power cables and wires technical manual 2010 edition
DESCRIPTION
Power Cables and Wires Technical Manual 2010 EditionTRANSCRIPT
2010 Edition
Power Cables & WiresTechnical Manual
Through the initiative of:
International Copper Association – South East Asia
Institute of Integrated Electrical Engineers of the Philippines, Inc.
ISBN 978-971-93962-8-4
iii
PREFACE
This book, Power Cables and Wires Technical Manual, was written toaddress the need by consumers, specifiers, and purchasers to have aready reference guide in correctly specifying or ordering the appropriatecables and/or wires that will satisfy their particular requirements.Towards this purpose, a Cable/Wire Ordering Form, which appears inAnnex D, was developed so that the User will be able to indicate anditemize his needs and give all data and information necessary for theWires and Cable Manufacturer or Supplier to be able to supply the wireor cable that the User requires.
All components necessary for the construction of a cable or wire, fromthe conductor to the insulator, are each discussed in this manual so as toeducate or inform the reader of its fundamental use or purpose to thefinal product. Moreover, all the different types of material and theircharacteristics have been identified and explained in this manual tofurther elucidate the reader.
This publication was made possible through the initiative and support ofthe International Copper Association – South East Asia and the Instituteof Integrated Electrical Engineers of the Philippines, who developed,published and will propagate its use as reference.
Though conscientious efforts have been exerted to ensure the accuracy ofthe information in this manual, comments regarding errors and omissionsare most welcome and highly appreciated. All suggestions will bestudied and considered for inclusion in this manual’s next edition.
iv
v
ACKNOWLEDGEMENT
This “Power Cables and Wires Technical Manual” was developed into aprinted publication through the collaborative efforts among professional,business and international organizations. In the course of the manual’sconceptualization, development and production, which spanned for morethan a year, several distinguished entities and individuals, havegenerously lent their utmost participation, assistance, knowledge,expertise and support towards the completion and publication of thismanual.
Special thanks are given to the Institute of Integrated ElectricalEngineers (IIEE) of the Philippines’ 2009 and 2010 Board of Governors,headed by their Presidents, Engrs. Arthur N. Escalante and Gregorio Y.Guevarra, respectively, for their insightful approval to engage theInstitute in this worthwhile project and sustaining the support until itscompletion. Of course, all of this would not have been possible withoutthe initiative and patronage of the International Copper Association –South East Asia, whose representative in the Philippines is Mr. JessieTodoc. Further, we want to recognize the critical support, knowledge andrelevant materials contributed by the following Wires and CablesCompanies; Columbia, Phelps Dodge, Sycwin and Philflex. Moreover,we would like to acknowledge the Bureau of Product Standards (BPS) ofthe Department of Trade and Industry (DTI) for the list of the existingPhilippine National Standards (PNS) on wires and cables.
Finally, eternal gratitude is given to the IIEE Adhoc Committee on Wiresand Cables, whose members are; Engr. Willington K. K. C. Tan, Engr.Cesar Gatpo, Ms. Maritess Templonuevo and Engr. Ricardo Lopez Jr.,who participated in the conceptualization and outline of the manual andwere instrumental in coming up with the Cable/Wire Ordering Form, andwhose indefatigable Chairman, Engr. Arthur A. Lopez, gave flesh to themanual. Special mention is given to Engr. Feldimir Siao of MERALCO,who conducted the review of the original manuscript and to Engr. WilsonYu for his valuable contributions.
Again, thank you very much.
vi
vii
Table of Contents
Preface iiiAcknowledgement vTable of Contents viiIntroduction 1
1 Material Consideration 11.1 Resistance and Conductivity 21.2 Weight 31.3 Amapacity 41.4 Voltage Regulation 41.5 Short Circuit 41.6 Other Factors 4
2 Wire/Cable Manufacturing Process 52.1 Drawing 62.2 Annealing 62.3 Stranding 62.4 Bunching 62.5 Extrusion 7
3 Conductor Size 74 Stranding 10
4.1 Concentric Stranding 104.2 Compressed Stranding 114.3 Compact Stranding 114.4 Bunch Stranding 134.5 Rope Stranding 134.6 Sector Conductors 134.7 Segmental Conductors 134.8 Annular Conductors 14
5 Physical and Mechanical Properties 145.1 Conductor Properties 145.2 Tempers of Conductors 155.3 Conductor Direct Current (DC) Resistance 165.4 Conductor AC Resistance 195.5 Cables in Magnetic Metal Conduit 215.6 Resistance at Higher Frequency 22
viii
6 Insulation 226.1 Elastomers 236.2 Plastics 276.3 Insulation Resistance 33
7 Cable Design and Construction 358 Low Voltage Wires and Cables 36
8.1 Building Wires 398.2 Secondary and Service Cables 44
9 Medium and High Voltage Wires and Cables 499.1 Bare Conductors 499.2 Covered Conductors 539.3 Insulated Cables 57
10 Installation of Wires and Cables 6210.1 Maximum Allowable Tensions on Conductors 6210.2 Sidewall Pressure 6810.3 Bending Radius 69
11 Packaging 7212 Cable/Wire Application 7213 Cable Installation Method 7214 Color Coding 7215 Reference Standards 7316 Storage 7317 Available Cable Handling Equipment at Site 7518 Safeguards for Installing Wires and Cables in
Conduit 7518.1 Before Pulling Wire/Cable 7618.2 While Pulling Wire/Cable 7618.3 After Pulling Wire/Cable 76
19 Safeguard for Switchboard and Similar OpenWiring 76
20 Wire/Cable Ordering Form 77Annexes 79
Annex A 81Annex B 157Annex C 165Annex D 171
Bibliography 173
Power Cables & Wires Technical Manual
1
INTRODUCTION
One of the fundamental concerns of electrical engineering is thetransmission and distribution of electricity to its final utilization in amanner that is safe, efficient and economical. The choice of conductormaterial including size and design takes into consideration the operatingvoltage, ampacity, mechanical properties, type of installation and overallcost.
Electric wires and cables come in a wide variety of types andconstruction. It usually consists of a low resistance conductor toproperly transmit electric current. They can be classified in variousways depending on the factors being considered such as the material,degree of insulation, service, or voltage application.
The aim of this manual is to provide sufficient information on the typesof wires and cables available in the market including its intendedapplication in order for the reader to make an intelligent selection. Atthe end section of this manual, more detailed information are includedon the types and applications of wires and cables that an electricalpractitioner would generally need.
1. MATERIAL CONSIDERATIONS
There are several high conductivity metals that may be used asconductor. A conductor is a metallic material which allows electriccurrent to flow through it with less resistance. Table 1 ranked thesemetals according to resistivity at 20°C.
The best conductor material is silver but due to its high cost per unitweight and being one of the precious metals, it is not economical touse in the transmission and distribution of electricity. Comparatively,gold with its excellent corrosion resistance and lower resistivity thanaluminum is also a good conductor but, same as silver, is very costly.Thus, these metals i.e., silver and gold are only used in electricalapplications where low resistivity and corrosion resistance is of utmostimportance such as electrical contacts.
Power Cables & Wires Technical Manual
2
Copper with its inherent lower resistivity than aluminum is the preferredconductor on certain applications. It is malleable and ductile. Also, ithas a relatively higher tensile strength and easily soldered. However, itis more expensive and heavier than aluminum.
Table 1. Resistivity of Metals at 20°CMetal Ohm-mm2/m
Silver 1.59×10−8
Copper 1.68×10−8
Gold 2.44×10−8
Aluminium 2.82×10−8
Tungsten 5.60×10−8
Zinc 5.90×10−8
Nickel 6.99×10−8
Iron 1.0×10−7
Platinum 1.06×10−7
Tin 1.09×10−7
1.1 Resistance and Conductivity
Resistance is the opposition of an object to the passage of electriccurrent. For direct current, resistance is dependent on the materiallength, cross-sectional area and resistivity. The electrical resistanceof a conductor is inversely proportional to the cross-sectional area ordiameter of a conductor i.e., the larger the conductor the lessresistance it has to the flow of current. Conductivity, on the otherhand, is the complete opposite of resistance.
Compared with copper, aluminum has a number of technicaldisadvantages, all of which can be satisfactorily overcome tobenefit from its economic attraction. The advantage of its lowerdensity (about one-third that of copper) is partly offset by its lowconductivity of just 61% that of copper. Thus, an aluminumconductor must have a cross-sectional area about 1.6 times that ofcopper conductor to have the equivalent dc resistance. Suchdifference is approximately equal to two sizes higher (i.e., in AWG).
Power Cables & Wires Technical Manual
3
The grade and quality of copper is very important and the highconductivity copper used for electrical purposes comfortably exceedsthe 100% IACS (International Annealed Copper Standard)value. Conductivity is greatly influenced by impurities and bymechanical working. Consequently, the purity is of the order of99.99%, which nowadays is obtained by final electrolyticrefining. Fortunately, the mechanical strength of annealed copperwire is adequate for nearly all types of insulated cable. If any minorworking of the material occurs during conductor manufacture, e.g. incompacting to reduce the overall dimensions, allowance has to bemade for work hardening by increasing the copper volume tocompensate for the reduction in conductance. In an extreme case,such as the use of hard drawn copper for self-supporting overheadlines, this may amount to as much as 3%. Copper is invariably usedin the annealed condition except for the conductors of self-supporting overhead cables. Solid aluminum conductors are alsomainly in a soft condition but stranded aluminum conductors are ¾H (hard) to H.
1.2 Weight
Although aluminum has only about sixty-one percent (61%) of theconductivity of copper, its lightness makes long spans possible.Aluminum’s low density is one of its important advantages. Also, itsrelatively large diameter for a given conductivity reduces corona(the discharge of electricity from the wire when it has a highpotential), which contributes to the losses of the wire. This makesaluminum ideal for the transmission of high voltage power over longdistances. However, due to aluminum’s relatively low tensilestrength, the aluminum conductors are usually cabled around a steelsupport wire to improve the total tensile strength of the cable. Thisenables the relatively expensive transmission towers to be spacedfurther apart without the wire sagging too much. Electricaltransmission lines are the largest users of aluminum wire products. Infact, this is the one market in which aluminum has virtually nocompetition from other metals.
However, the relatively large size of aluminum for a givenconductance does not permit the economical use of an insulation
Power Cables & Wires Technical Manual
4
covering. Hence, low voltage household, office, and factoryelectric wires and cables are usually copper, which also does nothave the corrosion problems common to aluminum wires. Infact, copper has been unchallenged as a conductor for all types ofinsulated cables for well over seventy (70) years.
1.3 Ampacity
In general, current ratings of aluminum cables are about 78%-80% ofthose of copper cables of the same conductor size. An aluminumcable needs to be thicker than a copper cable in order to have thesame current carrying capacity.
1.4 Voltage Regulation
Reactance is negligible in all DC circuits and, in AC circuits withsmall conductors of sizes equal to or less than 60 mm2. Voltagedrops for a copper conductor and an aluminum conductor with 1.6times the cross-sectional area would be the same. However, in ACcircuits with large conductors, the resistance value is influenced byskin and proximity effect, and the reactance becomes important.
1.5 Short Circuit
Copper conductors have higher capabilities in short circuitoperations than aluminum conductors. However, for covered andinsulated conductors the thermal limitations of the materials whichform part of conductor should be considered before making suchcomparison.
1.6 Other Factors
Aluminum oxidizes rapidly when exposed to air, a thin corrosionresistance film having a high dielectric strength forms quickly. Thus,additional care must be taken when making connections. Material ofterminal connections should be taken into consideration since thiscould corrode the aluminum conductor. Also, when a combination ofcopper and aluminum conductors are to be connected together,special technique or connectors are required to have a reliableconnection.
Power Cables & Wires Technical Manual
5
Small strands of aluminum conductor have lower bending tolerancethat these are not used in generating stations, substations or portablecables. When there are space limitations, copper cables are thesuitable choice since aluminum cables are larger in size for the samecurrent carrying capacity.
Economics does play a vital consideration in the choice of conductorbut should include the other overlying cost involved to complete aninstallation.
2. WIRE/CABLE MANUFACTURING PROCESS
Copper and aluminum rods undergo several stages of processing beforethey become wires or cables. Below is a flowchart of the wire/cablemanufacturing process.
Figure 1: Wire Manufacturing Process
Bare solid harddrawn wire (1)
Bare stranded soft
drawn wire (1, 2 & 3)
Drawing
(1)
Stranding/
Bunching
(3)
Extrusion
(4)
Stranding/
Bunching
(3)
Extrusion
(4)
Insulated solid harddrawn wire (1 & 4)
Insulated stranded harddrawn wire (1, 3, 4)
Bare stranded harddrawn wire (1 & 3)
Annealing
(2)
Bare solid soft drawnwire (1 & 2) Insulated stranded soft
drawn wire (1, 2, 3 & 4)
Power Cables & Wires Technical Manual
6
2.1 Drawing
Drawing is the process of pulling the copper or aluminum rods orwires at normal temperature through a die to reduce the cross-sectional area in order to get the desired dimension. The wire isdeformed due to the tapering of the die and the force exerted duringpulling.
2.2 Annealing
Annealing is the process of “softening” the temper of the wire andimproving its cold working properties and machinability throughsustained heating at a pre-determined temperature followed bycooling at a defined rate. There are many ways of annealing a wire;the most common practices in annealing copper is the continuousstrand or resistance annealing wherein annealing is done bymeans of a machine placed between the final capstan of a drawingmachine and the spooler so that the wire is drawn, annealed andspooled in one operation.
2.3 Stranding
Stranding is the process where a number of hard or soft wires are laidtogether geometrically in such a way that each wire holds its place inthe strand all throughout the entire length. Generally, the number ofwires in a strand is 7, 19, 37, 61, and could reach up to 91, 127 or168 depending on the desired size or cross-sectional area ofthe stranded wire. The lay of multi-layered stranded wires are laidin opposite direction alternately in its succeeding lay with theoutermost generally being left-handed.
2.4 Bunching
Bunching is similar to the stranding process except that all individualwires are twisted uniformly in the same direction without regard forgeometrical arrangement. It provides a more flexibleconductor than a single strand. A number of bunches twisted togetherin the same direction and in uniform manner is called a compound
Power Cables & Wires Technical Manual
7
bunch. A number of bunches twisted together so that each bunch,except the central one, has a helical form of pre-determined lay ratiois a stranded bunch. A number of stranded bunches twisted togetherso that each stranded bunch, except the central one, has a helicalform of pre-determined ratio is called a compound strand bunch.
2.5 Extrusion
Extrusion is the process where an insulation material iscontinuously coated or applied around the conductor as it passesthrough a die in the head of an extruding machine. The insulationmaterial in form of pellets, dice and the likes (can be plastic, nylon,rubber, etc.) are placed in a hopper that is situated over a barrel inwhich a screw revolves. The insulation material softens as it feedsinside the heated extruder barrel then melted out over the corematerial through the screw which forces the material along the barreland compresses it at the same time to convert the material into fluidmass. The conductor emerges from the tip of the core with thematerial stream inside the extruder head and the insulation isformed to the required size and shape as the insulated conductorpasses through the die.
3. CONDUCTOR SIZES
Similar to most industries, standards for measuring conductor sizes hadbeen developed. A conductor’s size is usually specified based on theconductor’s cross-sectional area or its diameter. Conductor sizes areusually identified in accordance with either of the two predominant wiresizes, the American Wire Gauge (AWG) which is originally known asBrown and Sharpe gauge (B&S) or the Metric Wire Gauge (MWG),which is the international standard (SI or IEC).
The American Wire Gauge (AWG) is used predominantly in the UnitedStates of America (USA). The diameter of AWG No. 4/0 is 0.46 inch andthe diameter of the AWG No. 36 is 0.005 inch. The other 38 intermediatesizes are governed by a geometric progression with the followingformula:
Power Cables & Wires Technical Manual
8
Thus, the ratio of any diameter to the next size is 1.122932.
The conductor diameter will approximately double after the next 6 AWGsizes or it will be half after the next 6 lower sizes. For conductor sizeslarger than AWG No. 4/0, the size is expressed in circular mils which isan arbitrary cross-sectional area of the conductor. It is computed bymultiplying the individual wire diameter in inches by 1,000, squaring theresult, and multiplying by the number of wires. Usually expressed inkcmil (new term) or MCM (old term) which denotes thousand circularmils.
The metric wire gauge is used by most countries in the world. It uses theSI unit of square millimeters (mm2) to designate conductor size (i.e.,cross-sectional area). However, the designated metric wire sizes are notthe precise sizes. IEC standard allows a variation of up to 20% in theconductor area from the designated size.
In the Philippines, the wire sizes used are in metric but are, technically,based on AWG sizes. That is, the nearest metric equivalents to the cross-sectional area of the standard AWG sizes were adopted. Solid conductorsizes are specified according to its diameter (mm), while strandedconductor sizes are specified according to its cross-sectional area (mm2).Table 2 shows the conversion table of the standard AWG sizes to theirmetric equivalences.
A conductor’s size is directly proportional to its current carryingcapacity. Hence, the bigger the size of the conductor, the higher thecurrent it can carry or will be able to transmit for a given temperature.Annex A shows the current carrying capacity of the various sizes of bareand insulated, as well as, solid and stranded conductors according to theirapplication and method of installation.
For stranded conductors, the area is based on the sum of the cross-sectional area of the individual strands. Stranding of conductors providethe desired properties of flexibility, however, it also increases slightlythe overall diameter because of the small gaps between the strands.Hence, a stranded conductor will always have a slightly larger overalldiameter than a solid conductor with the same size or gauge.
Power Cables & Wires Technical Manual
9
Table 2 - Conversion Table(Nearest AWG/kcmil to mm2)
PEC (PNS) ASTM Metric (IEC)mm2 (mm. dia.) AWG/kcmil
(mm. dia.)mm2 (mm. dia.)
SOLID(1.6 mm)(2.0 mm)(2.6 mm)(3.2 mm)
1412108
(1.63mm)(2.05 mm)(2.59 mm)(3.26 mm)
STRANDED2.03.55.58.0
(7 x 0.6 mm)(7 x 0.8 mm)(7 x 1.0 mm)(7 x 1.2 mm)
1412108
(7 x 0.615 mm)(7 x 0.775 mm)(7 x 0.978 mm)(7 x 1.23 mm)
2.54.06.010
(7 x 0.67 mm)(7 x 0.85 mm)(7 x 1.04 mm)(7 x 1.35 mm)
14223038
(7 x 1.6 mm)(7 x 2.0 mm)(7 x 2.3 mm)(19 x 2.3 mm)
6421
(7 x 1.56 mm)(7 x 1.96 mm)(7 x 2.47 mm)(19 x 1.69 mm)
162535
(7 x 1.71 mm)(7 x 2.13 mm)(7 x 2.52 mm)
506080100
(19 x 1.8 mm)(19 x 2.0 mm)(19 x 2.3 mm)(19 x 2.6 mm)
1/02/03/04/0
(19 x 1.89 mm)(19 x 2.13 mm)(19 x 2.39 mm)(19 x 2.68 mm)
50
7095
(19 x 1.8 mm)
(19 x 2.17 mm)(19 x 2.52 mm)
125150
200
(37 x 2.1 mm)(37 x 2.3 mm)
(37 x 2.6 mm)
250300350400
(37 x 2.09 mm)(37 x 2.29 mm)(37 x 2.47 mm)(37 x 2.64 mm)
120150
185
(37 x 2.03 mm)(37 x 2.3 mm)
(37 x 2.52 mm)
250325400
(61 x 2.3 mm)(61 x 2.6 mm)(61 x 2.9 mm)
450500600750
(37 x 2.8 mm)(37 x 2.95 mm)(61 x 2.52 mm)(61 x 2.82 mm)
240300400
(61 x 2.44 mm)(61 x 2.5 mm)(61 x 2.9 mm)
500 (61 x 3.2 mm) 1000 (61 x 3.25 mm) 500 (61 x 3.2 mm)
Power Cables & Wires Technical Manual
10
Left hand lay direction
Concentric Stranding
4. STRANDING
The conductor material may be either solid or stranded. A solidconductor is a single, solid strand of conductor for the whole length ofthe wire, while a stranded conductor is composed of several strands ofconductor concentrically wounded together over the whole length of thewire/cable. For the same cross-sectional area of a conductor, there arediameter differences between solid and various types of strandedconductors. This is an important consideration in the selection ofconnectors and in the methods of splicing and terminating.
Large sizes of solid conductors are too rigid for many applications thatthe solution would be to have smaller wires and strand them together toform the conductor. There are several ways of stranding the wirestogether which is dependent of the type and temper of the metal used.The following subsections will discuss the most commonly usedstranding for copper conductors.
4.1 Concentric Stranding
This consists of a central wire or core surroundedby one or more layer of hellically applied wires.Each layer is applied in a direction opposite tothe layer underneath, except for unilayconstruction wherein the layers are applied in thesame lay direction. Lay length is the distancerequired to make one complete revolution of astrand around the central conductor. Lay lengthrequirement based on the American Society ofTesting Materials (ASTM) standard is for neither it to be not lessthan 8 times nor more than 16 times the overall diameter of thatlayer.
For power cables, thestandard stranding is ClassB. The outermost layershould be of a left hand laywhich means that when yougo along the axis of the conductor the outermost layer of strandsshould roll towards the left as they recede from the observer. More
Power Cables & Wires Technical Manual
11
Compact Stranding
Compressed Stranding
flexibility is obtained by using small strands and increasing thenumber of wires in the conductor. Class C has one more layer thanClass B, Class D has one more layer than Class C and so on. Theclass designation goes up to M (those normally used for weldingcables).
4.2 Compressed Stranding
This construction slightly deforms the layersto allow the layer being applied to closetightly. The diameter of the conductor can bereduced by up to 3% of the equivalentconcentric strand. There is no, however,reduction in the conductor area.
4.3 Compact Stranding
This is similar to compressed stranding exceptthat additional forming is done to reduce theconductor diameter typically by 9% less thanits equivalent concentric stranded conductor.The resulting diameter is a near solidconductor.
Power Cables & Wires Technical Manual
12
Table 3 - Diameter for Stranded Copper and Aluminum Conductors
ConductorSize
Nominal Diameters (mm)
Concentric Stranded Compressed CompactClass B Class C
AWG8 3.708 3.759 3.581 3.4046 4.674 4.742 4.521 4.2934 5.893 5.944 5.715 5.4103 6.604 6.680 6.401 6.0452 7.417 7.518 7.188 6.8071 8.433 8.458 8.179 7.5951/0 9.474 9.500 9.169 8.5342/0 10.643 10.668 10.312 9.5503/0 11.938 11.963 11.582 10.7444/0 13.411 13.437 13.005 12.065kcmil250 14.605 14.630 14.173 13.208300 16.002 16.027 15.519 14.478350 17.297 17.297 16.789 15.646400 18.491 18.517 17.932 16.739450 19.609 19.634 19.025 17.780500 20.650 20.701 20.041 18.694550 21.717 21.717 21.057 19.685600 22.682 22.682 21.996 20.650650 23.597 23.622 22.885 21.463
700 24.486 24.511 23.749 22.276
750 25.349 25.375 24.587 23.063
800 26.187 26.213 25.400 23.825
900 27.762 27.762 26.949 25.375
1000 29.261 29.286 28.372 26.924
Notes:1. Compressed and compact nominal diameters are based on concentric lay
stranded Class B construction.2. The above diameters are based on ASTM specifications (converted into SI or
metric units).
Power Cables & Wires Technical Manual
13
Rope Stranding
Bunch Stranding
Segmental Conductor
Sector Conductor
4.4 Bunch Stranding
In this construction the conductor strands aretwisted together in the same direction withoutany regard to the geometric arrangement.Commonly used when very flexible wire isrequired for small conductor sizes, such asportable cables.
4.5 Rope Stranding
This is a combination of the concentricconductor and a bunch stranded conductor.The complete conductor is composed of anumber of groups of bunched or concentricstranded conductors assembled concentricallytogether.
4.6 Sector Conductors
The cross-section of these conductors isapproximately the shape of a circle’s sector. Amulti-conductor insulated cable with threesector conductor cables have three 120°segments that combine to form a circle as afinished cable. This cable have smallerdiameter than the cable with round conductors.Also, these cables have lower ac resistance due to a reduction of theproximity effect.
4.7 Segmental Conductors
A segmental conductor is a round, strandedconductor composed of three or four sectorsslightly insulated from one another. Thisconstruction has the advantage of lower a-cresistance due to less skin effect.
Power Cables & Wires Technical Manual
14
Annular Conductor
4.8 Annular Conductors
The round stranded conductors are laid arounda suitable core. The core is usually madewholly or mostly of non-conducting material.This construction has the advantage of lowertotal a-c resistance for a given cross-sectionalarea of conducting material by eliminating thegreater skin effect at the center.
5. PHYSICAL AND MECHANICAL PROPERTIES
Although high conductivity is an important feature of a good conductor,there are other factors that must be considered. Silver maybe the mostconductive material but high cost and lack of physical strength makes itinappropriate for commercial usage as wire and cable. Thus, thedominant metals used for wires and cables are copper and aluminum.
5.1 Conductor Properties
Copper and aluminum has its own advantageous anddisadvantageous characteristics that affect its use under varyingcircumstances. A comparison o f s o m e o f the characteristics ofcopper and aluminum is given in Table 4.
Power Cables & Wires Technical Manual
15
Table 4: Comparative Characteristics of Copper and Aluminum
CHARACTERISTICS (20o
C) COPPER ALUMINUM
Ultimate Tensile Strength (MN/m2)soft temper¾ H to H
225385
70-90125-205
Hardness (DPHN)soft¾ H to H
50115
20-2530-40
Weight for the same conductivity (kg.) 45.4 21.8
Cross section for the same conductivity(mm2)
0.05 0.08
Weight Resistivity(Ohms-g/m2) 0.153280 0.076149
Volume Resistivity (Ohms- mm2/m) 0.017241 0.028172
Temperature Coefficient of Resistance (o
C) 0.00393 0.00404
Thermal Conductivity (W/cm °C) 3.8 2.4
Coefficient of Thermal Expansion per °C 17.0 x 10-6 23.0 x 10-6
Density (kg/m3) 8890 2703
Melting Point (o
C) 1,083 659
Modulus of Elasticity (MN/m2) 26 14
Stress Fatigue Endurance Limit(approximate) (MN/m2)
+/- 65 +/- 40
5.2 Tempers of Conductors
Drawing copper or aluminum rods into a wire results in thehardening of the finished wire. This causes a soft temper rod tobecome a hard temper wire. It may be desirable to utilize aconductor of softer temper in cable construction. This can beachieved through an annealing process during or after wire drawingor stranding.
Annealing consists of heating the conductor to elevatedtemperatures for specific time periods. This is usually done in anoven or by continuous resistance annealing at the drawingmachine.
Copper can be provided in three (3) tempers based on ASTMstandards. These tempers are soft or annealed, medium-hard andhard-drawn. Soft or annealed is the most often used temper for
Power Cables & Wires Technical Manual
16
insulated conductors due to its flexibility. Medium hard-drawn andhard-drawn tempers are most often used in overhead applications dueto their higher breaking strengths.
On the other hand, aluminum can be provided in five (5) tempersbased on ASTM standards as shown in the Table 5, below. Notethat the overlapping values showing the same conductor maymeet the temper requirements of two classifications.
Table 5 – Tensile Strength of the Different Temper Classificationsof Aluminum
Classifications of 1350 Aluminum Tensile Strength(in kg/cm2)
Full Soft (H-0) 597.6 to 984.3¼ Hard (H-12 or H-22) 843.7 to 1195.3½ Hard (H-14 or H-24) 1054.7 to 1406.2¾ Hard (H-16 or H-26) 1195.3 to 1546.8
Full Hard (H-19) 1582 to 2039
Three quarters and full hard are the most common tempers usedwith 1350 aluminum for insulated conductors. Full hard drawntemper is most often used in overhead applications due its higherbreaking strengths.
5.3 Conductor Direct Current (DC) ResistanceThe DC resistance (Rdc) of a conductor of uniform cross section can becomputed as:
where, l = length of the conductor, meters (m)A= cross-sectional area of the conductor, square meters
(m2)ρ = (Greek: rho) electrical resistivity (also called specific
electrical resistance) of the material, ohm-meters (Ω-m)ρ for copper is 1.678 x 10-8 Ω-m at 20°Cρ for aluminum is 2.65 x 10-8 Ω-m at 20°C
Power Cables & Wires Technical Manual
17
Since resistance is temperature dependent, conversion of a givenresistance at a specified temperature to another is given by theseformulas:
Copper: Aluminum:
where, R2 = conductor resistance at temperature T2 in °CR1 = conductor resistance at temperature T1 in °C
These formulas are based on the resistance coefficient of copperhaving 100% conductivity and aluminum having 61.2% conductivitybased on International Annealed Copper Standard (IACS).
