Mylos KNXShutter actuator2CSY1104C/S

Product manual

Page 2: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

2 Contents | MYLOS® Building Automation

MYLOS® Building Automation Contents

Contents

1 Technical features ............................................................................. 31.1 Technical data ................................................................................................ 31.2 Connection diagram ....................................................................................... 4

2 Commissioning ................................................................................. 52.1 Parameters ..................................................................................................... 52.1.1 General .................................................................................................................. 52.2 Actuator .......................................................................................................... 62.3 Status ............................................................................................................. 72.4 Scenes ........................................................................................................... 82.5 Position .......................................................................................................... 9

3 Operation of communication objects ........................................... 10

4 Table of 8 bit scene telegram codes ............................................. 13

Page 3: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

MYLOS® Building Automation | Technical features 3

MYLOS® Building Automation Technical features

1 Technical features

The shutter actuator is a flash-mounted device for the ABB's Mylos Building Automation system, used for the control of a drive for shutters or blinds with the possibility of ascent, descent and louvre adjustment.On the rear side it has connecting terminals for ascent and descent commands of a motor operated shutter. From the parameters it is possible to choose the standby time to be applied to every change of direction.

1.1 Technical data

Power supply - Operating voltage 21…30 VDC over the bus - Absorbed power EIB / KNX < 12 mA

Nominal output values - Number of Up/DOWN outputs 1 exchange contactUP and DOWN are interlocked

- Rated voltage Un 230/440 VAC (50/60Hz) - Rated current In (per output) 8A

Connections - EIB / KNX Connection terminal Bus 0.6-0.8 mm ø, unipole

- Load circuit 1 screw terminal for phase connection, 2 screw terminals for UP and DOWN

- Connection cable cross section 0,2….2,5 mm2 braid0,2….4 mm2 unipole

- Tightening torque Max. 0.5 NmControl and display elements EIB / KNX

- red LED and EIB / KNX button To set the physical address

EIB / KNX voltage - SELV 24 VDC (safety extra low voltage)

Ambient temperature - Use -5 °C … + 45 °C - Storage -25 °C … + 55 °C - Transport -25 °C … + 70 °C

Design - Dimensions (H x W x D) in mm 17 x W x 15 - Width W in mm 17 - Mounting width in mm 7 - Mounting depth in mm 5

Case, colour - Plastic container, white or blackCE marking - acc. to EMC and Low-Voltage

Directives

Device type Application program Maximum number of communication objects

Maximum number of group addresses

Maximum number of associations

2CSYK1204 Shutter 1c/1.0 10 255 255

Page 4: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

4 Technical features | MYLOS® Building Automation

MYLOS® Building Automation Technical features

+ –

L

N

M

Supplied state The device is supplied with the physical address 1.0.1. The application program is preloaded. It is therefore only necessary to load group addresses and parameters during commissioning. However, the complete application program can be reloaded if required. A longer downtime may result if the application program is changed or after a discharge.

Assignment of the physical address The assignment and programming of the physical address is carried out in the ETS. The device features a Programming button for assignment of the physical device address. The red Programming LED lights up, after the button has been pushed. It switches off, as soon as the ETS has assigned the physical address or the Programming button is pressed again.

Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive agents or solutions should never be used.

Download behaviour Depending on the PC, which is used, the progress bar for the download may take up to one and a half minutes, before it appears, due to the complexity of the device.

Maintenance The device is maintenance-free. No repairs should be carried out by unauthorised personnel if damage occurs, e. g. during transport and/or storage.

1.2 Connection diagram

DO

WN

CO

MM

ON

UP

Page 5: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

MYLOS® Building Automation | Commissioning 5

MYLOS® Building Automation Commissioning

2 Commissioning

The main functions of the shutter actuator are described in this section. The shutter actuator parametrisation is performed via the Engineering Tool ETS Software application program.For the parametrisation you need a pc desktop or a laptop with ETS and connection to the KNX system (obtainable for example by means of RS232, USB or IP Interface).

2.1 Parameters

2.1.1 General

Operating modeIt is possible to define the device operation mode using this parameter, even if the parameters and communication objects for the two operating modes are very similar.

