pro-con structural study of alternate floor systems...and having an allowable bearing capacity of 20...
TRANSCRIPT
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 1 -
Pro-Con Structural Study of Alternate Floor Systems October 27, 2004
Executive Summary
For this assignment four different flooring systems were designed and
evaluated for a common bay of the Arlington Gateway Hotel. The four
systems along with the current system are evaluated in a pro-con format.
These systems are:
♦ Standard one-way reinforced concrete joist system
♦ Two-way waffle slab
♦ Open web steel joists on non-composite steal beams
♦ Non-composite steel beams and composite deck
♦ Two-way flat plate – Current system
Through the evaluation, the floor systems were designed for a minimum total
height of the flooring system to compare to the shallowness of the two-way
flat plate design.
The designs have a strict tolerance to reduce vibrations, deflections, and to
meet a 2-hour fire rating. At this time, there is a need to eliminate the
concrete joist system because in keeping with minimum system thickness,
layout and deflections are not desirable. All other systems have
advantages and should be further investigated.
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 2 -
Design Parameters
The hotel was designed using a live load of 40 psf for typical floors and 70 psf
for corridors. In my design I only designed for gravity loads, no lateral loads
were calculated. I chose to design the whole interior bay using the 70 psf
live load for corridors, as they pass through the center of the bay. Exterior
bays shall be designed using 40 psf live loads. These loads were taken from
ASCE 7 code book. Dead loads on the structure are made up of 15 psf for
partitions, 10 psf for MEP, and material self weight. At this time, fire rating of
the structure is not available. I designed the systems using a 2-hour fire
rating. I used a deflection of l/360 for all systems.
Design is of the common, center
bay of floors 4 through 14 as
displayed in the figure. The
cross-hatched area is the total
floor area of floors 10 through 14,
with an outline of the building
footprint shown. The bay is 26’-
11” for east to west and 19’-9” from north to south.
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 3 -
Two-way Flat Plate – Existing Condition
The current system is a two-way flat plate using a concrete compressive
strength of 4000 psi and 60 ksi steel reinforcing bars. A slab thickness of 8” is
used throughout the entire floor with #4 bottom bars spaced 10” each way.
The column strips have top reinforcement of
#5 bars spaced as per structural drawings.
Columns dimensions are 16” x 32” and use
5000 psi concrete on the fourth through
eighth floor and 4000 psi concrete on the
remaining upper floors. An existing layout of
the bay being designed is provided on the
left.
A major advantage to a two-way flat plate is the ability to have a relatively
small floor to floor height. This reduces the amount of exterior cladding
needed to enclose the building; thus, reducing the overall cost of the
structure. Also, it is a good system due to the flatness of the bottom slab
which allows for fast application of formwork. Concrete structures require
very little lead time, therefore can be designed and built in less time than
steel structures.
One-way Concrete Joists – Alternate System 1
The first alternate system I evaluated was a one-way concrete joist system. I
used the CRSI Handbook 2002 to aid in the design of this system. I used 4000
psi concrete with 60 ksi steel. In trying to design the thinnest system I
designed the system with a total floor thickness of 12.5” including a 4.5” slab
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 4 -
that provides a 2-hour fire rating. The layout
uses 30” forms + 5” ribs at a spacing of 35”
center to center. Each joist is reinforced
with #3 + #4 bottom bars and having top
bars of #4 at 12”. The beams were
designed as band beams spanning
between columns. Due to the long span
and shallowness of beam, a 12.5” x 48”
beam is required with 6-#7 bottom bars and
6 - #9 top bars for reinforcing.
There are several advantages to using a
concrete joist system. It is lighter than a
two-way flat plate and can also span
longer distances.
Waffle Slab – Alternate System 2
The use of a two-way waffle slab is
another alternative to the existing
flat plate. On the right is a
diagram of the proposed waffle
slab column strip and middle strip.
The system was designed using a
concrete compressive strength of
4000 psi and steel strength of 60
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 5 -
ksi. The total floor thickness is 12.5”, comprised of 8” drop panels and a 4.5”
slab. Use of 30” x 30” dome forms will allow for 3’-0” on-center spacing of
the 6” ribs. A 13” x 13” minimum size column is required for shear stresses in
the floor. At this time sizing of shear panels around column have not been
calculated. Reinforcement in the column strip is 2 - #6 bottom bars and 21 -
#5 top bars and includes 4 ribs. The reinforcement in the middle strip is a #4
for the long bar and a #5 short bar for bottom bars, while the top bars are to
be 8 - #5.
