    UNIVERSITATEA DIN ORADEA

    FACULTATEA DE INGINERIE ENERGETICĂ ȘIMANAGEMENT INDUSTRIAL

    PROGRAMUL DE STUDIU INGINERIA SISTEMELOR

    ELECTROENERGETICE 

    PROIECT

    LA DISCIPLINA

    SISTEME ELECTROENERGETICE

    STUDENT:

    Cociș PetreAnul IV ISE

    COORDONATOR ŞTIINŢIFIC:şef lucr. drd. ing. Mihnea Câmpan

    ORADEA

    2016

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    2/292

    Table of Contents

    Introducere ....................................................................................................................................................... 3

    Exemplu de calcul de circulație de putere într-un sisitem electroenergetic ............................................... 7

    I. I. Regim normal de funcționare RPN ................................................................................................... 10

    II. Regim de avarie (RDF) ......................................................................................................................... 18

    III. Regimul de minim ............................................................................................................................ 2

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    3/293

    Introducere

    În vederea efectuări calculelor de circulație de puteri într-un S.E.E în programulCNW-100 prin metoda indirecta de calcul de tip Newton – Raphson , vom începe prinprezentarea unor definiții respectiv a unor caracteristice ale unui sistem electroenergetic.   Definirea sistemului electroenergetic: 

    Sistemul energetic reprezintă ansamblul activităţilor de producere, transport şiconsum a energiei de toate formele, organizate pe un anumit teritoriu. Sub acest ultimaspect, se poate vorbi despre sisteme energetice regionale, naţionale şi continentale.

    Producerea si consumul de energie sunt procese de transformare a energiei dintr-oformă în altă formă.

      Subsistemele (elementele componente ale) sistemului electroenergetic sunt: 

    • Producţie, conţine echipamente şi instalaţii de producere a energiei electrice; • Transport, grupează liniile de transport şi echipamentele de modificare

    parametrilor energiei electrice, efectuând legătura între centrele de producţie şi sistemul de distribuţie; 

    • Distribuţie, administrează liniile şi echipamentele de modificare a parametrilorenergiei electrice, având rolul de a prelua energia de la subsistemul de transport şi a o furniza centrelor de consum laparametrii electrici la care consumatorul să poată folosi energia primită. 

    • Consum, conţine reţele interne de distribuţie a energiei care racordează consumatorii la subsistemul de distribuţie.

    Din punctul de vedere al managementului sistemului electroenergetic oparte din elementele sistemului sunt pasive (nu pot fi comandate) iar altelesunt active.

    Nivelele de tensiune, în sistemul electroenergetic naţional (SEN), au valoridiferite fiind standardizate numai anumite valori ale tensiunilor de linie:- joasă tensiune (JT), cu tensiunile 0.4 kV , 0.6 kV şi 1 kV;- medie tensiune (MT), pentru 6 kV, 10 kV sau 20 kV;- înaltă tensiune (ÎT), pentru 110 kV, 220 kV ;- foarte înaltă tensiune (FIT), pentru 400 kV şi 750 kV.

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    4/294

     

    În figura .1 sunt prezentate conexiunile dintre subsistemele SEE 

    Fig.1. Elementele de bază ale unui sistem electroenergetic 

    Transportul  energiei electrice se face la valori mari ale tensiunii de220 kV , 400 kV sau 750 kV, prin linii aeriene (LEA).La aceeaşi putere transportată cu când tensiunea este mare curentul este mic,aşa încât căderile de tensiune pe linie vor fi mici ceea ce face ca la capătulliniei să găsim o valoare a tensiunii apropiată de valoarea tensiunii injectate

     în linia de transport.Liniile de 220 kV sunt folosite pentru transportul puterilor medii iar

    liniile de 400 şi 750 kV sunt folosite pentru transportul puterilor mari ladistanţe foarte mari. Astfel liniile de 220 kV transportă puteri din domeniul

    GS

    GS

    Micro GS

    Sistem electric de putere

    (de transport)

    Sistem electric de

    distribu ie

    24 kV

    (MT)

    400 kV

    (FIT)

    400 kV

    (FIT)

    220 kV

    (IT)

    24 kV

    (MT)

    400 kV

    (FIT)

    220 kV

    (IT)

    110 kV

    (IT)

    Consumator

    industrial 110 kV

    (IT)

    10 kV

    (MT)

    Consumator

    industrial

    0,4 kV

    (JT)

    Consumatori

    rezidenţiali

    Consumatori

    comerciali

    400 kV

    (FIT)

    LT LT

    LT

    LC

    STE

    STE

    STC

    STCSTC

    ST

    PT

    LC

    LD

    LD

    PT

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    5/295

    100,…, 240 MW pe distanţe de 60,…, 80 km, pe când liniile de 750 kVtransportă puteri din domeniul 1800,…, 2000 MW pe distanţe de 1200,…,2000 km. Liniile de transport se întâlnesc sub numele de linii de repartiţie(repartiţie teritorială, repartiţie regională) a energiei electrice.

    Sistemul de distribu ţ ie are în componenţă staţii de transformare,posturi de transformare, linii (reţele) de distribuţie, echipamente de măsură,sisteme de protecţie, sistemul dispecer şi sistemul SCADA.Sistemul de distribuţie, când este localizat în zone populate, foloseştelinii subterane LES (numite şi LEC – linii în cablu) iar în rest linii aerieneLEA, la nivele de tensiune de 6 kV , 10 kV , 20 kV sau 110 kV.

    Tabelul 1 Tipurile de linii (fie de transport, fie de distribu ţ ie) cu specificarea puterii

     pe care o pot transporta  şi a lungimii optime d.p.d.v. economic. Tensiunea[kV]

    Tipul liniei Puterea maxima[MW]

    Lungimea liniei[km]

    0.23 LEA/ LEC 0.05 / 0.1 0.15 / 0.20

    0.4 LEA/ LEC 0.1 / 0.175 0.25 / 0.35

    6 LEA/ LEC 2 / 3 10 /8

    10 LEA/ LEC 3 / 5 15 /10

    20 LEA/ LEC 10/ 10 35 / 35

    110 LEA 60 0.80

    220 LEA 240 200

    450 LEA 700 800

    750 LEA 2000 2000

    Consumatorii sunt alimentaţi la tensiuni diferite, în funcţie deputerea cerută de instalaţiile acestora.

    Conectarea unui consumator de energie electrică la sistemulelectroenergetic se face printr-un punct de racordare la treapta de tensiune impusă devaloarea sarcinii maxime (de durată) absorbită în punctele de delimitare şi de distanţadintre consumator şi punctul de racordare.

    Consumatorii se încadrează în 4 clase , notate A,…, D în funcţie de putereaaparentă maximă Smax , vezi tabelul 1.2 Ultima coloană specifică o conectare directă 

    la reţeaua SEN sau prin intermediul unui transformator coborâtor de tensiune. Spreexemplu consumatorul din clasa A poate fi racordat direct la reţeaua de 220 kV sau

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    6/296

    prin intermediul unui transformator coborâtor de tensiune de la 220 kV la 110 kV(220/110).

    Momentul sarcinii indică distanţa dintre consumator şi punctul deracordare la SEN. Astfel consumatorul din clasa A trebuie să fie la o distanţă maimare de 30 km.

    Tabelul 2 Încadrarea consumatorilor în func ț ie de puterea aparenta maximă S max 

    Clasa Sarcinamaxima dedurata S max

    [MVA]

    Momentulsarcinii M  

    [MW km]

    Tensiuneala SEN

    [kV]

    Tensiunea laconsumator

    [kV]

    A  50 < Smax  > 1500

    400220

    110

    400/220220, 220/110

    110, 110/20, 110/10B  7,5 < Smax<

    50 ≤ 1500 10 10

    C 2,5 < Smax <

    7,530 ≤ M ≤ 80

    2010

    20, 20/6, 20/0.410, 10/0.4

    D  0,1 < Smax <2,5

    ≤ 8

    ≤ 3

    2010

    6

    20, 20/0.410, 10/0.46, 10/0.4

    Pentru asigurarea continuităţii alimentării cu energie electrică a consumatorului serecomandă reţele care să permită utilizarea mai multor surse de energie, în tabel fiindprecizate numărul de surse recomandat pentru fiecare categorie de consumatori.

