pp2165 xp95 module 3
TRANSCRIPT
PP2165/2009/Issue 3
Module 3.1
Analogue Addressable Devices
36 Brookside Road, Havant, Hampshire, PO9 1JR Tel: +44 (0)23 9249 2412 Fax: +44 (0)23 9249 2754
Website: www.apollo-fire.co.uk Email: [email protected]
Training Module 3.1PP2165/2009/Issue 4
3
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
2
© Apollo Fire Detectors Limited 2004-2009
MODULE 3.1
XP95The XP95 range of products to operate on analogue addressable fire alarm systems incorporating the Apollo communications protocol. The range includes ionisation smoke detectors, optical smoke detectors, heat detectors, manual call points and other peripheral devices.
Smoke and Heat DetectorsXP95 Smoke detectors use the same detection chambers as their Series 65 counterparts but the measure of the properties they detect are reported to the control panel as an analogue value. They are addressed using an XPERT card (discussed in Module 3). The bases are connected to the two-core loop wiring via two terminals, L1 and L2. The incoming and outgoing connections are on the same terminals and therefore removing a detector will not create an open-circuit on the loop. Smoke and heat detectors have an alarm LED, remote output terminals and an electronic self-test (all operated via control panel software).
Heat detectors incorporate a single thermistor bead for temperature sensing. There is no rate-of-rise element in the heat detectors as this can be accommodated within the control equipment. The standard heat detector has an alarm temperature of 55°C and the high temperature version has an alarm temperature of 90°C (analogue value 55).
Manual Call PointsThe XP95 manual call point is designed to report an alarm analogue value of 64 on breaking the glass. It also has to be able to report an alarm condition instantaneously regardless of which loop device the panel is communicating with. It does this by means of a special mechanism known as the ‘priority interrupt’. Using this interrupt facility, the manual call point can send alarm pulses at any point in the loop communication.
Manual call points are available in various formats including a standard red FIRE version and a red waterproof version. In areas where accidental damage could occur they can be fitted with a protective flap. All versions are addressed by means of a 7-bit DIL-switch.
IsolatorThe isolator is not an addressable device. It is designed specifically to isolate sections of the loop wiring in the event of a short-circuit fault. If isolators were not fitted, then a single short-circuit could disable an entire loop of devices. The BS5839 requirement is that a single short-circuit fault should not disable more than one zone of detection. An analogue addressable loop may cover many zones. Under these circumstances an isolator should be fitted at every zone boundary. It is recommended that an isolator should be placed every 20 detectors or the equivalent load (Approximately 20mA).
The isolator is a voltage-sensing device. In the event that the voltage on either side of the isolator falls below 14 volts, the isolator trips into isolation.
From the non-isolating side of the isolator, the panel sees the isolator as an approximate 2.8KΩ resistor across the loop. The isolator pulses the short-circuit side every five seconds with a 50mA pulse. As soon as the isolator sees a low load on one of the pulses, it restores power to the loop.
The isolator is available either as a stand-alone isolator with its own base or as an isolating base, which is fitted to the ceiling with a detector mounted to it. This device can save on wiring.
Isolators are now included in the latest manual call points so a zone could be finished with a call point. They are also fitted in our range of interfaces and most loop sounders.
ContentsXP95 3
Smoke and Heat Detectors 3
Manual Call Points 3
Isolator 3
Interfaces 4
Switch Monitor 5
Mini Switch Monitor (Interrupt) 6
Mini Switch Monitor 7
Switch Monitor Plus 9
Zone Monitor 9
Input/Output Unit 11
Output Unit 11
Sounder Control Unit 12
Mains Switching Input/Output Unit 13
3-Channel I/O Unit 14
Beam Detectors 16
Loop-Powered Beam Detector 16
Intelligent Reflective Beam Detector 17
Flame Detector 20
Base Mounted Flame Detectors 21
Intelligent Base Mounted Triple IR Flame Detector 21
Intelligent Base Mounted UV Flame Detector 22
Intelligent Base Mounted UV/IR² Flame Detector 22
Training Module 3.1PP2165/2009/Issue 4
5
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
4
© Apollo Fire Detectors Limited 2004-2009
InterfacesApollo manufacture a range of interfaces designed to enable connection of various inputs and outputs to the analogue addressable loop. These inputs and outputs will all be associated with the fire alarm systems i.e. they could be conventional detection devices such as beam detectors, flame detectors, heat cables or High Sensitivity Smoke Detectors (HSSDs). On the output side they could be sounder circuits, extinguishing systems, plant shutdowns, fire doors or sending alarm signals to other forms of control equipment.