Power Cables & Wires Technical Manual
18
Table 6 - DC Resistance in Ohms Per Kilometer at 25oC
Size Solid Concentric Lay StrandedAWG orkcmil
Copper*Uncoated
Aluminum Copper*UncoatedClass B, C
AluminumClass B, C
8643211/02/03/04/0250300350400450500550600650700750800
2.0991.3220.8300.6590.5520.4130.3280.2600.2070.164————————————
3.4442.1681.3611.0790.8560.6790.5380.4260.3380.2690.2280.1900.1620.1420.1260.114——————
2.1391.3480.8460.6720.5310.4230.3350.2660.2110.1670.1410.1180.1010.0880.0790.0710.0640.0590.0540.0510.0470.044
3.5102.2141.3911.1020.8720.6920.5510.4360.3440.2740.2320.1940.1660.1450.1290.1160.1050.0970.0890.0830.0770.072900 — — 0.039 0.064
1000 — — 0.035 0.058*Uncoated – without tin or lead covering
The resistance values of the different conductor sizes inTable 6 are applicable only when Direct Current (DC) isflowing through the conductors.
Power Cables & Wires Technical Manual
19
5.4 Conductor AC Resistance
When Alternating Current (AC), at sixty Hertz (60 Hz), is flowingthrough said conductors, the DC resistance values have to bemultiplied with the corresponding correction factor (Table 7) toobtain the AC resistance values of the different conductor sizes.
Table 7 - Multiplying Factors for Converting D.C. to A.C.Resistance
Size
Multiplying FactorFor Non-metallic SheathedCables in Air or Non-metallic Conduit
For Metallic SheathedCables or all Cables inMetallic Raceways
Copper Aluminum Copper AluminumUp to 32100000000002503003504005006007007508001000
1.0001.0001.0001.0011.0011.0021.0041.0051.0061.0091.0111.0181.0251.0341.0391.0441.067
1.0001.0001.0001.0001.0011.0011.0021.0021.0031.0041.0051.0071.0101.0131.0151.0171.026
1.001.011.011.021.031.041.051.061.071.081.101.131.161.191.211.221.30
1.001.001.001.001.001.011.011.021.021.031.041.061.081.111.121.141.19
1250150017502000
1.1021.1421.1851.233
1.0401.0581.0791.100
1.411.531.671.82
1.271.361.461.56
Power Cables & Wires Technical Manual
20
If a conductor is carrying high alternating current, the distribution ofthe current is not evenly distributed throughout the cross-sectionof the conductor. This is due to two independent effects known as“Skin Effect” and “Proximity Effect”.
5.4.1 Skin effect
Skin Effect is a natural phenomena in wires wherein alternatingelectric current (AC) tends to distribute itself within a conductorso that the current density near the surface of the conductor isgreater than at its core. That is, the electric current tends to flowat the “skin” of the conductor, at an average depth called theskin depth. The skin effect causes the effective resistance of theconductor to increase with the frequency of the current. Thehigher the frequency the smaller is the skin depth. The skineffect is due to eddy currents set up by the AC current. Themagnitude of the skin effect is influenced by the frequency, thesize of the conductor, the amount of current flowing, and thediameter of the conductor.
Skin depth varies as the inverse square root of the conductivityof the conductor material. This means that better conductorshave a reduced skin depth. The overall resistance of the betterconductor material is lower even though the skin depth is less.This tends to reduce the difference in high frequency resistancebetween metals of different conductivity. At 60 Hertz (Hz) incopper, skin depth is about a centimeter. At higher frequencies,skin depth is much smaller.
Likewise, skin depth also varies as the inverse square root of thepermeability (which is a macroscopic material property thatrelates or is the ratio of the magnetic flux density to the strengthof the magnetic field that induces it) of the conductor material.In the case of iron, its conductivity is about 1/7 that of copper.Its permeability, however, is about 10,000 times greater. Theskin depth of iron is about 1/38 that of copper or about220 micrometers at 60 Hz. Iron wire, therefore, is worthless as aconductor at power line frequencies.
Methods to minimize skin effect include using specially woven(braided) cable/wire and using hollow pipe-shaped conductors.
Power Cables & Wires Technical Manual
21
5.4.2 Proximity Effect
The Proximity Effect is associated with the magnetic fields oftwo conductors, which are close together. If each carries acurrent in the same direction, the halves of the conductor inclose proximity are cut by more magnetic flux than the remotehalves. Consequently, the current distribution is not eventhroughout the cross-section, a greater proportion being carriedby the remote halves. If the currents are in opposite direction,the halves in closer proximity carry the greater density ofcurrent. In both cases, the overall effect results in an increase inthe effective resistance of the conductor. The proximity effectdecreases with the increase in the spacing between cables.
Skin and Proximity Effects can be ignored with smallconductors carrying low currents. They become increasinglysignificant with larger conductors and it is often desirable fortechnical and economic reasons to design theconductors/cables to minimize them. Values of skin andproximity effects can be computed based on the formulasprovided by IEC 60287-1-1.
5.5 Cables in Magnetic Metal Conduit
Due to excessive hysteresis and eddy currents, all phases of an ACcircuit should be installed in the same magnetic metal conduits.Never install individual phases in separate metal conduits under anycircumstances due to the high inductance of such installation. Also,separate phases should not pass through magnetic structures sinceoverheating would occur in such situation. All phases should passthrough a magnetic enclosure together in order that there will be acancellation of the resultant magnetic field. However, the proximityof the magnetic material will increase the skin and proximity effect.Thus, there can be significant losses when large conductors are nearmagnetic materials.
Large cable sizes from 100 mm2 or larger should not be installed inseparate non-magnetic metal conduit due to the high circulatingcurrents in the conduit. The ampacity of the cables should be de-rated in such condition.
Power Cables & Wires Technical Manual
22
5.6 Resistance at Higher Frequency
Ampacity and resistance of cables to be operated at frequencieshigher than 60 hertz should be corrected. The inductive reactanceincreases at high frequencies which may affect the voltage drop.Insulated conductors should not be installed in metallic conduits orrun close to magnetic materials.
The correction factor for the resistance at frequencies other than 60hertz is provided as follows:
where, f = frequency in hertzRdc = conductor DC resistance at operating temperature
in Ohm/1000 ft
6. INSULATION
Insulation is that part of the cable or wire which is relied upon toinsulate the conductor from other conductors or conducting parts orfrom ground. Insulating materials are usually classified according to thetemperature they are able to withstand. The applied insulation mustperform adequately in the specified temperature range and its dielectricstrength should be sufficient to sustain the electrical stresses.
There are many insulating materials used in producing the variouscables to deliver electric power depending on their temperature limits,such as cotton, silk, paper, mica, glass fiber, asbestos, rubber, siliconeelastomer, etc. Sometimes insulating materials, such as cotton, silk andpaper are impregnated or coated with a dielectric liquid, such as oil, toenhance their insulating capabilities.
Power Cables & Wires Technical Manual
23
Cable insulation should have the following properties:
1. High Dielectric strength2. Low Dielectric Constant3. Good mechanical capability4. Resistance to ageing5. High temperature withstandability
In recent times, synthetic polymers have replaced natural materials suchas paper, mineral oil and natural rubber for the insulation of wires/cablesand for the over-sheathing of cables. The range of polymers available isextensive and variations in chemical composition enable specificmechanical, electrical and thermal properties to be obtained. Whereappropriate, these properties may be further modified by the addition ofspecific fillers, plasticizers, softness extenders, colorants, antioxidantsand many other ingredients.
In the cable industry, the term polymeric material is taken to signifypolymers which are rubbers or plastics. Rubbers are considered to besolid materials, with elastic properties, which are made from latexderived from living plants or synthetically and used in themanufacture of rubber products. Plastics, on the other hand, arematerials based on synthetic or modified natural polymers which atsome stage of manufacture can be formed to shape by flow, aided inmany cases by heat and pressure. These two material groups are thedominant means of insulating wires and cables.
6.1 Elastomers
An elastomer is a material which returns rapidly to approximately itsinitial shape after substantial deformation at room temperature by aweak stress and release of that stress. In cable technology, the terms“rubber” and “elastomer” are used synonymously andinterchangeably, although “rubber” to some implies “natural rubber”.
Elastomeric materials are used for insulation and sheaths. They areapplied mainly where the product has to be particularly flexible. Awide range of elastomers are nowadays available to the cableindustry. This makes possible the manufacture of compoundswith specific properties, such as abrasion and oil resistance,
Power Cables & Wires Technical Manual
24
weather and heat resistance, and flame resistance, combined withgood electrical and mechanical characteristics.
The classical elastomeric material, natural rubber (NR), was thefirst insulation to be used in the manufacture of electric cable. Its useas an insulation has been declining in recent years. Rubber gave wayto other insulating materials like impregnated paper, PVC, XLPE,etc. Rubber, though, is still considered the preferredinsulation for flexible cables and cables where very small bendingdiameter is desired. Rubbers for cable insulation and sheath,whether natural or synthetic, are normally crosslinked.
In place of rubber, synthetic elastomers produced by the co-polymerization of ethylene and propylene, are constantly findingnew areas of application in cable engineering. These co-polymers are generally known as Ethylene-propylene rubber (EPR).Because of its superior performance, with suitability for continuousoperation at 90°C, EPR has gradually displaced butyl rubber forinsulation and is now being considered as over sheath material forcable.
Polychloroprene (PCP), otherwise known as neoprene, was the firstcommercial synthetic rubber. It has rarely been used by itself forinsulation but is often used blended with natural rubber. Its majoruse is as a very tough flexible sheathing material.Polychloroprene compounds have good abrasion and tearresistance together with good resistance to swelling and to chemicalattack by a wide range of natural oils and aliphatic hydrocarbons.They do not normally support combustion
Chlorosulphonated polyethylene rubber (CSP, CSM) havesuperior electrical properties to compounds based on PCP and areparticularly advantageous for insulation and sheathing which isrequired to be oil resistant. CSP also has good resistance to ozoneand weathering. When blended with EVA or EPR and filled with asuitable carbon black, CSP compounds provide a strippabledielectric screening material for XLPE and EPR cables in the 10-30kV range.
Power Cables & Wires Technical Manual
25
Acrylonitrile-butadiene rubber (NBR/PVC blends) is theproduct of the co-polymerization of acrylonitrile with butadiene.This range of polymers is characterized by good oil resistance. Theaddition of PVC improves resistance to ozone, weathering andabrasion. By suitable choice of plasticizers, improvedprocessability and flame retardance are also obtained. Thesematerials are used solely for sheathing.
Fluorocarbon rubbers find application for sheathing where verygood resistance to oils is required at high temperatures. The bestknown material is a copolymer of vinylidene fluoride andhexafluoropropylene (Viton).
Ethylene-acrylic elastomers (EMA) are heat- and oil-resistantnon-halogen synthetic rubbers which can be compounded toresist ignition in the presence of flame and have low smokegeneration when burned. They are suitable for servicetemperatures of 40-170°C.
Silicone rubber is a material made from silicon and oxygen noted forhigh heat resistance. This is very soft thermoset insulation extremelyflexible and fire resistant. It has excellent electrical properties plusozone and resistance, low moisture absorption, weather resistance,and radiation resistance. It typically has low mechanical strength andpoor scratch resistance.
Table 8 shows the properties of thermoset insulation and jacketmaterials
Power Cables & Wires Technical Manual
26
Table 8: Properties of Thermoset Insulation and Jacket Materials
INSULATION ORJACKETMATERIAL
ST
YR
EN
EB
UT
AD
IEN
ER
UB
BE
R(S
BR
)
NA
TU
RA
LR
UB
BE
R
SY
NT
HE
TIC
RU
BB
ER
PO
LY
BU
TA
DIE
NE
NE
OP
RE
NE
HY
PA
LO
NC
HL
OR
OS
UL
FO
NA
TE
DP
OL
YE
TH
YL
EN
E(C
SP
E)
NIT
RIL
EO
RR
UB
BE
RB
UT
AD
IEN
EN
ITR
ILE
(NB
R)
NIT
RIL
E//
PO
LY
CH
LO
RID
E(N
BR
/PV
C)
ET
HY
LE
NE
PR
OP
YL
EN
ER
UB
BE
R(E
PR
)
CR
OS
S-L
INK
ED
PO
LY
ET
HY
LE
NE
(XL
PE
)
CH
LO
RIN
AT
ED
PO
LY
ET
HY
LE
NE
(CP
E)
SIL
ICO
NE
RU
BB
ER
Oxidation Resistance F F G G G E F E E E E E
Heat Resistance F-G F F F G E G G E G E O
Oil Resistance P P P P G G G-E G P G G-E F-G
Low Temp. Flexibility F-G G E E F-G F F F G-E O F O
Weather, SunResistance
F F F F G E F-G G E G E O
Ozone Resistance P P P P G E P G E G G-E O
Abrasion Resistance G-E E E E G-E G G-E E G F-G G-E P
Electrical Properties E E E E P G P F E E F-G O
Flame Resistance P P P P G G P G P P G O
Nuclear RadiationResistance
F-G F-G F-G P F-G E F-G P G E G E
Water Resistance G-E G-E E E E E G-E E G-E G-E G-E G-E
Acid Resistance F-G F-G F-G F-G G E G G G-E G-E E F-G
Alkali Resistance F-G F-G F-G F-G G E F-G G G-E G-E E F-G
Gasoline, Kerosene,Etc. (AliphaticHydrocarbons)Resistance
P P P P G F E G-E P F F P-F
Benzol, Toluol, Etc.(AromaticHydrocarbons)Resistance
P P P P P-F F G G F F F P
Degreaser Solvents(HalogenatedHydrocarbons)Resistance
P P P P P P-F P G P F P P-G
Alcohol Resistance F G G F-G F G E G P E G-E G
P = Poor F = Fair G = Good E = Excellent O = Outstanding
Power Cables & Wires Technical Manual
27
6.2 Plastics
Plastics may be further divided into thermoplastics and thermosets.A thermoplastic is a material in which the molecules are heldtogether by physical rather than chemical bonds. This means thatonce the material is above its melting point it can flow. The processis reversible and upon cooling the material hardens. The moleculesin a thermoset are held together by chemical bonds which are noteasily broken. This means that on heating the polymer does notsoften sufficiently to be reshaped. Typical examples are crosslinkedpolyethylene (XLPE) and elastomers. Unlike thermoplastics,thermosets are insoluble and infusible, i.e. it will not fuse together.Many thermoplastics may be converted to thermosets by appropriatetreatment to induce “crosslinking”, e.g. by the addition of a suitablechemical crosslinking agent or by irradiation.
6.2.1 Thermoplastics
Thermoplastics are the most popular insulating materials for lowvoltage wires and cables due to lower in cost and lighter weight.Some of the most popularly used are discuss below.
Polyvinyl Chloride (PVC)
Polyvinyl Chloride, also called vinyl, is a thermoplastic materialintroduced in 1932. Since then, PVC has become the standardinsulation used on wires and cables rated at 1000 volts or less.Vinyl compounds are mechanical mixtures of PVC resin,plasticizers, fillers, stabilizers, and modifiers. The quantity andtype of each ingredient determines the final properties of thecompound.
PVC compounds can be formatted to provide a broad range ofproperties from the standpoint of electrical, physical andchemical characteristics. However, in achieving superiority inone property, the other properties are usually compromised. Thegoal, therefore, is to optimize the critical property or propertieswithout allowing secondary properties to fall below acceptablelevels.
Power Cables & Wires Technical Manual
28
PVC has a high dielectric strength and good insulationresistance. It is inherently tough and resistant to flame, moistureand abrasion. Resistance to ozone, acids, alkalis, alcohols, andmost solvents are also adequate. PVC compounds can be maderesistant to oils and gasoline. Its temperature ratings range from60°C to 105°C based on basic formulation.
Disadvantage of PVC include a relatively high dielectricconstant and dissipation factor. Plasticizer loss throughevaporation or leeching eventually may cause embrittlement andcracking. PVC compounds significantly stiffen as temperaturesdecline, and are not generally recommended for uses whichrequire flexing below -10°C. However, special formulationshave been developed which will allow flexing to up to -40°C.
Polyethylene
Polyethylene is a long chain hydrocarbon thermoplastic materialwhich is produced by the polymerization of ethylene gas underhigh or low pressure. PE is popular because of its relatively lowprice, processability, resistance to chemicals and moisture,electrical properties, and low temperature flexibility. PE isproduced in low, linear low, medium, and high densities. As thedensity increases, so does the hardness, yield strength, stiffness,heat, and chemical resistance.
PE’s electrical properties are excellent. Typical values for anatural, unfilled insulation compound include a volumeresistivity of greater than 1016 ohm-cm, a dielectric constant of2.3, a dissipation factor of 0.0002, and a water absorption of lessthan 0.1%. However, if PE cables are exposed to sunlight,carbon black or a suitable inhibitor is added to screen out ultra-violet (UV) radiation. UV radiation can degrade both thephysical and electrical properties of the insulation.
A disadvantage of PE is that, like most plastics, it is susceptibleto degradation from treeing when it is subjected, to highelectrical stress. Treeing is a phenomenon occurring within thecable, when subjected to medium to high voltages, wherein the
Power Cables & Wires Technical Manual
29
breakdown of the insulation due to ionization occurs through theformation of carbonaceous “fronds” on the insulation due to thepresence of water or voids during the extrusion of the insulationmaterial at cable construction. The carbonaceous paths start at analmost imperceptible carbon core, generally at the conductorsurface, and gradually spread outwards through the insulation,increasing in width and complexity as progression takes place.Corona discharges and treeing may lead to premature cablefailure.
Polypropylene
Polypropylene is a thermoplastic insulating compound withcharacteristics similar to high density polyethylene withimproved heat resistance, tensile strength, and abrasionresistance. Polypropylene also has a lower specific gravity andlower dielectric constant than polyethylene. Polypropylene hasgood impact strength, low moisture absorption, excellentchemical resistance, high creepage resistance, and is useful inhigh frequency applications. It retains these excellent propertiesin cellular constructions. Typically, it is harder thanpolyethylene. This makes it suitable for thin wall insulations.
Polyurethane
Polyurethane is a broad class of polymers noted for goodabrasion and solvent resistance which can be in solid or cellularform. This thermoplastic material is used primarily as a cablejacket material. It has excellent oxidation, oil, and ozoneresistance. Some formulations also have good flame resistance. Itis a hard material with excellent abrasion resistance. It hasoutstanding "memory" properties, making it an ideal jacketmaterial for retractile cords.
Teflon
Teflon is an extremely reliable high temperature, low voltageinsulation often chosen for its non-aging characteristics, thinwall insulating capability, resistance to chemicals and abrasionresistance. Also, important is its low dielectric constant and low
Power Cables & Wires Technical Manual
30
power factor. There are two (2) types-Tetrafluorethylene TFE,and Fluorinatedethylenepropylene FEP. Teflon is not damagedby normal soldering operations. It is not suitable when subjectedto nuclear radiation and does not have good high voltagecharacteristics.TFE insulation in tape form (often fused) iswidely used and can be provided in very long lengths. Type FEPcan be extruded in long, continuous lengths and is readily colorcoded for use in control and instrumentation cables.
Tefzel
Tefzel ETFE is a melt processible fluorocarbon thermoplasticcombining many of the desirable properties of Teflon and Kynarrated at 150°C. Mechanically it is tough with excellent flex life,impact, cut-through, abrasion and weather resistant. Electricallyit is an excellent low loss dielectric and has outstanding electricalproperties. It is inert to most solvents and chemicals and ishydrolytically stable. Like irradiated polyethylene, it hasexcellent resistance to high-energy radiation.
Table 9 shows the properties of thermoplastic insulation andjacket materials.
Power Cables & Wires Technical Manual
31
Table 9: Properties of Thermoplastic Insulation and Jacket Materials
INSULATION ORJACKETMATERIAL
PO
LY
VIN
YL
CH
LO
RID
E(P
VC
)
LO
W-D
EN
SIT
YP
OL
YT
HY
LE
NE
CE
LL
UL
AR
PO
LY
TH
YL
EN
E
HIG
H-D
EN
SIT
YP
OL
YT
HY
LE
NE
PO
LY
PR
OP
YL
EN
E
CE
LL
UL
AR
PO
LY
PR
OP
YL
EN
E
PO
LY
UT
ET
HA
NE
NY
LO
N
CP
E
TE
FL
ON
(FE
P)
TE
FL
ON
(TP
E)
TE
FZ
EL
(ET
FE
)
Oxidation Resistance E E E E E E E E E O O E
Heat Resistance G-E G G E E E G E E O O E
Oil Resistance F G-E G G-E F F E E E O E-O E
Low Temp.Flexibility
P-G E E E P P G G E O O E
Weather, SunResistance
G-E E E E E E G E E O O E
Ozone Resistance E E E E E E E E E E O E
Abrasion Resistance F-G G F E F-G F-G O E E-O E O E
Electrical Properties F-G E E E E E P P E E E E
Flame Resistance E P P P P P P P E O E G
Nuclear RadiationResistance
F G-E G G-E F F G F-G O P-G P E
Water Resistance F-G E E E E E P-G P-F O E E E
Acid Resistance G-E G-E G-E E E E F P-E E E E E
Alkali Resistance G-E G-E G-E E E E F E E E E E
Gasoline, Kerosene,Etc. (AliphaticHydrocarbons)Resistance
P G-E G G-E P-F P P-G G E E E E
Benzol, Toluol, Etc.(AromaticHydrocarbons)Resistance
P-F P P P P-F P P-G G G-E E E E
Degreaser Solvents(HalogenatedHydrocarbons)Resistance
P-F G G G P P P-G G E E E E
Alcohol Resistance G-E E E E E E P-G P E E E E
P = Poor F = Fair G = Good E = Excellent O = Outstanding
Power Cables & Wires Technical Manual
32
6.2.2 Thermosetting
Most plastic insulations are thermoplastics, except forcrosslinked polyethylene which is the predominant insulation formedium and high voltage cables. Other thermosetting insulationmaterials are elastomers.
Crosslinked Polyethylene (XLPE)
Crosslinked polyethylene is a thermoset material produced bycompounding polyethylene or a copolymer of ethylene and vinylacetate (EVA) with a crosslinking agent, usually an organicperoxide. The individual molecules of polyethylene join togetherduring a curing process to form an interconnected network. Theterms “cure” and “vulcanize” are often similarly used todesignate crosslinking.
While the use of peroxide as the crosslinking agent means thatonly low density polyethylene can operate at higher temperaturesthan cables produced with thermoplastic or non-crosslinkedpolyethylene.
Crosslinking also significantly improves the physical propertiesof the polyethylene. Additives tend to reduce the electricalproperties of the insulation. This is the reason that EVAcopolymer is used only for low voltage applications. For mediumvoltage applications, crosslinked polyethylene fares well becausethe dielectric strength of the unfilled crosslinked polyethylene isabout the same as that of thermoplastic polyethylene. Impulsestrengths of 2700 V/mil are common.
For low voltage applications, the addition of fillers, in particular,medium thermal carbon black, provides increases in tensilestrength and hardness. It also provides the necessary ultravioletprotection for outdoor applications without the use of a jacket.The EVA copolymer is well suited to accepting up to a 30%loading of medium thermal carbon black. Between 2 and 3percent of very small particle size furnace carbon black isincorporated into the polyethylene if sunlight resistance isrequired without significantly reducing the electrical properties.
Power Cables & Wires Technical Manual
33
XLPE insulated cables may be operated continuously at aconductor temperature of 90°C and intermittently at 130°Cduring emergency conditions. XLPE has good low temperatureproperties, shows increased resistance to corona when comparedwith thermoplastic polyethylene, and has good impact, abrasion,and environmental stress crack resistance.
Recent technology has resulted in XLPE insulation compoundsthat are resistant to degradation from treeing. Two processes areavailable for imparting tree resistance to the compound. Oneinvolves additives and the other involves copolymer technology.Additives tend to reduce the electrical properties of thepolyethylene insulation and one finds slightly lower values fordielectric strength and slightly higher dissipation factor whencomparing the tree retardant insulations to the standard material.
For general purpose low voltage cables, it is possible toincorporate up to 30% calcium carbonate into XLPE to reducethe cost. However, to maintain the best electrical properties,especially when immersed in water, the filled compound shouldnot be used.
In the Philippines, compounds incorporating approximately 30%thermal carbon black are used. These have the advantage ofimproved resistance to hot deformation and cut-throughresistance.
6.3 Insulation Resistance
In order that a reasonable factor of safety may be provided, thefollowing insulation resistance is suggested as a guide, where theinsulation is subjected to test:
a) For circuits of 2.0 mm2 or 3.5 mm2 conductors – 500,000ohms;
b) For circuits of 5.5 mm2 or larger conductors, a resistancebased upon the allowable ampacity of conductors asfollows:
Power Cables & Wires Technical Manual
34
-70
-65
-40
-40
-40
-60
-40
-40
-60
-55
-20
260
200
105
105
105
150
130
105
80
105
80
-100 0 100 200 300
Teflon
Silicone Rubber
CPE
EVA
Hypalon (CSPE)
EPR
XLPE
Polypropylene
Polythylene
PVC (Premium)
PVC (Standard)
25 to 50 amperes, inclusive 250,000 ohms51 to 100 amperes, inclusive 100,000 ohms101 to 200 amperes, inclusive 50,000 ohms201 to 400 amperes, inclusive 25,000 ohms401 to 800 amperes, inclusive 12,000 ohmsOver 800 amperes 5,000 ohms
The above listed values shall apply to installations withvoltage of 600 V or less. For voltages above 600 V, theminimum insulation resistance shall be 1,000,000 ohms perthousand volts or a fraction thereof. The foregoing is to bedetermined with all fixtures, switches, receptacles, andwiring devices in place and connected.
c) Where climatic conditions are such that the wiring orequipment is exposed to excessive humidity, it may benecessary to modify the foregoing provisions.
6.4 Thermal Characteristics
Selection of the right insulation materials depends on the expectedoperating temperature which the wire or cable will be subjected. Thenominal operating temperature in °C of some the insulation materialsare shown in Figure 2, below.
Figure 2: Nominal Temperature Range of Wire Insulations in °C
Power Cables & Wires Technical Manual
35
7. CABLE DESIGN AND CONSTRUCTION
An insulated cable appears to be a relatively simple electrical device but,in fact, it can be considered an electrical system with many components.To understand it, let us examine its components and basics of operation.For simplicity, the following discussion shall be confined to a singleconductor cable. However, these fundamentals also apply to multiple-conductor cables.
The basic components of an insulated cable are the following:
a) Conductor – materials that transmits electrical energyb) Shielding – also referred to as screening, are used for medium to
high voltage cables. Basically, the use of this stress controllayers is to achieve a symmetrical dielectric fields within thecable structure. For some voltage levels, shielding may beapplied over the conductor. At higher voltage levels, it is appliedover the conductor and the insulation. This results in theconfining of all the voltage gradients to within the cablestructure if the shield over the insulation is essentially atground potential.
c) Primary Insulation or Dielectric – prevents leakage of currentfrom the conductor to the surroundings. It protects life andprevents damage resulting from electrical discharge. It alsophysically protects the conductor.
d) Jacket – also called sheaths, serve several purposes such as theyprovide mechanical, thermal, chemical, and environmentalprotection to the insulated conductors they enclosed, act aselectrical insulation when used over shields or armor, easeinstallation and routing concerns by enclosing multiple insulatedconductors. They may also protect the characteristics of theunderlying insulation. For example, a thin nylon jacket overPVC enhances the abrasion and fluid resistance of a 600V cable.Sheathing may also include various forms of metallic armoring,tapes, or wires to enhance the physical properties of the cableand to provide a built-in protective electrically grounded conduitfor the insulated conductors. Commonly used jacketing materialsinclude extrusions of PE, PVC and Nylon. PVC, Nylon and PE
Power Cables & Wires Technical Manual
36
are applied using thermoplastic extrusion lines which heat thematerial to the melting point and form it over the core. Thematerial is then cooled, usually in a water trough, and woundonto a reel. Some heat is used to soften the material so that it canbe formed around the core. It is then necessary to crosslink thematerial to obtain its full properties.
Depending on the customer requirement and/or the application, a cablemay be composed of a couple of the above-stated components or all of it.For special cases, additional sheathing or armoring may be required.
An illustration of the construction and components of a medium voltagepower cable is shown below.
Figure 3: Construction of a Medium Voltage Power Cable
8. LOW VOLTAGE WIRES AND CABLES
Classification of voltage level seems to be arbitrary in most cases sincemany standard governing bodies in the world do not agree as to thedivisions in the voltage level. IEC define low voltage as those 1000 voltsand below while ICEA define low voltage to be 2000 volts and below.NEC and IEEE define low voltage as 600 volts and below.
Primarily all low voltage wires and cables are insulated except thoseused as neutral or grounding wire. With reference to their cableconstruction, they are non-shielded cable.
Power Cables & Wires Technical Manual
37
There are two basic components in a non-shielded cable. They are theconductor and the electrical insulation, sometimes referred to as thedielectric. A third component used in some cable designs is an outerjacket. The figure below shows the construction of a low-voltage non-shielded cable.
Figure 4: Low-Voltage Non-Shielded Cable Construction
Conductor
The conductor material can be copper or aluminum with either a solid orstranded.
The primary reason for the use of stranded conductors is improvedflexibility. The stranded conductors can be compressed or compacted toachieve desired flexibility, diameter, and load current density. For theconductor size, there are diameter differences between solid and thevarious types of stranded conductors. This is an important considerationin the selection of connectors and in the methods of splicing andterminating.
Electrical Insulation or Dielectric
The electrical insulation must provide adequate physical and electricalprotection between the energized conductor and the nearest electricalground to prevent electrical breakdowns. For low voltage cables, 600volts and below, the insulation thickness required to provide the necessaryphysical protection against damage is more than adequate to provide thenecessary dielectric strength.
