Double action controller with analogue output 1 / 4 DIN - 96 x 96 Q3 line c User Manual • M.I.U.Q3 -1/03.11 • Cod. J30-478-1AQ3 IE U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl viale Indipendenza 56, 27029 Vigevano (PV) Tel.: +39-0381 69 871 - Fax: +39-0381 69 8730 Sito internet: www.ascontecnologic.com Indirizzo E-Mail: [email protected]

Upload: others

Post on 20-Jul-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

Double action controller with analogue output1/4 DIN - 96 x 96

Q3 line ccU s e r M a n u a l • M . I . U . Q 3 - 1 / 0 3 . 1 1 • C o d . J 3 0 - 4 7 8 - 1 A Q 3 I E

ULC US

LISTED

ISO 9001C e r t i f i e d

Ascon Tecnologic srlviale Indipendenza 56, 27029 Vigevano (PV)Tel.: +39-0381 69 871 - Fax: +39-0381 69 8730Sito internet: www.ascontecnologic.comIndirizzo E-Mail: [email protected]

Page 2: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

Double action controllerwith analogue output 1/4 DIN - 96 x 96

Q3 line cc

Q3

I1 I2 I3 1 2 3 MAN

SP

PV

HLD

AT

S2S1

REM45.8045 .80SCI

RUN

ULC US

LISTED

Page 3: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

2

Information

ccNOTES

ON ELECTRIC

SAFETY AND

ELECTROMAGNETIC

COMPATIBILITY

Please, read carefully these instructions before proceeding with the installation of the controller.Class II instrument, for indoor use only.

This controller has been designed with compliance to:Regulations on electrical apparatus (appliance, systems and installations) according tothe European Community directive 73/23/EEC amended by the European Comunity direc-tive 93/68/EEC and the Regulations on the essential protection requirements in electricalapparatus EN61010-1 : 93 + A2 : 95.

Regulations on Electromagnetic Compatibility according to the European Communitydirective n° 89/336/EEC, amended by the European Community directive n° 92/31/EEC,93/68/EEC, 98/13/EECand the following regulations:- Regulations on RF emissions:

EN61000-6-3: 2001 residential environmentsEN61000-6-4: 2001 industrial environments

- Regulation on RF immunity:EN61000-6-2: 2001 industrial equipment and system

It is important to understand that it’s responsibility of the installer to ensure the complianceof the regulations on safety requirements and EMC.Repairs: this device has no user serviceable parts and requires special equipment and spe-cialised engineers. Therefore, a repair can be hardly carried on directly by the user. For thispurpose, the manufacturer provides technical assistance and the repair service for its Customers.Please, contact your nearest Agent for further information.All the information and warnings about safety and electromagnetic compatibility aremarked with the B sign, at the side of the note.

Page 4: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

3

Table of contents

TABLE OF CONTENTS

1 INSTALLATION ...................................................Page 42 ELECTRICAL CONNECTIONS .............Page 83 PRODUCT CODING ......................................Page 184 OPERATIONS ......................................................Page 235 DISPLAYS ...............................................................Page 496 COMMANDS ........................................................Page 507 SETPOINT PROGRAMMER....................Page 558 TECHNICAL SPECIFICATIONS ...........Page 61

Main universal input

Control Alarms Retransmission

Resources

PV

AUX

IL1IL2IL3

Modbus RS485ParameterisationSupervision(option)

Q3

Setpoint Fuzzy tuning with automatic selection

One shotAuto tuning

One shotNatural Frequency

Operating mode

1212

Auxiliary input

Digital input

Special functions (option)

Digital inputs (IL1,IL2 or IL3) functions

PV / SP

1 OP1 OP2 OP3 OP5

2 Single OP4 OP1 OP2 OP3 OP5action3 OP5 OP1 OP2 OP3

4 OP1 OP2 OP3 OP5

5 OP1 OP4 OP2 OP3 OP5

6 Double OP4 OP2 OP1 OP3 OP5action7 OP1 OP5 OP2 OP3

8 OP5 OP2 OP1 OP3

11 Valve OP1 OP2 OP3 OP5(Option)

9 OP4 OP5 OP1 OP2 OP3

10 OP5 OP4 OP1 OP2 OP3

OP1

OP2

OP3

OP4

OP5

(option)

(Option)

Page 5: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

4

1 - Installation

1 INSTALLATION

Installation must only be carried out byqualified personnel.

Before proceeding with the installation ofthis controller, follow the instructions illus-trated in this manual and, particularly theinstallation precautions marked with theB symbol, related to the EuropeanCommunity directive on electrical protectionand electromagnetic compatibility.

BTo prevent hands or metal touching partsthat may be electrically live, the controllersmust be installed in an enclosure and/orin a cubicle.

IP 20 Terminal BlockEN61010 - 1 (IEC1010 - 1)

Product code label

Sealing front panel gasket

Mounting clamps

Front panelIP65 protectionEN 650529 (IEC 529)

Panelsurface

1.1 GENERAL DESCRIPTION

Page 6: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

5

1 - Installation

1.2 DIMENSIONAL DETAILS 1.3 PANEL CUT-OUT

96 mm3.78 in

110 mm4.33 in

10 mm max.0.39 in max.

10 mm max.0.39 in max.

96 mm3.78 in

92+

0.8

mm

3.62

+0.

031

in

113

mm

min

4.45

in

min

92+0.8 mm3.62+0.031 in

103 mm min4.05 in min

Page 7: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

6

1 - Installation

Operating conditions

M Altitude up to 2,000 m

T Temperature 0…50°C

%Rh Relative humidity 5…95 % non-condensing

1.4 ENVIRONMENTAL CONDITIONS B

Special conditions

M Altitude > 2,000 m

T Temperature >50°C

%Rh Humidity > 95 %

P Conducting atmosphere Use filter

Warm up

Use forced air ventilation

Use 24V~ supply version

Suggestions

Forbidden Conditions D

C Corrosive atmosphere

E Explosive atmosphere

Page 8: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

7

1 - Installation

1.5.1 INSERTTHE INSTRUMENT

1 Prepare panel cut-out;2 Check-front panel gasket

position;3 Insert the instrument through

the cut-out.

1.5.2 INSTALLATION SECURING

1 Fit the mounting clamps;2 Push the mounting clamps

towards the panel surface tosecure the instrument.

1

3

2

1.5.3 CLAMPS REMOVING

1 Insert the screwdriver in theclips of the clamps;

2 Rotate the screwdriver.

2

1

1.5.4 INSTRUMENTUNPLUGGING B

1 Push, and 2 Pull to remove the instrument,

Electrostatic discharges candamage the instrument

Before removing the instrumentthe operator must dischargehimself to ground.

1MΩ

1 2

1

2

1.5 PANEL MOUNTING [1]

2

1

1

UL note

[1] For Use on a Flat Surface of a Type 2and Type 3 ‘raintight’ Enclosure.

Page 9: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

6

5

4

3

2

1

28

27

30

29

26

25

7 19 31

8 20 32

9 33

10 34

11 23 35

12 24 36

0,5Nm

5.7 mm0.22 in

Rear terminalcover

Cable size1 mm2

(18 AWG)

8

2 - Electrical connections

2 ELECTRICALCONNECTIONS

28 screw terminals M3

Option terminals

Holding screw 0.5 Nm

Positive screw-driver PH1

Negative screw-driver0,8 x 4 mm

Terminals

Pin connectorq 1.4 mm 0.055 in max.

ØFork-shape AMP 165004Ø 5.5 mm - 0.21 in

LStripped wireL 5.5 mm - 0.21 in

N

L

RS48

5

1

2

3

4

5

6

7

8

9

10

11

12

19

20

23

24

25

26

27

28

29

30

31

32

33

34

35

36

LOGI

C IN

PUT

TCmV

TA

NC

C

NO

OP3

NO

C

NO

OP1

OP2

OP4

C

REM

OP5

24V—OUT

1

2

3

A

b

B

RTD

13

14

15

16

17

18

21

22

N/C

N/C

N/C

N/C

N/C

N/C

N/C

N/C

2.1 TERMINATION UNIT [1] B

UL note

[1] Use 60/70 °C copper (Cu) conductor only.

Page 10: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

6

5

4

3

2

1

28

27

30

29

26

25

7 19 31

8 20 32

9 33

10 34

11 23 35

12 24 36

18

21

6

5

4

3

2

1

28

27

30

29

26

25

7 19 31

8 20 32

9 33

10 34

11 23 35

12 24 36

18

21

A B

E C D E

A B

E C D E

9

2 - Electrical connections

PRECAUTIONS BDespite the fact that the instru-ment has been designed to workin an harsh and noisy environ-mental (level IV of the industrialstandard IEC 801-4), it is recom-mended to follow the followingsuggestions.

AAll the wiring must comply withthe local regulations. The supply wiring should be rout-ed away from the power cables.Avoid to use electromagneticcontactors, power Relays andhigh power motors nearby.Avoid power units nearby, espe-cially if controlled in phase angle

Keep the low level sensor inputwires away from the power linesand the output cables.If this is not achievable, useshielded cables on the sensorinput, with the shield connectedto earth.

Conduit for supply and output cables

Conduit for low level sensor cables

2.2 PRECAUTIONS AND ADVISED CONDUCTOR COURSE B

A = SupplyB = OutputsC = Analog inputsD = Analogue outputE = Digital input/output

Serial Comm.s

Page 11: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

10

2 - Electrical connections

2.3 EXAMPLE OF WIRING DIAGRAM (HEAT / COOL CONTROL) B

Notes:1] Make sure that the power supply voltage is

the same indicated on the instrument.2] Switch on the power supply only after that

all the electrical connections have beencompleted.

3] In accordance with the safety regulations,the power supply switch shall bring theidentification of the relevant instrument. Thepower supply switch shall be easily acces-sible from the operator.

4] The instrument is is PTC protected. In caseof failure it is suggested to return the instru-ment to the manufacturer for repair.