The interfaces come in three distinct housings, depending on type:
The standard interfaces are designed to be surface or flush-mounted to walls and consist of three parts: a backbox, a PCB and a protective cover. The PCB has an electronic circuit on one side and terminal blocks on the other.
The DIN-Rail versions clip to standard 35mm DIN-rails (DIN 46277) or are screwed to the base of a larger enclosure. These enable fire systems designers to determine the functions required and create multi-purpose interfaces for individual sites.
The switch monitor is available in two miniature versions: Mini Switch Monitor and Mini Switch Monitor (Interrupt). This ‘mini’ format means they can be incorporated into other equipment. The housing is 76 x 47 x 15mm and electrical connections are made via six flying leads.
Figure 1: Interface Enclosures (Standard, DIN-Rail and Mini)
Switch MonitorThe Switch Monitor and Mini Switch Monitor are designed to monitor devices with any combination of Fault, Fire and Pre-Alarm volt-free contacts. The devices themselves are functionally identical but are available in a standard and ‘mini’ version.
The devices report the status of the contacts by means of pre-set analogue value as follows:
Fault 4
Quiescent 16
Pre-Alarm 45-51
Alarm 64
The monitoring circuit is wired as follows:
The ‘fault’ contact should always be wired after the ‘fire’ and ‘pre-alarm’ contacts in the circuit so that an open fault contact will not disable the ‘fire’ contacts (‘fire’ should always override ‘fault’).
L1 (–ve)*
L2 (+ve)*
SW–SW+
20kΩ ±10% 1/3W
NORMALLYCLOSEDFAULT CONTACT
1kΩ 10kΩ
FIRE CONTACT
PRE-ALARMCONTACT
SWITCH MONITOR
XP95LOOP
XP95LOOP
Figure 3: Switch Monitor
* L1 & L2 are polarity insensitive, but, for the sake of consistency, it is recommended that L1 be kept negative
The status of the input circuit is indicated by two LEDs; red for ‘fire’ and yellow for ‘fault’. The ‘fire’ LED can only be lit on receipt of the command from the control panel, it does not illuminate automatically on closing the monitored ‘fire’ contact.
Typical applications are as an interface for conventional beam detectors, flame detectors and sprinkler flow switches. The ‘pre-alarm’ facility allows monitoring of high sensitivity smoke detection apparatus or any device where an alert signal is required as well as a full alarm.
The latest Mini Switch Monitor features as enclosure that can be fitted onto a DIN-Rail with a twist-click motion or mounted in a larger enclosure. It can also be mounted inside devices such as Manual Call Points.
Figure 2: New Mini Switch Monitor
Training Module 3.1PP2165/2009/Issue 4
7
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
6
© Apollo Fire Detectors Limited 2004-2009
Mini Switch Monitor (Interrupt)The Mini Switch Monitor (Interrupt) is only available in the ‘mini’ version and is designed to monitor equipment where a fast response is required. This is achieved by using the Apollo manual call point priority interrupt facility. The unit can monitor Fault and Fire contacts in exactly the same way as the standard Switch Monitors but does not have a Pre-Alarm facility.
The devices report the status of the contacts by means of pre-set analogue value as follows:
Fault 4
Quiescent 16
Alarm 64
The monitoring circuit is wired as follows:
The status of the input circuit is indicate by two LEDs: red for ‘fire’ and yellow for ‘fault’. The Fire LED can only be lit on receipt of the command from the control panel, it does not illuminate automatically on closing the monitored Fire contact.
This device can be used to interface a conventional manual call point to an XP95 system.
Mini Switch MonitorThe Mini Switch Monitor, part number 55000-760, monitors the state of one or more single-pole volt-free contacts and may be used in installations where space is limited. The unit also has a short-circuit isolator as standard.