Power Cables & Wires Technical Manual
38
Electrostatic Flux Lines Equipotential Lines
Another consideration in the design and application of cables is thedielectric field. In all electrical cables, irrespective of their voltageratings, there is a dielectric field present when the conductor is energized.This dielectric field is typically represented by electrostatic flux lines andequipotential lines between the conductor and electrical ground.
When a conductor is energized there are electrostatic lines of flux createdwithin the dielectric. The density of these flux lines is dependent upon themagnitude of the potential difference between the conductor and electricalground.The distance between the equipotential lines represents a voltagedifferential in the insulation. For a given voltage differential, these linesare closer together nearer the conductor.
Figure 5: Electrical Field of a Non-Shielded Cable
Above figure represents the electrical field of a non-shielded cable’scontact with a ground plane. It does not take into account the difference inthe dielectric constants of the insulation and the surrounding air.
Observe that the electrostatic flux lines are crowded in the insulationclosest to the ground. Also, the equipotential lines are eccentric in theirrelationship to the conductor and the cable dielectric surface. Thisdistortion of the fields is acceptable if the dielectric strength of thecable insulation is adequate to resist the concentration of the dielectricstresses. Low voltage non-shielded cables are usually designed to meetthis requirement.
Jacket/Sheaths
For special applications, a jacket is applied over the insulation. There areseveral materials available for use as jackets to provide the necessarychemical, physical, or thermal protection required by the application.
Power Cables & Wires Technical Manual
39
Low voltage wires and cables are primarily divided into two majorgroups, the building wires and secondary and service drop wires.
8.1 Building Wires
Building wires comprises the largest group of low voltage wires andcables which is primarily used in all residential, commercial andindustrial buildings. In the Philippines, the most common types ofthese building wires are the following:
8.1.1 Building Wires Types and Application
TW (Thermoplastic Moisture-Resistant)
The TW conductors are solid or stranded annealed (soft) copper,insulated with a moisture resistant and flame retardant polyvinylcompound (PVC). TW wire is used in interior wiring at circuitvoltages up to 600 volts. Maximum operating temperature is60°C in dry or wet application. Type TW building wire is used inresidential, commercial and industrial buildings for general-purpose lighting, appliance, power, control and relay panelapplications. It is used for low ampacity rated circuits. This typeof wire may be installed in conduits, ducts or raceways. Type TWwire is also suitable for installations in ambient temperaturesdown to -10°C.
THW (Thermoplastic Heat and Moisture Resistant)
The THW conductors are solid or stranded annealed (soft)copper, insulated with a tough heat and moisture resistant, andflame retardant polyvinyl compound (PVC). It is used in interiorwiring at circuit voltages up to 600 volts. Maximum operatingtemperature is 75°C in dry or wet application. It can be used forgeneral-purpose lighting, appliance, power, control and relaypanel applications. It is also applicable as machine tool wire andappliance wiring material. It is used for medium ampacity ratedcircuits. This type of wire may be installed in conduits, ducts orraceways.
Power Cables & Wires Technical Manual
40
THHN/THWN (Thermoplastic Heat and Moisture Resistant Wirewith Nylon Jacket)
The THHN/THWN conductors are solid or stranded annealed(soft) copper, insulated with a tough heat and moisture resistant,and flame retardant polyvinyl compound (PVC) with oil,chemical, and abrasion resistant nylon (polyamide) jacket. It isused in interior wiring at circuit voltages up to 600 volts.Maximum operating temperature is 90°C for dry applications(THHN) and 75°C for wet applications (THWN). It can be usedfor general-purpose lighting, power, control and relay panelapplications. It is also applicable for machine tool wire andappliance wiring material. It is used for high ampacity ratedcircuits. This type of wire may be installed in conduits, ducts orraceways.
The other types of conductor applications and insulations areshown in Annex B.
8.1.2 Building Wires Sizes and AmpacitySize and ampacity of building wires are given in Tables 10 and11, with reference to the Philippines Electrical Code based on anambient temperature of 30°C. Use appropriate correction factorspecified in the Philippine Electrical Code for ambienttemperature other than 30°C.
Power Cables & Wires Technical Manual
41
Table 10: Allowable Ampacities of Single-Insulated Conductors Rated0 Through 2 000 Volts in Free Air, Based on Ambient AirTemperature of 30°C
ConductorSizemm2
(mm dia.)
Temperature Rating of Conductor60°C 75°C 90°C 60°C 75°C 90°C
TypesTW,UF
TypesRHW,
THHW,THW,
THWN,XHHW,
ZW
TypesTBS, SA,SIS, FEP,
FEPB,MI,
RHH,RHW-2,THHN,THHW,THW-2,
TypesTW,UF
TypesRHW,
THHW,THW,
THWN,XHHW
TypesTBS, SA,
SIS, RHH,RHW-2,THHN,THHW,THW-2,
THWN-2,USE-2,XHH,
COPPER ALUMINUM
2 (1.6)3.5 (2)
5.5 (2.6)8 (3.2)
25304055
30355065
35405575
-253545
-304050
-354055
14223038
80105130155
95130160185
105140170195
658595115
80105115135
85115130155
506080
100
180205250290
220250300355
235260320370
135155185220
165185225265
185210255295
125150175200250
335375410440505
400440495540620
420475560570655
260295325345405
310355390410485
350400440465545
325375400500
600645675770
720775810930
770875875995
475510530620
560615640745
640690725835
Power Cables & Wires Technical Manual
42
Table 11: Allowable Ampacities of Insulated Conductors Rated 0Through 2 000 Volts, 60°C Through 90°C. Not More ThanThree Current-Carrying Conductors in Raceway, Cable, orEarth (Directly Buried), Based on Ambient Temperature of30°C
ConductorSize mm2
(mm dia.)
Temperature Rating of Conductor
60°C 75°C 90°C 60°C 75°C 90°C
TypesTW, UF
Types RHW,THHW,THW,
THWN,XHHW, ZW
Types TBS,SA, SIS, FEP,
FEPB, MI,RHH, RHW-
2, THHN,THHW,THW-2,
THWN-2,USE-2, XHH,
XHHW,XHHW-2,
ZW-2Types
TW, UF
Types RHW,THHW,THW,
THWN,XHHW
Types TBS,SA, SIS,
RHH, RHW-2, THHN,THHW,THW-2,
THWN-2,USE-2, XHH,
XHHW,XHHW-2,
ZW-2
COPPER ALUMINUM
2 (1.6)3.5 (2)
5.5 (2.6)8 (3.2)
20253040
20253550
25304055
-202530
-203040
-253545
14223038
557090
100
6585
110125
7090115130
40556575
50658090
658090
105
506080100
120135160180
145160195220
150170205225
95100120140
110120145170
125135165190
125150175200250
210240260280315
255280305330375
265295345355400
165185205220255
200225245265305
225250275.300345
325375400500
370395405445
435470485540
470530515580
305315335370
365380405440
410430460495
Apply appropriate adjustment factors if more than three (3) current carrying conductors ina raceway or cable with reference to the Philippine Electrical Code.
Power Cables & Wires Technical Manual
43
8.1.3 Resistances and Reactances
Resistances and reactances of copper wires in magnetic and non-magnetic conduits are given by Table 12, below:
Table 12: Copper Conductor Resistance and Reactance Data Line-to-neutral, mΩ/100 meter
ConductorSize mm2
(mm dia.)
Three-Single Conductor CablesIn Magnetic Duct Not In Magnetic Duct
Resistance"R"
Reactance"X"
Resistance"R"
Reactance"X"
Solid2 (1.6) 846.24 24.63 846.24 19.483.5 (2) 528.08 22.83 528.08 18.075.5 (2.6) 331.28 22.11 331.28 17.528 (3.2) 216.15 19.88 216.15 15.91
Stranded8 222.71 19.45 222.71 15.5514 140.06 18.60 140.06 14.8922 88.23 17.38 88.23 13.9130 55.76 16.33 55.43 13.0538 44.28 16.53 43.95 13.2250 35.42 16.24 35.10 12.9960 28.21 15.84 27.88 12.6680 22.63 15.32 21.98 12.23100 17.81 14.86 17.48 11.87125 15.48 15.25 15.06 12.20150 12.96 14.83 12.46 11.84200 10.00 14.46 9.54 11.58250 8.20 14.17 7.71 11.35325 7.08 14.14 6.53 11.28400 5.94 13.94 5.35 11.15500 5.02 13.74 4.43 10.99
Note: Typical values, use exact values if available.
Power Cables & Wires Technical Manual
44
8.2 Secondary and Service Cables
These cables are used by Distribution Utilities in low voltage powerdistribution. Both cables have the same construction; the difference isin the application. Secondary cables are those that are connected tothe distribution transformer and traverses from pole to pole whileservice drop cables are those that connect the customer’s serviceentrance wires to the secondary cable or distribution transformer.
8.2.1 Overhead secondary and service cables
In the Philippines, majority of the distribution system areoverhead construction. Most overhead secondary and servicecables are multiplex cables with sizes that are typically based inAWG. Cables are insulated by either polyethylene (PE) orcrosslinked polyethylene (XLPE) material. Basically, these cablesare classified based on the number of conductors twisted together(e.g. duplex, triplex, and quadruplex cables).
8.2.2 Underground secondary and service cables
Underground secondary and service cables are conductorsinstalled in conduit or directly buried in the earth and enter thebuilding metering facilities, switch, or service equipment. TypeUSE service cables are similar in construction to the generalpower cables for direct burial in earth.
Tables 13 & 14 show the characteristics of the different types ofMultiplex Secondary and Services Copper and Aluminum Cables,respectively. While, Tables 15 & 16 show the characteristics ofthe types of Single Conductors for Underground Service forCopper and Aluminum, respectively.
Power Cables & Wires Technical Manual
45
Table 13. Copper Multiplex Secondary and Services Cables
Code Word
Phase Conductor NeutralCable
Weightper 1000ft (lbs)
Ampacity
Sizes(# of
wires)
InsulationThickness
(mils)
Sizes(# of
wires)
RatedStrength
(lbs.)PE XLPE
DUPLEX
Theta 8 (7) 45 10 (1) 529 95 70 85
Kappa 8 (7) 45 8 (7) 777 114 70 85
Sigma 6 (7) 45 6 (7) 1228 177 90 110
TRIPLEX
Pica 8 (7) 45 10 (1) 529 158 70 85
Garamond 8 (7) 45 8 (7) 777 177 70 85
Gothic 6 (7) 45 6 (7) 1228 273 90 110
Casion 4 (7) 45 4 (7) 1938 425 115 145
Primer 2 (7) 45 4 (7) 1938 588 155 195
Century 2 (7) 45 2 (7) 3050 664 155 195
Corinthian 1/0 (19) 60 1/0 (7) 4752 1055 205 265
Doric 2/0 (19) 60 2/0 (7) 5926 1319 235 300
QUADRUPLEX
Tallahassee 6 (7) 45 6 (7) 1228 369 75 95
Richmond 4 (7) 45 4 (7) 1938 573 100 125
Seattle 2 (7) 45 2 (7) 3050 893 135 170
Nashville 1/0 (19) 60 1/0 (7) 4752 1420 180 230
Lincoln 2/0 (19) 60 2/0 (7) 5926 1773 205 265
Raleigh 3/0 (19) 60 3/0 (7) 7366 2220 235 305
Denver 4/0 (19) 60 4/0 (7) 9154 2781 270 350
Ampacity figures for black insulation only. Based on conductor temperature of 75°C forpolyethylene insulated conductors, 90°C for XLPE insulated conductors, ambienttemperature of 40°C; 2 ft./sec. wind in sun. Source: Southwire
Power Cables & Wires Technical Manual
46
Table 14: Aluminum Multiplex Cables with ACSR Neutral Messenger
Code Word
Phase Conductor Neutral CableWeight
per1000 ft
(lbs)
Ampacity
Sizes(# of
wires)
InsulationThickness
(mils)
Sizes(Stranding)
RatedStrength
(lbs.)PE XLPE
DUPLEX
Shepherd 6 (7) 45 6 (6/1) 1190 75 70 85
Terrier 4 (7) 45 4 (6/1) 1860 115 90 115
Chow 2 (7) 45 2 (6/1) 2850 176 120 150
Bull 1/0 (9) 60 1/0 (6/1) 4380 280 160 205
TRIPLEX
Voluta 6 (7) 45 6 (6/1) 1190 114 70 85
Periwinkle 4 (7) 45 4 (6/1) 1860 172 90 115
Conch 2 (7) 45 2 (6/1) 2850 262 120 150
Neritina 1/0 (7) 60 1/0 (6/1) 4380 420 160 205
Cenia 1/0 (9) 60 1/0 (6/1) 4380 414 160 205
Runcina 2/0 (7) 60 2/0 (6/1) 5310 520 185 235
Triton 2/0 (11) 60 2/0 (6/1) 5310 512 185 235
Mursia 3/0 (17) 60 3/0 (6/1) 6620 635 215 275
Zuzara 4/0 (18) 60 4/0 (6/1) 8350 789 245 315
Limpet 336.4 (19) 60336.4(18/1)
8680 1167 325 420
QUADRUPLEX
Hackney 4 (7) 45 4 (6/1) 1860 229 80 100
Palomino 2 (7) 45 2 (6/1) 2850 347 105 135
Costena 1/0 (9) 60 1/0 (6/1) 4380 549 140 180
Grullo 2/0 (11) 60 2/0 (6/1) 5310 677 160 205
Suffolk 3/0 (17) 60 3/0 (6/1) 6620 837 185 235
Appaloosa 4/0 (18) 60 4/0 (6/1) 8350 1038 210 275
Bronco 336.4 (19) 60336.4(18/1)
8680 1568 280 370
Conductor temperature of 90°C for XLPE, 75°C for PE; ambient temperature of 40°C;emissivity 0.9; 2 ft./sec. wind in sun. Source: Southwire
Power Cables & Wires Technical Manual
47
Table 15: Single Copper Conductors for Underground Service
Size(AWG
orkcmil)
Numberof
Strands
CompositeInsulation-Thickness
(mils)
CompositeInsulation-Thickness
(mm)
Approx.O.D.
(Inches)
Approx.O.D.(mm)
Approx.Net
Weightper
1000 ft.(lbs)
Ampacity
90°C 75°C
14 1 45 1.14 0.16 4.06 23 15 15
14 7 45 1.14 0.17 4.57 25 15 15
12 1 45 1.14 0.18 4.57 32 20 20
12 7 45 1.14 0.19 4.83 34 20 20
10 1 45 1.14 0.2 5.08 46 30 30
10 7 45 1.14 0.21 5.33 48 30 30
8 7 60 1.52 0.27 6.86 77 55 50
6 7 75 1.91 0.34 8.64 123 75 65
4 7 75 1.91 0.38 9.75 176 95 85
2 7 75 1.91 0.43 11 257 130 115
1 19 100 2.54 0.52 13.16 349 150 130
1/0 19 100 2.54 0.56 14.1 413 170 150
2/0 19 100 2.54 0.6 15.14 509 195 175
3/0 19 100 2.54 0.64 16.33 622 225 200
4/0 19 100 2.54 0.7 17.68 766 260 230
250 37 130 3.3 0.81 20.57 944 290 255
350 37 130 3.3 0.91 23.04 1273 350 310
500 37 130 3.3 1.03 26.19 1764 430 380
750 61 145 3.68 1.28 32.51 2625 535 475
1000 61 145 3.68 1.44 36.58 3443 615 545
Source: Okonite
Power Cables & Wires Technical Manual
48
Table 16: Single Aluminum Conductor for Underground Service
Code WordSize
(# of Wires)
ConductorDiameter
(inch)
InsulationThickness
(inch)
InsulationDiameter
(inch)
TotalWeight
(lb/1000 ft)
Impedance (ohm/1000ft) *
AC Resistance InductiveReactance
@60Hz@ 75°C @ 90°C
CORNELL/XLP 8 (7) 0.141 0.06 0.26 34 1.28 1.35 0.047
PRINCETON/XLP 6 (7) 0.178 0.06 0.3 47 0.807 0.847 0.0447
MERCER/XLP 4 (7) 0.225 0.06 0.35 67 0.508 0.533 0.0426
CLEMSON/XLP 2 (7) 0.283 0.06 0.41 97 0.319 0.335 0.0409
KENYON/XLP 1 (19) 0.322 0.08 0.49 128 0.253 0.266 0.0411
HARVARD/XLP 1/0 (19) 0.362 0.08 0.52 154 0.201 0.211 0.0402
YALE/XLP 2/0 (19) 0.406 0.08 0.57 186 0.159 0.167 0.0394
TUFTS/XLP 3/0 (19) 0.456 0.08 0.62 225 0.126 0.133 0.0387
BELOIT/XLP 4/0 (19) 0.512 0.08 0.68 274 0.1 0.105 0.038
HOFSTRA/XLP 250 (37) 0.558 0.095 0.75 329 0.085 0.0892 0.0382
GONZAGA/XLP 300 (37) 0.611 0.095 0.81 385 0.071 0.0744 0.0377
RUTGERS/XLP 350 (37) 0.66 0.095 0.85 439 0.0609 0.0639 0.0373
DARTMOUTH/XLP 400 (37) 0.706 0.095 0.9 493 0.0534 0.056 0.0369
BROWN/XLP 450 (37) 0.749 0.095 0.94 547 0.0476 0.0499 0.0366
EMORY/XLP 500 (37) 0.789 0.095 0.98 601 0.0429 0.045 0.0364
DUKE/XLP 600 (61) 0.866 0.11 1.09 725 0.036 0.0377 0.0365
FURMAN/XLP 700 (61) 0.935 0.11 1.16 830 0.0311 0.0325 0.0362
SEWANEE/XLP 750 (61) 0.968 0.11 1.19 883 0.0291 0.0305 0.036
FORDHAM/XLP 1000 (61) 1.118 0.11 1.34 1144 0.0223 0.0233 0.0354
* At random (calculated as 1.5 x cable OD) spacing between conductors. Source: Nexans
Power Cables & Wires Technical Manual
49
9. MEDIUM AND HIGH VOLTAGE WIRES AND CABLES
There is no consensus among standard governing bodies like (i.e., IEC,ANSI, IEEE, UL, NEC and others) concerning the classification ofvoltage level. Thus, for clarity of this manual we will utilize IEEE voltagelevel classifications wherein 601 V to 69,000 V is medium voltage and69,001 V to 230,000 V is high voltage. Furthermore, conductors are alsoclassified according to their degree of insulation covering (i.e. bare,covered, and insulated). Basically, construction of the wires and cables isthe same or similar for medium and high voltage applications.
9.1 Bare Conductors
Bare conductors are those without covering and primarily used foroverhead power transmission and distribution application. Insulatingmedium is air wherein the conductors are spaced from each other andany grounded object based on the system voltage. Insulators (e.gporcelain, glass, and polymers) are used to support the conductors andinsulate these from the supporting structure such as tower or pole.
Copper and aluminum conductors are commonly used for thisapplication. However, there are instances where economics dictate theuse of conductors with low conductivity such as galvanized steel,copper-clad steel (Copperweld) or aluminum-clad steel (Alumoweld)in the distribution system. In such cases, the conductor losses arelower than the cost of recovering the investment in the distributionline if copper or aluminum conductor is used. In this field ofapplication, the most dominant conductor used by the industry is thealuminum conductor steel reinforced (ACSR).
The succeeding tables (i.e., 17 to 19) show the physical and electricaldata for copper and aluminum conductors.
Power Cables & Wires Technical Manual
50
Table 17: Bare Stranded Copper Wires Physical and Electrical Data
Size(AWG or
kcmil)
Stran-ding
StrandingClass
WeightPer 1000ft. (Ibs.)
Dia.(mils)
Hard-DrawnMedium-Hard
DrawnSoft-Drawn(Annealed)
AllowableAmpacityRated
Strength(lbs)
DC ResistanceOhms/1000 ft
@ 20°C
RatedStrength
(lbs)
DC ResistanceOhms/1000 ft
@ 20°C
RatedStrength
(lbs)
DC ResistanceOhms/1000 ft
@ 20°C
8 7 B 51 146 777 0.6663 610 0.6629 499 0.6408 95
6 7 B 81 184 1228 0.4191 959 0.4169 794 0.403 130
4 7 A, B 128.9 232 1938 0.2636 1505 0.2622 1320 0.2534 170
3 7 A, B 162.5 260 2433 0.209 1885 0.2079 1670 0.201 200
2 7 A, B 204.9 292 3050 0.166 2360 0.165 2110 0.1578 230
1 7 A 258.4 328 3801 0.1316 2955 0.1309 2552 0.1252 265
1/0 7 A, AA 326.1 368 4752 0.1042 3705 0.1037 3221 0.1002 310
1/0 19 B 326.1 373 4752 0.1042 3705 0.1037 3221 0.1002 310
2/0 7 A, AA 410.9 414 5926 0.08267 4640 0.08224 4062 0.07949 355
2/0 19 B 410.9 418 6690 0.08267 4765 0.08224 4024 0.07949 355
3/0 7 A, AA 518.1 464 7366 0.06556 5812 0.06522 5118 0.06304 410
4/0 7 A, AA 653.3 522 9154 0.05199 7278 0.05172 6459 0.04999 480
4/0 19 B 653.3 528 9617 0.05199 7479 0.05172 6453 0.04999 480
250 19 A 771.9 574 11360 0.044 8836 0.04378 7627 0.04231 530
250 37 B 771.9 575 11600 0.044 8952 0.04378 7940 0.04231 530
300 19 A 926.2 628 13510 0.03667 10530 0.03648 9160 0.03526 590
350 19 A 1080.6 679 15590 0.03143 12200 0.03127 10680 0.03022 650
500 37 A, B 1543.8 814 22510 0.022 17550 0.02189 15240 0.02116 810
600 37 A, AA 1852.5 891 27020 0.01834 21060 0.01825 18300 0.01763 910
750 61 A, B 2315.6 998 34090 0.01467 26510 0.01459 22890 0.0141 1040
1000 61 A, B 3087.5 1152 45030 0.011 35100 0.01094 30500 0.01058 1240
Ampacity based on 75°C conductor temperature; 25°C ambient temperature; 2 ft/sec wind in sun.Source: Southwire
Power Cables & Wires Technical Manual
51
Table 18: Aluminum Conductor Steel Reinforced (ACSR) Physical Data
Codeword
Size(AWG or
kcmil)
No. ofWires
Diameter (inch) Weight (lb/1000ft) RatedStrength
(lbs)Steel Wire Al WireSteelCore
CompleteConductor
Al Steel Total
Turkey 6 6/1 0.0661 0.0661 0.066 0.198 24.4 11.6 36 1190
Swan 4 6/1 0.0834 0.0834 0.083 0.25 39 18.4 57.4 1860
Swanate 4 7/1 0.1029 0.0772 0.103 0.257 39 28 67 2360
Sparrow 2 6/1 0.1052 0.1052 0.105 0.316 61.9 29.3 91.2 2850
Sparate 2 7/1 0.1299 0.0974 0.13 0.325 62.3 44.7 102 3640
Robin 1 6/1 0.1181 0.1181 0.118 0.355 78.1 36.9 115 3550
Raven 1/0 6/1 0.1327 0.1327 0.133 0.398 98.4 46.6 145 4380
Quail 2/0 6/1 0.1489 0.1489 0.149 0.447 124.2 58.8 183 5310
Pigeon 3/0 6/1 0.1672 0.1672 0.167 0.502 155.9 74.1 230 6620
Penguin 4/0 6/1 0.1878 0.1878 0.188 0.563 197.6 93.4 291 8350
Waxwing 266.8 18/1 0.1217 0.1217 0.122 0.609 249.8 39.2 289 6880
Partridge 266.8 26/7 0.0788 0.1013 0.236 0.642 250.4 115.6 366 11300
Merlin 336.4 18/1 0.1367 0.1367 0.137 0.684 315.5 49.5 365 8680
Linnet 336.4 26/7 0.0884 0.1137 0.265 0.72 316.5 145.5 462 14100
Oriole 336.4 30/7 0.1059 0.1059 0.318 0.741 317 209 526 17300
Chickadee 397.5 18/1 0.1486 0.1486 0.149 0.743 372.5 58.5 431 9940
Ibis 397.5 26/7 0.0961 0.1236 0.288 0.783 374.1 171.9 546 16300
Pelican 477 18/1 0.1628 0.1628 0.163 0.814 446.8 70.2 517 11800
Flicker 477 24/7 0.094 0.141 0.282 0.846 449.5 164.5 614 17200
Hawk 477 26/7 0.1053 0.1354 0.316 0.858 448.6 206.4 655 19500
Hen 477 30/7 0.1261 0.1261 0.378 0.883 449.7 296.3 746 23800
Osprey 556.5 18/1 0.1758 0.1758 0.176 0.879 521.1 81.9 603 13700
Parakeet 556.5 24/7 0.1015 0.1523 0.305 0.914 524.2 191.8 716 19800
Dove 556.5 26/7 0.1138 0.1463 0.341 0.927 523.9 241.1 765 22600
Rook 636 24/7 0.1085 0.1628 0.326 0.977 598.8 219.2 818 22000
Grosbeak 636 26/7 0.1216 0.1564 0.365 0.99 598.7 275.3 873 25200
Drake 795 26/7 0.136 0.1749 0.408 1.108 749 344 1093 31500
Tern 795 45/7 0.0886 0.1329 0.266 1.063 748.9 146.1 895 22100
Rail 954 45/7 0.0971 0.1456 0.291 1.165 899 176 1075 25900
Cardinal 954 54/7 0.1329 0.1329 0.399 1.96 899 329 1228 33800
Curlew 1033.5 54/7 0.1383 0.1383 0.415 1.245 973 356 1329 36600
Bluejay 1113 45/7 0.1049 0.1573 0.315 1.259 1049 205 1254 29800
Bittern 1272 45/7 0.1121 0.168 0.336 1.345 1198 234 1432 34100
Lapwing 1590 45/7 0.1253 0.188 0.376 1.504 1498 292 1790 42200
Bluebird 2156 84/19 0.0961 0.1602 0.481 1.762 2040 468 2508 60300
Source: Nexans
Power Cables & Wires Technical Manual
52
Table 19: Aluminum Conductor Steel Reinforced (ACSR) Electrical Data
Code word
Size(AWG
orkcmil)
Resistance (ohm/kft) Reactance at 60 Hz**
Ampacity*(A)DC at
20°CAC at25°C
AC at50°C
AC at75°C
Capacitive(megohm-kft)
Inductiveat 25°C
(ohm/kft)
Inductiveat 50°C
(ohm/kft)
Inductiveat 75°C
(ohm/kft)
Turkey 6 0.642 0.655 0.75 0.816 0.751 0.12 0.139 0.144 105
Swan 4 0.403 0.412 0.479 0.522 0.715 0.115 0.131 0.137 140
Swanate 4 0.399 0.407 0.463 0.516 0.71 0.113 0.124 0.13 140
Sparrow 2 0.253 0.259 0.308 0.336 0.678 0.11 0.123 0.128 185
Sparate 2 0.251 0.256 0.297 0.33 0.674 0.109 0.118 0.121 185
Robin 1 0.201 0.206 0.247 0.27 0.66 0.107 0.119 0.122 210
Raven 1/0 0.159 0.163 0.197 0.216 0.642 0.104 0.114 0.116 240
Quail 2/0 0.126 0.13 0.162 0.176 0.624 0.102 0.112 0.113 275
Pigeon 3/0 0.1 0.103 0.121 0.145 0.606 0.0992 0.108 0.109 315
Penguin 4/0 0.0795 0.0822 0.107 0.116 0.597 0.0964 0.105 0.105 365
Waxwing 266.8 0.0644 0.0657 0.0723 0.0788 0.576 0.0903 0.0903 0.0903 445
Partridge 266.8 0.0637 0.0652 0.0714 0.0778 0.565 0.0881 0.0881 0.0881 455
Merlin 336.4 0.051 0.0523 0.0574 0.0625 0.56 0.0826 0.0826 0.0826 515
Linnet 336.4 0.0506 0.0517 0.0568 0.0619 0.549 0.0854 0.0854 0.0854 530
Oriole 336.4 0.0502 0.0513 0.0563 0.0614 0.544 0.0843 0.0843 0.0843 530
Chickadee 397.5 0.0432 0.0443 0.0487 0.0528 0.544 0.0856 0.0856 0.0856 575
Ibis 397.5 0.0428 0.0438 0.0481 0.0525 0.539 0.0835 0.0835 0.0835 590
Pelican 477 0.036 0.0369 0.0405 0.0441 0.528 0.0835 0.0835 0.0835 640
Flicker 477 0.0358 0.0367 0.0403 0.0439 0.524 0.0818 0.0818 0.0818 670
Hawk 477 0.0357 0.0366 0.0402 0.0438 0.522 0.0814 0.0814 0.0814 660
Hen 477 0.0354 0.0362 0.0398 0.0434 0.517 0.0803 0.0803 0.0803 660
Osprey 556.5 0.0309 0.0318 0.0348 0.0379 0.518 0.0818 0.0818 0.0818 710
Parakeet 556.5 0.0307 0.0314 0.0347 0.0377 0.512 0.0801 0.0801 0.0801 720
Dove 556.5 0.0305 0.0314 0.0345 0.0375 0.51 0.0795 0.0795 0.0795 730
Rook 636 0.0268 0.0277 0.0303 0.033 0.502 0.0786 0.0786 0.0786 780
Grosbeak 636 0.0267 0.0275 0.0301 0.0328 0.499 0.078 0.078 0.078 790
Drake 795 0.0214 0.0222 0.0242 0.0263 0.482 0.0756 0.0756 0.0756 910
Tern 795 0.0216 0.0225 0.0246 0.0267 0.488 0.0769 0.0769 0.0769 890
Rail 954 0.018 0.0188 0.0206 0.0223 0.474 0.0748 0.0748 0.0748 970
Cardinal 954 0.0179 0.0186 0.0205 0.0222 0.47 0.0737 0.0737 0.0737 990
Curlew 1033.5 0.0165 0.0172 0.0189 0.0205 0.464 0.0729 0.0729 0.0729 1040
Bluejay 1113 0.0155 0.0163 0.0178 0.0193 0.461 0.0731 0.0731 0.0731 1070
Bittern 1272 0.0135 0.0144 0.0157 0.017 0.451 0.0716 0.0716 0.0716 1160
Lapwing 1590 0.0108 0.0117 0.0128 0.0138 0.434 0.0689 0.0689 0.0689 1340
Bluebird 2156 0.00801 0.00903 0.00977 0.0105 0.409 0.0652 0.0652 0.0652 1610
* Ampacity is with sun and wind at 2 ft/s ** Reactance at 1 foot equivalent spacing
Source: Nexans
Power Cables & Wires Technical Manual
53
9.2 Covered Conductors
Covered conductors are bare conductors with thin insulation coveringused for overhead power distribution system. These are used forpower distribution circuits that transverse along routes with heavytree growth. The covering does not fully insulate the conductor but itis thick enough to reduce the chances of flashover whenever a treebranch falls between the conductors. Covered conductor is alsocommonly known as tree wire. Also, it helps minimize faults causedby animals and enable distribution utilities to utilize conductorconfigurations with tight spacing. Covered conductors are commonlyused as a cost-effective method for increasing overhead linereliability.