Position for bus voltage interruptionThe parameter allows you to define the device behaviour upon voltage failure. In particular, for the "No reaction" case the output contacts will remain in their position, whereas in the "Stop" case the shutter/blind will stop immediately.

Position upon bus voltage restorationSimilarly to the previous parameter, this parameter manages the device output contacts upon voltage restoration.

8 bit sceneIf it is set on “Enable” both the “Scene” communication object and the “Scenes” parameter window will appear.

Page 6: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

6 Commissioning | MYLOS® Building Automation

MYLOS® Building Automation Commissioning

2.2 Actuator

Stroke duration [0…6000] secParameter used to set the stroke duration in seconds.

Louvre adjustment duration [60…1000] msec (only if the operating mode set by parameters is Blind)The parameter determines louvre adjustment duration.

Pause in the change of direction. 300…10000 msecPause between two changes of direction

Maximum number of louvre adjustments [1…60] msec (only if the operating mode set by parameters is Blind)To set the maximum number of louvre adjustment.

Start-up delay [0…255] msecTo set the delay upon start-up of any device movement.

Switch-off delay [0…255] msecTo set the delay at the end of any device movement.

Switch the voltage-free outputs afterThis parameter allows the device to actually reach the (upper or lower) limit switch position. At the limit switch duration a further movement command in the same direction will cause:

- no reaction for "Limit switch reaching, no exceeding"; - a stroke equal to 2% of the stroke duration for "Limit switch, 2% exceeding"; - a stroke equal to 5% of the stroke duration for "Limit switch, 5% exceeding"; - a stroke equal to 10% of the stroke duration for "Limit switch, 10% exceeding"; - a stroke equal to 20% of the stroke duration for "Limit switch, 20% exceeding"; - a stroke equal to 110% of the stroke duration for "Stroke total time, 10% exceeding";

Page 7: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

MYLOS® Building Automation | Commissioning 7

MYLOS® Building Automation Commissioning

2.3 Status

Send position [0…255]If “Yes” the “Position status” and “Louvre status” communication objects will appear (the last one only in case of “BIlnd” operation).

Send the position after reaching the limit switchIf “Yes” the “Upper limit switch” and “Lower limit switch” will be displayed.

Page 8: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

8 Commissioning | MYLOS® Building Automation

MYLOS® Building Automation Commissioning

2.4 Scenes

Association 1 – Association 10The parameters allow you to determine which scene group the device belongs to. It is possible to select up to 10 associations and for each association you can select up to 64 scenes.

Page 9: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

MYLOS® Building Automation | Commissioning 9

MYLOS® Building Automation Commissioning

2.5 Position

Recall position [0…255]If it is set on “Enable” the “Recall position 0…255” communication objects will appear.

Objects for "Storing position"If it is set on “Enable” the “Store position 1 or 2” and “Store position 3 or 4” communication objects will appear.

Objects for "Recalling position"If it is set on “Enable” the “Recall position 1 or 2” and “Recall position 3 or 4” communication objects will appear.

Page 10: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

10 Operation of communication objects | MYLOS® Building Automation

MYLOS® Building Automation Operation of communication objects

3 Operation of communication objects

For the "Blind" operating mode:

No. Function Object name Type of datum Flags

0 Blind up-down Output 1 bit DPT Up Down C, W

For the "Shutter" operating mode:

0 Blind up-down Output 1 bit DPT Up Down C, W

If a telegram with the value “0” is received at this communication object, the shutter/blind is raised. If a telegram with the value “1” is received, the shutter/blind is lowered. The output contact reverts to the neutral position once the total travel time for UP/DOWN movement has elapsed.Telegram value: “0”:

- UP“1”:

- DOWN

For the "Blind" operating mode:

1 Louvres/Stop up-down Exit 1 bit DPT Up Down C, W

For the "Shutter" operating mode:

1 Stop up-down Output 2 bit (EIS 8) DPT 2.001 C, W

If the shutter/blind is in motion, the movement is stopped on receipt of a telegram at this communication object, regardless of whether a “0” or a “1” has been received.“Blinds” operating mode: If the shutter is idle, it is raised (“0”) or lowered (“1”) for the duration of the louvre adjustment and then stopped on receipt of a telegram at this communication object.“Shutter” operating mode: If the blind is idle, no action is carried out on receipt of a telegram at this communication object.Telegram value:“0”:

