proudly made in the usa - surefire · the bms-100 detects a flame utilizing the igniter or...

40
Proudly Made in the USA INSTALLATION & OPERATIONS MANUAL PROUDLY MADE IN THE USA

Upload: others

Post on 20-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

Proudly Made in the USA

INSTALLATION & OPERATIONS

MANUAL

PROUDLY MADE IN THE USA

Page 2: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

2

The BMS-100 system is designed as a pilot maintainer to operate in Flare, Combustor, and Fire Tube applica-tions in the Oil and Gas Industry. The BMS-100 system utilizes the SureFire FTL-F series, FT-1-S, and FT-1-ST units to provide ignition.

The controller’s display is designed to operate in ambient temperatures from – 40⁰F to 131⁰F, and is coated for corrosion resistance. The unit is mounted in a NEMA 4X enclosure supplied with a UV resistant keypad. Each unit includes function indicator LED’s, and contains a status code chart that is printed on the overlay to pro-vide assistance in troubleshooting. The unit requires 12 VDC and is solar ready with a specific solar power ter-mination port. The controller also has been evaluated for pollution degree 2.

This apparatus is suitable for use in Class 1, Division 2, Groups C and D, or unclassified locations.

The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot flame makes contact with the igniter or thermocouple, a signal is sent to the BMS-100 and the unit registers a flame. The BMS-100 also provides 2nd stage solenoid and actuator valve timing control after flame is proven.

The BMS-100 also comes with an adder daughter board that allows 4-20mA input and high temperature safety shutdown. Plus a USB data logging port to log pilot flame with real time and date stamp.

The BMS-100 contains relighting capability, providing the flare, combustor and fire tube application with more opportunity to re-ignite the fuel gas.

Every SureFire system must pass complete factory QA/QC inspections before shipment.

Also available are control solenoid valve, Actuator valve, Standby Pressure Switches and FT ignition unit.

We are dedicated to providing quality American made safety control systems for Combustor and Flare Appli-cations. The system has been developed through thousands of hours of critical design, engineering, and field testing.

INTRODUCTION

Page 3: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

3

Introduction 2

Table of Content 3

Certifications and Warnings 4

Warranty Statement 5

BMS-100 Description

Enclosure 6

Circuit Board 7

Graphic Overlay 8

LED Indicators / Keypad Functions 9

Component Description

SureFire Ignition Units 10

Additional Components 11

Installation Guide 12-15

Installation Wiring Diagram 16

Fuel Train Diagram 17-19

Operation Guide 20-22

Operation Guide: Sequence of Operation / Flow Chart 23-28

Specifications 29

Troubleshooting Guide 30-33

Daughter Board Information and Installation 34-36

Daughter Board Setup 37-38

BMS - 100 Software Versions 39

Contact and Version Info 40

TABLEOFCONTENT

Page 4: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

4

WARNINGS:

EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2, GROUPS C AND D, OR UNCLASSIFED APPLICATIONS;

EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS;

EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS USED IN THE FOLLOWING DEVICES: HAMLIN ELECTRONICS RELAY, MODEL HE721A0500, AL-LIED ELECRONICS RELAY, MODEL JW2SN-DC12V, AND PANASONIC RELAY, MODEL DS2E-SL2-DC5V

SUBSTITUTION OF THE FOLLOWING COMPONENTS MAY IMPAIR SUITABILITY FOR DIVISION 2

MISE EN GARDE

RISQUE D’EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT ALTÉRER APTITUDE POUR LA CLASSE I, DIVISION 2, GROUPES C ET D OU DES APPLICATIONS DE UNCLASSIFED ;

EXPLOSION DE DANGER - NE DÉBRANCHEZ PAS L’ÉQUIPEMENT À MOINS QUE LE POUVOIR A ÉTÉ ÉTEINTE OU L’ENVIRONNEMENT EST CLASSÉ NON DANGEREUX;

L’EXPOSITION À CERTAINS PRODUITS CHIMIQUES PEUT-ÊTRE DÉGRADER LES PROPRIÉTÉS DE L’ÉTANCHÉITÉ DES MATÉRIAUX UTILISÉS DANS LES APPAREILS SUIVANTS : RELAIS ÉLEC-TRONIQUE LIN, MODÈLE HE721A0500, ALLIÉES ÉLECTRONIQUE, MODÈLE JW2SN-DC12V ET RE-LAIS DE PANASONIC, MODÈLE DS2E-SL2-DC5V

SUBSTITUTION DES ÉLÉMENTS SUIVANTS PEUT ALTÉRER LES QUALITÉS DE DIVISION 2

Reference Designation Description Type of Protection

K1, K2, or K3 Relay Sealed Contacts

CERTIFACTIONSANDWARNINGS

Page 5: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

5

Warranty Statement

SureFire warrants all equipment of its own manufacture to be free of defects in material and

workmanship for a period of twenty-four (24) months from the date of manufacture.