The conductor materials are typically copper or aluminum or otherconductors designed to give a balance between strength andconductivity such as ACSR. Tree wire is commonly covered byinsulating materials such as polyethylene, XLPE, or EPR. Insulationthickness typically ranges from 30 to 150 mils. Tree wires mustalways be treated as bare conductors. However, closer spacings areallowed for this type of conductor.
While covered conductors help against trees, it has several setbackscompared to bare conductors. The covering may be susceptible todegradation due to ultraviolet radiation, tracking, and mechanicaleffects that cause cracking. Also, covered conductors are susceptibleto burn-downs. Burn-down is when a conductor burns through ormelts and falls to the ground. A covered conductor line can sufferburn-down due to lightning strikes, excessive tracking over time,vibration fatigue or tree branches falling on the line. The risk of burn-down can be reduced by suitable lightning protection systems,reduction of electrical stresses, improved tree trimming, reducedcarbon black content in the sheath material, and proper installationand tensioning.
The additional covering adds cost to the conductor such that acovered conductor line would cost about at least 20% more than abare conductor line. Covered conductors are heavier and have largerdiameters so wind loading is higher than bare conductors. Also, adamage cover makes it susceptible to corrosion, primarily from water.
Power Cables & Wires Technical Manual
54
If water penetrates the covering, it settles at the low points and causescorrosion since the covering prevents the trapped water fromevaporating. Water enters the conductor at pinholes caused bylightning strikes, cover damage caused by abrasion, and at holespierced by connectors. In contrast, rain simply washes over bareconductors and evaporation takes care of moisture.
There will be a low charging current flowing along the coveredconductor sheath since its surface is insulating but not fully insulated.This arises because the sheath forms an insulating layer between thehigh voltage conductor (metal) and the pin or post insulator to earth.This current will normally be less than 0.3mA which flows phase-phase or phase-ground. This current is held low to reduce trackingand erosion, especially under polluted conditions. Metal helical tiesform an intermediate electrode and can cause discharge problems atthe ends if bare. Connecting helical ties with any insulating piercingconnectors (IPCs) or use of semi-conducting plastic ties eliminatesthis problem.
For a covered conductor line, insulation piercing connectors (IPC) areused. IPC contains teeth that penetrate through the insulation to havecontact with the conductor and complete a connection.
Tables 20 and 21 show the relevant data of Copper and ACSRCovered Conductors, respectively.
Spacer cables are also alternatives to Covered Cables and performwell in areas with dense trees. Spacer cables are of bundledconfiguration using a messenger wire with a polymetric supportcradle holding up the three phases. The spacer cables’ reactiveimpedance is smaller because it significantly reduces spacing thantypical overhead constructions.
Power Cables & Wires Technical Manual
55
Table 20: Copper Single Layer Covered Conductors Data
Size(AWG
orkcmil)
Stran-ding
CoverThick.(mils)
O.D.Covered(mils)
CopperContent
Per1000 ft.
(lbs.)
Weight Per1000 ft. (lbs.) DC
ResistanceΩ/1000
ft.@20°C
AllowableAmpacity
+XLPE PE
6 7 30 238 81 90.3 90.3 0.503 130
4 7 30 285 128.9 140.8 140.8 0.316 175
2 7 45 373 204.9 227.1 227.1 0.199 230
1/0 7 60 477 326.1 363.3 363.3 0.125 305
2/0 7 60 522 410.9 453.3 453.3 0.0992 350
3/0 7 60 570 518.1 565.6 565.6 0.0788 405
4/0 7 60 626 653.3 707.6 707.6 0.0625 465
250 19 60 677 771.9 825.4 825.4 0.0530 520
300 19 60 729 926.2 984.6 984.6 0.0442 580
350 19 60 779 1080.6 1144.5 1144.5 0.0380 640
500 37 80 950 1543.8 1637.2 1637.2 0.0278 785
750 61 80 1128 2315.6 2422.8 2422.8 0.0182 995
1000 61 95 1307 3087.5 3234 3234 0.0140 1180
Source: Southwire
Power Cables & Wires Technical Manual
56
Table 21: 2-Layer 15kV ACSR Tree Wire
Size(AWG
orkcmil)
StrandingConductorDiameter
(mils)
CoveringThickness
(mils)CableO.D.(mils)
RatedStrength
(lbs)
Weightper
1000ft. (lbs)Inner
LayerOuterLayer
1/0 6/1 398 75 75 698 4161 255
2/0 6/1 447 75 75 747 5045 303
3/0 6/1 502 75 75 802 6289 362
4/0 6/1 563 75 75 863 7933 432
266.8 18/1 609 75 75 909 6536 441
266.8 26/7 642 75 75 942 10735 452
336.4 18/1 684 75 75 984 8246 536
336.4 26/7 720 75 75 1020 13395 555
336.4 30/7 741 75 75 1041 16435 621
397.5 18/1 743 75 75 1043 9443 611
397.5 24/7 772 75 75 1072 13870 609
477 24/7 846 75 75 1146 16340 719
477 26/7 858 75 75 1158 18525 762
477 30/7 883 75 75 1183 22610 854
556.5 18/1 879 75 75 1179 13015 813
556.5 24/7 914 75 75 1214 18810 828
556.5 26/7 927 75 75 1227 21470 878
636 18/1 940 75 75 1240 14915 912
636 24/7 977 75 75 1277 20900 936
636 26/7 990 75 75 1290 23940 993
795 26/7 1108 80 80 1428 29925 1234
795 45/7 1063 80 80 1383 20995 1031
Source: Southwire
Power Cables & Wires Technical Manual
57
9.3 Insulated Cables
Majority of insulated cables are utilized for undergroundtransmission and distribution systems. Being insulated for voltageshigher than 2 kV, that these cables are typically shielded.
9.3.1 Construction
The fundamental difference between non-shielded and shieldedcables is the inclusion of outer conducting components in thecable system. The basic components of a shielded cable areshown below.
Figure 6: Construction of Shielded Power Cable
Conductor
The conductors used in shielded cables are basically the same asthose used in non-shielded cables, with copper and aluminum asthe conductor.
Conductor Shield or Screen
The conductor shield is usually a semi-conducting materialapplied over the conductor circumference to shield out the surfaceirregularities of the conductor. With this shield, the resultingdielectric field lines will not be distorted by the shape of the outerstrands or other conductor contours. It prevents the formation ofdestructive discharges at the interface between the conductor andinsulation. Otherwise, the electrical stress around the conductorswould produce partial discharges on the surface of the insulationwhich deteriorates it and eventually results to cable failure. Also,it is essential that this stress control layer be compatible with theconductor and the cable insulation.
Power Cables & Wires Technical Manual
58
This layer also provides a smooth and compatible surface forthe application of the insulation. The conductor shield isextruded simultaneously with the insulation for a void-free bondbetween conductor shield and insulation. The shield may alsobe used to facilitate splicing and termination of the cable.
Insulation
This is the part of the cable that is relied upon to insulate theconductor from other conductor or conductive object or fromground. The differences between the insulation for shielded cablesas compared to non-shielded cables include material, processtechnology, and testing. The insulation thickness is primarilyinfluenced by the operating voltage. Therefore, the higher thevoltage, the thicker the insulation.
Insulation Shield or Screen
This absorbs the symmetrical radial stresses and discharges on thesurfaces of the insulation. It protects the cables from inducedpotentials. Shields help attenuate, make uniform and reduce thesurge potential stresses on the insulation. It increases safety tohumans and removes the risk of fire due to electrical discharges onthe cable surface.
The insulation shield or screen is a two-part system composed ofan auxiliary and a primary shield.
An auxiliary shield is usually a semi-conducting, non-metallicmaterial over the insulation circumference. It must be smooth,compatible with the insulation, and exhibit an acceptably lowvoltage drop throughout its thickness. A commonly usedauxiliary shield consists of an extruded semi-conductingpolymer to permit easy removal during field termination, butyet to remain uniformly bonded to the insulation throughoutthe cable length.
A primary shield is a metallic shield over the circumferenceof the auxiliary shield. It may consist of copper tape orConcentric Neutral (CN) wires. These concentric neutralwires are usually annealed.
Power Cables & Wires Technical Manual
59
CN wires serve two purposes, namely; they function as themetallic component of the insulation shield and as aconductor for the neutral return current. Their cross-sectional area must be properly sized in order to function asthe neutral conductor.
The primary shield must be capable of conducting thesummation of the “leakage” currents to the nearest groundwith an acceptable voltage drop. In some cases, it must also becapable of conducting fault currents.
The primary shield, by itself, without an intervening auxiliaryshield, cannot achieve acceptable physical contact with theinsulation surface. A relatively resilient auxiliary shield isnecessary to eliminate arcing between the insulation surfaceand the primary shield.
If the insulation shield is effectively at ground potential, noresulting distortion of the electrostatic flux or equipotential lineswill occur. The grounding of the insulation shield is the electricalconnection between the metallic component of the insulationshield and the system ground. This grounding of the insulationshield results in symmetrical dielectric fields. Electrostatic fluxlines are spaced symmetrically and perpendicular to equipotentiallines. The equipotential lines are concentric and parallel withrespect to each other, the conductor shield and the insulationshield. The presence of the shielding results in field lines asdepicted in Figure 7. In addition, grounding promotes personnelsafety by minimizing potentials on the outer surface of the cableand its accessories.
The shielding of the cable system can either be single-pointed or multiple-pointed grounding. A single-point groundedsystem is frequently referred to as an open circuit shield. Sincethe shield is grounded at a single point, there is no closed loopfor the flow of induced shield currents. A multiple-pointgrounded system, on the other hand, is one that has grounds atmore than one point. It is frequently called a closed or short-circuit shield system.
Power Cables & Wires Technical Manual
60
Each of the arrangements has its particular advantages anddisadvantages for selection. Knowledge of the total systemshould be taken into account when making these decisions.
In a shielded cable, the voltage difference betweenconductor and electrical ground is contained within the cable.For a non-shielded cable, the voltage difference betweenconductor and electrical ground is divided between the cableinsulation and any intervening air or other materials.
Figure 7: Electrical Field of a Shielded Cable
Insulation
Conductor
Conductor Shield
Insulation Shield
Electrostatic Flux Lines
Equipotential Lines
Power Cables & Wires Technical Manual
61
In Figure 7, observe that the field lines are closer to each othernear the conductor shield as compared to the insulation shield.The radial stresses or voltage gradients increase near theconductor.
Jackets/Sheaths
These cable components provide environmental protection overthe insulation shielding system. The material used can be anextruded jacket of synthetic material, metal sheaths/wires,armoring, or a combination of these types of materials.
9.3.2 Electrical Losses in Cables
When the cable is energized and carrying load, heat, which mustbe dissipated to the surrounding medium, is generated by theconductor, dielectric and sheath losses.
The heat generated by these losses in the conductor, thedielectric, the sheath and armor has to pass to the surroundingmedium, which may be the ground, air, water or some othermaterial. The current carrying capacity of an electric cable isnormally dictated by the maximum temperature of the conductor.The components of the cable, in addition to meeting theelectrical requirements, must also have as low a thermalresistivity, as possible, to ensure that the heat can be dissipatedefficiently. If the rate of rise of heat generation is greater than therate of rise of heat dissipation, the cable temperature willcontinue to increase which will result in the overheating of thecable and eventual breakdown.
9.3.3 Advantages of Shielded Cables
Electrical insulation surrounding a conductor creates a capacitorwhen the conductor is electrically energized. Thus, all insulatedconductors are capacitors.
In the majority of non-shielded cable systems, the cable surfacemakes intermittent contact with an electrical ground. Whereintimate contact with this ground is not made, the intervening air
Power Cables & Wires Technical Manual
62
spaces also act primarily as capacitors in ac circuits and asresistors in dc circuits. This forms a series of cable dielectric andair dielectric. Voltage across this circuit varies along the lengthof the cable depending on the voltage across the air gap. Thecable surface becomes a floating voltage point in a voltagedivider. This floating point voltage can vary considerably,depending on the cable design and the characteristics of the airgap. If the voltage is high enough, the cable surface canexperience detrimental surface tracking of arcing discharges toelectrical ground. The cable surface can also become potentiallyhazardous causing an electrical shock if contacted by fieldpersonnel.
Shielding the cable insulation surface and grounding of thisshielding eliminates tracking and arcing discharges. Thegrounding of this shield prevents the accumulation of anelectrical potential on the surface of the cable that could behazardous to any individual that comes into contact with thecable surface.
10. INSTALLATION OF WIRES AND CABLES
10.1 Maximum Allowable Tensions on Conductors
Care should be taken during installation of cables to prevent damagethat can result to future service failures. In preparing for a conductorpull, it is just as important to cover the other details as it is to assurethat the conductor does not exceed maximum sidewall pressure,minimum bending radii or maximum pulling tensions. These andother considerations can make the difference between a goodinstallation and one with damaged conductors.
Mechanical stresses during installation are generally more severethan those encountered while in service. The following informationprovides guidance in recognizing these conditions and provides amethodology to aid in keeping them within acceptable limits.
Power Cables & Wires Technical Manual
63
10.1.1 Maximum Allowable Tension
Calculations should be made whether the pull looks easy orimpossible, making the decision as where to pull an obviouschoice. When an obscure situation is encountered, the entire pullshould be reviewed. This review may include more rigorouscalculations or trial pulls. A final decision should be made basedon installation factors known to the end user and installer.
The sizes of the conduit are determined based on the calculationsof clearances, jamming, and fill. Pulling tensions may beevaluated by determining the maximum tension based on thepulling device used, and the maximum tension that can beapplied to the conductors. The lesser of these two values is themaximum allowable tension. After calculating the pullingtensions, sidewall pressures may be calculated.
Do not exceed the allowable tension stated by the manufacturerof the pulling device or 10,000 pounds, whichever is less. Do notuse metallic shielding wires, tapes or braids, or armor notdesigned for the purpose, in pulling tension calculations. Themaximum tension allowed for the conductors are computed asfollows:
Single Conductor:
T = S * A
Multiple Conductors:
T = N * S * A for 3 or less conductors
T = (0.8) * N * S * A for more than 3 conductors
where:T = conductor tension, lbsS = conductor stress, lbs/cmil (Table 22)A = conductor area, cmil (Table 23)N = number of conductors
Power Cables & Wires Technical Manual
64
Pulling different conductor sizes at the same time is notrecommended if the conductor size or other cable characteristicsare significantly different. If different size conductors must bepulled, it must be done with care.
Table 22: Maximum Allowable Conductor Stress
Cable Type Material Temper lbs/cmil
All Copper soft 0.008
Power Aluminum Hard 0.008
Power Aluminum 3/4 hard 0.006
Power Aluminum AA-8000 0.006
URD Aluminum 1/2 hard 0.003
Solid Aluminum Soft 0.002
Table 23: Concentric Stranded Copper & Aluminum Conductor Area
AWG cmil AWG cmil
14 4,110 250 250,00012 6,530 300 300,00010 10,380 350 350,0008 16,510 400 400,0006 26,240 450 450,0004 41,740 500 500,0003 52,620 600 600,0002 66,360 700 700,0001 83,690 750 750,000
1/0 105,600 800 800,0002/0 133,100 900 900,0003/0 167,800 1000 1,000,0004/0 211,600 1200 1,200,000
Power Cables & Wires Technical Manual
65
10.1.2 Pulling Tension Calculation
The following equations allow the user to calculate the expectedpulling tension of a conductor in a conduit pull.
Tin=W×L×
where; Tin = tension, lbs.W = weight of one foot of cable, lbs.L = length of pull, ft. = coefficient of friction for the particular duct
material and outer layer of the cable.
The weight of the cable and the length of the pull can bedetermined with great accuracy. The one variable that variestremendously is the value of the coefficient of friction—it canvary from 0.05 to 1.0.
Even when the materials used in the duct and jacket are known,the type and amount of lubricant can be an important factor inthis variation.
10.1.3 Coefficient of Friction
The coefficient of dynamic friction (μ) is a measure of thefriction between a moving conductor and the conduit. Thecoefficient of friction can have a large impact on the tensioncalculation.
Table 24: Typical Coefficients of Dynamic Friction (μ) for Cables withan Adequate Cable Lubrication During a Pull
Cable Outer Jacket or Insulation Conduit Type
EMT PVCType THHN/THWN (Nylon) 0.28 0.24
Type XHHW, USE, RHH/RHW (XLPE) 0.25 0.14
Power Cables & Wires Technical Manual
66
TriangularCradled
D
10.1.4 Conductor Configuration
The configuration of three single-conductors in a conduit isdetermined by the ratio of the conduit inner diameter (D) to theouter diameter (d) of one of the single conductors (D/d ratio).
Figure 8: Configuration of Three Single Conductors
A cradled configuration develops when three single-conductorsare pulled into a conduit where the D/d ratio is 2.5 or greater. Atriangular configuration develops when three single-conductorsare pulled into a conduit where the D/d ratio is less than 2.5.
10.1.5 Weight Correction Factor
This configuration of conductors can affect the tension. A weightcorrection factor (ω) is used in the tension equations to account for this effect. This is given by the following equations:
Single Conductor: = 1
Three Conductor (Triangular):
Three Conductor (Cradled):
Dd < 2.5
Dd ≥ 2.5
Power Cables & Wires Technical Manual
67
Four Conductors or More
To be conservative, it is recommended that the three-conductor(triangular) factor be used when pulling two conductors.
10.1.6 Tension Formulas
Horizontal Straight Section:Tout = WL+Tin
Inclined and Vertical Section:
Pulling up:Tout = WL(sin + cos) + Tin (lbs)
Pulling Down:Tout = WL(sin + cos) + Tin (lbs)
Elbows and Bends (approximation):Tout = Tin e
where; Tout = tension out of a section, lbsTin = tension into a section, lbsW = total cable weight, lbs/ftL = straight section length, ft = coefficient of dynamic friction
= weight correction factor
= straight section angle from horizontal,radians
= bend section angle, radianse = 2.71 natural logarithm base
Power Cables & Wires Technical Manual
68
10.1.7 Conductor Jamming
There is a tendency where cables may jam against the inside ofthe conduit when the diameter of each cable is about one-thirdthe inner diameter of the duct. This commonly occurs when thecables go around a bend or a series of bends. Jamming increasesthe pulling tension to a point that it can damage the cable. Thus,the jam ratio of the cables needs to be evaluated. The equationfor the jam ratio of three cables in a duct is as follows:
where; 1.05 factor to account the possible ovality of theconduit in a bend and for the cable of havinga slightly different diameter at any point
D = inside diameter of the duct or conduitd = outer diameter of each of the three cables
When the jam ratio falls between 2.6 and 3.2, jamming isprobable if there are bends in the run. Thus, to avoid possibleproblem with conductor jamming, it is advisable to avoid pullswhere the jam ratio is between 2.6 and 3.2.
10.2 Sidewall Pressure
Sidewall pressure is the vector force that exists on the cable as it ispulled through a bend. Because the surface area of the bend issmaller in small radius bends, that force is concentrated over a muchsmaller area. Most of the time sidewall pressure is the limiting factorin a cable pull. It is calculated by the following equations:
Single-conductor cable or multiple-conductor cable under commonjacket:
Dd
Jam ratio = 1.05
Power Cables & Wires Technical Manual
69
Three Conductor (Triangular):
Three Conductor (Cradled):
where; Sp = sidewall pressure, lbs/ftT = tension coming out of the bend, lbs = weight correction factorR = bend radius, ft
Table 25: Sidewall Bearing Pressure Limits
Cable Type SWBP, lbs/ftInstrumentation 100600 V non-shielded control 300600 V power 5005 to 15 kV shielded power 50025 to 46 kV power 300
10.3 Bending Radius
The following are the minimum values for the radii to whichinsulated cables may be bent during installation. These limits do notapply to conduit bends, sheaves or other curved surfaces aroundwhich the cable may be pulled under tension while being installed.Larger radii bends may be required for such conditions to limit
Power Cables & Wires Technical Manual
70
sidewall pressure. In all cases the minimum radii specified refers tothe inner surface of the cable and not to the axis of the cable.
The minimum bending radii for both single and multiple-conductorcable with or without lead sheath and without metallic shielding orarmor are as follows:
Table 26: Minimum Bending Radii for Power and Control Cableswithout Metallic Shielding or Armor
Thickness ofConductorInsulation,
inches
Overall Diameter of cables, inches
1.000 and less 1.001 to 2.0002.001and
largerMinimum Bending Radius asMultiple of Cable Diameter
0.156 andless
4 5 6
0.157 to0.315
5 6 7
0.316 andover
- 7 8
Source: Okonite
Power Cables & Wires Technical Manual
71
Table 27: Minimum Bending Radii for Power and Control Cables withMetallic Shielding or Armor, as Multiple of Cable Diameter
Type of Cable Power Control
Armored, flat tape or wire type 12... 12...
Armored, smooth aluminum sheath, up to; . .
...0.75 inches cable diameter 10*. 10*.
...0.76 to 1.5 inches cable diameter 12... 12...
...over 1.5 inches cable diameter 15... 15...
Armored, corrugated sheath or . .
...interlocked type 7... 7...
...with shielded single conductor 12... 12...
...with shielded multi-conductor **... **...
Non-armored, flat or corrugated . .
...tape shielded single conductor 12... 12...
...tape shielded multi-conductor **... **...
...multi-conductor overall tape shield 12... 12...
...LCS with PVC jacket 15... 15...
Non-armored, concentric neutral 8... —...
Non-armored, flat strap shielded 8... —...
Non-armored, wire shielded ***.. —...
* with shielded conductors 12
** 12 times single conductor diameter
or 7 times overall cable diameter — whichever is greater
*** See Power and control cables without metallic shielding
LCS = longitudinally applied corrugated shield
Source: Okonite
Power Cables & Wires Technical Manual
72
11. PACKAGING
The usual cut for small diameter building wires is 150 meter and ispackaged in boxes. However, for bigger diameter wires and powercables, these usually come in 300 meter rolls. For special and othercutting or packaging requirements, this has to be specified andcoordinated with the wires and cables manufacturer.
12. CABLE/WIRE APPLICATION
In ordering wires/cables, it is important that the manufacturer knows theintended application of the wires/cables. This in order that they canrecommend the type of cable best suited for the application. The usualservice conditions for cables are indoor/outdoor application in wet, damp,and/or dry environment. However, for cables that are to be used in specialapplication or condition, this has to be communicated to the manufacturer.
13. CABLE INSTALLATION METHOD
Knowledge of the cable installation method to be used is important for themanufacturer since the current carrying capacity of the cable will dependon where the cables are to be laid such as in open air, raceway, cable tray,conduit or directly buried. This is due to the heat generated by the cablesdue to their close proximity and the capability of the type of cableinstallation to dissipate this generated heat. Per Philippine ElectricalCode (PEC), certain de-rating factor has to be applied depending on theparticular installation method.
14. COLOR CODING
In accordance with the PEC, certain color coding is required forconductors of a multi-core cable. Ground conductors shall have acontinuous white, white stripe or gray outer finish. On the other hand, livewires can have any color, except the foregoing.
Equipment grounding conductor, however, shall have a continuous greencolor or a continuous green color with one or more yellow stripes.
Power Cables & Wires Technical Manual
73
For jacketed cords furnished with appliances, one conductor having itsinsulation colored light blue, with the other conductors having theirinsulation of a readily distinguishable color other than white or gray.
For electric space-heating cables, the lead wire shall have the followingcolor identification to indicate the circuit voltage on which it is to be used:
(1) 115 volt, nominal – yellow(2) 208 volt, nominal – blue(3) 230 volt, nominal – red(4) 265 volt, nominal – brown(5) 460 volt, nominal - orange
15. REFERENCE STANDARDS
Wires and cables are usually made to comply with certain referencestandard (e.g. Philippine National Standard (PNS), IEC, ASTM, ICEA,AIEC, NEMA, UL, etc.) Some PNS on wires and cables are listed inAnnex C.
16. STORAGE
Another important consideration or information needed to becommunicated to the wire manufacturer/supplier is the storage of the cableat site, whether it will be stored indoor or outdoor. If the cable will bestored outdoor and subjected to the elements, depending on the cableinsulation or construction and the sealing of its terminals, the cableperformance may be degraded. Likewise, for power conductors onreels, especially when it is expected to be stored outdoors forextended periods, special attention should also be taken on the material ofthe cable reel. Should the reels be made of wood, the reel may rot aftersome time making it difficult to transport the cable to another site.
Power Cables & Wires Technical Manual
74
Hereunder are some use and storage suggestions:
(1) Upon receipt, cable protective covering should be thoroughlyscrutinized for possible signs of damage during delivery. Ifevidence of damage is found, inform the carrier immediately.
(2) During unloading, make sure that theequipment used does not have contactwith the cable surface and itsprotective covering. When a crane isbeing used, a cradle supporting the reelflanges or a shaft through the arborhole should be used. If unloading isbeing done with the use of a forklift,the forks must lift the reel at 90° to theflanges and must be long enough toreach both flanges. The fork must notmake contact with the cable surface orthe cable protective covering.
(3) If an inclined ramp is used duringunloading, the ramp must be wideenough to have contact with bothflanges. When controlling the decentof the reel, it should be done throughthe use of the reel flanges and not thesurface of the cable.
(4) The reels should not be dropped fromthe delivering vehicle to the groundwhatever the circumstance.
(5) The weight of the reel and cable mustbe allowed to rest on the flanges,which, in turn, should be resting on ahard surface to prevent the flangesfrom sinking and shifting part of saidweight to the cables.
Power Cables & Wires Technical Manual
75
(6) Reels should be stored in an area where no falling debris ofconstruction material or other objects that can damage the cable.
(7) Cable should not be stored in an area where chemicals orpetroleum can be spilled or sprayed on the cable.
(8) Reels of cable with unjacketed sheath or armor (aluminum orsteel) should be stored indoors. Unjacketed sheath or armor easilycorrodes when exposed outside.
(9) Care must be taken when a reel of cable is rolled from one point toanother, see to it that there are no objects on the surface areawhich could have contact and damage the cable surface or itsprotective covering.
(10)Keep cable away from open fires or sources of heat.
(11)Cable ends must always be sealed to prevent the entrance ofmoisture.
17. AVAILABLE CABLE HANDLING EQUIPMENT AT SITE
It will be important for the cable and wire manufacturer/supplier to knowwhether there will be any cable handling equipment available at site so thatthey can prepare the means to unload the cables safely from the transportvehicle.
If a cable handling equipment is available at site, its capacity has to becommunicated to the manufacturer/supplier so as to ensure that it iscapable of handling the weight of the cable.
18. SAFEGUARDS FOR INSTALLING WIRES AND CABLESIN CONDUIT
Investigations have shown that cable failures often can be attributed todamage caused during installation due to carelessness, inexperience andinability to observe certain simple precautions. In order to eliminate suchpreventable causes of electrical shutdowns and loss of production, thefollowing procedures should be followed:
Power Cables & Wires Technical Manual
76
18.1 Before Pulling Wire/Cable
(1) Know and observe all Philippine Electrical Code rulesregarding installation.
(2) Check the conduit and wire/cable sizes and actual overalldiameters in order to be sure that the approved "fill" will notbe exceeded. Do not "crowd" the conduit.
