rego section 2 2006 - gas · pdf filedevices used for handling lp gas and anhydrous ammonia...

20
231 Dispensing Units Dispensing IMPORTANT INFORMATION: Product must be installed and used in strict conformance with NFPA Pamphlet 58 and/or NFPA Pamphlet 54 and all other codes, regulations and manufac- turer recommendations. Failure to follow these codes, regulations and recommendations could result in hazardous installation, bodily injury and/or death. PRODUCT TRAINING SCHOOLS AVAILABLE. Contact a GEC customer service representative for more information. WARNING: LP Gas is extremely flammable and explosive. Devices used for handling LP Gas and Anhydrous Ammonia must be installed and used in strict conformance with NFPA Pamphlet 58 and 54 and all other codes, regulations and manufacturer recommendations.

Upload: vandung

Post on 28-Feb-2018

218 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

231

Dispensing UnitsD

ispensing

IMPORTANT INFORMATION: Product must be installed and used in strict conformance with NFPA Pamphlet 58 and/or NFPA Pamphlet 54 and all other codes, regulations and manufac-turer recommendations.

Failure to follow these codes, regulations and recommendationscould result in hazardous installation, bodily injury and/or death.

PRODUCT TRAINING SCHOOLS AVAILABLE. Contact a GECcustomer service representative for more information.

WARNING: LP Gas is extremely flammable and explosive.Devices used for handling LP Gas and Anhydrous Ammonia mustbe installed and used in strict conformance with NFPA Pamphlet58 and 54 and all other codes, regulations and manufacturer recommendations.

Page 2: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

232

Dispensing UnitsD

ispe

nsin

g

GEC Dispenser Specification Design Form

STEP 1: Pick Your Cabinet Style Blackmer (LGF1P) Corken (C12)

No Cabinet - Pump/Meter Assy DU1 (pg 233) . . . . . . . . . . . . . . .� DU12 (pg 233) . . . . . . . . . . .�

Cabinet - Small

• Aluminum………………... DCS48DP.B1 (pg 233) . . . . . . .� DCS48DP.C12 (pg 233) . . .�• Galvanized………………. DCS59GAL.B1 (pg 234) . . . . . .� DCS59GAL.C12 (pg 234) . .�• White Enamel…………… DCS46PT.B1 . . . . . . . . . . . . . . .� DCS46PT.C12 (pg 234) . . . .�

Cabinet - Large

• Aluminum………………... DCL51DP.B1 (pg 235) . . . . . . .� DCL51DP.C12 (pg 235) . . . .�• Stainless Steel………….. DCL51SS.B1 (pg 236) . . . . . . .� DCL51SS.C12 (pg 236) . . .�• White Enamel…………… DCL49PT.B1 . . . . . . . . . . . . . . .� DCL49PT.C12 (pg 236) . . . .�

Cabinet - Large Walk-In

• Aluminum………….......... DCWI75DP.B1 (pg 237) . . . . . .� DCWI75DP.C12 (pg 237) . .�

Note: All dispensers include Pre-plumbed assembly connecting Pump, 1” Neptune meter, Veeter-Root display only register on base with all valvesand an explosion-proof on/off switch assembly. Standard configuration has outlet for cylinder filling (CFH) before the meter and motor fueling outlet(MFH) after the meter with Pullaway hose. B2T Pump Bypass to Tank fitting kit and V2T Vapor return from Meter to Tank fitting kit. (Customer to pro-vide tubing for Pump Bypass & meter vapor return.)