SureFire’s sole obligation hereunder shall be expressly limited to repair or exchange free of

charge, F.O.B. Farmington, NM, USA of such defective equipment. SureFire’s obligation

under this warranty is limited to the above and does not apply to claims which are a result of

improper installation, misuse, maladjustment, abnormal operating conditions, or lack of

routine maintenance as determined by SureFire. Nor does the warranty include the

furnishing of service for maintenance or problems arising from the foregoing causes. No

claims for labor, installation, removal, transportation, or other expenses will be recognized.

Notwithstanding any stipulation of the purchaser to the contrary, all other obligations,

representations, warranties and conditions, express or implied, statutory or otherwise,

including any implied warranties or conditions of merchantability, quality or fitness are

hereby excluded and, SureFire shall not be liable for any loss, cost or damages, of any kind

whatsoever, whether consequential, indirect, special or otherwise, arising out of or in

connection with the equipment or any defect therein, even if caused by the negligence of

SureFire, its employees or agents. The provisions hereof relating to the warranty and

limitations hereon and limitation of liability shall continue to be enforceable between the

parties notwithstanding termination of the within agreement for any reason including

fundamental breach. Equipment not of SureFire manufacture shall pass through to the end

user the vendor’s or manufacturer’s standard warranty.

WARRANTY

Page 6: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

6

Enclosure The SureFire BMS-100 system uses a polycarbonate NEMA 4X Enclosure to house the circuit board. The Graphic overlay, with a membrane keypad, is mounted on the exterior of the enclosure.

The NEMA 4X enclosure provides a high level of protection from harsh outdoor elements:

Windblown Dust Protection

Water Damage Protection - Rain, Sleet, Snow, Splashing and Direct Water Contact

Corrosion Protection

External Formation of Ice Protection

The Enclosure is IP66 certified, meaning it has been tested to the following:

Dust tight, no ingress of dust; complete protection against contact

Water projected in powerful water jets (12.5mm nozzle) against the enclosure from any direction shall have no harmful effects.

WARNING:

When drilling holes in the enclosure, ensure IP66 fittings are used to maintain the IP66 standard. Failure to use IP66 standard fittings nullifies the IP66 certification.

BMS‐100DESCRIPTION

Page 7: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

7

BMS-100 Circuit Board

The SureFire BMS-100 system is controlled by state of the art, non-arcing electronics that monitor and con-trol all combustor and flare applications. It comes with 2 LED indicators and a status code LED display.

BMS‐100DESCRIPTION

Page 8: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

8

Graphic Overlay The overlay provides the list of status codes on the face. The overlay is used for interfacing with the system and acquiring troubleshooting information.

BMS‐100DESCRIPTION

Page 9: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

9

5ButtonKeypad:The SureFire BMS-100 has a 5 button keypad to assist in controlling and monitoring the system. Note: Secondary & Tertiary functions can only be adjusted, when system is unlocked. Pre-purge time and timing between ignition attempts is now the same.

Button Functions

Primary: Turns the unit ON. Secondary: Press button for 5 seconds to display current number of ignition attempts. To set ignition attempts: Unlock system, press & hold ON button & use the up arrow button to set the number of ignition attempts. Range: 04 - 100

Turns the unit OFF.

Primary: Displays the code that corresponds with the current unit status. Secondary: Press button for 5 seconds to unlock the system. Tertiary: Up arrow - Increments settable value for pre-purge & safety T/C limit.

LED Indicators

The circuit board LEDs illuminate through the lid of the enclosure. The LEDs indicate the following:

LED Indicator Status

GREEN Blinking - Indicates a standby interlock is activated

RED LED ON - Indicates that the system is off

Blinking - Indicates a shutdown failure or interlock has been activated

LED ON - Indicates that the system is on and operating properly

BMS‐100DESCRIPTION

Primary: Displays the current battery voltage. Secondary: Press button for 5 seconds to display current pre-purge timing. To set pre-purge timing: Unlock system, press & hold Battery Volts button & use the up arrow button to set timing. Range: 01 - 10 minutes pre-purge time.

Primary: Displays the current flame strength value for the igniter or T/C.

Secondary: Press for 5 seconds to display current safety T/C limit.

To set safety T/C limit: Unlock system, press & hold T/C HTS button & use the up arrow button to set limit. Range: 100°F - 2400°F.