(3) Check the type of wire/cable to be installed.(4) Consider the use of larger conduits or additional pull boxes.(5) Check any obstruction on the conduit.(6) To loosen any burrs, pull a short mandrel or plug closely
approximating the diameter of the conduit and clean out anyremaining dirt or foreign matter, follow it up with a swab.
18.2 While Pulling Wire/Cable
(1) To prevent short bends, sharp edges and "crossover", alwayshave a man feed wire straight into a conduit by hand or over alarge diameter sheave for large conductors/cables.
(2) Remove all lashings used for temporary bunching ofindividual wires/cables before they enter the conduit.
(3) Lead-out wires at all pull boxes and conduits. Feed them inagain for the next run.
(4) Never pull directly around short right angled bends.
18.3 After Pulling Wire/Cable
Shut off the exposed ends of the excess wire/cable on the reel with atape to prevent moisture from entering the wire/cable.
19. SAFEGUARD FOR SWITCHBOARD AND SIMILAR OPENWIRING
To avoid cutting or deforming the insulation at the contact point use widetape or straps with rounded edges instead of narrow strings when bindinggroups of wires, especially non-braided wires.
Power Cables & Wires Technical Manual
77
20. WIRE/CABLE ORDERING FORM
In order to guide the user, electrical designer or the purchaser incorrectly ordering or specifying the cable or wire that is needed for hisspecific use and for the wire and cable manufacturer/supplier to have thenecessary information to know the specific needs of his customer so that hecan give a correct price quotation, a wire/cable ordering form has beendeveloped in Annex D.
Power Cables & Wires Technical Manual
78
79
ANNEXES
80
Power Cables & Wires Technical Manual
81
ANNEX A
Table A1. Conductor Types and Sizes for 115/230-Volt, 3-Wire,Single-Phase Dwelling Services and Feeders. Conductor Types RHH,RHW, RHW-2, THHN, THHW, THW, THW-2, THWN, THWN-2,XHHW, XHHW-2, SE, USE, USE-2
Conductor mm2 Service or FeederRating (Amperes)
Copper Aluminum
22303038
506080100
125175200
30385060
80100125150
175250325
100110125150
175200225250
300350400
Power Cables & Wires Technical Manual
82
Table A2. Ampacities of Not More Than Three Single InsulatedConductors, Rated 0 Through 2 000 Volts, Supported on aMessenger, Based on Ambient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor (See Table 3.10.1.13.)75°C 90°C 75°C 90°CTypeRH,
RHW,THHW,THW,
THWN,XHHW,
ZW
TypesTHHN, THHW,
THW-2, THWN-2,RHH, RWH-2,
USE-2, XHHW-2,ZW-2
TypesRH, RHW,
THHW, THW,THWN, ZHHW
TypeTHHN, THHW,RHH, XHHW,
RHW-2, XHHW-2,THW-2, THWN-2,
USE-2, ZW-2COPPER ALUMINUM
125150175200250
316363390416496
369423460486581
248285310327392
288331360382458
325375400500
576630659741
674740771870
458505529606
535590617709
Table A3. Ampacities of Insulated Single Copper Conductor CablesTriplexed in Air Based on Conductor Temperatures of 90°C and105°C and Ambient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105125175250375400500
370460580740770870
410510640825860970
375465580720750840
420520650810845940
Power Cables & Wires Technical Manual
83
Table A4. Ampacities of Insulated Single Aluminum ConductorCables Triplexed in Air Based on Conductor Temperatures of 90°Cand 105°C and Ambient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105125175250375400500
290360460595620705
320400510660685790
295365460585605690
330410515655680770
Table A5. Ampacities of Insulated Single Copper Conductor Isolatedin Air Based on Conductor Temperatures of 90°C and 105°C andAmbient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000Volts
Ampacity
5 001–15 000Volts
Ampacity
15 001–35 000Volts
Ampacity90°CTypeMV-
90
105°CTypeMV-105
90°CTypeMV-
90
105°CTypeMV-105
90°CTypeMV-
90
105°CTypeMV-105
125175250375400500
435545695890925
1 060
485605775990
1 0301 185
435545685875910
1 050
485600765980
1 0201 030
430540680860895
1 030
480595755960
1 0001 145
Power Cables & Wires Technical Manual
84
Table A6. Ampacities of Insulated Single Aluminum ConductorIsolated in Air Based on Conductor Temperatures of 90°C and105°C and Ambient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000Volts
Ampacity
5 001–15 000Volts
Ampacity
15 001–35 000Volts
Ampacity90°CTypeMV-
90
105°CTypeMV-105
90°CTypeMV-
90
105°CTypeMV-105
90°CTypeMV-
90
105°CTypeMV-105
125175250375400500
340425545700730845
380475605780815940
340425535690720830
380475600770805930
340425530680705815
375470590755790910
Table A7. Ampacities of an Insulated Three-Conductor CopperCable Isolated in Air Based on Conductor Temperatures of 90°Cand 105°C and Ambient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105125175250375400500
315390485610635695
350435545680705780
355430535665690760
395485600735765850
Power Cables & Wires Technical Manual
85
Table A8. Ampacities of an Insulated Three-Conductor AluminumCable Isolated in Air Based on Conductor Temperatures of 90°Cand 105°C and Ambient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-10512575250375400500
250305385490510575
280340430545565640
280340425535555625
315380475595615695
Table A9. Ampacities of an Insulated Triplexed or Three Single-Conductor Copper Cables in Isolated Conduit in Air Based onConductor Temperatures of 90°C and 105°C and Ambient AirTemperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105125175250375400500
310380475595615680
350425530660685760
325390480580600665
360435535650675745
Power Cables & Wires Technical Manual
86
Table A10. Ampacities of an Insulated Triplexed or Three Single-Conductor Aluminum Cables in Isolated Conduit in Air Based onConductor Temperatures of 90°C and 105°C and Ambient AirTemperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105125175250375400500
250300380485505570
280335425540560635
255305385480500555
290345430535555630
Table A11. Ampacities of an Insulated Three-Conductor CopperCable in Isolated Conduit in Air Based on Conductor Temperaturesof 90°C and 105°C and Ambient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105125175250375400500
275345425520540580
310385475580600650
310380470565585640
345425525630655715
Power Cables & Wires Technical Manual
87
Table A12. Ampacities of an Insulated Three-Conductor AluminumCable in Isolated Conduit in Air Based on Conductor Temperaturesof 90°C and 105°C and Ambient Air Temperature of 40°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105125175250375400500
215270340425440500
240300380475495550
245300380465485540
275335425515535605
Power Cables & Wires Technical Manual
88
Table A13. Ampacities of Three Single-Insulated CopperConductors in Underground Electrical Ducts (Three Conductors perElectrical Duct) Based on Ambient Earth Temperature of 20°C,Electrical Duct Arrangement per Figure 3.10.1.60, 100 Percent LoadFactor, Thermal Resistance (RHO) of 90, Conductor Temperaturesof 90°C and 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit (See Figure 3.10.1.60, Detail 1.)
125175250375400500
315380470580600660
340410505625650710
320385465560580630
340410500605630680
Three Circuits (See Figure 3.10.1.60, Detail 2.)125175250375400500
255310375455475520
275330405490510555
255305370435454490
275325395470490530
Six Circuits (See Figure 3.10.1.60, Detail 3.)125175250375400500
205245300360375405
220265325390405440
205240290345360385
220260310370385410
Power Cables & Wires Technical Manual
89
Table A14. Ampacities of Three Single-Insulated AluminumConductors in Underground Electrical Ducts (Three Conductors perElectrical Duct) Based on Ambient Earth Temperature of 20°C,Electrical Duct Arrangement per Figure 3.10.1.60, 100 Percent LoadFactor, Thermal Resistance (RHO) of 90, Conductor Temperaturesof 90°C and 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit (See Figure 3.10.1.60, Detail 1.)
125175250375400500
245300370465485535
265320400500520580
245300370450470520
265325400485505555
Three Circuits (See Figure 3.10.1.60, Detail 2.)125175250375400500
200240295365380420
215260320390405455
195240290350365400
215255315380395435
Six Circuits (See Figure 3.10.1.60, Detail 3.)125175250375400500
160190240285295330
175205255310325355
160195230275285315
170205250300315340
Power Cables & Wires Technical Manual
90
Table A15. Ampacities of Three Insulated Copper ConductorsCabled Within an Overall Covering (Three-Conductor Cable) inUnderground Electrical Ducts (One Cable per Electrical Duct)Based on Ambient Earth Temperature of 20°C, Electrical DuctArrangement per Figure 3.10.1.60, 100 Percent Load Factor,Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°Cand 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit (See Figure 3.10.1.60, Detail 1.)
125175250375400500
285350430525545590
310375460565585635
305370450540560605
330395485580600650
Three Circuits (See Figure 3.10.1.60, Detail 2.)125175250375400500
240290355425440480
260310380460480515
250300360425440480
265320385460480510
Six Circuits (See Figure 3.10.1.60, Detail 3.)125175250375400500
195235290345360385
215265310370385415
200240290335350375
215270305360375400
Power Cables & Wires Technical Manual
91
Table A16. Ampacities of Three Insulated Aluminum ConductorsCabled Within an Overall Covering (Three-Conductor Cable) inUnderground Electrical Ducts (One Cable per Electrical Duct)Based on Ambient Earth Temperature of 20°C, Electrical DuctArrangement per Figure 3.10.1.60, 100 Percent Load Factor,Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°Cand 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit (See Figure 3.10.1.60, Detail 1.)
125175250375400500
225275340420435490
240305365455475530
240290355435450505
260310385470490535
Three Circuits (See Figure 3.10.1.60, Detail 2.)125175250375400500
185225280340355395
200245300370385425
195235285345360395
210250305370385425
Six Circuits (See Figure 3.10.1.60, Detail 3.)125175250375400500
155185230275285315
165200245300315340
155190230270280310
165200245290300330
Power Cables & Wires Technical Manual
92
Table A17. Ampacities of Single Insulated Copper ConductorsDirectly Buried in Earth Based on Ambient Earth Temperature of20°C, Arrangement per Figure 3.10.1.60, 100 Percent Load Factor,Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°Cand 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit, Three Conductors (See Figure 3.10.1.60, Detail 9.)
125175250375400500
460560690835870970
500610745900940
1 045
430530650795830920
465570700855890995
Two Circuits, Six Conductors (See Figure 3.10.1.60, Detail 10.)125175250375400500
425510630765800880
460550680825860950
405490600730760845
430525645785820910
Power Cables & Wires Technical Manual
93
Table A18. Ampacities of Single Insulated Aluminum ConductorsDirectly Buried in Earth Based on Ambient Earth Temperature of20°C, Arrangement per Figure 3.10.1.60, 100 Percent Load Factor,Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°Cand 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit, Three Conductors (See Figure 3.10.1.60, Detail 9.)
125175250375400500
365440540660685770
390475580710740830
340410510630655730
365445545670700785
Two Circuits, Six Conductors (See Figure 3.10.1.60, Detail 10.)125175250375400500
355405495605630700
360435530650675775
315380470575595670
340410505620645720
Power Cables & Wires Technical Manual
94
Table A19. Ampacities of Three Insulated Copper ConductorsCabled Within an Overall Covering (Three-Conductor Cable),Directly Buried in Earth Based on Ambient Earth Temperature of20°C, Arrangement per Figure 3.10.1.60, 100 Percent Load Factor,Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°Cand 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit (See Figure 3.10.1.60, Detail 5.)
125175250375400500
360435530640670720
390470570690720775
375455550660685740
405490590710740800
Two Circuits, (See Figure 3.10.1.60, Detail 6.)125175250375400500
335405490590610655
340435525635660705
325415500600625665
350445535645670720
Power Cables & Wires Technical Manual
95
Table A20. Ampacities of Three Insulated Aluminum ConductorsCabled Within an Overall Covering (Three-Conductor Cable),Directly Buried in Earth Based on Ambient Earth Temperature of20°C, Arrangement per Figure 3.10.1.60, 100 Percent Load Factor,Thermal Resistance (RHO) of 90, Conductor Temperatures of 90°Cand 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit (See Figure 3.10.1.60, Detail 5.)
125175250375400500
280340420515535590
305370450555575640
295355435535555610
315385470575595655
Two Circuits, (See Figure 3.10.1.60, Detail 6.)125175250375400500
260315385475495540
280340415510530580
270325395480500550
290350425520540590
Power Cables & Wires Technical Manual
96
Table A21. Ampacities of Three Triplexed Single Insulated CopperConductors Directly Buried in Earth Based on Ambient EarthTemperature of 20°C, Arrangement per Figure 3.10.1.60, 100Percent Load Factor, Thermal Resistance (RHO) of 90, ConductorTemperatures 90°C and 105°C
ConductorSizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°C TypeMV-90
105°CType
MV-10590°C Type
MV-90
105°CType
MV-105One Circuit, Three Conductors (See Figure 3.10.1.60, Detail 7.)
125175250375400500
405485590715745815
435570635770805875
385465565675705760
405500605730760820
Two Circuits, Six Conductors (See Figure 3.10.1.60, Detail 8.)125175250375400500
365440535640670730
390475575690720785
350420510610635680
375450545655680735
Power Cables & Wires Technical Manual
97
Table A22. Ampacities of Three Triplexed Single InsulatedAluminum Conductors Directly Buried in Earth Based on AmbientEarth Temperature of 20°C, Arrangement per Figure 3.10.1.60, 100Percent Load Factor, Thermal Resistance (RHO) of 90, ConductorTemperatures 90°C and 105°C
Conductor
Sizemm2
Temperature Rating of Conductor(See Table 3.10.1.61)
2 001–5 000 VoltsAmpacity
5 001–35 000 VoltsAmpacity
90°CType
MV-90
105°CType
MV-105
90°CType
MV-90
105°CType
MV-105One Circuit, Three Conductors (See Figure 3.10.1.60, Detail 7.)
125175250375400500
315380465575595660
345415500620645715
300365445545565625
320395480585605670
Two Circuits, Six Conductors (See Figure 3.10.1.60, Detail 8.)125175250375400500
285345420515535590
305370455555575635
275330405480500555
295450435520540595
Power Cables & Wires Technical Manual
98
Table A23. Minimum Wire-Bending Space at Terminals
Wire Sizemm2
Wires per Terminal1 2 3 4 or more
mm mm mm mm125150175200250325375400
215d
250e
305e
330e
350e
380e
405e
430e
(50)(75)(75)(75)(75)(75)(75)(75)
215d
250d
305e
330e
350e
400e
460e
480e
(50)(50)(50)(75)(75)(75)(75)(75)
230b
280b
330e
350e
380e
455e
510e
560e
(25)(25)(25)(75)(75)(75)(75)(75)
250300350d
380e
400e
480e
560e
610e
(75)(75)(75)(75)(75)
1. Bending space at terminals shall be measured in a straight line from the end of thelug or wire connector in a direction perpendicular to the enclosure wall.
2. For removable and lay-in wire terminals intended for only one wire, bending spaceshall be permitted to be reduced by the following number of millimeters:
a 13 mmb 25 mmc 40 mmd 50 mme 75 mm
3. This column shall be permitted to determine the required wire-bending space forcompact stranded aluminum conductors in sizes up to 500 mm2 and manufactured usingAA-8000 series electrical grade aluminum alloy conductor material in accordance with3.10.1.14.
Power Cables & Wires Technical Manual
99
Table A24. Full-Load Current, Three-Phase Alternating-CurrentMotorsThe following values of full-load currents are typical for motors running at speeds usual for beltedmotors and motors with normal torque characteristics.
The voltages listed are rated motor voltages. The currents listed shall be permitted for systemvoltage ranges of 220 to 240, 380 to 415, and 440 to 480 volts.
Horsepower
Induction-Type SquirrelCage and Wound Rotor
(Amperes)Synchronous-Type UnityPower Factor* (Amperes)
230Volts
400Volts
460Volts
230Volts
400Volts
460Volts
½¾1
1½235
7½
2.23.24.26.06.89.615.222
1.31.82.33.34.36.19.714
1.11.62.13.03.44.87.611
————————
————————
————————
101520253040
2842546880104
182734445166
142127344052
———536383
———
33.640.852
———263241
506075100125150200
130154192248312360480
83103128165208240320
657796
124156180240
104123155202253302400
66.481.6104
134.4168
201.3268
526178
101126151201
250300350400450500
——————
403482560636711786
302361414477515590
——————
——————
——————
*For 90 and 80 percent power factor, the figures shall be multiplied by 1.1 and 1.25,respectively.
Power Cables & Wires Technical Manual
100
Table A25. Conversion Table of Polyphase Design B, C, and DMaximum Locked-Rotor Currents for Selection of DisconnectingMeans and Controllers as Determined from Horsepower andVoltage Rating and Design LetterFor use only with 4.30.9.10, 4.40.2.2, 4.40.5.1 and 4.55.1.8(c).
RatedHorsepower
Maximum Motor Locked-Rotor Current in Amperes,Two- and Three-Phase, Design B, C, and D*
230 Volts 400 volts 460 VoltsB, C, D E B, C, D E B, C, D E
½¾1
1½235
7½
20253040506492
127
202530405073122183
12.14.516.52232415981
1214.516.52232
46.578
116.5
1012.51520253246
63.5
1012.5152025
36.561
91.5101520253040
162232290365435580
225337449562674824
104.5149.5183237278
368.5
145.5217.5283.5364430523
81116145183218290
113169225281337412
506075100125150200
72587010851450181521702900
1030123615451873234128093745
463.558272496512111447
1933.5
65882710311247
1561.51873.52497.5
36343554372590810851450
515618773937117114051873
250300350400450500
——————
——————
2435.52937.53449.538674487
4829.5
31283750.54433
4993.55818
6237.5
182522002550290032503625
234428093277374542144682
*Design A motors are not limited to a maximum starting current or locked rotorcurrent.
Power Cables & Wires Technical Manual
101
Table A26 Ampacities of Two or Three Insulated Conductors,Rated 0 through 2000 Volts, Within an Overall Covering(Multiconductor Cable), in Raceway in Free Air Based on AmbientAir Temperature of 30ºC
Conductor Size
mm2
Temperature Rating of Conductor. See Table 3.10.1.13600C 750C 900C 600C 750C 900C
TypesTW,UF
TypesRH,
RHW,THHW,THW,
THWN,XHHW,
ZW
TypesTHHN,THHW,THW-2,
THWN-2,RHH,
RHW-2,USE-2,XHHW,
XHHW-2,ZW-2
TypesTW
TypesRH,
RHW,THHW,THW,
THWN,XHHW
TypesTHHN,THHW,THW-2,
THWN-2,RHH,
RHW-2,USE-2,XHHW,
XHHW-2,ZW-2
COPPER ALUMINUM
125150175200250
205234250274315
245281300328378
276317340371427
160185199218254
192221238261303
217250270295342
*Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection forthese conductor types shall not exceed 15 amperes for 2.0 mm2 (1.6 mm dia.), 20 amperes for 3.5mm2 (2.0 mm dia.), and 30 amperes for 5.5 mm2 (2.6 mm dia.) copper; or 15 amperes for 3.5 mm2
(2.0 mm dia.) and 25 amperes for 5.5 mm2 (2.6 mm dia.) aluminum and copper-clad aluminum.
Power Cables & Wires Technical Manual
102
Table A27. Ampacities of Multiconductor Cables with Not Morethan Three Insulated Conductors, Rated 0 Through 2000 Volts, inFree Air Based on Ambient Air Temperature of 40ºC (For TypesTC, MC, MI, UF, and USE Cables)
Conductor Sizemm2
Temperature Rating of Conductor. See Table 3.10.1.13.600C 750C 850C 900C 600C 750C 850C 900C
COPPER ALUMINUM125150175200250
212237257281321
274306332363416
305341371406465
320357388425487
166186202222255
214240261287330
239268292317368
250280304334385
*Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection forthese conductor types shall not exceed 15 amperes for 2.0 mm2 (1.6 mm dia.), 20 amperes for 3.5mm2 (2.0 mm dia.), and 30 amperes for 5.5 mm2 (2.6 mm dia.) copper; or 15 amperes for 3.5 mm2
(2.0 mm dia.), and 25 amperes for 5.5 mm2 (2.6 mm dia.) aluminum and copper-clad aluminum.
Table A28. Ampacities of Single Insulated Conductors, Rated 0 through 2000 Volts, in NonmagneticUnderground Electrical Ducts (One Conductor per Electrical Duct), Based on Ambient EarthTemperature of 20ºC, Electrical Duct Arrangement per Figure B-310-2, Conductor Temperature75ºC
ConductorSize
(mm2)
3 Electrical Duct(Fig. B-310-2,
Detail 2)
6 Electrical Duct
(Fig. B-310-2,Detail 3)
9 Electrical Duct(Fig. B-310-2,
Detail 4)
3 Electrical Duct(Fig. B-310-2,
Detail 2)
6 Electrical Duct(Fig. B-310-2,
Detail 3)
9 Electrical Duct(Fig. B-310-2,
Detail 4)
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
COPPER ALUMINUMRHO
60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
125175250400
410503624794
344418511640
327396484603
386472583736
295355431534
275330400494
369446545674
270322387469
252299360434
320393489626
269327401505
256310379475
302369457581
230277337421
214258313389
288350430538
211252305375
197235284347
10
3
Po
wer
Cab
les&
Wires
Tech
nical
Man
ual
Table A29. Ampacities of Three Insulated Conductors, Rated 0 through 2000 Volts, Within an OverallCovering (Three-Conductor Cable) in Underground Electrical Ducts (One Cable per Electrical Duct)Based on Ambient Earth Temperature of 20ºC, Electrical Duct Arrangement per Figure B-310-2,Conductor Temperature 75ºC
ConductorSize
(mm2)
1 Electrical Duct(Fig. B-310-2, Detail 1)
3 Electrical Duct(Fig. B-310-2, Detail 2)
6 Electrical Duct(Fig. B-310-2, Detail 3)
1 Electrical Duct(Fig. B-310-2, Detail 1)
3 Electrical Duct(Fig. B-310-2, Detail 2)
6 Electrical Duct(Fig. B-310-2, Detail 3)
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
TypesRHW, THHW,THW, THWN,XHHW, USE
COPPER ALUMINUM
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
125175250400500
297363444552628
265321389478539
256310375459518
280340414511579
222267320388435
209250299362405
258312377462522
184219261314351
169202240288321
233285352446521
207252308386447
201244297372430
219267328413480
174209254314361
163196237293336
505245299374433
144172207254291
132158190233266
10
4
Po
wer
Cab
les&
Wires
Tech
nical
Manu
al
Table A30. Ampacities of Three Single Insulated Conductors, Rated 0 Through 2000 Volts, inUnderground Electrical Ducts (Three Conductors per Electrical Duct) Based on Ambient EarthTemperature of 20ºC, Electrical Duct Arrangement per Figure B-310-2, Conductor Temperature 75ºC
ConductorSizemm2
1 Electrical Duct(Fig. B-310-2, Detail 1)
3 Electrical Duct(Fig. B-310-2, Detail 2)
6 Electrical Duct(Fig. B-310-2, Detail 3)
1 Electrical Duct(Fig. B-310-2, Detail 1)
3 Electrical Duct(Fig. B-310-2, Detail 2)
6 Electrical Duct(Fig. B-310-2, Detail 3)
TypesRHW, THHW, THW,THWN, XHHW, USE
TypesRHW, THHW, THW,THWN, XHHW, USE
TypesRHW, THHW, THW,THWN, XHHW, USE
TypesRHW, THHW, THW,THWN, XHHW, USE
TypesRHW, THHW, THW,THWN, XHHW, USE
TypesRHW, THHW, THW,THWN, XHHW, USE
COPPER ALUMINUM
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
RHO60LF50
RHO90LF100
RHO120LF100
125150175200
334373409442
290321351376
279308337361
310344377394
236260283302
220242264280
281310340368
192210228243
176192209223
261293321349
227252276297
218242265284
242272296321
185204222238
172190207220
220245266288
150165179191
137151164174
105
Pow
erC
ables&
Wires
Tech
nicalM
anu
al
Power Cables & Wires Technical Manual
106
Table A31. Ampacities of Two or Three Insulated Conductors,Rated 0 Through 2000 Volts, Cabled Within an Overall (Two- orThree-Conductor) Covering, Directly Buried in Earth, Based onAmbient Earth Temperature of 20ºC, Arrangement per FigureB-310-2, 100 Percent Load Factor, Thermal Resistance (Rho) of 90
ConductorSizemm2
1 Cable(Fig. B-310-2,
Detail 5)
2 Cable(Fig. B-310-2,
Detail 6)
1 Cable(Fig. B-310-2,
Detail 5)
2 Cable(Fig. B-310-2,
Detail 6)600C 750C 600C 750C 600C 750C 600C 750C
TypesUF
TypesRHW,
THHW,THW,
THWN,XHHW,
USE
TypesUF
TypesRHW,
THHW,THW,
THWN,XHHW,
USE
TypesUF
TypesRHW,
THHW,THW,
THWN,XHHW,
USE
TypesUF
TypesRHW,
THHW,THW,
THWN,XHHW,
USE
COPPER ALUMINUM
125175250400500
—————
333401481585657
—————
308370442535600
—————
261315381473545
—————
241290350433497
Note: For ampacities of Type UF cable in underground electrical ducts, multiply theampacities shown in the table by 0.74.
Power Cables & Wires Technical Manual
107
Table A32. Ampacities of Three Triplexed Single InsulatedConductors, Rated 0 Through 2000 Volts, Directly Buried in EarthBased on Ambient Earth Temperature of 20ºC, Arrangement perFigure B-310-2, 100 Percent Load Factor, Thermal Resistance (Rho)of 90
ConductorSizemm2
See Fig. B-310-2,Details 7
See Fig. B-310-2,Details 8
See Fig. B-310-2,Details 7
See Fig. B-310-2,Details 8
600C 750C 600C 750C 600C 750C 600C 750CTYPES TYPES
UF USE UF USE UF USE UF USECOPPER ALUMINUM
125175250400500
—————
370445436654744
—————
336403483587665
—————
289349424525608
—————
263316382471544
Table A33. Ampacities of Three Single Insulated Conductors, Rated0 Through 2000 Volts, Directly Buried in Earth Based on AmbientEarth Temperature of 20ºC, Arrangement per Figure B-310-2, 100Percent Load Factor, Thermal Resistance (Rho) of 90
ConductorSizemm2
See Fig. B-310-2,Detail 9
See Fig. B-310-2,Detail 10
See Fig. B-310-2,Detail 9
See Fig. B-310-2,Detail 10
600C 750C 600C 750C 600C 750C 600C 750CTYPES TYPES
UF USE UF USE UF USE UF USE
COPPER ALUMINUM
125175250400
————
429516626767
————
394474572700
————
335403490605
————
308370448552
Power Cables & Wires Technical Manual
108
Table A34. Maximum Number of Conductors and Fixture Wires inElectrical Metallic Tubing (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RH 2.0 (1.6)3.5 (2.0)
64
108
1613
2823
3931
6451
11290
169136
221177
282227
RHH,RHW, RHW-2
2.0 (1.6)3.5 (2.0)
43
76
119
2017
2723
4638
8066
120100
157131
201167
RH,RHH,RHW, RHW-2
5.5 (2.6)8.0 (3.2)
14
211
521
843
1375
1898
301613
532822
814234
1055544
1357056
223038
110
111
211
431
643
1075
17139
262013
342617
443322
506080
100
0000
1100
1111
1111
2211
4433
7655
111087
1513119
19171412
125150175200250
00000
00000
00000
11110
11111
11111
33322
55443
76654
98776
325375400500
0000
0000
0000
0000
1000
1111
1111
3221
4332
5443
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
8652
151185
2519148
43332413
58453318
96745530
1681299653
25419514581
332255190105
424326243135
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 6 10 16 28 39 64 112 169 221 282
RHH*, RHW*,RHW-2*, THHW,THW
3.5 (2.0)5.5 (2.6)
43
86
1310
2318
3124
5140
9070
136106
177138
227177
RHH*, RHW*,THW-2*, THW,THHW, THW-2
8.0 (3.2) 1 4 6 10 14 24 42 63 83 106
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
14223038
1111
3111
4321
8643
11864
1813107
32241712
48362618
63473424
81604431
506080
100
0000
1110
1111
2111
3321
6543
10976
1613119
20171512
26221916
125150175200250
00000
00000
11000
11111
11111
32111
54433
76654
108776
13111097
*Types RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
109
Table A34. Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
325375400500
0000
0000
0000
1000
1110
1111
2111
3332
4443
6554
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
129532
22161064
35261697
6145281612
8461382216
138101633626
2411761116446
3642661679669
47634721912691
608443279161116
223038
111
211
431
754
1075
16118
282015
433022
564029
715137
506080100
1000
1111
1111
3211
4332
7654
121087
19161311
25201714
32262218
125150175200250
00000
00000
11100
11111
11111
33211
65443
97665
1110986
151311108
325375400500
0000
0000
0000
1000
1111
1111
2111
4332
5443
7554
FEP, FEPB, PFA,PFAH, TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
12963
2115116
34251810
60433118
81594224
134987040
23417112270
354258185106
462337241138
590430309177
142230
211
431
753
1296
17128
282013
503524
755336
986947
1268860
PFA, PFAH, TFE 38 1 1 2 4 6 9 16 25 33 42
PFA, PFAH,TFE, Z
506080100
1000
1111
1111
3321
5432
8654
141198
21171411
27221815
35292419
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
1410643
25181175
412918118
7251312014
9869422719
161114704431
2822001227754
42630218511782
556394241153107
711504309195137
223038
111
311
532
964
1386
211310
372218
563428
744536
945746
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
8652
151185
2519148
43332413
58453318
96745530
1681299653
25419514581
332255190105
424326243135
*Types RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
110
Table A34. Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
XHH, XHHW,XHHW-2, ZW
142230
111
321
643
1075
14107
221611
392820
604331
785640
1007251
XHH, XHHW,XHHW-2
38506080
100
11000
11111
11111
43211
54332
87654
15131097
2319161311
3025211714
3832272218
125150175200250
00000
00000
11100
11111
11111
33211
65443
98765
1210986
151311108
325375400500
0000
0000
0000
1000
1110
1111
2111
4332
5443
6554
FIXTURE WIRES
TypeConductorSize (mm2)
Raceway Size (mm)15 20 25 32 40 50
FFH-2, RFH-2, FHH-3 0.751.25
87
1412
2420
4134
5647
9278
SF-2, SFF-2 0.751.252.0
1087
181512
302520
524334
715847
1169678
SF-1, SFF-1 0.75 18 33 53 92 125 206RFH-1, RFHH-2, TF, TFF, XF,XFF
0.75 14 24 39 68 92 152
RFHH-2, TF, TFF, XF, XFF 1.25 11 19 31 55 74 123
XF, XFF 2.0 8 15 25 43 58 96TFN, TFFN 0.75
1.252217
3829
6348
10883
148113
244186
PF, PFF, PGF, PGFF, PAF,PTF, PTFF, PAFF
0.751.252.0
211612
362821
594634
1037960
14010881
231179134
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
272014
473525
775641
1339872
18113398
298220161
KF-2, KFF-2 0.751.252.03.55.5
392719138
6948332315
11178543725
193136936443
2621851278758
43330520914496
KF-1, KFF-1 0.751.252.03.55.5
463322149
8257382516
13393634127
2301611087247
3132201489864
516362244161105
XF, XFF 3.55.5
43
86
1310
2318
3124
5140
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A35 should be used.