The device reports the status of the contacts by means of pre-set analogue values as follows:
Fault 4
Quiescent 16
Pre-Alarm 45-51
Alarm 64
The monitoring circuit is wired as follows:
The fault contact should always be wired after the ‘fire’ and ‘pre-alarm’ contacts in the circuit so that an open ‘fault’ contact will not disable the ‘fire’ contacts (’fire’ should always override ‘fault’)
Figure 4: Mini Switch Monitor (Interrupt)
RED BLACK
YELLOW GREEN VIOLET WHITE
LINE 1* LINE 2*
XP95 LOOP REMOTE LED
FAULT CONTACT
20kΩ ± 10% W
FIRE CONTACT
470Ω
* L1 and L2 are polarity insensitive, but for the sake of consistency, it is recommended that L1 be kept negative
MINI SWITCH MONITOR (INTERRUPT)
1 / 3
RED LINE 2*BLACK LINE 1*YELLOW
GREEN
VIOLET +WHITE –
20kΩ± 10% 1/3 W
FIRECONTACT
FAULT CONTACT
1kΩ 10kΩ
PRE-ALARMCONTACT
REMOTE LED
* L1 and L2 are polarity insensitive, but, for the sake of consistency, it is recommended that L1 be kept negative
Figure 5: Mini Switch Monitor
32
1
45
6
L+ In/Out
L- In
L- Out
Alarm LED
+R
SW2
SW1
R1
R2
R3
D1
© Apollo Fire Detectors Limited 2007-2008/TP
Key
R1 Alarm 1KΩR2 Pre-Alarm 10KΩR3 End of Line 20KΩD1 Optional Remote LED Part no 53832-070
Figure 6: New Mini Switch Monitor Wiring diagram
Training Module 3.1PP2165/2009/Issue 4
9
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
8
© Apollo Fire Detectors Limited 2004-2009
Switch Monitor PlusThe Switch Monitor Plus is an enhanced version of the Switch Monitor with additional features. The unit has a 30 second delay set by the eighth bit of the DIL-switch. This means that the device is suitable for monitoring flow switches which, by their very nature, have a tendency to “chatter” and have the potential for false alarms. The device also has an opto output which provides a means to reset a monitored detector.
The devices report the status of the contacts by means of pre-set analogue value as follows:
Fault 4
Quiescent 16
Pre-Alarm 45-51
Alarm 64
The monitoring circuit as wired as follows:
Figure 9: Switch Monitor Plus
L1 (–ve)*
L2 (+ve)*
OPTO –OPTO +
SW–SW+
20kΩ ±10% 1/3W
NORMALLYCLOSEDFAULT CONTACT
1kΩ 10kΩ
ALARM PRE-ALARM
R1 = 10kΩ1/4WD1 = IN4007TR1 = BC337RLY1 = 24V DC coil,
350Ω or greater
RLY1
R1
D1
TR1
+24V
0V
OPTO –
OPTO +
SWITCH MONITOR PLUS
XP95 LOOP
XP95LOOP
XP95LOOP
The status of the input circuit is indicated by two LEDs: red for ‘fire’ and yellow for ‘fault’. The Fire LED can only be lit on receipt of the command from the control panel, it does not illuminate automatically on closing the Fire contact.
Zone MonitorThe Zone Monitor is designed to monitor a zone of conventional detectors or manual call points. The detection circuit is fully monitored for short and open-circuit faults in the wiring and can incorporate ‘Active End-of-Line monitoring’ which enables detectors to be removed from their bases without disabling the remainder of the devices beyond it in the circuit. The unit is compatible with conventional intrinsically safe detectors when operated with a suitable galvanic isolator barrier. Because a barrier puts an additional 300Ω line impedance in the monitoring circuit, the sense windows of the zone monitor need to be altered accordingly. This is achieved by cutting a wire link on the PCB which accesses the IS operation of the unit.
The devices report the status of the contacts by means of the following pre-set analogue values:
Fault (o/c or s/c) 4
Quiescent 16
Alarm 64
The status of the input circuit is indicated by three LEDs
Red - indicates alarm condition (can only be operated on receipt os a command from the control panel.)
Green - indicates polling (flashes when the device is being communicated with)
Yellow - constant indicates short circuit on the loop wiring
- pulsing indicates a fault on the monitored circuit
The device is addressed using the first seven bits on an eight bit DIL switch. The eighth bit is used for setting the response type of the unit. Set to ‘1’ for fast response (MCP) and set to ‘0’ for normal (switch monitor).
12
3
45
6
Releasing Clip
© Apollo Fire Detectors Limited 2007-2008/TPFigure 7: Mini Switch Monitor on a DIN rail
© Apollo Fire Detectors Limited 2006-8/DJO/TP
1 2 3 4 5 6 7 8ON
0 1 0 1 11 1 0
Address 78 =
Example:
ON = 0
Fast
R
espo
nse
Figure 8: Mini Switch Monitor DIL switch
Typical application include are as an interface for conventional beam detectors, flame detectors and sprinkler flow switches. The pre-alarm facility allows monitoring of aspirating systems or any device where an alert signal is required as well as full alarm.
