push-out and composite beam tests of shear connectors

112
Retrospective eses and Dissertations Iowa State University Capstones, eses and Dissertations 1-1-1983 Push-out and composite beam tests of shear connectors David Joseph Dedic Iowa State University Follow this and additional works at: hps://lib.dr.iastate.edu/rtd Part of the Engineering Commons is esis is brought to you for free and open access by the Iowa State University Capstones, eses and Dissertations at Iowa State University Digital Repository. It has been accepted for inclusion in Retrospective eses and Dissertations by an authorized administrator of Iowa State University Digital Repository. For more information, please contact [email protected]. Recommended Citation Dedic, David Joseph, "Push-out and composite beam tests of shear connectors" (1983). Retrospective eses and Dissertations. 18147. hps://lib.dr.iastate.edu/rtd/18147

Upload: others

Post on 06-Dec-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Push-out and composite beam tests of shear connectors

Retrospective Theses and Dissertations Iowa State University Capstones, Theses andDissertations

1-1-1983

Push-out and composite beam tests of shearconnectorsDavid Joseph DedicIowa State University

Follow this and additional works at: https://lib.dr.iastate.edu/rtd

Part of the Engineering Commons

This Thesis is brought to you for free and open access by the Iowa State University Capstones, Theses and Dissertations at Iowa State University DigitalRepository. It has been accepted for inclusion in Retrospective Theses and Dissertations by an authorized administrator of Iowa State University DigitalRepository. For more information, please contact [email protected].

Recommended CitationDedic, David Joseph, "Push-out and composite beam tests of shear connectors" (1983). Retrospective Theses and Dissertations. 18147.https://lib.dr.iastate.edu/rtd/18147

Page 2: Push-out and composite beam tests of shear connectors

Push-out and composite beam tests

of shear connectors

by

David Joseph Dedic

A Thesis Submitted to the

Graduate Faculty in Partial Fulfillment of the

Requirements for the Degree of

MASTER OF SCIENCE

Department: Civil Engineering

Major: Structural Engineering

Signatures have been redacted for privacy

Iowa State University Ames, Iowa

1983

Page 3: Push-out and composite beam tests of shear connectors

ii

TABLE OF CONTENTS

1. INTRODUCTION

1.1 General

1.2 Objectives

1.3 Literature Review

1.4 General Test Program

1.4.1 1.4.2

Push-Out Test Program Composite Beam Test Program

2. DESCRIPTION OF TEST SPECIMENS

2.1 Push-Out Tests

2.1.1 2.1. 2

Description of Specimens Fabrication of Specimens

2.1.2.1 2.1.2.2

Type A Specimens Type B Specimens

2.1.3 Loading Apparatus and Instrumentation

2.2 Composite Beam Tests

2.2.1 2.2.2

Description of Specimens Loading Apparatus and Instrumentation

3. TESTS AND TEST PROCEDURES

3.1 Push-Out Tests

3.2 Composite Beam Tests

3.2.1 3.2.2

Elastic Range Ultimate Strength

4. TEST RESULTS AND ANALYSIS

4.1 Push-Out Test Results and Analysis

4.1.1 4.1. 2

Type A Specimens Type B Specimens

Page

1

1

3

4

6

6 6

8

8

8 17

17 19

22

24

26 34

41

41

42

44 45

46

46

47 56

Page 4: Push-out and composite beam tests of shear connectors

iii

4.2 Composite Beam Test Results and Analysis

4.2.1 Elastic Range Test Results and Analysis 4.2.2 Ultimate Strength Test Results and Analysis

5. SUMMARY AND CONCLUSIONS

5.1 Summary

5.2 Conclusions

6. ACKNOWLEDGMENTS

7. REFERENCES

8. APPENDIX. LOAD-SLIP AND LOAD-SEPARATION CURVES

61

62 66

82

82

85

86

87

89

Page 5: Push-out and composite beam tests of shear connectors

iv

LIST OF TABLES

Table 1. Summary of push-out specimens tested

Table 2. Actual widths for each composite beam tested

Table 3. Physical properties of concrete

Table 4. Physical properties of steel

Table 5. Total number of DCDTs, deflection dials, and

strain gages on each composite beam

Table 6. Summary of tests performed on the composite

beam specimens

Table 7. Push-out tests: summary of test results and

predicted ultimate loads for Type A specimens

Table 8. Description of type of failures occurring in

push-out test specimens

Table 9. Push-out tests: summary of test results and

predicted ultimate loads for Type B specimens

Table 10. Summary of ultimate strength test results for the

composite beam specimens

Page

15

29

32

32

38

43

49

50

57

63

Page 6: Push-out and composite beam tests of shear connectors

v

LIST OF FIGURES

Figure 1. Details and dimensions of the push-out specimens

Figure 2. Angle-plus-bar shear connector (Series 1 and 3)

Figure 3. Channel shear connector (Series 2 and 4)

Figure 4. Stud shear connector (Series 5)

Figure 5. Double-nutted high-strength bolt shear connector

(Series 6)

Page

9

10

11

12

13

Figure 6. Epoxied high-strength bolt shear connector (Series 7) 14

Figure 7. Formwork used for constructing the push-out specimens 18

Figure 8. Location of instrumention used in the push-out

tests

Figure 9. Photographs of push-out specimens in place for

testing

Figure 10. Cross-section of model bridge showing the location

o£ longitudinal cuts

Figure 11. Location of composite beam sections where measure­

ments of slab width and thickness were determined

Figure 12. Location of high-strength bolt shear connectors

added to Beams #3 and #4

Figure 13. Photographs of composite beam test set-up showing

test frame and specimen in place

Figure 14. Loading apparatus employed for testing the

composite beams

Figure 15. Location of instrumentation on Beams #2 and #3

23

25

27

28

33

35

36

39

Page 7: Push-out and composite beam tests of shear connectors

vi

Figure 16. Location of instrumentation on Beams #1 and #4

Figure 17. Comparison of load-slip curves for half-scale

connectors

Figure 18. Comparison of load-slip curves for full-scale

connectors, Type A specimens

Figure 19. Comparison of load-slip curves for Series 5, 6,

and 7 specimens

Figure 20. Interior beam load-deflection curves for Tests

A, B, and C

Figure 21. Exterior beam load-deflection curves for Tests

A, B, and C

Figure 22. Photograph of Beam #1 showing bending of the

level post-tensioning rod at the bracket

Figure 23. Photographs showing concrete compressive failure

in Beam #3

Figure 24. Photographs of the failure mechanism in Beam #4

Figure 25. Load-midspan strain curves for composite

beams

Figure 26. Midspan strain profiles at various values of load

per point

Figure 27. Comparison of theoretical and experimental load­

deflection curves

Figure 28. Load-end slip curves

Figure 29. Load-slip curves for each composite beam

40

52

55

59

65

65

67

70

72

74

76

77

78

80

Page 8: Push-out and composite beam tests of shear connectors

vii

Figure A.I. Load-slip curves for individual Series 1

push-out specimens 90

Figure A.2. Load-slip curves for individual Series 2

push-out specimens 91

Figure A.3. Load-slip curves for individual Series 3

push-out specimens 92

Figure A.4. Load-slip curves for individual Series 4

push-out specimens 93

Figure A.5. Load-slip curves for individual Series 5

push-out specimens 94

Figure A.6. Load-slip curves for individual Series 6

push-out specimens 95

Figure A. 7. Load-slip curves for individual Series 7

push-out specimens 96

Figure A.8. Representative load-separation .

curves for

Series 1 push-out specimens 97

Figure A. 9. Representative load-separation curves for

Series 2 push-out specimens 98

Figure A.lO. Representative load-separation curves for

Series 3 push-out specimens 99

Figure A.ll. Representative load-separation curves for

Series 4 push-out specimens 100

Figure A.12. Representative load-separation curves for

Series 5 push-out specimens 101

Page 9: Push-out and composite beam tests of shear connectors

viii

Figure A.13. Representative load-separation curves for

Series 6 push-out specimens

Figure A.14. Representative load-separation curves for

Series 7 push-out specimens

102

103

Page 10: Push-out and composite beam tests of shear connectors

1

1. INTRODUCTION

1.1 General

After a useful life of more than 20 years, many bridges in Iowa

don't comply with current bridge standards. Increases in the allowable

live loads, changes in the AASHTO design and rating specifications,

and the necessity to provide additional load capacity to support

resurfacing for additional life have rendered these bridges inadequate.

Therefore, strengthening or posting of load limits is essential.

The feasibility of strengthening bridges, in particular, single

span, composite concrete slab/steel beam bridges, was considered in

a study (11) conducted several years ago by the Engineering

Research Institute of Iowa State University. The study, henceforth

referred to as Phase I, considered the use of post-tensioning to

strengthen bridges, therefore increasing the life of the bridge. A

half-scale model bridge was tested and analytical procedures were

utilized in order to determine the bridge's behavior when subjected

to post-tensioning and vertical forces. Post-tensioning forces were

applied to the steel bridge beams through brackets bolted

to the bottom flanges of the beams. Findings of Phase I included

recommendations to investigate the shear capacity of a post-tensioned

bridge and to continue experimentation on the half-scale bridge

model constructed and tested during Phase I.

A literature search revealed that only minimal data existed on

the angle-pIus-bar shear connectors. To obtain data on the angle-plus-

Page 11: Push-out and composite beam tests of shear connectors

2

bar, as well as channels, studs, and high-strength bolts utilized as

shear connectors, several push-out specimens were fabricated and

tested. Additional shear connector information was obtained by sawing

the bridge model from Phase I into four composite concrete slab/steel

beam specimens. As the type of steel may be unknown on some of the

bridges requiring strengthening, it was decided the addition of

shear connectors, as well as the post-tensioning brackets, in the

field should be by bolting rather than welding. Shear connectors

(high-strength bolts) were added to two of the composite beam

specimens before testing, while the remaining two specimens were

tested lias fabricated,1I with only the original angle-plus-bar shear

connectors.

All testing performed on the push-out and composite beam

specimens consisted of static loads because fatigue wasn't considered

a factor in the rehabilitation of bridges. It was concluded that a

large portion of the existing bridge components' fatigue life had

already been used. Results obtained from the push-out specimens were

used in the composite beam tests and later in the analysis of the

field bridges. The effect shear connectors had on the behavior and

ultimate strength of post-tensioned composite beams was found by

varying the number of shear connectors in companion specimens.

Page 12: Push-out and composite beam tests of shear connectors

3

1.2 Objectives

The present research is part of an ongoing research project on

the strengthening of composite, single span steel I-beam/concrete

deck bridges by post-tensioning. Constructed between 1940 and 1960,

these bridges were found to be inadequate in terms of shear capacity

because of changes in design philosophy and methodology. Also, it

was desired to check the behavior of the shear connectors in a

post-tensioned composite beam.

The overall objective of this research study is to explore the

behavior and ultimate strength of various shear connectors used in

composite bridges. Although the results reported, herein, are limited

as to the number of specimens, they should provide an indication of

the actual behavior of shear connectors. The specific objectives of

this study are to:

Relate appropriate AASHTO criteria to the actual behavior

as determined from tests on the push-out and composite beam

specimens.

Determine the behavior and capacity of the angle-pIus-bar

shear connector.

Develop and test high-strength bolt shear connectors.

Determine the behavior and capacity of post-tensioned,

composite beam specimens before and after increasing the

specimen's shear capacity.

In order to verify experimental results from the push-out specimens,

as well as to develop design methodology, experimental results were

Page 13: Push-out and composite beam tests of shear connectors

4

checked against predictions from AASHTO bridge specifications.

1.3 Literature Review

Numerous types of mechanical shear connectors have been proposed

since the early 1920s for steel-concrete, composite construction.

Although spirals, channels, and studs found wide acceptance in the

United States then, stud connectors are almost exclusively used today

because of their ease of installation and low cost.

The use of two slab push-out tests for the evaluation of shear

connector behavior was common (17,19,21). These early investigations

suggested that the strength of shear connectors obtained from push-out

tests was lower than that obtained from beam tests. It was later

concluded by Slutter and Driscoll (18) that this relationship was

true. Also, the push-out test is still considered to be the most

reliable and useful method of determining load-slip and ultimate

load capacities of different types of connectors used in beams (2,13).

The use of high-strength bolts (ASTM A325) as shear connectors

has been tested in a couple of situations (3,4,5). Dallam (3,4), in

1968 and 1970, reported the testing of two slab push-out and composite

beam specimens with high-strength bolts (ASTM A325, various diameters)

as shear connectors. The bolts were loosely attached to the steel beam

section and held in place by wire-spring chairs. After the slab

concrete was cured for 28 days, the bolts were tightened to the minimum

specified bolt tension; the specimens were then tested to failure.

It was found that the bolts exhibited a greater useful capacity and

Page 14: Push-out and composite beam tests of shear connectors

5

ultimate strength than comparable studs. In 1976, Dorton et ale (5) de­

scribed the use of high-strength bolts (ASTM A325, Type 3 weathering steel,

7/8 in. diameter) in push-out specimens and a full-scale test bridge.

Double-nutted to the beam flange of a steel bridge stringer (H-pile

section substituted in the push-out specimens), the bolts were placed

in oversized holes to accommodate movement of the concrete deck, due

to post-tensioning. Both the push-out specimens and the test bridge

were subjected to fatigue and static loading. Dorton concluded that a

high-strength bolt, in this particular configuration, could be safely

used to replace a welded stud of the same diameter. In these previous

studies, the bolts were placed before the concrete slab was cast.

Slutter and Driscoll (18) tested a series of composite beams

and push-out specimens. They also re-evaluated the test results from

other investigations in order to substantiate their conclusions. Tests

were performed on composite beams with varying numbers of shear

connectors. A number of different shear connectors (channels, spirals,

bent studs, headed studs) were tested in the composite beam and push­

out specimens. Test results from this, and previous investigations,

were compared utilizing a method of analysis for determining the

ultimate moment capacity of beams when a weaker shear connection than

that proposed for design exists. Slutter and Driscoll concluded that

the ultimate flexural capacity of a beam could be evaluated even if the

number of shear connectors was less than that required to develop the

theoretical ultimate bending capacity. The analysis showed that the

Page 15: Push-out and composite beam tests of shear connectors

6

load-deflection curve of a beam was not significantly affected by

slip if there were enough shear connectors provided to develop the

theoretical ultimate bending capacity.

1.4 General Test Program

As previously stated, the research program conducted consisted

of the testing of both push-out specimens and composite beam specimens.