5] To protect the instrument internal circuitsuse:- 2 A~ T fuse for Relay outputs (220 VAC)- 4 A~ T fuse for Relay outputs (110 VAC)- 1 A~ T fuse for Triac outputs

6] Relay contacts are already protected withvaristors.Only in case of 24 V ~ inductive loads,use model A51-065-30D7 varistors (onrequest)

SupervisonCommands

RS485

Powersupplyswitch

CAlarm

V ~

Heating

Cooling

[3]

C

IL1

IL2

IL3

[6]

[6]

[5]

[5]

[5]

OP3

OP1

OP2

CT Current transformer 50 mA ~

OP5

I/P converter

3…15PSIIP

4…20mA

V ~

PTC

12

11

10

9

8

7

6

5

4

3

2

1

24

23

20

19

36

35

34

33

32

31

30

29

28

27

26

25

Page 12: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

11

2 - Electrical connections

2.3.1 POWER SUPPLY B

Switching power supply with mul-tiple isolation and internal PTC • Standard version:

nominal voltage:100 - 240V~ (- 15% + 10%)Frequency 50/60Hz

• Low Voltage version:Nominal voltage: 24V~ (- 25% + 12%)Frequency 50/60Hz or 24V– (- 15% + 25%)Power consumption 4W max.

For better protection againstnoise, it is recommended notto connect the earth clamp pro-vided for civilian installations.

L

N

25

26

Included PTC

Supply

27

2.3.2 PV CONTROL INPUT B

A L-J-K-S-R-T-B-N-E-W thermocouple type• Connect the wires with the polarity as shown• Use always compensation cable of the correct type

for the thermocouple used• The shield, if present, must be connected to a prop-

er earth.

B For Pt100 resistance thermometer

• If a 3 wires system is used, use always cables of thesame diameter (1mm2 min) (line 20 Ω/lead maximumresistance)

• When using a 2 wires system, use always cables of thesame diameter (1,5mm2 min) and put a jumper betweenterminals 11 and 12

C For ∆T (2x RTD Pt100) SpecialAWhen the distance between the controller and the

sensor is 15 mt. using a cable of 1.5 mm2 diame-ter, produces an error on the measure of 1°C (1°F).

R1 + R2 must be <320Ω

Wire resistance 150Ω max.

For 3 wires only.Maximum line resistance 20Ω/line

Use wires of the samelength and 1.5 mm2

size.Maximum line resistance 20Ω/line

10

11

12

A

B

A

R2

R1

10

11

12

A

b

B

11

12

Page 13: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

12

2 - Electrical connections

2.3.2 PV CONTROL INPUT B

D For mA, mV

Rj >10MΩ

mV mA11

12External

shunt 2.5Ω

D1 With 2 wires transducer

24V–4…20mA

Externalshunt 2.5Ω

Transducer

PV36

11

12

[1]mA

D2 With 3 wires transducer

[1] Auxiliary power supply for exter-nal transmitter 24V– ±20%/30mA max. without short circuitprotection

24V–

4…20mA

Externalshunt 2.5Ω

Transmitter

PV36

11

12

[1]mA

Page 14: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

13

2 - Electrical connections

A - From Remote Setpoint

Current 0/4…20mAInput resistance = 30Ω

Voltage1…5V, 0…5V, 0…10VInput resistence = 300KΩ

2.3.3 AUXILIARY INPUT (OPTION) B 2.3.4 DIGITAL INPUT B

• The input is active when thelogic state is ON, correspond-ing to the contact closed

• The input is inactive when thelogic state is OFF, corre-sponding to the contact open

For the measure of the load cur-rent (see page 47)

• Primary coil 10A…100A• Secondary coil 50mA default

100mA S3 internal jumper selec-table

B- For current transformer CT - Not isolated

9

8

10…100A 50/100mA

load CT

~

5 W burden resistor0.5Ω for 1A secondaryransformer coil

0.1Ω for 5A secondaryransformer coil

S3

24

23

mAmV-V

Rj 4

7

6

TTLo.c.

Isolatedcontact

Com.

IL 3

IL 2C2

C3

5

NPNo.c.

IL 1C1

Jumper for 100 mA secondary transformer coil

Page 15: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

14

2 - Electrical connections

2.3.5 OP1 - OP2 - OP3 - OP4 - OP5 OUTPUTS (OPTION) B

The functionality associated toeach of the OP1, OP2, OP4 andOP5 output is defined during theconfiguration of the instrumentindex n(see page 21).The suggested combinationsare:

Control outputs Alarms RetransmissionHeat Cool AL1 AL2 AL3 PV / SP

ASingleaction

OP1 OP2 OP3 OP5B OP4 OP1 OP2 OP3 OP5C OP5 OP1 OP2 OP3D

Double action

OP1 OP2 OP3 OP5E OP1 OP4 OP2 OP3 OP5F OP4 OP2 OP1 OP3 OP5G OP1 OP5 OP2 OP3H OP5 OP2 OP1 OP3I OP5 OP4 OP1 OP2 OP3

OP1 - OP2 Relay or Triac outputOP3 Relay output (for AL3 only)OP4 SSR drive control or Relay outputOP5 Control or retransmission analogue output

where:

L Valve drive OP1 s OP2 t OP3 OP5

Page 16: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

15

2 - Electrical connections

2.3.5-A SINGLE ACTION RELAY(TRIAC) CONTROL OUTPUT B

2.3.5-B SINGLE ACTION SSR DRIVECONTROL OUTPUT B

2.3.5-C SINGLE ACTION ANALOGUE OUTPUT B

2.3.5-D DOUBLE ACTION RELAY (TRIAC)/RELAY (TRIAC) CONTROL OUTPUT B

2.3.5-E DOUBLE ACTION RELAY (TRIAC)/SSR DRIVE CONTROL OUTPUT B

2.3.5-F DOUBLE ACTION SSR DRIVE /RELAY (TRIAC) CONTROL OUTPUT B

Fuse

Coil of the heatload contactor

31

32OP1 [1]

Fuse

Coil of the heatload contactor

31

32OP1 [1]

Fuse

Coil of the coolload contactor

32

33OP2 [1]

Fuse

Coil of the coolload contactor

32

33OP2 [1]

Fuse

Coil of the heatload contactor

31

32OP1 [1]

Load

StaticRelay

34

35OP4[2]

Cool load

StaticRelay

34

35OP4[2]

Heatload

Staticrelay

34

35OP4[2]

19

20OP5 LoadmA

Page 17: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

16

2 - Electrical connections

2.3.5-I HEAT/COOL CONTROL OUTPUT ANALOGUE/SSR DRIVE B

Cool load

StaticRelay

34

35OP4[2]

Notes:OP1 - OP2 Relay output • SPST Relay N.O., 2A/250 V~ for resistive

load, fuse 2A ~ T at 250V, 4A ~ T at 110V.OP1 - OP2 Triac output • N.O. contact for resistive load of up to 1A/250

V~max., fuse 1A ~ T.OP4 not isolated SSR drive output• 0…5V–, ±20%, 30 mA max.OP4 Relay output • SPST Relay N.O., 2A/250 V~ for resistive

load, fuse 2A ~ T at 250V, 4A ~ T at 110V.OP5 isolated analogue output• 0/4…20mA, 750Ω / 15V max.

2.3.5-G HEAT/COOL CONTROL OUTPUT RELAY (TRIAC)/ANALOGUE B

2.3.5-H HEAT/COOL CONTROL OUTPUT ANALOGUE/RELAY(TRIAC) B

2.3.5-L VALVE DRIVE OUTPUT RELAY (TRIAC) / RELAY (TRIAC)

Valve drive PID without potentiometer 3 poleoutput with N.O. contacts (open, close, stop).

Fuse

Coil of the heatload contactor

31

32OP1 [1]

19

20OP5 Cool

loadmA

19

20OP5 Heat

loadmA

19

20OP5 Heat

loadmA

Fuse

Coil of the coolload contactor

32

33OP2 [1]

OP1

33

32

31

OP2V~

Lower

Raise

M~

Notes:[1] Varistor for inductive load 24V~ only.

[2] When basic product code b= 9, OP4 (terminals 34, 35) is a Relay output.

Page 18: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

17

2 - Electrical connections

2.3.6 ALARM OUTPUTS B

e The relay/triac output OP1, OP2 and OP3,can be used as alarm outputs only if theyare not used as control outputs.

Fuse

AL1 load31

32OP1 [1]

33OP2 [1] AL2 load

V~

Fuse

Fuse

AL3 load28

29OP3 [1]

30[1] AL3 load

V~

Fuse

NC

C

NO

[1] Varistor for inductive load 24V~ only

2.3.7 OP5 ANALOGUE CONTROL OUTPUT (OPTION) B

2.3.8 SERIAL COMMUNICATIONS (OPTION) B

For control or PV/SP retransmission:• Galvanic isolation 500V~/1 min• 0/4…20mA, (750Ω or 15V– max.)

• Galvanic isolation 500V~/1 min• Compliance to the EIA RS485 standard

for Modbus/Jbus.• Setting dip switches.

C

1

2

3

19

20OP5 LoadmA

1234

A Please, read:gammadue® and deltadue® controllerseries serial communication and con-figuration

Page 19: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

18

3 - Product coding

3 PRODUCT CODING

The complete code is shown on the instru-ment label. The informations about productcoding are accessible from the front panelby mean of a particular procedure describedat section 5.2 page 49.

P/N : Q3-3150-0000CONF :S/N : A0A-9919/0013V~(L-N) : 100÷240V 50/60 Hz - 4W

B C D

Q3

I1 I2 I3 1 2 3 4 MAN

SP

PV

HLD

AT

S3S2S1

REM hard31 .50SCI

RUN

L M NI

P Q RO

Basic product code (hardware)

Configuration code (software)

Instrument label

Page 20: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

3.1 MODEL CODE

19

3 - Product coding

Line Basic AccessoriesConfiguration

1st part 2nd part

Q 3 A B C D - E F G 0 / I L M NModel:

Line 3Q

Power supply A100 - 240V~ (- 15% + 10%) 324V~ (- 25% + 12%) or 24V– (- 15% + 25%) 5

Triac - Triac - SSR Drive 5

Outputs OP1 - OP2 - OP4 BRelay - Relay - SSR Drive 1

The product code indicates the specific hardware configuration of the instrument, that can be modified by specialized engineers only.

Setpoint Programmer - special function ENot fitted 0Start-up + Timer 2

User manual FItalian/English (std) 0French/English 1German/English 2Spanish/English 3

Front panel colour GDark (std) 0Beige 1

O P Q R-

RS485 Modbus/Jbus SLAVE 5

Serial Communications CNone 0

Analogue output + Remote Setpoint 5

Options DNone 0Valve drive output 2

One "8 segments" program 3

Relay - Relay - Relay 9

Valve drive output + Analogue output (retr.) + Remote Setpoint 7

Page 21: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

20

3 - Product coding

3.2 CONFIGURATION CODING

A 4+4 index code follows themodel of the controller.The code has to be set to con-figure the controller(see chapter 3.1 page 19).