- Stop/louvre adj. UP“1”:

- Stop/louvre adj. DOWN

2 Recall position 0 ... 255 Exit 1 Byte DPT Percent U8

C, W

Page 11: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

MYLOS® Building Automation | Operation of communication objects 11

MYLOS® Building Automation Operation of communication objects

If a telegram is received at this communication object, the shutter/blind moves to the corresponding position for the received value.After reaching the target position, the louvres are positioned as before. Only if during the shutter/blind movement a telegram was received on the communication object “Move louvres 0…255”, the louvres will be positioned accordingly.Telegram value:“0”:

- Top“...”:

- Intermediate position“255”:

- Bottom

3Scene Output 1 Byte DPT Scene

ControlC, W

Output can be integrated into up to ten scenes with this communication object. A telegram is received which contains the number of the scene that is addressed together with the information about whether the shutter/blind is moved to the last saved position or whether the current position should be stored as the new preset value.The stored scene values are retained in the event of a bus voltage failure and if only the parameters are downloaded during programming. If the complete application is downloaded again during programming, the scene value is reset to the position “right at the top”.Telegram code:

- MXNNNNNNNNNNNN:

- 0...63: Scene numberM:

- “0”: Recall scene - “1”: Store scene

4Position status Output 1 Byte DPT Percent

U8C, R, T

The Shutter Actuator sends the current position of the shutter/blind to this communication object. The current position is sent approx. 5 seconds after the completion of a movement. If a new movement is started in the meantime, the current position is only sent once the last action has been completed.Telegram value: “0”:

- Top“...”:

- Intermediate position“255”:

- Bottom

For the "Shutter" operating mode:

5Louvres status Exit 1 Byte DPT Percent

U8C, R, T

The Shutter Actuator sends the current position of the louvres to this communication object. The current position is sent approx. 5 seconds after the completion of a movement. If a new movement is started in the meantime, the current position is only sent once the last action has been completed.Telegram value: “0”:

- Louvres opened to maximum“...”:

- Intermediate position“255”:

- Louvres closed

Page 12: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

12 Operation of communication objects | MYLOS® Building Automation

MYLOS® Building Automation Operation of communication objects

6 Recall position 1 or 2 Output 1 bit DPT Switch C, W

7 Recall position 3 or 4 Output 1 bit DPT Switch C, W

If a telegram is received at this communication object, the shutter/blind is moved to the stored preset position. In the “Blinds” operating mode, the louvre adjustment is carried out according to the preset position once the position has been reached.If a telegram with the value “0” is received, the shutter/blind moves to position 1 (or position 3). If a telegram with the value “1” is received, the shutter/blind moves to position 2 (or position 4).Telegram value: “0”:

- Move to position 1 or - Move to position 3

“1”: - Move to position 2 or - Move to position 4

8 Store position 1 or 2 Output 1 bit DPT Switch C, W

9 Store position 3 or 4 Output 1 bit DPT Switch C, W

If a telegram is received at this communication object, the current position of the shutter/blind is adopted as the new preset value.If a telegram with the value “0” is received, the current position is stored as the new preset value for position 1 (or position 3). If a telegram with the value “1” is received, the current position is stored as the new preset value for position 2 (or position 4). If position 1 or 2 is now recalled (position 3 or 4), the shutter/blind moves to the new preset values.The modified preset values are retained on bus voltage failure. After programming the Shutter Actuator, the preset values are reset to the values that were parameterised during the project design stage or the values adapted in operation are stored, depending parameterization.Telegram value: “0”:

- Set position 1 or - Set position 3

“1”: - Set position 2 or - Set position 4

10 Upper limit switch Output 1 bit DPT Start C, R, T

The Shutter Actuator sends the information to this communication object as to whether the shutter/blind is located in the upper limit position or not. The current position is sent approx. 1 second (plus the switch on duration of the louvre adjustment if applicable) after the upper limit position has been reached or left. If a new movement is started in the meantime, the current position is only sent once the last action has been completed.Telegram value: “0”:

- Shutter/blind not in upper limit position“1”:

- Shutter/blind in upper limit position

Page 13: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive

MYLOS® Building Automation | Table of 8 bit scene telegram codes 13

MYLOS® Building Automation Table of 8 bit scene telegram codes

Bit no. 7 6 5 4 3 2 1 0

8-B

it V

alue

s

Hex

adec

imal

Rec

all/

Sto

re

No

t d

efin

ed

Scene number Sce

ne n

o.