The following sections present brief descriptions of the particular

specimens tested; the test programs implemented are presented in detail

in later sections.

1.4.1 Push-Out Test Program

Twenty-two push-out specimens were fabricated and tested to

failure. Five types of shear connectors were investigated for ultimate

strength, separation behavior, and load-slip behavior. The breakdown

as to type and number of specimens is as follows: 6 angle-pIus-bar

specimens, 5 channel specimens, 3 stud specimens, 4 epoxied high-strength

bolt specimens, and 4 double-nutted high-strength bolt specimens.

Relative slip and separation between the concrete and steel were

measured with mechanical displacement dial gages. Load was applied

using a 400 kip universal testing machine.

1.4.2 Composite Beam Test Program

The model bridge, tested in Phase I, was sawed into four composite

concrete slab/steel beam specimens. Two of the specimens, one

interior-type and one exterior-type, were strengthened with additional

Page 16: Push-out and composite beam tests of shear connectors

7

shear connectors before testing, while the remaining two specimens were

tested in the "as fabricated" condition. The loading condition for all

tests consisted of two equal concentrated loads located about the

span centerline so that a region of constant moment existed. Each

specimen was tested several times with different levels of post­

tensioning before being loaded to failure. Electrical resistance

strain gages, utilized in Phase I, were used to measure strain at

different locations on the specimens. Vertical deflection of the

specimens, as well as relative slip between the steel beam and

concrete slab, was measured with mechanical displacement dial gages.

Page 17: Push-out and composite beam tests of shear connectors

8

2. DESCRIPTION OF TEST SPECIMENS

2.1 Push-Out Tests

2.1.1 Description of Specimens

The push-out specimens consisted of two sizes: one full-scale

and the other half-scale. Dimensions of the specimens are shown in

Figure 1. As is shown, each specimen consisted of a wide flange beam

2 ft. long with concrete slabs attached to each flange of the beam.

The size of the wide flange beams utilized (WlOx22 in the half-scale

specimens and W10x68 in the full-scale specimens) was chosen on the

basis of flange thickness of the beam sections. The flange thickness

of the full-scale specimens closely approximated that of the exterior

beams in existing bridges; the flange thickness in the half-scale

specimens nearly equalled that of the exterior beams in the model

bridge. As shown in Figures 2 and 6, and also described in Table 1,

shear connectors were rigidly attached to the beam flanges by bolting

or welding. Load was applied to the upper portion of the beam and

transmitted into the slabs through the shear connectors. Thus, both the

slabs and beam were subjected to compression.

The push-out specimens were grouped into two categories: Type A

specimens (shown in Figures 2, 3, and 4) employed welded connectors

installed before the concrete was poured. Type B specimens (Figures 5

and 6) had high-strength bolts inserted and tightened after the slabs

had hardened and cured. Thus, Type A specimens modeled shear connectors

Page 18: Push-out and composite beam tests of shear connectors

PL

1"

X l'

3"

¢ W

10

x 22

(H

.S.)

W

10

x 68

(F

.S.)

#3

REIN

FORC

EMEN

T" iii i

' ,~'

---r-

(TYP

E B

ONL

Y)

i J It/t

olh~~

r- 1

#4 REIN-~

FORC

EMEN

T

#3

REIN

FORC

EMEN

T (T

YPE

B O

NLY)

1 "

6"

1"

~BED O

F TE

STIN

G M

ACHI

NE

HALF

SCA

LE

(H.S

.)

FULL

SC

ALE

(F.S

.)

#3

REIN

FORC

EMEN

T (T

YPE

B O

NLY)

r1

----t

4+-

REFE

RENC

E I-

t---

--i ,

LI

NE

I

#3

REIN

FORC

EMEN

T 1

(TYP

E B

ONL

Y)

.1 -I

NE

OPRE

NE

OR D

RY G

ROUT

2"

(H.S

.)

:1: 12

"

20"

(F. S

. )

Fig

. 1

. D

eta

ils

and

d

imen

sio

ns

of

the

pu

sh-o

ut

specim

en

1.0

Page 19: Push-out and composite beam tests of shear connectors

10

BAR 5/8 x 3/8 x 0 1 5" REFERENCE LI NE (SERIES 1)

BAR 1 1/4 x 3/4 x 0 1 10" (SERIES 3)

L 3 x 3 X 3/16 X 0 1 1 1/4" (SER I ES 1) ~"-....L.L..--i~--\

L 6 x 6 x 3/8 X 0 1 3 1/4" (SERIES 3)

3/16"

BEAM CENTERLI NE

1 1/4"-1 5/16" (SERIES 1)

2 1/2" -1 5/8" (SERIES 3)

a. Details of half-scale (SERIES 1) and full-scale (SERIES 3) connector

b. Photograph of full-scale connector Fig. 2. Angle-pius-bar shear connector (Series 1 and 3)

Page 20: Push-out and composite beam tests of shear connectors

11

REFERENCE LINE

3/411~ C3 X 4.1 x O· 3 1/2"

(SERIES 2) C5 x 6.7 x O· 8"

(SERIES 4)

BEAM CENTERLINE

N o::t"

(/') (/') I.J.J I.J.J ..... ..... 0:: 0:: I.J.J I.J.J (/') (/')

+ T 1 3/4" 4"

-----+- - t- + 1 3/4" 4"

t -L

a. Details of half-scale (SERIES 2) and full-scale (SERIES 4) connector

b. Photograph of full-scale connector

Fig. 3. Channel shear connector (Series 2 and 4)

Page 21: Push-out and composite beam tests of shear connectors

12

REFERENCE LINE 3/8"

* 3/4"<1> X O' 5" HEADED STUD ----+I f f

4 3/8" 4 3/4"

t *

W10 x 68

BEAM CENTERLINE --~ 10 1/8"

! a. Details of full-scale stud connector

b.Photograph of stud connector

Fig. 4. Stud sheax connector (Series 5)

Page 22: Push-out and composite beam tests of shear connectors

13

REFERENCE LI NE

GROUT

2-3/4"</> x o I 6 1 /2 "----1~~~'irTw;,~1IIIot

ASTM A325 BOLT (6" C. to C.) WITH 3" THREAD LENGTH

W10 x 68

7/8"

f

a. Details of double-nutted high strength bolt shear connector

r-

" ( . ,

~.

' ,.

,.

3

" -

..... .. _­- ' .

' . .

b. Photograph of double-nutted connector prior. to placement of grout

Fig. 5. Double-nutted high strength bolt shear connector (Series 6)

Page 23: Push-out and composite beam tests of shear connectors

14

REFERENCE LINE

3 1/4 II I+----;....I_~ 1 5/8" 1+--+1

GROUT -------f!~~;rw;.;,~ ....