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    7/297

    Exemplu de calcul de circulație de putere într-un sisitemelectroenergetic

    În continuare se prezintă schema respectiv caracteristicile subsistemuluiconsiderat din localitățile A,B respectiv C, necesare în vederea realizări calcului în

    programul CNW-100, calcul de circulație a puterii prin metoda Newton–Raphson.Se vor efectua calcule ale sistemului considerat în trei regimuri diferite adică:

    -Regimul permanent normal;-Regimul de avarie;-Regimul de minim .

     Caracteristicile consumatorilor:

      Un-tensiune nominală;  Pmax- putera activă maximă absorbită;

     

    p0-valoarea procentuală a ponderii consumatorilor de categoria 0;  cosφn- factor de putere nominal;

    Tabelul 3. Caracteristicile consumatorilor  

    !n "#$%Pma&

    "'(%

    P0

    ")%co*φn

    +

    "'$,r%

    , 110-220 33. 38 0/8 7./.

    20 21. 0/ 8/2.

    4 10 27/. 20 0/72 1/7.

    4on*uma

    5ori

    4arac5eri*5ici con*uma5ori

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    8/29

    Figura.2 Schema electrică monofilar ă ini ț ială a subsistemului considerat

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    9/299

     Pe barele staţiei centralei îndepărtate, consumatorul se racordează astfel: 40%pe bara de 220 kV şi 60% pe bara de 110 kV deci vom avea:

     

    -pe bara de 110 kV: Pc=335x0,6=201[MW]Qk=75,95x0,6=45,573 [MVAr]

    -pe bara de 220 kV :Pc=335x0,4=134[MW]Qk=75,95x0,4=30,382 [MVAr]

      Datele caracteristice ale generatoarelor sincrone din centralelorsubsistemului considerat

      Datele nominale ale generatoarelor, utilizate în cadrul proiectului deSEE sunt :

    • Sn [MVA] puterea aparentă nominal ă ;• Pn [MW] puterea activ ă nominal ă ;• Un [kV] tensiunea nominală ;• cosφn [ - ] factorul de putere nominal;• cosφ min [ - ] factorul de putere minim capacitiv;• Xd [ur] reactanţa sincronă longitudinală ;• X'd [ur] reactanţa tranzitorie;• X''d [ur] reactanţa supratranzitorie;• GD 2 [tm 2 ] momentul de inerţie al rotorului generatorului

      Tabelul 4. Datele caracteristice ale generatoarelor sincrone

    Centrala electrică  Centrala mare Centrala limitată 

    nxPng [MW] 3x200 1x160 

    Sn [MVA] 235 187,5 

    Un [kV] 15,75 15,75 

    cosφn(ind) 0,85 0,8 

    cosφmin(cap) 0,985 0,989 Xd˝ 0,19 0,2124 

    Xdʹ  0,27 0,319 

    Xd 1,85 2,067 

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    10/2910

      Tabelul 3.Datele caracteristice ale transformatoarelor de bloc

    Stația nxSn [MVA]

    Unît [kV]

    Unjt [kV]

    Δpsc [kW]

    usc [%]

    Δpg [%]

    ig [%]

    Limitereglaj

    A 3x250 242 15,75 947 14 282 1,2 ±5

    B 1x190 242 15,75 500 11,7 150 0,6 ±5  Tabelul 4.Date caracteristice ale transformatoarelor de distribu ț ie

    Stația nxSn [MVA]

    Unît [kV]

    Unjt [kV]

    Δpsc [kW]

    usc [%]

    Δpg [%]

    ig [%]

    Limitereglaj

    Tr.B 2x160 220 22 455 11 210 1 ±12x1,33

    Tr.C 2x60 220 11 205 10,5 85 2 ±12x1,33

    At. A 2x200 231 121 485 10 105 0,35 ±12x1,25

    I.  Regim normal de funcționare RPN

    Regimul permanent normal (RPN) este un regim de durată cu variaţii lente în timpşi restrânse ca valoare a tensiunilor şi a parametrilor de transfer.Calculul R.P.N este obligatoriu pentru reducerea optimală a sistemelorelectroenergetice. Mărimile cunoscute sunt: puterile cerute de consumatori,configuraţia reţelei şi disponibilitatea surselor. Scopul imediat este cunoaşterea

    vectorului de stare (tensiunile ca modul şi fază). Cu ajutorul vectorului de stare şi amatricei de sistem putem determina circulaţia de puteri şi încărcarea surselor.

    În timpul calculului regimului permanent normal apar o serie de restricţii:• domeniile admisibile, favorabile şi optime ale nivelului tensiunilor nodurilor;• solicitările limită termice ale elementelor sistemului (încărcarea generatoarelor şitransformatoarelor, curenţii nominali ai liniilor);• disponibilitatea surselor;• funcţionarea stabilă static şi dinamic a grupurilor.

    La RPN toate cele teri generatoare din stația din localitatea A sun

    funcționale,iar puterile consumatorilor se consideră valorile maxime ale puterilorabsorbite,înTabelul I.1. se prezintă datele nodurilor generatoare ,iar în Tabelul I.2. se prezintă datele nodurilor consumatoare din sistem, valori necesare în vederea realizăricalculului în programul CNW-100 de calcul al circulației de puteri,caracteristicilenodurilor pasive sunt reprezentate de către liniile electrice a căror caracteristici seprezintă în Tabelul I.3. aceste valori nu se vor schimba nici în celelalte două regimuriprin care va trece sistemul electroenergetic considerat

    -puterea activă,respectiv reactivă totală consumată în regim normal este : 

    PconsTOT=577,5 [MW] QconsTOT=246,01[MVAr] 

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    11/2911

    Datele nodurilor generatoare regim normal de funcționare Tabelul I.1. 

    Centrala Nr. de

    generatoare

    Un 

    [kV]

    Pn 

    [MW]

    Sn 

    [MVA]

    Q

    [MVAr]

    Qmin 

    [MVAr]

    Qmax 

    [MVAr]Centrala

    mare3x 15,75 600 652,17 255,59 -337,61 370,5817

    Centralalimitată 

    1x 15,75 160 200 120 -29,58 139,71

    Datele consumatorilor în nodurile rețelei Tabelul I.2 

    Nr.nod

    Un [kV]

    P[MW]

    Q[MVAr]

    3 220 -134 -57,08

    4 220 0 0

    5 220 0 0

    6 110 -201 -85,62

    7 20 -215 -91,58

    8 10 -27,5 -11,19

      Date linii electrice 

    R[Ω]-rezistența electrică a liniei; X[Ω]-reactanța ; B[mS]-susceptanța;

    G[mS]-conductanța; Tabelul I.3 Linia

    electrică R

    [Ω] X

    [Ω] B

    [mS]G

    [mS]

    3-4 2,46 4,14 0 0,34

    5-4 5,72 37,06 0 0,22

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    12/2912

    După rularea programului respectiv efectuarea calculului, se impune încadrarea înbandă  a tensiunilor pe laturile sistemului,încadrare ce se relizează  cu ajutorulcomutatoarelor de ploturi cu care transformatoarele din stații sunt echipate,valorile de

     încadrare în limite a tensiunilor sunt:-220 kV → 210 − 242 kV; 

    -110 kV → 106 − 121 kV; -20 kV →  20,5 − 21 kV; -10 kV →  10,5 −10 kV; 

    Lucru în progamul CNW-100Se cer numarul total de noduri , numarul de noduri generatoare si numarul

    de zone . Daca nu se doreste definirea de zone se va introduce "0". In definireanumarului zonei nodului, nu exista nici o restrictie cu precizarea sa se fi definitzone si numarul respectiv sa incadreze

    in limita definita.

