protecting feeders with distributed resource · protecting feeders with distributed resource...

47
© 2015 HDR, all rights reserved. Scott Elling – HDR Inc. Protecting Feeders With Distributed Resource

Upload: others

Post on 07-Apr-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

© 2015 HDR, all rights reserved.

Scott Elling – HDR Inc.

Protecting Feeders With Distributed Resource

Page 2: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Several Hundred Mega Watts of distributed PV

Distribution Grid is no longer radial

Protection Considerations

Background

Page 3: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Quick Review

Protection considerations

Reclosing

Inverters vs Rotating Mass

Challenges

Directionality with PV

Agenda

Page 4: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Complete coverageo Relay Reach

Minimize outages

ProtectionConsiderations

Page 5: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Protective Reach

No Dead Zones

Page 6: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Protective Reach

No Dead Zones

Verify Relay trips for Ph-Ph Fault

Page 7: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Protective Reach

No Dead Zones

Verify Relay trips for Ph-Gr Fault

Page 8: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Protective Reach

Ph-Ph Ph-Gr

*Plotted in CAPE

Page 9: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Selectivity

TOC Coordinationo Upstreamo Downstream

Minimize Outages

Page 10: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Trip feeder before transformer fuse begins to melt

Upstream TOC Coordination

Page 11: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Trip feeder before transformer fuse begins to melt

Verify Ph-Ph Fault

Upstream TOC Coordination

Page 12: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Trip feeder before transformer fuse begins to melt

Verify Ph-Gr Fault

Upstream TOC Coordination

Page 13: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Ph-Ph Ph-Gr

Upstream TOC Coordination

*Plotted in CAPE

Page 14: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Fuse should melt before feeder relay sends trip

Trip Saving Scheme

Downstream TOC Coordination

Page 15: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Fuse should melt before feeder relay sends trip

Trip Saving Scheme

Verify 3-Ph Fault

Downstream TOC Coordination

Page 16: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Fuse should melt before feeder relay sends trip

Trip Saving Scheme

Verify Ph-Gr Fault

Downstream TOC Coordination

Page 17: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

3-Ph Ph-Gr

Downstream TOC Coordination

*Plotted in CAPE

Page 18: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

How is relay reach affected?

How TOC coordination affected?

What happens when we add PV?

Page 19: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Infeed

o Accounts for a portion of the voltage drop to the fault

o Fault current provided by Substation reduces

Effects on Relay Reach

Page 20: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Infeed

o Accounts for a portion of the voltage drop to the fault

o Fault current provided by Substation reduces

o Recheck Ph-Ph Fault

Effects on Relay Reach

Page 21: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Infeed

o Accounts for a portion of the voltage drop to the fault

o Fault current provided by Substation reduces

o Recheck Ph-Gr Fault

Effects on Relay Reach

Page 22: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Ph-Ph Ph-Gr

Effects on Relay Reach

*Plotted in CAPE

Page 23: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

The infeed desensitizes the Substation relay

Fault clearing times could become very high

The relay might not reach the entire zone of protection

Effects on Relay Reach

Page 24: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Source is intermittent

We need to protect for the worst case

PV may only be used against you

Does it adversely affect coordination?

Page 25: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Remove infeed to downstream devices when coordinating with Substation Relay

PV may only be used against you

Page 26: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Remove infeed to downstream devices when coordinating with Substation Relay

PV may only be used against you

Page 27: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Do not remove the PV when coordinating the feeder reclosers with downstream fuses

PV may only be used against you

Page 28: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Coordination and Reach Summary

Time in Cycles Before AfterReach Trip Time Ph-Ph 115 200Reach Trip Time Ph-Gr 345 565Upstream CTI 15 15Downstream CTI 17 17

*CTI: Coordination Time Interval

Page 29: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

PV behaves like a current source Inverters have no inertia Zero-sequence and negative-sequence current suppressed Positive-sequence current limited

Inverters vs Rotating Mass

Page 30: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

I1,PV limited

I2,PV suppressed

I0,PV exists via Ground Transformer

Sequence Networks

Page 31: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

I1,PV limited

I2,PV suppressed

I0,PV exists via Ground Transformer

Ph-Gr Fault

Sequence Networks

Page 32: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

I1,PV limited I2,PV suppressed

Sequence Networks

Ph-Ph Fault

Page 33: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

IEEE 1547 states DER should shut down in less than two seconds if Utility source is lost