STEP 2: Pick Your Hoses SEE Hose Assemblies - Page 238

MFHP Standard - Motor fuel hose (18’ Parker hose with A7793A Low Loss Valve/Nozzle & A2141A6L Pullaway) ....................................................�MFHP Economy - Motor fuel hose (3⁄4” x18’ Parker hose with 7554LV valve/A7575L3 Coupling & A2141A6L Pullaway) ............................................�MFHP Gasguard - Motor fuel hose ( 3⁄4” x18’ Parker hose with Gasguard LG1E safety nozzle & A2141A6L Pullaway) ..............................................�CFH Standard - Cylinder hose ( 1⁄2” x 6’ Parker hose with RegO 7901TB Quick-acting valve & 7193D-10 coupling)...................................................�CFH Long - Cylinder hose ( 1⁄2” x 10’ Parker hose/RegO 7901TB quick-acting valve & 7193D-10 coupling) ................................................................�

STEP 3: Pick Your Piping Kit SEE Installation Piping Kits - Page 239

T2P-1 - Tank to Pump piping kit for 1” inlet pump (Blackmer LGF1P) ...........................................................................................................................�T2P-114 - Tank to Pump piping kit for 1 1⁄4” inlet pump (Corken C10 & Blackmer LGLF1-14 & LGL1-14).....................................................................�T2P-112 - Tank to Pump piping kit for 1 1⁄2” inlet pump (Corken C12) ............................................................................................................................�DU-3Way - Optional 3-Way valve & components for CFH & MFH to be configured downstream of meter to meet NIST code ...............................................�

STEP 4: Select Your Options SEE Options - Page 240

TL36 - Tank Leg Stands (pair) with bolts .......................................................................................................................................................................�1124 - Fairbanks Beam Scale (1,000 lb capacity) .........................................................................................................................................................�400051-E1000 - Itron/Neptune Electronic register meter ..............................................................................................................................................�601010-000 - E1000 electronic register only .................................................................................................................................................................�MA-4-CX-10 - Liquid Controls standard meter w/air eliminator, strainer, differential valve and counter .......................................................................�ECK - Electrical Conduit Kit is pre-installed rigid conduit, junction boxes, seal-offs & union (NOTE: Electrician to supply properly sized wire & install

sealant in seal-off fitting.) ....................................................................................................................................................................................�DUPK - Pre-installed cylinder vapor purging system mounted to interior of cabinet ....................................................................................................�CK - Cable Kit Components to provide cable operation of 1 1⁄4” internal valve from inside cabinet...............................................................................�DURESS Kit - Components to provide externally mounted remote cable & thermal closure of A3209 internal valve.................................................�PK - Pneumatic Kit Components to provide remote pneumatic operation and thermal protection of internal valves...................................................�

Page 3: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

233

Dispensing UnitsD

ispensing

Diamond Plate - Closed

DCS48DP.B1 (Shown with options: MFHP Standard & CFH installed)

DCS48DP.C12 (Shown with options: MFHP Standard & CFH installed)

DU1 with 929980 switch DU12

CABINETS - SMALL (Actual Product May Vary From Photos)

MOTOR FUEL DISPENSING UNITS (Actual Product May Vary From Photos)

No Cabinet - Pump/Meter Assembly

Dimensions• 48”H x 36”W x 20”D

Page 4: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

234

Dispensing UnitsD

ispe

nsin

g

CABINETS - SMALL (con’t.) (Actual Product May Vary From Photos)

White Enamel - Closed

DCS46PT.C12 (Shown with options: MFHP Economy &CFH installed)

Dimensions• 46”H x 40”W x 18”D

DCS59GAL.B1

Galvanized - Closed

Dimensions• 59”H x 36”W x 20”D

DCS59GAL.C12

Page 5: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

235

Dispensing UnitsD

ispensing

CABINETS - LARGE (Actual Product May Vary From Photos)

Diamond Plate - Closed

DCL51DP.B1 (Shown with options: MFHP Standard & CFH installed)

DCL51DP.C12 (Shown with options: MFHP Standard & CFH installed)

Dimensions• 51”H x 47 1⁄2”W x 39 1⁄2”D

Page 6: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

236

Dispensing UnitsD

ispe

nsin

g

DCL51SS.B1 (Shown with options: MFHP Standard & CFH installed)

Stainless Steel - Closed

DCL51SS.C12 (Shown with options: MFHP Standard& CFH installed)

White Enamel - Closed

DCL49PT.C12 (Shown with options: MFHP Economy& CFH installed)

CABINETS - LARGE (con’t.) (Actual Product May Vary From Photos)

Dimensions• 51”H x 47 1⁄2”W x 39 1⁄2”D

Dimensions• 49”H x 44”W x 38”D

Page 7: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

237

Dispensing UnitsD

ispensing

CABINETS - WALK-IN (Actual Product May Vary From Photos)

Diamond Plate Walk-In - Closed

DCWI75DP.B1 (Shown with options: MFHP Standard, CFH & 1124-Scale installed)

Dimensions• 75”H x 48”W x 54”D

Storage shelving - The GEC walk-in cabinet featurestwo exclusive shelves for tickets, gloves, tools, &adapters on either side of the meter.