Page 10: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

10

SureFire FTL-F Series Ignition Unit The SureFire BMS-100 is compatible with any of the FTL-F piloted ignition units designed for combustor and flare applications. The pilots are reliable ignition system for all applications and utilizes a thermocouple to sense the pilot flame. Thermocouple and igniter element are easily field replaceable.

FT-1 Series Ignition Unit The SureFire BMS-100 is compatible with two (2) of the FT-1 Series ignition units designed for firetube applica-tions. The pilots are reliable ignition system and utilizes the igniter or thermocouple to sense the pilot flame.

Optional Flame Sensors

Igniter

Utilizes ohms resistance reading to verify flame Armored wiring harness to: 500°F duty / 800°F flash Direct termination to BMS-100 controller Thermocouple

Utilizes temperature reading to verify flame Armored wiring harness rated to: 1000°F duty / 1500°F flash Direct termination to the BMS-100 controller

FT-1-ST (above)

The unit above is utilizing a Thermocouple as a flame sensing mechanism.

FT-1-S (above)

The unit above is utilizing the Igniter Element as a flame sensing mechanism.

COMPONENTDESCRIPTION

FTL-F-72

FTL-F Mini

FTL-F-72 Flare Pilot Stainless steel 72” straight pilots for open flare application.

FTL-F Mini Combustor Pilot Stainless steel angle pilot for combustor application. Custom flange pattern and pilot length.

FTL-F-30 & FTL-F-40 Combustor Pilot Stainless steel 30” & 40” straight pilots for combustor applica-tion.

FTL-F-40

Page 11: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

11

Pressure Switch Used on a variety of standbys and shutdowns. Can be used as normally open or normally closed. Adjustable from 1psi — 15psi. 316 SS construction, wetted parts are NACE

1/4 in. ASCO Solenoid Valve

Fail closed device. No adjustment necessary. Simple termination and installation Application include - Combustor and Flare systems.

12 Volt, 1in. SureFire Actuator Controls the main fuel gas to the main burner. Factory programmed and pre-wired so no adjustment is necessary. 3 wire termination. Proof of valve closure contacts kits available Applications include - Combustor and Flare systems.

1in. & 2 in. SureFire Solenoid Valve Fail closed device. No adjustment necessary. Simple termination and installation. Kalrez elastomer plunger. Plunger replacement kits available. Applications include - Combustors and Flare systems.

COMPONENTDESCRIPTION

Page 12: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

12

EnclosureInstallation1. The enclosure is to be mounted on a pole or a building

that is capable of supporting 10 lbs. 2. Position the enclosure so that the LED display is clearly

visible for the operator. 3. Install conduit seal-off fittings for ALL electrical

connections at the enclosure. 4. Installation must comply with the local electric code.

Moun ng Hardware

Unistrut Clamp

Unistrut

2ndStageValveControl

SureFireActuator/SolenoidValve1. Install the SureFire Actuator or Solenoid Valve in the

fuel train for the vent or main line. 2. When an Actuator is being utilized. Terminate wires on

terminal block labeled Actuator Valve (1, 2, and 3) from the SureFire Actuator Valve terminals (1, 2 and 3), See note below.

NOTE: SureFire Actuator 1 @ Terminal block 1

SureFire Actuator 2 @ Terminal block 2

SureFire Actuator 3 @ Terminal block 3

NOTE: Must use SureFire Actuator valve or an actuator approved by SureFire.

3. When a 1” or 2” solenoid is being utilized. Terminate solenoid wires on ports 1 & 3 on Actuator Valve terminal block. Port 2 is not used. See Fig. 1.

WARNING

Before any welding is attempted, disconnect all wires going to the circuit board. Any damage caused by welding to the SureFire BMS is NOT covered under warranty.

Before terminating any wires, be sure no power is supplied to the controller. Any damage caused by standing on or using the enclosure as a step is NOT covered under warranty.

INSTALLATIONGUIDE

Page 13: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

13

PLC/ScadaConnectionThe proper connection method for the Alarm Out, Remote On, Remote Off and Run Status is as follow: 1. Terminate wires from the RTU/PLC to the Alarm out terminal

(Ports 6-7) 2. Terminate wires from the RTU/PLC to the Remote ON

terminals (Ports 11-12) and Remote OFF terminals (Ports 13-14)

NOTE: The remote ON / OFF receives a signal from a momentary switch (closed or open loop) from the PLC/SCADA to turn unit ON / OFF remotely.

NOTE: During a Shutdown error, unit cannot be reset remotely.

3. Terminate wires from the RTU/PLC to the Run Status terminals (Ports 15-16)

NOTE: These terminations are left un-touched if not used. NOTE: See page 28 for specification information on the ports above.

