main fields of application are hydrogen fuelling stations. Due to the specially selected material, this HDA 4400 is suited for the use in hydrogen applications. Protection ratings and applications: Intrinsically safe: - Class I Division 1 Group A, B, C, D T6 [C, US] - Class I Zone 0 AEx ia IIC T6 [US] - Ex ia IIC T6 [C] - Class I, II, III Division 1 and 2 Group A, B, C, D, E, F, G T6 [C, US] Non incendive - Class I Div. 2 Group A, B, C, D, T4A [C, US] - Class I Zone 2 AEx nL IIC T4 [US] - Class I Zone 2 Ex nL IIC T4 [C]
- Class I, II, III Div. 2 Group A, B, C, D, F, G, T4A [C, US] - Class I Zone 2 AEx nA II T4 [US - Class I Zone 2 Ex nA II T4 [C]
Status: 2017-08-01
Pressure transmitter HDA 4400 Ex Applications Intrinsically safe, Non incendive CSA Approval for hydrogen applications
Tecnical data Input data
Measuring range 1) bar 16 25 40 200 250 400 500 600 1050
Overload pressure bar 50 50 80 500 500 800 1000 1000 1400
Burst pressures bar 125 125 200 1250 1250 2000 3000 3000 3000
Mechanical connection (Torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm for measuring range ≤ 600 bar) (20 Nm for measuring range 1050 bar) G1/4 B DIN EN 837 (20 Nm for measuring range ≤ 600 bar) (40 Nm for measuring range 1050 bar)
Parts in contact with medium Stainless steel 1.4435 (Ni content ≥ 13 %) Measurement cell: gold-plated Seal: Copper (Cu-DHP) (G1/4 B)
Output data
Output signal, permitted load resistance 4 .. 20 mA, 2 conductor
RLmax = (UB - 12 V) / 20 mA [kΩ]
Accuracy acc. to DIN 16086, at limit setting
≤ ± 0.5 % FS typ. ≤ ± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L)
≤ ± 0.25 % FS typ. ≤ ± 0.5 % FS max.
Temperature compensation zero point
≤ ± 0.015 % FS / °C typ. ≤ ± 0.025 % FS / °C max.
Temperature compensation over range
≤ ± 0.015 % FS / °C typ. ≤ ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
≤ ± 0.3 % FS max.
Hysteresis ≤ ± 0.4 % FS max.
Repeatability ≤ ± 0.1 % FS
Rise time ≤ 2 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range -25 .. +85 °C Operation / ambient / fluid temperature range Intrinsically safe:
Ta = -25 .. +60 °C (connector M12x1) Ta = -40 .. +60 °C (1/2-14 NPT Conduit) Non Incendive: Ta = -25 .. +70 °C (connector M12x1) Ta = -40 .. +85 °C (1/2-14 NPT Conduit)
Storage temperature range -40 .. +100 °C Vibration resistance acc. to DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 10 g (1/2-14 NPT Conduit) ≤ 20 g (connector M12x1)
Protection class acc.to DIN EN 60529 / NEMA 2) ISO 20653
IP 67, NEMA 4 (connector M12x1) IP6K9K (1/2-14 NPT Conduit)
Relevant data for Ex applications
Supply voltage 12 .. 28 V DC
Max. input current Ii = 100 mA
Maximum input power up to 28 V: Pi = 1 W
Connection capacitance of the sensor Ci ≤ 22 nF
Inductance of the sensor Li = 0 mH
Insulation voltage 50 V AC, with integrated overvoltage protection to EN 61000-6-2
Other data
Residual ripple supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 1 million cycles (0 .. 100 % FS)
Weight approx. 150 g; approx. 300 g (1/2-14 NPT Conduit)
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit protection are provided. FS (Full Scale) = relative to the full measuring range
B.F.S.L. = Best Fit Straight Line 1) psi measuring ranges on request
2) With mounted female connector having the corresponding protection class
Relative pressure Accuracy 0.5 %
Applications:
Group 1 2 3 4
Protection class Intrinsically safe Gases and dusts
Intrinsically safe Gases
Non incendive (with field wiring) Gases
Non incendive Gases and dusts
Certificate CSA 1760344
Field of application
Intrinsically safe - Class I, II, III Division 1 Group A, B, C, D, E, F, G T6
Intrinsically safe - Class I Division 1 and 2 Group A, B, C, D T6 - Class I Zone 0 AEx ia IIC T6 - Ex ia IIC T6
Non incendive - Class I Division 2 Group A, B, C, D, T4A - Class I Zone 2 AEx nL IIC T4 - Class I Zone 2 Ex nL IIC T4
Non incendive -Class I, II, III Division 2 Group A, B, C, D, F, G, T4A - Class I Zone 2 AEx nA II T4 IP6x - Class I Zone 2 Ex nA II T4
Electrical connection
9 6, 9 9
Code no. for use in model code
A B C
Model Code: HDA 4 4 X X – A – XXXX – C N X – H00 (2m) Mechanical connection C = SF250CX20, Autoclave (7/16-20 UNF 2B) G = G1/4 B DIN EN 837
Electrical connection 6 = Male M12x1, 4 pole (female connector not supplied) 9 = 1/2-14 NPT Conduit (male threads),single leads
Output signal A = 4 .. 20 mA, 2 conductor
Measuring ranges in bar 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Approval C = CSA
Insulation voltage N = 50 V AC to housing
Types of protection and application areas A = Group 1 B = Group 2 and 3 C = Group 4
Modification number H00 = for hydrogen applications
Cable length in m (only for electr. connection code 9) Standard = 2 m
Dimensions:
Pin connections:
M12x1 connector
Conduit (single leads)
Note:
The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described please contact the relevant technical department. All technical details are subject to change. HYDAC ELECTRONIC GmbH Hauptstrasse 27, D-66128 Saarbruecken Telephone +49 (0)6897 509-01 Fax +49 (0)6897 509-1726 E-mail: [email protected] Internet: www.hydac.com
Pin HDA 44X6-A
1 + Sig
2 n.c.
3 - Sig
4 n.c.
Lead HDA 44X9-A
Green + Sig
White - Sig
green-yellow Housing
Connector
Snubber
Snubber Ø 0,5
Status: 2017-08-04
Description: The HDA 4400 intrinsically safe pressure transmitters are specially developed for use with the medium hydrogen and in hazardeous areas. Their design is based on the HDA 4000 series. By the use of two extremely precise and robust stainless steel measuring cells with thin-film strain gauges, each with their own electronics, the sensor comes complete with a redundant architecture and as a result has two output signals separate and independent from each other. These two output signals are inverted (signal 1 = 4 .. 20 mA and signal 2 = 20 .. 4 mA). This causes that the energy within the intrinsically safe circuit is kept constant as at any pressure the sum of the two output signals is 24 mA. Connection is carried out via a two channel Ex approved zener barrier. The dual approval in accordance with ATEX and IECEx enables universal, almost world-wide utilisation of the devices in potentially explosive atmospheres. By means of their redundant setup the transmitters are best suitable for safety circuits or functions in oil and gas industry. The equipment also is applicable in mining industry and fields with high dust exposure. Therewith main fields of application are in intrinsic safety systems. The main fields of application are found in safety-related systems. Due to the specially selected material, these HDA 4400 are suited for the use in hydrogen applications. Protection types and applications:
ATEX I M1 Ex ia I Ma
II 1G Ex ia IIC T6, T5 Ga II 1/2 G Ex ia IIC T6, T5 Ga/Gb II 2 G Ex ia IIC T6, T5 Gb
II 1D Ex ia IIIC T85/T95 °C Da II 3G Ex nA IIC T6, T5, T4 Gc II 3G Ex ic IIC T6, T5, T4 Gc II 3D Ex ic IIIC T85/T95/T105 °C Dc
IECEx Ex ia I Ma
Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia IIC T6, T5 Gb Ex ia IIIC T85/T95 °C Da Ex nA IIC T6, T5, T4 Gc Ex ic IIC T6, T5, T4 Gc Ex ic IIIC T85/95/T105 °C Dc
Pressure Transmitter HDA 4400 Ex Applications Intrinsically safe, non sparking ATEX / IECEx, dual approval for medium hydrogen Redundant
Technical Data Input data
Measuring range Signal 1 bar 16 25 40 200 250 400 500 600 1050
Measuring range Signal 2 bar 16 25 40 200 250 400 500 600 1050
Overload range bar 50 50 80 500 500 800 1000 1000 1400
Burst pressure bar 125 125 200 1250 1250 2000 3000 3000 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm for measuring range ≤ 600 bar) (20 Nm for measuring range 1050 bar)
Parts in contact with fluid Stainless steel 1.4435 (Ni content ≥ 13 %) Measuring cells: gold-plated
Output data
Output signal 1 4 .. 20 mA, 2 conductor Output signal 2 20 .. 4 mA, 2 conductor Permitted resistance, each RLmax = (UB - 12 V) / 20 mA [kΩ]
Accuracy acc. to DIN 16086, at limit setting
≤ ± 0.5 % FS typ.
≤ ± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L.)
≤ ± 0.25 % FS typ.
≤ ± 0.5 % FS max.
Temperature compensation zero point
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Temperature compensation over range
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
≤ ± 0.3 % FS max.
Hysteresis ≤ ± 0.4 % FS max.