    Aceste date trebuie sa se incadreze in limitele de 100 noduri ,200 laturi ,respectiv 20 zone pentru varianta CNW100 .Numarul nodului care se introduce trebuie sa fie diferit de numerele

    nodurilor celorlalte noduri introduse. Numerele nodurilor pot fi cuprinse intre1 .. 10.000.

    Valoarea tensiunii trebuie sa se incadreze in limitele uneia din- tre benziledefinite. In momentul in care se introduce tensiunea pentru un nod automat seva defini o banda de tensiune pentru nodul respectiv. Aceasta banda de tensiuneva trebui respectata in cazul in care se va modifica tensiunea nodului. Daca seva modifica tensiunea astfel incit sa se schimbe si banda, atunci va trebui stersnodul si reintrodus din nou.

    Numele nodului poate contine orice caracter in limita a maxim 8 caractere.Conventia de semne referitor la puterile in noduri este: "+" la pute- re

    injectata si "-" la putere ejectata din nod atit pentru P cit si pentru Q inductiv.Pentru nodurile generatoare se introduc si limitele puterii reactive generate.Se cer : nod initial, nod final, parametrii laturii introdusi la niv- elul laturii

    respective daca este linie sau tipul trafo daca este TR. Nodurile final si cel initialsint verificate daca exista si daca sint diferite intre ele. Nu se poate introduce olatura tip linie daca no- durile ei extreme sint la nivele de tensiune diferite si

    invers nu se poate introduce o latura tip trafo daca nodurile ei extreme sint laacelasi nivel de tensiune.

    Datele pentru latura tip linie se vor verifica daca sint in anumite limite. Nuse pot introduce parametrii rezitenta si reactanta pentru aceeasi latura nuli. Sepermit introducerea de parametrii negativi. Pentru o latura tip trafo dupaintroducerea tipului de TR ales din lista de TR disponibile se vor introduce plotulcurent si numarul de trafo in paralel.

    Dupa introducerea datelor ultimei laturi se afiseaza "Laturile sintCOMPLET initializate" si se revine la meniul general. Baza de date nu este

    completa decit dupa afisarea acestui mesaj. Daca la intoducerea unei laturi tiptrafo in catalog nu se gaseste nici un tip de TR care sa corespunda nivelelor detensiune ale noduri- lor extreme ale laturii, atunci se afiseaza un mesaj si se

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    13/2913

    permite introducerea unui nou tip de TR in catalog, corespunzator laturii cupricina. Dupa aceea se revine si introduce acest tip de trafo ca fiind folosit pentrulatura.

    In acelasi mod se procedeaza daca sint mai multe laturi pentru care nuse gasesc tipuri de TR corespunzatoare.

    În urma rulări calculului se prezintă  valorile obținute la regimul pemanentnormal,valori prezentate în următoarele tabele:╔═══════════════════════════════════════════════════════╗ ║  DATE GENERALE   ║ ╠═══════════════════════════════════════════════════════╣ ║ RETEAUA:Cocis Petre ║ ╠═══════════════════════════════════════════════════════╣ ║  PtotGen [MW].................. 582.7 ║ ║  QtotGen [Mvar]................ 337.0 ║ ║  PtotCons [MW]................. -577.5 ║ ║  QtotCons [Mvar]............... -244.9 ║ ║  Nr. total noduri ..... ....... 8 ║ 

    ║  Nr. noduri generatoare ....... 2 ║ ║  Nr. nod de referinta ......... 1 ║ ║  Nr. laturi ................... 7 ║ ║  Nr. tipuri de trafo .......... 5 ║ ║  Nr. zone ..................... 0 ║ ╚═══════════════════════════════════════════════════════╝ 

    ╔═══════════════════════════════════════════════════════╗ ║  MARIMI DE BAZA ║ ╠═════╦══════════╦════════════╦════════════╦════════════╣ ║Nivel║  S[MVA] ║  U[kV] ║  I[kA] ║  Z[Ά ] ║ ╠═════╬══════════╬════════════╬════════════╬════════════╣ ║  1 ║  100.0 ║  750.00 ║  0.077 ║  5625.0000 ║ ║  2 ║  100.0 ║  400.00 ║  0.144 ║  1600.0000 ║ ║  3 ║  100.0 ║  300.00 ║  0.192 ║  900.0000 ║ ║  4 ║  100.0 ║  220.00 ║  0.262 ║  484.0000 ║ 

    ║  5 ║  100.0 ║  110.00 ║  0.525 ║  121.0000 ║ ║  6 ║  100.0 ║  35.00 ║  1.650 ║  12.2500 ║ ║  7 ║  100.0 ║  26.00 ║  2.221 ║  6.7600 ║ ║  8 ║  100.0 ║  20.00 ║  2.887 ║  4.0000 ║ ║  9 ║  100.0 ║  15.00 ║  3.849 ║  2.2500 ║ ║  10 ║  100.0 ║  10.00 ║  5.774 ║  1.0000 ║ ║  11 ║  100.0 ║  6.00 ║  9.623 ║  0.3600 ║ ║  12 ║  100.0 ║  3.00 ║  19.245 ║  0.0900 ║ ║  13 ║  100.0 ║  1.00 ║  57.735 ║  0.0100 ║ ║  14 ║  100.0 ║  0.40 ║  144.338 ║  0.0016 ║ ╚═════╩══════════╩════════════╩════════════╩════════════╝ 

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    14/2914

     Date ini ț iale noduri

    ______________________________________________________________________| DATE INITIALE NODURI pag. 1/ 1 |

     ______________________________________________________________________

    | RETEAUA:Cociș Petre ZONA: 0 | ______________________________________________________________________

    | | | | MODUL | CONS - GEN | LIMITE Q |

    | NR. | NR. | NUME | TENSIUNE | P [MW] | MIN/MAX |

    | CRT.| NOD | TIP NOD | [Kv] | Q [MVAR] | [MVAR] |

     ______________________________________________________________________

    | | | | | | || 1 | 1 | Amare | 15.7500 | 422.680 | -121.800 |

    | | | ECH | | 217.786 | 458.550 |

    | | | | | | |

    | 2 | 2 | Blimitat | 15.7500 | 160.000 | -29.583 |

    | | | GEN | | 119.249 | 139.710 |

    | | | | | | |

    | 3 | 3 | A220 | 232.6112 | -134.000 | |

    | | | CONS | | -57.080 | |

    | | | | | | |

    | 4 | 4 | pasiv1 | 230.5893 | 0.000 | |

    | | | CONS | | 0.000 | |

    | | | | | | |

    | 5 | 5 | pasiv2 | 226.4540 | 0.000 | |

    | | | CONS | | 0.000 | |

    | | | | | | |

    | 6 | 6 | A110 | 112.5633 | -201.000 | |

    | | | CONS | | -85.080 | |

    | | | | | | |

    | 7 | 7 | ConsC | 20.9269 | -215.000 | |

    | | | CONS | | -91.580 | |

    | | | | | | |

    | 8 | 8 | consC | 10.4100 | -27.500 | |

    | | | CONS | | -11.190 | |

     ______________________________________________________________________

    Noduri caracteristice de sistem

    Pentru calculul regimurilor de funcţionarea ale sistemelor electroenergeticeeste importantă cunoaşterea caracteristicilor fiecărui nod în parte.Nodurile se împart în două categorii: noduri generatoare şi noduri consumatoare.Nodurile consumatoare în care consumul este nul sunt denumite şi noduri pasive.

    Unul din nodurile generatoare este un nod special, nodul de echilibrare,nodul din centrala cu cea mai mare putere din sistem. Faza tensiunii în nodul deechilibrare este nulă, fată de aceasta calculându-se fazele tensiunilor celorlalte noduri.

