pnmt(pasolink+ stm1)

Upload: azzura-gunawan

Post on 14-Oct-2015

67 views

Category:

Documents


4 download

DESCRIPTION

youporn

TRANSCRIPT

ROI-S04060-058E030613PN MTASOLINKOperation ManualPASOLINK+ (SDH) VersionETWORKANAGEMENTERMINALNEC CorporationCopyright 2003ROI-S04060Table of ContentsGETTING STARTED .......................................................................................................... 1INTRODUCTION ........................................................................................................................... 1CONVENTIONS USED IN THIS MANUAL ....................................................................................... 111.1PNMT COMMUNICATION INTERFACES ............................................................................. 21.1.1Communications .......................................................................................................21.21.3HARDWARE CONFIGURATION FOR MOBILE TERMINAL (PNMT) ....................................... 4SOFTWARE CONFIGURATION FOR MOBILE TERMINAL (PNMT)......................................... 42SYSTEM OPERATION & MAINTENANCE ...................................................................... 52.12.22.3THE PNMT SCREEN ......................................................................................................... 5LAUNCHING THE PNMT APPLICATION. ............................................................................ 7LOGIN ...............................................................................................................................82.3.1User Privilege ...........................................................................................................92.42.52.62.72.82.92.102.112.12LOGOUT .......................................................................................................................... 10SHUTTING DOWN THE PNMT ......................................................................................... 10SEARCHING FOR NETWORK ELEMENTS AND CONNECTING TO SELECTED PASOLINK .. 11CHANGE PASSWORD........................................................................................................ 12ALARM BUZZER SETTING ................................................................................................ 13REFRESH ......................................................................................................................... 14REMOTE VIEWING LINK SUMMARY WINDOW .............................................................. 15OVERALL TAB .............................................................................................................. 16ODU TAB .................................................................................................................... 182.12.12.132.13.12.142.14.22.14.32.152.15.12.15.22.15.32.15.42.15.52.15.62.162.16.12.16.22.16.32.16.42.16.52.16.62.16.72.16.82.16.9ODU tab .................................................................................................................. 18IDU TAB...................................................................................................................... 20IDU Tab .................................................................................................................. 20AUXILIARY I/O TAB ..................................................................................................... 22Relay output Setting.............................................................................................. 24Relay Configuration................................................................................................ 24CONTROL (CTRL) TAB ................................................................................................ 25The Control Module ................................................................................................ 25Setting the Date/Time ............................................................................................ 26CTRL Reset ............................................................................................................. 27Downloading the Configuration Files to the Control Module............................... 27Downloading a new Program File to the Control Module .................................... 29Uploading Control Module Configuration file to PNMT PC................................. 32MAINTENANCE ............................................................................................................ 34Maintenance menu ................................................................................................ 34Selecting Maintenance mode ................................................................................. 35Switching TX (for 1+1 system only) ....................................................................... 35Switching RX (for 1+1 system only)....................................................................... 36Main Signal Loopback -1 (STM-1 near-end loopback) .......................................... 36Main Signal Loopback -2 (STM-1 far-end loopback) ............................................. 37IF Loopback (STM-1 near-end loopback) .............................................................. 37ALS Restart ............................................................................................................ 38Selecting TX Mute status ....................................................................................... 382.16.102.16.112.16.122.16.132.16.14TX Frequency ...................................................................................................... 39RX Frequency ...................................................................................................... 39Selecting Carrier Wave status............................................................................ 39ATPC Manual ...................................................................................................... 39XPIC Forced Reset (for XPIC system only) ........................................................ 40iROI-S040602.172.17.12.17.22.17.32.17.42.182.18.12.18.22.18.32.18.42.18.52.18.62.18.72.18.82.18.92.192.19.12.19.22.19.32.19.42.202.20.12.212.21.1EQUIPMENT SETUP...................................................................................................... 41Equipment Configuration Window ........................................................................ 41Setup ....................................................................................................................... 42Editing the NE Name ............................................................................................. 44Editing the Note for NE ......................................................................................... 44PROVISIONING ............................................................................................................. 45Provisioning Window .............................................................................................. 45MAIN INTFC .......................................................................................................... 46Overhead (OH) Assignment ................................................................................... 49Manual Transmit Power Control (MTPC) Status ................................................. 51Automatic Transmit Power Control (ATPC) Status ............................................. 53SW Priority ............................................................................................................. 56Sub INTFC .............................................................................................................. 57BER Threshold........................................................................................................ 59MS-AIS Generation ................................................................................................ 62LINK PERFORMANCE MONITOR ................................................................................... 63Viewing Summary Link Performance Monitor ..................................................... 63Threshold setting .................................................................................................... 64Link Performance Monitor (Daily Data) window. ................................................. 65Link Performance Monitor (15 min Data) window ............................................... 66EVENT LOG .................................................................................................................. 67Event log monitor ................................................................................................... 67VERSION TAB............................................................................................................... 68Version Monitor ...................................................................................................... 68iiROI-S04060IntroductionThe PNMT is a PASOLINK Network Management Terminal developed by NEC for management of NECs PASOLINK and PASOLINK+ radio transmission network. The PNMT is a scaled down version of PASOLINK Network Management System (PNMS) that is designed as a maintenance tool for field engineers to locally and remotely monitor alarms, control points, generate repots, and archive data, all within a familiar graphical user interface, and all in real time. The PNMT is a Mobile laptop computer fitted with NEC PNMT software package that interfaces and controls NEC PASOLINK series short haul radio equipment.This Windows-NT/98 based software package remote monitors and controls the status and configuration of an entire PASOLINK network with associated equipment as well as the performance of the actual microwave links.Conventions Used in this Manual1FontWhat the Font RepresentsExampleItalicFor manual titles or related document names.Please refer to PASOLINK Operation Manual for details.HostnameBoldItems on the user interface. Items on the computer display.File and directory names.The Overall window [Button]Buttons on the user interface.Click on [OK] button to continue Click on [Execute] button to sendcommand.Menu ItemsA menu name followed by a colon (:) means that you must select the menu and then item.When the item is followed by an arrow(), a cascading menu follows.Select System Login/Logout