DCWI75DP.C12 Same as above but with a Corken pump installed instead ofBlackmer pump.

Page 8: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

238

Dispensing UnitsD

ispe

nsin

g

HOSE ASSEMBLIES (Actual Product May Vary From Photos)

MFHP Standard (shown with Pullaway)

MFHP Gasguard (shown with Pullaway)

MFHP Economy (shown with Pullaway)

CFH

GEC is proud to be a Parker Hose Distributor participating in the “Circle of Safety”, a certifiedprogram incorporating specific procedures and documentation for the fabrication and testingof safe reliable hose assemblies. All Parker Hose assemblies sold by GEC are fabricated andfully pressure tested by Parker to the “Circle of Safety” certified procedure.

Parker Technical Bulletin: LPG – Hose Evacuation Process

During the life of an LPG hose assembly, it may become necessary to evacuate the propane from the hoseassembly. This is often done by opening the valve on the hose end and venting to the atmosphere. If this evacuation isperformed rapidly, it may be detrimental to the hose and cause premature hose failure.

During the use of an LPG assembly, propane will permeate through the wall of the hose. This is a known phe-nomenon and regulatory agencies such as UL have maximum allowable rates of permeation (UL21-171 cc/ft/hr). Thecover of the hose is perforated to allow this permeating gas to escape, and prevent it from being trapped between thereinforcement and the cover where it may create cover separation and blistering.

In the process of evacuating an LPG hose assembly, LPG that is permeating through the wall of the hose maybecome trapped between the reinforcement layers and the inner liner of the hose. As the pressure is released from insidethe hose the LPG that is trapped between the inner liner and the reinforcement will expand as it vaporizes. The forceand volume change created by the vaporization may separate the inner liner from the reinforcement and create a tubecollapse and a hose failure.

To minimize the potential for this failure, the propane should be evacuated at as slow a rate as possible in orderto allow the pressure inside the hose wall to dissipate as much as possible.

Page 9: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

239

Dispensing UnitsD

ispensing

INSTALLATION PIPING KITS (Actual Product May Vary From Photos)

T2P-1 - Tank to pump piping kit

DU-3Way - Optional 3-Way valve for CFH & MFH to beconfigured downstream of meter to meet NIST code.

T2P-1 - Plumbing kit assembled

DURESS Kit - Shown installed with customer provided Unistrut and PE pipe handle.

A3209TL - Thermal latch

B2TBypass to Tank Fittings

V2TMeter Vapor Releaseto Tank Fitting

These items are includedin the Standard Cabinet.

OPTIONS

Page 10: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

240

Dispensing UnitsD

ispe

nsin

g

OPTIONS (Actual Product May Vary From Photos)

TL36 - Tank leg stands

1124 - Fairbanks beam scale(Platform-17 3⁄4” x 23 1⁄2”; Base-21” x 36”; Overheight-43”)

400051-E1000 - Itron/Neptune electronicregister/meter

ECK - Pre-installed electrical conduit

DUPK - cylinder vapor purging kit with purgeexhaust pipe and tank regulator/fittingsPK - pnematic kit

DURESS kit

601010-000 - Itron/Neptune electronic regis-ter ONLY

Connections to tank servicevalve

1

2

3

4

LEGEND1-Pump Bypass2-Meter Vapor Return3-Pneumatic Kit4-Purging Kit

CK - Cable kit

MA-4-CX-10

Page 11: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

241

Dispensing UnitsD

ispensing

Electrical Conduit Kit (ECK) Option For Dispensers(Actual Product May Vary From Photos)

Electrical option includes rigid conduit and junction box installed fromswitch to motor and from switch to external stub for power connection.