1stStageValveControl

SolenoidValve1. Ensure main supply gas is shut off. 2. Locate the pilot gas supply line. 3. Install a 1/4” ASCO or 1” SureFire solenoid valve in the

appropriate location in the pilot fuel train. 4. Cut and bend custom 3/8” tubing and connect to tubing

fittings on solenoid. 5. Use proper connectors and conduit for wiring. 6. Terminate solenoid wires at the Solenoid Valve

terminals (port 8-9) NOTE: See pages 17, 18 and 19 for solenoid location on fuel

trains for combustors and flares. NOTE: Solenoid proper flow direction. Reference ASCO: 2 = Inlet and 1 = Outlet

INSTALLATIONGUIDE

Page 14: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

14

Standbys1. Install a normally open or normally close dry contact

device in one of the assigned terminals (Ports 17-18 & 19-20)

2. If no device is used, a jumper needs to be inplace at the assigned terminal.

NOTE: Closed Contact = Normal Operation Open Contact = Failed Operation NOTE: Standby does not require a local reset to re-start

system.

Shutdowns 1. Install a normally open or normally close dry contact

device in one of the assigned terminals (Ports 21-22 & 23-24)

2. If no device is used, a jumper needs to be inplace at the assigned terminal.

NOTE: Closed Contact = Normal Operation Open Contact = Failed Operation NOTE: Shutdown requires a local reset to re-start system.

SureFireFTL‐ForFT‐1SeriesIgnitionUnit1. Ensure all supply gas is turned off and locked out /

tagged out 2. Install the FT unit in the flare or combustor. 3. The igniter has two white wires that are not polarity

sensitive and terminate wires to terminals (ports 27 & 28).

4. Flame Sensor wires need to be terminated as described on page 15.

INSTALLATIONGUIDE

Page 15: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

15

Flame Sensing Switch (Igniter or Thermocouple) Flame sensing mechanism will be dependent on the ignition unit being utilized. Ensure proper flame sensing mode has been selected. See Fig.1

For Igniter flame sensing, the igniter wires terminate at ports 27 & 28 and position switch on igniter.

For thermocouple flame sensing terminate the red (-) wire at port 5 and the yellow (+) wire at port 4 and position switch on thermocouple.

NOTE: Switch must be placed in proper position before power is applied to circuit board. Do not switch while circuit board is powered up.

Fig. 1

Solar Panel 1. Install 12 VDC Solar Panel 2. Connect negative (-) terminal to port 29 3. Connect positive (+) terminal to port 30 NOTES: Maximum rating for solar panel is 75 watts Circuit board has internal charge controller to charge 12 VDC

battery, if a battery is connected to port 31 & 32

Battery 1. Install a 12VDC SLA battery within an enclosure

separate of the SureFire enclosure. 2. Connect negative (-) terminal to port 31 3. Connect positive (+) terminal to port 32 NOTES: If battery is more than 10 feet away from SureFire

controller, use larger wire as needed. See page 28. If utilizing 12 VDC power supply, set voltage @ 13.4

VDC. Power supply should be rated for 90 + watts.

INSTALLATIONGUIDE

Page 16: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

16

INSTALLATIONWIRINGDIAGRAM

Page 17: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

17

1”Su

reFireSolenoid

FuelT

rain

1”SOLENOIDFUELTRAIN

Page 18: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

18

1”Su

reFireSolenoid

/Actu

atorFuelT

rain

1”SOLENOID/ACTUATORFUELTRAIN

Page 19: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

19

1/4”ASCO

Solenoid

/3PGValve/A

ctuatorFu

elTrain

1/4”SOLENOID/3PG/ACTUATORFUELTRAIN

Page 20: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

20

Run Codes Description

00 System Running

01 Purge Before Start-up

04 5 Second Alarm

05 Igniter On

Standby Codes Description

06 Spare Standby

07 Loss of Fuel Gas Standby

08 Flame Sense Countdown

Shutdown Codes Description

11 Manual / Remote Shut Off

12 Max Retries Exceeded

13 Low Battery Voltage

14 Igniter Disconnected

15 Igniter Short

16 Shutdown Interlock

17 ESD Activated

18 Replace FT-Ignition Unit

20 Solenoid Short

21 Solenoid Disconnected

19 T/C Flame Sensor Error or Disconnected

22 Safety T/C High Temp. Shutdown

23 Safety T/C Error or Disconnected

Status Code

OPERATIONSGUIDE

Page 21: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

21

Unit Status Run Status

Manual OFF Open

Shutdown Open

Standby Open

Unit ON

(Status Code 00) Closed

GREEN-LED

OFF

OFF

Blinking

ON

RED-LED

ON

Blinking

OFF

OFF

RunStatus

The Run Status (Ports 15-16) is a open/closed contact switch. The Run Status can be terminated at the RTU/

PLC device and provide remote monitoring of the unit.

