power system fault: detection and prevention
DESCRIPTION
Power System Fault: Detection and Prevention. Ryan Habib Wilkes University. Huy Tran Richland College. Purpose. Construct a simple data acquisition system to mimic the measuring of an arc flash incident. Arc Flash. - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/1.jpg)
1
Power System Fault: Detection and Prevention
Ryan HabibWilkes University
Huy TranRichland College
![Page 2: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/2.jpg)
Purpose Construct a simple data acquisition
system to mimic the measuring of an arc flash incident
2
![Page 3: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/3.jpg)
Arc Flash A rapid release of
energy in the form of an electrical explosion that results from a low impedance connection between lines of different voltage or phases
3
![Page 4: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/4.jpg)
Arc Flash damage Most burns from
electrical accidents are a result of arc flash
Temperatures can reach up to 20,000⁰C
Most occurrences are in industrial settings due to required power levels
4
![Page 5: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/5.jpg)
Arc Flash Experimentation
5
Analog Devices7B-47-K-04-1(Build-in CJC)
NI cRio: 16 Differential AI16 TTL Compatible DI/O
Fiber Optic Internet Connection
AD210 + MOVSlug calorimeters and Pressure sensors
Experimental DAQ System
![Page 6: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/6.jpg)
Arc Flash Simulation
6
![Page 7: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/7.jpg)
7
![Page 8: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/8.jpg)
SCADA (Supervisory Control And Data Acquisition) Systems
Versatile industrial control system Components
SensorRemote terminal unitCentral computer
8
![Page 9: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/9.jpg)
Sensors Reads a signal from a physical property
and converts it into one usable by a control system
Photoresistor Hall effect sensor
9
![Page 10: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/10.jpg)
Thermocouple Type K thermocouple
Produces output voltage dependent on temperature
Made of two metals with different conducting properties
Temperature range of -200⁰C to 1350⁰C
10
![Page 11: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/11.jpg)
Types of ThermocouplesType Materials TraitsB/R/S Platinum-Rhodium Low Sensitivity, High
Cost
E Chromel-Constantan High Sensitivity, Non-metallic
J Iron-Constantan Low Range, High Sensitivity
K Chromel-Alumel Inexpensive, Versatile, Reliable
N Nicrosil-Nisil More stable in high-energy environments
T Copper-Constantan Very Stable, especially at lower temperatures
11
![Page 12: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/12.jpg)
Analog to Digital Conversion
7B47 Signal Conditioning Module Successive Approximation ADC
12
![Page 13: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/13.jpg)
Data Logger Records digital data from the sensors Easily connected to other machines to
display information in real time
13
![Page 14: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/14.jpg)
GL800 Simultaneously displays and records
data from up to 20 inputs
14
![Page 15: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/15.jpg)
LabVIEW Large quantity of functions for data
acquisition, signal conditioning, and data analysis purposes
Extensive support for accessing instrumentation hardware
15
![Page 16: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/16.jpg)
System Setup Seven thermocouples were each
connected to their own 7B47 signal conditioning module
Each module was connected to an input of the GL800
USB/Ethernet cable connected GL800 to computer
16
![Page 17: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/17.jpg)
Test Process Place thermocouple in water to be
measured Send digital pulse to trigger the GL800
data recording Connect computer to GL800 to record
data on the computer Convert data from GL800 from voltage
to temperature
17
![Page 18: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/18.jpg)
Setup
Internet (Wireless or LAN)
7B47
7B47
7B47
7B47
7B47
7B47
7B47
7B47
+ - + -+ -+ -+ -+ -+ -+ -
CH1 CH4 CH5 CH6 CH7 CH8CH3CH2
Control & Monitor System
Communication System
Data Acquisition & Logger System
A/D Converter Equipment & Protection System
Industrial & Commercial Power Grid
DAQ System Utilized in Power System
18
![Page 19: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/19.jpg)
19
![Page 20: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/20.jpg)
Results: Change from Air to Hot Water
0 0.5 1 1.5 2 2.5 3 3.5 40
10
20
30
40
50
60
70
Air to Hot Water
Thermocouple 1Thermocouple 2Thermocouple 3Thermocouple 4Thermocouple 5Thermocouple 6Thermocouple 7
Time (s)
Tem
pera
ture
(oC)
20
![Page 21: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/21.jpg)
Results: Change from Air to Hot Water (Average)