NOTE: An Electrician is still required to complete installation. Alsoincluded is the sealing cement kit for electrician to seal the switch.

The junction box includes a stub thru the back panel with union for simpleelectrical hook-up.

Electrical option includes rigid conduit and junction box installed from switch tomotor and from switch to external stub for power connection.

NOTE: An Electrician is still required to complete installation. Also included is thesealing cement kit for electrician to seal the switch.

The junction box includes a stub thru the back panel with union for simple electricalhook-up.

Electrical option includes rigid conduit and junction box installed fromswitch to motor and from switch to external stub for power connection.

NOTE: Electrician is still required to complete installation. Also includedis the sealing cement kit for the electrician to seal the switch.

Conduit is stubbed thru back panel with union for simple hook-up.

Electrical option includes rigid conduit and junction box installed from switch tomotor and from switch to external stub for power connection.

NOTE: Electrician is still required to complete installation. Also included is thesealing cement kit for the electrician to seal the switch.

Conduit is stubbed thru back panel with union for simple hook-up.

Page 12: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

242

Dis

pens

ing

Dispensing Unit Accessories

“GASGUARD”, 2nd GENERATION,Nozzle For Safe Motor Fueling (GG20)New Features1.A more modern design, offering improved balance, less weight and higher flowrates, relative to system pressure drops than the previous LG1E design.

2. A new optional latching system which provides single handed action and bet-ter control of the lever operation.

3. A longer high srength aluminum alloy connector casting with a stainless steelACME thread insert provides longer service without distortion and wear fordeep access filler valves.

4. New style plastic molded components; Comfigrip, Saddle and Lever.

Manchester Vertical Propane Dispenser

Complete Vertical Dispensing Pack age• Vertical tank package includes LP dispenser, X-frame for mount-ing tank, crash post and railing; valves and fittings

• Motor fuel dispensing unit DU1VB (Blackmer) or DU1VC (Corken)• Tank to pump piping kit• Bypass piping kit• Vapor return piping kit• Cable kit• Motor fuel hose assembly & cylinder fill hose assembly

Other Equipment Options• LC Meters• Various tank sizes (600, 1250, 1600, 2000 gallon)• Fairbanks scales

Features• Only 10 ft. dia. circle required for the tank• Highly visible package unit requires less installation time

Other configurations are available.

Best advertising space money can buy.

Features • Water based paint with no VOC’s.• Is not classified as a hazardousmaterial.• Will clean up with soap and water.• Is an optional solution to Carboline’s Pyrocrete for fire-proofing.• Can provide a 2-hour fire protection rating on LPG instal-lations (re: vertical tank legs) with sufficient coats.• Available in 1 or 5 gallon containers.

Contego Intumescent Latex (thin film) Passive Fire Barrier PaintContego Passive Fire Barrier is a heavy-bodied,single-part latex fire-proofing paint material. It is awater based product with no volatile organic com-pounds, is not classified as a hazardous material,and will clean up with soap and water. It is an alter-native solution to Carboline Pyrocrete cementitiousmaterial that can be used to fire-proof and providea 2-hour fire protection rating (with sufficient coats)on LPG installations (re: vertical tank legs).

Method:When activated by heat or flame, a dense carbonchar is formed separating and sheilding the sub-strate from heat while off gassing displaces oxygenfrom the treated surface; thus eliminating two of thethree components needed for combustion.

Part # DescriptionPFB-001W 1 Gallon BucketPFB-005W 5 Gallon Pail

Part # Description Connection Inlet SizeGG20 Dispenser nozzle 360° swivel 3/4”

Part # DescriptionGG3N Maintenance kit for GG20 nozzleLG/2 Inlet swivel assemblyLG3/1 Maintenance kit for LG1E nozzle

Accessories

Page 13: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

243

DispensingPlumbing Kits

Cylinder Filling & Motor Fuel Dispensing Pumps

C1A Piping Kit for C10 & C12 Pump

NOTE• All pipe shall be ASTM SCH80 or better.• All valves and fittings accessories to be a min i mum 250 psi working pressure.• All forged fittings to be a minimum 2,000 psi working pressure.• All shut-off valves shall be suitable for LP Gas service and designed for a rated working pressure of at least 250 psi.