UL 1741 certification

DER Employs Anti-Islanding

Page 34: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Rotating Mass on same distribution grid

Transfer Trip to avoid islanding

Transfer Trip

Page 35: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Distributed resource includes Anti-Islanding Protection Do not reclose before the Anti-Islanding operates Load-to-Generation ratio – Supervision may not be necessary

if the minimum load exceeds the DER by an adequate threshold

Reclosing Considerations

Page 36: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Dead Line Only

Hot Bus – Dead Line

Synchronous Voltage

Potential Required

Be mindful of upstream reclosing

Supervision Options

Page 37: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Use caution with ATO Schemeso Allow Anti-Islanding Protection to operate before throwing over to

Back-up Transformerso Add supervision or a time delay to operation

Ensure voltage regulators support bi-directional flow and set them accordingly

Substation Considerations

Page 38: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Modelling the PV DERo Gathering necessary information in allotted timeo Nonconventional system parameters

Quantity of installations over limited time periodo Hundreds of MW installed in a 2 year span

Challenges Encountered

Page 39: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Smaller fused distribution transformers leave very little or no budget to squeeze consecutive protective zoneso Transformer fuse to Feeder relay to downstream recloser to solar

garden fuse

Some reclosers fit the desired standard installation better than others

Sorting out whether issues were existing or caused by the PV insertion

Challenges Encountered

Page 40: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Reverse looking directional element set more sensitive than non-directional elemento PV will not provide negative sequence current

Reverse looking directional element to supervise recloserso Directionality is inherent simply based on magnitudeo PV supplies 1.1 – 1.3 p.u. current under fault condition

Should directionality be utilized?

Page 41: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Questions?

Page 42: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

System Parameters

Page 43: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

System ParametersA - SourceVoltage 69 kVMVA 100R1 0.04201 puX1 0.16803 pu (Subtransient)R0 0.03151 pu (Subtransient)X0 0.1890 pu

B - High Side FuseSpeed Class SlowDesignation 100E

C - Distribution Transformer69 kV – 13.8 kVDyg1MVA 8.4/10.5Z1 7%Z0 6%

D - Feeder Relay TOC CurvesPhase Pick-up 672 APhase Time Dial 1.2Phase Curve U.S. InverseGround Pick-up 480 AGround Time Dial 7 Ground Curve U.S. Very Inverse

Page 44: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

System ParametersE - Line SegmentR1 0.07194 puX1 0.17223 puR0 0.24890 puX0 0.60360 pu

F - Branch FuseSpeed Class TDesignation 140T

G - Line SegmentR1 0.57551 puX1 1.37786 puR0 1.99118 puX0 4.82882 pu

H - Line SegmentR1 0.03597 puX1 0.08612 puR0 0.12445 puX0 0.30180 pu

I - Recloser TOC CurvesPhase Pick-up 300 APhase Time Dial 2Phase Curve U.S. Very InverseGround Pick-up 150 AGround Time Dial 7Ground Curve U.S. Very Inverse

Page 45: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

System ParametersJ - Inverter Step-up FuseSpeed Class TDesignation 40T

K - Ground Transformer* 5 parallel transformersZig-ZagMVA 1Base kV 13.8R0 0.03 puX0 0.6 pu

L - Inverter Step-up (ISU) Transformer* 5 parallel transformers13.8 kV – 480 VYd1MVA 1Z1 6%Z0 6%

M - Lump PV Source and Inverter* 5 parallel sourcesVoltage 480 VMVA 1R1 0.0 puX1 0.217 pu (Subtransient)R2 InfiniteX2 InfiniteR0 InfiniteX0 InfiniteCurrent Limit 1.2 pu

Page 46: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Phillip Richardson Venugopal Rao Tondupally Max Desruisseaux Kshitij Maurya Tyler Porter Andrew Volk Trevor Hauck Pratap Mysore Paul Nyombi

Acknowledgments

Page 47: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

Scott Elling, P.E. (MN)[email protected]/follow-us

Contact Information