E.g. Enter the code 0320 to choose:- T/C type J input with range

0...600°C.- Single PID control algorithm,

reverse action.- Relay output.

E.g. Enter the code 2301 to choose:- AL1 absolute, active high;- AL2 absolute, active low;- AL3 Used by Timer;- Local + 2 Stored Setpoints with

tracking function.

Index

1st part ofconfiguration

code

I L M N

Con.10320

Index

2nd part ofconfiguration

code

O P Q R

Con.22301

TC T Cu-CuNi 0TC K Chromel-Alumel IEC584 0TC S Pt10%Rh-Pt IEC584 0

Input type and range

Dc input 0…50mV linear

TR Pt100 IEC751 0

1Dc input 10…50mV linear 1Custom input and range [1]

TR Pt100 IEC751 0

1

TC L Fe-Const DIN43710 0

-328…752 °FTC J Fe-Cu45% Ni IEC584 0

32…2192 °F32…2912 °F

-99.9…572.0 °F-328…1112 °F32…1112 °F32…1112 °F

-200 …400 °C0…1200 °C0…1600 °C

Engineering and units

-99.9…300.0 °C

Engineering and units

-200…600 °C0…600 °C0…600 °C

654

6543210

TC R Pt13%Rh-Pt IEC584 032…2912 °F0…1600 °C 7TC B Pt30%RhPt6%Rh IEC584 032…3272 °F0…1800 °C 8

TC N Nicrosil-Nisil IEC584 032…2192 °F0…1200 °C 9TC E Ni10%Cr-CuNi IEC584 132…1112 °F0…600 °C 0

TC W3%Re-W25%Re 132…3632 °F0…2000 °C 2TC W5%Re-W26%Re 132…3632 °F0…2000 °C 3

TC NI-NiMo18% 132…2012 °F0…1100 °C 1

[1] For instance, other thermocouples types, ∆T (with 2 PT 100), customlinearisation etc.

I L

Page 22: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

21

3 - Product coding

Deviation active high

Heater break by CT [3]

4

active during ON output state

active low

Alarm 1 type and function

8

Disabled 0

5

Band

Sensor break/Loop break alarm (LBA) 1

Absolute 2active high

active during OFF output state

3active low

active out

9

6active in 7

Control modeON-OFF reverse action 0ON-OFF direct action 1PID single reverse action 2PID single direct action 3

PID double action

4567

Linear cool output

Oil cool output [2]Water cool output [2]ON-OFF cool output

Relay (OP1) 0SSR drive (OP4) 1Analogue (OP5) 2

Output configuration

Valve drive (OP1 and OP2)

34Heat OP5, Cool OP256Heat OP5, Cool OP4

Heat OP4, Cool OP5

Heat OP1, Cool OP2Heat OP1, Cool OP4Heat OP4, Cool OP2Heat OP1, Cool OP5

Single action Double action

Deviation active high

Heater break by CT [3]

4

active during ON output state

active low

Alarm 2 type and function

8

Disabled 0

5

Band

Sensor break/Loop break alarm (LBA) 1

Absolute 2active high

active during OFF output state

3active low

active out

9

6active in 7

[2] In consideration of the thermal characteristics of the different cooling liquids,2 different correcting methods of the control output are available. One for waterand the other for oil:

OP water = 100•(OP2/100)2 OP oil = 100•(OP2/100)1,5

[3] Only possible whether "Output configuration" n= 0 or 1 and HT.F.S. para-meter is different to OFF (see page 31).

OM

N

P

Page 23: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

22

3 - Product coding

Deviation active high

Heater break by CT [3]

4

active during ON output state

active low

Alarm 3 type and function

8

Disabled or used by Timer or related to the program 0

5

Band

Sensor break/Loop break alarm (LBA) 1

Absolute 2active high

active during OFF output state

3active low

active out

9

6active in 7

Setpoint typeLocal only 0Local and 2 tracking stored Setpoints 1Local and 2 Stand-by stored Setpoints 2Local and Remote (only if option is installed) 3Local with trim (only with remote Setpoint) 4Remote with trim (only if option is installed) 5Time programmable (if option installed) 6

Q

R

Page 24: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

Q3

I1 I2 I3 1 2 3 MAN

SP

PV

HLD

AT

S2S1

REM45.8045 .80SCI

RUN

23

4 - Operations

4.1.1 KEYS FUNCTIONS AND DISPLAY IN OPERATOR MODE

PV control input in engineering

units

Overrange

Underrange

SP operating Setpoint

(Local/Remote or Stored)

Control output LEDs (red)

å OP1 ON - ç OP2 OFF

Run/stop Timer or a program

Entry key for selection and value setting confirmation

Setpoint setting

Menu access

Auto/Man

Alarm status LEDs (reds)

Å AL1 ONÇ AL2 ONÉ AL3 ON

8 Status LEDs (green)

Communications runningÄ Tuning runningÖ Timer/Program runningá Program WaitingÜ Remote Setpoint activeú First stored Setpoint activeù Second stored Setpoint active

Digital input status LEDs (yellow)

ó - IL1 activeò - IL2 activeô - IL3 active

4 OPERATIONS

8888____ 8888----

Status LEDs (green)

Manual operating mode

Page 25: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

24

4 - Operations

4.1.2 KEYS FUNCTIONS AND DISPLAY IN PROGRAMMING MODE

AThe parameter setting procedurehas a timeout. If no keys arepressed for, at least, 30 seconds,the controller switches back,automatically, to the operatormode.

After having selected the para-meter or the code, press $and % to display or modify thevalue (see page 25) The value is entered when thenext parameter is selected, bypressing the R key.

Until the $ or % arepressed or if you wait for 30 sec-onds the parameter value is notinserted

Pressing the Q key, the nextgroup of parameters is present-ed on the display.

Q3

SP

PV

p.b.35 .0

Parameter value

Parameter mnemonic

Back to the previous parameter

Entry key for selection and value setting confirmation

Value modification

Access to the menu for:

Parameter settingConfiguration

Page 26: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

25

4 - Operations

4.2 PARAMETER SETTING

4.2.1 NUMERIC ENTRY (i.e. the modification of the Setpointvalue from 275.0 to 240.0 )

4.2.2 MNEMONIC CODES SETTING (e.g. configuration see page 30)

275.0274.8

275.0274.8

230.0274.8

240.0274.8

240.0 °C

Press $ or % momentar-ily to change the value of 1 unitevery pushContinued pressing of $ or% changes the value, at ratethat doubles every second.Releasing the button the rate ofchange decreases.In any case the change of thevalue stops when it has reachedthe max./min limit set for theparameter.

In case of Setpoint modification: press $ or% once to dis-play the local Setpoint insteadof working Setpoint.To evidence this change the dis-play flashes once. Then theSetpoint can be modified

Press the $ or % to display the next or previous mnemonicfor the selected parameter. Continued pressing of $ or % will display further mnemonicsat a rate of one mnemonic every 0.5 s. The mnemonic displayedat the time the next parameter is selected, is the one stored in theparameter.

Unit °C

Unit °f

Unit °C

Unit °f

Unitnone

Unit ph

Engineering UnitsDegree Centigrade

Degree Fahrenheit

Degree Centigrade

Degree Fahrenheit

no unitsdefined

Ph

Operatormode working Setpointdisplayed

Local Setpoint display

Setpoint modification

Setpoint entry.The operation isacknowledged byone flash of the display.

after 2 s

————Lower

————Raise

Page 27: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

COMMANDS(if configured)

26

4 - Operations

4.3 PARAMETERISATION - MAIN MENU

Menus.p.

MenuCont

MenuRu.pa

MenuConf

MenutM.s.U

Menuprog5033

passOK

stat

275..0274.8

l=r

s.sel

ProgramRun/Stop/Hold(see page 59)

Setpoint Menu (see page 27)

Operatormode

Control Menu(see page 28)

Aux. parameters Menu (see page 29)

Configuration Menu(see pages 30 and 31)

Timer/Start-up Menu(see page 29)

Back to the Operator mode

OPTION(if installed)

NO

YES

Back to the Operator mode

Program Menu (see page 58)

Password Entry

Must be equal to thevalue of the parameter

Code

Only if Code value≥5000

Direct access to the parameter

(only if Code<5000)

Setpoint selectionlocal/remote(see page 52)

Stored Setpoint selection (see page 52 )

Page 28: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

27

4 - Operations

4.3.1 PARAMETERISATION - SETPOINT MENU

AIs.p

A2s.p

sl. d

s.p. l

s.p. H

sl. u

A3s.p

s.p. I

s.p. 2

rtio

bias

é 0

é 0

é 0

é Off

é Off

éH.réange

éL.réange

é :::::::

é :::::::

é 1.00

é 0

s.p.Menu

Setpoint menu

AL1 alarm threshold[1](see page 32 )

AL2 alarm threshold[1](see page 32)

AL3 alarm threshold[1](see page 32)

Setpoint ramp up0ff/0.1…999.9digit/min

Setpoint ramp downOFF/0.1…999.9digit/min

1st stored Setpoint

1nd stored Setpoint

Ratio Setpoint

Remote Setpoint bias

Setpoint low limit lowrange…S.P. H

Setpoint high limit S.P. L…High range

LOCAL, PROGRAMMconfiguration index r= O, 6

LOCAL, + 2 STORED.configuration index r= 1, 2

REMOTE, LOCAL/REMOTE WITH TRIMconfiguration index r= 3, 4, 5

Note[1] It is not presented if the controller

has been configured with alarmn° 2 not active or of sensor breaktype. Digit O/P of the configura-tion code is assigned to 0 or 1.