    Mărimile caracteristice nodurilor sunt:- puterea activă injectată în nod P;- puterea reactivă injectată în nod Q;

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    15/2915

    - modulul tensiunii din nod U;- faza tensiunii “δ” faţă de o axă de referinţă aleasă arbitrar.

    Având în vedere interdependenţa dintre mărimile electrice menţionate, într-un nod nu se pot impune simultan toate cele patru mărimi. Se pot impune doar două mărimi urmând ca în urma calculării regimului să rezulte celelalte două mărimi.

     DATE INI Ț  IALE LATURI __________________________________________________________________________

    | DATE INITIALE LATURI pag. 1/ 1 |

     __________________________________________________________________________

    | RETEAUA:Cociș Petre ZONA: 0 | __________________________________________________________________________

    | | | | | Iadm [A] LINIE |

    | | NODURI | PARAMETRII| PARAMETRII_____________________________

    | NR. |INITIAL FINAL| LONGITUD. | TRANSV. | TRAFO & ATTR |

    | | NUMĂR | R [Ω] | G [mS] _____________________________| LAT.| NUME | X [Ω] | B [mS] |Ktr [IT/JT]|TIP buc. PLOT|

     __________________________________________________________________________| | | | | | |

    | 1 | 1 3 | 0.001 | 3.4104 | 15.3651 | 1 3 2 |

    | | Amare A220 | 0.046 | -36.2812 | | |

    | | | | | | |

    | 2 | 5 4 | 5.722 | 0.0000 | 975.0000 | linie |

    | |pasiv2 pasiv1 | 37.060 | 0.2210 | | |

    | | | | | | |

    | 3 | 3 4 | 2.461 | 0.0000 | 575.0000 | linie |

    | | A220 pasiv1 | 14.137 | 0.3390 | | |

    | | | | | | |

    | 4 | 3 6 | 0.089 | 0.0143 | 2.0107 | 5 2 9 |

    | | A220 A110 | 3.660 | -0.0956 | | |

    | | | | | | || 5 | 2 5 | 0.004 | 1.1368 | 15.3651 | 2 1 2 |

    | |Blimitat pasiv2 | 0.139 | -12.0937 | |

    , |

    | | | | | | |

    | 6 | 7 5 | 0.004 | 0.8678 | 10.3990 | 3 2 10 |

    | | ConsC pasiv2 | 0.166 | -6.6116 | | |

    | | | | | | |

    | 7 | 4 8 | 0.003 | 1.4050 | 21.8620 | 4 2 6 |

    | |pasiv1 consC | 0.106 | -19.8347 | | |

     __________________________________________________________________________

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    16/2916

    REZULTATE NODURI

     ______________________________________________________________________

    | REZULTATE NODURI pag. 1/ 1 |

     ______________________________________________________________________

    | RETEAUA:Cociș Petre ZONA: 0 || REGIMUL:RPN |

     ______________________________________________________________________

    | | | | TENSIUNE | CONS - GEN | LIMITE Q |

    | NR. | NR. | NUME | MODUL [Kv] | P [MW] | MIN/MAX |

    | CRT.| NOD | TIP NOD | FAZA [grd] | Q [MVAR] | [MVAR] | ______________________________________________________________________

    | | | | | | |

    | 1 | 1 | Amare | 15.7500 | 422.680 | -121.800 |

    | | | ECH | 0.0000 | 217.786 | 458.550 |

    | | | | | | |

    | 2 | 2 | Blimitat | 15.7500 | 160.000 | -29.583 |

    | | | GEN | -2.7086 | 119.249 | 139.710 |

    | | | | | | |

    | 3 | 3 | A220 | 232.6112 | -134.000 | |

    | | | CONS | -4.6393 | -57.080 | |

    | | | | | | |

    | 4 | 4 | pasiv1 | 230.5893 | 0.000 | |

    | | | CONS | -5.8754 | 0.000 | |

    | | | | | | |

    | 5 | 5 | pasiv2 | 226.4540 | 0.000 | |

    | | | CONS | -8.0886 | 0.000 | |

    | | | | | | |

    | 6 | 6 | A110 | 112.5633 | -201.000 | |

    | | | CONS | -7.8459 | -85.080 | |

    | | | | | | |

    | 7 | 7 | ConsC | 20.9269 | -215.000 | |

    | | | CONS | -12.5441 | -91.580 | |

    | | | | | | |

    | 8 | 8 | consC | 10.4100 | -27.500 | |

    | | | CONS | -7.3771 | -11.190 | |

     ______________________________________________________________________

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    17/2917

    REZULTATE CIRCULAȚIE DE PUTERI PE LATURI _________________________________________________________________________

    | REZULTATE CIRCULAȚIE DE PUTERI PE LATURI pag. 1/ 1 | _________________________________________________________________________

    | RETEAUA:Cociș Petre ZONA: 0 || REGIMUL:RPN |

     _________________________________________________________________________

    | | NODURI | INTRAT | IEȘIT | _P [MW] | _Q [MVAR] || | | | | TOTAL | TOTAL || NR. |INITIAL FINAL | P [MW] | P [MW] | LONG | LONG |

    | LAT.| NUME | Q [MVAR] | Q [MVAR] | TRANSV | TRANSV |

     _________________________________________________________________________

    | 1 | 1 3 | -422.680 | 420.736 | 1.944 | 50.432 |

    | | Amare A220 | -217.786 | 167.354 | 1.130 | 41.774 |

    | | | | | 0.814 | 8.658|

    | 2 | 5 4 | 56.797 | -57.184 | 0.387 | -9.038 |

    | | pasiv2 pasiv1 | 21.115 | -12.077 | 0.387 | 2.504 |

    | | | | | 0.000 | -11.542|

    | 3 | 3 4 | -85.214 | 84.867 | 0.347 | -16.189 |

    | | A220 pasiv1 | -10.145 | 26.334 | 0.347 | 1.995 |

    | | | | | 0.000 | -18.184|| 4 | 3 6 | -201.522 | 201.000 | 0.522 | 15.048 |

    | | A220 A110 | -100.128 | 85.080 | 0.335 | 13.803 |

    | | | | | 0.187 | 1.246|

    | 5 | 2 5 | -160.000 | 159.138 | 0.862 | 24.889 |

    | | Blimitat pasiv2 | -119.249 | 94.361 | 0.597 | 22.075

    , |

    | | | | | 0.264 | 2.813|

    | 6 | 7 5 | 215.000 | -215.936 | 0.936 | 23.895 |

    | | ConsC pasiv2 | 91.580 | -115.475 | 0.540 | 20.880 |

    | | | | | 0.396 | 3.015|

    | 7 | 4 8 | -27.683 | 27.500 | 0.183 | 3.068 |

    | | pasiv1 consC | -14.258 | 11.190 | 0.029 | 0.890 |

    | | | | | 0.154 | 2.178|

     _________________________________________________________________________

    ║  REZULTATE GLOBALE CIRCULATIE PUTERI ║ ╠════════════════════════════════════════════════════════════╣ ║ RETEAUA:Cocis Petre ║ ║ REGIMUL:RPN ║ ╠════════════╦═══════════════════════╦═══════════════════════╣ ║  TOTAL ║  NODURI ║  NODURI ║ ║  PUTERI ║  GENERATOARE ║  CONSUMATOARE ║ ╠════════════╬═══════════════════════╬═══════════════════════╣ ║ P [MW] ║  582.680 ║  -577.500 ║ ║ Q [MVAR] ║  337.035 ║  -244.930 ║ 