Power Cables & Wires Technical Manual
111
Table A35. Maximum Number of Compact Conductors in ElectricalMetallic Tubing (Based on Table 9.1.1.1)
COMPACT CONDUCTORSType Conductor
Size (mm2)Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100THW,THW-2, THHW
8.014223038
21111
43211
65431
119653
1612974
262015118
4635261913
6953402921
9070523827
11589674934
506080
100
1000
1111
1111
3211
4332
7554
121087
18151311
23201714
30252118
125150175200250
00000
00000
11100
11111
11111
33211
55443
87665
119886
1412
11108
325375400500
0000
0000
0000
1000
1111
1111
2111
4332
5443
7554
THHN, THWN,THWN-2
8.014223038
—2111
—4311
—7432
—13864
—181186
—29181310
—52322317
—78483426
—102634534
—130815843
506080
100
1100
1111
1111
3321
5433
8765
1412108
22181512
29242016
37302521
125150175200250
00000
10000
11110
11111
11111
43321
65544
108765
13111097
161412119
325375400500
0000
0000
0000
1110
1111
1111
3221
4443
6553
7664
XHHW, XHHW-2
8.014223038
31111
54311
86432
1511864
20151186
3425181310
5944322317
9066483426
11787634534
149111815843
506080
100
1100
1111
1111
3321
5433
8765
1412108
22181513
29242017
37312521
125150175200250
00000
10000
11110
11111
21111
43321
76544
109876
13111097
171413119
325375400500
0000
0000
0000
1110
1111
1111
3221
4333
6554
8665
Definition: Compact stranding is the result of a manufacturing process where thestandard conductor is compressed to the extent that the interstices (voids between strandwires) are virtually eliminated.
Power Cables & Wires Technical Manual
112
Table A36. Maximum Number of Conductors and Fixture Wires in ElectricalNonmetallic Tubing (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductor Size[mm2 (mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50RH 2.0 (1.6)
3.5 (2.0)43
87
1512
2721
3729
6149
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
32
65
109
1916
2622
4336
RH,RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
111
411
733
1365
1797
291512
223038
100
111
211
431
643
975
506080
100
0000
0000
1111
1111
2111
4332
125150175200250
00000
00000
00000
11110
11111
11111
325375400500
0000
0000
0000
0000
1000
1111
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
7541
131074
2217137
40312313
55423217
92715229
RHH*, RHW*,RHW-2*, THHW,THW, THW-2
2.0 (1.6) 4 8 15 27 37 61
RHH*, RHW*,RHW-2*, THHW,THW
3.5 (2.0)5.5 (2.6)
33
75
129
2117
2923
4938
RHH*, RHW*,RHW-2*, THHW,THW, THW-2
8.0 (3.2) 1 3 5 10 14 23
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
14223038
1110
2111
4321
7543
10864
171396
506080
100
0000
1100
1111
2111
3321
5543
125150175200250
00000
00000
10000
11111
11111
22111
325375400500
0000
0000
0000
0000
1110
1111
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
113
Table A36. Continued
CONDUCTORS
TypeConductor Size[mm2 (mm dia.)]
Raceway Size (mm)15 20 25 32 40 50
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
107421
1813853
32231586
5842261511
8058362115
13296603525
223038
111
111
421
753
965
15118
506080
100
0000
1110
1111
3211
4332
7544
125150175200250
00000
00000
11000
11111
11111
32211
325375400500
0000
0000
0000
1000
1110
1111
FEP, FEPB,PFA, PFAH,TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
10753
181395
3123169
56412917
77564023
128936738
142230
111
421
643
1285
16118
271913
PFA, PFAH,TFE
38 1 1 1 4 5 9
PFA, PFAH,TFE, Z
506080
100
0000
1111
1111
3211
4432
7654
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
128531
2215964
382716107
6848291813
9366402518
154109674230
223038
111
311
532
954
1276
201210
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
75411
1310743
22171375
403123139
5542321713
9271522921
2230
11
11
42
75
96
1511
Power Cables & Wires Technical Manual
114
Table A36. Continued
CONDUCTORS
TypeConductor Size[mm2 (mm dia.)]
Raceway Size (mm)15 20 25 32 40 50
XHH, XHHW,XHHW-2
38 1 1 1 3 5 8506080
100
0000
1110
1111
3211
4332
7654
125150175200250
00000
00000
11100
11111
11111
33211
325375400500
0000
0000
0000
1000
1110
1111
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50FFH-2, RFH-2, RFHH-3 0.75
1.2565
1210
2118
3932
5345
8874
SF-2, SFF-2 0.751.252.0
875
151310
272218
494032
675545
1119274
SF-1, SFF-1 0.75 15 28 48 86 119 197
RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 11 20 35 64 88 145
RFHH-2, TF, TFF, XF,XFF
1.25 9 16 29 51 71 117
XF, XFF 2.0 7 13 22 40 55 92
TFN, TFFN 0.751.25
1813
3325
5743
10278
141107
233178
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
171310
312418
544231
977556
13310377
221171128
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
221612
402922
705138
1259268
17212793
285210154
KF-2, KFF-2 0.751.252.03.55.5
312215107
5841281913
10171493322
182128886040
2501761218355
41329120013892
KF-1, KFF-1 0.751.252.03.55.5
382618127
6949332214
12185573824
2171521026844
2982091419361
493346233154101
XF, XFF 3.55.5
33
75
129
2117
2923
4938
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A37 should be used.
Power Cables & Wires Technical Manual
115
Table A37. Maximum Number of Compact Conductors in Electrical NonmetallicTubing (Based on Table 9.1.1.1)
COMPACT CONDUCTORS
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50THW, THW-2,THHW
8.014223038
11110
32111
64321
118643
1511864
251914107
506080100
0000
1110
1111
3211
4332
6544
125150175200250
00000
00000
11000
11111
11111
32211
325375400500
0000
0000
0000
1000
1110
1111
THHN, THWN,THWN-2
8.014223038
1111
4211
7432
12754
171075
2817129
506080100
1000
1111
1111
3321
5432
8654
125150175200250
00000
00000
11100
11111
11111
33221
325375400500
0000
0000
0000
1110
1111
1111
XHHW,XHHW-2
8.014223038
21111
43211
86432
1410754
19141075
322417129
506080100
1000
1111
1111
3321
5433
8754
125150175200250
00000
00000
11110
11111
11111
33321
325375400500
0000
0000
0000
1110
1111
1111
Definition: Compact stranding is the result of a manufacturing process where thestandard conductor is compressed to the extent that the interstices (voids between strandwires) are virtually eliminated.
Power Cables & Wires Technical Manual
116
Table A38 Maximum Number of Conductors and Fixture Wires inFlexible Metal Conduit (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RH 2.0 (1.6)3.5 (2.0)
65
108
1512
2419
3528
6250
9475
135108
184148
240193
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
43
76
119
1714
2521
4437
6755
9680
131109
171142
RH, RHH,RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
311
521
743
1165
1797
301512
452319
643427
884637
1156048
223038
110
111
211
431
542
1075
14117
211610
292214
372819
506080
100
0000
1100
1111
1111
2111
4332
6554
9876
121198
16141210
125150175200250
00000
00000
00000
11100
11111
11111
32211
44333
65544
87665
325375400500
0000
0000
0000
0000
1000
1111
1111
2111
3221
4333
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
9753
151185
2318137
36282111
53413017
94725430
1411088145
20315611664
27721215888
361277207115
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 6 10 15 24 35 62 94 135 184 240
RHH*, RHW*,RHW-2*, THW,THHW,
3.5 (2.0)5.5 (2.6)
54
86
1210
1915
2822
5039
7559
10885
148115
193151
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
8.0 (3.2) 1 4 6 9 13 23 35 51 69 90
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
14223038
1111
3111
4321
7542
10754
1813107
27201410
39292115
53392920
69513726
506080
100
0000
1110
1111
1111
3321
6543
9765
121097
17141210
22191613
125150175200250
00000
00000
11000
11111
11111
32111
43332
65443
87665
119876
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
117
Table A38 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
325375400500
0000
0000
0000
0000
1110
1111
1111
3221
4332
5443
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
13963
2216106
3324159
52382414
76563520
134986235
2021479353
29121213477
396289182105
518378238137
14223038
2111
4211
6431
10643
14964
2516118
38241712
55342418
76463324
99614332
506080
100
1000
1111
1111
2111
4321
7654
10976
1512108
20171412
27221815
125150175200250
00000
00000
11100
11111
11111
33211
54332
76554
98765
1211987
325375400500
0000
0000
0000
0000
1110
1111
1111
3221
4333
5443
FEP, FEPB,PFA, PFAH,TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
129642
21151164
322417107
5137261511
7454392216
13095683928
1961431035942
2822061488560
38528120111582
502367263151107
2230
11
31
53
75
117
1913
2920
4229
5739
7551
PFA, PFAH, TFE 38 1 1 2 3 5 9 14 20 27 36
PFA, PFAH,TFE, Z
506080
100
1100
1111
1111
3211
4332
8654
11986
1714119
23191513
30242016
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
1511643
25181175
392817117
6143261712
8963392417
157111684330
2361681036545
3402411489365
46332920112789
605429263166117
223038
111
311
532
854
1276
211210
311915
452722
613730
804939
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
97531
1511853
23181375
362821118
5341301712
9472543022
141108814533
2031561166448
2772121588865
36127720711585
2230
11
21
43
64
96
1611
2417
3424
4733
6144
Power Cables & Wires Technical Manual
118
Table A38 Continued
COMPACT CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
XHH, XHHW,XHHW-2
38 1 1 1 3 5 8 13 18 25 32506080100
1000
1111
1111
2211
4332
7654
10976
1513109
21171412
27231915
125150175200250
00000
00000
11100
11111
11111
33211
54433
76554
108765
1311987
325375400500
0000
0000
0000
0000
1110
1111
1111
3221
4333
5443
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50FFH-2, RFH-2, RFHH-3 0.75
1.2587
1412
2219
3529
5143
9076
SF-2, SFF-2 0.751.252.0
1197
181512
282319
443629
645343
1139476
SF-1, SFF-1 0.75 19 32 50 78 114 201
RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 14 24 37 58 84 148
RFHH-2, TF, TFF, XF,XFF
1.25 11 19 30 47 68 120
XF, XFF 2.0 9 15 23 36 53 94
TFN, TFFN 0.751.25
2317
3829
5945
9371
135103
237181
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
221712
362821
564332
886851
1289974
225174130
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
282015
473525
725339
1138361
16512189
290214157
KF-2, KFF-2 0.751.252.03.55.5
412819139
6848332315
10574513523
164116805536
2391681168053
42129720414094
KF-1, KFF-1 0.751.252.03.55.5
4834231510
8257382516
12588593925
196138936140
2852001358958
503353237157103
XF, XFF 3.55.5
54
86
1210
1915
2822
5039
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A39 should be used.
Power Cables & Wires Technical Manual
119
Table A39 Maximum Number of Compact Conductors in FlexibleMetal Conduit (Based on Table 9.1.1.1)
COMPACT CONDUCTORSType Conductor
Size (mm2)Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100THW, THHW,THW-2
8.014223038
21111
43211
65321
107543
1411864
252015117
3829221611
5543322316
7558433222
9876574229
506080
100
1000
1111
1111
2111
3321
6544
10876
1412108
19161411
25211815
125150175200250
00000
00000
11100
11111
11111
32211
44333
76554
98765
1210987
325375400500
0000
0000
0000
0000
1110
1111
1111
3221
4333
6554
THHN, THWN,THWN-2
8.014223038
3111
4311
7432
11753
161075
2918139
43271914
62382821
85523828
111694937
506080
100
1100
1111
1111
3211
4432
8654
121087
17141210
24201714
31262218
125150175200250
00000
10000
11110
11111
11111
33321
55433
87654
119876
14121098
325375400500
0000
0000
0000
1000
1110
1111
2111
3331
5443
6554
XHHW,XHHW-2
8.014223038
32111
54311
86432
139753
19141075
332418139
5037271914
7153382821
9772523828
12795694937
506080
100
1100
1111
1111
3211
4432
8754
121087
17151210
24201714
31262218
125150175200250
00000
10000
11110
11111
11111
43321
55443
87654
119876
141211108
325375400500
0000
0000
0000
1000
1111
1111
2111
3332
5443
6554
Definition: Compact stranding is the result of a manufacturing process where thestandard conductor is compressed to the extent that the interstices (voids between strandwires) are virtually eliminated.
Power Cables & Wires Technical Manual
120
Table A40 Maximum Number of Conductors and Fixture Wires in IntermediateMetal Conduit (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RH 2.0 (1.6)3.5 (2.0)
65
119
1814
3125
4234
6956
9879
151122
202163
261209
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
44
86
1311
2218
3025
4941
7058
10889
144120
186154
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
311
531
843
1586
20108
331714
472419
723830
975040
1246552
223038
110
111
311
532
653
1185
15117
231812
312416
413120
506080100
0000
1100
1111
1111
3211
4433
6654
10976
1412109
18151311
125150175200250
00000
00000
10000
11111
11111
11111
33221
54433
66554
87765
325375400500
0000
0000
0000
0000
1110
1111
1111
2111
3332
4443
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
10753
171395
2721158
47362715
64493620
104805933
1471138447
22817513072
30423417497
392301224124
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 6 11 18 31 42 69 98 151 202 261
RHH*, RHW*,RHW-2*, THHW,THW
3.5 (2.0)5.5 (2.6)
54
97
1411
2519
3426
5643
7961
12295
163127
209163
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
8.0 (3.2) 2 4 7 12 16 26 37 57 76 98
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
14223038
1111
3211
5431
9653
12964
2015117
28211511
43322316
58433122
75564128
506080100
1000
1111
1111
3211
4332
6544
9865
1412108
19161311
24201714
125150175200250
0000
0000
1100
1111
1111
3211
4432
7644
9865
121087
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
121
Table A40 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
325375400500
000
000
000
100
110
111
111
321
433
543
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
141063
2417116
39291810
68493118
91674224
1491096839
2111549756
32623815086
436318200115
562410258149
14223038
2111
4311
7432
13854
171075
2817129
40251713
62382720
83513627
107664735
506080
100
1100
1111
1111
3321
4432
8654
11976
1714129
23191613
29242017
125150175200250
00000
00000
11110
11111
11111
33221
54433
87654
109876
13121097
325375400500
0000
0000
0000
1110
1111
1111
2111
3332
5443
6554
FEP, FEPB,PFA, PFAH, TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
1310743
23171275
382820118
6648341914
8965462619
145106764331
2051501076144
3172311669567
42330922112790
545398285163116
2230
11
32
54
106
139
2115
3021
4732
6343
8156
PFA, PFAH, TFE 38 1 1 2 4 6 10 14 22 30 39
PFA, PFAH,TFE, Z
506080
100
1100
1111
1111
4321
5433
8765
121087
19151310
25211714
32272218
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
1611743
28201275
463220129
7956342115
10776462920
175124764833
2471751076847
38127116610573
51036222114098
657466285180127
223038
111
311
633
1065
1487
231411
332016
503025
674133
875343
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
107531
1713954
27211586
4736271511
6449362015
10480593324
147113844735
2281751307253
3042341749771
39230122412492
2230
11
31
43
85
117
1812
2518
3927
5237
6747
Power Cables & Wires Technical Manual
122
Table A40 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
XHH, XHHW,XHHW-2
38 1 1 2 4 5 9 13 20 27 35
506080
100
1100
1111
1111
3321
5432
8654
11976
17141210
23191613
30252017
125150175200250
00000
00000
11110
11111
11111
33321
54433
87654
119876
14121098
325375400500
0000
0000
0000
1110
1111
1111
2111
3332
5443
6554
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50FHH-2, RFH-2, RFHH-3 0.75
1.2598
1613
2622
4538
6151
10084
SF-2, SFF-2 0.751.252.0
12108
201713
332722
574738
776451
12610484
SF-1, SFF-1 0.75 21 36 59 101 137 223RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 15 26 43 75 101 165
RFH-2, TF, TFF, XF, XFF 1.25 12 21 35 60 81 133
XF, XFF 2.0 10 17 27 47 64 104
TFN, TFFN 0.751.25
2519
4232
6953
11991
161123
264201
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
231813
403123
665138
1138766
15311889
250193145
ZF, ZFF, ZHF, HF, HFF 0.751.252.0
302216
523828
856346
14610879
197145107
322238175
KF-2, KFF-2 0.751.252.03.55.5
4431211410
7553362517
12387604127
2121491037047
2872021399564
468330227156104
KF-1, KFF-1 0.751.252.03.55.5
5237251610
9063422818
147103694630
2531781197952
34224016110770
558392264175114
XF, XFF 3.55.5
54
97
1411
2519
3426
5643
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A41 should be used.
Power Cables & Wires Technical Manual
123
Table A41 Maximum Number of Compact Conductors inIntermediate Metal Conduit (Based on Table 9.1.1.1)
COMPACT CONDUCTORSType Conductor
Size (mm2)Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100THW, THW-2,THHW
8.014223038
21111
43211
76431
1310754
17131075
282216128
4031231712
6248362618
8364483525
10782624532
506080100
1000
1111
1111
3321
4432
7654
10976
1613119
21181513
27232016
125150175200250
00000
00000
11110
11111
11111
33221
54433
76654
109876
13111098
325375400500
0000
0000
0000
1110
1111
1111
2111
3332
5443
6554
THHN, THWN,THWN-2
8.014223038
3111
5311
8533
14965
191286
32201410
45282015
70433123
93584131
120745340
506080100
1100
1111
2111
4332
5443
9765
131097
20161411
26221815
34282419
125150175200250
00000
10000
11111
11111
21111
43322
65443
97765
1210987
151311109
325375400500
0000
0000
0000
1110
1111
1111
2111
4332
5443
7664
XHHW, XHHW-2 8.014223038
32111
64311
97533
1612965
22161286
3727201410
5238282015
8059433123
10780584131
138103745340
506080100
1100
1111
2111
4332
5443
9765
131197
20171411
26221815
34292420
125150175200250
00000
10000
11111
11111
21111
43332
65443
98765
1210987
161312119
325375400500
0000
0000
0000
1110
1111
1111
2111
4332
5443
7664
Definition: Compact stranding is the result of a manufacturing process where thestandard conductor is compressed to the extent that interstices (voids between strandwires) are virtually eliminated.
Power Cables & Wires Technical Manual
124
Table A42 Maximum Number of Conductors and Fixture Wires inLiquidtight Flexible Nonmetallic Conduit (Type FNMC-B*) (Based onTable 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
10 15 20 25 32 40 50
RH 2.0 (1.6)3.5 (2.0)
33
65
108
1613
2923
3830
6250
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
21
43
76
1210
2117
2722
4436
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
111
311
521
843
1476
1897
291512
223038
000
110
111
211
431
643
975
506080100
0000
0000
1100
1111
1111
2111
4332
125150175200250
00000
00000
00000
00000
11111
11111
11111
325375400500
0000
0000
0000
0000
0000
1000
1111
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
5431
9753
151295
2519148
44332514
57433218
93715329
RHH†, RHW†,RHW-2†, THW,THHW, THW-2
2.0 (1.6) 3 6 10 16 29 38 62
RHH†, RHW†,RHW-2†, THHW,THW
3.5 (2.0)5.5 (2.6)
31
53
86
1310
2318
3023
5039
RHH†, RHW†,RHW-2†, THW,THHW, THW-2
8.0 (3.2) 1 1 4 6 11 14 23
RHH†, RHW†,RHW-2†, TW,THW, THHW,THW-2
14223038
1100
1111
3111
5321
8643
11864
181397
506080100
0000
0000
1110
1111
2211
3321
6543
125150175200250
00000
00000
00000
11000
11111
11111
32111
325375400500
0000
0000
0000
0000
1000
1110
1111
*Corresponds to Section 3.51.2.1(2).†Types RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
125
Table A42 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]Raceway Size (mm)
10 15 20 25 32 40 50THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
85311
139632
22161064
36261697
6346291612
8159372115
13397613525
223038
110
111
211
431
754
975
15118
506080100
0000
1000
1111
1111
3211
4332
7654
125150175200250
00000
00000
00000
11100
11111
11111
33211
325375400500
0000
0000
0000
0000
1000
1110
1111
FEP, FEPB, PFA,PFAH, TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
75411
129632
21151164
352518107
6144321813
7957412317
12994683927
2230
11
11
31
53
96
128
1913
PFA, PFAH, TFE 38 0 1 1 2 4 5 9
PFA, PFAH, TFE,Z
506080100
0000
1100
1111
1111
3321
4432
7654
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
96421
1510643
26181175
423018118
7352322014
9567412618
156111684330
223038
100
111
311
532
965
1276
201210
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
54311
97531
1512953
25191486
4433251410
5743321813
9371532922
2230
11
11
21
43
75
97
1611
Power Cables & Wires Technical Manual
126
Table A42 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]Raceway Size (mm)
10 15 20 25 32 40 50XHH, XHHW,XHHW-2
38 0 1 1 1 4 5 8
506080
100
0000
1000
1111
1111
3211
4332
7654
125150175200250
00000
00000
00000
11100
11111
11111
33211
325375400500
0000
0000
0000
0000
1000
1110
1111
FIXTURE WIRES
TypeConductorSize (mm2)
Raceway Size (mm)
10 15 20 25 32 40 50FFH-2, RFH-2 0.75
1.2554
87
1512
2420
4235
5446
8975
SF-2, SFF-2 0.751.252.0
654
1197
191512
302520
534435
695746
1139375
SF-1, SFF-1 0.75 11 19 33 53 94 122 199RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 8 14 24 39 69 90 147
RFHH-2, TF, TFF, XF,XFF
1.25 7 11 20 32 56 72 119
XF, XFF 2.0 5 9 15 25 44 57 93
TFN, TFFN 0.751.25
1410
2317
3930
6348
11185
144110
236180
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
13107
211612
372921
604635
1058161
13610579
223173129
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
17129
282015
483526
775742
13610073
17612995
288212156
KF-2, KFF-2 0.751.252.03.55.5
24171285
402819139
7049342315
11279543725
197139956544
2551801238557
41829520213993
KF-1, KFF-1 0.751.252.03.55.5
29201496
4834231510
8358392617
13494634227
2351651117348
3042141449562
499350236156102
XF, XFF 3.55.5
31
53
86
1310
2318
3023
5039
Note: This table is for concentric stranded conductors only. For compactstranded conductors, Table A43 should be used.
Power Cables & Wires Technical Manual
127
Table A43 Maximum Number of Compact Conductors in Liquidtight FlexibleNonmetallic Conduit (Type FNMC-B*) (Based on Table 9.1.1.1)
COMPACT CONDUCTORS
TypeConductorSize (mm2)
Raceway Size (mm)10 15 20 25 32 40 50
THW, THW-2,THHW
8.014223038
11110
21111
43211
75431
129753
1512964
251914117
506080
100
0000
1000
1111
1111
3211
4332
6544
125150175200250
00000
00000
00000
11100
11111
11111
32211
325375400500
0000
0000
0000
0000
1000
1111
1111
THHN, THWN,THWN-2
8.014
—1
2
4
7
13
17
28
223038
110
111
311
432
864
1176
17129
506080
100
0000
1100
1111
1111
4321
5433
8654
125150175200250
00000
00000
10000
11110
11111
11111
33221
325375400500
0000
0000
0000
0000
1110
1111
1111
XHHW,XHHW-2
8.014
11
32
54
96
1511
2015
3324
223038
110
111
311
432
864
1176
17129
506080
100
0000
1100
1111
1111
4321
5433
8754
125150175200250
00000
00000
10000
11110
11111
11111
33321
325375400500
0000
0000
0000
0000
1110
1111
1111
*Corresponds to Section 3.51.2.1(2).Definition: Compact stranding is the result of a manufacturing process where the standard conductors
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.
Power Cables & Wires Technical Manual
128
Table A44 Maximum Number of Conductors and Fixture Wires in LiquidtightFlexible Nonmetallic Conduit (Type FNMC-A*) (Based On Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
10 15 20 25 32 40 50
RH 2.0 (1.6)3.5 (2.0)
33
64
108
1613
2823
3831
6451
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
21
43
76
119
2017
2723
4538
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
111
311
521
843
1375
1897
301613
223038
000
110
111
211
431
643
1075
506080100
0000
0000
1100
1111
1111
2111
4433
125150175200250
00000
00000
00000
00000
11110
11111
11111
325375400500
0000
0000
0000
0000
0000
1000
1111
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
5431
9753
151295
2419148
43332413
58443318
96745530
RHH†, RHW†,RHW-2†, THW,THHW, THW-2
2.0 (1.6) 3 6 10 16 28 38 64
RHH†, RHW†,RHW-2†, THHW,THW
3.5 (2.0)5.5 (2.6)
31
43
86
1310
2318
3124
5140
RHH†, RHW†,RHW-2†, THW,THHW, THW-2
8.0 (3.2) 1 1 4 6 10 14 24
RHH†, RHW†,RHW-2†, TW,THW, THHW,THW-2
14223038
1100
1111
3111
4321
8643
11864
1813107
506080100
0000
0000
1110
1111
2111
3321
6543
125150175200250
00000
00000
00000
11000
11111
11111
32111
325375400500
0000
0000
0000
0000
1000
1110
1111
*Correspond to Section 3.51.2.1(1).†Types RHH, RHW,and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
129
Table A44 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
10 15 20 25 32 40 50
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
85311
139632
22161064
35251696
6245281612
8360382216
137100633626
223038
110
111
211
431
754
975
16118
506080
100
0000
1000
1111
1111
3211
4332
7654
125150175200250
00000
00000
00000
11100
11111
11111
33211
325375400500
0000
0000
0000
0000
1000
1110
1111
FEP, FEPB,PFA, PFAH,TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
75411
129632
21151164
342518107
6044311813
8059422417
13397704028
2230
11
11
31
53
96
128
2013
PFA, PFAH,TFE
38 0 1 1 2 4 5 9
PFA, PFAH,TFE, Z
506080
100
0000
1100
1111
1111
3321
5432
8654
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
96421
1510643
25181175
412918118
7251312014
9769422618
161114704431
223038
111
111
311
532
964
1386
211310
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
54311
97531
1512953
24191485
4333241310
5844331813
9674553022
2230
11
11
21
43
75
107
1611
Power Cables & Wires Technical Manual
130
Table A44 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
10 15 20 25 32 40 50
XHH, XHHW,XHHW-2
38 0 1 1 1 4 5 8506080
100
0000
1000
1111
1111
3211
4332
7654
125150175200250
00000
00000
00000
11100
11111
11111
33211
325375400500
0000
0000
0000
0000
1000
1110
1111
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
10 15 20 25 32 40 50FFH-2, RFH-2, RFHH-3 0.75
1.2554
87
1412
2320
4135
5547
9277
SF-2, SFF-2 0.751.252.0
654
1197
181512
292420
524335
705847
1169677
SF-1, SFF-1 0.75 12 19 33 52 92 124 205RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 8 14 24 39 68 91 152
RFHH-2, TF, TFF, XF,XFF
1.25 7 11 19 31 55 74 122
XF, XFF 2.0 5 9 15 24 43 58 96
TFN, TFFN 0.751.25
1410
2217
3929
6247
10983
146112
243185
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
13107
211612
372821
594534
1038060
13910780
230178133
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
17129
272015
473525
765641
1339872
17913297
297219161
KF-2, KFF-2 0.751.252.03.55.5
25171285
402819139
6948332315
11077533624
193136946443
2601831268658
43130320914396
KF-1, KFF-1 0.751.252.03.55.5
29211496
4833221510
8257392517
13192624127
2311621097247
3102181469763
514361243161105
XF, XFF 3.55.5
31
43
86
1310
2318
3124
5140
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A45 should be used.