2"<1> X 3/16" PLATE WASHER

2-3/4"<1> X O' 6 1/2" ASTM A325 BOLTS (6" C. to C.)

~~~

HARDENED CONCRETE

/

7/8"

t

W10 x 68

a.Details of epoxied high strength bolt connector

6"

b. Photograph of connector prior to installation of the bolts

Fig. 6. Epoxied high strength bolt shear connector (Series 7)

Page 24: Push-out and composite beam tests of shear connectors

15

Table 1. Summary of push-out specimens tested

SERIES TYPE CONNECTOR SPECIMENS DESCRIPTION

1 A half-scale angle-pIus-bar HAl HA2 HA3

2 A half-scale channel HCl HC2 HC3

3 A full-scale angle-pIus-bar FAI FA2 FA3

4 A full-scale channel FCI FC2

5 A full-scale stud FSI FS2 FS3

6 B double-nutted high- Nl strength bolt N2

N3 N4

7 B epoxied high-strength El bolt E2

E3 E4

Page 25: Push-out and composite beam tests of shear connectors

16

currently in use on various composite bridges and on the half-scale

. bridge of Phase I, while Type B specimens modeled techniques of

adding shear connectors to existing bridges. Because the type of

steel on several of the bridges requiring strengthening is unknown,

only shear connectors that can be added by bolting rather than

welding were tested.

Table 1 presents a breakdown of the push-out specimens grouped

according to specimen series and type. As shown, Type A specimens

were designated by two letters and one number. The first letter

designates the specimen size; H for half-scale and F for full-scale.

The second letter indicates the type of connector welded to the

flange: S represents stud, A for angle-pIus-bar, and C for channel.

The number distinguishes between the various specimens in a given series.

Type B specimens were all full-scale specimens and, therefore,

designated by just a letter and a number. The letter represents the

process used for attaching the slab to the beam flange by bolting:

E for epoxied and N for double-nutted. The number distinguishes

between specimens within a series. As may be seen, Series I through 5

5 were Type A specimens and Series 6 and 7 were Type B specimens.

Earlier research had shown that the bond doesn't change the

specimen's ultimate strength (17). Thus, although the beam flanges

and shear connectors were thoroughly cleaned with a wire brush

and then with acetone, no attempt was made to destroy the natural

bond between the concrete and steel.

Page 26: Push-out and composite beam tests of shear connectors

17

2.1.2 Fabrication ~ Specimens

A general description of the push-out specimens was given in the

previous section. The following two sections, Section 2.1.2.1 and

Section 2.1.2.2, present the fabrication procedures used for the

Type A and the Type B specimens, respectively.

2.1.2.1 ~ A Specimens The first step in the fabrication of

the specimens was welding the shear connectors to the beams. Channel

and angle-plus-bar connectors were welded utilizing a standard

weld while the studs were installed using a Nelson stud welder. The

location of the shear connectors in the various specimens may be

determined by correlating the reference line in Figures 2 through 6

with the reference line in Figure 1.

The push-out specimens were cast vertically; rather than horizon­

tally, so that both slabs could be cast from the same batch of concrete

in order to omit any variation in concrete strength from one slab to

another. Concrete was mixed in a 9 cu. ft. mixer in the structures

laboratory and cast into the forms in three individual lifts. Each

lift was thoroughly vibrated; care was taken to minimize the formation

of voids adjacent to the shear connectors. Forms were fabricated so

that thre~ specimens could be cast simultaneously, as shown in Figure 7.

Each slab was provided with a small amount of reinforcement, two layers

of 04 reinforcement, arranged as shown in Figure 1.

A minimum of three 6 in. diameter x 12 in. long standard ASTM

quality test cylinders were made during each pour. The specimens, as

Page 27: Push-out and composite beam tests of shear connectors

18

Fig. 7. Formwork used for constructing the push-out specimens

Page 28: Push-out and composite beam tests of shear connectors

19

well as the control cylinders, were covered with burlap and plastic

then wet cured for 5 to 7 days. Due to time constraints, the specimens

needed to be tested before 28 days had elapsed. Therefore, a high­

strength concrete was employed. From the nine day compressive strength

determined, the specimens were found to be sufficiently strong for

testing at an age of 14 days. Compressive strength values for all

Type A specimens are presented in a later section.

2.1.2.2 ~ ~ Specimens Fabrication of Type B specimens

began with the vertical casting of slabs in the same formwork used

for Type A specimens (Figure 7). A nominal amount of reinforcement was

provided, as well as three #3 reinforcing bars as labeled and shown

in Figure 1. The #3 reinforcing bars provided temporary connection

of the slab to the beam flanges until the high-strength bolt shear

connectors were in place. Prior to testing, the #3 reinforcing bars

were removed, so that the only connection between the slabs and wide

flange beam sections was provided by the high-strength bolts. Because

all the specimens were full-size, concrete was purchased from a local

ready-mix plant rather than mixing it in the laboratory as was done

for the half-scale, Type A specimens which required smaller aggregate.

The concrete was placed in two lifts, each of which was properly

vibrated to prevent honeycombing.

Four 6 in. diameter x 12 in. long standard ASTM quality test

cylinders were made for each set of three specimens. The specimens

and cylinders were then covered with burlap and plastic and wet-cured

Page 29: Push-out and composite beam tests of shear connectors

20

for 7 days. Due to the time required for the more involved fabrication

of Type B specimens, Series 6 specimens were tested 41 days after the

concrete was cast and Series 7 specimens were tested 52 days after

casting. Appropriate compressive strength values are presented later.

After the formwork was removed, each specimen was rotated so that

one slab was resting on the floor and the other resting on the beam

section so the desired shear connectors could be added. Two different

methods of adding high-strength bolt shear connectors to existing beams

were investigated for ease of installation, ultimate strength and

characteristics of load-slip and load-separation.

The first fabrication technique examined was the double-nut

configuration depicted in Figure 5. Two 3 1/4 in. diameter x 6 in.

deep cores, at 6 in. center to center, were drilled into each slab of

the Series 6 specimens. Location of the cores along the length of the

beam is given by the reference lines in Figure 1 and Figure 5. The

concrete cores were removed and a 3/4 in. diameter hole was drilled

through the beam flange at the center of each core. The side walls of

the core holes were then roughened and cleaned to improve the bonding

between the nonshrink Five Star grout and the hardened concrete.

Acetone was used to remove the oil residue left from drilling the steel

beams; water was used to remove the cementitious materials resulting

from the coring.

High-strength bolts (ASTM A325 3/4 in. diameter x 6 1/2 in. long)

were then placed in the holes through the beam flange and adjusted for

Page 30: Push-out and composite beam tests of shear connectors

21

an overall length of 5 in. above the flange. Bolts were then tightened

to the beam flange in a double-nut configuration. To retard the hydra­

tion process in the grout, the core walls were rinsed with water

immediately prior to placement of the grout.

When the grouting was placed, three 3 in. diameter x 6 in. long

standard ASTM quality test cylinders were made for determining the

compressive strength. The grouting and cylinders were wet-cured for

4 to 5 days.

The addition of shear connectors to Series 7 specimens followed a

different procedure, as portrayed in Figure 6. Two 3 1/4 in. diameter x

I 1/2 in. deep cores, at 6 in. center to center, were drilled into each

slab. The reference lines of Figure 1 and Figure 6 locate the core

holes along the length of the beam. At the center of each core, a

3/4 in. diameter core was drilled to the beam flange. After removal

of all core material, a 3/4 in. diameter hole was drilled through the

beam flange at each core location. The buildup of steel shavings

in the 3/4 in. core caused the drilling to be halted frequently in order

to remove the shavings. To provide an even bearing surface for the

1/8 in. plate washer and bolt combination, Five Star grout was placed

in the 3 1/4 in. diameter core and leveled off 1 1/2 in. below the top

surface of the slab. The grout used for leveling was allowed to wet

cure for a minimum of 4 days.

In order to fill voids and provide bonding between the bolt and

the slab, a concrete-steel epoxy was employed. The epoxy was spread

Page 31: Push-out and composite beam tests of shear connectors

22

thoroughly over the shaft of a 3/4 in. diameter x 6 1/2 in. long ASTM

A325 high-strength bolt. The epoxy-covered bolt was then placed in

the 3/4 in. diameter core and moved vertically up and down to provide an

even coating of epoxy between the core walls and bolt shaft. The bolts

were immediately tightened, thus forcing out any voids in the viscous

epoxy and providing uniform bonding between the steel and concrete.

The epoxy was allowed to cure for a minimum of 24 hours before Five

Star grout was placed in the 3 1/4 in. diameter cores (Figure 6).

Two 3 in. diameter x 6 in. long standard ASTM quality test

cylinders were made of the grout used in the previously described

patching process. The patching on all specimens and the control

cylinders were wet-cured for a minimum of 4 days.

2.1.3 Loading Apparatus and Instrumentation

Slip and separation between the slabs and the beams were measured

on all push-out specimens. The instrumentation for all specimens

consisted of eight deflection dials, located as shown in Figure 8.

Four deflection dials recorded slip and the remaining four deflection

dials measured separation at two elevations along the slab.

The four deflection dials (used to measure slip) were rigidly

attached to the web of the beam as shown in Figure 8. The stem of

each deflection dial was allowed to bear against blocks attached to

the slab as shown. Slip was measured relative to the centerline

of the various shear connectors.

The remaining four deflection dials, used to measure separation

Page 32: Push-out and composite beam tests of shear connectors

23

1 1/2" TYP.

1r-

1/2"</> THREADED ROD

a. Top vi ew

, b. Side v; e\'/

,--... . Vl Vl . ::c u.. -i 1 = = N N ........ ........ .- .-L.[') r--..

Tf

REFERENCE -,LINE

12"

11 f

Fig. 8. Location of instrumentation used in the push-out tests

Page 33: Push-out and composite beam tests of shear connectors

24

or "uplift," were rigidly attached to the platen of the universal

testing machine. As shown in Figure 8, separation was measured at

the connector centerline and 1 in. from the end of the slab bearing

on the testing machine platen.

The arrangement for testing in the universal testing machine is

shown in the photographs of Figure 9. Placement of the half-scale test

specimen in the testing machine is shown in Figure 9a and for the full­

scale test specimen in Figure 9b. For uniform load distribution, the

lower ends of the slabs were bearing either on a 1/4 in. thick pad of

neoprene or a thin layer of dry Portland cement. Load was applied

to the upper end of the steel beam by the head of the testing machine

through a steel distribution plate. A 3/4 in. diameter steel ball was

placed between the head of the testing machine and steel plate on the

half-scale specimens to provide concentric loading. When the full-scale

specimens were tested, the steel ball was removed due to the higher

loads involved. To restrain the slabs in the event that sudden

failure occurs, rope was wrapped around the various specimens during

testing.

2.2 Composite Beam Tests

As has previously been mentioned, the half-scale model bridge,

constructed during Phase I of this study, was cut into four individual

beams. The physical description, as well as the loading and instrumen­

tation of the four composite beams, is presented in the following

sections.

Page 34: Push-out and composite beam tests of shear connectors

a.

Hal

f-sc

ale

spec

imen

b.

" F

ull-

scal

e sp

ecim

en

Fig

. 9

. P

ho

tog

rap

hs

of

pu

sh-o

ut

spec

imen

s in

p

lace fo

r te

stin

g

N

V1

Page 35: Push-out and composite beam tests of shear connectors

26

2.2.1 Description of Specimens

The four composite steel beam/concrete slab specimens were fabricated

from the half-scale model bridge from Phase I. The model bridge framing

plan and midspan cross-section may be found in Reference 11. The

composite beam specimens were obtained by making five longitudinal cuts

in the model bridge as depicted in Figure 10. The cuts were made with

a gasoline-engine powered concrete saw which was provided and operated

by personnel from the Iowa Department of Transportation.

Two of the beams, Beams #1 and #4 (Figure 10), had a nominal slab

width of 1 ft Sin. and were exterior-type composite beams with a flange

on one side only. The remaining beams, Beams #2 and #3, had a nominal

flange width of 4 ft 10 in. and were interior-type composite beams with

equal widths of slab on each side of the beam centerline. Flange

widths on Beams #2 and #3 were made equal to the stringer spacing,

thus minimizing the number of saw cuts required. Flange widths on

Beams #1 and #4 were determined by calculating the width of slab

needed to locate the centroid of the slab about a vertical axis through

the centerline of the steel beam. This was done to decrease the possi-

bility of unsymmetrical bending. The actual composite beam slab

widths, given in Figure 11 and Table 2 along with the average slab

thicknesses, were the result of inaccuracies in the cutting process.

All four beams were equipped with the post-tensioning system used

in the testing of the model bridge of Phase I. Post-tensioning forces

of various magnitude were applied during testing of the beams by

stressing the Dywidag Threadbars on each beam. Details of the post-

Page 36: Push-out and composite beam tests of shear connectors

l' 5" 4' 10 1/8" 1'71/16"

( "'

,

-- "" ~ ~ CUTS

5' ,

I I

i

27

4' -

-..

I

1 0 1 /8" l' 71/16"

)

..

i I

l' 5"

z: 3: o 0:: U

-N

4' 10 1/8" 4' 10 1/8" 4' 10 1/8" 7 "--"~~---'--"':--"':'4----~-----1~'------':""'----'l~~7"

i I BEAM 1 il BEAM 2 tt! BEAM 3 ttl BEAM 4

Fig.IO. Cross-section of model bridge showing the location of longitudinal cuts

Page 37: Push-out and composite beam tests of shear connectors

28

CD CD Q) CD 210"210"210" 8 SECTIONS @ 21 a" " 16 1 a"

I~

x Y

TYPICAL SECTION FOR BEA~IS 2 AND 3

where, T = tl + t2 2

SLAB

BEAM

26 1 a"

@@@ 21 0"21 all

·1

x

TYPICAL SECTION FOR BEAMS 1 AND 4

Fig.11. Location of composite beam sections where measurements of slab width and thickness were determined (See Table 2 for values of each variable )

Page 38: Push-out and composite beam tests of shear connectors

Tab

le 2

. A

ctu

al w

idth

s fo

r ea

ch c

om

po

site

bea

m t

est

ed

BE

AM

II

I BE

AM

114

POIN

T a x

(IN

. )

ta (I