A command variable where the user must enter the appropriate value.This is also commonly used when asking for a password.

KeycapKeyboard keys.Press Enter key.1 Getting StartedROI-S040601.1PNMT Communication Interfaces1.1.1 CommunicationsCommunications between the PNMT and the radio network equipment can be via the PNMT Port of the PASOLINK equipment, via the DSC to a remote node in the network.1.1.1.1 PNMT Port InterfaceOn the PASOLINK equipment, the PNMT Port is located on the front of the equipment.ODUThe PNMT Port consists of an RJ-45 connector and connects to ControlModule(CTRL) installed in the IDU via a serial cable to the relevant communications port of the PNMT Computer. The PNMT Port has the following properties: Port Configuration: Connector type: Bit per second rate: Stop bits: Data bit length:RS-232RJ-45 modular jack1200/2400/4800/9600/19200 (default 19200)18 Parity:no parity.2Fig. 1: Connecting the PNMT to Pasolink+ IDUIDU PNMT portPasolink+ IDUPNMT CablePNMTROI-S04060The following table is the pin assignment of the connection between the IDU PNMTPort and PNMT PC.PNMT portCabling diagram between PNMT PC and PNMT port3PNMT(PC) to Pasolink+ (PNMT port)3M9pin(F) RJ45PC (PNMT) Pasolink+RS-232C RS-232C1 DCD 1 1 1 CD2 RXD 2 2 2 TXD3 TXD 3 3 3 RXD4 DTR 4 4 4 DSR5 GND 5 5 5 GND6 DSR 6 6 6 DTR7 RTS 7 7 7 CTS8 CTS 8 8 8 RTS9 RI 9ROI-S040601.2Hardware Configuration for Mobile Terminal (PNMT)Recommended PNMT mobile PC configuration:Laptop PC with TFT DISPLAY (IBM PC or compatible)CPU:RAM: HDD: FDD:Pentium-II 500 or higher128 MB or more5 GB or more3.5 x 1CD-ROM:8 X or higherDisplay: 800x600 Screen area (16-bit color)Integrated Sound Card + Speaker1.3Software Configuration for Mobile terminal (PNMT)All structured and modular programs used in PNMT are resident in the hard disk and RAM of the personal computer. The Windows operating system is employed which is capable of multi-task processing using the Pentium microprocessor. The PNMT software basically consist of two parts, the operating system and the application programs .The operating system-Windows 98 (English Version) or-Windows NT Workstation Ver4.0 (English Version)-Windows 2000 (English Version)The application programs-PNMT softwareOther applications:-Internet Explorer 5.0 or higher-Acrobat Reader (to read Help File with PDF)4ROI-S04060This chapter explains the menu structure and procedures for operating of the PNMT.The explanation uses typical PNMT screens to illustrate the hierarchy of menu.2.1The PNMT ScreenThe PNMT window is comprised of the following main parts (Refer to figure 1). For detailed descriptions, refer to the Users Manual for the Windows NT operating system.Title barThe title bar of the window is used to indicate the title of the window.Common Menu barThe common menu bar of the window presents the System and Help options,illustrates the commands that can be executed from the various options. The Help function also can display the html version of this operation manual.NE-specific Menu barThis menu is a list of tasks that can be performed to the specific network element(NE) displayed in the PNMT. Configuration, Event Log, and Link Performance Monitor functions can be executed in the NE-specific Menu bar.Block DiagramThe block diagram illustrates the equipments of the PASOLINK Radio system. Itsmain purpose in the window is to display the current summary alarm state of the equipment. You can click on a specific block to display the status of equipment in thedata window.Data windowThis window displays in detail the status and alarm items of a specific equipment ofthe NE. You can select the tab or the block of the specific equipment you want to monitor in the data window.TabsTo view the status and alarms in the PASOLINK radio, click on the tab at the bottom of the Data window.Command ButtonThe command button is used to enter the data selected on the pop-up window intothe computer.Selectable FieldThe selectable field is a standard Windows input field where the user can scroll downon a list of values available for that option.Login UserThis indicates the current user that logged-in in the PNMT.52 System Operation & MaintenanceROI-S04060Title BarNE-Specific Menu BarBlock DiagramCommonMenu BarCommonTool BarDataWindowTabsLogin UserSelectable FieldCommand ButtonFig. 