AlarmOut

The Alarm Out (Ports 6-7) is an open/close contact switch. The Alarm Out can be terminated at the RTU/PLC

device and provide remote monitoring of the unit.

Note: Table content below is when system is running.

OPERATIONSGUIDE

Unit Status Alarm

Manual OFF Open

Shutdown Open

Standby Closed

Unit ON

(Status Code 00) Closed

GREEN-LED

OFF

OFF

OFF

ON

RED-LED

ON

Blinking

OFF

OFF

Page 22: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

22

ActuatorOperationalCon igurations

The actuator operate in 4 modes using the operational pins with a shunt.

OPERATIONSGUIDE

Daughter Board

Installed

Actuator

Operation Modes

NO

Opens After

30 Seconds

YES Opens after

30 Seconds

NO Stays

Close

YES Open/Closes Based

on 4-20mA Signal

Shunt

Location

Use Pins 2 & 3

Use Pins 3 & 4

Pin 1

Pin 2

Pin 3

Pin 4

Note: When the Daughter Board is not utilized a jumper should be installed on the Daughter Board port. See fig. 2.

Actuator operational pins are located at the lower left hand corner of the circuit board. See fig. 1

Fig. 1

Fig. 2

Page 23: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

23

Igni on Process with out Daughter Board

1) Press the ON Button

2) Pre-purge - Pre-purge countdown displayed. Green LED ON.

3) Audible Alarm - 5 second countdown displayed. Green LED ON.

4) Igniter - 8 second countdown displayed. Green LED ON

5) Solenoid valve opens - Igniter remains on for another 5 seconds. Green LED ON.

6) Ignition is achieved and a 30 second flame proof timing begins. Pilot ignites. Green LED ON.

7) Flame is sensed, flame proof timing countdown expires, the display reads “On” (Status code 00). Green LED ON.

8) 30 second timer begins before actuator valve opens (count down not visible).

9) After 30 seconds the actuator valve opens.

Re‐Igni on Process ‐ Flame Out

1) Once the system recognizes that no flame is sensed, the system will automatically begin the re-ignition

process.

2. Reference step 2 - 7 in the “Ignition Process Section”

Re‐Igni on Process ‐ Standby

1) System in standby. Blinking Green LED.

2) Once the System resolves the Standby issue, the system will automatically begin the re-ignition process

3) Reference step 2- 7 in the “Ignition Process Section”

Re‐Igni on Process ‐ Shutdown

1) The System requires manual reset in the event of a shutdown

2) System in shutdown. Blinking Red LED.

3) Once the Shutdown issue has ben resolved, press the OFF button then ON button to reset.

4) Reference step 2 - 7 in the “Ignition Process Section”

OPERATIONSGUIDE‐SEQUENCEOFOPERATION

Page 24: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

24

Flowchart without Daughter Board

OPERATIONSGUIDE‐FLOWCHART

Page 25: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

25

Igni on Process with Daughter board (No 4‐20mA Input)

1) Press the ON Button

2) Pre-purge - Pre-purge countdown displayed. Green LED ON.

3) Audible Alarm - 5 second countdown displayed. Green LED ON.

4) Igniter - 8 second countdown displayed. Green LED ON

5) Solenoid valve opens - Igniter remains on for another 5 seconds. Green LED ON.

6) Ignition is achieved and a 30 second flame proof timing begins. Pilot ignites. Green LED ON.

7) Flame is sensed, flame proof timing countdown expires the display reads “T/C temperature val-ue” (Status code 00). Green LED ON.

8) Thermocouple temperature is observed.

Re‐Igni on Process ‐ Flame Out

1) Once the system recognizes that no flame is sensed, the system will automatically begin the re-ignition process.

2. Reference step 2 - 7 in the “Ignition Process Section”

Re‐Igni on Process ‐ Standby

1) System in standby. Blinking Green LED.

2) Once the System resolves the Standby issue, the system will automatically begin the re-ignition process

3) Reference step 2- 7 in the “Ignition Process Section”

Re‐Igni on Process ‐ Shutdown

1) The System requires manual reset in the event of a shutdown

2) System in shutdown. Blinking Red LED.

3) Once the Shutdown issue has ben resolved, press the OFF button then ON button to reset.

4) Reference step 2 - 7 in the “Ignition Process Section”

OPERATIONSGUIDE‐SEQUENCEOFOPERATION

Page 26: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

26

Flowchart with Daughter Board (No 4-20mA Input)

OPERATIONSGUIDE‐FLOWCHART

Page 27: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

27

Igni on Process with Daughter Board, Safety T/C, and 4‐20mA Input

1) Press the ON Button

2) Pre-purge - Pre-purge countdown displayed. Green LED ON.

