power grid protection - nebula.wsimg.com
TRANSCRIPT
Page | 0
October 22, 2013
Submitted by: Mihnathul Munthaha Neerulpan
Student ID# 999495810
Power Grid Protection
Index Page
1 Transformer Protection 1
2 Generator Protection 7
3 Motor Protection 12
4 Transmission Line Protection 15
5 Bus Protection 24
6 Appendix 27
7 References 30
Page | 1
Here we are going to discuss the principles of basic protection schemes for main
components (equipment)-Transformer, Generator, Motor, Line and Bus bar- in the power
grid. (A.C system)
1. Transformer Protection
Condition Protection
Internal
Winding phase-phase
Phase-ground fault
87T(differential)
51,51N(overcurrent)
87RGF(restricted ground fault)
Winding inter-turn fault 87T,
Buchholz relay
Core insulation failure, shorted
lamination
87T ,
Buchholz relay,
Tan fault 87T,
Buchholz relay and tank ground
protection relay
Over fluxing 24(volt/Hz)
External
Overload 49(thermal)
Overvoltage 59(overvoltage)
External system short circuit 51,51G(time overcurrent
50,50G(Instantaneous overcurrent)
Major Protection Schemes for Transformers
Differential protection
o Modified/Percentage/Biased/ differential protection
Overcurrent protection
Zero sequence over current protection
Ground fault protection
Thermal protection
Over fluxing protection
1.1 Transformer Differential Protection Scheme
It is based on the fact that any fault within electrical equipment would cause the
current entering it to be different from the current leaving it. Hence it works for internal
faults only.
Simple representation of a differential protection scheme is sown in Fig.1.1. If there
is an internal fault, the CT secondary currents are not matched and hence the differential
current is not zero. This causes the overcurrent element to pick up and operate the
circuit breakers to isolate the transformer. If there is no internal fault in the transformer,
zero current flows through the differential overcurrent element.
Page | 2
Fig.1.1Simple representation of differential protection scheme of transformers.
Let a transformer with turn ratio is to be protected, In order to compare the
measured primary and secondary currents of the transformer CT must have matched turn ratio.
Let’s find the relation between transformer and CT turn ratio. Considering Fig.1.1,
Transformer turns ratio given by
The corresponding CT ratio given by
Then, Current in CT- 1 primary
Current in CT- 1 secondary =
Current in CT- 2 primary =
Current in CT- 2 secondary
If there is no fault, then with proper connections account for the CT polarity, we should
obtain circulatory current through CT secondary (i.e. current measured at primary of first CT and
secondary of second CT must be same).
Hence
1.1.2. Percentage/Biased/Modified Differential Protection
Differential protection discussed above has the following challenges.
The primary of transformer will carry no load current even when the secondary is open
circuited. This will lead to differential current.
It is not possible to exactly match the CT’s, this will also lead to differential currents
under healthy conditions.
To prevent the differential protection for picking up under such conditions, a percentage
differential protection scheme is used, in which a second coil known as restraining coil is also
there. This restraining coil makes the relay restrain from the small currents such as no load
current, differential current due to CT mismatch etc. Fig. 1.2 (a) shows the fundamental armature
- coils arrangement of the differential relay. Now let’s find the operating condition for this relay.
Page | 3
Fig.1.2. Percentage differential relay
Ampere-turns acting on the left-hand section of the restraining coil =
Ampere-turns acting on the right-hand section of the restraining coil =
Total ampere-turns acting on the restraining coil =
We have flux,
Noting that torque in an electromagnetic relay is proportional to the square of the flux, Torque
produced by the restraining coil = [
]
Where M is a constant of proportionality.
Restraining torque produced by control spring =
Total restraining torque, [
]
Similarly, operating torque is due to the current (or flux) through he operating coil and is given
by, [ ]
The relay trips if the operating torque is greater than the restraining torque.
i.e. when: [ ] [
]
(neglecting the restraining torque due to spring)
This can be written as
Where
Where accounts for the effect of spring.
i.e. The relay operates when:
Fig1.3 shows the percentage differential protection scheme for a three phase
transformer. Connect Δ side CT’s in Y and, the Y side CT’s in Δ. By doing so, the zero sequence
currents would be restricted within the CT Δ on the LV side and within the main winding Δ on
the HV side. Thus no zero sequence would flow through the restraint winding and the balance
maintained.