Repeatability ≤ ± 0.1 % FS
Rise time ≤ 2 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range -25 .. +85 °C
Operating/ ambient / fluid temperature range
T6, T85 °C Ta = -25 .. 60 °C T5, T95 °C Ta = -25 .. 70 °C T105 °C Ta = -25 .. 80 °C T4 Ta = -25 .. 85 °C
Storage temperature range -40 .. +100 °C
- mark EN 61000-6-1 / 2 / 3 / 4 EN 60079-0 / 11 / 15 / 26 EN 50303
Vibration resistance acc. to DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 20 g
Ingress protection acc. to DIN EN 60529 1) IP 67
Relevant data for Ex applications Ex ia, ic Ex nA
Supply voltage 12 .. 28 V DC 12 .. 28 V DC
Max. input current Ii = 100 mA
Maximum input power Pi = 0.7 W max. power consumption ≤ 1W
Connection capacitance of sensor Ci ≤ 22 nF
Inductance of sensor Li = 0 mH
Safety barrier two channel, Rmin = 280 Ω (e.g. Pepperl & Fuchs Z789)
Insulation voltage 50 V AC, with integrated overvoltage protection to EN 61000-6-2
Other data
Residual ripple of supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 1 million cycles (0 .. 100 % FS)
Weight ~ 210 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override, and short circuit protection are provided. FS = Full Scale = bezogen auf den vollen Messbereich
B.F.S.L. = Best Fit Straight Line
1) with mounted mating connector in corresponding protection class
Relative pressure Accuracy 0.5 %
Status: 2017-08-04
Applications: Code used in Model code
1 9 C
ATEX KEMA 05 ATEX 1016X
I M1 Ex ia I Ma
II 1G Ex ia IIC T6, T5 Ga II 1/2G Ex ia IIC T6, T5 Ga/Gb II 1D Ex ia lIIC T85/T95 °C Da
II 2G Ex ia IIC T6, T5 Gb
II 3G Ex nA llC T6,T5 Gc II 3G Ex ic llC T6,T5 Gc ll 3D Ex ic lllC T85/T95°C Dc
IECEx KEM 08.0014X
Ex ia I Ma
Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia lIIC T85/T95 °C Da
Ex ia IIC T6, T5 Gb
Ex nA llC T6,T5 Gc Ex ic llC T6,T5 Gc Ex ic lllC T85/T95°C Dc
Application fields Mining Protection class: intrinsically safe ia with barrier
Gases / conductive dust Protection class: intrinsically safe ia with barrier
Gases Protection class: intrinsically safe ia with barrier
Gases Protection class: Non sparking nA
Gases/ conductive dust Protection class: intrinsically safe ic with barrier
Model Code:
HDA 4 4 C 6 – A A – XXXX – XXXX – E N X – H00
Mechanical connection C = SF250CX20, Autoclave (7/16-20 UNF 2B)
Electrical connection 6 = M12x1, 4 pole, male (mating connector not included)
Output signal 1 A = 4 .. 20 mA, 2 conductor
Output signal 2 A = 20 .. 4 mA, 2 conductor
Measuring ranges in bar (output signal 1) 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Measuring ranges in bar (output signal 2) 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Approval E = ATEX / IECEx
Insulation voltage N = 50 V AC to housing
Protection types and applications: ATEX IECEx
1 = I M1 Ex ia I Ma II 1G Ex ia IIC T6, T5 Ga II 1/2 G Ex ia IIC T6, T5 Ga/Gb II 2 G Ex ia IIC T6, T5 Gb II 1D Ex ia IIIC T85/T95 °C Da
Ex ia I Ma Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia IIC T6, T5 Gb Ex ia IIIC T85/T95 °C Da
9 = II 3G Ex nA IIC T6, T5 Gc Ex nA IIC T6, T5 Gc Only in conjunction with electrical connection „6“ and with the impact
protection metal safety sleeve (see instrument dimensions)
C = II 3G Ex ic IIC T6, T5 Gc II 3D Ex ic IIIC T85/T95°C Dc
Ex ic IIC T6, T5 Gc Ex ic IIIC T85/T95°C Dc
Modification number H00 = for hydrogen applications
Status: 2017-08-04
Instrument dimensions:
With impact protection metal safety sleeve: Protection types and applications (code) 9 The impact protection metal safety sleeve is included in the scope of supply. A straight mating connector is required for electrical connection. E.g. female connector M12x1,4 pole, straight, with 3m shielded cable: ZBE 06S-03, Part.no. 6098243
Pin connections: M12x1 connector
Pin HDA 44C6-AA
1 + Sig 1 (for output signal 1)
2 - Sig 1 (for output signal 1)
3 + Sig 2 (for output signal 2)
4 - Sig 2 (for output signal 2)
Note:
The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described please contact the relevant technical department. All technical details are subject to change without notice.
HYDAC ELECTRONIC GmbH Hauptstrasse 27, D-66128 Saarbruecken Telephone +49 (0)6897 509-01 Fax +49 (0)6897 509-1726 E-mail: [email protected] Internet: www.hydac.com
Connector
impact protection metal safety sleeve
Snubber Ø 0,5
Status 2017-01-18
Description: These HDA 8400 versions of pressure transmitters are specially developed for the use with the medium hydrogen and for series applications, e.g. in the mobile sector. As with most of the HYDAC pressure transmitters, the HDA 8400 have a robust and long-life measurement cell with thin-film strain gauge. All of the parts getting in contact with media (sensor cell and mechanical connection) are made of stainless steel and are welded together with each other. This means that there are no sealing points in the interior of the sensor hence no chance of leakage. Due to the specially selected material, these HDA 8400 are suited for the use in hydrogen applications.
Pressure Transmitter
HDA 8400 for medium hydrogen (Minimum order quantity 500 units)
Technical data: Input data
Measuring range 25 40 60 100 160 250 400 600 900 1050
Overload pressure 50 80 120 200 320 500 800 1000 1400 1400
Burst pressure 125 200 300 500 800 1250 2000 3000 3000 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm, 20 Nm at 900 bar) G 1/4 B DIN EN 837 (20 Nm) 9/16-18 UNF 2A (ISO 8434-3) (25 Nm)
Parts in contact with medium Stainless steel 1.4435 (Ni content 13 %)
Seal: Copper (Cu-DHP) (G 1/4 B); Zurcon22
(Polyurethane) (9/16-18 UNF 2A)
Output data
Output signal 4 .. 20 mA, ratiometric, many others possible
Accuracy acc. to DIN 16086, at limit setting
± 0.5 % FS typ.
± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L) ± 0.25 % FS typ.
± 0.5 % FS max.
Temperature compensation zero point
± 0.015 % FS / °C typ.
± 0.025 % FS / °C max.
Temperature compensation over range
± 0.015 % FS / °C typ.
± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
± 0.3 % FS max.
Hysteresis ± 0.4 % FS max.
Repeatability ± 0.1 % FS
Rise time < 2 ms
Long-term drift ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range - 25 .. 85 °C
Operating temperature range - 40 .. 100 °C
Storage temperature range - 40 .. 100 °C
Fluid temperature range - 40 .. 100 °C
- mark EN 61000-6-1 / 2 / 3 / 4
Vibration resistance acc. to DIN EN 60068-2-6 at 5 .. 2000 Hz
25 g
Shock resistance acc. to DIN EN 60068-2-27
100 g / 6 ms / half sine 500 g / 1 ms / half sine
Ingress protection acc. to DIN EN 60529 1) ISO 20653 1)
IP 67 IP 6K9K
Other Data
Supply voltage when used acc. to UL specifications
8 .. 30 V DC; 5 V DC ± 5 % (ratiometric) – limited energy – acc. to 9.3 UL 61010; Class 2; UL 1310/1585; LPS UL 60950
Residual ripple of supply voltage 5 %
Electrical connection 2) M12x1, 4 pol., plastic or metal (solid version) Metri-Pack series 150, 3 pole
Life expectancy > 1 million load cycles (0 .. 100 % FS)
Weight approx. 55 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit
protection are provided. FS = Full Scale = relative to complete measuring range,
B.F.S.L. = Best Fit Straight Line 1)
With mounted female connector having the corresponding protection class. 2)
Other connectors / options are available on request.
Relative pressure Accuracy 0.5 %
Dimensions:
Pin connections:
M12x1, 4 pole
Pin
1 + signal
2 n.c.
3 - signal
4 n.c.
Metri-Pack, 3 pole
Pin
1 - signal
2 + signal
3 n.c.
HYDAC ELECTRONIC GMBH Hauptstrasse 27, D-66128 Saarbrücken Phone: +49 (0)6897 / 509-01 Fax: +49 (0) 6897 / 509-1726 e-mail: [email protected] Internet: Global Presence. Local Expertise. www.hydac.com
Note: The information in this brochure relates to the operating conditions and applications described. For applications and operating conditions not described. please contact the relevant technical department. Subject to technical modifications.
Male
connection
Orifice
Status 2017-01-18
Description: These HDA 8400 versions of pressure transmitters are specially developed for the use with the medium hydrogen and for series applications, e.g. in the mobile sector. As with most of the HYDAC pressure transmitters, the HDA 8400 have a robust and long-life measurement cell with thin-film strain gauge. All of the parts getting in contact with media (sensor cell and mechanical connection) are made of stainless steel and are welded together with each other. This means that there are no sealing points in the interior of the sensor hence no chance of leakage. Due to the specially selected material, these HDA 8400 are suited for the use in hydrogen applications. All HDA 8400 have successfully passed the component testing for type approval according to EC 79-2009 / V0 406-2010.
