power system control

18
11 June 2022 Delft University of Technology Electrical Power System Essentials ET2105 Electrical Power System Essentials Prof. Lou van der Sluis Power System Control

Upload: elle

Post on 14-Jan-2016

84 views

Category:

Documents


4 download

DESCRIPTION

Power System Control. ET2105 Electrical Power System Essentials. Prof. Lou van der Sluis. Introduction (1). The customer expects electrical power at constant frequency and voltage The system load changes continuously Electricity can not be stored in large quantities - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Power System Control

21 April 2023

DelftUniversity ofTechnology

Electrical Power System Essentials

ET2105 Electrical Power System EssentialsProf. Lou van der Sluis

Power System Control

Page 2: Power System Control

25. Power System Control | 18

Electrical Power System Essentials ET2105

Introduction (1)

• The customer expects electrical power at constant frequency and voltage

• The system load changes continuously

• Electricity can not be stored in large quantities

• Maintaining the balance between generation and consumption

Page 3: Power System Control

35. Power System Control | 18

Electrical Power System Essentials ET2105

Introduction (2)

• The active power balance is controlled by generators

• Another method is load shedding

• The reactive power balance is controlled by generators and static components

• The synchronous generator plays an important role

Page 4: Power System Control

45. Power System Control | 18

Electrical Power System Essentials ET2105

Increase of Active Power Consumption

• Kinetic energy in the rotating parts of the generator and turbine are 200 MJ

• Suddenly a 10 MW load is connected. What happens to the frequency?• In 1 second the load consumes 10 MJ more active power P• The frequency will drop to 48.7 Hz

f1 = 50 Hz (3000 RPM)

Page 5: Power System Control

55. Power System Control | 18

Electrical Power System Essentials ET2105

10 kV system:P = 2 MW; cos φ = 0.9Xgen = 3 Ω

This results in:I = 128 A ∠-26°Q = 969 kvar

• Suddenly the load consumes Q = 1.5 Mvar and P remains at 2 MW. What happens?• The power factor drops to 0.8• The current becomes I = 146 ∠-37°• The terminal voltage drops with 100 V

Increase of Reactive Power Consumption (1)

Page 6: Power System Control

65. Power System Control | 18

Electrical Power System Essentials ET2105

• P remains 2 MW• Q increases from 969 kvar 1.5 Mvar• I increases from 128 A ∠-26° 147 A ∠-37°• V drops with 100 V

Increase of Reactive Power Consumption (2)

Page 7: Power System Control

75. Power System Control | 18

Electrical Power System Essentials ET2105

Increase of Reactive Power Consumption (3)

Page 8: Power System Control

85. Power System Control | 18

Electrical Power System Essentials ET2105

Increase of Reactive Power Consumption (4)

• Conclusion:• The voltage depends on the reactive power• The angle of transmission depends on the active power

Page 9: Power System Control

95. Power System Control | 18

Electrical Power System Essentials ET2105

Some Important Conclusions

• The frequency is a common parameter throughout the system

• The voltage is controlled locally

• The control mechanism for P (rotor angle) and Q (voltage amplitude) operate more or less separately

Page 10: Power System Control

105. Power System Control | 18

Electrical Power System Essentials ET2105

The Primary Control• Speed governor control of a generating unit:

• Speed governor characteristics:

Page 11: Power System Control

115. Power System Control | 18

Electrical Power System Essentials ET2105

The Secondary Control or Load Frequency Control

Power exchange between three control areas

a) The original (scheduled) situationb) Incremental generation after losing 400 MW of generation in

control area B

Page 12: Power System Control

125. Power System Control | 18

Electrical Power System Essentials ET2105

Voltage Control and Reactive Power (1)

Automatic voltage control

Page 13: Power System Control

135. Power System Control | 18

Electrical Power System Essentials ET2105

Voltage Control and Reactive Power (2)

Tap-changing transformer

Page 14: Power System Control

145. Power System Control | 18

Electrical Power System Essentials ET2105

Voltage Control and Reactive Power (3)

Capacitor banks

Courtesy of TenneT TSO B.V.

Page 15: Power System Control

155. Power System Control | 18

Electrical Power System Essentials ET2105

Reactive Power Injection

Current through a Thyristor Controlled Reactor

Static Var Compensator (SVC)

Page 16: Power System Control

165. Power System Control | 18

Electrical Power System Essentials ET2105

Controlling Active Power FlowsThe Phase Shifter

Phasor diagram of the phase shifter

Page 17: Power System Control

175. Power System Control | 18

Electrical Power System Essentials ET2105

Controlling Reactive Power Flows (1)A transmission line with a series capacitor

Page 18: Power System Control

185. Power System Control | 18

Electrical Power System Essentials ET2105

Controlling Reactive Power Flows (2)Thyristor-controlled series capacitor

TCSC reactance as a function of the Thyristor firing angle