N.)

PO

INT

a x (I

N.)

ta

(IN

.)

1 1

0.5

0

4.2

5

1 1

0.0

0

4.0

0

2 1

0.2

5

4.2

5

2 1

0.0

0

4.0

0

3 1

0.2

5

4.3

8

3 1

0.0

0

4.1

2

4 9

.62

4

.25

4

10

.00

4

.00

5

9.2

5

4.1

2

5 1

0.0

0

4.1

2

6 9

.62

4

.12

6

10

.00

4

.25

7

10

.25

4

.12

7

10

.25

4

.12

8

10

.38

4

.25

8

10

.12

4

.12

N

1.

0 9

10

.50

4

.12

9

10

.00

4

.12

10

1

0.6

2

4.1

2

10

9.7

5

4.0

0

11

10

.38

4

.12

11

9

.50

4

.12

12

1

0.6

2

4.1

2

12

9.7

5

4.0

0

13

1

1.0

0

4.1

2

13

1

0.1

2

4.0

0

14

11

.25

3

.88

14

1

0.6

2

3.8

8

AV

E.

10

.32

4

.16

A

VE.

1

0.0

1

4.0

7

aRef

er

to F

ig.

11 fo

r d

efi

nit

ion

of

x,

t,

X,

Y,

and

T.

Page 39: Push-out and composite beam tests of shear connectors

Tab

le

2 (c

on

tin

ued

)

BEAM

fI2

BE

AM

113

PO

INT

X

a (I

N.)

y

a

(IN

.)

Ta

(IN

.)

POIN

T

Xa

(IN

.)

ya

(IN

.)

Ta

(IN

.)

1 3

1.1

2

28

.50

4

.22

1

28

.00

28

.62

4.0

6

2 3

1.1

2

28

.62

4

.25

2

28.6

2 28

.62

4.0

6

3 3

1.1

2

28

.62

4

.19

3

28

.75

2

8.2

5

4.0

0

4 3

1.0

0

28

.50

4

.16

4

28

.62

2

7.8

8

4.0

6

5 3

1.0

0

28

.50

4

.09

5

28

.50

2

7.6

2

4.0

6

6 3

1.1

2

28

.38

4

.09

6

28

.50

2

7.3

8

4.1

9

7 3

1.0

0

28

.25

4

.06

7

28

.50

2

7.2

5

4.1

9

8 3

1.0

0

28

.12

4

.16

8

28

.38

2

7.0

0

4.1

2

V..l

9 3

0.7

5

28

.12

4

.16

9

28

.62

2

7.0

0

4.0

6

0

10

30

.62

2

8.2

5

4.0

6

10

29

.00

2

7.1

2

4.0

6

11

30

.38

2

8.2

5

4.0

3

11

28

.88

27

.12

4

.19

12

2

9.8

8

28

.38

4

.00

12

2

8.8

8

27

.12

4

.12

1

3

29

.62

2

8.7

5

4.0

6

13

28

.62

2

7.0

0

4.1

9

14

29

.50

2

9.0

0

4.1

2

14

28

.62

2

7.2

5

4.1

2

AV

E.

30

.66

2

8.4

5

4.1

2

AV

E.

28

.61

2

7.5

2

4.1

1

Page 40: Push-out and composite beam tests of shear connectors

31

tensioning system employed may be found in Reference 11.

The properties of the concrete and steel in the four beams,

although also available in Reference 11, are presented in Tables 3 and

4 for convenient reference.

The shear capacity of the beams was less than that required by

AASHTO bridge standards (1). Therefore, additional shear connectors

(high-strength bolts double-nutted to the top flange) were added to

one interior beam, Beam #3, and one exterior beam, Beam #4. The loca­

tions of the existing angle-pIus-bar shear connectors for all four

composite beams are given in Reference 11; the locations of the shear

connectors added to Beam #3 and Beam #4 are shown in Figure 12.

These locations were dictated by the location of the existing angle­

plus-bar connectors. Core holes were located on either side of the

beam centerline; however, this placement was varied slightly on the

exterior beams so that the cores did not have to pass through

the curbs. For ease of construction, the core holes (3 1/4 in. diam­

eter) were drilled before the bridge was cut into individual beams.

The additional shear connectors were 1/2 in. diameter x 4 in.

long ASTM A325 high-strength bolts. The bolts were double-nutted to

the beam flange similar to the configuration (shown in Figure 5)

used in the Series 6 push-out specimens. An ultimate strength value

for the existing angle-pIus-bar shear connector was computed using

data obtained from the push-out tests. The total resisting force of

the angle-pIus-bar connectors was then determined for each beam and

Page 41: Push-out and composite beam tests of shear connectors

32

Table 3. Physical properties of concrete

Deck

Curb

f' (psi) c

3300

7450

Table 4. Physical properties of steel

Reinforcement

113

114

Prestressing

W16 x 26

W14 x 22

(J (ksi) y

69.8

70.8

44.1

44.7

(J 1 (ksi) u t

110.8

109.7

156.1

66.9

69.4

E(ksi)

2830

5080

E(ksi)

29,100

24,100

29,990

28,990

Page 42: Push-out and composite beam tests of shear connectors

"':I ..... OQ

t-' N

tl:It"' ro 0 III (') S Pl til rt ..... ~o Vol::l

III 0 ::l H\ 0.

::r ~ ..... +,-OQ

::r 1

til rt t1 III ::l

OQ rt ::r 0' o I-' rt

til ::r ro III t1

(') o 5 ro (') rt o t1 til

III 0. 0. ro 0.

rt o

r. BEARING -+ 1 1/2" 3/8" l' 1 1 /4" 1. l' 1 1/2" --k-

~< 8 1/4" 8" -'+<--

- 85/8" 9 1/8"

~

1 11/16"

7' 8 3/4" 7' 9 3/8"

2' 6 3/8"

t 2' 6 1/4"

co t ---+ rn » 3:

w

2' 5 3/4" 2' 5 3/4"

7' 10" 7' 10"

3/8"

8 5/8" ->j.- 1 1/4" 77/8" -':"""'::..!...C....-tmt--~ 1 1/2"

l' 1 1 /2" ..:.....:..L:....:.~tt)rl--

It BEARING I

8 3/4"

7 18" l' 1 3/8"

r

co rn » 3: oj:>

((

,..------ril--

l' 0" --r 1 3/16"~ l' 2 1/2"

-t- 15/16,,11

l' 5 3/8" 1/1"

r 1 3/16"11 1•

l' 10 1/2" I.iT'

" 6 t,,, 7/B"lt -L- .. I·~'

2' 5 1/4"

I .. ~,

2' 3 7/8"

+--t-H---2' 3 1/8" t-= .. 'T 3/

4"li 2' 6 1/8" =ff. I ~" --r- ..

l' 10 7/8" J. 1" Iw =m; l' 5"

I· l' 2 5/8" 7/8"

J i<

l' a"

l

Page 43: Push-out and composite beam tests of shear connectors

34

was found to be less than that required. Therefore, sufficient bolt

connectors were added to one interior and one exterior composite beam

to increase the shear capacity to the required level. The ultimate

strength of the bolts was calculated using the welded stud formula

for shear connectors in the AASHTO standards (1). From the laboratory

work performed on the push-out specimens, this was found to be slightly

conservative.

2.2.2 Loading Apparatus and Instrumentation

This section outlines the loading apparatus and instrumentation

employed on the four test specimens. The same loading apparatus,

except for slight variations in the load point location, was used in

all tests. The instrumentation was nearly identical on each of the

composite beams.

Load was applied to the beams through two 100 kip hydraulic

jacks bearing against a steel frame anchored to the structural testing

floor. Photographs of the test set-up used on the interior and exterior

beams are shown in Figure 13a and 13b, respectively. The load points

were nominally 80 in. apart; however, the exact locations may be found in

Figure 14 along with other details of the test set-up. In order to

transmit force uniformly to the slab, a combination of steel plates and

neoprene pads was placed between the jacks and the slab. To transmit

force through the curb and slab on the exterior-type composite beams,

a concrete block was placed under the neoprene pads. Force was then

transmitted through the concrete block and curb, which were at the same

Page 44: Push-out and composite beam tests of shear connectors

35

a. Interior beam specimen

b. Exterior beam specimen

Fig. 13. Photographs of composite beam test set-up showing test frame and specimen in place

Page 45: Push-out and composite beam tests of shear connectors

~

I

100 KIP LOAD CELL

36

W-SHAPE CONNECTED TO TEST FRAME

,

~ X .. I. Y "I

W14 x 22 (.BEAM 1 & 4.) .W16 x 26 {BEAM 2 & 37

'- OF SPAN

J..-------13' 0" ---~~ l ' 2 1/4" : ~f__--------- 26' 0 II

[ill PL - 1" x 9 II X 9 II

4" SLAB

EJ 3" X 9" X 9" NEOPRENE PAD

BEAM X Y

1 39 3/4" 40" 2 40" 40" 3 38 7/8/1 40 1/2/1 4 39 1/2" 39 3/4"

Fig. 14. Loading apparatus employed for testing the composite beams

Page 46: Push-out and composite beam tests of shear connectors

37

elevation. To prevent horizontal restraint at the load points, pin

and roller supports were provided under the jacks. The jack pin

support coincided with the beam's roller support and the jack roller

support with the beam's pin support; details of the load points

are provided in Figure 14.

The load on the specimen was measured by a 100 kip load cell and

checked by hydraulic jack pressure. The load cell was placed under

the jack pin support (Figure 14) and values of load were recorded

by the data acquisition system. Loads determined by jack pressure

were in good agreement with those determined using the load cell.

Post-tensioning load was applied by two 60 kip hydraulic jacks.

As was done in Phase I, the post-tensioning force was accurately

determined through the use of strain gages mounted on the tendons.

Instrumentation for all tests consisted of mechanical displacement

dial gages, electrical-resistance strain gages, and direct current dis­

placement transducers (DCDTs). DCDTs were used to measure relative

movement between the steel beam and concrete slab, or relative slip,

as well as the deflection at three locations. At all other locations,

displacements were measured with mechanical displacement dial gages,

henceforth referred to as deflection dials.

Electrical-resistance strain gages, henceforth referred to as strain

gages, were attached to the steel and concrete wherever measurement

of strains was desired. The strain gages were installed in the normal

manner with recommended surface preparation and adhesive. The majority

of the strain gages were installed during Phase I (i.e., on the model

Page 47: Push-out and composite beam tests of shear connectors

38

bridge) while the remaining strain gages were mounted after the com-

posite beam specimens had been fabricated. All the strain gages were

self-temperature compensated and provided with three-wire leads to

minimize the effect of the long lead wires and any temperature changes.

DCDT and strain gage measurements were read and recorded by the data acqui-

sition system, while deflection dial measurements were recorded manually.

All four composite beams, as may be seen in Figures 15 and 16,

were tested as simply supported beams. Also shown in these figures

are the locations of the strain gages, deflection dials, and DCDTs

used in each of the composite beam tests; note the DCDTs located at

the ends of each beam to measure relative slip. The total number of

DCDTs, strain gages, and deflection dials employed on each composite

beam is given in Table 5.

Table 5. Total number of DCDTs, deflection dials, and strain gages on each composite beam

BEAM NO.

1

2

3

4

DCDTs

5

5

5

5

DEFLECTION DIALS

8

7

7

8

STRAIN GAGES

16

18

26

29

Page 48: Push-out and composite beam tests of shear connectors

-.l 2"

T

39

-.l 2"

______ L_ ____ _L ____ __L ___ A__ T

• • •

--I\-- 2 1/4" 2 1/4"--11--I... 6' 6,,--~-+-I-f---V 6"~ 6"1--6' 0" _101 3' 11"-1 2' 7" ~ I.... 26' O"------------~ .. I

SIDE VIEW SYMBOL

1--2' 3"

1 r-1 ' 8"

2' 3"~

1'8"11

OJ 8" i

-t4 I- 3/4" TYPICAL SECTION

c::::::::::J ~

S •

TYPE OF MEASUREMENT GAGE

VERTICAL DISPLACEMENT DCDT RELATIVE SLIP DCDT VERTICAL DISPLACEt·1ENT DEFLECTION HORIZONTAL DISPLACEMENT DEFLECTION STRAIN STRAIN

F2'3"

r1' 1~1' 1"

2'3"~ l' l'+j....1' 1~1

SECTION 3 - 3

Fig. 15. Location of instrumentation on Beams #2 and #3

Page 49: Push-out and composite beam tests of shear connectors

40

~--------------~ ____________ ~--1 2"

____ _A_ __ - ----- ----- --A- - _.ll...-_ T

• • • •

, --11-- 2 1/4" 2 1/4"--11--

I" 6' 6"--J--o+ol .. f---6' 6"-----I6"r-2'9"+3'3"+/-3' 1l"+2'7"~ ,.. 26' 0" -,

SIDE VIEW SYMBOL TYPE OF MEASUREMENT GAGE

c::::J VERTICAL DISPLACEt~ENT DCDT ~ RELATIVE SLIP DCDT 0 VERTICAL DISPLACEMENT DEFLECTION ~ HORIZONTAL DISPLACEMENT DEFLECTION • STRAIN STRAIN

7"

-r--1 ~3/4"

SECTION 6 - 6 SECTION 3 - 3 TYPICAL SECTION

Fig. 16. Location of instrumentation on Beams #1 and #4

Page 50: Push-out and composite beam tests of shear connectors

41

3. TESTS AND TEST PROCEDURES

This section outlines the details of the specific tests. Each

test program (i.e., push-out tests and composite beam tests) consisted

of several individual tests. In this section, only test set-ups will

be discussed; interpretation and discussion of results will be presented

in Section 4.

3.1 Push-Out Tests

The tests involving both Type A and Type B push-out specimens

proceeded in the same general manner. Testing began with a pre-load

of approximately 10% of the predicted ultimate load for each specimen.

The pre-load value of 10 to 25 kips was applied for a variety of

reasons: to insure an even distribution of force through the proper

seating of the steel distribution plate on the beam flanges, to check

the operation of the deflection dials, and to break the bond between

the concrete and the steel beam.

By destroying the bond, consistent ultimate load results will

occur because the entire load is on the connectors (17). The bond was

physically destroyed even though it has been reported that shrinkage

of the concrete is sufficient to destroy bond (18). Previous research

(14) has indicated that the load-slip relationship will not be affected

by unloading and reloading the specimens.

After the pre-load had been released and equilibrium in the system

established, the load was applied in increments of varying magnitude.

Page 51: Push-out and composite beam tests of shear connectors

42

The magnitude of the increments for the tests varied from 10 kips to

50 kips at the beginning of the tests and I to 5 kips when failure

was imminent. After each increment of load, slip and separation

displacements were recorded. At higher values of load, the load was

held constant so that behavior (e.g., crack patterns) could be

recorded. When failure occurred, photographs were taken to show the

final deformed shape and the ultimate load was recorded. The specimens

were then removed from the testing machine and disassembled to deter­

mine the effects of the loading on the slabs and shear connection. The

duration of each test was approximately 40 minutes; the set-up time for

each test varied from I to 2 hours.

3.2 Composite Beam Tests

As has previously been mentioned, numerous tests were performed

on each composite beam. Test variables included magnitude of the

initial post-tensioning force and magnitude of vertical load. Four

tests were performed on each beam; the magnitude of test variables,

as well as the combination of variables in each test, is summarized

in Table 6. A description of the four tests performed on each beam,

as well as occurrences and test set-ups unique to the individual

composite beams during execution, is provided in the next two sections

(Section 3.2.1 discusses elastic range tests, Tests A, B, and C, while

Section 3.2.2 covers the ultimate strength tests, Test D).

To distinguish between tests, a number and a letter are used to

designate each test. Thus, Test 3A indicates the Test A of Beam #3.

Page 52: Push-out and composite beam tests of shear connectors

43

Table 6. Summary of tests performed on the composite beam specimens

BEAM NO.

1

2

3

4

TEST

A B C D

A B C D

A B C D

A B C D

POST-TENSIONING FORCE (KIPS)

0 12 24 34

0 16 32 48

0 16 32 48

0 12 24 34

VERTICAL LOAD PER LOAD POINT (KIPS) MAXIMUM INCREMENT

9 1 9 1 9 1

35.0 1a

18 1 15 1 15 1 48.3 1b

15 1 15 1 15 1 50.4 Ib

9 1 9 1 9 1

38.1 l a

aIncrement was increased to Zk after the vertical load reached 9k •

bIncrement was increased to Zk after the vertical load reached 15k •

Page 53: Push-out and composite beam tests of shear connectors

44

3.2.1 Elastic Range

The following sentences describe the testing procedures utilized

in Tests A, B, and C on the four composite beams.

Initially in Test A, each composite beam was loaded with a pre-

load of 1 to 2 kips to insure proper seating at the load points and

to check the performance of all gages and DCDTs. After the preload-

ing, initial "zero" readings for all strain gages, deflection dials,

and DCDTs were recorded. As loading progressed, strain and displace-