Pressure Transmitter
HDA 8400 for medium hydrogen tested according to EC 79 (Minimum order quantity 500 units)
Technical data: Input data
Measuring range 900
Nominal operating pressure 1) 700 1)
Maximum permitted operating pressure 1) 875 1)
Burst pressure 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (20 Nm) G 1/4 B DIN EN 837 (20 Nm) 9/16-18 UNF 2A (ISO 8434-3) (25 Nm)
Parts in contact with medium Stainless steel 1.4435 (Ni content 13 %)
Seal: Copper (Cu-DHP) (G 1/4 B); Zurcon22
(Polyurethane) (9/16-18 UNF 2A)
Output data
Output signal 4 .. 20 mA, ratiometric, many others possible
Accuracy acc. to DIN 16086 at limit setting
± 0.5 % FS typ.
± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L) ± 0.25 % FS typ.
± 0.5 % FS max.
Temperature compensation zero point
± 0.015 % FS / °C typ. ± 0.025 % FS / °C max.
Temperature compensation Span
± 0.015 % FS / °C typ. ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
± 0.3 % FS max.
Hysteresis ± 0.4 % FS max.
Repeatability ± 0.1 % FS
Rise time < 2 ms
Long-term drift ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range - 25 .. 85 °C
Operating temperature range - 40 .. 100 °C
Storage temperature range - 40 .. 100 °C
Fluid temperature range - 40 .. 100 °C
- mark EN 61000-6-1 / 2 / 3 / 4
Vibration resistance acc. to DIN EN 60068-2-6 at 5 .. 2000 Hz
25 g
Shock resistance acc. to DIN EN 60068-2-27
100 g / 6 ms / half sine 500 g / 1 ms / half sine
Ingress protection to DIN EN 60529 2) ISO 20653
IP 67 IP 6K9K
Other Data
Supply voltage when used acc. to UL specifications
8 .. 30 V DC; 5 V DC ± 5 % (ratiometric) – limited energy – according to 9.3 UL 61010; Class 2; UL 1310/1585; LPS UL 60950
Residual ripple of supply voltage 5 %
Electrical connection M12x1, 4 pol., plastic or metal (solid version) Metri-Pack series 150, 3 pole
Life expectancy > 1 million load cycles (0 .. 100% FS)
Weight approx. 55 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit
protection are provided. FS = Full Scale = relative to complete measuring range,
B.F.S.L. = Best Fit Straight Line 1)
Tested / validated according to EC 79/2009, nominal operating pressure 700 bar at reference temperature 20 °C, max. permitted operation pressure 875 bar
2) With mounted female connector having the corresponding protection class.
Relative pressure Accuracy 0.5 %
Dimensions:
Pin connections:
M12x1, 4 pole
Pin
1 + signal
2 n.c.
3 - signal
4 n.c.
Metri-Pack, 3 pole
Pin
1 - signal
2 + Signal
3 n.c.
HYDAC ELECTRONIC GMBH Hauptstrasse 27, D-66128 Saarbrücken Phone: +49 (0)6897 / 509-01 Fax: +49 (0) 6897 / 509-1726 e-mail: [email protected] Internet: www.hydac.com
Note: The information in this brochure relates to the operating conditions and applications described. For applications and operating conditions not described. please contact the relevant technical department. Subject to technical modifications.
Male
connection
Orifice
Description: This intrinsically safe version of the pressure transmitter HDA 4400 has been specially developed for the use in hydrogen applications and potentially explosive atmospheres and it is based on the HDA 4000 series. The approval complying with CSA enables the utilisation of the devices meeting the requirements of the North American market for potentially explosive atmospheres. As with the industry model, the HDA 4400 has a stainless steel measurement cell with thin-film strain gauge. The main fields of application are hydrogen fuelling stations. Due to the specially selected material, this HDA 4400 is suited for the use in hydrogen applications. Protection ratings and applications: Intrinsically safe: - Class I Division 1 Group A, B, C, D T6 [C, US] - Class I Zone 0 AEx ia IIC T6 [US] - Ex ia IIC T6 [C] - Class I, II, III Division 1 and 2 Group A, B, C, D, E, F, G T6 [C, US] Non incendive - Class I Div. 2 Group A, B, C, D, T4A [C, US] - Class I Zone 2 AEx nL IIC T4 [US] - Class I Zone 2 Ex nL IIC T4 [C]
- Class I, II, III Div. 2 Group A, B, C, D, F, G, T4A [C, US] - Class I Zone 2 AEx nA II T4 [US - Class I Zone 2 Ex nA II T4 [C]
Status: 2017-08-01
Pressure transmitter HDA 4400 Ex Applications Intrinsically safe, Non incendive CSA Approval for hydrogen applications
Tecnical data Input data
Measuring range 1) bar 16 25 40 200 250 400 500 600 1050
Overload pressure bar 50 50 80 500 500 800 1000 1000 1400
Burst pressures bar 125 125 200 1250 1250 2000 3000 3000 3000
Mechanical connection (Torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm for measuring range ≤ 600 bar) (20 Nm for measuring range 1050 bar) G1/4 B DIN EN 837 (20 Nm for measuring range ≤ 600 bar) (40 Nm for measuring range 1050 bar)
Parts in contact with medium Stainless steel 1.4435 (Ni content ≥ 13 %) Measurement cell: gold-plated Seal: Copper (Cu-DHP) (G1/4 B)
Output data
Output signal, permitted load resistance 4 .. 20 mA, 2 conductor
RLmax = (UB - 12 V) / 20 mA [kΩ]
Accuracy acc. to DIN 16086, at limit setting
≤ ± 0.5 % FS typ. ≤ ± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L)
≤ ± 0.25 % FS typ. ≤ ± 0.5 % FS max.
Temperature compensation zero point
≤ ± 0.015 % FS / °C typ. ≤ ± 0.025 % FS / °C max.
Temperature compensation over range
≤ ± 0.015 % FS / °C typ. ≤ ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
≤ ± 0.3 % FS max.
Hysteresis ≤ ± 0.4 % FS max.
Repeatability ≤ ± 0.1 % FS
Rise time ≤ 2 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range -25 .. +85 °C Operation / ambient / fluid temperature range Intrinsically safe:
Ta = -25 .. +60 °C (connector M12x1) Ta = -40 .. +60 °C (1/2-14 NPT Conduit) Non Incendive: Ta = -25 .. +70 °C (connector M12x1) Ta = -40 .. +85 °C (1/2-14 NPT Conduit)
Storage temperature range -40 .. +100 °C Vibration resistance acc. to DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 10 g (1/2-14 NPT Conduit) ≤ 20 g (connector M12x1)
Protection class acc.to DIN EN 60529 / NEMA 2) ISO 20653
IP 67, NEMA 4 (connector M12x1) IP6K9K (1/2-14 NPT Conduit)
Relevant data for Ex applications
Supply voltage 12 .. 28 V DC
Max. input current Ii = 100 mA
Maximum input power up to 28 V: Pi = 1 W
Connection capacitance of the sensor Ci ≤ 22 nF
Inductance of the sensor Li = 0 mH
Insulation voltage 50 V AC, with integrated overvoltage protection to EN 61000-6-2
Other data
Residual ripple supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 1 million cycles (0 .. 100 % FS)
Weight approx. 150 g; approx. 300 g (1/2-14 NPT Conduit)
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit protection are provided. FS (Full Scale) = relative to the full measuring range
B.F.S.L. = Best Fit Straight Line 1) psi measuring ranges on request
2) With mounted female connector having the corresponding protection class
Relative pressure Accuracy 0.5 %
Applications:
Group 1 2 3 4
Protection class Intrinsically safe Gases and dusts
Intrinsically safe Gases
Non incendive (with field wiring) Gases
Non incendive Gases and dusts
Certificate CSA 1760344
Field of application
Intrinsically safe - Class I, II, III Division 1 Group A, B, C, D, E, F, G T6
Intrinsically safe - Class I Division 1 and 2 Group A, B, C, D T6 - Class I Zone 0 AEx ia IIC T6 - Ex ia IIC T6
Non incendive - Class I Division 2 Group A, B, C, D, T4A - Class I Zone 2 AEx nL IIC T4 - Class I Zone 2 Ex nL IIC T4
Non incendive -Class I, II, III Division 2 Group A, B, C, D, F, G, T4A - Class I Zone 2 AEx nA II T4 IP6x - Class I Zone 2 Ex nA II T4
Electrical connection
9 6, 9 9
Code no. for use in model code
A B C
Model Code: HDA 4 4 X X – A – XXXX – C N X – H00 (2m) Mechanical connection C = SF250CX20, Autoclave (7/16-20 UNF 2B) G = G1/4 B DIN EN 837
Electrical connection 6 = Male M12x1, 4 pole (female connector not supplied) 9 = 1/2-14 NPT Conduit (male threads),single leads
Output signal A = 4 .. 20 mA, 2 conductor
Measuring ranges in bar 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Approval C = CSA
Insulation voltage N = 50 V AC to housing
Types of protection and application areas A = Group 1 B = Group 2 and 3 C = Group 4
Modification number H00 = for hydrogen applications
Cable length in m (only for electr. connection code 9) Standard = 2 m
Dimensions:
Pin connections:
M12x1 connector
Conduit (single leads)
Note:
The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described please contact the relevant technical department. All technical details are subject to change. HYDAC ELECTRONIC GmbH Hauptstrasse 27, D-66128 Saarbruecken Telephone +49 (0)6897 509-01 Fax +49 (0)6897 509-1726 E-mail: [email protected] Internet: www.hydac.com
Pin HDA 44X6-A
1 + Sig
2 n.c.