3) Audible Alarm - 5 second countdown displayed. Green LED ON.

4) Igniter - 8 second countdown displayed. Green LED ON

5) Solenoid valve opens - Igniter remains on for another 5 seconds. Green LED ON.

6) Ignition is achieved and a 30 second flame proof timing begins. Pilot ignites. Green LED ON.

7) Flame is sensed, flame proof timing countdown expires, the display reads “T/C temperature” (Status code 00). Green LED ON.

8) Thermocouple temperature is observed. Green LED ON.

9) 4-20mA pressure input is monitored. Green LED ON.

10) Actuator valve opens and closes according to 4-20mA pressure input. Green LED ON.

Re‐Igni on Process ‐ Flame Out

1) Once the system recognizes that no flame is sensed, the system will automatically begin the re-ignition

process.

2. Reference step 2 - 7 in the “Ignition Process Section”

Re‐Igni on Process ‐ Standby

1) System in standby. Blinking Green LED.

2) Once the System resolves the Standby issue, the system will automatically begin the re-ignition process

3) Reference step 2- 7 in the “Ignition Process Section”

Re‐Igni on Process ‐ Shutdown

1) The System requires manual reset in the event of a shutdown

2) System in shutdown. Blinking Red LED.

3) Once the Shutdown issue has ben resolved, press the OFF button then ON button to reset.

4) Reference step 2 - 7 in the “Ignition Process Section”

OPERATIONSGUIDE‐SEQUENCEOFOPERATION

Page 28: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

28

Flowchart with Daughter Board, Safety T/C, and 4-20mA Input

OPERATIONSGUIDE‐FLOWCHART

Page 29: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

29

PowerSupplySpeci icationsDevice Specification

Battery 12V DC —13.4V DC

12 VDC Power Supply SET @ 13.4V DC

Solar Panel 12V DC Solar Panel

Solar Panel 75W Maximum (Solar panel not tested by Intertek)

Max System Amperage 5.0A / 0.6A Avg.

IgnitionUnitSpeci icationsDevice Specification

Ignition Unit @ In Rush 6.5A

Ignition Unit @ Steady state 2.0A nominal (During ignition only)

SensorSpeci icationsDevice Specification

Standby Switches Dry Contact Switch (Open / Close loop)

Shutdown Switches Dry Contact Switch (Open / Close loop)

Remote On/Off Dry Contact Switch (Open / Close loop)

Note: No voltage or current should be applied to the ports above.

Run Status 12V or 24V DC @ 2A

Max Volts: 26V DC

Max Current: 2A

Alarm Out 12V or 24V DC @ 0.5A

Max Volts: 26V DC

Max Current: 0.5A

Battery/SureFireIgniterWiringRequirements16 AWG @ 10 ft., Copper Stranded

14 AWG @ 20 ft., Copper Stranded

12 AWG @ 30 ft., Copper Stranded

SoftwareType:ClassB

SPECIFICATIONS

Page 30: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

30

NOTE:

RUNCODESStatus Codes Symptom Action Visual

00 System Running

Pilot flame is present

No errors present

Normal Operation

Display reads On or Thermocouple temper-ature value

Green LED ON

01 Purge Before Start-up

Pilot flame not present

Normal Operation

Pre-purge countdown is displayed, adjusta-ble between 1-10 minutes.

Green LED ON

04 5 Second Alarm

Pilot flame not present

System is warning operators on ignition attempt

Ignition warning buzzer can be heard

Green LED ON

05 Igniter On

Pilot flame not present

Igniter element is receiving voltage

8 second countdown

Igniter element temperature is increasing

Green LED ON

STANDBYCODESStatus Codes Symptom Action Visual

06 Spare Standby

Pilot flame not present

No activity when attempting start-up

Ports 19 & 20 are Activated

System detecting an open circuit

Customer supplied switch is activated

Check switching device for faulty operation

Verify wiring from switching device

Verify jumper is installed

Jumper is required if function is not being utilized

Blinking Green LED

07 Loss of Fuel Gas

Standby

Pilot flame not present

No activity when attempting start-up

Ports 17 & 18 are activated

System detecting an open circuit

Customer supplied switch is activated

Check switching device for faulty operation

Verify wiring from switching device

Verify jumper is installed

Jumper is required if function is not being utilized

Blinking Green LED

08 Flame Sense Count-

down

Pilot flame present

Normal Operation

30 second countdown is displayed

System looking for pilot flame

Green LED ON

TROUBLESHOOTINGGUIDE

Page 31: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

31

SHUTDOWNCODESStatus Codes Symptom Action Visual

11 Manual/Remote Shut

Off

Pilot flame not present System has been turned OFF Manually

System has been turned OFF remotely

System received a momentary signal to the Remote Off terminals, ports 15&16

Display reads OFF

Red LED ON

12 Max Retries Exceeded

Pilot flame not present

System has exceeded relighting attempts without success.