Using the ‘fast response’ setting allows the device to monitor conventional, non-standard call point onto the addressable loop using the priority interrupt.
Training Module 3.1PP2165/2009/Issue 4
11
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
10
© Apollo Fire Detectors Limited 2004-2009
Figure 10: Zone Monitor
L1 (–ve)*
L2 (+ve)*
Zone OP –ve
Zone OP +ve
XP95LOOP
XP95LOOP
ZONE MONITOR
* L1 and L2 are polarity insensitive but,for the sake of consistency, it is recommended that L1 be kept negative
The monitoring detector circuit is as follows:
The Zone Monitor is often used when an addressable system is installed on a site that already has a conventional system fitted. Instead of removing all the old detectors, they can be connected to the new system using the zone monitor.
Zone Monitorterminals
MCPSeries 60 detectorsin standard bases
6.2KΩEOL
OP –ve
OP +ve
Zone Monitorterminals
OP –ve
OP +ve
Capacitor
Series 60 detectorsin (Schottky) diode bases
Actice EOLdevice
MCP
Figure 11: Zone Monitor Outputs
Input/Output UnitThe Input/Output Unit provides a loop-powered changeover relay capable of switching up to 1 amp at 30 volts AC or DC. The relay provides both a normally open and a normally closed pair which may be utilised by the installer to operate fire alarm related apparatus and functions, such as fire doors, extinguishing systems and shutting down machinery. The unit has two inputs, one is a fully monitored input, capable of monitoring fault and fire contacts; the second is a logic input, which could be utilised to monitor a local supply.
This unit is also commonly used to interface conventional control panels onto an analogue addressable system.
The devices report the status of the contacts by means of the following pre-set analogue values:
Fault 4
Quiescent 16
Switch Closed Input bit 0 set to a ‘1’
Opto input high Input bit 1 set to a ‘1’
The status of the opto input is indicated by input bit ‘1’. If the input is low (<1 volt) then input bit 1 is set to a ‘0’. If the input is high (>4 volts) then input bit 1 is set to a ‘1’.
The wiring detail is as follows:
The relay is operated by changing output command bit 0 from 0 to 1.
Figure 12: Input/Output Unit
L1 (–ve)*
L2 (+ve)*
XP95LOOP
XP95LOOP
INPUT/OUTPUT UNIT * L1 and L2 are polarity insensitive but,for the sake of consistency, it is recommended that L1 be kept negative
RELAYOUTPUT
N/CCOMN/O
OPTIONAL MONITORING OFAN EXTERNAL VOLTAGE
<1v = logic 0 >4v = logic 1DO NOT EXCEED 35V
NOT POLARITY SENSITIVE
20kΩ± 10%, W1/3
NORMALLY CLOSEDFAULT CONTACT
4.7kΩ N/OINPUT CONTACT
OP
TOO
PTO
I/P +
I/P –
Output UnitA loop-powered addressable relay capable of switching up to 1 amp at 30V AC or DC is available.
Training Module 3.1PP2165/2009/Issue 4
13
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
12
© Apollo Fire Detectors Limited 2004-2009
Sounder Control UnitThe Sounder Control Unit is designed to power and control a circuit of conventional sounders with a maximum alarm load of 1 amp (the DIN-Rail version will accept an alarm load of 5 amps).
The device will report a fault to the control panel in the event of a short-circuit or open-circuit fault in the sounder circuit and also if there is a fault in the local power supply.
The device reports these conditions by means of the following pre-set analogue values:
Fault 4
Normal 16
The sounders are operated by sending the appropriate output command bits from the control panel:
• Thesoundersareoperatedcontinuouslybysendingoutputcommandbit0.
• Thesoundersareoperatedinpulsedmode(1secondon,1secondoff)bysendingoutputcommand bit 1.
The device has two additional features which can be incorporated by the system:
• Agroupaddressisusedbythesoundercontrolunit.Thismeansthatanumberofunitscanbe operated by a single command to a common group address. The group address is set on a second 4 bit DIL-switch.
• Synchronisationofthepulsedoutputsonthesoundercontrolunitsisachievedbypollingaddress 0 just prior to energising the sounders. The sounders may need re-synchronising if they are operated for a significant length of time (over 1 hour).