If the CT’s are connected as shown in fig.1.3, during normal operation , currents in the
restraint windings(R) are equal, such that there is no current in the operating winding(Op) of any
relay. Equating the current in the restraint windings we get the restraint on the various system
ratios as
√
√
Page | 4
Fig.1.3Percenage Differential Protection of three phase
transformer
1.2 Transformer Overcurrent Protection
This scheme uses both magnitude and phase angle of current for decision making. They
are commonly used for protection from phase and ground faults. Figure 1.4 shows two numbers
of phase-fault over-current relays and one ground-fault over-current relay for providing over-
current protection to the star-delta transformer. Such a scheme may serve the purpose of
providing either the primary protection for smaller transformers or the back-up protection for
bigger transformers
The pick-up value of the phase-fault over-current units is set such that they do not pick up
on maximum permissible overload, but are sensitive enough to pick up on the smallest phase
fault. The pick-up of the earth fault relay, on the other hand, is independent of the loading of the
transformer. The neutral current under load conditions is quite small. The neutral current is
essentially because of load unbalance.
Fig.1.4 Over current protection
Page | 5
1.3 Zero sequence over current protection
To obtain sensitive ground fault detection, use a relay that responds only to the zero-
sequence current of the system (since zero sequence current generates only during a fault related
to ground). A zero-sequence overcurrent relay simply measures the sum of the three phase
currents, as given in Equation 1.4. Unbalanced faults involving ground, such as phase-to-ground
(L-G) or phase-to-phase-to-ground (L-L-G) faults cause zero-sequence current, also referred to as
ground or residual current. CT connection configurations and the neutral current of a delta-
grounded wye transformer are additional sources of zero sequence current. Set zero-sequence
overcurrent elements at very sensitive levels (i.e. a low pickup setting) because the zero-sequence
current generated under load conditions is typically small compared to load currents.
Zero sequence current is given by,
1.4 Ground fault Protection of transformers
Ground fault protection of transformers can be archived either differential relays or
overcurrent relays. The exact relay selection and connection depends on the type of transformer
bank.
Fig.1.5 Over current (delta) and differential (wye) ground fault protection for a delta-wye transformer
Page | 6
1.5 Thermal Protection
Fig. 1.6 Transformer Thermal Protections
1.6 Over fluxing protection
The flux and the applied voltage in a transformer are related through the following expression
Where
V is the r.m.s value of the voltage
f is the frequency
N is the number of turns in the winding.
Thus, we can write the flux as
Whenever there is an over-voltage (frequency remaining constant), the transformer core is
subjected to a higher value of flux in order to be able to support the higher applied voltage. By
design, transformers operate at the knee of the saturation curve at normal voltage. Hence, any
increase in applied voltage, and the consequent increase in flux density, drives the transformer
deeper into saturation. The transformer, therefore, draws an excessive magnetization current.
Hence, this condition is described as over excitation. This, considerably, increases the core losses
giving rise to overheating of the transformer. Further, saturation of the core causes the flux to
flow into adjacent structures, causing high eddy current losses in the core and adjacent
conducting materials. Such an operating condition cannot be allowed to continue for long and the
transformer should be tripped if there is a prolonged over-excitation. It can be easily seen that
over-excitation can also occur in case of low-frequency operation of the transformer at rated
voltage.