3 - Sig
4 n.c.
Lead HDA 44X9-A
Green + Sig
White - Sig
green-yellow Housing
Connector
Snubber
Snubber Ø 0,5
Description: These HDA 4400 intrinsically safe versions of pressure transmitters are specially developed for use with the medium hydrogen and in hazardeous areas. There design is based on the HDA 4000 series. The dual approval in accordance with ATEX and IECEx enables universal, almost world-wide utilisation of the devices in potentially explosive atmospheres. As with the industry model, the HDA 4400 has a stainless steel measuring cell with thin-film strain gauge. The main fields of application are hydrogen fuelling stations. Due to the specially selected material, these HDA 4400 are suited for the use in hydrogen applications. Protection types and applications:
ATEX I M1 Ex ia I Ma
II 1G Ex ia IIC T6, T5 Ga II 1/2 G Ex ia IIC T6, T5 Ga/Gb II 2 G Ex ia IIC T6, T5 Gb II 1D Ex ia IIIC T85 °C Da
II 3G Ex nA IIC T6, T5, T4 Gc II 3G Ex ic IIC T6, T5, T4 Gc II 3D Ex ic IIIC T80/T90/T100 °C Dc
IECEx Ex ia I Ma
Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia IIC T6, T5 Gb Ex ia IIIC T85 °C Da Ex nA IIC T6, T5, T4 Gc Ex ic IIC T6, T5, T4 Gc Ex ic IIIC T80/T90/T100 °C Dc
Status: 2017-08-04
Pressure Transmitter HDA 4400 Ex Applications Intrinsically safe, non sparking ATEX / IECEx, dual approval for medium hydrogen
Technical Data Input data
Measuring range bar 16 25 40 200 250 400 500 600 1050
Overload range bar 50 50 80 500 500 800 1000 1000 1400
Burst pressure bar 125 125 200 1250 1250 2000 3000 3000 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm for measuring range ≤ 600 bar) (20 Nm for measuring range 1050 bar) G 1/4 B DIN EN 837 (20 Nm for measuring range ≤ 600 bar) (40 Nm for measuring range 1050 bar)
Parts in contact with fluid Stainless steel 1.4435 (Ni content ≥ 13 %) Measuring cell: gold-plated Seal: Copper (Cu-DHP) (G 1/4 B)
Output data
Output signal, 4 .. 20 mA, 2 conductor
permitted resistance RLmax = (UB - 12 V) / 20 mA [kΩ]
Accuracy acc. to DIN 16086
at limit setting
≤ ± 0.5 % FS typ.
≤ ± 1.0 % FS max.
Accuracy at minimum setting
(B.F.S.L)
≤ ± 0.25 % FS typ.
≤ ± 0.5 % FS max.
Temperature compensation
zero point
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Temperature compensation
over range
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Non-linearity at max. setting
acc. to DIN 16086
≤ ± 0.3 % FS max.
Hysteresis ≤ ± 0.4 % FS max.
Repeatability ≤ ± 0.1 % FS
Rise time ≤ 2 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range -25 .. +85 °C
Operating / ambient / fluid temperature range
T6, T80/T85 °C Ta = -25 .. 60 °C T5, T90 °C Ta = -25 .. 70 °C T100 °C Ta = -25 .. 80 °C T4 Ta = -25 .. 85 °C
Storage temperature range -40 .. +100 °C
- mark EN 61000-6-1 / 2 / 3 / 4
EN 60079-0 / 11 / 15 / 26
EN 50303
Vibration resistance acc. to DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 20 g
Ingress protection acc. to DIN EN 60529 1) IP 67
Relevant data for Ex applications Ex ia, ic Ex nA
Supply voltage 12 .. 28 V DC 12 .. 28 V DC
Max. input current Ii = 100 mA
Maximum input power Pi = 1 W max. power consumption ≤ 1 W
Connection capacitance of the sensor Ci ≤ 22 nF
Inductance of the sensor Li = 0 mH
Insulation voltage 50 V AC, with integrated overvoltage protection acc. to EN 61000-6-2
Other data
Residual ripple of supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 1 million cycles (0 .. 100 % FS)
Weight 150 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override, and short circuit protection are provided. FS = Full Scale = relative to the full measuring range
B.F.S.L.= Best Fit Straight Line 1) With mounted female connector having the corresponding protection class.
Relative pressure Accuracy 0.5 %
Applications: Code used in Model Code
1 9 C
ATEX KEMA 05 ATEX 1016X
I M1 Ex ia I Ma
II 1G Ex ia IIC T6 Ga II 1/2G Ex ia IIC T6 Ga/Gb II 1D Ex ia lIIC T85 °C Da
II 2G Ex ia IIC T6 Gb
II 3G Ex nA llC T6,T5 Gc II 3G Ex ic llC T6,T5 Gc ll 3D Ex ic lllC T80/T90°C Dc
IECEx KEM 08.0014X
Ex ia I Ma
Ex ia IIC T6 Ga Ex ia IIC T6 Ga/Gb Ex ia lIIC T85 °C Da
Ex ia IIC T6 Gb
Ex nA llC T6,T5 Gc Ex ic llC T6,T5 Gc Ex ic lllC T80/T90°C Dc
Application fields Mining Protection class: intrinsically safe ia with barrier
Gases / conductive dust Protection class: intrinsically safe ia with barrier
Gases Protection class: intrinsically safe ia with barrier
Gases Protection class: Non sparking nA
Gases / conductive dust Protection class: intrinsically safe ic with barrier
Model Code: HDA 4 4 X 6 – A – XXXX – E N X – H00 Mechanical connection C = SF250CX20, Autoclave (7/16-20 UNF 2B) G = G1/4 B DIN EN 837
Electrical connection 6 = M12x1, 4 pole, male (mating connector not included)
Output signal A = 4 .. 20 mA, 2 conductor
Measuring ranges in bar 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Approval E = ATEX / IECEx
Insulation voltage N = 50 V AC to housing
Types of protection and application areas ATEX IECEx
1 = I M1 Ex ia I Ma II 1G Ex ia IIC T6 Ga II 1/2 G Ex ia IIC T6 Ga/Gb II 2 G Ex ia IIC T6 Gb II 1D Ex ia IIIC T85 °C Da
Ex ia I Ma Ex ia IIC T6 Ga Ex ia IIC T6 Ga/Gb Ex ia IIC T6 Gb Ex ia IIIC T85 °C Da
9 = II 3G Ex nA IIC T6, T5 Gc Ex nA IIC T6, T5 Gc Only in conjunction with electrical connection „6“ and with the impact
protection metal safety sleeve (see instrument dimensions)
C = II 3G Ex ic IIC T6, T5 Gc II 3D Ex ic IIIC T80/T90°C Dc
Ex ic IIC T6, T5 Gc Ex ic IIIC T80/T90°C Dc
Modification number H00 = for hydrogen applications
Dimensions:
With impact protection metal safety sleeve: Types of protection and application areas: 9
The impact protected metal safety sleeve is included. A straight female connector is required for electrical connection; e.g. female connector M12x1, 4 pole, straight, with 3m shielded cable: ZBE 06S-03, Mat. Nr. 6098243
Pin connections: M12x1 connector
Pin HDA 44X6-A
1 + Sig
2 n.c.
3 - Sig 2
4 n.c.
Note:
The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described please contact the relevant technical department. All technical details are subject to change without notice. HYDAC ELECTRONIC GmbH Hauptstrasse 27, D-66128 Saarbrücken Telephone +49 (0)6897 509-01 Fax +49 (0)6897 509-1726 E-mail: [email protected] Internet: www.hydac.com
Description: This intrinsically safe version of the pressure transmitter HDA 4400 has been specially developed for the use in hydrogen applications and potentially explosive atmospheres and it is based on the HDA 4000 series. The approval complying with CSA enables the utilisation of the devices meeting the requirements of the North American market for potentially explosive atmospheres. As with the industry model, the HDA 4400 has a stainless steel measurement cell with thin-film strain gauge. The main fields of application are hydrogen fuelling stations. Due to the specially selected material, this HDA 4400 is suited for the use in hydrogen applications. Protection ratings and applications: Intrinsically safe: - Class I Division 1 Group A, B, C, D T6 [C, US] - Class I Zone 0 AEx ia IIC T6 [US] - Ex ia IIC T6 [C] - Class I, II, III Division 1 and 2 Group A, B, C, D, E, F, G T6 [C, US] Non incendive - Class I Div. 2 Group A, B, C, D, T4A [C, US] - Class I Zone 2 AEx nL IIC T4 [US] - Class I Zone 2 Ex nL IIC T4 [C]
- Class I, II, III Div. 2 Group A, B, C, D, F, G, T4A [C, US] - Class I Zone 2 AEx nA II T4 [US - Class I Zone 2 Ex nA II T4 [C]
Status: 2017-08-01
Pressure transmitter HDA 4400 Ex Applications Intrinsically safe, Non incendive CSA Approval for hydrogen applications
Tecnical data Input data
Measuring range 1) bar 16 25 40 200 250 400 500 600 1050
Overload pressure bar 50 50 80 500 500 800 1000 1000 1400
Burst pressures bar 125 125 200 1250 1250 2000 3000 3000 3000
Mechanical connection (Torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm for measuring range ≤ 600 bar) (20 Nm for measuring range 1050 bar) G1/4 B DIN EN 837 (20 Nm for measuring range ≤ 600 bar) (40 Nm for measuring range 1050 bar)
Parts in contact with medium Stainless steel 1.4435 (Ni content ≥ 13 %) Measurement cell: gold-plated Seal: Copper (Cu-DHP) (G1/4 B)
Output data
Output signal, permitted load resistance 4 .. 20 mA, 2 conductor
RLmax = (UB - 12 V) / 20 mA [kΩ]
Accuracy acc. to DIN 16086, at limit setting
≤ ± 0.5 % FS typ. ≤ ± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L)
≤ ± 0.25 % FS typ. ≤ ± 0.5 % FS max.