Figure 13: Sounder Control Unit
L1 (–ve)*
L2 (+ve)*
XP95LOOP
SOUNDER CONTROL UNIT
* L1 and L2 are polarity insensitive but,for the sake of consistency, it is recommended that L1 be kept negative
N/C
COM
N/O
SO
UN
DE
R +
SO
UN
DE
R –
FUSEVex
–
Vex
+
LOCAL POWERSUPPLY
10kΩEOL
FAULTINPUT
SOUNDERS WITH
POLARISINGDIODES
NORMALLYCLOSEDFAULT
CONTACT
FAULT INPUTNOT USED
(WIRE LINK MUST BE FITTED)
NORMALLY OPENFAULT CONTACT
Mains Switching Input/Output UnitThe Mains Switching Input/Output Unit provides a loop-powered changeover relay capable of switching up to 5 amp at 250 volts AC or 2 amp at 48 volts DC. The relay provides both a normally open and a normally closed pair which may be utilised by the installer. The unit has two inputs, one of which is a fully monitored input capable of monitoring fault and fire contacts, the second is a logic input which could be utilised to monitor a local supply.
The devices report the status of the contacts by means of the following pre-set analogue values:
Fault 4
Normal 16
Switch Closed Input bit 0 set to a “1”
The wiring detail is as follows:
Figure 14: Mains Switching Input/Output Unit
N/O COMN/C
I/P +
I/P –
I/P +I/P –
+L+L–L–L
XP95 LOOP
+ –
+ –
Live mains conductors
470Ω∗
N/O INPUTCONTACT
20KΩEOL
∗The resistor value may be anywhere within the range 200Ω to 11kΩ
The relay is operated by changing output command bit 0 from 0 to 1.
A DIN-Rail version of this device will be available over the coming months.
Training Module 3.1PP2165/2009/Issue 4
15
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
14
© Apollo Fire Detectors Limited 2004-2009
3-Channel I/O UnitThis device has three volt-free, single pole, changeover relay outputs rated at 1A at 30 volts and three monitored switch inputs all at one address. There are versions of this device available with built-in bi-directional short-circuit isolator. It can be obtained as a PCB only or in a 250 x 175 x 75mm plastic enclosure. This device would be used where multiple inputs and outputs are required i.e. at building lift control.
CHANNEL 3 RELAY 3
CHANNEL 2 RELAY 2
CHANNEL 1 RELAY 1
1 2
1 2 3
1 2 3
3
CHANNEL 3
CHANNEL 2
CHANNEL 1
4
N/O
COM
N/C
N/O
COM
N/C
N/O
COM
N/C
XP95 LOOP ADDRESS SWITCH
–L1OUT
–L1IN
+L2
+L2
LEDs 1. SWITCH CLOSED 2. FAULT 3. RELAY ON 4. ISOLATOR
IP3+
IP3–
IP2+
IP2–
IP1+
IP1–
N/C FAULT CONTACT
EOL 20kΩ
4.7kΩ
N/O ALARM CONTACT
Figure 15: 3-Channel Input/Output Unit
Start
OutputRequired?
Fast ResponseRequired?
Delay InputRequired?
Limited Space
UseSwitchMonitor
UseMini-Switch
Monitor
UseSwitch
Monitor Plus
UseMini-Switch
Monitorwith Interrupt
Input alsoRequired?
UseOutput
Unit
UseInput/Output
Unit
Yes
No
Yes
Yes
Yes
Yes
No
No
No
No
Interface Selection Chart
The Zone Monitor Unit and Sounder Control Unit are interfaces whichhave a dedicated function and do not appear on the above chart.
Training Module 3.1PP2165/2009/Issue 4
17
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
16
© Apollo Fire Detectors Limited 2004-2009
Beam DetectorsApollo beam detectors have been designed to protect large open spaces such as atria, museums, churches, warehouses and factories or anywhere ceiling heights exceed 10m up to 25m (life protection) 40m (property)
Loop-Powered Beam DetectorThe Loop-powered Beam Detector is made up of three main parts: the transmitter, which projects a beam of infra-red light; the receiver, which registers the light and produces an electrical signal and the interface, which processes the signal and generates alarm or fault signals.
Figure 16: Loop-Powered Beam Detector
receiver
light cone
transmitter
Side view of transmitter and receiver End view of receiver
The beam detector has been developed from designs that have been well proven in countless fire protection systems. A major advance, however, is that the beam detector is loop-powered and needs no separate 24V supply.