    ╠════════════╬══════════╦════════════╩═══════════════════════╣ ║  ║  ║  CONSUMATE ║ ║  TOTAL ║ GENERATE ╠════════════╦═══════════╦═══════════╣ ║  PUTERI ║  ║ ADMITANTE ║ INJECTATE ║  TOTAL ║ ║  ║  ║TRANSVERSALE║  ║  ║ ╠════════════╬══════════╬════════════╬═══════════╬═══════════╣ ║ P [MW] ║  582.680 ║  0.000 ║  -577.500 ║  -577.500 ║ ║ Q [MVAR] ║  337.035 ║  0.000 ║  -244.930 ║  -244.930 ║ ╠════════════╬══════════╩════╦═══════╩═══════╦═══╩═══════════╣ ║ PIERDERI ║  TOTALE ║ LONGITUDINALE ║ TRANSVERSALE ║ ╠════════════╬═══════════════╬═══════════════╬═══════════════╣ ║  ŰP [MW] ║  5.180 ║  3.365 ║  1.815 ║ 

    ║ 

    ŰQ [MVAR]

    ║  92.105

    ║  103.921

    ║  -11.816

    ║ 

    ╠════════════╩═══════════════╩═══════════════╩═══════════════╣ ║  RANDAMENTUL TRANSPORTULUI DE ENERGIE 99.11 [%] ║ ╚════════════════════════════════════════════════════════════╝ 

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    18/2918

    II.  Regim de avarie (RDF)

    Acest regim adică regimul de avarie este un regim tranzitoriu în care sistemulconsiderat se află la un moment dat

    În cazul regimului de defect sau avarie, se va considera următoarea stare de

    funcționare a subsistemului considerat:-în centrala depărtată (din localitatea A) se consideră că două dintre cele treigeneratoare s-a defectat ;-se verifică dacă noua putere furnizată de către cele două generatoare rămasefuncționale (unul din localitatea A, unul din centrala limitată din B ) ,vor acoperi celpuțin consumul puterii consumatorilor de categoria 0 din subsistemul considerat ;-se impune limite de reglaj al tensiuni astfel ,la nivelul de tensiune de :

    -220 kV → 210 − 242 kV;-110 kV → 106 − 121 kV;

    -20 kV →  20,5 − 21 kV; -10 kV →  10,5 −10 kV; -reglaj ce se realizează cu ajutorul comutatoarelor de ploturi ale transformatoarelor-numărul transformatoarelor de distribuție,dar și a celor la consumatori va fi redus launu.

    La ieşirea din funcţiune a unui generator, în urma unei avarii, celelalte (n-1)generatoare rămase în stare de funcţionare trebuie să acopere consumul de putere alconsumatorilor vitali din sistem, la care se adaugă pierderile de putere pe reţeaua detransport.

    Din motive de economie şi întreţinere în exploatare centralele sunt dotate, deobicei, cu generatoare de acelaşi tip şi cu aceeaşi putere nominală. Numărul degeneratoare dintr-o centrală va fi de cel puţin două şi ,având în vedere considerentede stabilitate, este de dorit ca puterea unitară a unui grup generator să nu depăşească 20% din puterea totală instalată în sistem.

    -în Tabelul II.1 se prezintă caracteristicile generatoarelor precum și numărulacestora

    -puterea activă,respectiv reactivă totală consumată în regim de defect este : p0consTOT=227,4 [MW] QconsTOT=96,87[MVAr]

    Tabelul II.1 a).Datele nodurilor generatoare regim avarie 

    Centrala Nr. degeneratoare

    Un [kV]

    Pn [MW]

    Sn [MVA]

    Q[MVAr]

    Qmin [MVAr]

    Qmax [MVAr]

    Centralamare

    1x 15,75 200 217,39 85,199 -337,61 370,5817

    Centralalimitată 

    1x 15,75 160 200 120 -29,58 139,71

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    19/2919

    În Tabelul II.2. se prezintă datele nodurilor consumatoare din sistem, valorinecesare în vederea realizări calculului în programul CNW-100 de calcul alcirculației de puteri

    Tabelul II.2. b).Datele consumatorilor în nodurile re ț elei) (f ăr ă nodurile generatoare)

    Nr.nod

    Un [kV]

    po [MW]

    Q0 [MVAr]

    3 220 -50,92 -21,69

    4 220 0 0

    5 220 0 0

    6 110 -76,38 -32,5

    7 20 -94,6 -40,29

    8 10 -5,5 -2,34

    În urma rulări calculului se prezintă valorile obținute la regimul de avarie,valoriprezentate în următoarele tabele:

    ╔═══════════════════════════════════════════════════════╗ ║  DATE GENERALE ║ ╠═══════════════════════════════════════════════════════╣ ║ RETEAUA:Cocis Petre ║ ╠═══════════════════════════════════════════════════════╣ ║  PtotGen [MW].................. 229.8 ║ ║  QtotGen [Mvar]................ 109.0 ║ ║  PtotCons [MW]................. -227.4 ║ ║  QtotCons [Mvar]............... -96.8 ║ ║  Nr. total noduri ..... ....... 8 ║ ║  Nr. noduri generatoare ....... 2 ║ ║  Nr. nod de referinta ......... 1 ║ ║  Nr. laturi ................... 7 ║ ║  Nr. tipuri de trafo .......... 5 ║ ║  Nr. zone ..................... 0 ║ ╚═══════════════════════════════════════════════════════╝ 

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    20/2920

    _____________________________________________________________________| DATE INIȚIALE NODURI pag. 1/ 1 ||_____________________________________________________________________

    | REȚEAUA:Cociș Petre ZONA: 0 ||_____________________________________________________________________

    | | | | MODUL | CONS - GEN | LIMITE Q |

    | NR. | NR. | NUME | TENSIUNE | P [MW] | MIN/MAX |

    | CRT.| NOD | TIP NOD | [Kv] | Q [MVAR] | [MVAR] ||_____________________________________________________________________

    | | | | | | |

    | 1 | 1 | Amare | 15.7500 | 69.808 | -40.600 |

    | | | ECH | | 55.262 | 152.850 |

    | | | | | | |

    | 2 | 2 | Blimitat | 15.7500 | 160.000 | -29.583 |

    | | | GEN | | 53.716 | 139.710 |

    | | | | | | |

    | 3 | 3 | A220 | 234.6409 | -50.920 | |

    | | | CONS | | -21.690 | |

    | | | | | | |

    | 4 | 4 | pasiv1 | 235.2788 | 0.000 | |

    | | | CONS | | 0.000 | |

    | | | | | | |

    | 5 | 5 | pasiv2 | 235.3193 | 0.000 | |

    | | | CONS | | 0.000 | |

    | | | | | | |

    | 6 | 6 | A110 | 115.5658 | -76.380 | |

    | | | CONS | | -32.500 | |

    | | | | | | |

    | 7 | 7 | consB | 21.9236 | -94.600 | |

    | | | CONS | | -40.290 | |

    | | | | | | |

    | 8 | 8 | consC | 10.7003 | -5.500 | |

    | | | CONS | | -2.340 | |

    |_____|_____|__________|______________|_______________|______________|

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    21/2921

     _________________________________________________________________________

    |_________________________________________________________________________

    | DATE INIȚIALE LATURI pag. 1/ 1 ||_________________________________________________________________________

    | REȚEAUA:Cociș Petre ZONA: 0 ||_________________________________________________________________________