Plumbing KitsInstallation Notes1.On 1" installation it is recommended that 1 1⁄4" pipe size beused up through Flex Connector (#11) and reduce down to 1"after union to pump.

2.On 1 1⁄2" pump installation we recommend that 1 1⁄4" pipe fromtank valve be increased in size to 1 1⁄2" after the ball valve (#5).

* Not included in kit.

1

2

3

4

56 7

8

9 10 11 12

Part # Description

T2P-1 itKgnibmulP"1

T2P-114 11 /4 tiKgnibmulP"

T2P-112 11 /2 tiKgnibmulP"

T2P-114 Parts Listing & Drawing Shown Below

Ref. # Part # Description1 A3209R050 Rego 1 1⁄4” Internal Valve

2 N-114X8 1 1⁄4” x 8” Sch80 Nipple

3 EL90-1142M 1 1⁄4” Sch80 Elbow

4 N-114X4 1 1⁄4” x 4” Sch80 Nipple

5 T-100-114 1 1⁄4” Ball Valve

6 N-114X18 1 1⁄4” x 18” Sch80 Nipple

7 STYLEB-DI-114 1 1⁄4” “Y” Strainer

8 034HXP 3⁄4” Sch80 Hex Plug

9 FH114X18 1 1⁄4” x 18” Flexline

10 FC-114-3M 1 1⁄4” Full Coupling

11 FH114X18-UNION 1 1⁄4” x 18” SS Flex Hose w/XH Union

12 SN-114X100 1 1⁄4” x 1” Sch80 Swage Nipple

Ref. # Qty Part # Description

11 A3209D050 1-1/4” Internal Valve

1 A3209TL Thermal Latch Kit

2 1 T-100-114 1-1/4” Ball Valve

3 2 EL90-114-2M 1-1/4” 90°Elbow

4 1 STYLE B-DI-114 1-1/4” Strainer

4A 1 934 HXP 1/4” Forges Steel Hex Plug

5 1 FH114X18-UNION 1-1/4” x 18” Flex Connector w/ Union

6 1 BU112X114-2M 1-1/2” x 1-1/4” Bushing

7 3 N-114X4 1-1/4” x 4” Nipples

8 2 N-114X12 1-1/4” x 12” Nipples

9 2 N-114X2 1-1/4” x 2” Nipples

10 1 PL-631-54 Gauge Snubber

11 1 J1458 Pressure Gauge

12 1 SN-100X034 1” x 3/4” Swaged Nipple

13 1 034TEE-3M 3/4” Tee

14 1 N-034X3 3/4” x 3” Nipple

15 1 B166-12 3/4” Bypass

16 1 3127U 3/4” Relief Valve

17 1 3272G 3/4” Excess Flow Valve

18 1 BU034X012-2M 1/2” x 1/4” Bushing

19 1 E8LP2X10FT 1/2” Hose Assembly - 10 ft

20 1 7901TC 1/2” Quick Action Valve

21 1 3175B 1/2” Hose Coupling

22 1 U1-8E 1/2” Flare x 3/4” MIP Connector

23 1 2906E POL x 1/2” Flare Connector

24* 1 5764A Adapter 1/4” Female x 1-3/4” Acme

25* 1 7193D-10 POL Connector - 1/4” x POL Male

Page 14: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

244

Filling SystemD

ispe

nsin

g

Hydraulic Automatic Cylinder Filling System

Designed to provide accurate, economical filling of LP-Gas DOT and fork lift cylinders by weight. Filling stops automatically as the total weight of thecylinder reaches the amount pre-set on the scale. One individual can efficiently handle up to four cylinder filling operations simultaneously, to max-imize profits, increase efficiency and allow servicing of more customers.