Rec

all (

A)/

S

tore

(S)

0 00 0 0 0 0 0 0 0 0 1 A1 01 0 0 0 0 0 0 0 1 2 A2 02 0 0 0 0 0 0 1 0 3 A3 03 0 0 0 0 0 0 1 1 4 A4 04 0 0 0 0 0 1 0 0 5 A5 05 0 0 0 0 0 1 0 1 6 A6 06 0 0 0 0 0 1 1 0 7 A7 07 0 0 0 0 0 1 1 1 8 A8 08 0 0 0 0 1 0 0 0 9 A9 09 0 0 0 0 1 0 0 1 10 A

10 0A 0 0 0 0 1 0 1 0 11 A11 0B 0 0 0 0 1 0 1 1 12 A12 0C 0 0 0 0 1 1 0 0 13 A13 0D 0 0 0 0 1 1 0 1 14 A14 0E 0 0 0 0 1 1 1 0 15 A15 0F 0 0 0 0 1 1 1 1 16 A16 10 0 0 0 1 0 0 0 0 17 A17 11 0 0 0 1 0 0 0 1 18 A18 12 0 0 0 1 0 0 1 0 19 A19 13 0 0 0 1 0 0 1 1 20 A20 14 0 0 0 1 0 1 0 0 21 A21 15 0 0 0 1 0 1 0 1 22 A22 16 0 0 0 1 0 1 1 0 23 A23 17 0 0 0 1 0 1 1 1 24 A24 18 0 0 0 1 1 0 0 0 25 A25 19 0 0 0 1 1 0 0 1 26 A26 1 A 0 0 0 1 1 0 1 0 27 A27 1B 0 0 0 1 1 0 1 1 28 A28 1C 0 0 0 1 1 1 0 0 29 A29 1D 0 0 0 1 1 1 0 1 30 A30 1E 0 0 0 1 1 1 1 0 31 A31 1F 0 0 0 1 1 1 1 1 32 A32 20 0 0 1 0 0 0 0 0 33 A33 21 0 0 1 0 0 0 0 1 34 A34 22 0 0 1 0 0 0 1 0 35 A35 23 0 0 1 0 0 0 1 1 36 A36 24 0 0 1 0 0 1 0 0 37 A37 25 0 0 1 0 0 1 0 1 38 A38 26 0 0 1 0 0 1 1 0 39 A39 27 0 0 1 0 0 1 1 1 40 A40 28 0 0 1 0 1 0 0 0 41 A41 29 0 0 1 0 1 0 0 1 42 A42 2 A 0 0 1 0 1 0 1 0 43 A43 2B 0 0 1 0 1 0 1 1 44 A44 2C 0 0 1 0 1 1 0 0 45 A45 2D 0 0 1 0 1 1 0 1 46 A46 2E 0 0 1 0 1 1 1 0 47 A47 2F 0 0 1 0 1 1 1 1 48 A48 30 0 0 1 1 0 0 0 0 49 A49 31 0 0 1 1 0 0 0 1 50 A50 32 0 0 1 1 0 0 1 0 51 A51 33 0 0 1 1 0 0 1 1 52 A52 34 0 0 1 1 0 1 0 0 53 A53 35 0 0 1 1 0 1 0 1 54 A54 36 0 0 1 1 0 1 1 0 55 A55 37 0 0 1 1 0 1 1 1 56 A56 38 0 0 1 1 1 0 0 0 57 A57 39 0 0 1 1 1 0 0 1 58 A58 3A 0 0 1 1 1 0 1 0 59 A59 3B 0 0 1 1 1 0 1 1 60 A60 3C 0 0 1 1 1 1 0 0 61 A61 3D 0 0 1 1 1 1 0 1 62 A62 3E 0 0 1 1 1 1 1 0 63 A