Advantages of a waffle slab design are the ability of it to span long spans
with minimal deflection and self weight. A disadvantage to it is the amount
of time involved in placing formwork and rebar. The extra labor required will
add to the building cost and lengthen the time it will take to erect the
structure.
Steel Joists – Alternate System 3
The third system I chose was to use a total slab
thickness of 4.5” reinforced concrete with 6x6
W2.1xW2.1 welded wire fabric or a fiber mesh
on non-composite metal decking. The
concrete compressive strength is 3000 psi. The
1.5 C24 galvanized decking is on 18LH4 open
web steel joists spaced 4’-0” on center with 2
rows of bridging. The joists span from east to west and sit on W18x55 non-
composite beams. The beams spanning east to west between columns
were designed as non-composite W16x31 beams as illustrated in the
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 6 -
diagram is provided. All steel has a tensile strength of 50 ksi. The 4.5” slab
was required for a 2-hour fire rating and beams will need to have
fireproofing applied to them. The total thickness of the floor system is 22”.
The advantage of a steel structure is the quickness of erection of the
structure and the lighter weight of the total system over concrete.
Disadvantages are the requirement of fireproofing, which increases cost of
the structure and the lead time involved in ordering and fabricated of the
steel members. Also, floor to floor heights are greater than that of concrete
requiring more exterior cladding and also more surface area and higher
lateral loads throughout the structure.
Non-Composite Beams and Composite Decking – Alternate System 4
My fourth and final alternative is the use of non-composite beams with
composite metal decking. The system includes a 4.5” reinforced concrete
slab with 6x6 W1.4xW1.4 welded wire fabric or
the use of an acceptable fiber mesh. The
decking is 1.5VL18 galvanized composite
metal decking on W14x90 beams with tensile
strength of 50 ksi. The total thickness of the
system is roughly 20”.
The disadvantages and advantages are similar to that of the steel joist
system. The possibility of designing this system with composite beams exists
and will reduce beam sizes by weight and depth, which may provide a
more viable option.
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 7 -
Conclusion
The only system I can eliminate at this time is the one-way concrete joists. To
keep the total slab thickness the same, a 48” wide beam is needed
between columns. The current beam is at its limits for my desired deflection
of l/360. The three other systems require further investigation along with the
possibility of making the steel systems use composite steel beams to reduce
beam sizing.
The overall advantages and disadvantages of each system are as follows.
The concrete systems require no additional fireproofing, which steel requires;
thus, limiting its expense. With the foundation sitting on decomposed rock
and having an allowable bearing capacity of 20 to 40 tons per square foot,
weight of the building structural system is not a major concern. It is not a
factor in selection of a flooring system. All systems can be designed as
moment frames to resist lateral loads. As mentioned above, steel floor
systems require a larger floor-to-floor height creating a need for more
exterior cladding. Also, the building will be taller and have to resist more
lateral loads from wind due to the increase surface area of the façade.
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 8 -
Structural Floor Systems Comparison Chart
System Overall Thickness
Overall Weight Advantages Disadvantages Further
Investigation
Two-way Flat Plate 8" 100 psf
Thin floor system Ease of placing formwork Fireproofing not required
Heavy system Labor intensive Existing
One-Way Concrete Joist
12.5" 72 psf Fireproofing not required Low floor-to-floor heights Desirable finish
Labor intensive Takes longer to construct No
Waffle Slab 12.5" 91 psf Fireproofing not required Low floor-to-floor heights Desirable finish
Labor intensive Takes longer to construct Yes
Steel Beams and Joists 22" 60 psf
Lighter structure Quick construction Ease of construction
Requires fire proofing Long material lead times Taller structure
Yes
Steel Beams and Composite Metal Deck
20" 51 psf Lighter structure Quick construction Ease of construction
Requires fire proofing Long material lead times Taller structure
Yes
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 9 -
Appendix Title Pages 1. One-Way Joist System 10-11
2. Two-Way Waffle Slab 12
3. Steel Joists 13
4. Steel Beams 14
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 10 -
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 11 -
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 12 -
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 13 -
Michael Gray Structural Option Faculty Consultant – Dr. Linda Hanagan Arlington Gateway Hotel Arlington, VA
Rendering courtesy of WDG Architecture
Arlington Gateway Hotel - Technical Assignment 2 - 14 -