Page 29: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

28

4 - Operations

4.3.2 PARAMETERISATION - CONTROL MENU

MenuCont

t.d.

t.i.

p.b.é 5:0

é 5:0

é 1:00

tune

hy.é 0:5

Op. H

t.c.é 20

é100:0

d.Erré Off

M.resé 50

O.C.é 1:00

MU.hy

MU.tM

é 0:5

é 60

Op.HCé100:0

t.c. C

r.C.G.aé 1:0

é 20

d.bndé 0:5

S.Outé 0

hy. Cé 0:5

PIDAlgorithm

On-OffAlgorithm

Valve drivealgorithm

Heat / CoolAlgorithm

Tune run/stopstrt / StoP

Proportional band0.5...999.9 of span

Integral time 0ff / 0.1…100.0 min

Derivative time 0ff / 0.01…10.00 min

Control outputhysteresis

0.1...10.0% sc.

Cool output hysteresis (On-Off only)0.1...10.0% sc.

Control Menu

Overshoot control0.01…1.00

Manual reset(only with integral time = 0ff)0.0...100.0% output

Error dead band0ff/0.1...10.0 digit

Cycle time(time proportional only)1…200 seconds

Control output high limit10.0…100.0%

Motor travel time15…600 seconds

Minimum output step0.1…5.0%

Dead band -10.0…10.0%

Cool relative gain0.1…10.0

Cool cycle time (heat/cool time proportion-ing only)1…200 seconds

Cool control output high limit (PID only)10.0…100.0%

Output safety value0.0…100.0% (-100.0…100.0% for Heat / Cool)

Back to thetuneparameter

Page 30: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

Au.paMenu

A1hy

A1L.b In.sh

Addr

rt.lo.

rt.hi

t.fil

é Off

é 1

é Off

énone

é 0:5

éH. réange

éL. réange

st.tMé 1

St.OPé 0:5

t.Lbaé OFF

tM.s.UMenu

s.p.sb

t.Act

s.p.s.U

Op.Hs

t.h.s.U

é 0

é100:0

é 1

é 0

é Off

tiMeé 0:5

t.Mod

29

4 - Operations

4.3.3 PARAMETERISATION - AUXILIARY PARAMETERS MENU 4.3.4 PARAMETERISATION - TIMER AND START-UP MENUIf options installed

Auxiliary parameters Menu

Timer andStart-up Menu

AL1 hysteresis0.1…10.0% of span

Alarm latching and blocking functionsnone / Ltchbloc / Lt.bL

LBA delay(see page 40)0ff= sensor break1…9999 s LBA

Soft-start output value( t.Mod = OFFonly)0ff/0.1…100.0%

Soft-start activation time (only if st.Op differ-ent than 0ff)1…9999 s

Filter time constantOFF/1...30 s

Input shift OFF/-60...60 digit

Communicationaddress(if option installed)0ff / 1…247

Retransmission low range(only if installed)whole range

Retransmission high range(only if installed)whole range

Timer Action (only if t.Mod notequal to Offor to 1)(see table page 43)

Timer setting1…9999 s or min

Stand-by Setpoint (only if t.Mod= 7) S.P. L…S.P. H

Hold time0…500 min

Start-up Setpoint S.P. L…S.P. H

Output high limitduringStart-up5.0…100.0%

Timer/Start-up operating mode(see table 1 page 43)

Back to the A1hy parameter Back to the t.Mod parameter

TIMER FUNCTION(only with AL3 enabled)

START-UP FUNCTION(only if t.Mod = 1)

AL2 and AL3 parameters

Page 31: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

MenuConf

pass 33

Con.1

Con.2

Il1

Il2

Il3

Unité Off

é Off

énone

é Off

OK

4.3.5 CONFIGURATION MENU

NO

YES

IL2 digital input function(see table 1)

IL3 digital input function(see table 1)

Engineering units(see table 2)

Entry of digits I - L - M - N of the configuration code(chapter 3.2 pages 20,21)

Entry of digits O - P - Q - R of the configuration code(chapter 3.2 pages 21,22)

IL1 digital input function(see table 1)

Back to the

operator mode

Password Entry

Must be equal to the value of the parameter Code

Only if Code value<5000

(33 default from factory)

30

4 - Operations

Enter the password beforeaccessing to the configurationmenu.

If a not configured controller issupplied, when powered up forthe first time, the display shows:

Until the configuration code isset correctly, the controllerremains in stand-by with inputand output deactivated.

A 4+4 index code follows themodel of the controller. It has to be set to configurethe controller.(see chapter 3.1 page 19)

Con.19999

E.g. Enter the code 0320 tochoose:- T/C type J input with range 0...600°C;- Single PID control algorithm,

reverse action;- Relay output.

E.g. Enter the code 2301 tochoose:- AL1 absolute, active high;- AL2 absolute, active low;- AL3 Used by Timer;- Local + 2 Stored Setpoints with

Tracking function.

Index

1st part ofconfiguration

code

I L M N

Con.10320

Index

2nd part ofconfiguration

code

O P Q R

Con.22301

Page 32: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

sc.Hi

sc.dd

sc.lo

prot

baud

retr

rtH

Ht.f.s Code

rs.iné4=20

éM:bus

é9600

é4=20

ép:U:

é 33

31

4 - Operations

N° of decimals0…3

Low range -999…9999(min. 100 digit)

High range -999…9999(min. 100 digit)

Remote Setpointinput(see table 3)

CT primary highrangeOff/1…200 A

Communication protocolM.buS / jbuS

Baud rate1200/24004800/9600

Output range0=20 / 4=20mA

Retransmitted signalunless used as a con-trol analogue outputP.U. / S.P.

LINEAR SCALEONLY

ANALOGUE OUTPUTOPTION OP5(if installed)

CT (only on proportion-al output other than

the servomotor)

REMOTE SETPOINT(if configured)

SERIAL COM.OPTION

(if installed)

Password 0…9999

33 default from factory

Back to the Con.1 parameter

Table 1 - Digital input functionséIl1

Value Description Value Descriptionnone Not used S.P. I 1st stored Setpointkey.I Keyboard lock S.P. 2 2st stored SetpointH.PU Measure Hold Strt Run TimerA.Man Auto/Man r.=H. Run/stop of a programl=r Local/Remote

éIl3 éIl2

Table 2 - Engineering unitséunit

Value Description Value Description°C degree centigrade A Ampere°f degree Fahrenheit bar Bar

none none psI PSImU mV rh RhU Volt ph pHmA mA

Table 3 - Remote Setpoint input typeérs:In

Value Description Value Description0=5 0…5 Volt 0=20 0…20 mA1=5 1…5 Volt 4=20 4…20 mA0=10 0…10 Volt

Page 33: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

32

4 - Operations

4.4 PARAMETERS

For a simpler use of the con-troller, its parameters have beenorganised in groups (menu),according to their functionalityarea.

4.4.1 SETPOINT MENU

A ALARM TYPE AND OPERATION CONDITIONSThe OP1, OP2 or OP3 outputs, canbe used for alarms if they are notused as control outputs It is possible to configure up to 4alarms: AL1, AL2, AL3, AL4 (seepages 21 and 22), selecting, for eachof them:A the type and the operating condi-

tion of the alarm;B the functionality of the alarm

acknowledgement (latching)#ltch (see page 39);

C The blocking function is activatedon start up (see p. 39);

D Loop break or sensor break(see page 40).

AL1 alarm thresholdAL2 alarm thresholdAL3 alarm threshold

Alarm occurrences of OP1,OP2and OP3 outputs, respectivelylinked to AL1, AL2 and AL3.

The range of the alarm thresh-old correspond to the wholespan and it is not limited by theSP Setpoint span.

When the event occures, thedisplay will shows the redledsÅ,Ç or É, respec-tively on.

#A3s.P#A2s.P#A1s.P

Absolute alarm (full scale)OnOff

Activehigh

Activelow

hy

high rangelow rangeAlarm threshold

OnOff

Band alarmOnOff

Activeout

Activein

hy

SP

full scalefull scale

hy

alarm threshold

OnOff

Deviation alarmOnOff

Activehigh

Activelow

hy

+ high range- low rangeAlarm threshold

OnOff

SP

Page 34: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

33

4 - Operations

Setpoint ramp upSetpointramp down

This parameter specifies themaximum rate of change of theSetpoint in digit/min.

When the parameter is OFF,this function is disabled andthe new Setpoint is reachedimmediately after beingentered. Otherwise, the Setpoint value isreached according to the con-figured rate of change.The new Setpoint value is called"Target Setpoint". It can be dis-played by means the parameter#t.S.P.(see procedure at page 49).

#sl. d#sl. u When Remote Setpoint is con-

figured, we suggest to disable#sl. u and #sl. d parametersOff.

Setpoint low limitSetpoint high limit

Low / high limit of the Setpointvalue.

1st stored Setpoint2nd stored Setpoint

Values of the two Setpoints, thatare activated by mean of digi-tal inputs, communication para-meters, and keypad. TheSetpoint active is indicated bythe ú or ù green led.

If index r= 1 (tracking), the previous Local Setpointvalue will be lost, when thestored Setpoint is selected.

If index r= 2 (Stand-by), the Local Setpoint value will not

#s.p. 2#s.p. 1

#s.p. H#s.p. l

Setpointchange

Target Setpoint= 350°C

t t = 10

#sL. u = 10digit/minutes

Example

InitialSetpoint= 250°C

be lost, when the Stand-bySetpoint is selected. It will oper-ate again when back to Local.

See stored Setpoint selection pro-cedure at page 52.

Page 35: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

34

4 - Operations

Remote Setpoint Bias and Ratio

bias = 20ratio = 0.1

ratio = –0.1

Remotesignal

Range600100200

RemoteSetpoint span

10V

bias = 100

a b

a´ b´

-200 °CHRa (b´ ) b (a´ )LR

PV = process variableLR = PV low limitHR = PV high limitSR = Remote Setpointa (a´) = SR starting pointb (b´) = SR ending point

4.4.1 SETPOINT MENU

If SR starting point is lower thenthe ending point, bothexpressed in engineering units:

biaS= starting point = a

rtio=

Example:biaS= 20rtio=

100 - 20600 - (-200)

80800

= 0.1=

b - aHR - LR

Remote Setpoint Ratio

Ratio is the coeff. which definesthe remote Setpoint span withrespect to the input span.

Remote Setpoint

Bias defines the starting point ofanalogue Remote Setpoint ineng. units corresponding to thelow limit (current or voltage) ofthe remote signal.

