pv grid integration – system management issues and ... · forecasting needs and industry...

18
PV Grid Integration – System Management Issues and Collaboration Aspects EUCI Developer Conference, Oahu, HI Emma M. Stewart, Ph.D. December 13th, 2011

Upload: others

Post on 05-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

PV Grid Integration – System Management Issues and Collaboration Aspects EUCI Developer Conference, Oahu, HI Emma M. Stewart, Ph.D. December 13th, 2011

Page 2: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Highlights DNV/BEW Perspective

Some Industry Concerns of Renewable Integration - Inherent variability of solar - Lack of appropriate and standard models - Lack of performance data for validation - Non-standard distribution systems across the nation

How to prepare for the integration of high penetration of PV

Options/Solutions - Adapting codes and standards - Updating models - Validating new technologies - Utility collaborations to understand impacts to existing processes

Q&A

2

Page 3: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

T&D Solar & Wind Grid Penetration Assessments

Renewable portfolio standard studies Hi-PV Impact & Cluster Studies

Variability Studies Interconnect Studies

BEW Engineering and Consulting Service Areas

Solar PV Energy Assessments

Bankability & Due Diligence

Wind Technology Assessment

Developers

Utilities Owners

Manufacturers

PUCs

Gov. Agencies/DOE

Page 4: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

4

Work needed to bridge the gaps - “Seams” Infrastructure and Control Interface with Utilities

Electric Sector Paradigm Shift

Source: D. Nakafuji, HECO

Page 5: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

BEW/DNV Perspective Emerging levels of distributed generation “behind-the-meter” generation is increasing

Levels are exceeding “rules-of-thumb” used in standard utility practices for planning - Installed levels of DG are a continually moving target

Industry lacks capability (tools/data) to effectively plan for PV impacts on the grid

Currently no cost-effective, commercially available capability exists to meet solar forecasting needs and industry standardization of monitoring equipment is lacking

Integrating utility departments and software communications is essential for sustainable renewable deployments

Developing a collaborative of utility staff, developers, regulatory agencies to develop a cooperative framework for a sustainable and cost effective renewable expansion plan - Combining utility optimal locational value of development strategies with public and private preference - Integration of energy efficiency, renewable development while reducing greenhouse emissions

5

Page 6: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Real World Integration Issues Lack of recorded PV generation and

customer load profile changes - Operational observability is limited in

renewable fields

Accurate distribution system modeling - Limited validation of models with

recorded data - Accurate modeling of single phase

and three phase PV inverters and generator characteristics - Quality is varied

Integration of customer-owned generation with utility owned generation

Maintaining performance, reliability and safety is the key for utilities

Utility interconnections need to be considered in the mix

Variability is often not quantified accurately due to lack of predicted/validated/measured data

6

Irradiance ramp rates translate to system frequency impacts through

detailed simulation

Page 7: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Issues Being Encountered as Penetration Increases

Midnight Midnight

MW

12 noon Midnight Midnight

MW

12 noon

Min & Max output of base (firm) generating units

Output of intermittent units

Excess Energy – curtailed or dumped Utility PAYS FOR THIS

Supply exceeds Demand at minimum load

Supply does not meet demand at maximum load

Costly Energy – procured, Utility PAYS FOR THIS

Local DG changing load shape

Curtailment Reliability Masked Loads

Integration of DSM need to be coupled to system

7

Source: D. Nakafuji, HECO

Page 8: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Local Feeder Load Impacts

8

Concerns: 1. Need to assess the feeder loading not only at peak

periods but also when the loads are lower (light load Sundays) – Rule 14H

2. Circuit peaks often not coincident with System peaks

Concerns 1.PV provides energy (kWh) for day time load but misses the evening peak 2.Dispatchable resources need to be available to meet evening peak load

System Load Impacts

Feeder and System Load Impacts

Page 9: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Graphical Flow of Model Interfaces – Bringing together Modeling, Data and Departments

The existing models are not designed to simulate the operation of large numbers of distributed resources

Conversion of single phase and poly-phase PV inverter characteristics from an unbalanced distribution model to a balanced transmission model

Highly variable PV systems must be analyzed in a detailed dynamic and steady state simulation

As more detailed inverter control schemes become widely available to customers the impact must be justifiable and proven through simulation

Availability of measured data is essential for validation and lacking in many cases

9

Source: R. Davis, E. Stewart; BEW; Solar Power International.