Temperature compensation zero point
≤ ± 0.015 % FS / °C typ. ≤ ± 0.025 % FS / °C max.
Temperature compensation over range
≤ ± 0.015 % FS / °C typ. ≤ ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
≤ ± 0.3 % FS max.
Hysteresis ≤ ± 0.4 % FS max.
Repeatability ≤ ± 0.1 % FS
Rise time ≤ 2 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range -25 .. +85 °C Operation / ambient / fluid temperature range Intrinsically safe:
Ta = -25 .. +60 °C (connector M12x1) Ta = -40 .. +60 °C (1/2-14 NPT Conduit) Non Incendive: Ta = -25 .. +70 °C (connector M12x1) Ta = -40 .. +85 °C (1/2-14 NPT Conduit)
Storage temperature range -40 .. +100 °C Vibration resistance acc. to DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 10 g (1/2-14 NPT Conduit) ≤ 20 g (connector M12x1)
Protection class acc.to DIN EN 60529 / NEMA 2) ISO 20653
IP 67, NEMA 4 (connector M12x1) IP6K9K (1/2-14 NPT Conduit)
Relevant data for Ex applications
Supply voltage 12 .. 28 V DC
Max. input current Ii = 100 mA
Maximum input power up to 28 V: Pi = 1 W
Connection capacitance of the sensor Ci ≤ 22 nF
Inductance of the sensor Li = 0 mH
Insulation voltage 50 V AC, with integrated overvoltage protection to EN 61000-6-2
Other data
Residual ripple supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 1 million cycles (0 .. 100 % FS)
Weight approx. 150 g; approx. 300 g (1/2-14 NPT Conduit)
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit protection are provided. FS (Full Scale) = relative to the full measuring range
B.F.S.L. = Best Fit Straight Line 1) psi measuring ranges on request
2) With mounted female connector having the corresponding protection class
Relative pressure Accuracy 0.5 %
Applications:
Group 1 2 3 4
Protection class Intrinsically safe Gases and dusts
Intrinsically safe Gases
Non incendive (with field wiring) Gases
Non incendive Gases and dusts
Certificate CSA 1760344
Field of application
Intrinsically safe - Class I, II, III Division 1 Group A, B, C, D, E, F, G T6
Intrinsically safe - Class I Division 1 and 2 Group A, B, C, D T6 - Class I Zone 0 AEx ia IIC T6 - Ex ia IIC T6
Non incendive - Class I Division 2 Group A, B, C, D, T4A - Class I Zone 2 AEx nL IIC T4 - Class I Zone 2 Ex nL IIC T4
Non incendive -Class I, II, III Division 2 Group A, B, C, D, F, G, T4A - Class I Zone 2 AEx nA II T4 IP6x - Class I Zone 2 Ex nA II T4
Electrical connection
9 6, 9 9
Code no. for use in model code
A B C
Model Code: HDA 4 4 X X – A – XXXX – C N X – H00 (2m) Mechanical connection C = SF250CX20, Autoclave (7/16-20 UNF 2B) G = G1/4 B DIN EN 837
Electrical connection 6 = Male M12x1, 4 pole (female connector not supplied) 9 = 1/2-14 NPT Conduit (male threads),single leads
Output signal A = 4 .. 20 mA, 2 conductor
Measuring ranges in bar 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Approval C = CSA
Insulation voltage N = 50 V AC to housing
Types of protection and application areas A = Group 1 B = Group 2 and 3 C = Group 4
Modification number H00 = for hydrogen applications
Cable length in m (only for electr. connection code 9) Standard = 2 m
Dimensions:
Pin connections:
M12x1 connector
Conduit (single leads)
Note:
The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described please contact the relevant technical department. All technical details are subject to change. HYDAC ELECTRONIC GmbH Hauptstrasse 27, D-66128 Saarbruecken Telephone +49 (0)6897 509-01 Fax +49 (0)6897 509-1726 E-mail: [email protected] Internet: www.hydac.com
Pin HDA 44X6-A
1 + Sig
2 n.c.
3 - Sig
4 n.c.
Lead HDA 44X9-A
Green + Sig
White - Sig
green-yellow Housing
Connector
Snubber
Snubber Ø 0,5
Status: 2017-08-04
Description: The HDA 4400 intrinsically safe pressure transmitters are specially developed for use with the medium hydrogen and in hazardeous areas. Their design is based on the HDA 4000 series. By the use of two extremely precise and robust stainless steel measuring cells with thin-film strain gauges, each with their own electronics, the sensor comes complete with a redundant architecture and as a result has two output signals separate and independent from each other. These two output signals are inverted (signal 1 = 4 .. 20 mA and signal 2 = 20 .. 4 mA). This causes that the energy within the intrinsically safe circuit is kept constant as at any pressure the sum of the two output signals is 24 mA. Connection is carried out via a two channel Ex approved zener barrier. The dual approval in accordance with ATEX and IECEx enables universal, almost world-wide utilisation of the devices in potentially explosive atmospheres. By means of their redundant setup the transmitters are best suitable for safety circuits or functions in oil and gas industry. The equipment also is applicable in mining industry and fields with high dust exposure. Therewith main fields of application are in intrinsic safety systems. The main fields of application are found in safety-related systems. Due to the specially selected material, these HDA 4400 are suited for the use in hydrogen applications. Protection types and applications:
ATEX I M1 Ex ia I Ma
II 1G Ex ia IIC T6, T5 Ga II 1/2 G Ex ia IIC T6, T5 Ga/Gb II 2 G Ex ia IIC T6, T5 Gb
II 1D Ex ia IIIC T85/T95 °C Da II 3G Ex nA IIC T6, T5, T4 Gc II 3G Ex ic IIC T6, T5, T4 Gc II 3D Ex ic IIIC T85/T95/T105 °C Dc
IECEx Ex ia I Ma
Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia IIC T6, T5 Gb Ex ia IIIC T85/T95 °C Da Ex nA IIC T6, T5, T4 Gc Ex ic IIC T6, T5, T4 Gc Ex ic IIIC T85/95/T105 °C Dc
Pressure Transmitter HDA 4400 Ex Applications Intrinsically safe, non sparking ATEX / IECEx, dual approval for medium hydrogen Redundant
Technical Data Input data
Measuring range Signal 1 bar 16 25 40 200 250 400 500 600 1050
Measuring range Signal 2 bar 16 25 40 200 250 400 500 600 1050
Overload range bar 50 50 80 500 500 800 1000 1000 1400
Burst pressure bar 125 125 200 1250 1250 2000 3000 3000 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm for measuring range ≤ 600 bar) (20 Nm for measuring range 1050 bar)
Parts in contact with fluid Stainless steel 1.4435 (Ni content ≥ 13 %) Measuring cells: gold-plated
Output data
Output signal 1 4 .. 20 mA, 2 conductor Output signal 2 20 .. 4 mA, 2 conductor Permitted resistance, each RLmax = (UB - 12 V) / 20 mA [kΩ]
Accuracy acc. to DIN 16086, at limit setting
≤ ± 0.5 % FS typ.
≤ ± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L.)
≤ ± 0.25 % FS typ.
≤ ± 0.5 % FS max.
Temperature compensation zero point
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Temperature compensation over range
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
≤ ± 0.3 % FS max.
Hysteresis ≤ ± 0.4 % FS max.
