Dual Pressure Control KP 44 Ambient temperatures t 1 min. -40°C (-40°F) t 1 max. 65°C (150°F) Caution: Do not mount the control in a position where dirt, sediment or oil will affect the operation of the control. Test pressure (p test ) Control Safety Control MWP 17 bar P e Safety MWP 17 bar P e Connections Enclosure Caution: The mounting panel must be plane to avoid damage of control Mounting Electrical connections Contact material AgCdO Contact load, Ag contact set Control Safety DKRCC.PI.CD0.B1.02-520H1468 ©Danfoss A/S 1 060R9766 060R9766 Instructions P test max. 22 bar P e P test max. 22 bar P e 1. Lefthand pressure setting spindle 2. Differential setting spindle 3. Main arm 4. Righthand pressure setting spindle 5. Main spring 6. Differential spring 7. Bellows 8. Pressure connections 9. Switch 10. Terminal 11. Earth terminal 12. Cable entry 13. Tumbler 14. Locking plate 15. Impulse lever The switch in the KP has a snap-action function, and the bellows moves only when the cut-in or cut-out value is reached. (320 psig) (320 psig) (246 psig) (246 psig) Cable entry ½ in. internal thread accepts ½ in. NPT or NPS Electrical ratings: AC-1: 16 A, 400 V AC-3: 16 A, 400 V AC-15: 10 A, 400 V DC-13: 12 W, 220 V When used according to UL regulations: 120 V a.c. : 16 FLA, 96 LRA 240 V a.c. : 8 FLA, 48 LRA 240 V d.c. : 12 W, pilot duty

Upload: ninaninoninos

Post on 12-Apr-2015

10 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: pressostato intruções montagem.pdf

Dual Pressure Control

KP 44

Ambient temperatures

t1 min. -40°C (-40°F)

t1 max. 65°C (150°F)

Caution: Do not mount the control in a position where

dirt, sediment or oil will affect the operation of the

control.

Test pressure (p test

)

Control Safety

Control MWP 17 bar Pe

Safety MWP 17 bar Pe

Connections

Enclosure

Caution: The mounting panel must be plane to avoid damage

of control

Mounting

Electrical connections

Contact material AgCdO

Contact load, Ag contact set

Control Safety

DKRCC.PI.CD0.B1.02-520H1468 ©Danfoss A/S 1

06

0R

97

66

06

0R

97

66

Instructions

Ptest

max.

22 bar Pe

Ptest

max.

22 bar Pe

1. Lefthand pressure setting spindle 2. Diff erential setting spindle 3. Main arm 4. Righthand pressure setting spindle 5. Main spring 6. Diff erential spring 7. Bellows 8. Pressure connections 9. Switch 10. Terminal 11. Earth terminal 12. Cable entry 13. Tumbler 14. Locking plate 15. Impulse lever

The switch in the KP has a snap-action function, and the bellows moves only when the cut-in or cut-out value is reached.

(320 psig)

(320 psig)

(246 psig)(246 psig)

Cable entry ½ in. internal thread

accepts ½ in. NPT or NPS

Electrical ratings:

AC-1: 16 A, 400 VAC-3: 16 A, 400 VAC-15: 10 A, 400 VDC-13: 12 W, 220 V

When used according to UL regulations:

120 V a.c. : 16 FLA, 96 LRA240 V a.c. : 8 FLA, 48 LRA240 V d.c. : 12 W, pilot duty

Page 2: pressostato intruções montagem.pdf

06

0R

97

66

06

09

76

6

2 ©Danfoss A/S DKRCC.PI.CD0.B1.02-520H1468

©D

an

foss

A/S

06

-20

06

(A

C-D

SL/

mr)

Setting

CONTROL side setting SAFETY side setting

CUT-IN equals CUT-OUT minus CUT-IN equals CUT-OUT plus

DIFFERENTIAL DIFFERENTIAL

Example: Example:

CUT-OUT – DIFF. = CUT-IN CUT-OUT + DIFF. = CUT-IN

8 bar (116 psi) – 2 bar (29 psi) = 6 bar (87 psi) 4 bar (58 psi) + 1 bar (15 psi) = 5 bar (73 psi)

Adjustment

Control side setting Control side diff erential

Safety side setting

Note:

Remove lockplate before adjustment

Replace lockplate after adjustment (if desired)

1. Adjust range spindle to

desired CUT-OUT value

2. Adjust diff erential

spindle to desired

DIFFERENTIAL (DIFF.)

value

1. Adjust range

spindle to desired

CUT-OUT value.

2. DIFFERENTIAL (DIFF.)

is fi xed. Value printed

on scale plate.