Power Cables & Wires Technical Manual
131
Table A45 Maximum Number of Compact Conductors inLiquidtight Flexible Nonmetallic Conduit (Type FNMC-A*) (Basedon Table 9.1.1.1)
COMPACT CONDUCTORS
TypeConductorSize (mm2)
Raceway Size (mm)
10 15 20 25 32 40 50THW,THW-2, THHW
8.014223038
11110
21111
43211
65431
119753
1612964
262015118
506080
100
0000
1000
1111
1111
3211
4332
7554
125150175200250
00000
00000
00000
11100
11111
11111
33211
325375400500
0000
0000
0000
0000
1000
1111
1111
THHN, THWN,THWN-2
8.014223038
—1110
2111
4311
7432
13864
181186
29181310
506080
100
0000
1100
1111
1111
3321
5433
8765
125150175200250
00000
00000
10000
11110
11111
11111
33321
325375400500
0000
0000
0000
0000
1110
1111
1111
XHHW,XHHW-2
8.014223038
11110
32111
54311
86432
1511864
20151186
3425181310
506080
100
0000
1100
1111
1111
3321
5433
8765
125150175200250
00000
00000
10000
11110
11111
21111
43321
325375400500
0000
0000
0000
0000
1110
1111
1111
*Corresponds to Section 3.51.2.1(1).
Power Cables & Wires Technical Manual
132
Table A46 Maximum Number of Conductors and Fixture Wires in LiquidtightFlexible Metal Conduit (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RH 2.0 (1.6)3.5 (2.0)
65
108
1613
2923
3830
6250
9375
143115
186149
243195
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
43
76
1210
2117
2722
4436
6655
10284
133110
173144
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
311
521
843
1476
1897
291512
442318
683628
894637
1166148
223038
110
111
211
431
643
975
14117
221711
292214
382919
506080
100
0000
1100
1111
1111
2111
4332
6544
10876
131198
16141210
125150175200250
00000
00000
00000
11111
11111
11111
32211
44333
65544
87665
325375400500
0000
0000
0000
0000
1000
1111
1111
2111
3221
4333
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
9753
151295
2519148
44332514
57433218
93715329
1401088044
21516512368
28021516089
365280209116
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 6 10 16 29 38 62 93 143 186 243
RHH*, RHW*,RHW-2*, THHW,THW
3.5 (2.0)5.5 (2.6)
53
86
1310
2318
3023
5039
7558
11589
149117
195152
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
8.0 (3.2) 1 4 6 11 14 23 35 53 70 91
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
14223038
1111
3111
5321
8643
11864
181397
27201410
41302215
53402920
70523826
506080
100
0000
1110
1111
2211
3321
6543
8765
131198
17151210
23191613
125150175200250
00000
00000
11000
11111
11111
32111
43332
65543
87665
119876
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
133
Table A46 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
325375400500
0000
0000
0000
1000
1110
1111
1111
3221
4332
5443
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
13963
2216106
3626169
63462916
81593721
133976135
2011469253
30822514181
401292184106
523381240138
14 2 4 7 12 15 25 38 59 76 100223038
111
211
431
754
975
15118
231712
362619
473325
614432
506080
100
1000
1111
1111
3211
4332
7654
10876
1613119
21171412
27231915
125150175200250
00000
00000
11100
11111
11111
33211
54332
76554
108765
1211987
325375400500
0000
0000
0000
1000
1110
1111
1111
3331
4333
6553
FEP, FEPB,PFA, PFAH,TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
129632
21151164
352518107
6144321813
7957412317
12994683927
1951421025841
2992181568964
38928420311783
507370266152108
2230
11
31
53
96
128
1913
2920
4430
5840
7552
PFA, PFAH,TFE
38 1 1 2 4 5 9 14 21 28 36
PFA, PFAH,TFE, Z
506080
100
1100
1111
1111
3321
4432
7654
11986
18141210
23191613
30252017
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
2014854
26181175
423018118
7352322014
9567412618
156111684330
2351671026445
3602551569969
46933220312990
611434266168118
223038
211
311
532
965
1276
201210
311915
482923
623830
814940
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
97531
1512953
25191486
4433251410
5743321813
9371532922
140108804433
2151651236850
2802151608966
36528020911686
2230
11
21
43
75
97
1611
2417
3626
4834
6244
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
134
Table A46 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
XHH, XHHW,XHHW-2
38 1 1 1 4 5 8 12 19 25 33506080
100
1000
1111
1111
3211
4332
7654
10976
1613119
21171412
28231916
125150175200250
00000
00000
11100
11111
11111
33211
54332
76554
108765
13111087
325375400500
0000
0000
0000
1000
1110
1111
1111
3331
4333
6553
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50FFH-2, RFH-2, RFHH-3 0.75
1.2587
1512
2420
4235
5446
8975
SF-2, SFF-2 0.751.252.0
1197
191512
302520
534435
695746
1139375
SF-1, SFF-1 0.75 19 33 53 94 122 199RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 14 24 39 69 90 147
RFHH-2, TF, TFF, XF,XFF
1.25 11 20 32 56 72 119
XF, XFF 2.0 9 15 25 44 57 93
TFN, TFFN 0.751.25
2317
3930
6348
11185
144110
236180
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
211612
372921
604635
1058161
13610579
223173129
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
282015
483526
775742
13610073
17612995
288212156
KF-2, KFF-2 0.751.252.03.55.5
402819139
7049342315
11279543725
197139956544
2551801238557
41829520213993
KF-1, KFF-1 0.751.252.03.55.5
4834231510
8358392617
13494634227
2351651117348
3042141449562
499350236156102
XF, XFF 3.55.5
53
86
1310
2318
3023
5039
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A47 should be used.
Power Cables & Wires Technical Manual
135
Table A47 Maximum Number of Compact Conductors inLiquidtight Flexible Metal Conduit (Based on Table 9.1.1.1)
COMPACT CONDUCTORS
TypeConductorSize (mm2)
Raceway Size (mm)10 15 20 25 32 40 50 65 80 90 100
THW, THW-2,THHW
8.014
11
21
43
75
129
1512
2519
3829
5845
7659
9977
223038
110
111
211
431
753
964
14117
221611
342517
443223
574230
506080
100
0000
1000
1111
1111
3211
4332
6544
10876
1513119
20161412
26211815
125150175200250
00000
00000
00000
11100
11111
11111
32211
44333
76554
98765
1210987
325375400500
0000
0000
0000
0000
1000
1111
1111
1111
3331
4333
6554
THHN, THWN,THWN-2
8.014
1
2
4
7
13
17
28
43
66
86
112
223038
110
111
311
432
864
1176
17129
261914
412922
533828
695037
506080
100
0000
1100
1111
1111
4321
5433
8654
121087
19151310
24201714
32262218
125150175200250
00000
00000
10000
11110
11111
11111
33221
54433
87655
119876
14121198
325375400500
0000
0000
0000
0000
1110
1111
1111
2111
4332
5443
6554
XHHW,XHHW-2
8.014
11
32
54
96
1511
2015
3324
4937
7656
9873
12995
223038
110
111
311
432
864
1176
17129
261914
412922
533828
695037
506080
100
0000
1100
1111
1111
4321
5433
8754
121087
19161311
24201714
32272218
125150175200250
00000
00000
10000
11110
11111
11111
33321
55443
87665
119876
151211108
325375400500
0000
0000
0000
0000
1110
1111
1111
2111
4332
5443
6554
Definition: Compact stranding is the result of a manufacturing process where the standard conductorscompressed to the extent that the interstices (voids between strand wires) are virtually eliminated.
Power Cables & Wires Technical Manual
136
Table A48 Maximum Number of Conductors and Fixture Wires in Rigid Metal Conduit(Based on Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
RH 2.0 (1.6)3.5 (2.0)
65
108
1713
2923
3932
6552
9375
143115
191154
246198
387311
558448
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
43
76
1210
2117
2823
4638
6655
10285
136113
176146
276229
398330
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
311
521
843
1476
19108
311613
442318
683629
914838
1186149
1859777
267139112
223038
110
111
211
431
643
1075
14117
221711
302315
382919
604630
876644
506080
100
0000
1100
1111
1111
2211
4433
6544
10876
1311108
17141211
26232017
38332824
125150175200250
00000
00000
00000
11111
11111
11111
32211
44433
65544
87665
13111098
1816151311
325375400500
0000
0000
0000
0000
1000
1111
1111
2111
3331
4333
6554
9886
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
9753
151295
2519148
44332514
59453419
98755631
1401078044
21616512368
28822116491
370284212118
581446332185
839644480267
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 6 10 17 29 39 65 93 143 191 246 387 558
RHH*, RHW*,RHW-2*, THHW,THW
3.5 (2.0)5.5 (2.6)
53
86
1310
2318
3225
5241
7558
11590
154120
198154
311242
448350
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
8.0 (3.2) 1 4 6 11 15 24 35 54 72 92 145 209
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
14223038
1111
3111
5321
8643
11864
1814107
27201410
41312215
55413021
71533827
111836042
1601208761
506080
100
0000
1110
1111
2211
3321
6543
8765
131198
18151310
23191614
36312621
52443731
125150175200250
00000
00000
11000
11111
11111
32111
43332
65543
87665
119876
1715131210
2522191714
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
137
Table A48 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
325375400500
0000
0000
0000
1000
1110
1111
1111
3221
4332
5443
8775
1210108
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
13963
2216106
3626179
63462916
85623922
1401026437
2001469253
30922514282
412301189109
531387244140
833608383221
1202877552318
14 2 4 7 12 16 27 38 59 79 101 159 230223038
111
211
431
754
1075
16118
231712
362619
483425
624433
987051
14110074
506080
100
1000
1111
1111
3211
4332
7654
10876
1613119
21181512
27231916
43363025
63524336
125150175200250
00000
00000
11110
11111
11111
33221
54332
76554
108775
13111087
2017151311
2925222016
325375400500
0000
0000
0000
1000
1111
1111
1111
3331
4443
6554
9776
1311118
FEP, FEPB, PFA,PFAH, TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
129632
22161164
352618107
6144321813
8360432517
13699714129
1941421025841
3002191579064
40029220912085
515376269154110
808590423242172
1166851610350249
2230
11
31
53
96
128
2014
2920
4431
5941
7753
12083
174120
PFA, PFAH, TFE 38 1 1 2 4 6 9 14 21 28 37 57 83
PFA, PFAH, TFE,Z
506080
100
1100
1111
1111
3321
5432
8654
11986
18141210
24191613
30252117
48403327
69574739
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
1510643
26181175
423018118
7352322014
10071432719
164116714531
2341661026445
3612561579969
48234220913293
621440269170120
974691423267188
1405997610386271
223038
111
311
532
965
1386
221310
311915
482923
643931
825040
1297863
18611392
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
97531
1512953
25191486
4433251410
5945341914
9875563123
140107804433
2161651236851
2882211649168
37028421211887
581446332185137
839644480267197
2230
11
21
43
75
107
1612
2417
3726
4935
6345
9970
143101
Power Cables & Wires Technical Manual
138
Table A48 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
XHH, XHHW,XHHW-2
38 1 1 1 4 5 9 12 19 26 33 52 76506080100
1000
1111
1111
3211
4332
7654
10976
1613119
22181512
28231916
44373025
64534436
125150175200250
00000
00000
11110
11111
11111
33221
54332
76654
109775
13111097
2018151411
3025222016
325375400500
0000
0000
0000
1000
1111
1111
1111
3331
4443
6554
9776
1311118
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50FFH-2, RFH-2, RFHH-3 0.75
1.2587
1512
2420
4235
5748
9479
SF-2, SFF-2 0.751.252.0
1197
191512
312520
534435
725948
1189879
SF-1, SFF-1 0.75 19 33 54 94 127 209
RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 14 25 40 69 94 155
RFHH-2, TF, TFF, XF,XFF
1.25 11 20 32 56 76 125
XF, XFF 2.0 9 15 25 44 59 98TFN, TFFN 0.75
1.252317
4030
6449
11184
150115
248189
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
211612
382922
614735
1058161
14311083
235181136
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
282015
483626
795842
13510073
184136100
303223164
KF-2, KFF-2 0.751.252.03.55.5
402819139
7150342315
11480553825
197138956544
2671881298959
43931021314698
KF-1, KFF-1 0.751.252.03.55.5
4834231510
8459402617
13696644228
2351651117348
31822415010065
524368248164107
XF, XFF 3.55.5
53
86
1310
2318
3225
5241
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A49 should be used.
Power Cables & Wires Technical Manual
139
Table A49 Maximum Number of Compact Conductors in RigidMetal Conduit (Based on Table 9.1.1.1)
COMPACT CONDUCTORS
TypeConductorSize (mm2)
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150THW,THW-2, THHW
8.014
21
43
75
129
1612
2620
3829
5945
7860
10178
158122
228176
223038
111
211
431
753
975
15118
221611
342517
453323
584330
916747
1329768
506080100
1000
1111
1111
3211
4332
7654
10876
1513119
20171412
26221915
41342924
59504235
125150175200250
00000
00000
11110
11111
11111
33211
44333
76554
98775
1211987
1917151311
2824222017
325375400500
0000
0000
0000
1000
1111
1111
1111
3331
4443
6554
9776
1311119
THHN, THWN,THWN-2
8.014
2
5
8
13
18
30
43
66
88
114
179
258
223038
111
311
532
864
1186
181310
261914
412922
553929
705038
1107960
15911486
506080100
1100
1111
1111
4321
5433
8765
121087
19151310
25211714
32262218
51423529
73605142
125150175200250
00000
10000
11110
11111
21111
43321
54433
87655
1110876
141211108
2320171513
3328252219
325375400500
0000
0000
0000
1110
1111
1111
2111
4332
5443
6554
10996
1513139
XHHW,XHHW-2
8.014
32
54
96
1511
2115
3425
4936
7656
10175
13097
205152
296220
223038
111
311
532
864
1186
181310
261914
412922
553929
705038
1107960
15911486
506080100
1100
1111
1111
4321
5433
8765
121087
19161311
25211714
32272219
51433529
73625142
125150175200250
00000
10000
11110
11111
21111
43321
55443
87665
1110986
151311108
2320181613
3429252319
325375400500
0000
0000
0000
1110
1111
1111
2111
4332
5443
7554
10887
15121210
Definition: Compact stranding is the result of a manufacturing process where the standard conductorscompressed to the extent that the interstices (voids between strand wires) are virtually eliminated.
Power Cables & Wires Technical Manual
140
Table A50 Maximum Number of Conductors and Fixture Wires inRigid PVC Conduit, Schedule 80 (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
RH 2.0 (1.6)3.5 (2.0)
43
86
1310
2319
3226
5544
7963
12399
166133
215173
341274
490394
RHH, RHW, RHW-2
2.0 (1.6)3.5 (2.0)
32
54
97
1714
2319
3932
5646
8873
11898
153127
243202
349290
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
111
311
632
1164
1586
261311
371916
593124
794133
1035443
1638568
23412298
223038
100
111
111
331
542
864
1296
19149
262013
332517
534127
775838
506080100
0000
0000
1110
1111
1111
3332
5443
8765
111087
1513119
23201715
33292521
125150175200250
00000
00000
00000
11100
11111
11111
22111
43332
55443
76554
1110987
1614131210
325375400500
0000
0000
0000
0000
0000
1111
1111
1111
3221
3332
6554
8775
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
6531
11963
2015116
35272011
49382815
82634726
118916737
18514210659
25019214379
324248185103
514394294163
736565421234
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 4 8 13 23 32 55 79 123 166 215 341 490
RHH*, RHW*,RHW-2*, THHW,THW
3.5 (2.0)5.5 (2.6)
32
65
108
1915
2620
4434
6349
9977
133104
173135
274214
394307
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
8.0 (3.2) 1 3 5 9 12 20 29 46 62 81 128 184
RHH*, RHW*,RHW-2*, TW,THW THHW,THW-2
14223038
1110
1111
3311
7532
9753
161286
2217128
35261913
48352618
62463323
98735337
1411057754
506080100
0000
1100
1111
1111
3211
5433
7654
111087
1513119
20171412
32272319
46393327
125150175200250
00000
00000
00000
11111
11111
21111
33221
55443
76654
98775
151312109
2219171513
325375400500
0000
0000
0000
0000
1000
1111
1111
2111
3332
4443
7665
10887
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
141
Table A50 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
9642
171274
2820137
51372313
70513218
118865431
1701247845
26519312270
35826116495
464338213123
736537338195
1055770485279
14 1 3 5 9 13 22 32 51 68 89 141 202223038
110
111
321
643
864
14107
201410
312216
423022
543929
866145
1248865
506080100
0000
1110
1111
2111
3321
6543
9765
141198
18151310
24201714
38322622
55463831
125150175200250
00000
00000
10000
11111
11111
32111
43332
65543
87665
119876
1815131210
2522191714
325375400500
0000
0000
0000
0000
1110
1111
1111
3221
4332
5443
8775
12997
FEP, FEPB,PFA, PFAH, TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
86421
1612853
27201486
4936261510
6850362014
11584603424
164120864935
2571881357755
34725318210474
45032823513596
714521374214152
1024747536307218
2230
11
21
43
75
107
1712
2417
3826
5235
6746
10673
153105
PFA, PFAH, TFE 38 1 1 1 3 5 8 11 18 25 32 51 73
PFA, PFAH,TFE, Z
506080100
0000
1110
1111
3211
4321
7544
10865
1512108
20171411
27221815
42352924
61504134
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
107432
1914854
33231496
5942261611
8258362216
13898603826
198141865438
3102201358560
41829718211581
542385235149104
860610374236166
1233875536339238
223038
110
211
422
854
1165
18119
261613
412520
553327
724335
1146956
1649980
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
65311
119632
20151164
352720118
4938281511
8263472619
11891673728
1851421065943
2501921437959
32424818510376
514394294163121
736565421234173
2230
11
11
32
64
86
1410
2014
3122
4230
5539
8762
12589
Power Cables & Wires Technical Manual
142
Table A50 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
XHH, XHHW,XHHW-2
38 0 1 1 3 4 7 10 16 22 29 46 66506080100
0000
1110
1111
2111
3321
6543
9765
141198
19161311
24201714
39322722
56463832
125150175200250
00000
00000
11000
11111
11111
32111
43332
65543
97665
1110876
1815141210
2622201714
325375400500
0000
0000
0000
0000
1110
1111
1111
3221
4332
5443
8665
11997
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50FFH-2, RFH-2, RFHH-3 0.75
1.2565
119
1916
3428
4739
7967
SF-2, SFF-2 0.751.252.0
765
14119
242016
433528
594939
1008267
SF-1, SFF-1 0.75 13 25 42 76 105 177
RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 10 18 31 56 77 130
RFHH-2, TF, TFF, XF,XFF
1.25 8 15 25 45 62 105
XF, XFF 2.0 6 11 20 35 49 82
TFN, TFFN 0.751.25
1612
2922
5038
9068
12495
209159
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
15118
282216
473627
856649
1189168
198153115
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
191410
362719
614533
1108159
15211282
255188138
KF-2, KFF-2 0.751.252.03.55.5
28191396
5337251711
8862432920
159112775335
2201551077349
37126117912382
KF-1, KFF-1 0.751.252.03.55.5
332316107
6344291913
10674503321
190133905939
2631851248254
44231020913890
XF, XFF 3.55.5
32
65
108
1915
2620
4434
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A51 should be used.
Power Cables & Wires Technical Manual
143
Table A51 Maximum Number of Compact Conductors in Rigid PVC Conduit,Schedule 80 (Based on Table 9.1.1.1)
COMPACT CONDUCTORS
TypeConductorSize (mm2)
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150THW, THW-2,THHW
8.014223038
11110
32111
54311
97543
1310754
22171396
322518139
5039292115
6852392920
8868513726
140108816042
2001551168560
506080
100
0000
1100
1111
2111
3321
6543
8765
131198
17151210
23191613
36302622
52443731
125150175200250
00000
00000
10000
11111
11111
22111
43332
65543
87665
119876
1715131210
2521191714
325375400500
0000
0000
0000
0000
1110
1111
1111
3221
4332
5443
8775
1210108
THHN, THWN,THWN-2
8.014223038
1111
3111
6321
11653
15965
2515118
36221612
57352519
77473425
99614433
158987053
22614010075
506080
100
0000
1110
1111
3211
4332
7654
10876
1613119
22181512
28231916
45373125
64534437
125150175200250
00000
00000
11000
11111
11111
33211
44332
76554
108765
1211987
2017151311
2925221916
325375400500
0000
0000
0000
1000
1110
1111
1111
3331
4443
6553
9885
1311118
XHHW, XHHW-2 8.014223038
11111
43111
75321
129653
1713965
292115118
4231221612
6548352519
8865473425
11485614433
181134987053
26019314010075
506080
100
0000
1110
1111
3211
4332
7654
10876
1613119
22181512
28241916
45383126
64544437
125150175200250
00000
00000
11100
11111
11111
33211
54332
76554
108775
13111097
2117151411
3025222017
325375400500
0000
0000
0000
1000
1110
1111
1111
3221
4333
6553
9776
1311118
Definition: Compact stranding is the result of a manufacturing process where thestandard conductors compressed to the extent that the interstices (voids between strandwires) are virtually eliminated.
Power Cables & Wires Technical Manual
144
Table A52 Maximum Number of Conductors and Fixture Wires in RigidPVC Conduit, Schedule 40 and HDPE Conduit (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
RH 2.0 (1.6)3.5 (2.0)
54
98
1612
2822
3830
6350
9072
139112
186150
240193
378304
546439
RHH, RHW, RHW-2
2.0 (1.6)3.5 (2.0)
43
75
119
2016
2722
4537
6453
9982
133110
171142
269224
390323
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
211
421
743
1375
1897
301512
432218
663528
894637
1156048
1819476
261137109
223038
110
111
211
431
643
1075
14107
221611
292214
372819
594529
856543
506080100
0000
1000
1111
1111
2111
4332
6544
9876
131198
16141210
26221916
37322824
125150175200250
00000
00000
00000
11110
11111
11111
32211
44333
65544
87665
12111098
1816141311
325375400500
0000
0000
0000
0000
1000
1111
1111
2111
3221
4333
6554
9886
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
8642
141184
2418137
42322413
57443218
94725430
1351037743
20916011966
28021516089
361277206115
568436325181
822631470261
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 5 9 16 28 38 63 90 139 186 240 378 546
RHH*, RHW*,RHW-2*, THHW,THW
3.5 (2.0)5.5 (2.6)
43
86
1210
2217
3024
5039
7256
11287
150117
193150
304237
439343
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
8.0 (3.2) 1 3 6 10 14 23 33 52 70 90 142 205
RHH*, RHW*,RHW-2*, TW,THW, THHN,THW-2
14223038
1110
2111
4321
8643
11864
1813107
26191410
40302215
53402920
69513726
109815941
1571178560
506080100
0000
1110
1111
2111
3321
6543
8765
131198
17151210
22191613
35302521
51433630
125150175200250
00000
00000
11000
11111
11111
32111
43332
65543
87665
119876
1715131210
2521191714
325375400500
0000
0000
0000
0000
1110
1111
1111
3221
4332
5443
8665
1110107
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
145
Table A52 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
11853
211595
3425159
60432716
82593721
135996236
1931418951
29921813779
401293184106
517377238137
815594374216
1178859541312
14 1 4 6 11 15 26 37 57 77 99 156 225223038
111
211
431
753
975
16118
221612
352518
473325
614332
966850
1389873
506080
100
1000
1111
1111
3211
4332
7654
10876
1513119
21171412
37221815
42352924
61514235
125150175200250
00000
00000
11100
11111
11111
33211
44332
76554
108765
1211987
2017151311
2824211916
325375400500
0000
0000
0000
1000
1110
1111
1111
3221
4333
5443
9776
1311118
FEP, FEPB, PFA,PFAH, TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
11863
2015106
33241710
58423017
79584124
131966939
1881379856
29021215287
389284204117
502366263150
790577414237
1142834598343
142230
211
431
753
1286
17128
281913
402819
624330
835840
1077551
16911881
244170117
PFA, PFAH, TFE 38 1 1 2 4 5 9 13 20 28 36 56 81
PFA, PFAH, TFE,Z
506080
100
1000
1111
1111
3321
4432
8654
11976
1714129
23191613
30242016
47393226
68564638
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
139632
24171064
402817117
7049301913
9568412618
158112694330
226160986243
3502481529667
46933320412990
605429263166116
952675414261184
1376976598378265
223038
111
311
532
954
1276
211210
301814
462823
623830
804939
1267762
18311190
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
86421
1411843
24181375
4232241310
5744321813
9472543022
135103774332
2091601196649
2802151608966
36127720611585
568436325181134
822631470261193
2230
11
21
43
75
97
1611
2316
3525
4834
6144
9769
14099
Power Cables & Wires Technical Manual
146
Table A52 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100 125 150
XHH, XHHW,XHHW-2
38 1 1 1 3 5 8 12 19 25 32 51 74506080
100
1000
1111
1111
3211
4332
7654
10876
1613119
21171412
27231915
43363024
62524335
125150175200250
00000
00000
11100
11111
11111
33211
54332
76554
108765
1311987
2017151311
2925221916
325375400500
0000
0000
0000
1000
1110
1111
1111
3221
4333
5443
9776
1311118
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50FFH-2, RFH-2, RFHH-3 0.75
1.2586
1412
2319
4033
5446
9076
SF-2, SFF-2 0.751.252.0
1086
171412
292419
504233
695746
1149476
SF-1, SFF-1 0.75 17 31 51 89 122 202RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 13 23 38 66 90 149
RFHH-2, TF, TFF, XF,XFF
1.25 10 18 30 53 73 120
XF, XFF 2.0 8 14 24 42 57 94
TFN, TFFN 0.751.25
2016
3728
6046
10580
144110
239183
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
191511
352720
574433
1007758
13710679
227175131
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
251813
453324
745440
1299570
17613095
292216158
KF-2, KFF-2 0.751.252.03.55.5
362617128
6546312214
10775523524
187132906242
2561801248557
42429920514194
KF-1, KFF-1 0.751.252.03.55.5
433020139
7855372416
12890604026
2231571057045
3052141449562
506355239158103
XF, XFF 3.55.5
43
86
1210
2217
3024
5039
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A53 should be used.
Power Cables & Wires Technical Manual
147
Table A53 Maximum Number of Compact Conductors in Rigid PVC Conduit,Schedule 40 and HDPE Conduit (Based on Table 9.1.1.1)
COMPACT CONDUCTORS
TypeConductorSize (mm2)
Raceway Size (mm)15 20 25 32 40 50 65 80 90 100 125 150
THW, THW-2,THHW
8.014223038
11111
43111
65321
119653
1512964
262015117
3728211511
5744332417
7659443223
9876574229
155119896646
2241731299567
506080100
0000
1111
1111
3211
4332
6554
9875
1512109
20161412
25211815
40342924
58494235
125150175200250
00000
00000
11100
11111
11111
32211
44332
76554
98765
1210987
1916151311
2724211916
325375400500
0000
0000
0000
1000
1111
1111
1111
3221
4333
5554
9776
1311119
THHN, THWN,THWN-2
8.014223038
2111
4211
7432
13854
171186
2918139
41251814
64402821
86533829
111684937
1751087758
25315611284
506080100
1000
1111
1111
3321
5433
8754
12986
18151210
24201714
31262218
49413428
72595041
125150175200250
00000
00000
11110
11111
11111
33321
54433
87654
119876
14121098
2219171513
3228242218
325375400500
0000
0000
0000
1110
1111
1111
2111
4332
5443
6554
10886
1512129
XHHW,XHHW-2
8.014223038
31111
54211
86432
1411854
20151186
332518139
4735251814
7355402821
9973533829
12794684937
2001491087758
29021515611284
506080100
1100
1111
1111
3321
5433
8755
121087
18151210
24201714
31262218
49423429
72605042
125150175200250
00000
00000
11110
11111
11111
43321
54433
87654
119876
141211108
2319171513
3328252218
325375400500
0000
0000
0000
1110
1111
1111
2111
4332
5443
6554
10886
1512129
Definition: Compact stranding is the result of a manufacturing process where thestandard conductors compressed to the extent that the interstices (voids between strandwires) are virtually eliminated.