Shut-off Valve

LP-Gas Supply

Hydrostatic Relief Valve

1

6 Strainer

7

8

3

Open

2

4 A,B

Closed

KeyNo. Description Size

PartNo.

Assembly for Fairbanks-Morse. Includes items 1 thru 8below. 7194MD

Assembly for Howe. Includes items 1 thru 8 below. 7194HD

1 Propane control valve1⁄2" NPT female, with

1⁄8" NPT femalehydraulic connection

7177

2 Master cylinder, withactuator lever

1⁄8" NPT hydraulicconnection 7188

3 Hydraulic hose assembly3⁄16" I.D. with 1⁄8"

NPT male ends, 431⁄2"overall length

7194-1

1-3Valve, Cylinder, and HoseAssembly for Fairbanks-Morse scales

— 7188MS

1-3 Valve, Cylinder, and HoseAssembly for Howe scales — 7188HS

4A

Bracket Kit for Fairbanks Morse scales, complete with screws, washers, nuts and instructions

— 7194M-3K

4B

Bracket kit for Howescales, complete withscrews, washers, nuts andinstructions

— 7194H-3K

5 Can of hydraulic fluid,complete with filling spout 11⁄2 ounce 7188-21

6 Propane filling hoseassembly

1⁄2" I.D., with1⁄2" NPT male ends.

72” overall lengthE8LP2X6FT

7 Quick-acting shut-off valve1⁄2" NPT inlet x1⁄4" NPT outlet 7901TB

8* Soft nose cylinderconnector

1⁄4" NPT male xPOL male 7193D-10

* Any of the RegO® hose end adapters for cylinder filling may be used with these systems. Seethe “Hose End Adapters for Cylinder Filling’’ sections of this catalog for ordering information.NOTE: Part No. 7188HS contains items 1, 2, 3, 4B and 5. Part No. 7188MS contains items

1, 2, 3, 4A and 5.

Page 15: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

245

Dispensing

Autogas

IMPORTANT INFORMATION: Product must be installed and used in strict conformance with NFPA Pamphlet 58 and/or NFPA Pamphlet 54 and all other codes, regulations andmanufacturer recommendations.

Failure to follow these codes, regulations and recommendationscould result in hazardous installation, bodily injury and/or death.

PRODUCT TRAINING SCHOOLS AVAILABLE. Contact a GECcustomer service representative for more information.

WARNING: LP Gas is extremely flammable and explosive.Devices used for handling LP Gas and Anhydrous Ammonia mustbe installed and used in strict conformance with NFPA pamphlet58 and 54 and all other codes, regulations and manufacturer recommendations.

Page 16: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

246

Heading goes hereD

ispe

nsin

gHeading goes hereHeading goes hereAutogas

LGL Autogas PumpDesigned for use with single and dual hose fuel dispensers inabove or under ground applications.

Part # GPM HP Inlet Outlet RPMMaximumWorkingPressure

MaximumDifferentialPressure

MountingReliefValveSetting

LGL154 11.2 3 2” ANSI 300#Raised Face

Flange (8) Bolt

1.5” ANSI 300#Raised Face

Flange (4) Bolt

1,750 @60 Hz

425 PSI140 PSI

Rigid Baseor C-Face

225 PSILGL156 21 5 160 PSILCL158 32.3 7.5 200 PSI

Part # GPM HP Inlet Outlet RPMMaximumWorkingPressure

MaximumDifferentialPressure

Mounting

FF07522.5 7.5

1.5” ANSI 300#Raised Face

Flange

1” ANSI 300#Raised Face

Flange

3,450 @ 60 Hz or2,880 @ 50 Hz

400 PSI

150 PSIRigid Base

DLF075 C-Face

FF15033.8 10 250 PSI

Rigid Base

DLF150 C-Face

Corken Autogas PumpModel 075 is designed for one dual hose dispenser while the model 150 is designedfor two dual hose dispensers. The autogas series was designed for applicatons thatrequire a low flow rate and horsepower yet high differential pressure.