127 7F 0 1 1 1 1 1 1 1 0 A128 80 1 0 0 0 0 0 0 0 1 S129 81 1 0 0 0 0 0 0 1 2 S130 82 1 0 0 0 0 0 1 0 3 S131 83 1 0 0 0 0 0 1 1 4 S132 84 1 0 0 0 0 1 0 0 5 S133 85 1 0 0 0 0 1 0 1 6 S134 86 1 0 0 0 0 1 1 0 7 S135 87 1 0 0 0 0 1 1 1 8 S136 88 1 0 0 0 1 0 0 0 9 S137 89 1 0 0 0 1 0 0 1 10 S138 8A 1 0 0 0 1 0 1 0 11 S139 8B 1 0 0 0 1 0 1 1 12 S140 8C 1 0 0 0 1 1 0 0 13 S141 8D 1 0 0 0 1 1 0 1 14 S142 8E 1 0 0 0 1 1 1 0 15 S143 8F 1 0 0 0 1 1 1 1 16 S144 90 1 0 0 1 0 0 0 0 17 S145 91 1 0 0 1 0 0 0 1 18 S146 92 1 0 0 1 0 0 1 0 19 S147 93 1 0 0 1 0 0 1 1 20 S148 94 1 0 0 1 0 1 0 0 21 S149 95 1 0 0 1 0 1 0 1 22 S150 96 1 0 0 1 0 1 1 0 23 S151 97 1 0 0 1 0 1 1 1 24 S152 98 1 0 0 1 1 0 0 0 25 S153 99 1 0 0 1 1 0 0 1 26 S154 9A 1 0 0 1 1 0 1 0 27 S155 9B 1 0 0 1 1 0 1 1 28 S

Bit no. 7 6 5 4 3 2 1 0

8-B

it V

alue

s

Hex

adec

imal

Rec

all/

Sto

re

No

t d

efin

ed

Scene number Sce

ne n

o.

Rec

all (

A)/

S

tore

(S)

156 9C 1 0 0 1 1 1 0 0 29 S157 9D 1 0 0 1 1 1 0 1 30 S158 9E 1 0 0 1 1 1 1 0 31 S159 9F 1 0 0 1 1 1 1 1 32 S160 A0 1 0 1 0 0 0 0 0 33 S161 A1 1 0 1 0 0 0 0 1 34 S162 A2 1 0 1 0 0 0 1 0 35 S163 A3 1 0 1 0 0 0 1 1 36 S164 A4 1 0 1 0 0 1 0 0 37 S165 A5 1 0 1 0 0 1 0 1 38 S166 A6 1 0 1 0 0 1 1 0 39 S167 A7 1 0 1 0 0 1 1 1 40 S168 A8 1 0 1 0 1 0 0 0 41 S169 A9 1 0 1 0 1 0 0 1 42 S170 AA 1 0 1 0 1 0 1 0 43 S171 AB 1 0 1 0 1 0 1 1 44 S172 AC 1 0 1 0 1 1 0 0 45 S173 AD 1 0 1 0 1 1 0 1 46 S174 AE 1 0 1 0 1 1 1 0 47 S175 AF 1 0 1 0 1 1 1 1 48 S176 B0 1 0 1 1 0 0 0 0 49 S177 B1 1 0 1 1 0 0 0 1 50 S178 B2 1 0 1 1 0 0 1 0 51 S179 B3 1 0 1 1 0 0 1 1 52 S180 B4 1 0 1 1 0 1 0 0 53 S181 B5 1 0 1 1 0 1 0 1 54 S182 B6 1 0 1 1 0 1 1 0 55 S183 B7 1 0 1 1 0 1 1 1 56 S184 B8 1 0 1 1 1 0 0 0 57 S185 B9 1 0 1 1 1 0 0 1 58 S186 BA 1 0 1 1 1 0 1 0 59 S187 BB 1 0 1 1 1 0 1 1 60 S188 BC 1 0 1 1 1 1 0 0 61 S189 BD 1 0 1 1 1 1 0 1 62 S190 BE 1 0 1 1 1 1 1 0 63 S

4 Table of 8 bit scene telegram codes

Page 14: Product manual Mylos KNX Shutter actuator 2CSY1104C/S€¦ · Cleaning If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution. Corrosive