0 0.5 1 1.5 2 2.5 3 3.5 40
10
20
30
40
50
60
70
Air to Hot Water
average
Time (s)
Tem
pera
ture
(oC)
21
![Page 22: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/22.jpg)
Results: Change from Air to Cold Water
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
15
20
25
30
Air to Cold Water
Thermocouple 1Thermocouple 2Thermocouple 3Thermocouple 4Thermocouple 5Thermocouple 6Thermocouple 7
Time (s)
Tem
pera
ture
(oC)
22
![Page 23: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/23.jpg)
Results: Change from Air to Cold Water (Average)
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
15
20
25
30
Air to Cold Water
average
Time (s)
Tem
pera
ture
(oC)
23
![Page 24: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/24.jpg)
Results: Change from Hot Water to Air
0 1 2 3 4 5 60
10
20
30
40
50
60
Hot Water to Air
Thermocouple 1Thermocouple 2Thermocouple 3Thermocouple 4Thermocouple 5Thermocouple 6Thermocouple 7
Time (s)
Tem
pera
ture
(oC)
24
![Page 25: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/25.jpg)
Results: Change from Hot Water to Air (Average)
0 1 2 3 4 5 60
10
20
30
40
50
60
Hot Water to Air
average
Time (s)
Tem
pera
ture
(oC)
25
![Page 26: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/26.jpg)
Results: Change from Cold Water to Air
0 0.5 1 1.5 2 2.5 3 3.5 40
2
4
6
8
10
12
14
16
18
Cold Water to Air
Thermocouple 1Thermocouple 2Thermocouple 3Thermocouple 4Thermocouple 5Thermocouple 6Thermocouple 7
Time (s)
Tem
pera
ture
(oC)
26
![Page 27: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/27.jpg)
Results: Change from Cold Water to Air (Average)
0 0.5 1 1.5 2 2.5 3 3.5 411.5
12
12.5
13
13.5
14
14.5
15
15.5
Cold Water to Air
Average
Time (s)
Tem
pera
ture
(oC)
27
![Page 28: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/28.jpg)
Results: Change from Hot Water to Cold Water
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
15
20
25
30
35
40
45
50
Hot Water to Cold Water
Thermocouple 1Thermocouple 2Thermocouple 3Thermocouple 4Thermocouple 5Thermocouple 6Thermocouple 7
Time (s)
Tem
pera
ture
(oC)
28
![Page 29: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/29.jpg)
Results: Change from Hot Water to Cold Water (Average)
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
15
20
25
30
35
40
45
Hot Water to Cold Water
average
Time (s)
Tem
pera
ture
(oC)
29
![Page 30: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/30.jpg)
Results: Change from Cold Water to Hot Water
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
15
20
25
30
35
40
45
50
Cold to Hot Water
Thermocouple 1Thermocouple 2Thermocouple 3Thermocouple 4Thermocouple 5Thermocouple 6Thermocouple 7
Time (s)
Tem
pera
ture
(oC)
30
![Page 31: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/31.jpg)
Results: Change from Cold Water to Hot Water (Average)
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
15
20
25
30
35
40
45
50
Cold to Hot Water
average
Time (s)
Tem
pera
ture
(oC)
31
![Page 32: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/32.jpg)
Results: Change from Adding Hot Water to Cold Water
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
15
20
25
30
Adding Hot Water to Cold Water
Thermocouple 1Thermocouple 2Thermocouple 3Thermocouple 4Thermocouple 5Thermocouple 6Thermocouple 7
Time (s)
Tem
pera
ture
(oC)
32
![Page 33: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/33.jpg)
Results: Change from Adding Hot Water to Cold Water (Average)
0 0.5 1 1.5 2 2.5 3 3.5 40
5
10
15
20
25
30
Adding Hot Water to Cold Water
average
Time (s)
Tem
pera
ture
(oC)
33
![Page 34: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/34.jpg)
Data Analysis System did a solid, yet unspectacular,
job of reading changes in water temperature
Variance in quality of measurements throughout the different tests
Could be attributed to variety of factors, including low sample rate and lack of memory
34
![Page 35: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/35.jpg)
Comparisons with LabVIEW
Using LabVIEW would’ve solved the issues with sample rate and memory
Interface is much less intuitive Weeks/months to master skills
necessary for this type of task
35
![Page 36: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/36.jpg)
Conclusion The DAQ system was able to measure
changes in temperature in a relatively effective manner
The components in the system are versatile enough to be used in a wide array of situations
For these specific tests, a data logger with a higher sampling rate, along with a sensor with a more narrow range, would have been more effective
36
![Page 37: Power System Fault: Detection and Prevention](https://reader036.vdocuments.mx/reader036/viewer/2022062410/5681637f550346895dd460fc/html5/thumbnails/37.jpg)
Acknowledgements Dr. Wei-Jen Lee Zhenyuan Zhang Zhaohao Ding The University of Texas at Arlington National Science Foundation
37