Page | 7
Fig.1.7 Typical protection of a 750KVAtransformer
In fig.1.7, 87T differential, 86-Lockout auxillary,50/51 Overcurrent and short circuit,
50G ground fault, 67 Directional overcurrent, V,S Voltage and power metering
2. Generator Protection
Conditions Protection
Internal Fault
Stator Phase fault 87G( Generator Differential)
Stator ground fault
87N(ground differential)
51N(Neutral over current)
59N(ground overvoltage)
27-3N(third harmonic under voltage)
Ground faults in the rotor -field winding 64F( detection of generator field ground)
Abnormal operating
Overload 49(thermal)
Over excitation Overvoltage 24(volts/Hz),
59( over voltage)
Loss of field
40Q (Protection for failure of the
excitation system -Reactance based)
40Z (Protection for failure of the
excitation system -Impedance based)
Unbalanced operation ( Single phasing)
(46)
46( unbalance current )
47 (unbalance voltage )
Under and over frequency (81O/81U) 81U(under frequency)
81O(over frequency)
Loss of synchronization-out of step 78(out of step or pole slip)
25(synchronism check when paralleling)
Motoring or loss of prime move 32R (Reverse power-anti-motoring)
Inadvertent energizing 50/27
Page | 8
Generator Protection Schemes
Differential Protection Scheme
Modified Differential Protection/Percentage differential protection
High impedance differential protection
Self-balancing differential protection
Restricted or balanced earth fault
Negative phase sequence
High impedance Protection
Self-balancing Protection
Inadvertent energizing protection
2.1Differential Protection scheme
The differential protection principle is same as explained earlier for transformer
protection. Differential scheme protection to three phase alternator winding is shown in fig.2.1
Fig.2.1 Differential scheme Protection to three-phase alternator winding
2.2 High Impedance Protection
This is another type differential relay, here we keep high impedance coils and hence the
actuating quantity is voltage instead of current. The relay discriminated between internal and
external faults by the voltage that appear that across the relay. On external faults the voltage
across the relay will be low, while for internal faults the voltage across the relay is relatively
high.
This scheme has higher sensitivity than the percentage differential relay, and thus may be
more susceptible to disoperation caused by proximity effects.
Page | 9
Fig.2.2 High impedance differential
2.3 Self balancing Protection scheme
The self-balancing differential scheme has been used for phase and ground faults on small
generators with low-resistance neutral grounding. As shown in fig.2.3, leads from both ends of
the phase winding are placed in the opening of a window-type CT. Any difference between the
currents entering and leaving the winding is detected by an instantaneous overcurrent (IOC)
relay.
Fig.2.3 Self balancing Protection
2.4 Restricted or balanced earth fault protection
In case of small size generator the neutral end of 3 phase winding is not available because
it is made inside the generator and grounded through some low resistance then percentage
differential relay for ground fault is provided and is known as restricted earth fault protection.
Page | 10
Fig.2.4 Restricted earth fault protection
2.5 Negative phase sequence protection
Unbalance may cause due to single phase fault or unbalanced loading and it gives rise to
negative sequence current. This current in rotor causes rotor overheating and damage to the rotor.
This can be protected by negative sequence current filter- which will detect only negative
sequence current that creates during the unbalance condition- with over current relay.
Fig.2.5 Generator protection against unbalanced loading using negative sequence filter
2.6 Inadvertent Energizing Protection
Inadvertent energizing is the accidental energizing of generators when they are off-line.
Operating errors, breaker head flashovers, control circuit malfunctions, or a combination of these
causes’ results in generators being accidentally energized while off-line. Unlike conventional
protection systems that provide protection when equipment is in service, these schemes provide
protection when equipment is out of service. The most widely used dedicated protection systems
used to detect inadvertent energizing include:
a) Directional overcurrent relays
b) Frequency supervised overcurrent
c) Distance relay scheme
d) Voltage supervised overcurrent
e) Auxiliary contacts scheme with overcurrent relays
Page | 11
2.7 Multi-function generator protection systems As of now we discussed about the basics of each protection scheme individually. While
implementation, generally we use multiple protection schemes together to form a multi-function
protection system.Fig.2.7 shows the typical protection of a large generator.
Fig.2.7 Typical protection for a large or important generator
In most cases, new generators are being protected with either dual multifunction generator
protection systems (MGPS) or a single multifunction generator protection, possibly backed up by
some single function relays.
Figure 2.7 shows the block diagram of a typical MGPS. The MGPS has analog inputs
(voltage and current signals), digital inputs, and digital outputs for sending trip and alarm signals.