The beam detector operates as a conventional detector, in that it changes to the alarm state at a pre-set level of smoke obscuration, but is able to communicate with the control panel and return information when interrogated.
The Loop-Powered Beam Detector is set on commissioning to one of four levels of obscuration, determined with reference to the environment in which it is installed. The levels are 25%, 35%, 50% and 65% where 25% is the most sensitive and 65% the least sensitive level.
A DIL-switch on the interface is used to set the obscuration level.
Up to 100m can be converted using this beam from the transmitter to receiver with 7.5m either side, therefore a total coverage of 1500m² can be achieved.
Things to look out for when using beam detectors:
1. Make sure the components of the beam detector are fitted to stable, solid surfaces. 2. Make sure there is a clear 'line of sight' between the TX, RX and any reflectors used. 3. Ensure no direct sunlight falls onto the receiver.
Intelligent Reflective Beam DetectorThe Intelligent Reflective Beam Detector is a compact detector for detecting smoke in large, open areas such as atria, warehouses, theatres and churches. The transmitter and receiver form a single unit mounted to a wall of the building. A reflector, which returns the IR beam from the transmitter to the receiver, is mounted on the opposite wall. In the event of smoke partially obscuring the light, an imbalance between the transmitted and received light will occur. On interrogation by the control panel the detector will then transmit an alarm value.
The intelligent reflective beam detector is supplied in two versions: one for use at distances of 5–50m from detector to reflector and the other for distances of 50–100m.
Figure 17: Intelligent Reflective Beam Detector
5 - 50m
50 - 100m
Training Module 3.1PP2165/2009/Issue 4
19
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
18
© Apollo Fire Detectors Limited 2004-2009
The detector is factory set to a beam obscuration of 35% which is the best setting for most factories and warehouses. The setting can be changed to 25% for offices and clean areas such as theatres or to 50% for hostile areas such as mills or foundries.
The detector compensates automatically for gradual contamination of the lenses in order to avoid false alarms.
The detector is non-latching and resets 30 seconds after an alarm event ceases and in 3 seconds after the removal of a fault.
The intelligent reflective beam detector is loop-powered and requires no external power supply. Each beam detector draws approximately 9mA from the analogue addressable loop and, unless proven by calculation, it is recommended that no more than ten beam detectors be powered from each loop.
The reflective beam detector responds to output bits from the protocol as follows:
• Whenoutputbit2issettologic1ontwoormoreconsecutivepollingstheredalarmLEDisilluminated.
• Whenoutputbit1issettologic1ontwoormoreconsecutivepollings,thebeamdetectorcarries out a self-test. If the test is successful, an analogue value of 64 is transmitted to the control panel. If a value less than 54 is transmitted, the self test has failed and the beam detector should be inspected.
• Outputbit0isnotused.
The beam detector returns a pre-set analogue value corresponding to its status. These values are defined below.
Analogue Value Significance
0 Microprocessor fault
1 Sensor fault
2 Prism (reflector) targeting mode
3 Alignment mode
4 General fault warning
5 ‘Signal High’ fault
6 Contamination compensation limit reached
20 Alignment drift negative
25 Detector normal
30 Alignment drift positive
32 Contamination compensation level low (40%)
33 Contamination compensation level medium (60%)
34 Contamination compensation level high (80%)
45–54 Pre–alarm values
64 Alarm
Auto-Aligning Beam Detector with Laser Alignment#
The Auto-Aligning beam detector is a compact detector for detecting smoke in large open areas such as warehouses, theatres, churches and sports centres. It comprises of a ground level Controller, a Detector Head with an operating range of 8m-50m and a single prism. The operating range of each detector head can be increased up to 100m by using an Extension Kit, which comprises three additional prisms. For large areas, up to a maximum of four separate detector heads can operate off of one controller.
A built-in laser provides rapid initial alignment and thereafter the detector head will continuously automatically align and compensate for any building movement. The status of each detector can be monitored through the Controller which is sited at ground level to avoid the need for expensive lifting gear. The detector head operates both as a transmitter and a receiver. A well-defined IR beam is projected to a prism mounted on the opposite wall, which is reflected back to the receiver. In the event of smoke partially obscuring the light an imbalance between the transmitted and received light will occur. On interrogation by the control panel the detector will then transmit an alarm value. To protect distances from 50m to 100m, four prisms are required.