Repeatability ≤ ± 0.1 % FS
Rise time ≤ 2 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range -25 .. +85 °C
Operating/ ambient / fluid temperature range
T6, T85 °C Ta = -25 .. 60 °C T5, T95 °C Ta = -25 .. 70 °C T105 °C Ta = -25 .. 80 °C T4 Ta = -25 .. 85 °C
Storage temperature range -40 .. +100 °C
- mark EN 61000-6-1 / 2 / 3 / 4 EN 60079-0 / 11 / 15 / 26 EN 50303
Vibration resistance acc. to DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 20 g
Ingress protection acc. to DIN EN 60529 1) IP 67
Relevant data for Ex applications Ex ia, ic Ex nA
Supply voltage 12 .. 28 V DC 12 .. 28 V DC
Max. input current Ii = 100 mA
Maximum input power Pi = 0.7 W max. power consumption ≤ 1W
Connection capacitance of sensor Ci ≤ 22 nF
Inductance of sensor Li = 0 mH
Safety barrier two channel, Rmin = 280 Ω (e.g. Pepperl & Fuchs Z789)
Insulation voltage 50 V AC, with integrated overvoltage protection to EN 61000-6-2
Other data
Residual ripple of supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 1 million cycles (0 .. 100 % FS)
Weight ~ 210 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override, and short circuit protection are provided. FS = Full Scale = bezogen auf den vollen Messbereich
B.F.S.L. = Best Fit Straight Line
1) with mounted mating connector in corresponding protection class
Relative pressure Accuracy 0.5 %
Status: 2017-08-04
Applications: Code used in Model code
1 9 C
ATEX KEMA 05 ATEX 1016X
I M1 Ex ia I Ma
II 1G Ex ia IIC T6, T5 Ga II 1/2G Ex ia IIC T6, T5 Ga/Gb II 1D Ex ia lIIC T85/T95 °C Da
II 2G Ex ia IIC T6, T5 Gb
II 3G Ex nA llC T6,T5 Gc II 3G Ex ic llC T6,T5 Gc ll 3D Ex ic lllC T85/T95°C Dc
IECEx KEM 08.0014X
Ex ia I Ma
Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia lIIC T85/T95 °C Da
Ex ia IIC T6, T5 Gb
Ex nA llC T6,T5 Gc Ex ic llC T6,T5 Gc Ex ic lllC T85/T95°C Dc
Application fields Mining Protection class: intrinsically safe ia with barrier
Gases / conductive dust Protection class: intrinsically safe ia with barrier
Gases Protection class: intrinsically safe ia with barrier
Gases Protection class: Non sparking nA
Gases/ conductive dust Protection class: intrinsically safe ic with barrier
Model Code:
HDA 4 4 C 6 – A A – XXXX – XXXX – E N X – H00
Mechanical connection C = SF250CX20, Autoclave (7/16-20 UNF 2B)
Electrical connection 6 = M12x1, 4 pole, male (mating connector not included)
Output signal 1 A = 4 .. 20 mA, 2 conductor
Output signal 2 A = 20 .. 4 mA, 2 conductor
Measuring ranges in bar (output signal 1) 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Measuring ranges in bar (output signal 2) 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Approval E = ATEX / IECEx
Insulation voltage N = 50 V AC to housing
Protection types and applications: ATEX IECEx
1 = I M1 Ex ia I Ma II 1G Ex ia IIC T6, T5 Ga II 1/2 G Ex ia IIC T6, T5 Ga/Gb II 2 G Ex ia IIC T6, T5 Gb II 1D Ex ia IIIC T85/T95 °C Da
Ex ia I Ma Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia IIC T6, T5 Gb Ex ia IIIC T85/T95 °C Da
9 = II 3G Ex nA IIC T6, T5 Gc Ex nA IIC T6, T5 Gc Only in conjunction with electrical connection „6“ and with the impact
protection metal safety sleeve (see instrument dimensions)
C = II 3G Ex ic IIC T6, T5 Gc II 3D Ex ic IIIC T85/T95°C Dc
Ex ic IIC T6, T5 Gc Ex ic IIIC T85/T95°C Dc
Modification number H00 = for hydrogen applications
Status: 2017-08-04
Instrument dimensions:
With impact protection metal safety sleeve: Protection types and applications (code) 9 The impact protection metal safety sleeve is included in the scope of supply. A straight mating connector is required for electrical connection. E.g. female connector M12x1,4 pole, straight, with 3m shielded cable: ZBE 06S-03, Part.no. 6098243
Pin connections: M12x1 connector
Pin HDA 44C6-AA
1 + Sig 1 (for output signal 1)
2 - Sig 1 (for output signal 1)
3 + Sig 2 (for output signal 2)
4 - Sig 2 (for output signal 2)
Note:
The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described please contact the relevant technical department. All technical details are subject to change without notice.
HYDAC ELECTRONIC GmbH Hauptstrasse 27, D-66128 Saarbruecken Telephone +49 (0)6897 509-01 Fax +49 (0)6897 509-1726 E-mail: [email protected] Internet: www.hydac.com
Connector
impact protection metal safety sleeve
Snubber Ø 0,5
Status 2017-01-18
Description: These HDA 8400 versions of pressure transmitters are specially developed for the use with the medium hydrogen and for series applications, e.g. in the mobile sector. As with most of the HYDAC pressure transmitters, the HDA 8400 have a robust and long-life measurement cell with thin-film strain gauge. All of the parts getting in contact with media (sensor cell and mechanical connection) are made of stainless steel and are welded together with each other. This means that there are no sealing points in the interior of the sensor hence no chance of leakage. Due to the specially selected material, these HDA 8400 are suited for the use in hydrogen applications.
Pressure Transmitter
HDA 8400 for medium hydrogen (Minimum order quantity 500 units)
Technical data: Input data
Measuring range 25 40 60 100 160 250 400 600 900 1050
Overload pressure 50 80 120 200 320 500 800 1000 1400 1400
Burst pressure 125 200 300 500 800 1250 2000 3000 3000 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm, 20 Nm at 900 bar) G 1/4 B DIN EN 837 (20 Nm) 9/16-18 UNF 2A (ISO 8434-3) (25 Nm)
Parts in contact with medium Stainless steel 1.4435 (Ni content 13 %)
Seal: Copper (Cu-DHP) (G 1/4 B); Zurcon22
(Polyurethane) (9/16-18 UNF 2A)
Output data
Output signal 4 .. 20 mA, ratiometric, many others possible
Accuracy acc. to DIN 16086, at limit setting
± 0.5 % FS typ.
± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L) ± 0.25 % FS typ.
± 0.5 % FS max.
Temperature compensation zero point
± 0.015 % FS / °C typ.
± 0.025 % FS / °C max.
Temperature compensation over range
± 0.015 % FS / °C typ.
± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
± 0.3 % FS max.
Hysteresis ± 0.4 % FS max.
Repeatability ± 0.1 % FS
Rise time < 2 ms
Long-term drift ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range - 25 .. 85 °C
Operating temperature range - 40 .. 100 °C
Storage temperature range - 40 .. 100 °C
Fluid temperature range - 40 .. 100 °C
- mark EN 61000-6-1 / 2 / 3 / 4
Vibration resistance acc. to DIN EN 60068-2-6 at 5 .. 2000 Hz
25 g
Shock resistance acc. to DIN EN 60068-2-27
100 g / 6 ms / half sine 500 g / 1 ms / half sine
Ingress protection acc. to DIN EN 60529 1) ISO 20653 1)
IP 67 IP 6K9K
Other Data
Supply voltage when used acc. to UL specifications
8 .. 30 V DC; 5 V DC ± 5 % (ratiometric) – limited energy – acc. to 9.3 UL 61010; Class 2; UL 1310/1585; LPS UL 60950
Residual ripple of supply voltage 5 %
Electrical connection 2) M12x1, 4 pol., plastic or metal (solid version) Metri-Pack series 150, 3 pole
Life expectancy > 1 million load cycles (0 .. 100 % FS)
Weight approx. 55 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit
protection are provided. FS = Full Scale = relative to complete measuring range,
B.F.S.L. = Best Fit Straight Line 1)
With mounted female connector having the corresponding protection class. 2)
Other connectors / options are available on request.
Relative pressure Accuracy 0.5 %
Dimensions:
Pin connections:
M12x1, 4 pole
Pin
1 + signal
2 n.c.
3 - signal
4 n.c.
Metri-Pack, 3 pole
Pin
1 - signal
2 + signal
3 n.c.
HYDAC ELECTRONIC GMBH Hauptstrasse 27, D-66128 Saarbrücken Phone: +49 (0)6897 / 509-01 Fax: +49 (0) 6897 / 509-1726 e-mail: [email protected] Internet: Global Presence. Local Expertise. www.hydac.com
Note: The information in this brochure relates to the operating conditions and applications described. For applications and operating conditions not described. please contact the relevant technical department. Subject to technical modifications.
Male
connection
Orifice
Status 2017-01-18
Description: These HDA 8400 versions of pressure transmitters are specially developed for the use with the medium hydrogen and for series applications, e.g. in the mobile sector. As with most of the HYDAC pressure transmitters, the HDA 8400 have a robust and long-life measurement cell with thin-film strain gauge. All of the parts getting in contact with media (sensor cell and mechanical connection) are made of stainless steel and are welded together with each other. This means that there are no sealing points in the interior of the sensor hence no chance of leakage. Due to the specially selected material, these HDA 8400 are suited for the use in hydrogen applications. All HDA 8400 have successfully passed the component testing for type approval according to EC 79-2009 / V0 406-2010.
Pressure Transmitter
HDA 8400 for medium hydrogen tested according to EC 79 (Minimum order quantity 500 units)
Technical data: Input data
Measuring range 900
Nominal operating pressure 1) 700 1)
Maximum permitted operating pressure 1) 875 1)
Burst pressure 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (20 Nm) G 1/4 B DIN EN 837 (20 Nm) 9/16-18 UNF 2A (ISO 8434-3) (25 Nm)
Parts in contact with medium Stainless steel 1.4435 (Ni content 13 %)
Seal: Copper (Cu-DHP) (G 1/4 B); Zurcon22
(Polyurethane) (9/16-18 UNF 2A)
Output data
Output signal 4 .. 20 mA, ratiometric, many others possible
Accuracy acc. to DIN 16086 at limit setting
± 0.5 % FS typ.
± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L) ± 0.25 % FS typ.
± 0.5 % FS max.
Temperature compensation zero point
± 0.015 % FS / °C typ. ± 0.025 % FS / °C max.
Temperature compensation Span
± 0.015 % FS / °C typ. ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
± 0.3 % FS max.
Hysteresis ± 0.4 % FS max.