The MGPS may also have bi directional communication ports, which may be RS-232, RS-485,
fiber optic, or some other hardware interface for communicating with the external world. Internal
hardware consists of an analog data acquisition system that includes signal scaling, isolation,
filtering (anti-aliasing) analog multiplexing, and analog-to-digital conversion. The digital
subsystem consists of a microprocessor, read only memory (ROM) for program storage, random-
access memory (RAM) for temporary storage of information, and electrically erasable
programmable memory (EEPROM) for storage of set points. The functional operation and
performance of the MGPS are determined by both hardware and software programs.
Page | 12
Fig.2.7.diagram of a typical MGPS
3. Motor Protection
Conditions Protection
Internal Fault
Phase fault 87S( Stator Differential)
Ground fault
87N(ground differential)
51N(Neutral over current)
59N(ground overvoltage)
27-3N(third harmonic under voltage)
Abnormal operating
Overload 49(thermal)
Over voltage 24(volts/Hz),
59P( Phase over voltage)
59X (Auxiliary Overvoltage)
Under voltage 27P Phase under voltage
Loss of Load or under current 37
Unbalanced operation ( Single phasing)
46( unbalance current )
47 (unbalance voltage )
Under and over frequency (81O/81U) 81U(under frequency)
81O(over frequency)
Extended start (accelerating time) 48 (incomplete sequence)
Loss of supply 56 (field application )
Stalling (mechanical Jamming/Jogging)
Motor protection schemes can be easily compared with that of generator.
Page | 13
Major Protection scheme for motors are:
Differential protection
Extended start time protection
Ground fault
Unbalance
Reduction in supply voltage
Over voltage protection
Under voltage protection
3.1 Differential Protection
Principle is same as explained earlier for transformer protection. Differential protection
may be considered the first line of protection for internal phase-to-phase or phase-to-ground
faults.
Fig.3.1 Differential protection scheme for a 3 phase induction motor
3.2 Extended start time protection
The relay function protects the motor from overheating in case of abnormal loading during
motor starts. The motor can be tripped if the motor does no reach a running condition within the
programmable motor acceleration time.
3.3 Protection against Unbalance
Unbalanced currents give rise to a negative sequence component in the stator current. The
negative sequence current produces an additional flux which rotates at synchronous speed in the
opposite direction of the rotor. The eddy currents which are induced in the rotor parts will have
Page | 14
the double network frequency. During such sustained conditions, the temperature of the rotor
may reach high levels which accelerate the ageing of the insulation and cause mechanical stress
on the rotating components. The relay calculates negative sequence current and compares it with
the set operate value for the trip function.
Fig.3.2 Negative sequence voltage relay for protection against unbalance in supply voltage.
3.4 Reduction in Supply Voltage
The torque developed by an induction motor is proportional to the square of the applied
voltage as given in Eq.3.1. Therefore, any small reduction in voltage has a marked effect on the
developed torque. The reduced torque may cause the motors to lose speed and draw more current.
Large motors should be disconnected when a severe low voltage condition persists for more than
a few seconds. Under-voltage relays are used for protection against reduced supply voltage.
Torque,
Where is the slip
is rotor resistance
is rotor reactance
rotor induced e.m.f
stator voltage/supply voltage
3.5 Overvoltage Protection
The overall result of an overvoltage condition is a decrease in load current and poor power
factor. Although old motors had robust design, new motors are designed close to saturation point
for better utilization of core materials and increasing the V/Hz ratio cause saturation of air gap
flux leading to motor heating.
3.6 Under voltage Protection
The overall result of an under voltage condition is an increase in current and motor heating
and a reduction in overall motor performance. The under voltage protection element can be
thought of as backup protection for the thermal overload element. In some cases, if an under
voltage condition exists it may be desirable to trip the motor faster than thermal overload
element. Motors that are connected to the same source/bus may experience a temporary under
voltage, when one of motors starts. To override this temporary voltage sags, a time delay set
point should be set greater than the motor starting time.