FEATURES
•GroundlevelControlleravoidsexpensiveliftinggear
•Automaticcompensationforbuildingmovement
•Laserassistedalignmentforquickinstallation
•Upto4detectorsperController
•Eachdetectoradjustsfrom8mto100m
•EN54:12approved
The detector is factory set to a beam obscuration of 35% which is the best setting for most factories and warehouses. The setting can be changed to 25% for offices and clean areas such as theatres or to 50% for hostile areas such as mills or foundries.
The detector compensates automatically for gradual contamination of the lenses in order to avoid false alarms.
The detector is non-latching and resets 30 seconds after an alarm event ceases and in 3
Training Module 3.1PP2165/2009/Issue 4
21
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
20
© Apollo Fire Detectors Limited 2004-2009
seconds after the removal of a fault.
The Auto-Aligning Beam Detector requires a 14 to 28V DC power supply. It can be interfaced onto the Apollo addressable loop using an Apollo Switch Monitor Unit (55000-843) or Mini Switch Monitor (55000-760).Power to the detector can be supplied using an EN54 approved power supply or directly from the addressable loop - please refer to the Quick Start Guide supplied with the product for details.
A fault is indicated by the amber LED flashing every 10 seconds.
If the drift compensation function has reached its limit the amber LED flashes once every 10 seconds and an error code is displayed on the ground level Controller. The detector will continue to function but maintenance procedures should be carried out at the earliest opportunity.
Training Module 3.1PP2165/2009/Issue 4
23
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
22
© Apollo Fire Detectors Limited 2004-2009
The beam detector may return a pre-alarm value before a full alarm condition occurs. The analogue value depends on the smoke density and the set obscuration level.
Analogue value returned
Actual obscuration at set obscuration level of
25% 35% 50%
45 16 23 33
46 16 26 34
47 17 27 35
48 18 28 36
49 19 29 38
50 20 30 40
51 21 31 42
52 22 32 44
53 23 33 46
54 24 34 48
Table 1: Analogue Value and Set Obscuration Level
Input bits 2, 1 and 0 reflect the status of the corresponding output bit.
The type code of the reflective beam detector is 101 01 (bits 210 43).
The amber LED flashing once a second indicates a fault.
If the drift compensation function has reached its limit the amber LED flashes once every 2 seconds. The detector will continue to function but maintenance procedures should be carried out at the earliest opportunity.
The Firebeam
The Firebeam reflective beam detector is a conventional device. Because it draws so little current (3MA), it can be powered directly from the loop. A switch monitor would be required to pick up fire and fault conditions. One of the biggest advantages of the Firebeam is the self-alignment, so when buliding movement occurs the beam re-aligns itself.
Flame DetectorThe Infra-Red (IR) Flame Detector is designed for use where open, flaming fires may be expected. It is sensitive to low-frequency, flickering infra-red radiation emitted by flames during combustion. False alarms due to such factors as flickering sunlight are avoided by a combination of filters and signal processing techniques
The flame detector is loop-powered and needs no external power supply. It is connected to a control panel using either the XP95 or Discovery protocol. A remote LED alarm indicator may be connected to the flame detector.
In quiescent condition i.e. in the absence of a flame, the detector returns an analogue value of 25. When a flame is visible, the detector signals an alarm by increasing the analogue value returned to 55, usually within 1.5 seconds. The analogue value may continue to rise until it reaches a pre-set maximum of 64.
In the alarm state, the flame detector latches for 20 seconds, with the analogue value decreasing to 25 once the flame is no longer detected.
Flame detectors are used when detection is required to be:
• unaffectedbyconventioncurrents,draughtsorwind
• tolerantoffumes,vapours,steam,dustandmist
• responsivetoaflamemorethan25metresaway
• fastreacting
Typical applications examples are:
• agriculture–grainandmaltprocessing,animalfeedmanufacture
• aircrafthangars
• automotiveindustry–spraybooths,partsmanufacture
• chipboardandMDFmanufacture
• metalfabrication
• powerplants
• transformerstations
Figure 18: Flame Detector
Height
Width
Length
Training Module 3.1PP2165/2009/Issue 4
25
© Apollo Fire Detectors Limited 2004-2009
Training Module 3.1PP2165/2009/Issue 4
24
© Apollo Fire Detectors Limited 2004-2009
BASE MOUNTED FLAME DETECTORS
FUNCTIONThe Intelligent Base Mounted Flame Detectors are designed to protect areas where open fires may be expected.
