r86467 (1)

Upload: deyvi-mtz-hdez

Post on 14-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 r86467 (1)

    1/10

    Final Control Elements Characteristics

    In many control systems the rate of flow of a fluid along a pipe is

    controlled by a valve which uses pneumatic action to move a valve stem

    and hence a plug or plugs into the flow path, so altering the size of the

    gap through which the fluid can flow (Figure 6.21). The term single

    seatedis used where just one plus is involved and double seatedwherethere are two. A single-seated valve has the advantage compared with

    the double-seated valve of being able to close more tightly but the

    disadvantages that the force on the plug is greater from the fluid and so a

    larger area diaphragm may be needed.

    Figure 6.22 shows the basic elements of a common form of such a

    control valve. The movement of the stem, and hence the position of the

    plug or plugs in the fluid flow, results from the use of a diaphragm

    moving against a spring and controlled by air pressure (Figure 6.22).

    The air pressure from the controller exerts a force on one side of the

    diaphragm, the other side of the diaphragm being at atmospheric

    pressure, which is opposed by the force due to the spring on the other

    side. When the air pressure changes then the diaphragm moves until

    there is equilibrium between the forces resulting from the pressiu^e andthose from the spring. Thus the pressure signals from the controller

    result in the movement of the stem of the valve. There are two alternative

    forms, directand reverse action forms (Figure 6.23) with the difference

    being the position of the spring. The valve body is joined to the

    diaphragm element by the yoke.

  • 7/29/2019 r86467 (1)

    2/10

  • 7/29/2019 r86467 (1)

    3/10

    6.4.1 Forms of plug

    There are many forms of valve body and plug. The selection of the form

    of body and plug determine the characteristic of the control valve, i.e. the

    relationship between the valve stem position and the flow rate through it.

    For example. Figure 6.24 shows how the selection of plug can be used to

    determine whether the valve closes when the controller air pressure

    increases or opens when it increases and Figure 6.24 shows how the

    shape of the plug determines how the rate of flow is related to the

    displacement of the valve stem:

    1Linear plug

    The change in flow rate is proportional to the change in valve stem

    displacement, i.e.:change in flow rate = k(change in stem displacement)

    where it is a constant. IfQ is the flow rate at a valve stem

    displacement Sand ^max is the maximum flow rate at the maximum

    stem displacement S'max, then we have:

    or the percentage change in the flow rate equals the percentage

    change in the stem displacement. Such valves are widely used forthe control of liquids entering cisterns when the liquid level is being

  • 7/29/2019 r86467 (1)

    4/10

    controlled.

    2 Quick-opening plug

    A large change in flow rate occurs for a small movement of the

    valve stem. This characteristic is used for on-oflf control systems

    where the valve has to move quickly from open to closed and vice

    versa.

    3Equal percentage plugThe amount by which the flow rate changes is proportional to the

    value of the flow rate when the change occurs. Thus, if the amount

    by which the flow rate changes is Ag for a change in valve stem

    position A5, then it is proportional to the value of the flow Q when

    the change occurs, i.e.

    where k is a constant. Generally this type of valve does not cut off

    completely when at the limit of its stem travel, thus when S = 0 we

    have Q = gmin. If we write this expression for small changes and

    then integrate it we obtain:

    And so

  • 7/29/2019 r86467 (1)

    5/10

    Example

    A valve has a stem movement at full travel of 30 mm and has a

    linear plug which has a minimum flow rate of 0 and a maximum

    flow rate of 20 mVs. What will be the flow rate when the stem

    movement is 15 mm?

    The percentage change in the stem position from the zero setting is

    (15/30) X 100 = 50%. Since tlie percentage flow rate is the same asthe percentage stem displacement, then a percentage stem

    displacement of 50% gives a percentage flow rate of 50%, i.e.

    10 mVs.

    ExampleA valve has a stem movement at full travel of 30 nun and an equal

    percentage plug. This gives a flow rate of 2 mVs when the stem

    position is 0. When the stem is at fiill travel there is a maximum

    flow rate of 20 mVs. What will be the flow rate when the stem

    movement is 15 mm?

    6.4.2 Rangeability and turndown

    The term rangeability R is used for tlie ratio Qnax/Qmn, i.e. the ratio of

    the maximum to minimum rates of controlled flow. Thus, if theminimum controllable flow is 2.0% of the maximum controllable flow,

    then the rangeability is 100/2.0 = 50. Valves are often not required to

    handle the maximum possible flow and the tenn turndown is used for the

    For example, a valve might be required to handle a maximum flow

    which is 70% of tliat possible. With a minimum flow rate of 2.0% of the

    maximum flow possible, tlien the turndown is 70/2.0 = 35.

    6.4.3 Control valve sizing

    The term control valve sizingis used for the procedure of determining

    the correct size, i.e. diameter, of the valve body. A control valve changes

    the flow rate by introducing a constriction in the flow path. But

    introducing such a constriction introduces a pressure difference between

    the two sides of the constriction. The basic equation (from an application

    of Bernoulli's equation) relating the rate of flow and pressure drop is:

    where AT is a constant which depends on the size of the constrictionproduced by the presence of the valve. The equations used for

    determining valve sizes are based on this equation. For a liquid, this

  • 7/29/2019 r86467 (1)

    6/10

    equation is written as:

    where >4v is the valve flow coefficient, Ap the pressure drop in Pa across

    the valve and p the density in kg/m^ of the fluid. Because the equation

    was originally specified with pressure in pounds per square inch and

    flow rate in American gallons per minute, another coefficient Cv based

    on these units is widely quoted. With such a coefficient and the

    quantities in SI units, we have:

    where Vis the specific volume of tlie steam in m^/kg, the specific volume

    being the volume occupied by 1 kg. Table 6.1 shows some typical values

    of ^v, Cv and the related valve sizes.