Repeatability ± 0.1 % FS
Rise time < 2 ms
Long-term drift ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range - 25 .. 85 °C
Operating temperature range - 40 .. 100 °C
Storage temperature range - 40 .. 100 °C
Fluid temperature range - 40 .. 100 °C
- mark EN 61000-6-1 / 2 / 3 / 4
Vibration resistance acc. to DIN EN 60068-2-6 at 5 .. 2000 Hz
25 g
Shock resistance acc. to DIN EN 60068-2-27
100 g / 6 ms / half sine 500 g / 1 ms / half sine
Ingress protection to DIN EN 60529 2) ISO 20653
IP 67 IP 6K9K
Other Data
Supply voltage when used acc. to UL specifications
8 .. 30 V DC; 5 V DC ± 5 % (ratiometric) – limited energy – according to 9.3 UL 61010; Class 2; UL 1310/1585; LPS UL 60950
Residual ripple of supply voltage 5 %
Electrical connection M12x1, 4 pol., plastic or metal (solid version) Metri-Pack series 150, 3 pole
Life expectancy > 1 million load cycles (0 .. 100% FS)
Weight approx. 55 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit
protection are provided. FS = Full Scale = relative to complete measuring range,
B.F.S.L. = Best Fit Straight Line 1)
Tested / validated according to EC 79/2009, nominal operating pressure 700 bar at reference temperature 20 °C, max. permitted operation pressure 875 bar
2) With mounted female connector having the corresponding protection class.
Relative pressure Accuracy 0.5 %
Dimensions:
Pin connections:
M12x1, 4 pole
Pin
1 + signal
2 n.c.
3 - signal
4 n.c.
Metri-Pack, 3 pole
Pin
1 - signal
2 + Signal
3 n.c.
HYDAC ELECTRONIC GMBH Hauptstrasse 27, D-66128 Saarbrücken Phone: +49 (0)6897 / 509-01 Fax: +49 (0) 6897 / 509-1726 e-mail: [email protected] Internet: www.hydac.com
Note: The information in this brochure relates to the operating conditions and applications described. For applications and operating conditions not described. please contact the relevant technical department. Subject to technical modifications.
Male
connection
Orifice
Status: 2017-08-04
Description: The HDA 4400 intrinsically safe pressure transmitters are specially developed for use with the medium hydrogen and in hazardeous areas. Their design is based on the HDA 4000 series. By the use of two extremely precise and robust stainless steel measuring cells with thin-film strain gauges, each with their own electronics, the sensor comes complete with a redundant architecture and as a result has two output signals separate and independent from each other. These two output signals are inverted (signal 1 = 4 .. 20 mA and signal 2 = 20 .. 4 mA). This causes that the energy within the intrinsically safe circuit is kept constant as at any pressure the sum of the two output signals is 24 mA. Connection is carried out via a two channel Ex approved zener barrier. The dual approval in accordance with ATEX and IECEx enables universal, almost world-wide utilisation of the devices in potentially explosive atmospheres. By means of their redundant setup the transmitters are best suitable for safety circuits or functions in oil and gas industry. The equipment also is applicable in mining industry and fields with high dust exposure. Therewith main fields of application are in intrinsic safety systems. The main fields of application are found in safety-related systems. Due to the specially selected material, these HDA 4400 are suited for the use in hydrogen applications. Protection types and applications:
ATEX I M1 Ex ia I Ma
II 1G Ex ia IIC T6, T5 Ga II 1/2 G Ex ia IIC T6, T5 Ga/Gb II 2 G Ex ia IIC T6, T5 Gb
II 1D Ex ia IIIC T85/T95 °C Da II 3G Ex nA IIC T6, T5, T4 Gc II 3G Ex ic IIC T6, T5, T4 Gc II 3D Ex ic IIIC T85/T95/T105 °C Dc
IECEx Ex ia I Ma
Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia IIC T6, T5 Gb Ex ia IIIC T85/T95 °C Da Ex nA IIC T6, T5, T4 Gc Ex ic IIC T6, T5, T4 Gc Ex ic IIIC T85/95/T105 °C Dc
Pressure Transmitter HDA 4400 Ex Applications Intrinsically safe, non sparking ATEX / IECEx, dual approval for medium hydrogen Redundant
Technical Data Input data
Measuring range Signal 1 bar 16 25 40 200 250 400 500 600 1050
Measuring range Signal 2 bar 16 25 40 200 250 400 500 600 1050
Overload range bar 50 50 80 500 500 800 1000 1000 1400
Burst pressure bar 125 125 200 1250 1250 2000 3000 3000 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm for measuring range ≤ 600 bar) (20 Nm for measuring range 1050 bar)
Parts in contact with fluid Stainless steel 1.4435 (Ni content ≥ 13 %) Measuring cells: gold-plated
Output data
Output signal 1 4 .. 20 mA, 2 conductor Output signal 2 20 .. 4 mA, 2 conductor Permitted resistance, each RLmax = (UB - 12 V) / 20 mA [kΩ]
Accuracy acc. to DIN 16086, at limit setting
≤ ± 0.5 % FS typ.
≤ ± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L.)
≤ ± 0.25 % FS typ.
≤ ± 0.5 % FS max.
Temperature compensation zero point
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Temperature compensation over range
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
≤ ± 0.3 % FS max.
Hysteresis ≤ ± 0.4 % FS max.
Repeatability ≤ ± 0.1 % FS
Rise time ≤ 2 ms
Long-term drift ≤ ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range -25 .. +85 °C
Operating/ ambient / fluid temperature range
T6, T85 °C Ta = -25 .. 60 °C T5, T95 °C Ta = -25 .. 70 °C T105 °C Ta = -25 .. 80 °C T4 Ta = -25 .. 85 °C
Storage temperature range -40 .. +100 °C
- mark EN 61000-6-1 / 2 / 3 / 4 EN 60079-0 / 11 / 15 / 26 EN 50303
Vibration resistance acc. to DIN EN 60068-2-6 at 10 .. 500 Hz
≤ 20 g
Ingress protection acc. to DIN EN 60529 1) IP 67
Relevant data for Ex applications Ex ia, ic Ex nA
Supply voltage 12 .. 28 V DC 12 .. 28 V DC
Max. input current Ii = 100 mA
Maximum input power Pi = 0.7 W max. power consumption ≤ 1W
Connection capacitance of sensor Ci ≤ 22 nF
Inductance of sensor Li = 0 mH
Safety barrier two channel, Rmin = 280 Ω (e.g. Pepperl & Fuchs Z789)
Insulation voltage 50 V AC, with integrated overvoltage protection to EN 61000-6-2
Other data
Residual ripple of supply voltage ≤ 5 %
Current consumption ≤ 25 mA
Life expectancy > 1 million cycles (0 .. 100 % FS)
Weight ~ 210 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override, and short circuit protection are provided. FS = Full Scale = bezogen auf den vollen Messbereich
B.F.S.L. = Best Fit Straight Line
1) with mounted mating connector in corresponding protection class
Relative pressure Accuracy 0.5 %
Status: 2017-08-04
Applications: Code used in Model code
1 9 C
ATEX KEMA 05 ATEX 1016X
I M1 Ex ia I Ma
II 1G Ex ia IIC T6, T5 Ga II 1/2G Ex ia IIC T6, T5 Ga/Gb II 1D Ex ia lIIC T85/T95 °C Da
II 2G Ex ia IIC T6, T5 Gb
II 3G Ex nA llC T6,T5 Gc II 3G Ex ic llC T6,T5 Gc ll 3D Ex ic lllC T85/T95°C Dc
IECEx KEM 08.0014X
Ex ia I Ma
Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia lIIC T85/T95 °C Da
Ex ia IIC T6, T5 Gb
Ex nA llC T6,T5 Gc Ex ic llC T6,T5 Gc Ex ic lllC T85/T95°C Dc
Application fields Mining Protection class: intrinsically safe ia with barrier
Gases / conductive dust Protection class: intrinsically safe ia with barrier
Gases Protection class: intrinsically safe ia with barrier
Gases Protection class: Non sparking nA
Gases/ conductive dust Protection class: intrinsically safe ic with barrier
Model Code:
HDA 4 4 C 6 – A A – XXXX – XXXX – E N X – H00
Mechanical connection C = SF250CX20, Autoclave (7/16-20 UNF 2B)
Electrical connection 6 = M12x1, 4 pole, male (mating connector not included)
Output signal 1 A = 4 .. 20 mA, 2 conductor
Output signal 2 A = 20 .. 4 mA, 2 conductor
Measuring ranges in bar (output signal 1) 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Measuring ranges in bar (output signal 2) 0016; 0025; 0040; 0200; 0250; 0400; 0500; 0600; 1050
Approval E = ATEX / IECEx
Insulation voltage N = 50 V AC to housing
Protection types and applications: ATEX IECEx
1 = I M1 Ex ia I Ma II 1G Ex ia IIC T6, T5 Ga II 1/2 G Ex ia IIC T6, T5 Ga/Gb II 2 G Ex ia IIC T6, T5 Gb II 1D Ex ia IIIC T85/T95 °C Da
Ex ia I Ma Ex ia IIC T6, T5 Ga Ex ia IIC T6, T5 Ga/Gb Ex ia IIC T6, T5 Gb Ex ia IIIC T85/T95 °C Da
9 = II 3G Ex nA IIC T6, T5 Gc Ex nA IIC T6, T5 Gc Only in conjunction with electrical connection „6“ and with the impact
protection metal safety sleeve (see instrument dimensions)
C = II 3G Ex ic IIC T6, T5 Gc II 3D Ex ic IIIC T85/T95°C Dc
Ex ic IIC T6, T5 Gc Ex ic IIIC T85/T95°C Dc
Modification number H00 = for hydrogen applications
Status: 2017-08-04
Instrument dimensions:
With impact protection metal safety sleeve: Protection types and applications (code) 9 The impact protection metal safety sleeve is included in the scope of supply. A straight mating connector is required for electrical connection. E.g. female connector M12x1,4 pole, straight, with 3m shielded cable: ZBE 06S-03, Part.no. 6098243
Pin connections: M12x1 connector
Pin HDA 44C6-AA
1 + Sig 1 (for output signal 1)
2 - Sig 1 (for output signal 1)
3 + Sig 2 (for output signal 2)
4 - Sig 2 (for output signal 2)
Note:
The information in this brochure relates to the operating conditions and applications described. For applications or operating conditions not described please contact the relevant technical department. All technical details are subject to change without notice.