Power Cables & Wires Technical Manual
148
Table A54 Maximum Number of Conductors and Fixture Wires inType A, Rigid PVC Conduit (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RH 2.0 (1.6)3.5 (2.0)
76
1210
2016
3427
4435
7056
10484
157126
204164
262211
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
54
97
1512
2420
3126
4941
7461
11293
146121
187155
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
311
632
1054
1686
21119
331714
502621
753931
985141
1256552
223038
110
111
321
542
753
1185
16128
241812
322416
413120
506080
100
0000
1110
1111
2111
3211
5433
7654
10987
1412109
18151311
125150175200250
00000
00000
11000
11111
11111
11111
33221
54443
76554
87765
325375400500
0000
0000
0000
0000
1110
1111
1111
2111
3332
4443
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0(3.2)
11863
1814106
31241810
51392916
67513821
105806033
1571208950
23518113575
30723617698
395303226125
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 7 12 20 34 44 70 104 157 204 262
RHH*, RHW*,RHW-2*, THHW,THW
3.5 (2.0)5.5 (2.6)
64
108
1613
2721
3528
5644
8465
12698
164128
211165
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
8.0 (3.2) 2 4 8 12 16 26 39 59 77 98
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
14223038
1111
3211
6431
9753
13975
2015117
30221611
45332417
59443222
75564129
506080
100
1000
1111
1111
3211
4332
6544
10876
1412109
19161311
24211714
125150175200250
00000
00000
11110
11111
11111
32211
44332
76554
98765
1210987
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
149
Table A54 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
325375400500
0000
0000
0000
1110
1111
1111
1111
3331
4333
5443
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)
16117
271912
443220
735333
967044
15010969
225164103
338246155
441321202
566412260
8.0 (3.2)14223038
43111
75311
128532
1914864
25181186
402817129
5943261914
8964392821
11784523727
150108664735
506080
100
1100
1111
2111
4321
5433
8654
111086
17141210
23191613
29242017
125150175200250
00000
10000
11111
11111
21111
33221
54433
87654
109876
14121097
325375400500
0000
0000
0000
1110
1111
1111
2111
3332
5443
6554
FEP, FEPB,PFA, PFAH, TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
14
1511843
26191385
433122139
7051372115
9368482820
146106764431
2181591146546
3272391719870
42731222412891
549400287165117
2230
11
42
64
107
149
2115
3222
4933
6444
8256
PFA, PFAH, TFE 38 1 1 3 5 6 10 15 23 30 39
PFA, PFAH,TFE, Z
506080
100
1110
1111
2111
4332
5433
8765
131097
19161311
25211714
32272218
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
181385
3122138
52372214
85603723
112794830
1751247648
26318611472
395280171108
515365224141
661469287181
14223038
3211
6421
10743
161175
211597
34231411
50352117
76523226
99684133
127885343
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
11863
1814106
31241810
51392916
67513821
105806033
1571208950
23518113575
30723617698
395303226125
142230
211
431
753
1286
15118
241812
372619
554028
755237
936748
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
150
Table A54 Continued
CONDUCTORS
TypeConductorSize [mm2
(mm dia.)]
Raceway Size (mm)
15 20 25 32 40 50 65 80 90 100
XHH, XHHW,XHHW-2
38 1 1 3 4 6 9 14 21 28 35506080
100
1100
1111
2111
4321
5433
8654
121087
18151210
23191613
30252017
125150175200250
00000
10000
11111
11111
21111
33321
55433
87654
119876
14121098
325375400500
0000
0000
0000
1110
1111
1111
2111
3332
5443
6554
FIXTURE WIRES
TypeConductor Size
(mm2)Raceway Size (mm)
15 20 25 32 40 50FFH-2, RFH-2, RFHH-3 0.75
1.25109
1815
3025
4841
6454
10085
SF-2, SFF-2 0.751.252.0
13119
221815
373125
615141
816754
12710585
SF-1, SFF-1 0.75 23 40 66 108 143 224RFH-1, RFHH-2, TF,TFF, XF, XFF
0.75 17 29 49 80 105 165
RFHH-2, TF, TFF, XF,XFF
1.25 14 24 39 65 85 134
XF, XFF 2.0 11 18 31 51 67 105
TFN, TFFN 0.751.25
2821
4736
7960
12898
169129
265202
PF, PFF, PGF, PGFF,PAF, PTF, PTFF, PAFF
0.751.252.0
262015
453526
745843
1229470
16012493
251194146
HF, HFF, ZF, ZFF, ZHF 0.751.252.0
342518
584231
967152
15711685
206152112
324239175
KF-2, KFF-2 0.751.252.03.55.5
4935241611
8459402818
14098674631
2281601107651
30021114510067
470331228157105
KF-1, KFF-1 0.751.252.03.55.5
5941281812
10070473120
167117795234
2721911288555
35725116911273
561394265175115
XF, XFF 3.55.5
64
108
1613
2721
3528
5644
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A55 should be used.
Power Cables & Wires Technical Manual
151
Table A55 Maximum Number of Compact Conductors in Type A, RigidPVC Conduit (Based on Table 9.1.1.1, Chapter 9)
COMPACT CONDUCTORS
TypeConductorSize (mm2)
Raceway Size (mm)15 20 25 32 40 50 65 80 90 100
THW, THW-2,THHW
8.014223038
32111
54311
86532
1410864
18141075
282216128
4233241813
6449372719
8465483625
10783624632
506080100
1100
1111
1111
3321
4433
7654
11986
16141210
21181513
28232017
125150175200250
00000
10000
11111
11111
11111
33221
54433
87654
109876
13111098
325375400500
0000
0000
0000
1110
1111
1111
2111
3332
5443
6554
THHN, THWN,THWN-2
8.014223038
3111
5321
9643
15975
201297
32201410
48302116
72453224
94584231
121755440
506080100
1110
1111
2111
4332
6543
9765
131198
20171411
27221815
34282419
125150175200250
00000
11000
11111
11111
21111
43322
65443
98765
1210987
151311109
325375400500
0000
0000
0000
1110
1111
1111
3221
4332
5443
7664
XHHW,XHHW-2
8.014223038
43111
65321
118643
1813975
23171297
3727201410
5541302116
8362453224
10880584231
139103755440
506080100
1110
1111
2111
4332
6543
9765
131198
20171412
27221815
34292420
125150175200250
00000
11000
11111
11111
21111
43332
65543
98765
1210987
161312119
325375400500
0000
0000
0000
1110
1111
1111
3221
4332
5443
7664
Definition: Compact stranding is the result of a manufacturing process where thestandard conductors compressed to the extent that the interstices (voids between strandwires) are virtually eliminated.
Power Cables & Wires Technical Manual
152
Table A56 Maximum Number of Conductors in Type EB, PVC Conduit (Based onTable 9.1.1.1)
CONDUCTORS
TypeConductor Size
[mm2 (mm dia.)]Raceway Size (mm)
50 80 90 100 125 150RH 2.0 (1.6)
3.5 (2.0)7459
166134
217175
276222
424341
603485
RHH, RHW,RHW-2
2.0 (1.6)3.5 (2.0)
5344
11998
155128
197163
303251
430357
RH, RHH, RHW,RHW-2
5.5 (2.6)8.0 (3.2)
14
351815
794133
1045443
1326955
20310685
288151121
223038
1196
262013
342617
433321
665033
947247
506080
100
5443
111087
1513119
19161412
29252218
41363126
125150175200250
21111
55443
76554
98765
141211109
2017161412
325375400500
1111
3211
3322
4433
7655
10977
TW 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
111856335
25019214379
327251187104
415319238132
638490365203
907696519288
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
2.0 (1.6) 74 166 217 276 424 603
RHH*, RHW*,RHW-2*,THHW, THW
3.5 (2.0)5.5 (2.6)
5946
134104
175136
222173
341266
485378
RHH*, RHW*,RHW-2*, THW,THHW, THW-2
8.0 (3.2) 28 62 81 104 159 227
RHH*, RHW*,RHW-2*, TW,THW, THHW,THW-2
14223038
2116118
48362618
62463424
79594330
122916646
1731299466
506080
100
7654
1513119
20171412
26221815
40342824
56484034
125150175200250
33221
76654
108775
1211987
1917151311
2724211916
325375400500
1111
3322
4433
6544
9766
131188
*Type RHH, RHW, and RHW-2 without outer covering.
Power Cables & Wires Technical Manual
153
Table A56 Continued
CONDUCTORS
TypeConductor Size[mm2 (mm dia.)]
Raceway Size (mm)50 80 90 100 125 150
THHN, THWN,THWN-2
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
1591167342
35926216595
468342215124
595434274158
915667420242
1300948597344
14223038
30191310
68423022
89553929
114705037
1751077657
24815310980
506080
100
8754
18151310
24201714
31262118
48403327
68564739
125150175200250
43321
87665
1110876
141211108
2219171512
3127242118
325375400500
1111
4322
5433
6544
10866
141299
FEP, FEPB,PFA, PFAH, TFE
2.0 (1.6)3.5 (2.0)5.5 (2.6)
15511381
348254182
454332238
578422302
888648465
1261920660
8.0 (3.2)142230
46332316
104745236
136976846
1731238659
26618913291
378269188129
PFA, PFAH, TFE 38 11 25 32 41 63 90
PFA, PFAH,TFE, Z
506080
100
9765
20171411
27221815
34282319
53433629
75625142
Z 2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
1861328151
419297182115
547388238150
696494302191
1069759465294
15191078660417
14223038
36241512
81553427
105724436
134925645
2061428670
29320112299
XHH, XHHW,XHHW-2, ZW
2.0 (1.6)3.5 (2.0)5.5 (2.6)8.0 (3.2)
111856335
25019214379
327251187104
415319238132
638490365203
907696519288
142230
261913
594230
775639
987150
15010977
213155110
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A57 should be used.
Power Cables & Wires Technical Manual
154
Table A56 Continued
CONDUCTORS
TypeConductor Size[mm2 (mm dia.)]
Raceway Size (mm)50 80 90 100 125 150
XHH, XHHW,XHHW-2
38 10 22 29 37 58 82506080
100
8765
19161311
25201714
31262218
48403327
69574739
125150175200250
43321
97665
1110986
151211108
2219171512
3228242218
325375400500
1111
4322
5433
6544
10866
141299
Note: This table is for concentric stranded conductors only. For compact strandedconductors, Table A57 should be used.
Power Cables & Wires Technical Manual
155
Table A57 Maximum Number of Compact Conductors in Type EB,PVC Conduit (Based on Table 9.1.1.1)
CONDUCTORS
TypeConductor Size
(mm2)Raceway Size (mm)
50 80 90 100 125 150THW, THW-2, THHW
8.014223038
302317139
6852392920
8969513826
11387654834
1741341007452
24719114310574
506080100
8654
17151210
23191614
29242117
45383227
64544638
125150175200250
33321
87665
119876
141211108
2119171512
3026242118
325375400500
1111
4322
5433
6544
10877
141299
THHN, THWN,THWN-2
8.014223038
34211511
77473425
100624433
128795742
1961218765
27917212493
506080100
9865
22181512
28232016
36302520
56463832
79655545
125150175200250
44332
108765
1311987
161412119
2522191714
3531272420
325375400500
1111
4433
6533
7644
11977
16141010
XHHW,XHHW-2
8.014223038
3929211511
8865473425
11585624433
146109795742
2251671218765
32023817212493
506080100
9865
22181512
28242016
36302521
56473832
79675546
125150175200250
44332
108775
13111097
171412119
2622191714
3731282520
325375400500
1111
4333
6544
7655
11977
16131010
Definition: Compact stranding is the result of a manufacturing process where thestandard conductors compressed to the extent that the interstices (voids between strandwires) are virtually eliminated.
Power Cables & Wires Technical Manual
156
Power Cables & Wires Technical Manual
157
ANNEX B
Conductor Application and Insulation
Power Cables & Wires Technical Manual
158
Table B1. Conductor Application and InsulationsTrade Name Type
LetterMaximumOperating
Temperature
ApplicationProvisions
InsulationOuter
CoveringaMaterial Conductor
Area (mm2)Thickness
(mm)
Fluorinatedethylenepropylene
FEPor
FEPB
90°C
200°C
Dry and damp locations
Dry locations — specialapplicationsb
Flourinatedethylene
Propylene
2.0 – 5.5
8.0 – 30
0.50
0.80
None
Flourinatedethylene
Propylene
2.0 – 8.0 0.40 Glass braid
14 – 30 0.40 Other suitablebraid material
Mineral insulation(metalsheathed)
MI 90°C
250°C
Dry and wet locations
For special applicationsb
Magnesium oxide 0.75 – 1.25c
1.25 – 5.55.6 – 2223 – 250
0.580.901.301.40
Copper oralloy steel
Moisture-, heat-,andoil-resistantthermoplastic
MTW 60°C
90°C
Machine tool wiring in wetlocations as permitted inNFPA 79 see Article 6.70)
Machine tool wiring in drylocations as permitted inNFPA 79 (see Article 6.70)
Flame-retardantmoisture-, heat-,andoil-resistantthermoplastic
0.65 – 3.55.58.014
22 – 3038 – 100101 – 250251 – 500
(a)0.800.801.201.601.602.002.402.80
(b)0.400.500.800.801.001.301.601.80
(a) None
(b) Nylon jacketor equivalent
Paper 85°C For underground serviceconductors, or by specialpermission
Paper Lead sheath
Perfluoro-alkoxy
PFA 90°C
200°C
Dry and damp locations
Dry locations — specialapplicationsb
Perfluoro-alkoxy 2.0 – 5.58.0 – 3038 – 100
0.500.801.20
None
159
Pow
erC
ables&
Wires
Tech
nicalM
anual
Perfluoro-alkoxy
PFAH 250°C Dry locations only.Only for leadsWithin apparatusor within raceways
connected to apparatus(nickel or nickel-coated
copper only)
Perfluoroalkoxy 2.0 – 5.58.0 – 3038 –100
0.500.801.20
None
Thermoset
Thermoset
RH
RHH
75°C
90°C
Dry and damp locations
Dry and damp locations
Flame-retardantthermoset
2.0 – 3.5d
5.58.0 – 3038 –100
101 – 250251 – 500
501 – 1 000For 601 – 2000
Volts, seeTable
3.10.1.62
0.801.201.602.002.402.803.20
Moistureresistant,
flame-retardant,nonmetalliccovering1
Moisture-resistantthermoset
RHWe 75°C Dry and wet locationsWhere over 2 000 voltsInsulation, shall beOzone resistant
Flame-retardant,moisture-resistantthermoset
2.0 – 5.5dd
8.0 – 3038 –100
101 – 250251 – 500501 – 1 000
For 601 – 2000Volts, see
Table3.10.1.62
1.201.602.002.402.803.20
Moistureresistant,
flame-retardant,nonmetalliccovering5
aSome insulations do not require an outer covering.bWhere Design conditions require maximum conductor operating temperature above 90 oCcFor signaling circuits permitting 300-volts insulation.dFor size 2.0 – 3.5 mm2, RHH insulation shall be 1.20 mm thickness.eListed wire type designated with the suffix “-2”, such as RHW-2, shall be permitted to be used at continuous 90 oC operating temperature, wet or dry.fSome rubber insulations do not require an outer covering.
160
Pow
erC
ables&
Wires
Tech
nicalM
anual
Table B1. (Continued)
Trade NameTypeLetter
MaximumOperating
Temperature
ApplicationProvisions
InsulationOuter
CoveringaMaterials ConductorArea (mm2)
Thickness(mm)
Moisture-resistantthermoset
RHW-2 90°C Dry and wet locations Flame-retardant,moisture-resistantthermoset
2.0 – 5.58.0 – 3038 – 100101 – 250251 – 500
501 – 1 000For 601 – 2 000
Volts, seeTable
3.10.1.62
1.201.602.002.402.803.20
Moisture-resistant,flame-retardant,nonmetalliccoveringf
Silicon SA 90°C
200°C
Dry and wet locations
For special applicationb Silicon rubber
2.0 – 5.58.0 – 3038 – 100101 – 250251 – 500
501 – 1 000
1.201.602.002.402.803.20
Glass or othersuitable braidmaterial
Thermoset SIS 90°C Switchboardwiring only
Flame-retardantthermoset
2.0 – 5.58.0 – 3038 – 100
0.801.202.40
None
Thermoplasticand fibrousouter braid
TBS 90°C SwitchboardWiring only
Thermoplastic 2.0 – 5.58.0
14 – 3038 – 100
0.801.201.602.00
Flame-retardant,nonmetalliccovering
Extendedpolytetrafluoro-ethylene
TFE 250°C Dry locations only. Only forleads within apparatus orwithin raceways connectedto apparatus,or as openwiring (Nickel or nickel-coated copper only)
ExtrudedPolytetrafluoro-ethylene
2.0 – 5.58.0 – 3038 – 100
0.500.801.20
None
161
Pow
erC
ables&
Wires
Tech
nicalM
anual
Heat-resistantthermoplastic
THHN 90°C Dry and damp location Flame- retardant,heat-resistantthermoplastic
2.0 – 3.55.5
8.0 – 1422 – 30
38 – 100125 – 250251 – 500
0.400.500.801.001.301.601.80
Nylon jacketor equivalent
Moisture-andheat-resistantthermoplastic
THHW 75°C
90°C
Wet location
Dry location
Flame-retardant,moisture- and heat-resistantthermoplastic
2.0 – 5.58.0
14 – 3038 – 100101 – 250251 – 500
0.801.201.602.002.402.80
None
Moisture-andheat-resistantthermoplastic
THWc 75°C
90°C
Dry and wet locations
Special applications withinelectric discharge lightingequip. Limited to 1 000open –circuit volts or less(size 2.0 – 8.0 mm2 only aspermitted in Section4.10.6.10)
Flame-retardant,moisture- and heat-resistantthermoplastic
2.0 – 5.58.0
14 – 3038 – 100101 –250251 – 500
501 – 1 000
0.801.201.602.002.402.803.20
None
Moisture-andheat-resistantthermoplastic
THWNe 75°C Dry and wet locations Flame-retardant,moisture- and heat-resistantthermoplastic
2.0 – 3.55.5
8.0 – 1422 – 30
38 – 100125 – 250251 – 500
0.400.500.801.001.301.601.80
Nylon jacketor equivalent
aSome insulations do not require an outer coveringbWhere design conditions require maximum conductor operating temperature above 90°CeListed wire type designated with the suffix “-2”, such as RHW-2, shall be permitted to be used at a continuous 90°C operating temperature, wet or dry.fSome rubber insulations do not require an outer covering.
162
Pow
erC
ables&
Wires
Tech
nicalM
anual
Table B1. (Continued)
Trade NameTypeLetter
MaximumOperating
TemperatureApplicationProvisions
InsulationOuter
CoveringaMaterials ConductorArea (mm2)
Thickness(mm)
Moisture-resistant
thermoplastic
TW 60 C Dry and wet locations Flame-retardant,Moisture-resistantThermoplastic
2.0 – 5.58.0
14 – 3038 – 100
101 – 250251 – 500
501 – 1 000
0.801.201.602.002.402.803.20
None
Undergroundfeeder andbranch-circuitcable —singleconductor
(For Type UFcable employingmore than oneconductor, seeArticle 3.39.)
UF 60°C See Article 3.39 Moisture-resistant 2.0 – 5.58.0 – 3038 – 100
1.60g
2.00g
2.40g
Integral withinsulation
75°C Moisture- andheat- resistant
Undergroundservice-entranceCable — singleconductor(For Type USEcable employingmore than oneconductor, seeArticle 3.38.)
USEe 75°C See Article 3.38. Heat- and moisture-resistant
2.0 – 5.58.0 – 3038 – 100
101 – 250251 – 500
501 – 1 000
1.201.602.002.402.803.20
Moisture-resistantnonmetalliccovering
[(See3.38.1.1(b)]
163
Pow
erC
ables&
Wires
Tech
nicalM
anual
Thermoset XHH 90°C Dry and damp locations Flame-retardantthermoset
2.0 – 5.58.0 – 3038 – 100
101 – 250251 – 500
501 – 1 000
0.801.201.401.702.002.40
None
Moisture-resistantthermoset
XHHWe 90°C Dry and damp locations
Wet locations
Flame-retardantmoisture-resistantthermoset
2.0 – 5.58.0 – 3038 – 100
101 – 250251 – 500
501 – 1 000
0.801.201.401.702.002.40
None
Moisture-resistantthermoset
XHHW-2 90°C Dry and damp locations Flame-retardantmoisture-resistantthermoset
2.0 – 5.58.0 – 3038 – 100
101 – 250251 – 500
501 – 1 000
0.801.201.401.702.002.40
None
Modifiedethylenetetrafluoro-ethylene
Z 90°C
150°C
Dry and damp locations
Dry locations — specialapplicationsb
Modified ethylenetetrafluoro-ethylene
2.0 – 3.55.5
8.0 – 2230 –38
50 – 100
0.400.500.640.891.20
None
Modifiedethylenetetrafluoro-ethylene
ZWe 75°C
90°C
150°C
Wet locations
Dry and damp locations
Dry locations — specialapplicationsb
Modified ethylenetetrafluoro-ethylene
2.0 – 5.5 8.0 – 30 None
aSome insulations do not require an outer covering.bWhere design conditions require maximum conductor operating temperatures above 90°C.eListed wire types designated with the suffix “2,” such as RHW-2, shall be permitted to be used at a continuous 90°C operating temperature, wet or dry.gIncludes integral jacket.iInsulation thickness shall be permitted to be 2.80 mm for listed Type USE conductors that have been subjected to special investigations. The nonmetallic covering over individual rubber-covered conductors ofaluminum-sheathed cable and of lead-sheathed or multiconductor cable shall not be required to be flame retardant. For Type MC cable, see 3.30.3.1. For nonmetallic-sheathed cable, see Part 3.34.3. For TypeUF cable, see Part 3.40.3.
164
Pow
erC
ables&
Wires
Tech
nicalM
anual
Power Cables & Wires Technical Manual
165
ANNEX C
Philippine National Standard for Electrical Products
1. PNS 35-1:2004 - Electric wires and cables – Thermoplasticinsulated electric copper wires and cablesrated 600 volts – Part 1: Generalspecifications
2. PNS 35-2:2006 - Electric wires and cables – Thermoplasticinsulated electric copper wires and cablesrated 600 volts – Part 1: Non-metallic flatjacketed electric wires – Specifications
3. PNS 40:1984 - Electric wires and cables – Copperredraw rod for electrical purposes –Specification
4. PNS 43:1984 - Electric wires and cables – ECAmendments 01: aluminum redraw rod for electrical1985 purposes – Specification
5. PNS 106:1987 - Enameled copper wires – Test method6. PNS 107:1987 - Polyurethane enameled copper wires,
class 105 – Specifications7. PNS 108:1987 - Polyester enameled copper wires, class
105 – Specification8. PNS 109:1987 - Polyvinyl formal enameled copper wires,
class 105 – Specification9. PNS 110:1987 - Polyester amide-imide enameled copper
wires, class 180 - Specification10. PNS 111:1987 - Oleo-resinous enameled copper wires –
Specification11. CDPNS 163:XXXX - Electrical products – Polyvinyl chloride
insulated flexible cords and fixture wires– Specification
12. PNS 260:2004 - Electric wires and cables – Annealedcopper wires – Specification
13. CDPNS 261:XXXX - Electric wires and cables – PVCinsulated low voltages cable for roadvehicles – Specification
Power Cables & Wires Technical Manual
166
14. CDPNS 661:XXXX - Organic chemicals – PlasticizedPolyvinyl chloride compounds forelectrical insulation – Specification
15. PNS 662:1992 - Electrical wires and cables – Ampacitiesof insulated electric 8u77 conductors,0-35,000 volts
16. PNS 1086:1992 - Electrical wires and cables – Hard-drawn solid copper wires for electricalpurposes – Specification
17. PNS 1087:1992 - Electrical wires and cables – Hard-drawncopper stranded – Specification
18. PNS 1088:2006 - Electric wires and cables Copper andaluminum conductors for electricalpurposes – Test methods
19. PNS 1129:1993 - Hard-drawn aluminum wires for electricpurposes – Specifications
20. PNS 1130:1993 - Hard-drawn aluminum strandedconductors – Specification
21. PNS 1207:2006 - Electric wires and cables – Soft-drawn(annealed) copper stranded conductorsfor electrical purposes – Specification
22. PNS 1289:1995 - Electric wires and cables – PVCinsulated battery cables – Specification
23. PNS 1487-1-1:1997 - Common test methods for insulating andsheathing materials of electric cables –Part 1: Methods for general application –Section 1: Measurement of thickness andoverall dimensions – Test fordetermining mechanical properties
24. PNS 1487-1-2:1997 - Common test methods for insulating andsheathing materials of electric cables –Part 1: Methods for general application –Section 2: Thermal ageing methods
25. PNS 1487-1-3:1997 - Common test methods for insulating andsheathing materials of electric cables –Part 1: Methods for general application –Section 3: Methods of determining thedensity – Water absorption tests –Shrinkage
Power Cables & Wires Technical Manual
167
26. PNS 1487-1-4:1997 - Common test methods for insulating andsheathing materials of electric cables –Part 1: Methods for general application –Section 4: Test at low temperature
27. PNS 1487-2-1:1997 - Common test methods for insulating andAmendments 01 & sheathing materials of electric cables –02:1997 Part 2: Methods specific to elastomeric
compounds – Section 1: Ozone resistancetest–hot set test–Mineral oil immersiontest
28. PNS 1487-3-1:1997 - Common test methods for insulating andsheathing materials of electric cables –Part 3: Methods specific to PVCcompounds – Section 1: Pressure test athigh temperature – Test for resistance tocracking
29. PNS 1487-3-2:1997 - Common test methods for insulating andsheathing materials of electric cables –Part 3: Methods specific to PVCcompounds – Section 2: loss of mass test– Thermal stability test
30. PNS 1487-4-1:1997 - Common test methods for insulating andsheathing materials of electric cables –Part 4: Methods specific to polyethyleneand polypropelene compounds – Section1: Resistance to environmental stresscracking – Wrapping test after thermalageing in air – Measurement of the meltflow index – carbon black and/or mineralcontent measurement in PE
31. PNS 1487-4-2:1997 - Common test methods for insulating andsheathing materials of electric cables –Part 4: Methods specific to polyethyleneand polypropelene compounds – Section2: Elongation at break after pre-conditioning – Wrapping test afterthermal ageing in air – Measurement ofmass increase – Long term stability test –(Appendix A) – Test method for copper-
Power Cables & Wires Technical Manual
168
catalysed oxidative degradation(Appendix B)
32. PNS 2048:2006 - Electric wires and cables –Thermoplastic-insulated undergroundfeeder - Specification
33. PNS ASTM B230: - Standard Specification for Aluminum2005 1350-H19 Wire for Electrical Purposes
(ASTM published 2004)34. PNS ASTM B231: - Standard Specification Concentric-Lay-
2005 Stranded Aluminum 1350 Conductors(ASTM published 2004)
35. PNS ASTM B233: - Standard Specification for Aluminum2005 1350 Drawing Stock for Electrical
Purposes (ASTM published 2003)36. PNS ASTM B400: - Standard Specification for Compact
2005 Round Concentric-Lay-StrandedAluminum 1350 Conductors(ASTM published 2004)
37. PNS ASTM B609: - Standard Specification for Aluminum2005 1350 Round Wire, Annealed and
Intermediate Tempers, for ElectricalPurposes (ASTM published 2004)
38. PNS ASTM B786: - Standard Specification for 19 Wire2005 Combination Unilay-Stranded
Aluminum Conductors for SubsequentInsulation (ASTM published 2004)
39. PNS ASTM B800: - Standard Specification for 8000 Series2005 Aluminum Alloy Wire for Electrical
Purposes-Annealed and IntermediateTempers (ASTM published 2000)
40. PNS ASTM B801: - Standard Specification Concentric-Lay-2005 Stranded Conductors of 8000 Series
Aluminum Alloy for SubsequentCovering or Insulation (ASTMpublished 1999)
41. PNS ASTM B172: - Standard Specification for Rope-Lay-2005 Stranded Copper Conductors Having
Bunch-Stranded Members, for ElectricalConductors (ASTM published 2001)
Power Cables & Wires Technical Manual
169
42. PNS ASTM B173: - Standard Specification for Rope-Lay-2005 Stranded Copper Conductors Having
Concentric-Stranded members, forElectrical Conductors (ASTM published2001)
43. PNS ASTM B174: - Standard Specification for Bunch-2005 Stranded Copper Conductors for
Electrical Conductors(ASTM published 2002)
44. PNS ASTM D1047:- Standard Specification for Poly(Vinyl2005 Chloride Jacket for Wire and Cable
(ASTM published 2001)45. PNS ASTM D1351:- Standard Specification for
2005 Thermoplastic Polyethylene Insulationfor Electrical Wire and Cable(ASTM published 2002)
46. PNS ASTM D2219:- Standard Specification for Poly(Vinyl2005 Chloride) Insulation for Wire and Cable,
60OC Operation(ASTM published 2002)
47. PNS ASTM D2220:- Standard Specification for Poly(Vinyl2005 Chloride Insulation for Wire and Cable,
75OC Operation(ASTM published 2002)
48. PNS ASTM D2308:- Standard Specification for2005 Thermoplastic Polyethylene Jacket for
Electrical Wire and Cable(ASTM published 2002)
49. PNS ASTM D3554:- Standard Specification for Track-2005 Resistant Black Thermoplastic High-
Density Polyethylene Insulation forWire and Cable, 75OC Operation(ASTM published 2001)
Power Cables & Wires Technical Manual
170
Power Cables & Wires Technical Manual
171
Annex D
Power Cables & Wires Technical Manual
173
Bibliography
1) Electric Cables Handbook 3rd Edition by Moore (Blackwell,1997)
2) Cable handbook by Phelps Dodge Philippines3) National Electrical Code4) Philippine Electrical Code5) Wikipedia
Power Cables & Wires Technical Manual
174