1: Common Parts of a Window6ROI-S040602.2Launching the PNMT application.To start PNMT:1.Power ON the system.NOTEConnect the RS-232C cable 30seconds after IDU'spower is ON and make sure that the RS-232C cable is connected between Com 1 of the PNMT PC andthe PNMT Port of the IDU.2.Login to Windows 2000/NT/98 Workstation. Please refer toWindows 2000/NT/98 Manual.Click on Start Programs Pnmt Pnmt then PNMT system logo appears followed by the Link summary window in the PNMT main window (See figure below)3.7ROI-S040602.3LoginUsers are registered by means of login name and password.To protect the network and network management system from unauthorized access or unauthorized modifications, five levels (refer to the table shown in section 2.3.1User Level Privilege) of users are defined with different privileges. The functions that are available depend on the users access level. Therefore, some of the functions may or may not be carried out.The highest level or administrator level has full access to the network and network management system and has the ability to create and assign privileges to other users.To login:1.Click on Systemwindow.Login/Logout in the Menu bar on main2.3.4.Enter the Username.Enter the valid Password for the specific User.Click on the [OK] button.8ROI-S040602.3.1 User Level PrivilegeUser Privilege (STM-1)*Admin : Enable to access to the all Network Elements.*Remote : Enable to access to the all Network Elements.(Disable to change network configuration and change program with downloading.)*Local : Enable to access to the Local NE and Opposite NE.(Disable to change network configuration and change program with downloading.)*User : Enable to access to items which doesn't affect to the equipment.*Monitor : Enable to monitor only and disable to control.954321CategoryITEMMonitorUserLocalRemoteAdminMenu-SystemDate/TimeOOOAlarm BuzzerOOOODownload Program FileOConnect(Remote Login)OOMenu-Configuration FileDownload FileOUpdateOUpload FileOProvisioningMTPCMTPC TX POWEROOORX THRESHOLD LEVELOOOADDITIONAL ATTOOOATPCATPC MAXIMUMOOOATPC MINIMUMOOOHYSTERESISOOORX Threshold LevelOOORX THRESHOLD LEVELOOOADDITIONAL ATTOOOATPC ALM ModeOOOTX POWER CONTROL onODU CPU ALM ModeOOOBER ALMTHRESHLD(RADIO)HIGH BER(RADIO) THRESHOLDOOOLOW BER(RADIO) THRESHOLD(for RXSW)OOOBER ALMTHRESHLD(DMR)E-BER(DMR) THRESHOLDOOOSD(DMR) THRESHOLDOOOBER ALMTHRESHLD(MUX)E-BER(MUX) THRESHOLDOOOSD(MUX) THRESHOLDOOOMAIN INTFCMAIN OUTPUT CONTROLOOOALSOOOALS DELAY TIMEOOOSUB BASEBANDINTERFACESUB INTFCOOOWS INTFCOOOWS LINE LENGTHOOOOH ASSIGNMENTASSIGNMENTOOOVF-? SETTINGOOOV11-? SETTINGOOOV11-? DIRECTIONAL SETTINGOOOLAN CARDOOOMAINTMAINTOOOOTX/RX FREQUENCYOOOTX SWITCHOOOTX MUTEOOOIF LOOPBACKOOOMAIN SIGNAL LOOPBACK-1OOOMAIN SIGNAL LOOPBACK-2OOOCW(Mod Carrier)OOOALS RESTARTOOOATPC MANUAL CONTROLOOORX SWITCHOOOEquipment SetupEquipment SetupOOONE NameOOONoteOOOOAux I/OInput Item TypeOOOOInput NameOOOOOutput NameOOOOOutput ControlOOOOPMONPMON ThresholdOOOOSave to diskOOOOLoggingSave to diskOOOOCTRL(MODEM, ODU)ResetOOOROI-S040602.4LogoutTo logout from PNMT:1.Click Systemwindow.Login/Logout on the Menu bar on the main2.3.Select Logout from the Login /Logout window.Click on [OK] button to continue the Logout process.2.5Shutting Down the PNMTTo close the PNMT application:1. Click System Exit on the Menu bar on the main window2. Click [Yes] to confirm closing the application.10ROI-S040602.6Searching for Network Elements and Connecting to Selected PASOLINKThe summary description (PASOLINK name, Equipment type, Opposite PASOLINK, etc.) of the current station where PNMT is connected can be displayed using this function. Summary description of the opposite station belonging to that link is also displayed.To search for or connect to PASOLINK in the network:1. Click on SystemConnect on Menu bar on main window.NOTEInitially only the current NE physically connected to the PNMT and its opposite station will be shown on the Network Element List.2.Click on [Search for Element] button to display all connected NEs inthe network.Select and highlight the NE to be viewed.Click [Connect] button. The Link Summary of the PASOLINK selected and its opposite station will be displayed.3.4.11ROI-S040602.7Change PasswordTo change the password:1.Click on System window.Change