HYDAC ELECTRONIC GmbH Hauptstrasse 27, D-66128 Saarbruecken Telephone +49 (0)6897 509-01 Fax +49 (0)6897 509-1726 E-mail: [email protected] Internet: www.hydac.com
Connector
impact protection metal safety sleeve
Snubber Ø 0,5
Status 2017-01-18
Description: These HDA 8400 versions of pressure transmitters are specially developed for the use with the medium hydrogen and for series applications, e.g. in the mobile sector. As with most of the HYDAC pressure transmitters, the HDA 8400 have a robust and long-life measurement cell with thin-film strain gauge. All of the parts getting in contact with media (sensor cell and mechanical connection) are made of stainless steel and are welded together with each other. This means that there are no sealing points in the interior of the sensor hence no chance of leakage. Due to the specially selected material, these HDA 8400 are suited for the use in hydrogen applications. All HDA 8400 have successfully passed the component testing for type approval according to EC 79-2009 / V0 406-2010.
Pressure Transmitter
HDA 8400 for medium hydrogen tested according to EC 79 (Minimum order quantity 500 units)
Technical data: Input data
Measuring range 900
Nominal operating pressure 1) 700 1)
Maximum permitted operating pressure 1) 875 1)
Burst pressure 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (20 Nm) G 1/4 B DIN EN 837 (20 Nm) 9/16-18 UNF 2A (ISO 8434-3) (25 Nm)
Parts in contact with medium Stainless steel 1.4435 (Ni content 13 %)
Seal: Copper (Cu-DHP) (G 1/4 B); Zurcon22
(Polyurethane) (9/16-18 UNF 2A)
Output data
Output signal 4 .. 20 mA, ratiometric, many others possible
Accuracy acc. to DIN 16086 at limit setting
± 0.5 % FS typ.
± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L) ± 0.25 % FS typ.
± 0.5 % FS max.
Temperature compensation zero point
± 0.015 % FS / °C typ. ± 0.025 % FS / °C max.
Temperature compensation Span
± 0.015 % FS / °C typ. ± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
± 0.3 % FS max.
Hysteresis ± 0.4 % FS max.
Repeatability ± 0.1 % FS
Rise time < 2 ms
Long-term drift ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range - 25 .. 85 °C
Operating temperature range - 40 .. 100 °C
Storage temperature range - 40 .. 100 °C
Fluid temperature range - 40 .. 100 °C
- mark EN 61000-6-1 / 2 / 3 / 4
Vibration resistance acc. to DIN EN 60068-2-6 at 5 .. 2000 Hz
25 g
Shock resistance acc. to DIN EN 60068-2-27
100 g / 6 ms / half sine 500 g / 1 ms / half sine
Ingress protection to DIN EN 60529 2) ISO 20653
IP 67 IP 6K9K
Other Data
Supply voltage when used acc. to UL specifications
8 .. 30 V DC; 5 V DC ± 5 % (ratiometric) – limited energy – according to 9.3 UL 61010; Class 2; UL 1310/1585; LPS UL 60950
Residual ripple of supply voltage 5 %
Electrical connection M12x1, 4 pol., plastic or metal (solid version) Metri-Pack series 150, 3 pole
Life expectancy > 1 million load cycles (0 .. 100% FS)
Weight approx. 55 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit
protection are provided. FS = Full Scale = relative to complete measuring range,
B.F.S.L. = Best Fit Straight Line 1)
Tested / validated according to EC 79/2009, nominal operating pressure 700 bar at reference temperature 20 °C, max. permitted operation pressure 875 bar
2) With mounted female connector having the corresponding protection class.
Relative pressure Accuracy 0.5 %
Dimensions:
Pin connections:
M12x1, 4 pole
Pin
1 + signal
2 n.c.
3 - signal
4 n.c.
Metri-Pack, 3 pole
Pin
1 - signal
2 + Signal
3 n.c.
HYDAC ELECTRONIC GMBH Hauptstrasse 27, D-66128 Saarbrücken Phone: +49 (0)6897 / 509-01 Fax: +49 (0) 6897 / 509-1726 e-mail: [email protected] Internet: www.hydac.com
Note: The information in this brochure relates to the operating conditions and applications described. For applications and operating conditions not described. please contact the relevant technical department. Subject to technical modifications.
Male
connection
Orifice
Status 2017-01-18
Description: These HDA 8400 versions of pressure transmitters are specially developed for the use with the medium hydrogen and for series applications, e.g. in the mobile sector. As with most of the HYDAC pressure transmitters, the HDA 8400 have a robust and long-life measurement cell with thin-film strain gauge. All of the parts getting in contact with media (sensor cell and mechanical connection) are made of stainless steel and are welded together with each other. This means that there are no sealing points in the interior of the sensor hence no chance of leakage. Due to the specially selected material, these HDA 8400 are suited for the use in hydrogen applications.
Pressure Transmitter
HDA 8400 for medium hydrogen (Minimum order quantity 500 units)
Technical data: Input data
Measuring range 25 40 60 100 160 250 400 600 900 1050
Overload pressure 50 80 120 200 320 500 800 1000 1400 1400
Burst pressure 125 200 300 500 800 1250 2000 3000 3000 3000
Mechanical connection (torque value, recommended)
SF250CX20, Autoclave (7/16-20 UNF 2B) (15 Nm, 20 Nm at 900 bar) G 1/4 B DIN EN 837 (20 Nm) 9/16-18 UNF 2A (ISO 8434-3) (25 Nm)
Parts in contact with medium Stainless steel 1.4435 (Ni content 13 %)
Seal: Copper (Cu-DHP) (G 1/4 B); Zurcon22
(Polyurethane) (9/16-18 UNF 2A)
Output data
Output signal 4 .. 20 mA, ratiometric, many others possible
Accuracy acc. to DIN 16086, at limit setting
± 0.5 % FS typ.
± 1.0 % FS max.
Accuracy at minimum setting (B.F.S.L) ± 0.25 % FS typ.
± 0.5 % FS max.
Temperature compensation zero point
± 0.015 % FS / °C typ.
± 0.025 % FS / °C max.
Temperature compensation over range
± 0.015 % FS / °C typ.
± 0.025 % FS / °C max.
Non-linearity at max. setting acc. to DIN 16086
± 0.3 % FS max.
Hysteresis ± 0.4 % FS max.
Repeatability ± 0.1 % FS
Rise time < 2 ms
Long-term drift ± 0.3 % FS typ. / year
Ambient conditions
Compensated temperature range - 25 .. 85 °C
Operating temperature range - 40 .. 100 °C
Storage temperature range - 40 .. 100 °C
Fluid temperature range - 40 .. 100 °C
- mark EN 61000-6-1 / 2 / 3 / 4
Vibration resistance acc. to DIN EN 60068-2-6 at 5 .. 2000 Hz
25 g
Shock resistance acc. to DIN EN 60068-2-27
100 g / 6 ms / half sine 500 g / 1 ms / half sine
Ingress protection acc. to DIN EN 60529 1) ISO 20653 1)
IP 67 IP 6K9K
Other Data
Supply voltage when used acc. to UL specifications
8 .. 30 V DC; 5 V DC ± 5 % (ratiometric) – limited energy – acc. to 9.3 UL 61010; Class 2; UL 1310/1585; LPS UL 60950
Residual ripple of supply voltage 5 %
Electrical connection 2) M12x1, 4 pol., plastic or metal (solid version) Metri-Pack series 150, 3 pole
Life expectancy > 1 million load cycles (0 .. 100 % FS)
Weight approx. 55 g
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit
protection are provided. FS = Full Scale = relative to complete measuring range,
B.F.S.L. = Best Fit Straight Line 1)
With mounted female connector having the corresponding protection class. 2)
Other connectors / options are available on request.
Relative pressure Accuracy 0.5 %
Dimensions:
Pin connections:
M12x1, 4 pole
Pin
1 + signal
2 n.c.
3 - signal
4 n.c.
Metri-Pack, 3 pole
Pin
1 - signal
2 + signal
3 n.c.
HYDAC ELECTRONIC GMBH Hauptstrasse 27, D-66128 Saarbrücken Phone: +49 (0)6897 / 509-01 Fax: +49 (0) 6897 / 509-1726 e-mail: [email protected] Internet: Global Presence. Local Expertise. www.hydac.com
Note: The information in this brochure relates to the operating conditions and applications described. For applications and operating conditions not described. please contact the relevant technical department. Subject to technical modifications.
Male
connection
Orifice