#bias

#rtio

Page 36: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

35

4 - Operations

If SR starting point is higherthen the ending point, bothexpressed in engineering units

biaS= starting point = a´

rtio=

Example:biaS= 100rtio=

20 - 100600 - (-200)

- 80800

= - 0.1=

b´ - a´

HR - LR

Working Setpoint (SP) as com-bination of Local Setpoint (SL)and remote signal

Setpoint type Loc.t(configuration index r= 4 )SP = SL + (rtio • REM)

+ biaS

Setpoint type reM.t (configuration index r= 5 )SP = REM + (rtio • SL)

+ biaS

SIGN = Remote signal percentage

SPAN = HR-LR

REM =SIGN * SPAN

100

Examples:Local Setpoint (SL) with anexternal Trim with multiplyingcoeff. of 1/10:Setpoint type = Loc.trtio= 0.1biaS= 0

Remote Setpoint (SR) with aninternal Trim with multiplyingcoeff. of 1/5:Setpoint type = reM.trtio= 0.2biaS= 0

Remote Setpoint range equal tothe Input range:Setpoint type = Loc.trtio = 1biaS= LRSL = 0

Page 37: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

36

4 - Operations

4.4.2 CONTROL MENU

275..0274.8

MenuCont

tunestrt

tunestop

Operatormode

press until

Control menu

To startselect strt

To stop select stop

STEP response

SP

End of the tuningoperating and setting of

the new calculatedterms.

Start of autotuneoperation

Setpoint change

PV variable

Control output

Natural frequency

PV variable

Control output

tuning start

End of the tuningoperating and settingof the new calculated

terms.

RunTuning

4.4.2.1 AUTOMATIC TUNE

The Fuzzy-Tuning determinesautomatically the best PID termwith respect to the processbehaviour.

The controller provides 2 types of“one shot” tuning algorithm, thatare selected automatically accord-ing to the process condition whenthe operation is started.

#tune This type is selected when, atthe start of the autotune oper-ation, the PV is far from theSetpoint of more than 5% of thespan. This method has the bigadvantage of fast calculation,with a reasonable accuracy inthe term calculation.

This type is selected when the PVis close to the SP Setpoint.This method has the advantageof a better accuracy in the termcalculation with a reasonablespeed calculation.

The Fuzzy Tuning determinesautomatically the best methodto use to calculate the PIDterm, according the processconditions.

FUZZY-TUNINGSTART/STOPPROCEDURE

Start/stop of the Fuzzy TuningThe Tuning operation can bestarted or stopped any time.

The green led Ä is ON whenthe Fuzzy Tuning is in progress.At the end of this operation, thecalculated PID terms parameterare stored and used by the con-trol algorithm and the controllergoes back to the operator mode.The green led Ä becomes off.

Page 38: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

37

4 - Operations

Proportional band

This parameter specifies the pro-portional band coefficient thatmultiplies the error (SP - PV).

Integral time

It is the integral time value, thatspecifies the time required by theintegral term to generate an out-put equivalent to the proportionalterm. When Off the integralterm is not included in the con-trol algorithm.

Derivativetime

It is the time required by the pro-portional term P to repeat theoutput provided by the deriva-tive term D. When Off thederivative term is not includedin the control algorithm.

#t.d.

#t.i.

#P.b. Overshoot control

This parameter specifies the spanof action of the overshoot control.Setting lower values (1.00 —> 0.01)the overshoot generated by aSetpoint change is reduced. Theovershoot control doesn’t affect theeffectiveness of the PID algorithm.Setting 1, the overshoot control isdisabled.

Manual Reset

This specifies the control outputvalue when PV = SP, in a PD onlyalgorithm (lack of the integralterm).

Error Dead Band

Inside this band for (PV - SP), the control output does notchange to protect the actuator (out-put Stand-by).

#d.err

#M.res

#O.C. Control outputcycle timeCool cycle time

It’s the cycle time of the timeproportioning control output.The PID control output is pro-vided by the pulse width modu-lation of the waveform.

Control output high limitCool output high limit

It specifies the maximum valuethe control output can be set. It isapplied in manual mode, too.

OutputSafety Value

Output Value in case of inputanomaly.

#S.Out

#Op.C.H#Op. H

#t.c. C#t.c. Control output

hysteresisCool outputhysteresis#hy. C

#hy.

Control or alarm output hystere-sis span, set in % of the full scale.

Travel time

It provides the time required tothe motor positioner to go fromthe 0% position to 100%.

Minimum step

It specifies the minimum allowedtime of activation of the output toa motor positioner that producesa sensible effect. It is related to thedeadband of the positioner.

#MU.hy

#MU.tM

Off

SPOn

hy

Page 39: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

38

4 - Operations

4.4.2 CONTROL MENU

4.4.2.2 HEAT / COOL CONTROL

By a sole PID control algorithm, the con-troller handles two different outputs, oneof these performs the Heat action, the otherone the Cool action.It is possible to overlap the outputs.

The dead band parameter #d.bnd, is the zonewhere it is possible to separate or overlapthe Heat and Cool actions.

The Cool action can be adjusted using therelative cool gain parameter #r.C.Ga.

To limit the Heat and Cool outputs the para-meters #0p. H and #0p.HC can be used.

When there is an overlap, the displayed out-put # OUt shows the algebric sum of theHeat and Cool outputs.

A Heat /Cool actions separatedInsert positive #d.bnd value (0…10%)

B Heat /Cool actions overlappedInsert negative #d.bnd value (-10…0%)

100%

100%

#d.bnd

#Op.HC#Op. H

50%

Heatcool

Cooloutput0%

0%PID output

-100%

100%

100%

#d.bnd

#Op.HC#Op. H

50%

Heatoutput

Cooloutput0%

0%PID output

-100%

C Cool action adjustingExample with different relative cool gains

D On-Off Cool action

100%

100%

#d.bnd

#hy. C

50%

Heatoutput

Cooloutput0%

0%PID output

On

Off

100%

100%

#d.bnd

#r.C.Ga 0.1…10.0

50%

Heatoutput

Cooloutput0%

0%PID output

-100%=2.0=1.0=0.5

Page 40: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

39

4 - Operations

4.4.3 AUXILIARY PARAMETERS MENU

AL1 alarm hysteresisAL2 alarm hysteresisAL3alarm hysteresis

Hysteresis of the threshold ofboth the alarms, that activateOP1 and OP2 control output. Itis specified as a % of the fullscale.

AL1, AL2, AL3 latching and blocking functions

For each alarm it is possible toselect the following functions:none none;Ltch latching;bloc blockingLt.bL both latching and blocking.

#AIL.b#A2L.b#A3L.b

#A3hy#A2hy#AIhy #Ltch ALARM

ACKNOWLEDGE FUNCTIONThe alarm, once occurred, is presented on the display until tothe time of acknowledge. The acknowledge operation consistsin pressing any key.After this operation, the alarm leaves the alarm state only whenthe alarm condition is no longer present.

#bloc START-UP DISABLING

DisableSP∆SP

OnOff

Start-up

∆SP Disable

SP

OnOff

Start-up

Ramp down

Ramp up

∆SP Threshold = SP ± range

Page 41: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

40

4 - Operations

ALARMS WITH LBA (LOOP BREAK ALARM) AND SENSOR BREAK OPERATIONSelect the code 1 on o, p or q configuration indexes (seepages 21 or 22). The following parameter is then available:

LBA delay#t.lba

4.4.2 CONTROL MENU

Setting a value between 1 and9999 s the alarm works asLBA+Sensor break with delay [1].This condition is shown bymeans a red led as well as theblinking PV display.

Setting OFF the alarm worksas Sensor break with imme-diate action.This condition is shown bymeans the red led of the select-ed alarm as well as:

275.0274 .8

1 2 3

mA

°C

OP1

or275.0 275.01 2 3

8888____ 8888----

1 2 3

When the cause of the alarm disappears, the alarm status stops.

Soft-startcontrol output value

Value of the control output dur-ing the Soft-start activation time.

Soft-startactivation time

Time duration (starting from thepower on) of the Soft-start func-tion.

Soft-start

100%

Power-on

#St.tM

#St.OP

OP

Time

#st.tM

#st.Op Input filter time constant

Time constant, in seconds, of theRC input filter applied to the PVinput.When this parameter is set toOff the filter is bypassed.

Input shift

This value is added to the mea-sured PV input value. Its effect isto shift the whole PV scale of upto ± 60 digits.

#In.sh

Filter response100%

0

PV63,2%

t.Fil Time

#t.fil

Note [1] In case of sensor break,condition, the alarm action is imme-diate.

Page 42: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

41

4 - Operations

4.4.4.1 START-UP FUNCTION (OPTION)

Controller address

the address range is from 1 to 247and must be unique for each con-troller on the communication bus tothe supervisor. When set to Off the controller isnot communicating.

Retransmissionlow rangeRetransmissionhigh range#rt.Hi

#rt.lo

#Addr

4.4.4 TIMER AND START-UP MENU (OPTION)

To improve the instrument per-formances and to reduce thewiring and installation costs,two special functions are avail-able:4.4.4.1 Start-up4.4.4.2 Timer

In order to have the above func-tions the product code digitemust be 2 (see page 19).

For example: Q3 3100-2000To select these functions use theparameter: (see page 43).

Timer/Start-upoperator mode

A Selecting Timer or Start-up, the Soft-start functionis disabled, therefore theparameters #st.Op and#st.tM will not be shown(see page 29).

#t.Mod

By means of this function it ispossible to manipulate the con-trol output when the controlleris switched on.

To config-ure Start-up func-tion theparameter

“Timer/Start-up operating mode”must be set to # 1 (see page43).Three parameters are associat-ed to the Start-up function.

Start-up hold time0…500 min

Start-up Setpoint(S.P. L…S.P. H)

#S.P.s.U

#t.h.s.U

t.Mod 1

Control outputhigh limit5.0%…100.0%

The Start-up function includesthree phases:1st “Limy” - The control output

is limited to the #Op.Hs

2nd “Hold” - The process variableis maintained to the Start-upSetpoint for the time fixed bythe parameter #t.h.s.U

3rd “Off” - When the #t.h.s.Utime is elapsed the processvariable is maintained to theworking Setpoint.

Whether the process variable,for any reason (e.g. loadchange), decreases at a valuelower than ( #s.p.sU - 40 digits),the Start-up function starts againfrom the “Limy” phase.

#Op.Hs

Page 43: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

42

4 - Operations

When the Start-up is in Holdphase, if the local Setpointbecomes lower than the Start-up Setpoint or if the operatingmode changes to manual, theStart-up function passes to the“Off” phase.