Page | 15
4. Transmission Line Protection
Major Fault Types for transmission line:
Single line-to-ground (85%)
Line-to-line (8%)
Three Phase (2%)
Line-to-line-to-ground (5%)
Based on communication transmission line protection can be broadly divided into two
Pilot aided schemes : Communication between distance relay is needed
Non-pilot aided schemes(step distance): No communication between distance relays
General Protection Schemes for Transmission Lines:
Overcurrent
Directional overcurrent
Zero sequence over current protection
Distance
o Reactance
o Impedance
o Mho
o Quadrilateral
Line current differential
Phase comparison
Stepped time/distance protection scheme
Directional Comparison Blocking(DCB)
Permissive Overreach transfer trip(POTT)
4.1Overcurrent Protection
Overcurrent protection is the simplest and least expensive form of fault protection that can
be placed on transmission lines. This operates using magnitude of current. The ac connections for
three-phase and one ground time overcurrent (TOC) relays and instantaneous overcurrent (IOC)
relays are shown in fig.4.1.
Fig.4.1 Connections for overcurrent phase and ground relay
Page | 16
Operating condition of torque can be derived from Universal torque Equation (Eq.4.3).Spring
torque is the restraining torque and current coil produces the operating torque. Solving to the
balance point (zero torque) in Eq.4.1, determines the trip current (pickup current)
√
The plug-setting multiplier, PSM
Where the current through the relay operating coil and is the plug-setting of the
relay. The value of PSM tells us about the severity of the current as seen by the relay. A PSM
less than 1 means that normal load current is flowing. At PSM > 1, the relay is supposed to pick
up. Higher values of PSM indicate how serious the fault is.
4.1.2Directional overcurrent Protection
Relay responds to overcurrent condition in the forward direction only (device 67, 67N,
67NT) will not respond to reverse faults.
Fig.4.2.Directional overcurrent protection
Fig.4.3 Directional overcurrent protection representation
Page | 17
In fig.4.3, for the given fault relay 101A,102A and !04A operates. Relay 103A does not operate
as the direction of current is still the same for that relay.
4.2Distance Protection Scheme
The basic principle is that the apparent impedance seen by the relay reduces drastically in
case of line fault (or during fault on a line, the current rises significantly and the voltage collapses
significantly). If the ratio of apparent impedance to the positive sequence impedance is less than
unity, it indicates a fault.
There are three types of distance relays as given below which are applied to long lines, short lines
and medium lines respectively.
o Reactance
o Impedance
o Mho
Distance protection scheme is inherently directional
Fig.4.4 Distance relay
The Universal relay torque equation:
| | | |
| |
Where,
Operating characteristics of all relay can be explained using this.
4.2.1Impedance Relay
Operating torque is produced by current coil, | |
Restraining torque is produced by voltage coil, | |
In order to operate the relay,
Page | 18
| | | |
(Neglecting spring torque)
| |
| |
| |
| | √
| | | |
i.e. | |
Fig.4.5 operating characteristics of an impedance relay on R-X diagram
4.2.2 Reactance relay
Operating torque is obtained by current, | |
Restraining torque due to current-voltage directional element, | |
In order to operate the relay,
| | | |
| |
| |
| |
Define
| |
| |
| |
Page | 19
Fig.4.6 Reactance relay characteristics
4.2.3Mho relay
Current-voltage directional element produces operating torque, | |
Voltage provide restraining torque, | |
i.e. In order to operate the relay,
| | | |
| | | |
| |
| |
Define
| |
| | | |
Page | 20
Fig.4.7 Mho relay characteristics
4.2.4 Quadrilateral relay
Quadrilateral relay combines the advantage of reactance with directional relay and
resistive reach control. It is applied for earth fault protection of short and medium lines where
high fault resistance tolerance is required
Fig.4.8 Quadrilateral relay characteristics
4.3 Out-of-step Protection
Out-of-Step (OOS) (unstable power swing phenomena), causes uncontrolled tripping of
circuit, as the apparent impedance during power swings can enter into the reach of distance relays
If the apparent impedance stays longer than the time delay in a given zone, that distance element
will trip as for a fault. To prevent such tripping, out-of-step blocking schemes are employed. In
fig.4.9 If the timer expires between the two zones, out-of-step condition is declared and selected
distance elements are blocked.
As we know stable power swings are not dangerous and we need to differentiate stable from
unstable power swings. So this is also taken into account of out-of-step trip function by this.
Page | 21
Fig.4.9 out of step blocking distance scheme.
.