Verify proper fuel gas pressure, air/fuel mixer settings, amperage to igniter, and wire size.

Verify proper valve operation: Solenoids, diaphragm valve, actuator valve, etc.

Plugged pilot or solenoid orifice

Plugged vent on solenoid or diaphragm valve

Blinking Red LED

13 Low Battery Voltage

Pilot flame not present

Battery or power supply below minimum voltage required to operate system

Verify battery volts is 12.0 volts

Check or replace battery if required

Check solar panel for faulty operation

Blinking Red LED

14 Igniter Disconnected

Pilot flame not present

Check wiring installation and installation specifications

Igniter element could have wore out or is broken.

Check power supply. When power sup-ply is inefficient, system detects an open circuit

Blinking Amber and Red LED

15 Igniter Short

Pilot flame not present

Ensure igniter wires are not touching each other or grounding to conduit.

Ensure there is no moisture in the con-duit.

Check power supply. When power sup-ply is inefficient, system detects a short circuit .

Blinking Amber and Red LED

NOTE:

If the present issue is not resolved by the above steps, please call SureFire Technical Support @ 505-333-2876

TROUBLESHOOTINGGUIDE

Page 32: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

32

NOTE:

If the present issue is not resolved by the above steps, please call SureFire Technical Support @ 505-333-2876

SHUTDOWNCODESStatus Codes Symptom Action Visual

16 Shutdown Interlock

Pilot flame not present

Ports 23 & 24 are activated

System detecting an open circuit

Customer supplied switch is activated

Check switching device for faulty opera-tion

Verify wiring from switching device

Verify jumper is installed

Jumper is required if function is not be-ing utilized

Blinking Red LED

17 ESD Activated

Pilot flame not present

Ports 23 & 24 are activated

System detecting an open circuit

Customer supplied switch is activated

Check switching device for faulty opera-tion

Verify wiring from switching device

Verify jumper is installed

Jumper is required if function is not be-ing utilized

Blinking Red LED

18 Replace FT-Ignition

Unit

Pilot flame not present

Igniter has deteriorated causing high ohms.

Blinking Red LED

19 T/C Flame Sensor

Error or Disconnected

Pilot flame not present

Check device for failure

Verify wiring from device

System detecting a disconnect upon ini-tial start-up

Ensure proper flame sensing mode has been selected

Blinking Red LED

TROUBLESHOOTINGGUIDE

Page 33: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

33

NOTE:

If the present issue is not resolved by the above steps, please call SureFire Technical Support @ 505-333-2876

SHUTDOWNCODESStatus Codes Symptom Action Visual

20 Solenoid Disconnected

Pilot flame not present

System detecting a disconnect

Check device for faulty coil

Verify wiring from device

Blinking Red LED

21 Solenoid Short

Pilot flame not present

System detecting a short

Check device for wire short

Verify wiring from device

Blinking Red LED

22 Safety T/C High Temp. Shutdown

Pilot flame not present

Safety high temperature set point reached

System detecting a disconnect upon ini-tial start-up

Check device for failure

Verify wiring from device

If not using Safety T/C, check for jumper on T/C port

Blinking Red LED

23 Safety T/C Error or

Disconnected

Pilot flame not present

System detecting a disconnect upon ini-tial start-up

Check device for failure

Verify wiring from device

System detecting the device is discon-nected

If not using Safety T/C, check for jumper

Blinking Red LED

TROUBLESHOOTINGGUIDE

Page 34: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

34

DAUGHTERBOARDPCB

Daughter Board Printed Circuit Board The SureFire Daughter Board PCB has a USB port, USB ejection switch, 4-position dip switch, Safety T/C port, 4-20mA Input port, Battery, programming port, and 2 LED lights.

Blinking orange LED shows that USB is communicating with the Daughter Board and recording flame strength data.

Green LED illuminates when the “USB eject switch” is pressed to show that USB can be removed.

WARNING: Do not remove USB jump drive until Green LED is on.

USB Port

Dip Switch

Safety T/C Port

Jumper if not used

4-20mA Input Port

Programming Port Battery (CR2032)

USB Eject Switch

Orange LED

Green LED

Page 35: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

35

DAUGHTERBOARDINSTALLATION

How to attach Daughter Board on to the BMS-100: 1. There are 4 standoffs on the Daughter Board that helps the Daughter Board mount to the BMS-100. As

shown in the picture below, Fig. 1.