ment readings were taken after each load increment. As shown in

Table 6, each composite beam was loaded to slightly less than the cal-

culated elastic limit of the steel beam. Behavior was noted and

photographs were taken throughout the test. After the load was

released, beams were allowed to sit unloaded for a few minutes before

final "zero" readings were recorded.

Tests Band C were slightly different from Test A in that a

predetermined force was applied to the post-tensioning tendons

(Table 6 for magnitude of post-tensioning force). Composite beam

specimens were then pre-loaded, vertical load applied, and readings

taken as was done during Test A. The procedure used to "lock in" the

post-tensioning force was similar to that used in Phase I. Test length

(approximately one hour) was controlled in order to minimize any

variations in temperature and drift that may occur in the strain gages.

Page 54: Push-out and composite beam tests of shear connectors

45

3.2.2 Ultimate Strength

The final test performed on each beam, Test D, consisted of applying

vertical load to the post-tensioned beam until the ultimate capacity of

the beam was reached. The test procedure up to the calculated elastic

limit of the steel beam was identical to Tests Band C except that a

higher post-tensioning force (Table 6) was locked into each composite

beam. At the calculated elastic limit of the steel beam, the loading

increment was increased to 2 kips per load point. Behavior of the beam

was noted and photographs taken when significant deformations occurred

and when failure occurred.

Page 55: Push-out and composite beam tests of shear connectors

46

4. TEST RESULTS AND ANALYSIS

In Chapter 3, the details of the test program were presented.

In subsequent sections of this chapter, the results of each test and

events which occurred during each test will be summarized and an

analysis of their significance presented. For clarity, each test

will be discussed separately.

4.1 Push-Out Test Results and Analysis

Earlier, the push-out specimen descriptions (Section 2.1) and

push-out test procedures (Section 3.1) were presented. The following

sections will present behavioral information and data obtained from the

various push-out tests. Experimental results obtained are then compared to

theoretical values and to each other when relevant.

The data from the push-out tests consisted of slip and separation

measurements, as well as ultimate load values for each specimen. The

four slip readings obtained were averaged together to produce the average

slip per connector. In the case of a stud or high-strength bolt shear

connector, a connector consists of two studs or bolts. The load per

connector is one-half the total load applied to the steel beam.

The separation between the concrete and steel was measured at two

locations along the face of the slab. Deflection dials located 1 in.

above the bed of the testing machine were used to check for excessive

sliding of the specimen on the testing machine platen, as well as

separation between the slabs.

Page 56: Push-out and composite beam tests of shear connectors

47

The results from these dials indicated movement along the platen was

occurring, but was of a small enough magnitude to neglect. Relative sepa­

ration of the slabs at the base was found by averaging the two deflection

dials. The separation at the base does not provide a true value of

the "uplift" on the connectors but was checked to insure that it was

small; separation was found to be small, and, thus, was not given any

further consideration.

The average of the two deflection dials at connector level is

also referred to as the uplift of the slab from the beam. This

"uplift" or separation was checked to insure that it was "less than half

the interface slip at the corresponding load level" (22); thus, closely

approximating the uplift forces present in an actual composite beam.

All but one connector, the angle-pIus-bar, met the 50% limit. The

rigid nature of the angle-pIus-bar connector probably caused the

excessive separation and will be discussed in more detail later.

Because the uplift values obtained in the Series 2, 4, 5, 6 and 7

connectors were within the 50% limit (see typical load-separation

curves in the Appendix), the effect of uplift was considered to

have minimal influence on the behavior of these connectors.

4.1.1 ~ A Specimens

As explained in Section 1.2.1, the Type A specimens were tested in

order to obtain experimental values for angle-pIus-bar connectors (used

on bridges built from the 1940s to 1960s), welded studs, and channel

Page 57: Push-out and composite beam tests of shear connectors

48

connectors. By comparing experimental results to existing design

equations (1), a design rationale could be developed for the angle­

plus-bar connectors. The use of two slab push-out specimens is

generally accepted for the determination of the strength of shear

connectors (2,13,22). Results obtained from push-out tests provide

an upper limit to values used for the design of composite beams after

the push-out test results are checked for any inconsistencies (18,22).

To eliminate several of the variables, concrete compressive

strengths were held nearly constant and the physical dimensions of

the push-out specimens were held constant. Table 7 presents com­

pressive concrete strengths, experimental and theoretical ultimate

loads, and types of failure for Series 1 through 5. Predicted ulti­

mate load values for Series 2, 4, and 5 were obtained by using relation­

ships from AASHTO (1); those for Series 1 and 3 were obtained by using

a modified form of the AASHTO channel formula (1). As may be seen,

within the various specimen series the experimental ultimate load values

are very consistent as are the failure mechanisms (except for one case).

This same consistency can also be seen in the load-slip curves for

the individual specimens of a given series (see the Appendix).

The connector ultimate load values obtained experimentally

compared very well to the predicted values for the half-scale specimens

(Series 1 and 2). Referring to Table 7, the ratio of predicted to

experimental ultimate load for the channel and angle-pIus-bar

connectors yielded results between 1.00 and 1.13. The slightly low

Page 58: Push-out and composite beam tests of shear connectors

Tab

le

7.

Pu

sh-o

ut t~sts:

Sum

mar

y o

f te

st

resu

lts

and

pre

dic

ted

ult

imate

lo

ad

s fo

r T

ype

A

spec

imen

s

SPEC

IMEN

CO

MPR

ESSI

VE

OBS

ERV

ED

PRED

ICTE

D

RATI

O

OF

TYPE

D

ESIG

NA

TIO

N

STRE

NG

TH,

CONN

ECTO

R U

LTIM

ATE

PR

EDIC

TED

TO

OF

£

' c

ULT

IMA

TE L

OA

D,

LOA

D,

EXPE

RIM

ENTA

L FA

ILU

RE

a

PS

I K

IPS

KIP

S U

LT.

LOAD

SER

IES

1 H

Al

4110

3

8.0

4

2.1

1

.11

D

HA

2 41

10

41. 6

4

2.1

1

.01

D

H

A3

4110

4

2.0

4

2.1

1

.00

D

SE

RIE

S 2

HC1

41

10

40

.5

44

.2

1.0

9

C

HC2

4110

3

9.0

4

4.2

1

.13

C

HC

3 41

10

41

.4

44

.2

1.0

7

A

SER

IES

3 FA

1 48

50

12

5.4

1

82

.8

1.4

6

C

FA2

4850

1

29

.1

18

2.8

1

.42

C

FA

3 50

00

12

9.5

1

85

.5

1.4

3

C

SER

IES

4 FC

1 46

70

87

.7

12

4.7

1

.42

A

FC

2 46

70

84

.8

12

4.7

1

.47

A

SE

RIE

S 5

FS1

5000

5

8.1

6

3.9

1

.10

B

FS

2 46

60

56

.1

60

.6

1.0

8

B

FS3

4660

6

0.1

6

0.6

1

.01

B

a S

ee T

able

8.

~

\0

Page 59: Push-out and composite beam tests of shear connectors

Tab

le 8

. D

esc

rip

tio

n o

f ty

pe

of

fail

ure

s o

ccu

rrin

g

in p

ush

-ou

t te

st

spec

imen

s

LETT

ER D

ESIG

NA

TIO

N

A

B C

D

DES

CR

IPTI

ON

Ten

sile

cra

ckin

g o

f th

e s

lab

(s

imu

ltan

eou

s w

ith

co

ncre

te

cru

shin

g a

dja

cen

t to

co

nn

ecto

r)

Fra

ctu

re o

f th

e sh

ear

con

nec

tor

abo

ve

the b

eam

fl

an

ge o

r w

eld

p

rece

ded

by

crac

kin

g o

f th

e sl

ab

Fra

ctu

re i

n w

eld

att

ach

ing

th

e c

on

nec

tor

to th

e b

eam

fl

an

ge

Sh

eari

ng

of

a w

edge

o

f co

ncre

te f

rom

un

der

th

e c

on

nec

tor

(co

ncu

rren

t w

ith

th

e se

para

tio

n o

f th

e s

lab

fro

m t

he b

eam

fl

an

ge)

V1 o

Page 60: Push-out and composite beam tests of shear connectors

51

experimental values can be attributed to an unequal distribution of

load between the two connectors caused by slight eccentricities of

the specimen in the testing machine (21).

In Figure 17, the load-slip curves for half-scale, angle-pIus-bar

and channel shear connectors are presented. These load-slip curves

(as well as others which follow) are the average of the load-slip

curves for the individual specimens, which are presented in the Appendix.

The angle-pIus-bar connector provides more resistance to slip at all

values of load. Compared to the half-scale channel, the angle-pIus-bar

connector provided a more rigid connection as well as a slightly

higher ultimate strength.

The full-scale, angle-pIus-bar shear connector (Series 3), which was

previously used on composite bridges in Iowa, was compared to both

channel connectors (Series 4) and the stud connectors (Series 5). Of

the full-scale specimens tested, only Series 5 yielded results in good

agreement with calculated values (ratios of predicted to experimental

ultimate loads between 1.01 and 1.10). The low experimental results can

again be attributed to slight eccentricity of the specimen in the testing

machine. The results from the Series 3 and 4 specimens were in poor

agreement with the calculated values (ratios between 1.42 and 1.47),

although the low experimental ultimate load values, as well as

failure modes, were very consistent within a given series.

The low results for the Series 4 specimens were probably caused

by a large number of voids located adjacent to the loaded side of the

Page 61: Push-out and composite beam tests of shear connectors

52

50

VI c... ....... 40 ~

.. 0:: 0 I- 30 u w z z 0

o SERIES 1 (ANGLE-PLUS-BAR) u 20

0:: o SERIES 2 (CHANNEL) w c... 0 10 c:x: 0 .....I

0 0 .020 .040 .060 .080 .100 .120 .140 .160

AVERAGE SLIP, IN.

Fig. 17. Comparison of load-slip curves for half-scale connectors

Page 62: Push-out and composite beam tests of shear connectors

53

connectors. After testing, when the slabs were fully separated from

the connectors, it was discovered that voids comprised approximately

15% of the effective concrete bearing area. The percentage of voids

found in the other specimens was found to be considerably less. A

considerable number of the voids found were located near the channel

flange welded to the beam. Previous research (21) has indicated that

high stresses exist near the beam flange, and that the greatest portion

of the load carried by a channel connector is carried by the flange

welded to the beam. In Table 7, it can be noted that the Series 4

specimens (and one Series 2 specimen) failed by tensile cracking

in the concrete slabs. Since this failure was a function of the

dimensions of the slabs, this might also have caused the low experimental

values.

Series 3 specimens also experienced failure at loads much lower

than calculated. As can be noted in Table 7, all the Series 3 specimens

failed through the weld. Inadvertently, a 3/16 in. weld was provided

rather than the 1/4 in. weld specified on the bridge plans used for

modeling the laboratory bridge (11). The shear and bending capacity

of the 3/16 in. weld was calculated and found to be slightly below the

observed ultimate load. By providing a 1/4 in. weld, the capacity

would have been increased approximately 33%; thus, the ratio of

predicted to experimental ultimate load would have been lowered con­

siderably. In Section 4.1, it was noted that the separation of the

slab from the beam, or "uplift," was considered a significant problem

Page 63: Push-out and composite beam tests of shear connectors

54

on the Series 3 specimens. This is true because the angle-pIus-bar

connector, being a rigid connector, provides a greater resistance to

slip, which increases the tendency of the slabs to separate from the

beam. The failure of the weld at the leading (or first loaded) edge

of the angle further influenced the separation tendency.

The load vs. slip curves for the full-scale shear connectors

(Series 3, 4 and 5 specimens) are presented in Figure 18. For com­

parison, load-slip curves from two other research projects (15,21)

are also given. As may be seen, the rigid, angle-pIus-bar shear

connectors provided more resistance to slip than the flexible channel

or stud connectors. Referring back to Figure 17, this same difference

in rigidity can be seen in the half-scale specimens (Series land 2).

As may be seen, there is good agreement between Series 5 and the pre­

viously tested studs (15). A lack of agreement at the lower loads can

be attributed to the fact that the previously tested specimens were

not pre-loaded (Series 5 specimens were pre-loaded to 10% of the ultimate)

and some bond between the concrete and steel may have been present.

The channel connector (Series 4) did not correlate very well with the

previously tested channel connector (21). Though larger in size, as

well as length, the Series 4 connector exhibited consistently lower

values of load at equivalent values of slip. The presence of voids

adjacent to the connector is thought to have caused the difference.

To summarize, a modified form of the AASHTO formula for the

ultimate strength of a channel can be used to predict the capacity of

Page 64: Push-out and composite beam tests of shear connectors

55

160

140

(/) 120 0-...... :::.t:

.. 0::: 100 0 I-U l.JJ Z z 80 0 U

0::: l.JJ 0- 60 Cl '-'-c:( 0 ...J

40 0 SERIES 3 (ANGLE-PLUS-BAR) 0 SERIES 4 (C5 x 6.7 x o' 8") 6 SERIES 5 (2-3/4"<1> x O' 5" STUDS)

20 2-3/4"CP X O' 3" STUDS [REF. 21J C4 x 5.4 x O' 6" [REF. 1'5]

OL-__ -L ____ ~ __ ~ ____ ~ ____ ~ __ ~ ____ ~ ____ ~ __ ~ __ ~

o .020.040.060 .080 .100 . 120 • 140 . 160 .180

AVERAGE SLIP, IN.

Fig. 18. Comparison of load-slip curves for full-scale connectors, Type A specimens

Page 65: Push-out and composite beam tests of shear connectors

56

an ang1e-p1us-bar shear connector. However, the weld capacity should

be carefully checked for the effects of shear and bending. Keeping in

mind that the push-out specimen provides a conservative estimate of

shear connectors in a beam, the predicted ultimate load can be used

safely for the static analysis of shear connectors on bridges already

in use (18).

4.1.2 ~! Specimens

Type B specimens (Series 6 and 7), as stated in Section 1.2.1,

were tested to discover the effectiveness of using high-strength bolts

as shear connectors. The two bolt configurations tested (Figures 5 and 6)

produced the results shown in Table 9. Although a limited number of

specimens were tested, consistent results were obtained for each

connector series. This agreement is evident in the ultimate load

values in Table 9 and in the specimen load-slip curves which are

presented in the Appendix.

In order to evaluate the effectiveness of Type B specimens, welded

stud specimens (Series 5) were used for comparison. As may be observed

in Figures 4, 5, and 6, the physical dimensions of the connectors were

essentially identical (height was approximately 5 in. and the diameter

was 3/4 in.). The main differences between the bolts and studs were