4.4 Differential and biased differential Protection of Transmission Lines
Biased-differential elements compare an operating current with a restraint current as
explained earlier.
Fig.4.10 Differential Relay Operating Characteristics
In fig. 3.8,
4.5 Phase comparison relaying
This relay compares the relative phase angles between two currents. It is used to determine
the current direction with respect to reference quantity. For Example In a normal/balanced power
flow, the phase angle between voltage and current (power factor angle) is 30⁰.When power flows
in opposite direction, then the angle will be 180⁰-30⁰.i.e.For fault in forward or reverse direction,
the phase angle of current with respect to voltage is –Φ or 180⁰-Φ.
Where Φ is the impedance/power factor angle.
Page | 22
Fig.4.11Basic Phase comparison operation
Fig.4.11 shows the phase comparison operation, clearly for external/through fault the direction of
current flow reverses by 1800.
4.6 Time stepped distance protection(Non-pilot) scheme
Conventional time-stepped distance protection is illustrated in Figure 4.12. One of the
main disadvantages of this scheme is that the instantaneous Zone 1protection at each end of the
protected line cannot be set to cover the whole of the line length and is usually set to about 80%.
This leaves two 'end zones', each being about 20% of the protected line length. Faults in these
zones are cleared in Zone 1 time by the protection at one end of the line and in Zone 2 time (with
a time lag) by the protection at the other end of the line.
Each zone characteristics is listed below:
Zone 1: Trips with no intentional time delay.Underreaches to avoid unnecessary operation
for faults beyond remote terminal. Typical reach setting range 80-90% of ZL
Zone 2: Set to protect remainder of line. Overreaches into adjacent line/equipment.
Minimum reach setting 120% of ZL.Typically time delayed by 15-30 cycles
Zone 3: Remote backup for relay/station failures at remote terminal. Reaches beyond ZL
(reaches nearest line/ equipment)
Page | 23
Fig.4.12 Conventional stepped time distance scheme
4.7 Permissive Overreaching Transfer Trip (POTT)
POTT schemes implement the logic shown in Figure 4.13. Since the Zone 2 trip output
requires an enable from a receiver output (permissive signal), the scheme is considered a tripping
scheme. This improves performance speed for faults detected by Zone 2 elements because the
relay operates as soon as an enabling signal is received for the remote terminal.
Fig.4.13.POTT Tripping Logic
Page | 24
5. Bus Protection
Major Bus Protection schemes
Differential
Bus bar blocking
Fault bus
5.1Differential Protection The principle is same as explained earlier. This requires sectionalizing the bus bars into different
zones
Fig.4.1 Differential protection for Bus bars
For fig.4.1, For External Fault
and For Internal Fault,
Fig.4.2 Differential Protection-Double bus double breaker
Page | 25
5.2 Bus bar blocking scheme
It’s a very low cost and simple scheme. Blocking scheme covers phase and earth faults and gives
adequate sensitivity – independent of no. of circuits. No additional CTs required. But it is only
suitable for simple bus bars and sensitivity is limited by load current.
Fig.4.3 Simple blocking scheme for a single bus with a single source
5.3 Fault Bus relay scheme
This scheme requires isolating the bus support structure from ground and grounding this
structure through a single-point ground and CT.
Page | 27
Appendix
A.1 Sequence Voltages and currents [12]
Symmetrical components are used to simplify analysis of unbalanced three phase power
systems under both normal and abnormal conditions.
A system of three unbalanced phasors can be resolved in the following three symmetrical
components:
Positive Sequence: A balanced three-phase system with the same phase sequence as the
original sequence.(abc,bca,cab)
Negative sequence: A balanced three-phase system with the opposite phase sequence as
the original sequence.(acb,bac,cba)
Zero Sequence: Three phasors that are equal in magnitude and phase
Fig.A.1 representation of (a) an unbalanced network, its (b) positive sequence(c) negative sequence (d) zero
sequence
Define Then,
[
] [
] [
]
Similarly,
[
] [
] [
]
A.2 Transmission Line Classification
Various protection schemes are applied to transmission line based on its length, nominal
voltage etc. Transmission lines are classified as follows depending on their source to line
impedance (SIR) ratio:
1. Short line SIR>4
2. Medium line 0.5<SIR<4
3. Long line SIR<0.5
A.3 Directional comparison Scheme
The idea behind this scheme is to obtain the response of the distance relay element at other
end to speed decision making (i.e. it overcomes the disadvantages of stepped distance protection
scheme). This scheme requires additional communication signals and it can quickly clear the
Page | 28
fault anywhere on the primary line. In this underreaching function, overreaching function,
blocking functions etc. are implemented for different zones using logic gates and IC’s to ensure
full protection of the line as well as high speed tripping. The primary difference between the
various directional comparison schemes is the way in which the relays use the information from
the other terminal.
