    Cascade Control

  • 8/21/2019 Process Control Chap 9 Cascade Control

    2/20

    Cascade control• A disadvantage of conventional feedback control is that corrective action for

    disturbances does not begin until after the controlled variable deviates from the set

    point.

    • Feedforward control offers large improvement over feedback control for

    processes that have large time constants or t ime delays. However, feedforward

    control requires that the disturbances be measured explici tly and that a model

    be available to calculate the control ler output.

    •  An alternative approach, one that can significantly improve the dynamic response

    to disturbances, employs a secondary measurement point and a secondary

    feedback contro ller.

    • The second measurement point is located so that it recognizes the upset

    condition sooner than the controlled variable, but the disturbance is notnecessarily measured.

    • This approach, cascade control, is widely used in the process industries and is

    particularly useful when the disturbances are associated with the manipulated

    variable or when the final control element exhibits nonlinear behaviour(Shinskey,

    1996).

  • 8/21/2019 Process Control Chap 9 Cascade Control

    3/20

    A furnace temperature control scheme that uses

    conventional feedback control

    Furnace

    Hot oil

    Cold oil

    Stack gasTC

    TT

    Fuel gas

    • Consider the natural draft furnace

    temperature control .

    • The conventional feedback

    control system may do

    satisfactory job of regulating the

    hot oil temperature despite

    disturbances in oil flow rate or

    cold oil temperature.

    • However, if a disturbance occursin the fuel gas supply pressure,

    the fuel gas flow will change,

    which upsets the furnace

    operation and changes the hot oil

    temperature.

    • Only then will the temperature

    controller (TC) begin to takecorrective action by adjusting the

    fuel gas flow.

    • Thus, we anticipate that

    conventional feedback control

    may result in very sluggish

    responses to changes in fuel gas

    supply pressure.

  • 8/21/2019 Process Control Chap 9 Cascade Control

    4/20

    A furnace temperature control scheme using

    cascade control

    Furnace

    Hot oil

    Cold oil

    Stack gasTC

    TT

    Fuel gas

    PT

    PC

  • 8/21/2019 Process Control Chap 9 Cascade Control

    5/20

    • A cascade control configuration which consists of a primary controlloop (TT and TC) and a secondary control loop that controls the

    pressure via PT and PC.

    • The primary measurement is the hot oil temperature that is used bythe master controller (TC) to establish the set point for thesecondary (slave) loop controller (PC).

    • If a disturbance in supply pressure occurs, the pressure controllerwill act quickly to hold the fuel gas pressure at its set point.

    • The cascade control scheme provides improved performancebecause the control valve will be adjusted as soon as the change insupply pressure is detected.

    • Because the pressure control loop responses rapidly, the supplypressure disturbance will have little effect on furnace operation andexit oil temperature

  • 8/21/2019 Process Control Chap 9 Cascade Control

    6/20

    • The cascade control loop structure has two distinguishing features:

    1. The output signal of the master controller serves as the set point for the slavecontroller 

    2.The two feedback control loops are nested, with the secondary control loop

    (for the slave controller) locate inside the primary control loop (for the mastercontroller)

    • Thus there are two controlled variables, two sensors, and one manipulatedvariable, whereas, the conventional control structure has one controlledvariable, one sensor, and one manipulated variable.

    • The primary control loops can change the set point of the pressure control loopbased on deviations of the hot oil temperature from its set point.

    • If the hot oil temperature is at its set point, the deviation variable for thepressure set point is also zero, which keeps the pressure at its desired steadystate value.

  • 8/21/2019 Process Control Chap 9 Cascade Control

    7/20

    • The simplest cascade control scheme involves twocontrol loops that use two measurement signals tocontrol one primary variable. In such a control system,the output of the primary controller determines the set

    point for the secondary controller. The output of thesecondary controller is used to adjust the controlvariable. Generally, the secondary controller changesquickly while the primary controller changes slowly.

    Once cascade control is implemented, disturbancesfrom rapid changes of the secondary controller will notaffect the primary controller.

  • 8/21/2019 Process Control Chap 9 Cascade Control

    8/20

    Single loop control and cascades

    control of a heat exchanger

    https://controls.engin.umich.edu/wiki/index.php/File:FlowOfInformationHeatEx2.jpghttps://controls.engin.umich.edu/wiki/index.php/File:HeatExDoubleLoop2.jpghttps://controls.engin.umich.edu/wiki/index.php/File:FlowOfInformationHeatEx1.jpghttps://controls.engin.umich.edu/wiki/index.php/File:HeatExSingleLoop1.jpg

  • 8/21/2019 Process Control Chap 9 Cascade Control

    9/20

    Information flow of a two loop cascade

    control

    • there are two separate loops. Loop 1 is known as the primary loop, outerloop, or the master, whereas loop 2 is known as the secondary loop, innerloop, or the slave. To identify the primary and secondary loops, one mustidentify the control variable and the manipulated variable. In this case,

    the control variable is the temperature and the reference variable is thesteam flow rate. Hence, the primary loop (loop 1) involves the controlvariable and the secondary loop (loop 2) involves the reference variable.Please note that the user sets the set point for loop 1 while the primarycontroller sets the set point for loop 2.

    https://controls.engin.umich.edu/wiki/index.php/File:Twoloopcascadecontrol1.jpg

  • 8/21/2019 Process Control Chap 9 Cascade Control

    10/20

    General cascade schematic

    • The reactor below needs to be cooledduring continuous-feed operation of anexothermic reaction.