    | | | | | Iadm [A] LINIE |

    | | NODURI | PARAMETRII| PARAMETRII_____________________________

    | NR. |INITIAL FINAL| LONGITUD. | TRANSV. | TRAFO & ATTR |

    | | NUMĂR | R [?] | G [mS] |_________ Ň _________________| LAT.| NUME | X [?] | B [mS] |Ktr [IT/JT]|TIP buc. PLOT|

    | _______________________________________________________________________

    | | | | | | |

    | 1 | 1 3 | 0.004 | 1.1368 | 15.3651 | 1 1 2 |

    | | Amare A220 | 0.139 | -12.0937 | | |

    | | | | | | |

    | 2 | 5 4 | 5.722 | 0.0000 | 975.0000 | linie |

    | |pasiv2 pasiv1 | 37.060 | 0.2210 | | |

    | | | | | | |

    | 3 | 3 4 | 2.461 | 0.0000 | 575.0000 | linie |

    | | A220 pasiv1 | 14.137 | 0.3390 | | |

    | | | | | | || 4 | 3 6 | 0.089 | 0.0143 | 2.0107 | 5 2 9 |

    | | A220 A110 | 3.660 | -0.0956 | | |

    | | | | | | |

    | 5 | 2 5 | 0.004 | 1.1368 | 15.3651 | 2 1 2 |

    | |Blimitat pasiv2 | 0.139 | -12.0937 | |

    , |

    | | | | | | |

    | 6 | 7 5 | 0.009 | 0.4339 | 10.3990 | 3 1 10 |

    | | consB pasiv2 | 0.333 | -3.3058 | | |

    | | | | | | |

    | 7 | 4 8 | 0.007 | 0.7025 | 21.8620 | 4 1 6 |

    | |pasiv1 consC | 0.212 | -9.9174 | | |

    |_____|______________|___________|___________|___________|_______________|

    |_____________________________________________________________________

    | REZULTATE NODURI pag. 1/ 1 |

    | ____________________________________________________________________

    |REȚEAUA:Cociș Petre ZONA: 0 || REGIMUL:RDF |

    |_____________________________________________________________________

    | | | | TENSIUNE | CONS - GEN | LIMITE Q |

    | NR. | NR. | NUME | MODUL [Kv] | P [MW] | MIN/MAX |

    | CRT.| NOD | TIP NOD | FAZA [grd] | Q [MVAR] | [MVAR] |

    |_____________________________________________________________________| | | | | | |

    | 1 | 1 | Amare | 15.7500 | 69.808 | -40.600 |

    | | | ECH | 0.0000 | 55.262 | 152.850 |

    | | | | | | |

    | 2 | 2 | Blimitat | 15.7500 | 160.000 | -29.583 |

    | | | GEN | 6.3456 | 53.716 | 139.710 |

    | | | | | | |

    | 3 | 3 | A220 | 234.6409 | -50.920 | |

    | | | CONS | -2.2579 | -21.690 | |

    | | | | | | |

    | 4 | 4 | pasiv1 | 235.2788 | 0.000 | |

    | | | CONS | -1.4051 | 0.000 | |

    | | | | | | || 5 | 5 | pasiv2 | 235.3193 | 0.000 | |

    | | | CONS | 1.1101 | 0.000 | |

    | | | | | | |

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    22/2922

    | 6 | 6 | A110 | 115.5658 | -76.380 | |

    | | | CONS | -3.4347 | -32.500 | |

    | | | | | | |

    | 7 | 7 | consB | 21.9236 | -94.600 | |

    | | | CONS | -2.4909 | -40.290 | |

    | | | | | | |

    | 8 | 8 | consC | 10.7003 | -5.500 | |

    | | | CONS | -1.9789 | -2.340 | |

    |_____|_____|__________|______________|_______________|______________|

    |________________________________________________________________________

    | REZULTATE CIRCULAȚIE DE PUTERI PE LATURI pag. 1/ 1 ||________________________________________________________________________

    | REȚEAUA:Cociș Petre ZONA: 0 || REGIMUL:RDF |

    |________________________________________________________________________

    | | NODURI | INTRAT | IE?IT | _P [MW] | _Q [MVAR] |

    | | | | | TOTAL | TOTAL |

    | NR. |INITIAL FINAL | P [MW] | P [MW] | LONG | LONG |

    | LAT.| NUME | Q [MVAR] | Q [MVAR] | TRANSV | TRANSV |

    |________________________________________________________________________

    | 1 | 1 3 | -422.680 | 420.736 | 1.944 | 50.432 || | Amare A220 | -217.786 | 167.354 | 1.130 | 41.774 |

    | | | | | 0.814 | 8.658|

    | 2 | 5 4 | 56.797 | -57.184 | 0.387 | -9.038 |

    | | pasiv2 pasiv1 | 21.115 | -12.077 | 0.387 | 2.504 |

    | | | | | 0.000 | -11.542|

    | 3 | 3 4 | -85.214 | 84.867 | 0.347 | -16.189 |

    | | A220 pasiv1 | -10.145 | 26.334 | 0.347 | 1.995 |

    | | | | | 0.000 | -18.184|

    | 4 | 3 6 | -201.522 | 201.000 | 0.522 | 15.048 |

    | | A220 A110 | -100.128 | 85.080 | 0.335 | 13.803 |

    | | | | | 0.187 | 1.246|

    | 5 | 2 5 | -160.000 | 159.138 | 0.862 | 24.889 |

    | | Blimitat pasiv2 | -119.249 | 94.361 | 0.597 | 22.075, |

    | | | | | 0.264 | 2.813|

    | 6 | 7 5 | 215.000 | -215.936 | 0.936 | 23.895 |

    | | consB pasiv2 | 91.580 | -115.475 | 0.540 | 20.880 |

    | | | | | 0.396 | 3.015|

    | 7 | 4 8 | -27.683 | 27.500 | 0.183 | 3.068 |

    | | pasiv1 consC | -14.258 | 11.190 | 0.029 | 0.890 |

    | | | | | 0.154 | 2.178|

    |_____|_______________|__________|__________|_____________|_____________|

    În regim de avarie (avarierea unui transformator), transformatoarele rămase înstare de funcţionare vor acoperi cel puţin puterea cerută de consumatorii vitali.Întrucât, de obicei regimul de avarie este de scurtă durată transformatoarele pot fisupraîncărcate cu 10-20 % din puterea nominală.

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    23/2923

    ╔════════════════════════════════════════════════════════════╗ ║  REZULTATE GLOBALE CIRCULATIE PUTERI ║ 

    ╠════════════════════════════════════════════════════════════╣ ║ RETEAUA:Cocis Petre ║ ║ REGIMUL:RPN ║ ╠════════════╦═══════════════════════╦═══════════════════════╣ ║  TOTAL ║  NODURI ║  NODURI ║ ║  PUTERI ║  GENERATOARE ║  CONSUMATOARE ║ ╠════════════╬═══════════════════════╬═══════════════════════╣ ║ P [MW] ║  229.808 ║  -227.400 ║ ║ Q [MVAR] ║  108.977 ║  -96.820 ║ ╠════════════╬══════════╦════════════╩═══════════════════════╣ ║  ║  ║  CONSUMATE ║ ║  TOTAL ║ GENERATE ╠════════════╦═══════════╦═══════════╣ ║  PUTERI ║  ║ ADMITANTE ║ INJECTATE ║  TOTAL ║ ║  ║  ║TRANSVERSALE║  ║  ║ ╠════════════╬══════════╬════════════╬═══════════╬═══════════╣ ║ P [MW] ║  229.808 ║  0.000 ║  -227.400 ║  -227.400 ║ ║ Q [MVAR] ║  108.977 ║  0.000 ║  -96.820 ║  -96.820 ║ ╠════════════╬══════════╩════╦═══════╩═══════╦═══╩═══════════╣ ║ PIERDERI ║  TOTALE ║ LONGITUDINALE ║ TRANSVERSALE ║ ╠════════════╬═══════════════╬═══════════════╬═══════════════╣ ║  ŰP [MW] ║  5.180 ║  3.365 ║  1.815 ║ ║  ŰQ [MVAR] ║  92.105 ║  103.921 ║  -11.816 ║ ╠════════════╩═══════════════╩═══════════════╩═══════════════╣ ║  RANDAMENTUL TRANSPORTULUI DE ENERGIE 98.95 [%] ║ ╚════════════════════════════════════════════════════════════╝ 

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    24/2924

    III.  Regimul de minim

    La regimul de minim de considerăm faptul că puterea tranzitată prin subsistemulconsiderat scade la 20% din valoarea inițială.