There are two possibilities:A Start-up Setpoint #sp.sU

lower than the localSetpoint.The “Hold” phase startswhen the process variablePV achieves the #sp.sU(with a tolerance of 1 digit).

B Start-up Setpoint #sp.sUgreater than or equal tothe local Setpoint.

When the process variable PVachieves the local Setpoint (with atolerance of 1 digit), the Start-upfunction passes directly to the “Off”phase.

If, at the controller power-on, theprocess variable PV is greater thanthe lowest between the #sp.sUand the working Setpoint , thenext phase (“Hold” or “Off”) willbe executed instead of the “Limy”phase.

During the “Limy” and “Hold”phases the Ö led is on.

4201285

RUN

Start-upSetpoint

A #s.p.sU < local Setpoint SP

B #s.p.sU ≥ local Setpoint SP

noise Setpoint SP

PV

40 digit

1 digit#t.h.S.U #t.h.S.U#S.P.S.U

power-on

OP=OP.H5with TC = 25%1 s min.

1st “Limy” 2nd “Hold” 3rd “Off” 1st “Limy”2nd “Hold” 3rd “Off”

noiseSetpoint SP

PV

40 digit

1 digit

#s.p.s.Upower-on

OP=OP.H5with TC = 25%1 s min.

1st “limy” 3rd “Off” 1st “Limy” 3rd “Off”

4.4.4.1 START-UP FUNCTION (OPTION)

Page 44: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

43

4 - Operations

4.4.4.2 TIMER FUNCTION (OPTION)

AThe Timer can’t beenabled with Heat / Coolcontrol.

To enable this function do the fol-lowing:

1 In order to use this AL3 func-tion, index qmust be setto 0 in configuration (seepage 22).

2 To select one of the 6 possi-ble functioning modes of theTimer, set the value of the 2following parameters in para-meterisation (see p. 29).

Timer Action

By this parameter can bedefined (see table 2):- the time units;- the starting mode;- the OP3 status when the timer

is running.When the timer is not running, theOP3 takes the opposite status.

#t.Act Timer setting

(1…9999 s/min)

Stand-by Setpoint

(only for t.Mod = 7)(S.P. L…S.P. H)

#S.P.sb

#tiMe

Timer/Start-up counting mode Value

Countingstart time

End mode

When inside theband

Control mode 2Output to 0 3

When launched Control mode 4Output to 0 5

When launched.Control disabled Control mode 6

When launchedstand-by Setpoint Control mode 7

table 1

table 2

Timeunits

Starting mode

[1] OP3

statusValue

Seconds

Manual bykeypad

Off 0On 1

Auto at thepower on [2]

Off 2On 3

Minutes

Manual bykeypad

Off 4On 5

Auto at thepower on [2]

Off 6On 7

[1] If used by Timer;[2] Using this selection, manual

starting mode is possible too.Now the other parameter valuescan be entered:

Timer/Start-upoperating mode

By this parameter can be defined (see table 1):- the counting start time;- the control output status at the

end of the counting.

#t.Mod

Disabled OFFStart-up function 1

Page 45: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

44

4 - Operations

TIMER COUNTING MODES

A - Counting start time inside the band,end in control mode.

The time counting starts only when the erroris inside a ± 1 digit band. The control actionis not affected by the Timer function.

C - Counting start time = timer launchtime, end in control mode.

The time counting starts when the timer islaunched. The control action is not affectedby the Timer function.

B - Counting start time inside the band,end with control output forced to zero.

The time counting starts only when the erroris inside a ± 1 digit band. At the end, the con-trol output is forced to zero. [1]

#tiMeTimer launch

Setpoint

Processvariable PV

Output OP

OP3

±1 digitband

#t.Mod = 2 #tiMeTimer launch

Setpoint

Processvariable PV

Output OP

OP3

±1digitband

#t.Mod =3 #tiMeTimer launch

Setpoint

Processvariable PV

Output OP

OP3

#t.Mod = 4

[1] When the Timer is not running the con-trol output is forced to zero, also before theTimer launch,

4.4.4.2 TIMER FUNCTION (OPTION)

Page 46: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

45

4 - Operations

TIMER COUNTING MODES

D - Counting start time = timer launch time,end with control output forced to zero.

The time counting starts when the timer islaunched. At the end, the control output isforced to zero [1].

F - Control action with stand-by Setpointduring the counting time

The time counting starts when the timer islaunched and the control action use theStand-by Setpoint. At the end, the controlaction use the working Setpoint.

E - No control action during the counting time.

The time counting starts when the timer islaunched and the control output is forced tozero. At the end, the control action starts.

#tiMeTimer launch

Setpoint

Processvariable PV

Output OP

OP3

#t.Mod = 5#tiMe

Timer launch

Setpoint

Processvariable PV

Output OP

OP3

#t.Mod = 6 #tiMeTimer launch

Setpoint

Processvariable PV

Output OP

OP3

#s.p. 2

#t.Mod =7

[1] When the Timer is not running the con-trol output is forced to zero, also before theTimer launch.

Page 47: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

46

4 - Operations

If there is a power failure dur-ing the Timer execution, thevalue of the elapsed time islost.

Depending on Timer action#t .act selection, when thecontroller restarts you can havetwo different situations:• with automatic mode

( #t .act = 2,3,6,7), theTimer function starts againand the counting time isreinitialised;

• with manual mode ( #t.act = 0,1,4,5), the con-trol output is forced to Q0 if #tMod = 3 e 5; other-wise the control actionrestarts using the workingSetpoint.

TIMER STARTING

See the Timer starting procedureat page 50 (chapter 6.2.2).

DISPLAY

When the Timer is running, theled Ö is on.

When the Timer ends, theSetpoint display shows alterna-tively the message #End andthe Setpoint value until a key ispressed.

TIMER REMAINING TIME

When the timer is running it isalways possible to see theremaining time and to modify it.

End 850

850 850

RUN

POWER FAILURE

850 850

RUN

tM.r. 60

RUN

tM.r. 234

RUN

tM.r. 234

RUN

Operator mode and Timer running

Press until

Remaining time.

Counting stop.

Remaining timevalue

Value change

If set to # 0the timer ends

4.4.4.2 TIMER FUNCTION (OPTION)

Page 48: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

47

4 - Operations

With CT option, it is possible todisplay the load current and setan alarm threshold.

The setting can be done bymeans the 8 or 9 configurationindex of the codes O, P or Q(see pages 21 and 22).It is possible to set one of thealarms (see pages 21 and 22) tohave an alarm when, during theON time of the time proportion-al output, the load current is lessthen the specified threshold(index 8), or during the OFFtime there is a value > 3% of fullscale load current.

The alarm condition must belonger than 120 ms to set thealarm.By the parameter:

CT primary high rangeOFF/ 1…200A

the load current display can beadapted to the transformercharacteristics (OFF means dis-abled).

During the OFF time the para-meter #t.Cur latches the last ontime current value.

#Ht.f.S

CURRENT TRANSFORMER INPUTWhen OP5 output is present andnot configured as control out-put, it retransmits linearised PVor SP. On configuration (see page 31)it is possible to set

Analoguerange0=20 / 4=20

Retransmitted signalnone P.U. / S.P.

The following parameters definethe low and high range of theOP5 retransmission output cor-responding to 0…4mA or 20mA (see page 29):

Retransmission low rangeRetransmission high range#rt.Hi

#rt.lo

#rtH

#retr

RETRANSMISSION

4.4.5 CONFIGURATION MENU

Example:• T/C S, range 0…1600°C;• Output range, 4…20 mA;• Retransmitted signal PV on

800…1200°C range.

20

4

800 1200 1600

#retr = 4=20#rt.H = P.U.#rt.Lo = 800#rt.Hi =1200

mA

°C

With rt.lo greater thanrt.hi it is possible to obtaina reverse scale.

Page 49: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

48

4 - Operations

Communication protocolM.bus/ j.bus

Baud rate1200/ 24004800/ 9600

#baud

#prot

SERIAL COMMUNICATIONS

Example:CT input on OP1, alarm on AL2 during on time (configuration digitp = 8 , see page 21)

ON ON

ON ON

3%

A2s.p

t.Cur

120 ms 120 ms

OFFOP1

AL2 OFF OFF OFF

Load

cur

rent

4.4.5 CONFIGURATION MENU

CURRENT TRANSFORMER INPUT

Page 50: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

49

5 - Displays

5 DISPLAYS

5.1 OF THE PROCESS VARIABLES 5.2 OF THE CONFIGURATION CODES

274.8 °C

275.0S.P.

63.4Out

380.0t.S.P.

47t.Cur

33tM.r.

275..0274.8

274.8 °C

2002Con.1

2321Con.2

00AreL.

3150Hard

275..0274.8 Engineering

units(see table 2 page 31)

Basic product code (Hardware page 19)

1st part of the configuration code(see pages 20 and 21)

2nd part of the configuration code(see pages 21 and 22)

OP1 outputPID only

Local Setpoint

modifiable value

Timer remaining timemodifiable value(if option installed,see page 46)

Target Setpoint valuelocal mode only(not displayed if theSlopes are disabled)

Load current in Ampere(CT option only,see page 47)

Software release

Operatormode

Operatormode

Engineeringunits (see Table 2 page 31)

Manual AUTO

Page 51: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

50

6 - Commands

COMMANDS TO THE CONTROLLER AND OPERATING PHASES6 COMMANDS

The commands can beentered in 3 ways:

6.1 KEYPADsee page 51

• Setpoint modification• manual mode • Timer start• Program start/stop• local/remote selection • stored Setpoint display• Keypad lock• Outputs lock

6.2 DIGITAL INPUTSsee page 54

6.3 SERIAL COMMUNICATIONS

see the manual on this topic

Page 52: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

51

6 - Commands

6.1 KEYPAD COMMANDS

6.1.1 SETPOINT MODIFICATION

The Setpoint is directly modifiedwith the $%keys.Once entered, the new value ischecked and becomes operatingafter 2 seconds.. The end of thisphase is flagged by flashingmomentarily the display with SP.