DETECTOR TYPES
Three types of flame detector are availiable:
1. UV Flame Detector 55000-022 2. UV/IR2 Flame Detector 55000-023 3. Triple IR Flame Detector 55000-024
FEaTURES
UV
The detector is sensitive to ultraviolet radiation emitted by flames during combustion. Since it requires only UV radiation the detector responds even to stationary flames with no flicker like cigarette lighters and blue gas flames.
The detector is set to respond to ultraviolet radiation (185−260nm) emitted by almost all flames, including those invisible to the naked eye, e.g. hydrogen fires.
The detector has a single UV sensor with a narrow spectral response in order to discriminate between flames and most spurious sources of radiation and is designed for internal fully enclosed areas.
Caution: The detector will also detect electrical discharges from lightning or arc welding.
UV/Dual IR
The detector is sensitive to ultraviolet and low-frequency, flickering infra-red radiation emitted by flames during combustion. Since it requires both UV and IR radiation the detector can operate in applications where a basic single UV or single IR detector would be inappropriate. The detector
Figure 19: Base Mounted Flame Detector
is set to respond to ultraviolet (185−260nm) and low-frequency flickering infra-red (0.75−2.7µm) radiation at 1−15Hz in order to detect all flickering flames, including those invisible to the naked eye, e.g. those emitted by hydrogen fires. The detector has one UV and two IR sensors responding to different wavelengths in order to discriminate between flames and spurious sources of radiation. False alarms due to electrical discharges from lightning or arc welding and flickering sunlight are minimised by combining the UV/IR signals.
Triple IR
The detector is sensitive to low-frequency, flickering infra-red radiation emitted by flames during combustion. Since it responds to flickering radiation the detector can operate even if the lens is contaminated by a layer of oil, dust, water-vapour or ice. The detector is set to respond to low-frequency radiation at 1−15Hz (0.75−2.7µm) in order to detect all flickering flames, including those invisible to the naked eye, e.g. those emitted by hydrogen fires. The detector has three IR sensors that respond to different IR wavelengths in order to discriminate between flames and spurious sources of radiation. False alarms due to factors such as flickering sunlight are avoided by a combination of filters and signal processing techniques.
aPPlICaTIONS FOR FlamE DETECTORS
UV
UV Flame detectors are used when detection is required to be unaffected by convection currents, draughts or wind. These include engine rooms in ships, factories affected by draughts or wind and warehouses.
They are fast reacting and respond to a flame more than 25m away. The UV flame detector is affected by arc welding, electrical sparks, lightning, nuclear radiation and UV light sources. For applications where these phenomena are present a UV flame detector should not be used.
UV/Dual IR
This detector is not affected by any of the sources mentioned above. They are used in aircraft hangers, generator rooms (diesel and gas turbines) and paintworks.
TRIPlE IR
The triple IR flame detector is also fast reacting but is also tolerant of fumes, vapours, steam, dust and mist, while being unaffected by the phenomena listed above. It may, however, be affected by modulated IR radiation. Triple IR flame detectors are used in waste handling, colour printing and paper manufacturing.
ElECTRICal CONSIDERaTIONS
The detectors are loop powered and need no external supply. A remote LED alarm indication may be connected to the flame detector.
Training Module 3.1PP2165/2009/Issue 4
26
© Apollo Fire Detectors Limited 2004-2009
DImENSIONS
100mm x 40mm (Detector only)100mm x 48mm (Detector and base)
WEIghT Detector 150g Detector and base 210g
aCCESSORIESA portable Flame Detector Test unit is available, part number 29600-226.
An adjustable mounting bracket is also available, part number 29600–458.
Please answer the following questions:
1. Which product uses 'interrupt'?
2. What are isolators used for?
3. Which two interface products are packaged in the 'mini' format?
4. Name three typical applications for a flame detector?
5. Name the three main parts of the beam detector?
6. What distances do the two versions of the Reflective Beam Detector cover?
7. What interface should be used to monitor or activate the following:
a) Flow switch
b) Conventional manual call point
c) Door retainers
d) 12V sounders
e) Plant shutdown (240V)
f) Smoke dampers
g) Conventional detectors
h) Plant shutdown 24V
i) Beam detectors (fire, pre-alarm & fault)
j) Lift control (shut down, maintenance & return to ground)
k) Aspirating system
Module 3.1: XP95 Test