    În prezentul regim vom avea în vedere :-numărul generatoarelor aflate în funcțiune din centrala mare trebuie redus la 1, învedera echilibrării producerii respectiv în funcție de consumul avut (în R.G.20%).-sarcina la care va funcționa generatoarele rămase în funcțiune,unul din centrala mareși unul cel din centrala limitată,fiind necesară o astfel de funcționare în vedereacreșterii elasticități schemei de funcționare a subsistemului considerat,sarcina ce se vadetermina în funcție de puterea activă totală consumată în prezentul regim dat.

    Determinarea sarcini la care va funcționa generatoarele:

    -limita minimă de încărcare a generatoarelor sincrone este Pg=0,1х Pn;-puterea activă,respectiv reactivă totală consumată în regim de defect este : p20%consTOT=115,5 [MW] QconsTOT=49,20[MVAr]

    Deci în funcție de aceste considerente rezultă deci, faptul că un puterea uni singurgrup va fi conform inegalității :

    2∙Pg≥ 115,5[MW]deci:Pg≈ 60 [MW]

    -conform celor prezentate rezultă deci ca un singur generator din centrala mare vafuncționa la sarcina de aproximativ 30% din sarcina maximă de 200 [MW],iargeneratorul din centrala limitată la aproximativ 30% din sarcina maximă cea ce

     însemnă:PnA•30%=60 [MW]PnB•38%=60,8[MW] deci condiția PnA+PnB=120 ≥ 115,5[MW] ,este îndeplinită,Deci noile date de calcul vor fii:

    a).Datele nodurilor generatoare regim de minimTabelul III.1 

    Centrala Nr. degeneratoare

    Un [kV]

    Pn [MW]

    Q[MVAr]

    Qmin [MVAr]

    Qmax [MVAr]

    Centralamare

    1x 15,75 60 65,21 -337,61 370,5817

    Centralalimitată 

    1x 15,75 60,8 76 -29,58 139,71

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    25/2925

    b).Datele consumatorilor în nodurile re ț elei) (f ăr ă nodurile generatoare)

    Tabelul III.2

    Nr.nod

    Un [kV]

    P20% [MW]

    Q0 [MVAr]

    3 220 -26,8 -11,41

    4 220 0 0

    5 220 0 0

    6 110 -40,2 -17,12

    7 20 -43 -18,31

    8 10 -5,5 -2,34

    Funcţia sistemului electroenergetic este de a asigura alimentarea cu energie electrică a consumatorilor racordaţi la acesta. Energia trebuie livrată la anumiţi parametri(tensiuni, frecvenţă, etc.) şi la un anumit nivel pentru a se asigura întregul consum.• în procesul de transport al energiei electrice apar pierderi de putere pe reţelele detransport şi în transformatoarelor din sistem;• posibilitatea apariţiei unor avarii la generatoarele din sistem;• generatoarele, în general, se încarcă până la o putere de 0,9 din puterea nominală 

    pentru a putea prelua eventualele şocuri de putere din sistem;În urma rulări calculului se prezintă valorile obținute la regimul de

    minim,valori prezentate în următoarele tabele:╔═══════════════════════════════════════════════════════╗ ║  DATE GENERALE ║ ╠═══════════════════════════════════════════════════════╣ ║ RETEAUA:Cocis Petre ║ ╠═══════════════════════════════════════════════════════╣ ║  PtotGen [MW].................. 116.7 ║ ║  QtotGen [Mvar]................ 120.0 ║ ║  PtotCons [MW]................. -115.5 ║ 

    ║  QtotCons [Mvar]............... -54.8 ║ ║  Nr. total noduri ..... ....... 8 ║ ║  Nr. noduri generatoare ....... 2 ║ ║  Nr. nod de referinta ......... 1 ║ ║  Nr. laturi ................... 7 ║ ║  Nr. tipuri de trafo .......... 5 ║ ║  Nr. zone ..................... 0 ║ ╚═══════════════════════════════════════════════════════╝ 

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    26/2926

    ╔═══════════════════════════════════════════════════════╗ ║  MARIMI DE BAZA ║ ╠═════╦══════════╦════════════╦════════════╦════════════╣ ║Nivel║  S[MVA] ║  U[kV] ║  I[kA] ║  Z[ŕ] ║ ╠═════╬══════════╬════════════╬════════════╬════════════╣ ║  1 ║  100.0 ║  750.00 ║  0.077 ║  5625.0000 ║ 

    ║  2 ║  100.0 ║  400.00 ║  0.144 ║  1600.0000 ║ ║  3 ║  100.0 ║  300.00 ║  0.192 ║  900.0000 ║ ║  4 ║  100.0 ║  220.00 ║  0.262 ║  484.0000 ║ ║  5 ║  100.0 ║  110.00 ║  0.525 ║  121.0000 ║ ║  6 ║  100.0 ║  35.00 ║  1.650 ║  12.2500 ║ ║  7 ║  100.0 ║  26.00 ║  2.221 ║  6.7600 ║ ║  8 ║  100.0 ║  20.00 ║  2.887 ║  4.0000 ║ ║  9 ║  100.0 ║  15.00 ║  3.849 ║  2.2500 ║ ║  10 ║  100.0 ║  10.00 ║  5.774 ║  1.0000 ║ ║  11 ║  100.0 ║  6.00 ║  9.623 ║  0.3600 ║ ║  12 ║  100.0 ║  3.00 ║  19.245 ║  0.0900 ║ ║  13 ║  100.0 ║  1.00 ║  57.735 ║  0.0100 ║ ║  14 ║  100.0 ║  0.40 ║  144.338 ║  0.0016 ║ ╚═════╩══════════╩════════════╩════════════╩════════════╝ 

    ______________________________________________________________________| DATE INITIALE NODURI pag. 1/ 1 |

     ______________________________________________________________________

    | RETEAUA:Cociș Petre ZONA: 0 | ______________________________________________________________________

    | | | | MODUL | CONS - GEN | LIMITE Q |

    | NR. | NR. | NUME | TENSIUNE | P [MW] | MIN/MAX |

    | CRT.| NOD | TIP NOD | [Kv] | Q [MVAR] | [MVAR] |

     ______________________________________________________________________| | | | | | |

    | 1 | 1 | Amare | 15.7500 | 55.948 | -40.600 |

    | | | ECH | | -5.609 | 152.850 |

    | | | | | | |

    | 2 | 2 | Blimitat | 15.7500 | 60.800 | -29.583 |

    | | | GEN | | 120.000 | 139.710 |

    | | | | | | |

    | 3 | 3 | A220 | 230.7334 | -26.800 | |

    | | | CONS | | -11.410 | |

    | | | | | | |

    | 4 | 4 | pasiv1 | 232.7927 | 0.000 | |

    | | | CONS | | 0.000 | |

    | | | | | | || 5 | 5 | pasiv2 | 236.4418 | 0.000 | |

    | | | CONS | | 0.000 | |

    | | | | | | |

    | 6 | 6 | A110 | 115.0236 | -40.200 | |

    | | | CONS | | -17.120 | |

    | | | | | | |

    | 7 | 7 | consB | 20.7831 | -43.000 | |

    | | | CONS | | -18.310 | |

    | | | | | | |

    | 8 | 8 | consC | 10.3322 | -5.500 | |

    | | | CONS | | -2.340 | |

     _____________________________________________________________________|

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    27/2927

     __________________________________________________________________________

    | DATE INITIALE LATURI pag. 1/ 1 |

     __________________________________________________________________________

    | RETEAUA:Cociș Petre ZONA: 0 | __________________________________________________________________________