6.1.2 AUTO/MANUAL MODE 6.1.3 TIMER STARTING(option)

Depending on the Timer action#t.act selection, there can betwo different starting ways:- Automatic at the power on- Manual by keypad, digital inputs

or serial communications.To start/stop the Timer:

For Setpoint access andmodification from Manual sta-tus, see the procedure on chap-ter 5 (see page 49).The bumpless action is presentswitching between AUTO, MANand vice versa.

AIn case of power failure, theAUTO/MAN status and the

output value remain stored inthe controller memory.

Operator mode

Example of Setpointmodification from275 to 350

Modified Setpoint value

Flash momentarilythe SP value to con-firm that it hasbecome operating.back to the operatormode

Operator mode

(automatic)

Select manualgreen

led on

Modify theoutput value

Back to the operator mode

after 2 seconds

AUTO AUTO

SP = PV

OPMAN=OPAUTO

SP (PV)

OY

0

0

MAN

Op.rSP

changeOP

100%Setpoint SP

co

100% output OP

OPAUTO=OPMAN

PV

OP

275.0274.8

MAN

50.0274.8

MAN

35.0274.8

MAN

Modification of control output valueA

The new value is immediatelyworking without any confirm.

274.8275.0

274.8350.0

274.8350.0

350 350

350 350

RUN

Timer stopback to the operator mode

Timer start

Operatormode

Timer runningledÖ on

Page 53: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

S.P. 1S.Sel

274.8275.0

noneS.Sel

S.P. 2S.Sel

S.P. 1S.Sel

LocS.Sel

S.P. 2S.Sel

52

6 - Commands

6.1.4 PROGRAM STARTING(see chapter 7, page 55)

6.1.5 LOC/ REM SELECTIONconfiguration index r= 4 or 5)

6.1.6 STORED SETPOINTS SELECTION(configuration index r = 1 or 2)

The selected Setpoint becomes operatingpressing the è

When in Remote, the green led Ü is on

The selected Setpointbecomes operating

pressing theè key.

The corrispondig green led

(ú or ù) is on

Operatormode

Press until

Select S.P.1to force

the first Setpoint

Select S.P.2to force the

second Setpoint

Select none to free theSetpoint modification, then

Press $%to change the local Setpoint

Select Locto come back to the previ-ous local Setpoint value

274.8275.0

Loc L=r

reM L=r

TrackingIndex r = 1

Stand-byIndex r = 2

6.1 KEYPAD COMMANDS

Press until

Select reMto enable Remote Setpoint

Select Locto enable Local Setpoint

Page 54: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

53

6 - Commands

To lock/unlock the keypad pressthe keys í and è simulta-neously for 2 seconds.To confirm the keypadlock/unlock the display flashesonce.

The keypad lock/unlock can beachieved by serial communica-tions too.

AThe keypad lock is main-tained in case of powerfailure.

The outputs are switched to theOFF status by pressing the keysí and %together.When the outputs are locked ,the message #Off is dis-played instead of the Setpointvalue.To unlock the outputs pressagain the keys simultaneously (the Soft-start will be enabled).

The outputs lock/unlock canbe achieved by serial com-munications too

AThe outputs lock/unlockis maintained in case ofpower failure.

6.1.7 KEYPAD LOCK 6.1.8 OUTPUTS LOCK

Q3

SP

PV

45.8045 .80

SP

PV

45.8045 .80

Q3

operator mode

Press simultaneouslyfor 2 seconds

operator mode

Press simultaneouslyfor 2 seconds

Page 55: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

54

6 - Commands

6.2 DIGITAL INPUT COMMANDS

A function is assigned, throughthe configuration procedure toeach IL1, IL2 and IL3 digitalinput. (see the parameters set-ting at tab. 1 at page 31).The configured function is acti-vated when the digital input (freevoltage contact or open collec-tor output) is in the On state(closed). It is deactivated by set-ting the input to the Off state(open).The activation of the functionthrough the digital input has thehighest priority than through thekeypad or through the serialcommunication.

FunctionParameter

valuePerformed operation

Notes

None #OFF — —Not used

Set manual mode #A.Man Automatic Manual

Keypad lock #keb.I Unlock LockedWith the keypad locked the commands from digital inputs and serial communications arestill operating

PV measure hold #H.pU Normal

operationPV is hold The value of PV is “frozen” at the time the digital

input goes to the close state

#l=r. Local Remote

#sp.1 Local 1st SP The permanent closure forces the chosen storedvalue. Setpoint modification is not possible.The impulsive closure, selects the stored value.Setpoint modification is allowed.If more than one digital input is selecting a Setpoint,the last to be activated is the operating one.

1st stored Setpoint

#sp.2 Local 2nd SP

#H.=r. Hold RunWhen the input is in the On state, the program isexecuted up to the end. When off, the program isforced in hold.

2nd stored Setpoint

Start/stopof a program

Off On

Timer #t.run —Timer start

Pro

gram

med

Set

poi

ntS

tand

ard

Set

poi

nt

Set Remote mode

The impulsive closure is enough to start the Timer

Page 56: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

55

7 - Programmed Setpoint

7 PROGRAMMED SETPOINT

INTRODUCTIONThe controller supplied with theSetpoint programmer option (mod.Q3-3… &) offers the functionali-ty to define, store, display and exe-cute a program consisting in theSetpoint profile in time.

MAIN CHARACTERISTICS• 1 program, 8 segments/program• start, stop, hold etc, com-

mands from the keypad• time base in seconds, min-

utes or hours• continuous or up to 1…9999

time cycling of the program• 1 OP3 digital output with the

state profile defined by theprogram

• setting of the maximumallowed deviation from theSetpoint

The program consists of asequence of segments.

For each segment, it is specified:• the Setpoint

to reach#s.p.

• the duration of the segment#t.i.

• the state of the OP3 output

The program consists of:• 1 initial segment named O• 1 end segment named f• 1…6 normal segments

alvayspresent

Initial segment - 0Its main purpose is to define thevalue the process variable hasto maintain before starting theprogram.

End segment - FIts main purpose is to define thevalue the process variable hasto maintain at the end of the pro-gram and until further changesof Setpoint.

Normal segments - ===These segments build up theprofile program. There are 3types of segments:

7.1 PROGRAM STRUCTURE

Ramp

#ti.==

#s.p.==

#s.p.==

#ti.==

#s.p.==

Dwell

#ti.==

#s.p.==

Step

#ti.== = 0

s.p. = Target Setpointti. =Duration

=Previous segment=Current segmente=Next segment

Page 57: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

56

7 - Programmed Setpoint

EXAMPLE OF SETPOINT PROFILE 7.2 SETPOINT PROGRAMMER OPERATION

300

250

200

150

100

50

350

1° 2° 3° 4° 5° 6° End

300 50 70 80 110 170 190 Time

t1 t2 t3 t4 t5 t6

Segment Initial

Time t0

Programstart

°C Setpoint

#S.P. 2

#S.P. 3

#S.P. 4 #S.P. 5

#S.P. 6Maximumallowed

deviation

#CIo

#Opn

OP3 DigitalOutput

band

#S.P. f#S.P. 0

#S.P. I

If the PV controlled input value exceeds the band, centred aroundthe SP, the segment time is extended of the same time the PV inputstays out of the band. The band width is defined in a parameter ofthe program segment.The actual segment period is calculated as ti..==+Ti

7.2.1 MAXIMUM ALLOWEDDEVIATION ( bbaanndd )

A. Ramp

#ti.--

#ti.-- + Ti

Ti

#band

PV

SP#band

B. Dwell

#ti.--

ti.-- + Ti

Ti

PV

SP

#band

#band

Page 58: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

57

7 - Programmed Setpoint

7.2 SETPOINT PROGRAMMER OPERATION

7.2.2 RE-START OF A PROGRAM AFTER A POWER FAILURE

The parameter #fail . spec-ifies the behaviour of the pro-grammer at power up (see page58). Selected between the fol-lowing 3 choices:

#Cont Continue

#res Reset

#raMp Ramp

If #Cont is selected,the execution of the programstarts from the point reached atthe power failure time.

All the parameters, likeSetpoint and the remainingtime are restored at the valuesthey had at power off.

PV

ti

SPPower Off

Power Off time

If #res is selected, at power on the program endsand goes back to local mode.

If #raMp is selected, the execution of the programstarts from the point reached atthe power failure time.In this case, the programs con-tinue with PV reaching SV witha ramp, whose slope corre-sponds to the one of the seg-ment running at the power off.

Power off during a dwell

Power off during a ramp

ti

Power Off

ti

Power Off

Page 59: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

58

7 - Programmed Setpoint

7.3 PARAMETERISATION - PROGRAM MENU (OPTION)

Menuprog

Fail

Unit

n.Seg

Cyc.

band

ti. O

S.P. 0

dO. O

ti. 1

S.P. 1

dO. 1

S.P. F

dO. F

Restart after a power offCont = continueres = resetraMp = continuewith the slope

Time unitsp.sec= secondsp.Min = minutes

N° of segments1…6 max.

N° of program cycles OFF / 1…9999

Allowed deviationOFF / full range

Program menu

Segment 0 time0…9999 Unit

Segment 0 Setpointfull range

Segment 0 Digital output [1]Clo = closedOpn = openOff = inhibited

Segment 1 time0…9999 Unit

Segment 1 Setpointfull range

Segment 1 Digital output [1]

End segment Setpointwhole range

End segment digital output[1]Clo = closedOpn = openOff = inhibited

Continue for all the 6 normal

segments

[1] One digital output is provid-ed which can be controlledby the program. This outputis, usually, OP3. If this func-tionality is not required, it canbe inhibited by setting Offthe parameter #d.O.--

Back to the fail parameter

Page 60: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

59

7 - Programmed Setpoint

7.4 START/STOP OF A PROGRAM

The various commands, sup-ported by the controller, are dif-ferent for each of the followingoperating phases:A] when in Local Setpoint modeB]during the execution of a pro-

gram C]when the program is in hold

Commands supported by thecontrollers

Type ofoperatingsetpoint

Local Programmed Programmed

Phase Start of aprogram

Supportedcommands

Executionof a program

Holdof a program

Settingof Localsetpoint

When theprogram is

ended it comesback to normal

mode

Programstart

Programstop

in local mode

Programhold

Programstop

in local mode

Programcontinuation

Programstop

in local mode

BA C

The different phase are dis-played in a chained way, just foreasing the understanding of thefunctionality.Two different mode for startingand stopping a program are pro-vided:direct mode with the ê keythrough the parameter menu

Page 61: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

60

7 - Programmed Setpoint

1st DIRECT MODE WITH ê 2nd THROUGH THE PARAMETER MENU

statrun

stathold

stathold

275.0274.8

275.0274.8

RUN

333.0329.0

RUN

Operator mode(local Setpoint)

Program start

Program start

Program Hold

Program reset

Program hold

Continue up to the program end

Program runningÖ led

continuously on

Program holdÖ led flashing A

The Ö green led is flashed at highrate when the controlled

variable is out of the allowed deviationband

The current time of a segment is holdup to the time the variable re-enter in

the band.