    • The reactor has been equipped with acooling water jacket with the water flowrate being controlled by cold water valve.

    • This valve is controlled by two separatetemperature controllers. An “inner-loop”or “slave” (highlighted in orange)temperature transmitter communicates tothe slave controller the measurement ofthe temperature of the jacket.

    • The “outer-loop” or “master” (green)temperature controller uses a mastertemperature transmitter to measure thetemperature of the product within thereactor.

    https://controls.engin.umich.edu/wiki/images/7/70/CascadeReactorEx.jpg

  • 8/21/2019 Process Control Chap 9 Cascade Control

    11/20

    • The reactor temperature is affected by changes indisturbance variables such as reactant feed temperature orfeed composition.

    • The simplest control strategy, adjust a control valve on thecooling water inlet stream.

    • However, an increase in the inlet cooling watertemperature, may cause unsatisfactory performance

    • Add a feedback controller for the jacket temperature,whose set point is determined by the reactor temperature

    controller• The control system measures the jacket temperature,

    compare it to a set point, and uses the resulting error signalas the input to a controller for the cooling water makeup.

  • 8/21/2019 Process Control Chap 9 Cascade Control

    12/20

    • The principal advantage of the cascade control

    strategy is that a second measure variable is

    located to a potential disturbance and its

    associated feedback loop can react quickly,

    thus improving the close loop response.

  • 8/21/2019 Process Control Chap 9 Cascade Control

    13/20

    https://controls.engin.umich.edu/wiki/index.php/File:Slave1.jpghttps://controls.engin.umich.edu/wiki/images/7/7d/Master.jpghttps://controls.engin.umich.edu/wiki/images/4/4c/Cascade.jpg

  • 8/21/2019 Process Control Chap 9 Cascade Control

    14/20

    https://controls.engin.umich.edu/wiki/index.php/File:Solvey2.jpghttps://controls.engin.umich.edu/wiki/index.php/File:Step_2.jpg

  • 8/21/2019 Process Control Chap 9 Cascade Control

    15/20

    https://controls.engin.umich.edu/wiki/index.php/File:Y1t.jpghttps://controls.engin.umich.edu/wiki/index.php/File:Step_3.jpg

  • 8/21/2019 Process Control Chap 9 Cascade Control

    16/20

    • In order to have a smooth flow of information throughout the control system, a hierarchy ofinformation must be maintained. In a double loop cascade system, the action of the secondaryloop on the process should be faster than that of the primary loop. This ensures that thechanges made by the primary output will be reflected quickly in the process and observed when

    the primary control variable is next measured. This hierarchy of information can be preserved byapplying the following conditions when setting up the cascade controls.

    -There must be a clear relationship between the measured variables of the primary andsecondary loops.

    -The secondary loop must have influence over the primary loop.

    -Response period of the primary loop has to be at least 4 times larger than the response periodof the secondary loop.

    -The major disturbance to the system should act in the primary loop.

    -The primary loop should be able to have a large gain, Kc.

    • Cascade control is best when the inner loop is controlling something that happens at fairly highfrequency. Cascade control is designed to allow the master controller to respond to slowchanges in the system, while the slave controller controls disturbances that happen quickly. If set

    up in reverse order, there will be a large propagation of error. Hence, it is important to maintainthe hierarchy of information. In summary, the master controller responds to SLOW changes inthe system, while the slave controller responds to the high frequency, or FAST changes in thesystem. This also requires that the inner control scheme be tuned TIGHTLY so error is notallowed to build. Commonly, the inner loops controls a flow controller, which will reduce theeffect of changes such as fluctuations in steam pressure.

  • 8/21/2019 Process Control Chap 9 Cascade Control

    17/20

    • Characteristic equation?

    • If the inner loop is removed?

  • 8/21/2019 Process Control Chap 9 Cascade Control

    18/20

    performance

    • Cascade control can improve the response to a set pointchange by using an intermediate measurement and twofeedback controllers. However, its performance in thepresence of disturbances is usually the principal concern.

    • When the slave loop responds faster than the master loop,the cascade control system will have improved stabilitycharacteristics and thus should allow larger values of Kc1 tobe used in the primary loop. Cascade control also makesthe close loop process less sensitive to errors in the processmodel used to design the controller