the method of attachment to the beam flange (discussed in Section 2.1.2)

and the tensile strength. The minimum tensile strength of a high­

strength bolt is 120 ksi, while the tensile strength of a stud is

approximately 71 ksi (15) or 40% less than the bolt.

Page 66: Push-out and composite beam tests of shear connectors

Tab

le

9.

Pu

sh-o

ut

tests

: Su

mm

ary

of

test

resu

lts

and

pre

dic

ted

ult

imate

lo

ads

for

Typ

e B

sp

ecim

ens

SPEC

IMEN

C

OM

PRES

SIV

E O

BSER

VED

PR

EDIC

TED

a RA

TIO

OF

TY

PEb

DES

IGN

ATI

ON

ST

REN

GTH

, CO

NN

ECTO

R U

LTIM

ATE

PR

EDIC

TED

TO

OF

f'

(P

SI)

U

LTIM

ATE

LO

AD

, LO

AD

, EX

PERI

MEN

TAL

FAIL

UR

E c

KIP

S K

IPS

ULT

. LO

AD

SLA

B GR

OUT

SER

IES

6

Nl

5140

45

50

65

.4

65

.3

1.0

0

B

N2

5140

45

50

71

.2

65

.3

.917

B

V

I '-

I

N3

5140

45

50

70

.0

65

.3

.933

B

N4

5140

45

50

66

.9

65

.3

.976

B

SER

IES

7

El

5180

57

60

75

.0

65

.6

.875

B

E2

5180

57

60

76

.0

65

.6

.863

B

E3

5180

57

60

72

.2

65

.6

.909

B

E4

5180

57

60

72

.2

65

.6

.909

B

ap

red

icte

d u

lt.

load

bas

ed o

n A

ASH

TO

form

ula

fo

r w

elde

d st

ud

s (1

).

b S

ee

Tab

le 8

.

Page 67: Push-out and composite beam tests of shear connectors

58

Comparing values from Tables 7 and 9, it is evident that the bolt

connectors exhibited consistently higher values of ultimate load

than the studs. The Series 6 specimens produced ratios of predicted

to experimental ultimate load between .917 and 1.00 and the Series 7

ratios were between .863 and .909.· Series 5 connector ratios were

consistently greater than 1.01. The deviation in the ultimate strengths

may be attributed to the large differences of tensile strength between

the connectors, because an increase in the tensile strength is usually

accompanied by an increase in shear strength. In Table 9, the ultimate

load capacity of the epoxied bolt connector (Series 7) is shown to be

slightly higher than the double-nut bolt connector (Series 6). This

small difference is likely due to the reduced cross-sectional area on

the double-nut bolts because the threads were located in the shear

plane (Figure 5). Ratios of predicted to experimental ultimate load

below 1.00 for the bolt connectors (Table 9) indicate that the AASHTO

formula for the ultimate strength of studs provides a conservative

estimate of the ultimate strength of high-strength bolt shear connectors.

As may be seen in Figure 19, there is good correlation between

the Series 5, 6, and 7 specimen load-slip curves. Some of the variation

at medium values of load were probably caused by the method of attach­

ment to the beam (bolting versus welding). Up to loads of 15 to 20 kips,

the curves have approximately the same slope. From 20 to 45 kips, the

effect on the load-slip behavior due to bolting is noticeable. The

lower resistance to slip of the bolts is probably related to the seating

of the bolt in the hole through the flange. The seating effect was

Page 68: Push-out and composite beam tests of shear connectors

10

0,r

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

----

-_

80

Vl

0...

........ ~ ..

c:::

a 60

f-

U

LJ.J

z:

z: a

4+ #

I V

1 u

II

SERI

ES 5

(W

ELDE

D ST

UD)

'" c::

: 0

SERI

ES 6

(D

OUBL

E-NU

TTED

BOL

T)

LJ.J

0...

0 SE

RIES

7

(EPO

XIED

BOL

T)

Cl

cl:

a -l

20 OL

' ____

____

____

~ __

____

____

_ ~ __

____

____

__ ~ __

____

____

__ ~ __

____

___ ~~ __

____

___ ~ __

____

____

__ ~ __

____

____

__ ~

o .0

40

.080

.1

20

.160

.2

00

.240

.2

80

AVER

AGE

SLIP

, IN

.

Fig

. 1

9.

Com

pari

son

of

load

-sli

p

curv

es

for

Seri

es

5,

6,

and

7 sp

ecim

ens

Page 69: Push-out and composite beam tests of shear connectors

60

caused by deformation of the bolt threads until bearing in the hole was

achieved.

For loads up to 15 to 20 kips, the bolts provided a higher

resistance to slip than the studs. This occurred in the Series 7

specimens, because the slab was clamped down to the beam by the bolt,

and, thus, friction had to be overcome initially. The existence of

the nut on the flange in the Series 6 specimens helped create a more

rigid connection than that caused by a welded stud, because the nut

provided a higher connector stiffness.

Variations in the load-slip characteristics between the doub1e­

nutted bolt connector (Series 6) and the epoxied bolt connector

(Series 7) were minimal. Any differences can be explained by

examining the methods of attachment to the beam flange. The bonding

of the slab to the bolt, due to the epoxy and, more importantly, the

frictional forces from pretensioning the bolt, probably helped to lower

the initial slip values in the epoxied bolt connector. Beyond 30 kips,

the double-nutted bolt connector was more resistant to slip. The

main reason was the nut that was tightened against the beam flange.

The nut provided more bearing area for the concrete and increased the

connector stiffness adjacent to the beam. The location of high stresses

at the base of the connector is a well-known fact (21,22). The addi­

tion of a nut at the base can be compared to increasing the flange

thickness of a channel. The concrete restraint offered by increasing

the bearing area tends to stiffen the connector which is directly

Page 70: Push-out and composite beam tests of shear connectors

61

related to a decrease in slip at corresponding load levels (21).

The double-nutted bolt connector is the easier to install. Referring to

Section 2.1.2.2, it can be seen that the double-nut configuration can

be implemented with fewer installation steps (only one coring operation

and no epoxy to apply), quicker (metal shavings do not delay the

procedure), and employing fewer materials and equipment (only one

core bit needed and no epoxy is necessary). By using the AASHTO

ultimate strength formula for studs (1), the ultimate strength of the

double-nutted bolt connector can be conservatively estimated. The

need for bolting rather than welding (due to unknown steel beam

properties), coupled with the relative ease of application and con­

servative values of ultimate strength obtained through use of

existing shear stud relationships, make the double-nut connector

a viable method of increasing the shear capacity of existing composite

beams. Previous studies (4,5) have shown that high-strength bolts

performed satisfactorily under fatigue loading. Although a slightly

different bolting technique was utilized, fatigue effects should not

be significant in the author's opinion.

4.2 Composite Beam Test Results and Analysis

As previously mentioned in Section 1.2.2, the main thrust of

these tests was to determine the effects of additional shear connectors

on post-tensioned composite beams. Results and events of the elastic

range tests will be presented in Section 4.2.1, and ultimate strength

test results and occurrences will be discussed in Section 4.2.2.

Page 71: Push-out and composite beam tests of shear connectors

62

By post-tensioning a composite beam, the post-tensioning tendons

become part of the beam structure, thereby rendering the post­

tensioned portion of the beam statically indeterminate to the first

degree. When vertical load is applied to the beam, the force in the

post-tensioning tendons will change (referred to as the 8-T effect).

The load-deflection relation for this system is nonlinear; however, for

small values of post-tensioning, or axial, load (relative to the column

buckling load) the relationship is essentially linear. Secondary

P-8 effects in the 8-T analysis were neglected during Phase I.

However, the large deflections caused by large vertical loads normally

require the addition of P-8 effects. Because the thrust of this

testing was to discover the effects of variable amounts of shear

connection, the P-8 effects were ignored. Therefore, beams that were

compared (e.g., Beams #1 and #4) had equal amounts of post-tensioning

force applied. As will be seen, reasonable agreement between predicted

and experimental ultimate moment values (Table 10) was obtained

despite the omission of P-8 effects.

4.2.1 Elastic Range Test Results and Analysis

Results presented and discussed in this section are for Tests

A, B, and C, all of which involved loading which produced stresses in

the steel beams below the elastic limit. Only experimental results are

presented in the following paragraphs; comparisons between experimental

results and theoretical results will be presented in the following

section on ultimate strength. Tests A, B, and C were performed on all

Page 72: Push-out and composite beam tests of shear connectors

Tab

le 1

0.

Sum

mar

y o

f u

ltim

ate

str

en

gth

test

resu

lts

for

the c

om

po

site

bea

m

spec

imen

s

BEAM

N

O.

1 2 3 4

TYPE

O

F U

LTIM

ATE

U

LTIM

ATE

BE

ND

ING

MO

~lli

NT,

IN-K

IPS

FA

ILU

RE

VER

TIC

AL

LOA

D,

KIP

S M

u M

' u

Mu"

Mu

III

Sh

ear

con

nec

tio

n

35

.0

4140

39

18

4529

41

86a

Tes

t st

op

ped

b

efo

re f

ail

ure

4

8.3

58

13

5780

65

29

6367

a

Cru

shin

g o

f co

ncre

te s

lab

5

0.4

61

02

5780

65

34a

N.A

.b

Cru

shin

g o

f sl

ab

and

cu

rb

38

.1

4503

39

18

4585

a N

.A.b

Mu

-ex

per

imen

tal

test

mom

ent

(dea

d

load

in

clu

ded

)

Mu

' -

theo

reti

cal

bas

ed o

n n

o p

ost

-ten

sio

nin

g a

nd a

deq

uat

e sh

ear

con

nec

tio

n a

ssum

ed

Mu

" -

theo

reti

cal

bas

ed o

n p

ost

-ten

sio

nin

g a

nd a

deq

uat

e sh

ear

con

nec

tio

n a

ssum

ed

Mu'"

-

theo

reti

cal

bas

ed o

n p

ost

-ten

sio

nin

g a

nd

inad

equ

ate

shea

r co

nn

ecti

on

~se

the

theo

reti

cal

ben

din

g m

omen

t as

mar

ked

.

b N

ot A

pp

lica

ble

.

Mu

a .98

9

.91

3

.93

4

0\ w

.982

Page 73: Push-out and composite beam tests of shear connectors

64

of the composite beams without any unusual occurrences.

Experimental midspan deflections, due to vertical load only, for

the interior and exterior composite beams are presented in Figure 20

and Figure 21, respectively. As may be seen, there is very little

difference in the resulting deflection behavior either due to the

post-tensioning force (Test A, B, and C) or the additional shear

connectors (Beam #1 vs. Beam #4 and Beam #2 vs. Beam #3). Deflections

obtained from Test A (no prestress force locked in the beams) were

most linear throughout the entire elastic range. This is expected

because without the post-tensioning force applied the problem is linear.

After the post-tensioning force is locked in, the relation between

vertical load and deflection is nonlinear but, as shown in Figure 20

and Figure 21, this is insignificant throughout the entire elastic

range.

The slight differences in deflections at lower values of load are

most likely due to the varying degree of bond between the steel beam

and concrete slab and variation of prestress force. Previous testing

(during Phase I) when the beams were part of the half-scale model bridge

as well as the cutting process, movement of the beams for testing, and

the initial pre-load before each test accounted for the varying degree

of bond present. Different values of prestress force also caused a

slight variation in deflection (Figures 20 and 21). At higher values

of prestress force, the composite beams tended to deflect more at lower

values of vertical load. This is probably due to a lower moment of

Page 74: Push-out and composite beam tests of shear connectors

65

14

12 V) a.. ...... ~ 10 ~

I-Z ...... 0 8 a.. 0: w 0..

Cl 6 c:( 0 -J

4 TEST BEAM A B C

2 • • • 2 -- 3 0 6 0

Fig. 20. Interior beam load-deflection curves for Tests A, B, and C

Vl 0.. ...... ~

~

I-Z

0 a.. 0: w 0..

Cl c:( Cl -J

12r----------------------------------,

10

8

6

4 TEST BEAM

I~ B C

1 • • 2 4 6 0

O~ ____ L_ ____ L_ __ __J~ __ __J~ __ __J~ __ ~

0.000 0.100 0.200 0.300 0.400 0.500 0.600 MIDSPAN DEFLECTION, INCHES

Fig. 21. Exterior beam load-deflection curves for Tests A, B, and C

Page 75: Push-out and composite beam tests of shear connectors

66

inertia resulting from cracks in the concrete caused by prestressing.

At higher values of vertical load, the concrete cracks were closed,

thus increasing the stiffness of the post-tensioned composite beam.

Though both of the strengthened composite beams deflected

slightly more than their unstrengthened counterparts, this was

probably due to a small decrease in the moment of inertia because

of a smaller slab width but mainly due to experimental error.

4.2.2 Ultimate Strength Test Results and Analysis

The ultimate strength test, Test D, performed on each composite

beam provided data for vertical loading from 0 kips to ultimate.

Data obtained from the various tests will be compared to illustrate

the effects of varying the amount of shear connection in a post­

tensioned composite beam. Theoretical results will also be compared

to the experimental data.

Test lD, performed on the lias fabricated" exterior composite

beam (Beam #1), proceeded up to 18 kips per load point uneventfully.

At a vertical load of 18 kips, deformation in the bracket and the

flange under the bracket became visible. The beam continued to resist

load; however, the rate of slip occurring increased more rapidly (as

will be shown later). While loading proceeded, it was noted that the

post-tensioning rods remained level as the beam deflected. Figure 22

shows bending in the rod at the bracket caused by the rods remaining

level. This phenomenon was noted in all the composite beams when

loaded to their ultimate strength.

Page 76: Push-out and composite beam tests of shear connectors

67

Fig. 22. Photograph of Besm #1 showing bending of the level post­tensioning rod at the bracket

Page 77: Push-out and composite beam tests of shear connectors

68

At 30 kips, it was noticed that the bottom flange of the steel

beam had rotated to within 1/16 in. of the abutment. At 35 kips, the

sixth angle-pIus-bar shear connector from one end failed. The composite

beam failed to accept additional load at this point and testing was

terminated. Upon closer examination, it was noted that the slab

"rode up" over the shear connector. This phenomenon was similar to that

found in the Series 1 push-out specimens. The maximum recorded end

slip was .238 in. and the midspan displacement was approximately 3.57 in.

The other composite beam tested in the "as fabricated" condition,

Beam #2, was loaded to a maximum of 48.3 kips per point. During Test 2D,

the beam was noticed to have tilted slightly at a load of 18 kips as

one centerspan deflection dial read 0.2" lower than the other. This

value remained constant throughout the remainder of the test. The

deflection dials were removed at 37 kips along with the other displace­

ment gages to prevent damage if sudden failure occurred. A ruler at

the midspan provided approximate displacement values and the end

DCDTs measured relative slip until the test was terminated. At

48.3 kips, loading was stopped because of the danger of sudden failure

in the testing frame. The maximum slip recorded was .015 in. and the

midspan displacement was approximately 3 3/8 in. After the load was

removed, permanent flange deformation of approximately 2 1/2 in.