Rigid Base Mount

C-Face Mount

Part # Inlet/Outlet Differential Pressure Range

B166-1CAV 1” 100-225 PSI

Bypass Valve

Page 17: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

247

AutogasD

ispensing

PRO2100 Propane DispenserAttractive cabinet design• Option for Stainless Steel Cabinet• Option for Galvanized with vinyl wrap• Option for Powder Painted in company colors• Gas Pump style nozzle boot• Convenient On-Off Button switch, light when on• Small profile, easy mount baseLiquatech LPM 102 meter standard• Option for LC MA-4 & Tuthill Systems• Option for pump and motor includedCFT Electronic Dispensing Computer• 3 display, full retail, with total sale, price per gallon and gallons pumped• Electronic keypad with 5 programmable price levels, selectable by operator• Shift log in & log out with passcode for operator• Dispenser lock down with pass code, no need for pad locks• Integrated pump control• Fuel management system integration standard• Gilbarco 2 wire protocol embedded for Retail gas station integration• Electronic automatic temperature compensation• Electronic calibrationImproved Hydraulics• Inlet & return ball valve for service isolation• Reduced potential leaks with mono-block inlet & outlet (CFT Exclusive)• Solenoid flow control for accuracy & positive shutoff

PRO6100 Propane Dispenser (Single Hose, Single display)PRO6200 Propane Dispenser (Dual Hose, Dual Display)• Standard meter has 3-18 gallons per minute flow rate• Explosion-proof junction box for safe electrical connections• Simple maintenance• Liquid inlet & vapor outlet gauges for diagnostics• 110 vac/60Hz OR 220vac/50 Hz power supply* Optional Hose-end Safety Nozzles for dispensing propane in the safest manner possible.• Separate display for functions & programming• 16-key alpha-numeric keypad• 5-level secured access programming• Communicates to most fuel management systems and uses Gilbarco 2-wire communication

protocol• White powder-coated cabinet standard* Custom Vinyl Wrap optional• Computerized volume/price calculator• Self diagnostics for troubleshooting• Lexan display panel• Optional stainless steel cabinet available• Easy-to-read back-lit LCD displays

Page 18: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

248

AutogasD

ispe

nsin

g

PRO7100 Propane Dispenser (Single Hose, Single display)PRO7200 Propane Dispenser (Dual Hose, Dual Display)• Dispensers can fill all ASME and DOT tanks• Standard meter has 3-18 gallons per minute flow rate• Explosion-proof junction box for safe electrical connections• Simple maintenance• Liquid inlet & vapor outlet gauges for diagnostics• 110 vac/60Hz OR 220vac/50 Hz power supply

* Optional Hose-end Safety Nozzles for dispensing propane in the safest mannerpossible.

• Separate display for functions & programming• 16-key alpha-numeric keypad• 5-level secured access programming• Communicates to most fuel management systems and uses Gilbarco 2-wire communication

protocol• White powder-coated cabinet standard

* Custom Vinyl Wrap optional• Computerized volume/price calculator• Self diagnostics for troubleshooting• Lexan display panel• Optional stainless steel cabinet available• Easy-to-read back-lit LCD displays

Gilbarco® Encore® S• Retail style propane dispenser• Dispensers can fill all ASME and DOT tanksStandard features:• Gilbarco® Encore® S platform electronics• CRIND and pump interface with Passport®, G-SITE® and most third party POS systems• Capable of stand alone operation• Automatic temperature compensation (ATC) for propane• Flow rate meter (2 - 40 gallons per minute)• Rego breakaway hose - 8’ standard• GG20 Gasguard nozzle for LPG autogasAvailable options:• Mono CRIND® Card Reader in Dispenser (PCI complaint)• Extended hose• Tripod safety mounting system• Standard and customized graphics packages• Extended Warranty

Pending NTEP and UL approval

Page 19: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

249

AutogasD

ispensing

LPG Autogas Tankless Skid PackagePre-Assembled & tested, fully integrated design. Ready to installexisting customer tanks (tank must meet minimum requirements)with just hook up the electricity, connect to tank and go! Requiresminimal additional materials, just mount tank, connect vapor return,bypass return and pump supply, and it is ready for service!