    | | | | | Iadm [A] LINIE |

    | | NODURI | PARAMETRII| PARAMETRII_____________________________

    | NR. | INITIAL FINAL| LONGITUD. | TRANSV. | TRAFO & ATTR |

    | | NUMĂR | R [] | G [mS] ______________________________| LAT.| NUME | X [] | B [mS] | Ktr [IT/JT]| TIP buc. PLO|

     __________________________________________________________________________

    | | | | | | |

    | 1 | 1 3 | 0.004 | 1.1368 | 14.5968 | 1 1 3 |

    | | Amare A220 | 0.139 | -12.0937 | | |

    | | | | | | |

    | 2 | 5 4 | 5.722 | 0.0000 | 975.0000 | linie |

    | | pasiv2 pasiv1| 37.060| 0.2210| | |

    | | | | | | |

    | 3 | 3 4 | 2.461 | 0.0000 | 575.0000 | linie |

    | | A220 pasiv1 | 14.137 | 0.3390 | | |

    | | | | | | || 4 | 3 6 | 0.178 | 0.0072 | 1.9853 | 5 1 10 |

    | | A220 A110 | 7.321 | -0.0478 | | |

    | | | | | | |

    | 5 | 2 5 | 0.004 | 1.1368 | 15.3651 | 2 1 2 |

    | | Blimitat pasiv2 | 0.139 | -12.0937 | |

    , |

    | | | | | | |

    | 6 | 7 5 | 0.009 | 0.4339 | 11.1970 | 3 1 4 |

    | | consB pasiv2 | 0.333 | -3.3058 | | |

    | | | | | | |

    | 7 | 4 8 | 0.007 | 0.7025 | 22.3940 | 4 1 4 |

    | | pasiv1 consC | 0.212 | -9.9174 | | |

     _________________________________________________________________________|

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    28/2928

     ______________________________________________________________________

    | REZULTATE NODURI pag. 1/ 1 |

     ______________________________________________________________________

    | RETEAUA:Cociș Petre ZONA: 0 || REGIMUL:R20% |

     ______________________________________________________________________

    | | | | TENSIUNE | CONS - GEN | LIMITE Q |

    | NR. | NR. | NUME | MODUL [Kv] | P [MW] | MIN/MAX |

    | CRT.| NOD | TIP NOD | FAZA [grd] | Q [MVAR] | [MVAR] |

     ______________________________________________________________________

    | | | | | | |

    | 1 | 1 | Amare | 15.7500 | 55.948 | -40.600 |

    | | | ECH | 0.0000 | -5.609 | 152.850 |

    | | | | | | |

    | 2 | 2 | Blimitat | 15.7500 | 60.800 | -29.583 |

    | | | GEN | 0.7972 | 120.000 | 139.710 |

    | | | | | | |

    | 3 | 3 | A220 | 230.7334 | -26.800 | |

    | | | CONS | -1.7906 | -11.410 | |

    | | | | | | |

    | 4 | 4 | pasiv1 | 232.7927 | 0.000 | || | | CONS | -1.7000 | 0.000 | |

    | | | | | | |

    | 5 | 5 | pasiv2 | 236.4418 | 0.000 | |

    | | | CONS | -1.1594 | 0.000 | |

    | | | | | | |

    | 6 | 6 | A110 | 115.0236 | -40.200 | |

    | | | CONS | -3.0402 | -17.120 | |

    | | | | | | |

    | 7 | 7 | consB | 20.7831 | -43.000 | |

    | | | CONS | -3.0104 | -18.310 | |

    | | | | | | |

    | 8 | 8 | consC | 10.3322 | -5.500 | |

    | | | CONS | -2.3150 | -2.340 | | _____________________________________________________________________|

     _________________________________________________________________________

    | REZULTATE CIRCULAȚIE DE PUTERI PE LATURI pag. 1/ 1 | _________________________________________________________________________

    | RETEAUA:Cociș Petre ZONA: 0 || REGIMUL:R20% |

     _________________________________________________________________________

    | | NODURI | INTRAT | IE?IT | _P [MW] | _Q [MVAR] |

    | | | | | TOTAL | TOTAL |

    | NR. | INITIAL FINA | P [MW] | P [MW] | LONG | LONG || LAT.| NUME | Q [MVAR] | Q [MVAR] | TRANSV | TRANSV |

     _________________________________________________________________________

    | 1 | 1 3 | -422.680 | 420.736 | 1.944 | 50.432 |

    | | Amare A220 | -217.786 | 167.354 | 1.130 | 41.774 |

    | | | | | 0.814 | 8.658|

    | 2 | 5 4 | 56.797 | -57.184 | 0.387 | -9.038 |

    | | pasiv2 pasiv1 | 21.115 | -12.077 | 0.387 | 2.504 |

    | | | | | 0.000 | -11.542|

    | 3 | 3 4 | -85.214 | 84.867 | 0.347 | -16.189 |

    | | A220 pasiv1 | -10.145 | 26.334 | 0.347 | 1.995 |

    | | | | | 0.000 | -18.184|

    | 4 | 3 6 | -201.522 | 201.000 | 0.522 | 15.048 |

    | | A220 A110 | -100.128 | 85.080 | 0.335 | 13.803 || | | | | 0.187 | 1.246|

    | 5 | 2 5 | -160.000 | 159.138 | 0.862 | 24.889 |

  • 8/15/2019 Proiect Sisteme Electroenergetice - For Merge (Recovered)

    29/29

    | | Blimitat pasiv2 | -119.249 | 94.361 | 0.597 | 22.075

    , |

    | | | | | 0.264 | 2.813|

    | 6 | 7 5 | 215.000 | -215.936 | 0.936 | 23.895 |

    | | consB pasiv2 | 91.580 | -115.475 | 0.540 | 20.880 |

    | | | | | 0.396 | 3.015|

    | 7 | 4 8 | -27.683 | 27.500 | 0.183 | 3.068 |

    | | pasiv1 consC | -14.258 | 11.190 | 0.029 | 0.890 |

    | | | | | 0.154 | 2.178|

     ________________________________________________________________________|

    ╔════════════════════════════════════════════════════════════╗ ║  REZULTATE GLOBALE CIRCULATIE PUTERI ║ ╠════════════════════════════════════════════════════════════╣ ║ RETEAUA:Cocis Petre ║ ║ REGIMUL:R20% ║ ╠════════════╦═══════════════════════╦═══════════════════════╣ ║  TOTAL ║  NODURI ║  NODURI ║ ║  PUTERI ║  GENERATOARE ║  CONSUMATOARE ║ ╠════════════╬═══════════════════════╬═══════════════════════╣ ║ P [MW] ║  116.748 ║  -115.500 ║ ║ Q [MVAR] ║  114.391 ║  -49.180 ║ ╠════════════╬══════════╦════════════╩═══════════════════════╣ ║  ║  ║  CONSUMATE ║ ║  TOTAL ║ GENERATE ╠════════════╦═══════════╦═══════════╣ ║  PUTERI ║  ║ ADMITANTE ║ INJECTATE ║  TOTAL ║ ║  ║  ║TRANSVERSALE║  ║  ║ ╠════════════╬══════════╬════════════╬═══════════╬═══════════╣ ║ P [MW] ║  116.748 ║  0.000 ║  -115.500 ║  -115.500 ║ ║ Q [MVAR] ║  120.000 ║  0.000 ║  -54.789 ║  -54.789 ║ ╠════════════╬══════════╩════╦═══════╩═══════╦═══╩═══════════╣ ║ PIERDERI ║  TOTALE ║ LONGITUDINALE ║ TRANSVERSALE ║ ╠════════════╬═══════════════╬═══════════════╬═══════════════╣ 

    ║  ŰP [MW] ║  5.180 ║  3.365 ║  1.815 ║ ║  ŰQ [MVAR] ║  92.105 ║  103.921 ║  -11.816 ║ ╠════════════╩═══════════════╩═══════════════╩═══════════════╣ ║  RANDAMENTUL TRANSPORTULUI DE ENERGIE 98.93 [%] ║ ╚════════════════════════════════════════════════════════════╝