at midspan was observed. Some local buckling of the web under one

load point (near the location where the diaphragms formerly framed

in) was evident.

Page 78: Push-out and composite beam tests of shear connectors

69

Test 3D, performed on the strengthened, interior composite beam

(Beam #3), went according to plans up to a loading of 23 kips. At

this point, flange deformation under the brackets was noticeable and

the deflection dials were reset due to the large vertical deflections.

Deflection dials and DCDTs, except those measuring slip, were removed

at 44.2 kips (midspan displacement was 3.34 in.). Using a string line

stretched between the beam ends and a ruler, midspan displacements were

measured approximately. Testing was terminated at 48.8 kips because

the usable stroke on the hydraulic jack was reached. At this point,

cracks were observed on the underside of the slab, as well as crushing

of the concrete on the top side of the slab at the span centerline;

however, the beam was still capable of resisting load. At this point,

the maximum midspan deflection and end slip was 5 9/16 in. and .009

in., respectively.

In order to fail the composite beam, it was decided to release the

load, add 3 in. of steel plate at the load points, and resume loading.

Occasional readings were taken with a deflection dial and string

line at midspan and two DCDTs to record end slip; all the measurements

were initialized at 0 kips of vertical load. At a maximum load of

50.4 kips, a sudden compressive failure in the slab occurred at the

span centerline. A top view of the slab crushing can be seen in Figure 23a

and the bottom view is shown in Figure 23b. During reloading, the

maximum deflection never exceeded 5 9/16 in. and the final end slip

was .009 in. The shear connectors showed no signs of distress;

Page 79: Push-out and composite beam tests of shear connectors

:---

a.

Top

of s

lab

b.

Bot

tom

of

slab

,00"

". -

Fig

. 2

3.

Ph

oto

gra

ph

s sh

owin

g co

ncre

te c

om

pre

ssiv

e fa

ilu

re

in B

eam

#3

-...J

o

Page 80: Push-out and composite beam tests of shear connectors

71

however, some web buckling was noted in the same location as in

Beam #2.

The final ultimate strength test, Test 4D, proceeded uneventfully

up to 22 kips where it was noted that the lower beam flange in the

vicinity of the post-tensioning load brackets had deformed similar to

the previous composite beams. At 24 kips, near one load point, concrete

was visibly peeling away from the flange on the underside of the slab.

The chipping of the concrete was noticeable later (at approximately

28 kips) under the other load point but eventually ceased at both

locations around 30 kips. A loud cracking sound occurred at 33 kips

and a sudden drop in load of 2 kips followed. Holding the load constant,

it was discovered that the block of concrete under one of the jacks

had cracked. It was decided to continue the test; just before the

ultimate load of 38.1 kips was reached, a lateral bow of approximately

1/2 in. was observed. A sudden failure occurred simultaneously in

the slab and curb 16 in. from the span centerline (Figure 24a).

The compressive failure of the concrete was accompanied by local buckling

of the top flange directly below the distressed concrete, as is shown

in Figure 24b.

A comparison of theoretical and experimental ultimate bending

moment values is presented in Table 10. As may be seen, the experimental

moment was within 9.5% of the predicted capacity for all four composite

beams. The predicted ultimate bending moments were based on a plastic

stress distribution, which was modified when a state of inadequate

Page 81: Push-out and composite beam tests of shear connectors

72

• 0- 0' ; • : ..

a. Curb and slab failure

b. Top flanqe failure

Fig. 24. Photographs of the failure mechanism in Beam #4

Page 82: Push-out and composite beam tests of shear connectors

73

shear connection existed (18). The exterior-type composite beams,

Beams #1 and #4, provided experimental values that agreed very well

with the predicted values (Table 10). Also, it should be noted that

the addition of shear connectors increased the experimental ultimate

moment capacity only 8.8%. If the effects of post-tensioning aren't

included, the theoretical ultimate moment capacity of the exterior and

interior beams is reduced approximately 14% and 11.5%, respectively.

The type of failure, given in Table 10, for all of the composite

beams was as predicted. Beams #3 and #4, provided with an adequate

shear connection, failed by slab (and curb) crushing, while Beam #1,

with inadequate shear connection, failed through the shear connection.

Beams #2 and #3, interior-type beams, also provided reasonable

results. Though Test 2D was terminated, the maximum experimental

moment was close to the predicted value. The experimental moment

obtained in Test 3D could have been the result of stopping the test

to extend the stroke on the hydraulic jack before testing to failure.

Some crushing of the concrete was noted before stopping the test and

the reduction in cross-sectional area of the slab probably reduced

the ultimate moment slightly.

Figure 25 presents the effects of different levels of shear

connection on the bottom flange strains. As may be seen, there was

small variation due to the amount of shear connection, especially at

low loads. This agrees with the fact that the difference in relative

slip between "as fabricated" and strengthened beams was very small (as

will be seen in Figure 28). Reasonable correlation between experimental

Page 83: Push-out and composite beam tests of shear connectors

74

40~----------------~--------------------~

.. I­Z ........

2[ 20 c:: W 0...

C « 3 10

W16 x 22 THEORETICAL LOAD­STRAIN CURVE

o II o

o STRENGTHENED - BEAM 3 6 liAS FABRICATED II

- BEAM 2

0~ ____ ~ ____ ~ ______ ~ ____ -L ______ L-____ -1

o 500 1000 1500 2000 2500 BOTTOM FLANGE STRAIN, MICRO INCHES PER INCH a. Comparison of interior beams and theory

3000

40~--------------------------------------~

V') e. 30 ~

.. I­Z ........

:53 20 c:: W 0...

C

C§ 10 -1

W14 x 22 THEORETICAL LOAD-~ STRAIN CURVE o

o STRENGTHENED - BEAM 4 II liAS FABRICATED II

- BEAM 1

O~ ____ J-____ -L ____ ~~ ____ ~ ____ -L ____ ~

o 500 1000 1500 2000 2500 BOTTOM FLANGE STRAIN, MICRO INCHES PER INCH

b. Comparison of exterior beams and theory

3000

Fig. 25. Load-midspan strain curves for composite beams

Page 84: Push-out and composite beam tests of shear connectors

75

and computed strains is also shown in Figure 25. The theoretical

strains were based on full interaction between the beam and slab.

Profiles of strain at the centerline are given in Figure 26 for

the various beams at several levels of loading. Once again the

observed strains agree well with calculated strains (based on full

interaction), as well as between beams with different amounts of shear

connection. The strains at the higher values of load did not correlate as

well with the theoretical strain profiles. These differences were most

noticeable at the steel-concrete interface where slip may occur, thus

creating a localized effect at the gages.

In all tests, the measured deflection exceeded the theoretical

bending deflections, as illustrated in Figure 27. The theoretical

deflections are based on 100% interaction between the concrete and steel

beam and on the steel beam acting alone. As shown in Figure 27, the

experimental values are closer to the 100% interaction line. This

high degree of interaction agrees with the low relative slips experi­

mentally obtained. The theoretical curves in Figure 27 are based on

deflections due to bending effects only (no shear deformation effects

or P-~ effects) and, therefore, underestimate the observed deflections.

Illustrated in Figure 28 are the load vs. end slip curves for

each of the composite beams. As may be seen, the difference in slip

between the strengthened and "as fabricated" beams at low loads is

small. The rigid nature of the angle-pIus-bar connectors result in

low values of slip which may lower the difference in slips, especially

Page 85: Push-out and composite beam tests of shear connectors

76

all

V) c:c w c:: ::r:: :::I u u :z: ...... 5" .. c:c :z: cr:: 0 -l ...... V) I- 9" u w LOAD THEO. BEAM BEAM V)

w 1 4 I- K ...... 5.1 K 1 • • V)

0 20.0 2 0 0 a... :::E :::E 821" ,- c:r:

W

Ll.. c:c 0

::r:: I-a... w 0

28" COVER -800 -400 0 400 800 1200 1600 PLATE STRAIN, MICRO INCHES PER INCH

a • P = 5.1 K, P ~ 20.0K for exterior-type beams

V) 0" w c:c :J: c:r: U -l :z: V)

....... 4" ... LOAD THEO. BEAM BEAM :z: 2 3 0 .......

-, O. OK I- , • • u w

30.7K 2 0 0 V)

w I-

~12" :::E cr::

0 W 0... c:c :::E 0 U

Ll.. 0

:J: I-0...

~ 20" COVER -800 -400 0 400 800 1200 , 600 PLATE STRAIN, MICRO INCHES PER INCH

b. P = 10.OK, P = 30.7 K for interior-type beams

Fig. 26. Midspan strain profiles at various values of load per point

Page 86: Push-out and composite beam tests of shear connectors

77

35

30

U')

25 0... ....... ~

'" I- 20 z ....... 0 0...

c:: 15 w 0...

Cl <C

10 0 -..J

5 6 STRENGTHENED - BEAM 3 o liAS FABRICATED" - BEAM 2

0 0.00 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60

MIDSPAN DEFLECTION, INCHES a. Interior beams

30 o STRENGTHENED - BEAM 4 6 liAS FABRICATED" - BEAM 1

25 19 6 U') 0... cP .... ~ 20 ~

'" I- () Z .... 0 ~ 15 0 c::

0 W 0...

Cl 10 <C 0 -..J

5 W14 x 22 ALONE

0 0.00 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60

MIDSPAN DEFLECTION, INCHES b. Exterior beams

Fig. 27. Comparison of theoretical and experimental load-deflection curves

Page 87: Push-out and composite beam tests of shear connectors

78

50~---------=------------------------~

V) a. ~ 40

.. .­z ..... ~ 30 c:: w a. Cl

~ 20 -' -' « u ..... ~ 10 w :>

o liAS FABRICATED" - BEAM 2 o STRENGTHENED - BEAM 3

OL-____ ~ ____ ~ ____ ~ ______ ~ ____ ~ ____ ~

V) a.

0.000 0.005 0.010 0.015 0.020 0.025 END SLIP, INCHES

a. Interi or beam 50~----------------------------------~

~ 40 .. .­z ..... a a. 30 c:: w a. Cl

~ 20 -' -' « u ..... ~ 10 w :>

A liAS FABRICATED" - BEAM 1 o STRENGTHENED - BEAM 4

OL-____ ~ ____ ~ ____ ~ ____ ~ ____ ~ __ ~ 0.000 0.005 0.010 0.015 0.020 0.025

END SLIP, INCHES b. Exterior beam

Fig. 28. Load-end slip curves

Page 88: Push-out and composite beam tests of shear connectors

79

at small values of load. At approximately 70% of the ultimate load,

the "as fabricated" beams tended to exhibit more slip as a result of

having less shear connectors. Though Beam #2 was not taken to failure,

it can be noted that the increase in the slip was increasing at

approximately the same rate as Beam #1, which failed through the

shear connectors.

Figure 29 presents the experimental force per connector vs.

relative slip for each of the composite beams and the average load­

slip curve for the Series 1 push-out specimens. The approximate force

in the shear connector was found by expressing the vertical load

in terms of horizontal shearing force. Because Beams #3 and #4 had

two different types of shear connectors (angle-pIus-bar and high­

strength double-nutted bolt), a value for the bolt connectors in terms

of the angle-pIus-bar was approximated. As shown in Figure 29, a

typical connector in each of the composite beams provided roughly

the same amount of resistance to slip at equal values of force. The

load vs. slip curves from the composite beams were of the same shape

as the Series I curve, even though the values of slip were much lower.

As previously noted for the same connector, results from push-out

tests are more conservative than composite beam results. It may also

be noted in Figure 29 that the connector in Beam #1 has a maximum

calculated force of 39.9 kips, which is similar to that found experi­

mentally by the push-out tests (6% higher). All other beams had

connector forces lower than the push-out test connectors. This agrees

Page 89: Push-out and composite beam tests of shear connectors

V)

c...

....... ~

~

0:::

0 fo-

u w

z:

z:

0 u 0:::

w

c..

. w

u 0:

:: 0 l.J

...

50.1--------------------------------------------------------------~

40

----

---

--

0 -- -

0 ,-

----

-'=

--S

ER

IES

1

....-

PUSH

-OUT

SPE

CIM

ENS

/"

6 /'

30

• ,/

0 •

~·O

/ /

• /

.%1

0 BE

AM 1

-liA

S FA

BRI C

ATED

" 20

/

• BE

AM 2

-"A

S FA

BRI C

ATED

" e

/ 0

BEAM

3 -

STRE

NGTH

ENED

~

/ 6

BEAM

4 -

STRE

NGTH

ENED

/

10

/ 8

/ /

oV

0.00

0 o.

mo

0.02

0 0.

030

0.04

0 0.

050

0.06

0 0.

070

0.08

0 RE

LATI

VE S

LIP

, IN

CHES

Fig

. 2

9.

Lo

ad

-sli

p

curv

es

for

each

co

mp

osi

te

beam

00

o

Page 90: Push-out and composite beam tests of shear connectors

81

with the fact that only Beam #1 failed in its shear connection, while

the other beams (except Beam #2) failed by crushing of the concrete.

Page 91: Push-out and composite beam tests of shear connectors

82

5. SUMMARY AND CONCLUSIONS

5.1 Summary

The rehabilitation of composite bridges by post-tensioning the

steel beams was investigated in an earlier study (11). This study

was undertaken to investigate the inadequate shear connection that

exists between the deck and steel beams as a result of changes in

design philosophies.

The literature review substantiated the use of push-out tests

to determine the strength of shear connectors. Previous research

had indicated that high-strength steel bolts might be substituted

for welded stud connectors of the same diameter, with a gain in

ultimate capacity and no loss of fatigue capacity.

This study summarizes the results of the laboratory testing of

22 two slab push-out specimens and 4 composite concrete slab-steel

beam specimens. The composite beam specimens were cut from the model

bridge utilized in Phase I (11).

Good correlation was found between the experimental results

of the push-out tests and the theoretical results. Also, there was

excellent agreement in the ultimate strengths and load-slip

characteristics of the specimens in a given series.

The ultimate strength of angle-pIus-bar shear connectors,

employed on existing bridges, was found theoretically with a modi­

fied form of the AASHTO formula for the ultimate strength of channel

Page 92: Push-out and composite beam tests of shear connectors

83

shear connectors. Good agreement between experimental and theoretical

results was found, but it was noted that care must be taken not to

exceed the capacity of the weld between the angle and wide flange

beam. This is due to the rigid nature of the angle-pIus-bar connector

which increases the separation between the slab and beam, thereby

increasing the bending stresses on the connector weld.

Two methods of increasing the shear capacity of composite bridges

without welding, as the type of steel in some bridges is unknown,

were tested; both involved high-strength bolts as shear connectors.

The ultimate capacity of the high-strength bolts was conservatively

predicted using the AASHTO formula for the ultimate strength of

welded stud shear connectors. Experimentally obtained values were

consistently higher than predicted values, while the load-slip

characteristics of the bolt connectors were very similar to the stud

connectors. On the basis of its behavior and ease of installation,

the double-nutted bolt shear connector was used to strengthen two of