2. Make sure when attaching Daughter Board to BMS-100, the “J4” connection faces towards and aligns with the connector on the BMS-100.

3. Place the Daughter Board on to the BMS-100 and make sure all 4 standoffs align with the holes on the BMS-100 board. Press Daughter Board down until it clicks into place. As shown in the picture below, Fig. 2.

Standoffs

Standoff

Connector ‘J4’

Standoff

Standoff

Fig. 1

Fig. 2

Page 36: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

36

DAUGHTERBOARDINSTALLATION

BMS-100 Circuit Board with Daughter Board

The SureFire BMS-100 system with the Daughter Board in place.

Daughter Board mounted on BMS-100

Page 37: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

37

DAUGHTERBOARDSETUP

Set High-Temperature shutdown value from T/C: 1. Unlock the system by holding down the “status code” button for 5 seconds.

2. Hold down the “Flame Value/T/C HTS” button for 5 seconds to see set-point value and press the “Status Code/ “ button to set high-temperature shut down value. (Default value is set to 1900°).

NOTE: The temperature will scroll quickly when button is held down. If you go past the temperature set point continue to hold the up arrow button and the display will scroll past 2400°F and re-start at 100°F again. 

Shutdown Codes

Status Codes Symptom Action Visual

22 Safety T/C High

Temperature Shut down

Pilot flame not present High temperature set point reached

System detecting a disconnect upon ini-tial start-up

Check device for failure

Verify wiring from device

If not using Safety T/C, check for jumper on T/C port

Blinking Red LED

23 Safety T/C

Error or Disconnect

Pilot flame not present System detecting a disconnect upon ini-tial start-up

Check device for failure

Verify wiring from device

System detecting the device is discon-nected

If not using Safety T/C, check for jumper on T/C port

Blinking Red LED

Controller start up: 1. After daughter board is installed on main circuit board, apply 12 VDC power to BMS-100.

2. Let system go through boot up process for 30 seconds, before setting any set points.

3. After boot up process is complete, display will show “OFF”.

 

Page 38: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

38

DAUGHTERBOARDSETUP

4-20mA Input Dip Switch Settings

Warning: Remove power from the system when selecting dip switch setting.

NOTE: The 4-20mA input will control the actuator valve only after flame is proven.

There are 4 pre-defined settings for 4-20mA input, which controls the actuator valve to open and close. The table below shows the 4 different settings that can be selected. Choose the pressure setting desired and turn ON the switch that corresponds with the pressure setting.

Example: To set up Switch 1 setting, put switch 1 to the ON position and make sure all other switches stay in the OFF position. At this setting, when the transducer detects 1.5oz of pressure, the system will turn ON the actuator valve to the open position and keep the valve open until the transducer detects 0.5oz of pres-sure. Once the transducer detects the pressure at 0.5oz or below, the system will close the actuator valve.

Dip Switch Settings

Dip Switch No ON OFF Dip Switch setting

Switch 1 (ON) Switch 2,3,&4 (OFF)

1.5 oz.

(5.0 mA)

0.5 oz.

(4.45 mA)

Switch 2 (ON) Switch 1,3,&4 (OFF)

2.0 oz.

(5.3 mA)

0.5 oz.

(4.45 mA)

Switch 3 (ON) Switch 1,2,&4 (OFF)

2.5 oz.

(5.55 mA)

0.5 oz.

(4.45 mA)

Switch 4 (ON) Switch 1,2,&3 (OFF)

3.0 oz.

(5.85 mA)

1.0 oz.

(4.7 mA)

oz. = Ounce

mA = Milliamp

Page 39: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

39

Software Version Release Date Description

V 1.72 4/16/2019 Standard base software — not using jumper

V 1.82 4/26/2019 Standard base software — using jumper

SOFTWAREVERSIONS

Software Version Release Date Description

V 1.2 4/3/2019 Standard base software

BMS-100 Daughter Board

BMS-100

Page 40: Proudly Made in the USA - SureFire · The BMS-100 detects a flame utilizing the igniter or thermocouple as the flame sensing device. Once the pilot ... Graphic overlay, with a membrane

40

BMS-100 Installation and Operations Manual

08/21/2017

Last Update: 4/10/2019

Version 2.0

SureFire Farmington, NM Office:

1910 Rustic Place, Farmington, NM 87401 P: 505-333-2878 F: 505-333-2879

SureFire Houston, TX Office:

12510 Cutten Rd. Houston, TX 77066 P: 281-377-9756 F: 281-379-1081

Tech Support:

505- 333-2876

For SureFire Product Updates Please Visit:

www.surefire-controls.com