C o m p l e te Sy s te m

A n a l y ti c a l Mo d e l

Ex te r n a l V ariables PV D a t a Wind Data I n ve rt e r Mo d e l l i n g Sma rt G ri d D a t a

G e n e r a ti o n Pl a n n i n g PR O MO D PPl u s Ma p s Pl e xos s

Pr o te c ti o n Syn e rG EE Asp e n D i st ri vi e w C yme D i st

T r a n s m i s s i o n Pl a n n i n g Po w e rW o rl d PSS/ E PSL F

D i s tr i b u ti o n Pl a n n i n g Syn e rG EE PSS/ Si n ca l Mi l l So f t Asp e n D i st ri vi e w C yme D i st

O p e r a ti o n s SC AD A

Page 10: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Many Different Disciplines… Must Understand Each Other

T

10

Photovoltaic Meteorology Utility Network

Main topic Financial Profitability Weather of tomorrow

Load Balancing/ Integration of

transmission and distribution

Heartbeat 1 Second 1 Hour 15s to 15 Minutes

Forecast years days Tomorrow 8h00, 8h15,…

Page 11: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Options/Solutions: Energy Meteorology

11

Invest into energy meteorology

Adapt utility grid to variable distributed power input

Develop forecast products to the needs of the variable renewable power Higher time resolution New forecast

parameters (ramps)

Adapt PV systems to the energy economy and utility system management aspects Real time data for

observeability Interaction Grid assistance

Page 12: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Present US DG Standards Status PV Inverter implements the interface to utility

grid

In US - designed to meet IEEE 1547 - Based on low penetration installations from

California Rule 21 which is 15%

Listed to UL-1741 (harmonized with IEEE 1547) - Anti-Islanding - Tight over/under voltage and frequency trip

settings - Unity Power Factor

Purpose is to get out of the way in fault condition and let existing utility protection scheme operate - May contribute to cascading faults

Harmonics and Flicker Requirements - IEEE 519 - 1992 - IEC Standard 61000-3-6

Perception vs. Reality - Lack of measured data ties

utilities/developers hands, and hinders interconnect process

12

Page 13: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Benefits of Collaborations No man is an island – utilities can work

together – may not be interconnected physically but lessons can be learned throughout - Data can be shared and processes

informed - Cost sharing - How much data needs to be collected?

What can you learn from it?

SMUD & HECO collaborating on Hi-PV studies

Clusters of individual sites can be considered vs. a study on each individual generator - Limitations on interconnections can be

better informed, costs shared

Instead of connecting PV on every feeder in California and Hawaii up to 15% of Peak BEFORE considering detailed impacts - First one over 15% is the issue - Waste of resources/Time

Analyze detailed impacts of clusters and inform where more or less can be added

13

Page 14: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Lessons Learned (So Far!) Multiple criteria must be considered at both

the steady state and dynamic level to assess feeder level and system wide penetration levels

Availability of measured data is essential for validation and lacking in many cases

Highly variable PV systems must be analyzed in a detailed dynamic and steady state simulation

Feeders can be characterized in terms of load type, geo location, voltage, and PV penetration

Commercially available tools must be integrated and used for different tasks

As more detailed inverter control schemes become widely available to customers the impact must be justifiable and proven through simulation

Availability of measured data is key to fully understanding impacts and sustainable development - Software integration is essential for maintaining

growing portfolio

Issues traditionally considered ‘key bottlenecks’ to increase in penetration are often wrongly perceived

Utilities must prepare for high penetrations of variable resources and get ahead of the curve - Utilities must pre-plan for upgrades and

operational changes ahead of time

All stakeholders must find common ground for continued sustainable development

14

Page 15: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved. 15

Thank You!

PV Grid Integration – System Management Issues and Collaboration Aspects

Jam

es H

ardy

/Pho

toAl

to/G

etty

Imag

es

Emma Stewart Senior Engineer, Power Systems BEW Engineering a DNV Company 2303 Camino Ramon, Suite 220 San Ramon, CA 94583 [email protected] www.bewengineering.com

Page 16: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved. 16

DNV – An independent foundation since 1864

9,000 employees, of which 76% have university degree

300 offices

100 countries

Page 17: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Preparing for the Integration of High Renewable Penetration

17

• Load Forecasting, PV locational maps

• Distribution feeder analysis • Feeder-Substation-Area-Utility wide

• Transmission planning • Impacts of DGPV and central PV plants.

• Generation planning • Conventional resources needs, spinning, ramping, etc

• Protection, operations, finance

Page 18: PV Grid Integration – System Management Issues and ... · forecasting needs and industry standardization of monitoring equipment is lacking Integrating utility departments and software

© Det Norske Veritas AS. All rights reserved.

Two schools of thought for PV penetration impacts studies Traditional Representation of PV from a

transmission POV Recommended Representation of PV for

a Transmission Analysis

G System

GEN Sources

46 kV

Transmission 138KV

Load at 46 kV Substation

Traditional transmission representation of PV

Negative Load

G System

GEN Sources

46 kV

Transmission 138 kV

Distribution Lines/Load at 46/12 kV Substation

46/12 kV PV

Inverter/Gen Model – Dist 3 Phase

Sub-Transmission/ Distribution XFRMR

Transmission/Sub-Transmission XFRMR

Potential data transfer points

18

W Wind Model Power Electronics Config

PV Inverter/Gen Model – Central 3

Phase

PV

Inverter/Gen Model – Dist 1 Phase