the composite beams.

The shear capacity of the four composite beams was predicted,

employing the results of the push-out tests. Because the shear capacity

was inadequate to develop the full bending capacity of the composite

beams, double-nutted shear connectors were added to two of the beams

employing the procedure used for the push-out specimens.

Deformation of the beams near the post-tensioning brackets

and of the post-tensioning tendon at the brackets occurred, but the

Page 93: Push-out and composite beam tests of shear connectors

84

post-tensioning system did not fracture. Instead, beam failures were

the result of shear connector failure or crushing of the slab (and/or

curb) concrete. Ultimate moment capacity was closely predicted

(within 10% of experimental values) for each of the beams utilizing

a plastic stress distribution. To account for a state of inadequate

shear connection, the plastic stress distribution was modified.

The addition of shear connectors affected the load-slip charac­

teristics at large values of vertical load and increased the ultimate

moment capacity slightly, however, the load-deflection curves weren't

significantly affected. Adding shear connectors also prevented failure

of the shear connection, in the case of the exterior beams. The

force developed in the composite beam shear connectors was similar

to that developed by the connectors in the push-out specimens.

Strains and deflections were predicted fairly accurately when

based on full interaction of the slab and steel beam. Experimentally

obtained deflections were consistently higher than those predicted

with full interaction.

Post-tensioning had little noticeable effect on the load-slip

or load-deflection characteristics of the composite beams, when

loaded in the elastic range of the steel beam. Secondary post­

tensioning effects (P-~ and ~-T) were ignored in the theoretical

analysis of the beams, but the accuracy of the predicted ultimate

moment values were unchanged. Computation of the ultimate moment

capacity without the effects of post-tensioning indicates a reduction

up to 14% of the beam capacity.

Page 94: Push-out and composite beam tests of shear connectors

85

5.2 Conclusions

1. The ultimate shear strength of angle-pIus-bar shear connectors

can be approximated using a modified form of the AASHTO formula

for the ultimate strength of channels. It is extremely important

to consider the strength of the weld used to attach the connector

to the beam flange.

2. High-strength bolts can be used as shear connectors with little or

no difference in the strength or behavior from that of welded

shear studs.

3. High-strength bolts attain a higher ultimate strength than

welded studs. A conservative value of ultimate shear strength

can be obtained employing the AASHTO formula for welded stud

ultimate strength.

4. Based on the limited number of tests performed, the shear

capacity of a composite beam can be increased by the addition

of double-nutted high-strength bolt connectors.

5. The ultimate moment capacity of a composite beam can be slightly

increased by the addition of bolt connectors in this particular

configuration.

Page 95: Push-out and composite beam tests of shear connectors

86

6. ACKNOWLEDGMENTS

The work described in this thesis was conducted at tile Iowa

State University structures laboratory, Ames, Iowa, by the Engineering

Research Institute of Iowa State University and made possible by

funding from the Iowa Department of Transportation under Research

Project HR 238.

I wish to express my appreciation to Dr. Wayne Klaiber for

his support and guidance during the preparation of this thesis.

Appreciation is also extended to Dr. W. W. Sanders, Jr. and

Kenneth Dunker for their assistance in the conduct of this project.

I thank Dr. Lowell Greimann and Dr. Fred Graham for sitting on my

committee.

Special thanks are given to Doug Wood, Research Associate,

for his assistance in various phases of the project. Thanks are

also due to the undergraduate students, Tim Dedic and Brad Beck,

for their contributions to this investigation.

I am especially grateful to my wife, Margaret, for her continued

understanding and encouragement throughout this project.

Page 96: Push-out and composite beam tests of shear connectors

87

7 . REFERENCES

1. American Association of State Highway and Transportation Officials. Standard Specifications for Highway Bridges. 12th edition. Washington, D.C.: American Association of State Highway and Transportation Officials, 1977.

2. Cook, J. P. Composite Construction Methods. New York: John Wiley and Sons, Inc., 1977.

3. Dallam, L. N. "Pushout Tests With High-Strength Bolt Shear Connectors." Missouri Cooperative Highway Research Program Report 68-7. Engineering Experiment Station, University of Missouri-Columbia, 1968.

4. Dallam, L. N. "Static and Fatigue Properties of High-Strength Bolt Shear Connectors." Missouri Cooperative Highway Research Program Report 70-2. Engineering Experiment Station, University of Missouri-Columbia, 1970.

5. Dorton, R. A., M. Holowka, and J. P. C. King. "The Conestoga River Bridge - Design and Testing." Canadian Journal of Civil Engineering, 4, No.1, March, 1977.

6. Gaylord, E. H., Jr., and C. N. Gaylord, Editors. Engineering Handbook. Second edition. New York: Book Company, 1979.

Structural McGraw-Hill

7. Goble, G. G. "Shear Strength of Thin Flange Composite Specimens." American Institute of Steel Construction, Engineering Journal, 5, No.2 (April, 1968), 62-65.

8. Heins, C. P., and D. A. Firmage. Design ~ Modern Steel Highway Bridges. New York: John Wiley and Sons, Inc., 1979.

9. Johnson, R. P. Composite Structures of Steel and Concrete. Vol. 1. New York: John Wiley and Sons, Inc., 1975.

10. Klaiber, F. W., K. F. Dunker, and W. W. Sanders, Jr. "Strengthening of Single Span Steel Beam Bridges." Journal of the Structural Division, Proceedings, ASCE, 108, No. ST12 (December, 1982), 2766-2780.

11. Klaiber, F. W., K. F. Dunker, and W. W. Sanders, Jr. "Feasibility Study of Strengthening Existing Single Span Steel Beam Concrete Deck Bridges." Final Report. Engineering Research Institute, Iowa State University, Ames, Iowa, 1981.

Page 97: Push-out and composite beam tests of shear connectors

88

12. Klaiber, F. W., W. W. Sanders, Jr., and D. J. Dedic. "Post­Tension Strengthening of Composite Bridges." Final Report. IABSE Symposium on Maintenance, Repair, and Rehabilitation of Bridges, 39, International Association of Bridge and Structural Engineers, 1982, 123-128.

13. Knowles, P. R. Composite Steel and Concrete Construction. New York: John Wiley and Sons, Inc., 1973.

14. Ollgard, J. G. "The Strength of Stud Shear Connectors in Normal and Lightweight Concrete." 11.S. Thesis. Lehigh University, Bethlehem, Pennsylvania, 1970.

15.

16.

Ollgard, J. Strength of Concrete." Engineering

G., R. G. Slutter, and J. W. Fisher. "Shear Stud Connectors in Lightweight and Normal-Weight American Institute of Steel Construction, Journal, 8, No.2 (April, 1971), 55-64.

Sabnis, G. M., Editor. Engineering. New York:

Handbook £f Composite Construction Van Nostrand Reinhold Company, 1979.

17. Siess, C. P., N. H. Newmark, and 1. M. Viest. "Small Scale Tests of Shear Connectors and Composite T-Beams." Studies of Slab and Beam Highway Bridges: Part III. University of Illinois Bulletin, 49, No. 45, Bulletin Series No. 396 (February, 1952).

18. Slutter, R. G., and G. C. Driscoll. "Flexural Strength of Steel-Concrete Beams." Journal of the Structural Division. Proceedings, ASCE, 91, No. ST2 (April, 1965), 71-99.

19. Viest, I. H. "Investigation of Stud Shear Connectors for Composite Concrete and Steel T-Beams." Journal of the American Concrete Institute, 27, No.8 (April, 1956),875-891.

20. Viest, 1. M., and C. P. Siess. "Design of Channel Shear Connectors for Composite I-Beam Bridges." Public Roads, 28, No.1 (April, 1954), 9-16.

21. Viest, I. M., C. P. Siess, J. P. Appleton, and N. M. Newmark. "Full Scale Tests of Channel Shear Connectors and Composite T-Beams." Studies of Slab and Beam Highway Bridges: Part IV. University of Illinois Bulletin, 50, No. 29, Bulletin Series No. 405 (December, 1952).

22. Yam, L. C. P. Design of Composite Steel-Concrete Structures. London: Surrey University Press, 1981.

Page 98: Push-out and composite beam tests of shear connectors

89

8. APPENDIX. LOAD-SLIP AND LOAD-SEPARATION CURVES

Page 99: Push-out and composite beam tests of shear connectors

90

40

Vl 0... ...... ~ 30 .. 0::: 0 I-u w z z 0 20 u 0::: SPECIMEN w 0...

0 HAl 0 c:t:

HA2 0 10 0 ....l

HA3 6.

OL-____ -J ______ -L ______ ~ ______ L_ ____ _....!

.000 .040 .080 .120 .160 .200 AVERAGE SLIP, IN.

Fig. A.l. Load-slip curves for individual Series 1 push-out specimens

Page 100: Push-out and composite beam tests of shear connectors

91

40

(/)

0-...... ::..:: .. 30 c:: 0 I-U w :z: :z: 0 20 u c:: SPECIMEN w 0-

Cl HC! 0 c:( 0 10 HC2 0 .-J

HC3 D.

OL-______ L-______ L-______ ~ ______ ~ ____ __J

.000 .040 .080 .120 .160 .200 AVERAGE SLIP, IN.

Fig. A.2. Load-slip curves for individual Series 2 push-out specimens

Page 101: Push-out and composite beam tests of shear connectors

VI

a... ~

:::.::: ..

0:::

0 I- u lJ...I

Z

Z

0 U

vv

,-7f

T

\0

N

0:::

lJ...I

a..

. C

l

40

lJi

SPEC

IMEN

ex:

: 0 ...

..J

FA1

0

FP,2

0

FA3

D-

rt/

20 oL.----L----L----L---~~--~--~~--~--~~--~

.000

.0

20

.040

.0

60

.080

.1

00

.120

.1

40

.160

.1

80

AVER

AGE

SLIP

, IN

.

Fig

. A

.3.

Lo

ad

-sli

p

curv

es

for

ind

ivid

ual

Seri

es

3 p

ush

-ou

t sp

ecim

ens

Page 102: Push-out and composite beam tests of shear connectors

Vl

Cl..

.....

. ~ ..

c::

0 I-

U

l..L.J

Z

Z

0 u c::

l..L.J

Cl..

Cl

<t

0 --I

120

100 60

r ~

~J ~

SPEC

IMEN

FC1

0

FC2

CJ

I r

20 o I

.O~O

O~--

~~--

~---

-~--

~~--

~~--

~~--

~L--

-~--

--~

.020

.0

40

.060

.0

80

.100

.1

20

.160

.1

40

.180

AV

ERAG

E SL

IP,

IN.

Fig

. A

.4.

Lo

ad

-sli

p

curv

es

for

ind

ivid

ual

Seri

es

4 p

ush

-ou

t sp

ecim

ens

1..0

W

Page 103: Push-out and composite beam tests of shear connectors

VI

c.. ......

120

100

~

80

.. 0

::

o I­

U

L1.J

Z

Z o

60 r

.f:

r-~ I

\0

U

I

rVI

---.6:=

::::..

---A

(j I

,p

-o:

: L1

.J c.

. ~

I ~

SPEC

I~lE

N g

40

l-~

FS1

0

FS2

0

FS3

b.

I /-

jJ'

20

O~r _

__

__

_ L-_

__

_ ~ _

__

__

_ ~ _

__

__

_ ~ _

__

_ ~ _

__

__

_ ~ _

__

_ ~~ _

__

_ ~ _

__

_ ~

.000

.0

20

.040

.0

60

.080

.1

00

.12

0

.14

0

.16

0

.180

AV

ERAG

E SL

IP,

IN.

Fig

. A

.5.

Lo

ad

-sli

p

curv

es

for

ind

ivid

ual

Seri

es

5 p

ush

-ou

t sp

ecim

ens

Page 104: Push-out and composite beam tests of shear connectors

120

100

V'l

0... ......

:::..:: ..

80

c:::

0 I- u LLI

:z:

:z:

0 60

r u

.~

\D

VI

c:::

LLI

0...

Cl

40

L /§

SP

ECIM

EN

c"l:

0 -J

Nl

0

N2

0

N3

b..

20 V

I

N4

0

OL' _

____

___ L

_ __

__

__

~ _

__

__

__

_ ~ _

__

__

_ ~~ _

__

__

_ _

L _

__

__

__

_ L

_ __

__

__

~ _

__

__

__

_ ~ _

__

__

_ ~

.000

.0

40

.OBO

.1

20

.160

.2

00

.240

.2

BO

.320

.3

60

AVER

AGE

SLIP

, IN

.

Fig

. A

.6.

Lo

ad

-sli

p

cu

rves

for

ind

ivid

ual

Seri

es

6 p

ush

-ou

t sp

ecim

ens

Page 105: Push-out and composite beam tests of shear connectors

120

100

(/)

0- ......

::.<:: .,

80

0::

0 I-

U w

z z 0 60

I u

~

1.0

0::

0-

W

0-

n

40 L

~

SPEC

IMEN

« 0 -l

E1

0

E2

0

E3

6.

20~

E4

0

oLI----L---~~--~--_f~--~--~~--~--~~--~

.000

.0

40

.080

.1

20

.160

.2

00

.240

.2

80

.320

.3

60

AVER

AGE

SLIP

, IN

.

Fig

. A

.7.

Lo

ad

-sli

p

curv

es fo

r in

div

idu

al

Seri

es

7 p

ush

-ou

t sp

ecim

ens

Page 106: Push-out and composite beam tests of shear connectors

97

40

(/)

0-...... ~ .. 30 ~ 0 f0-e...> LLJ z Z 0 20 e...>

~ SPECIMEN LLJ 0-

Cl HA2(AT CONNECTOR) 0 c:( 0 10 HA2(AT BASE) 0 .....J

O~ ______ ~ ______ ~ ______ ~ ______ ~ ______ ~ .000 .010 .020 .030 .040 .O~O

AVERAGE SEPARATION, IN.

Fig. A.8. Representative load-separation curves for Series 1 push-out specimens

Page 107: Push-out and composite beam tests of shear connectors

98

40

V') c.. ...... ~

~ 30

0::: 0 I-U w z z 0 20 u 0::: SPECIMEN w c..

Cl HCl(AT CONNECTOR) 0 c:::( 0

10 HCl(AT BASE) 0 --J

OL-____ ~ ______ -L ______ ~ ______ ~ ____ ~

.000 .010 .020 .030 .040 .050 AVERAGE SEPARATION, IN.

Fig. A.9. Representative load-separation curves for Series 2 push-out specimens

Page 108: Push-out and composite beam tests of shear connectors

120

100

V'l

0- ...... ~ ..

80

a:::

0 I-

<..

) W

Z

z: 8

60

rr

I I

IJ:)

IJ

:)

a:::

w

0- ~ 4

011

iT

SPEC

IMEN

FA1(

AT C

ONNE

CTOR

) 0

FAl(A

T BA

SE)

0

FA3(

AT C

ONNE

CTOR

) •

20~ /

/ FA

3(AT

BAS

E)

a &r

__

__

__

__

L-_

__

__

_ ~ _

__

__

__

_ ~ _

__

__

_ ~~ _

__

__

_ ~ _

__

__

__

_ ~ _

__

__

_ ~ _

__

__

__

_ ~ _

__

__

_ ~

.000

.0

20

.040

.0

60

.080

.1

00

.120

.1

40

.160

.1

80

AVER

AGE

SEPA

RATI

ON.

IN.

Fig

. A

.lO

. R

ep

rese

nta

tiv

e l

oad

-sep

ara

tio

n

cu

rves

for

Seri

es

3 p

ush

-ou

t sp

ecim

ens

Page 109: Push-out and composite beam tests of shear connectors

120

100

o (/)

Cl..

.....

. ~ 8

0 o

0::::

a I- u

o w

:z

: :z

: ,....

. 8

60

, ?

? a a

0::::

w

C

l..

/ ~

40

L

/ SP

ECIM

EN

FC1{

AT C

ONNE

CTOR

) 0

FCl{A

T BA

SE)

0

.020

.0

40

.060

.0

80

.100

.1

20

.140

.1

60

.180

AV

ERAG

E SE

PARA

TION

, IN

.

Fig

. A

.II.

R

ep

rese

nta

tiv

e lo

ad

-sep

ara

tio

n

cu

rves

for

Seri

es

4 p

ush

-ou

t sp

ecim

ens

Page 110: Push-out and composite beam tests of shear connectors

120

100

V')

0... ......

:.:

80

c:::

0 I- u l!J

:z::

:z::

0 60

r .....

. u

~

--n

--D

0 .....

. c::

: l..

LJ

0...

Cl

40 L

f/

SPEC

IMEN

« a

FS3(

AT C

ONNE

CTOR

) 0

-I

FS3(

AT B

ASE)

0

OLr

__

__

__

~ _

__

_ ~~ _

__

_ _

L _

__

__

_ ~ _

__

_ ~~ _

__

_ ~ _

__

__

_ ~ _

__

_ ~~ _

__

_ ~

.000

.0

20

.040

.0

60

.080

.1

00

.120

.1

40

.160

.1

80

AVER

AGE

SEPA

RATI

ON,

IN.

Fig

. A

.12

. R

ep

rese

nta

tiv

e lo

ad

-sep

ara

tio

n

cu

rves

for

Seri

es

5 p

ush

-ou

t sp

ecim

ens

Page 111: Push-out and composite beam tests of shear connectors

120

100

V)

0..

.....

. ~ ..

80

0::

0 l- t.

.)

UJ

Z

Z ~

60

, f

/ .....

. 0 tv

U

J

0..

~ 4a

l) /

SP

ECIM

EN

N2(A

T CO

NNEC

TOR)

0

N2(A

T BA

SE)

0

I r I

20 OA

r ___

____

_ ~ __

____

~ __

____

__ ~ __

____

~ __

____

__ ~ __

____

~ __

____

__ ~ __

____

~ __

____

__J

.000

.0

08

.016

.0

24

.032

.0

40

.048

.0

56

.064

.0

72

AVER

AGE

SEPA

RATI

ON,

IN.

Fig

. A

.13

. R

ep

rese

nta

tiv

e lo

ad

-sep

ara

tio

n

cu

rves

for

Seri

es

6 p

ush

-ou

t sp

ecim

ens

Page 112: Push-out and composite beam tests of shear connectors

(/)

0- .......

:::.::

0:::

0 t- U

LU

z:

z:

0 U

0::::

LU

0

-

0 c:x:

0 ....J

120

100 80

SPEC

IMEN

E2

(AT

CONN

ECTO

R)

0 E2

(AT

BASE

) 0

o I

I I

I I

.000

.0

20

.040

.0

60

.080

.1

00

.120

.1

40

.160

.1

80

AVER

AGE

SEPA

RATI

ON,

IN.

Fig

. A

.14

. R

ep

rese

nta

tiv

e lo

ad

-sep

ara

tio

n

cu

rves

for

Seri

es

7 p

ush

-ou

t sp

ecim

ens

......

o w