reducing the cost of replacing failed condensate systems
TRANSCRIPT
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
1/25
REDUCING THE COST OFREPLACING FAILED
CONDENSATE PIPING
SYSTEMS
Mr. Larry Stonitsch, President
Rovanco Piping Systems, Inc.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
2/25
Several Ways Steam & Condensate Systems are
Installed: Detail A Above Ground
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
3/25
Several Ways Steam & Condensate Systems are
Installed: Detail B In a Tunnel
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
4/25
Several Ways Steam & Condensate Systems are
Installed: Detail C Shallow Concrete Trench
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
5/25
Several Ways Steam & Condensate Systems are
Installed: Detail D Direct Buried Dual Line Conduit
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
6/25
Several Ways Steam & Condensate Systems are
Installed: Detail E Direct Buried Single Line Conduit
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
7/25
Direct Buried Dual Line Conduit
System Prior to 1970
Both pipes were put into a common conduit because it was less expensive toinstall one outer protective conduit with several lines in it, i.e. a steam line, a
high pressure return and sometimes a gravity return.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
8/25
Direct Buried Dual Line Conduit
System Inefficiencies:
The condensate line would almost always fail far
sooner than the steam line. If the condensate line developed leaks there was no
way to replace the line without cutting open the
outer conduit, replacing the corroded line andclosing it up again.
If the condensate line was severely corroded it
would usually saturate the insulation on the steamline requiring it to be replaced.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
9/25
Current Day Single Line Direct Buried
Steam & Condensate System
It has been found to be more efficient and cost effective, over the life ofthe steam and condensate systems, to install separate steam and
condensate lines.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
10/25
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
11/25
Current Day Direct Buried Single
Line Conduit System Disadvantages:
During replacement of the condensate system,
the steam system gets damaged. Replacement of only the condensate line is still
relatively expensive due to trenching, backfilling
& restoration of the trench in addition to the costof the piping system, approximately $61,000 formaterial & labor.
Replacing both systems triples the cost toapproximately $184,000.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
12/25
Typical Direct Buried Single Line Steam &
Condensate System with Expansion Loops
This system is
manufactured withexpansion loops and
the pipe enteringmanholes and
buildings.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
13/25
Rovanco Designed System with Expansion
Joints or Bellows for the Condensate Line
An expansion bellow has been added to the
condensate line.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
14/25
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
15/25
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
16/25
If the Condensate Line Fails(cont): The pipe supports are designed with sled runners on all four fins (Detail 3-B
cross section). Once the condensate carrier pipe is cut loose, a 40 section can be removed and
the rest of the condensate line can be pulled out of the 10 gauge conduit and cutinto 40 sections (Detail 3-B).
Pulling Old Carrier Pipe Out of Conduit Detail 3-B
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
17/25
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
18/25
If the Condensate Line Fails(cont):The supports are galvanized so they should be in good condition and may bereused.
Pull ing New Carrier Pipe Into Exist ing Conduit Detail 3-D
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
19/25
Estimated Costs of this Piping
System: Cost of Pipe
Cost of Installation
1. Excavation
2. Installing the pipe
3. Closing up the joints
4. Backfilling
5. Reseeding or paving
NOTE: Cost estimates are based on Drawing 1 (sheet 1 of 4) as a Direct Buried
Conduit as per Detail E.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
20/25
Cost Estimate #1 STEAM LINE
334 lin ft of 8 Schedule 40 Carbon Steel with 2-1/2 of Mineral Wool Insulation in a
16 10 Gauge Steel Conduit with a Fusion Bonded Epoxy Protective Coating4 90 Elbows2 Anchors2 End Seals
CONDENSATE LINE320 lin ft of 3 Schedule 80 Carbon Steel with 1-1/2 of Mineral Wool Insulation in an8 10 Gauge Steel Conduit 20 Mil Thick with a Fusion Bonded Epoxy ProtectiveCoating
4 90 Elbows
2 Anchors2 End Seals
TOTAL INSTALLED COST: including all materials, excavation and backfilling,grading and surface repair, i.e., reseeding or resodding, pipe fitting, welding,pressure testing and commissioning of systems.
$198,000
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
21/25
Cost Estimate #2 STEAM LINE
334 lin ft of 8 Schedule 40 Carbon Steel with 2-1/2 of Mineral Wool Insulation in a
16 10 Gauge Steel Conduit with a Fusion Bonded Epoxy Protective Coating4 90 Deg Elbows2 Anchors2 End Seals
CONDENSATE LINE300 lin ft of 3 Schedule 80 Carbon Steel with 1-1/2 of Mineral Wool Insulation in an8 10 Gauge Steel Conduit 20 Mil Thick with a Fusion Bonded Epoxy ProtectiveCoating
Expansion Joint/Bellows
2 Anchors2 End Seals
TOTAL INSTALLED COST: the additional cost for the expansion devise is offset bythe elimination of four (4) 90 Elbows, 20 ft of Condensate Line, less excavating,
backfill and welding.
$198,000
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
22/25
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
23/25
Cost Estimate #4 Replace Condensate Piping by cutting out a 50 section and
replacing only the condensate pipe and mineral woolinsulation.
TOTAL INSTALLED COST:
Based on our estimates, the savings to the system ownerwould be $36,000 if this innovation is used to install andreplace the condensate line.
In addition to the monetary savings, less than 15% of the piperouting would be excavated. Therefore, the majority of thearea would be undisturbed and usable during the repair
period. Also, the construction period would be reduced by at least
50% from 30 days to 15 days.
$32,000
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
24/25
Additional Options for Replacing
the Condensate Line
Use a condensate pipe made of Stainless Steel. Additional cost for the
condensate pipe shown on drawing 1 would be $4,600.
Use a Schedule 160 Carbon Steel condensate pipe which is 3 times thicker
than Schedule 40 and should provide 30% longer life. Additional cost for
condensate pipe shown on drawing 1 would be $2,005.
Install condensate receivers in the building or manhole, vent the receivers to
reduce pressure and lower the temperature to below 212 F. In this type of
system you can send the condensate back to the boiler in a noncorrosive pipe
such as PEX or FRP. The initial installed cost of this would be 50% less on
drawing 1.
-
8/13/2019 Reducing the Cost of Replacing Failed Condensate Systems
25/25
QUESTIONS??
Contact:Mr. Larry Stonitsch
orMs. Brenda Nowatzki20535 SE Frontage Rd
Joliet, Illinois 60431Tel: (815) 741-6700Fax (815) [email protected]@rovanco.com