Page 62: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

61

8 - Technical specification

8 TECHNICAL SPECIFICATIONS

Total configurability(see chapter 3.2 page 20

chapter 4.3.5 page 30)

PV Input(see pages 11,12 and page 20)

Features(at 25°C environmental temp.) Description

From keypad or serial communication the user selects:- the type of input - the type and functionality of the alarms- the type of control algorithm - the type of Setpoint- the type of output - control parameter values

Common characteristics

A/D converter with resolution of 50,000 pointsUpdate measurement time: 0.2 secondsSampling time: 0.5 secondsInput bias: - 60…+ 60 digitInput filter with enable/disable: 1…30 seconds

Accuracy 0.25% ± 1 digits for temperature sensors0.1% ± 1 digits (for mV and mA)

Between 100…240V~the error is minimal

Resistance thermometer(for ∆T: R1+R2 must be <320Ω)

Pt100Ω at 0°C(IEC 751)°C/°F selectable

2 or 3 wires connectionBurnout (with any combination)

Max. wire Res:20Ω max. (3 wires)Sensitivity: 0.35°C/10° T.env.<0.35°C / 10Ω Wire Resistance

Thermocouple

L,J,T,K,S, R, B, N, E, W3, W5(IEC 584)Rj >10MΩ°C/°F selectable

Internal cold junction compensation con NTCError 1°C/20°C ±0.5°C Burnout

Line: 150Ω max.Input drift: <2µV/°C T.env.<5µV / 10Ω Wire Resistance

DC input (current)4…20mA,0-20mAwith external shunt 2.5ΩRj >10MΩ

Burnout. Engineering unitsConf. decimal point positionInit. Scale -999…9,999Full Scale -999…9,999(min. range of 100 digits)

Input drift:<0.1% / 20°C T.env.

<5µV / 10Ω Wire ResistanceDC input (voltage) 10…50mV, 0-50mV

Rj >10MΩ

Page 63: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

62

8 - Technical specification

Features(at 25°C environmental temp.) Description

Auxiliary inputs

Remote Setpoint (option)Not isolatedaccuracy 0.1%

Current0/4…20mARj = 30Ω Bias in engineering units and ± range

Ratio from -9.99…+99.99Local + Remote SetpointVoltage

1-5/ 0-5/ 0-10VRj = 300KΩ

CT current transformer(see pages13 and 47)

50 or 100 mAinput hardwareselectable

Current visualisation 10 … 200AWith 1A resolutionand Heater Break Alarm

Digital inputs3 logic

The closure of the external con-tact produces any of the follow-ing actions:

Auto/Man mode change, Local/Remote Setpoint mode change,Stored Setpoints activation, keypad lock, measure hold

Timer activation, program run/hold (if options installed)

Operating mode and Outputs

1 single or double actionPID loop orOn/Off with 1, 2 or 3 alarms

Control output

Single action

AL1 alarm AL1 alarmOP1-Relay/TriacOP4-SSR drive-RelayOP5-AnalogueOP1-Relay/Triac OP2-Relay/Triac

Double actionHeat / Cool

OP1-Relay/Triac OP4-SSR drive-RelayOP4-SSR drive-Relay OP2-Relay/TriacOP1-Relay/Triac OP5-AnalogueOP5-Analogue OP2-Relay/Triac

OP1-Relay/Triac OP2-Relay/TriacValve drive

AL2 alarm Retransmiss.

OP1-Relay/Triac

OP1-Relay/Triac

OP1-Relay/TriacOP1-Relay/Triac

OP2-Relay/Triac

OP2-Relay/Triac

OP2-Relay/TriacOP2-Relay/TriacOP2-Relay/Triac

OP3-Relay

OP3-RelayOP3-RelayOP3-RelayOP3-RelayOP3-RelayOP3-RelayOP3-RelayOP3-Relay

OP5-Analogue

OP5-AnalogueOP5-AnalogueOP5-Analogue

OP5-AnalogueOP5-Analogue

OP5-Analogue OP4-SSR drive-Relay OP1-Relay/Triac OP3-RelayOP2-Relay/Triac

Page 64: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

63

8 - Technical specification

Features(at 25°C environmental temp.) Description

Control mode

Algorithm PID with overshoot control or On-off - PID with valve drive algorithm, for controlling motorised positionersProportional band (P) 0.5…999.9%

Integral time (I) 0.1…100.0 min

Derivative time (D) 0.01…10.00 min

Error dead band 0.1…10.0 digit

Overshoot control 0.01…1.00

Manual reset 0.0…100.0%

Cycle time (Time proportional only) 1…200 s

Control output high limit 10.0…100.0%

Soft-start output value 0.1…100.0%

Output safety value 0.0…100.0% (-100.0…100.0% for Heat / Cool)

Control output hysteresis 0.1…10.0% On-Off algorithm

Dead band -10.0…10.0%

Double action PID algorithm (Heat / Cool) with overlap

Relative cool gain 0.1…10.0

Cycle time (Time proportional only) 1…200 s

Control output high limit 10.0…100.0%

Cool output hysteresis 0.1…10.0%

Motor travel time 15…600 s Valve drive PID algorithm without feedback potentiometerMotor minimum step to 0.1…5.0%

Single actionPID algorithm

OFF = O

OFF = O

Page 65: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

64

8 - Technical specification

Features(at 25°C environmental temp.) Description

OP1-OP2 outputs SPST Relay N.O., 2A/250V~ for resistive loadTriac, 1A/250V~ for resistive load

OP3 output SPDT relay N.O., 2A/250V~ for resistive loadOP4 output Logic not isolated: 0/5V–, ±10% 30mA max. - SPST Relay N.O., 2A/250V~ for resistive load

OP5 analogue output(option)

Control or PV/SPretransmission

In current: 0/4…20mA 750Ω/15V max.

AL1 - AL2 - AL3alarms

Hysteresis 0.1…10.0% c.s.

Action

Active highAction type

Deviation threshold ±range

Band threshold 0…range

Absolute threshold whole range

Special functions

Sensor break, heater break alarm

Acknowledge (latching), activation inhibit (blocking)

Connected to Timer or program (if options installed)

Setpoint

Local

Up and down ramps 0.1…999.9 digit/min (OFF=0) Low limit: from low range to high limitHigh limit: from low limit to high range

Local plus two stored (tracking or STAND-BY)

Local and Remote

Local with trim

Remote with trim

Programmable

Galvanic isolation: 500 V~/1 minResolution 12bit (0.025%)Accuracy: 0.1 %

Active low

If option installed

Page 66: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

65

8 - Technical specification

Features(at 25°C environmental temp.) Description

Fuzzy-Tuning one shoot The controller selects automatically the best method according to the process conditions

Step responseNatural frequency

Auto/Man station Standard with bumpless function, by keypad, digital input or serial communications

Programmable Setpoint(optional)

1 program, 8 segments (1 initial and 1 end) - From 1 to 9999 cycles or continuous cycling (Off)Start, stop, hold, etc. activated from the keypad, digital input and serial communications

Special functions(option)

Timer (see page 43)

Serial comm. (option) RS485 isolated, Modbus/Jbus protocol, 1,200, 2,400, 4,800, 9,600 bit/s 3 wiresAuxiliary Supply +24V– ± 20% 30mA max. - for external transmitter supply

Operational Safety

Measure inputControl outputParametersAccess protection

General characteristics

Power supply(PTC protected)SafetyElectromagnetic compatibilityUL and cUL OmologationProtection EN60529 (IEC 529)

Automatic start at the power on, manual start by keypad, Digital inputs or serial comm.s

Control output high limit: 5.0…100.0%Hold time: 0…50 minStart-up Setpoint: from Setpoint low limit to Setpoint high limitStand-by Setpoint: from Setpoint low limit to Setpoint high limitSetting time: 1…9,999 s/min

Start-up (see page 41)

Parameter and configuration data are stored in a non volatile memory for an unlimited timeSafety value: -100%…100%Detection of out of range, short circuit or sensor break with automatic activation of the safety strategies and alerts on display

Password to access the configuration and parameters data, keypad lock, outputs lock100 - 240V~ (- 15% + 10%) 50/60 Hz or 24V~ (- 25% + 12%), 50/60 Hz and 24V– (- 15% + 25%)Compliance to EN61010-1 (IEC 1010 – 1), installation class 2 (2500V) pollution class 2, instrument class IICompliance to the CE standards (see page 2)File 176452

IP65 front panel

Power consumption 4W max.

1/4 DIN - 96 x 96, depth 110 mm, weight 470 g approx.Dimensions

Page 67: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

66

Warranty

1 WARRANTY

We warrant that the products willbe free from defects in material andworkmanship for 18 months from the date of delivery.The warranty above shall not applyfor any failure caused by the use ofthe product not in line with theinstructions reported on this manual.

Page 68: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

67

Page 69: Q3 line - Ascon Tecnologic€¦ · Q3 line c User Manual • M.I.U.Q3 -1 /03.11 • Cod. J30-478-1AQ3 I E U L C US LISTED ISO 9001 Certified Ascon Tecnologic srl via le Indipendenza

66

Main universal input Digital input

Thermocouple Isolated contact

RTD (Pt100) NPN open collector

Delta Temp (2x RTD) TTL open collector

mA and mVSetpoint

Custom Local

Frequency Stand-by

Auxiliary inputKeypad lock

Current transformer Outputs lock

mA Remote setpoint Start-up function

Volt Remote setpoint Timer function

Feedback potentiometer

Memorized

Remote

Setpoint programmer

Logic

mA mV

mA

SPDT Relay

Triac

SPST Relay

Output

Setpoint slopes inhibition

PV hold

Run, Hold, Reset andprogram selection

Auto/Manual

Digital input connected functions

ICONS TABLE