  • 7/29/2019 r86467 (1)

    7/10

    Example

    Determine the valve size for a valve that is required to control the

    flow of water when the maximum flow rate required is 0.012 mVs

    and the permissible pressure drop across the valve at this flow rate is

    300 kPa.

    Taking the density of water as 1000 kg/m^ we have

    Thus, using Table 6.1, this value of coefficient indicates that the

    required valve size is 960 mm.

    6.4.4 Valve positioners

    Frictional forces and unbalanced forces on the plug may prevent the

    diaphragm from positioning the plug accurately. In order to overcome

    this, valve positioners may be fitted to the control valve stem. They

    position the valve stem more accurately and also provide extra power tooperate the valve and so increase the speed of valve movement. Figure

    6.25 shows the basic elements of a positioner.

    The output from the controller is applied to a spring-loaded bellows. A

    flapper is attached to the bellows and is moved by pressure applied to the

    bellows. An increase in this pressure brings the flapper closer to thenozzle and so cuts down the air escaping from it. As a consequence, the

  • 7/29/2019 r86467 (1)

    8/10

    pressure applied to the diaphragm is increased. The resulting valve stem

    displacement takes the flapper away from the nozzle until the air leakage

    from the nozzle is just sufficient to maintain the correct pressure on the

    diaphragm.Air

    6.4.5 Other forms of flow control valves

    The type of control valve described in the earlier parts of this section isbasically thesplit-body globe valve body with a plug or plugs. This is the

    most commonly used form. There are, however, other forms. Figure

    6.26(a) shows a 3-way globe. Other valve types are thegate (Figure

    6.26(b)), the ball(Figure 6.26(c)), the butterfly (Figure 6.26(d)) and the

    louvre (Figure 6.26(e)). All excise control by restricting the fluid flow.

    Ball valves use a ball with a through-hole which is rotated; they have

    excellent shut-oflf capability. Butterfly valves rotate a vane to restrict the

    air flow and, as a consequence, suffer from the problem of requiring

    significant force to move from the full-open position and so can 'stick' in

    that position.

  • 7/29/2019 r86467 (1)

    9/10

    6.4.6 Fail-safe design

    Fail-safe design means that the design of a plant has to take account of

    what will happen if the power or air supply fails so that a safe shut-down

    occurs. Thus, in the case of a fuel valve, the valve should close if failure

    occurs, while for a cooling water valve the failure should leave the valve

    open. Figure 6.27 shows a direct acting valve which shuts down the fluid

    flow if the air supply to the diaphragm fails.

    6.5 Motors

    Electric motors are frequently used as the final control element in

    position or speed-control systems. The basic principle on which motors

    are based is that a force is exerted on a conductor in a magnetic field

    when a current passes through it. For a conductor of lengthL carrying a

    current / in a magnetic field of flux densityB at right angles to the

    conductor, the forceFequalsBIL.

    There are many different types of motor. In the following, discussion

    is restricted to those types of motor that are commonly used in control

    systems, this including d.c. motors and the stepper motor. Astepper

    motoris a form of motor that is used to give a fixed and consistentangular movement by rotating an object through a specified number of

    revolutions or fraction of a revolution.

    6.5.1 D.c. motors

    In the d.c. motor, coils of wire are mounted in slots on a cylinder of

    magnetic material called the armature. The armature is mounted on

    bearings and is free to rotate. It is mounted in the magnetic field

    produced byfield poles. This magnetic field might be produced by

    permanent magnets or an electromagnet with its magnetism produced by

    a current passing through the, so-termed, ^/eW coils. Whether permanent

    magnet or electromagnet, these generally form the outer casing of the

    motor and are termed thestator. Figure 6.28 shows the basic elements of

    d.c. motor with the magnetic field of the stator being produced by acurrent through coils of wire. In practice there will be more than one

  • 7/29/2019 r86467 (1)

    10/10

    armature coil and more than one set of stator poles. The ends of the

    armature coil are connected to adjacent segments of a segmented ring

    called the commutatorwhich rotates witli the armature. Brushes in fixed

    positions make contact with the rotating commutator contacts. They

    carry direct current to the armature coil. As the armature rotates, the

    commutator reverses the current in each coil as it moves between the

    field poles. This is necessary if the forces acting on the coil are to remain

    acting in the same direction and so continue the rotation.

    For a d.c. motor with the field provided by a permanent magnet, thespeed of rotation can be changed by changing the size of the current to

    the armature coil, the direction of rotation of the motor being changed by

    reversing the current in the armature coil. Figure 6.29 shows how, for a

    permanent magnet motor, the torque developed varies with the rotational

    speed for different applied voltages. The starting torque is proportional

    to the applied voltage and the developed torque decreases with increasing

    speed.

    D.c. motors with field coils are classified as series, shunt, compound

    and separately excited according to how the field windings and armature

    windings are connected.