- Can control Pneumatic internal valves in ALL tank openings,liquid feed to pump, bypass & vapor return. Minimumrequirement of 1-1/4” bottom liquid opening for internal valveinstallation

- Welded 3” channel frame, adjustable for expansion, heavy vinylcoating for long life durability

- Corken DLF-075 pump with single or 3 phase motor – 18 gpmrating.

- Pre installed B166-CAU bypass an inlet flange set.- All piping pre assembled with flexible isolation in & out of pump with protective coating and

paint. Kit includes flex hoses, vapor valves with excess flows, and other hardware for bypassand vapor

- Ball valves for easy maintenance at all service points.- Inlet & outlet gauges for pump diagnostics- Pre wired with explosion proof junction box, large for accessories. Access room for card

reader- Optional base plate 2000, 3000, 6000 or 7000 series LPG dispensers with card reader

interface- Optional Tripod safety system (not available with tool box option on Pro- 2100 dispenser)- Designed to accommodate 2000, 3000, 6000 or 7000 series LPG dispensers with card reader

interface- Designed to accommodate Tripod Safety System (Optional kit)

1,000 or 2,000 Gallon Horizontal or Vertical LPG AutogasSkid PackageFeatures:Pre-Assembled and tested, fully integrated design. Ready to installwith minimal installation work requirements, just hook up withelectricity, fill with LPG and go!

- 1000 or 2000 gal horizontal tank on saddles, with 3 bottom openings,1-1/4”, powdercoated with side mounted valving for easy fill, gaugeread and access. Fully welded 6” x1/4” channel frame, with dispenserpad.

- 1000 or 2000 gal Vertical Tank with re-inforced legs, with 3 bottomopenings, powder-coated with side mounted valving for easy fill,gauge read and access. Fully welded 6” x1/4” channel frame, withdispenser pad.

- Pneumatic internal valves in ALL bottom outlets, liquid feed to pump,bypass liquid return, vapor return to tank.

- Corken DLF-075 pump with single or 3 phase motor – 18 gpm rating.- All piping pre assembled with flexible isolation in & out of pump withprotective coating and paint.- Ball valves for easy maintenance at all service points.- Strainer with service drain, conveniently located for easy access.- Inlet & outlet gauges for pump diagnostics- Pre wired with explosion proof junction box, large for accessories. Access room for card reader- 2000, 3000, 6000 or 7000 series LPG dispensers with card reader interface

Page 20: Rego Section 2 2006 - Gas · PDF fileDevices used for handling LP Gas and Anhydrous Ammonia must ... PK-pnema tic exhaust pipe and tank regulator/fittings ... Complete Vert i c al

250

AutogasD

ispe

nsin

g

LPG Autogas Mini Skid PackageFeatures:Pre-Assembled & tested, fully integrated system. Ready to install withminimal installation work requirements at the site.- Can control Pneumatic internal valves in ALL tank openings, liquid feed

to pump, bypass & vapor return.- Welded 3” channel frame, adjustable for expansion, heavy vinyl coating

for long life durability- Corken DLF-075 pump with single or 3 phase motor – 18 gpm rating.- Pre installed B166-CAU bypass an inlet flange set.- All piping pre assembled with flexible isolation in & out of pump with

protective coating and paint.- Ball valves for easy maintenance at all service points.- Inlet & outlet gauges for pump diagnostics- Pre wired with explosion proof junction box, large for accessories. Access

room for card reader- Optional base plate 2000, 3000, 6000 or 7000 series LPG dispensers

with card reader interface- Optional Tripod safety system (not available with tool box option on Pro-

2100 dispenser)

“GASGUARD”, 2nd GENERATION,Nozzle For Safe Motor Fueling (GG20)New Features1.A more modern design, offering improved balance, less weight and higher flow

rates, relative to system pressure drops than the previous LG1E design.2. A new optional latching system which provides single handed action and

better control of the lever operation.3. A longer high srength aluminum alloy connector casting with a stainless steel

ACME thread insert provides longer service without distortion and wear fordeep access filler valves.