Commonly used directional comparison schemes are:
1. Permissive Overreaching Transfer Trip (POTT)
2. Permissive Underreaching Transfer Trip (PUTT)
3. Directional Comparison Blocking (DCB)
4. Directional Comparison Unblocking (DCUB)
5. Direct Underreaching Transfer Trip (DUTT)
6. Direct Transfer Trip (DTT)
A.4 Communication systems typically used for protective relaying include:
Fiber optic (FO)
Pilot-wire 50, 60 Hz (PW)
Pilot-wire audio tones (AT)
Power line carrier (PLC)
Microwave (MW)
Point-to-point radio (R)
A.5 Power swing
Power swing is caused by the large disturbances in the power system, which can cause the
change in load impedance within the relay’s operating characteristic, to induce unwanted relay
operations at different network locations. These undesirable measurements may aggravate the
power-system disturbance and cause major power outages, or even power blackout. Particularly,
distance relays should not trip unexpectedly during dynamic system conditions such as stable
unstable power swings, and allow the power system to return to a stable operating condition.
Thereby, a Power Swing Block (PSB) function is adopted in modern relays to prevent unwanted
distance relay element operation during power swing. The main purpose of the PSB function is to
differentiate between power faults and power swings, and block distance or other relay elements
from operations during a stable power swing.
Fig.A.5 shows the reactance (resistance is neglected) variation (more curves if there are
more number of parallel lines) during swing. If the area 1 and area 2 are equal which implies a
stable power swing, it can go back to normal operating condition after the opening of CB with
the old or new impedance.
Fig.A.5. One-line diagram of a two source transmission line and power angle curve
Page | 29
Electrical power transmitted from source to receiver is given by the power transfer equation,
Where:
is sending end voltage
is receiving end voltage
is the angle by which leads by
is the total reactance between the sending end and receiving end voltages ( )
With fixed values of , relationship between can be described in the power
angle curve as shown in fig.4.(b) ( more in ref.12)
A.5 Blinders
Blinders limit the operation of distance relays (quad or mho) to a narrow region that
parallels and encompasses the protected line. Applied to long transmission lines, where mho
settings are large enough to pick up on maximum load or minor system swings.
Page | 30
References 1. IEEE Std C37.2-2008, IEEE Standard for Electrical Power System Device Function
Numbers, Acronyms, and Contact Designations
2. IEEE Std C37.91-2008, IEEE Guide for Protecting Power Transformers.
3. IEEE Std C37.102-2006, IEEE Guide for AC Generator Protection
4. IEEE Std C37.113-1999, IEEE Guide for Protective Relay Applications to Transmission
Lines
5. IEEE Std C37.234-2009, IEEE Guide for Protective Relay Applications to Power System
Buses
6. Electric Power Distribution Systems Operations, NAVFAC MO-201,April 1990
7. Y.G.Paithankar,S.R.Bhide, ‘Fundamentals of Power System Protection’,(Prentice Hall of
India),2003.
8. C.L.Wadhwa, ‘Electrical Power systems’,Sixth ed.,New age international publishers, 2010
9. ‘Applied Protective Relaying’, Westing House Electric Corporation, Relay Instrument
Division, New Jersey
10. L.G.Hewiton, Mark Brown, Ramesh Balakrishnan, ‘Practical Power system Protection’
11. P.M.Anderson, ‘Power system Protection’, IEEE Power series on Power
Engineering,1999
12. D.P.Kothari,I.J Nagrath, Modern Power system Analysis, Fourth Ed.,2011