Password on the Menu bar on main2.3.4.5.Enter the Old password.Enter New PasswordEnter new password on the Confirm New Password to confirm. Click on [OK] button.NOTEFor details on initial user name and password, please refer to PNMT Install manual.12ROI-S040602.8Alarm Buzzer SettingThis function is used to activate and set the Alarm Buzzer. The desired sound scheme can also be set using this function.To set the Alarm Buzzer:1. Click System |Alarm Buzzer in the main window.2.Select the Wave file or Beep box to activate the buzzer. No sound is thefactory setting of the PNMTIf you select the Wave file box, enter the location of the sound file (*.wav) Otherwise; click on [] to locate the desired file. You can also preview the*.wav file by click on the arrow next to the browse button. If you select the Beep box, Click on [Edit] to edit the beep with its frequency and duration. You can also preview the Beep by click on the arrow next to the browsebutton.Click on [OK] button to activate the new setting.3.4.13ROI-S040602.9RefreshThis function is supported only by PNMT. This function enables PNMT to acquire all status manually and to update equipment informationTo Refresh:Click on Refresh Refresh in the main window or click on the refresh icon in the tool bar.NOTEMetering items such as TX power, RX level, power supply and BER are automatically refreshed every 15 seconds. This function is used when the immediate refreshing of these metering items is necessary or confirmation of all current status is immediately required.14ROI-S040602.10Remote Viewing Link Summary WindowYou can view a target link within the one Root NE of the PASOLINK network by searching the connected NEs and then connecting to a target NE. Please refer to Section 2.6 Searching for Network Elements and Connecting to Selected PASOLINK. This function allows you to connect to any NE in the network remotely.NOTE: For multi-Root NE network, you can only connect to NEs that are beingpolled by the same CMPC as the local NE where you are directly connected via thePNMT cable.Link Summary window (1+0 configuration)15ROI-S040602.11Overall TabThis tab is displayed on startup. The overall tab provides a snapshot at the most significant monitored items in the NE.The Overall tab gives a snapshot of the important settings of the NE. This window only displays current settings and there are no control functions associated with this window.Overall Tab1+0 ConfigurationOverall Tab1+1 TwinpathConfigurationOverall Tab1+1 Hot StandbyConfiguration16ROI-S04060The following items are displayed in this tab:MTPC TX Power the current value (in dB) of the Manual TransmitterPower Control attenuation set in the ODU. The MTPC Attenuation will only have a valid data if the MTPC is enabled.TX Frequency the current transmit frequency used. RX Frequency the current receive frequency used. Frame ID the set frame ID of the NE.TX Power Control shows the current power control mode used by the ODU. The TX Power Control is either Automatic Transmitter Power Control (ATPC) or Manual Transmitter Power Control (MTPC).MAIN INTFC shows the current main interface used by the IDU. The available interfaces for the STM-1 signal are: Electrical, Optical and Optical Single Fiber (SF).ALS shows the current setting of the Automatic Laser Shutdown (ALS). It can either be Enable or Disable. The ALS is an IDU function that intermittently turns on/off the laser output when a certain period elapses after STM-1 LOS mode starts.MAINT the current state of the Maintenance status.Selected TX (for Hot-standby configuration only) shows the current system used for signal transmission.Selected RX (for 1+1 system only) shows the current system used for signal reception.XPIC (for XPIC system only) - shows the current setting of XPIC function. The XPIC can either be set as Master, Slave, or Not Used (disabled).ooo o ooooooo17ROI-S040602.12ODU TabThis function is to display the values and status of the monitored items of the ODU. This window only displays current settings and there are no control functions associated with this window.To set the ODU parameters see the chapters on Equipment Setup and Provisioning.2.12.1 ODU tabTo view the alarm and status display of the ODU:1.Click the ODU tab in Link Summary window of the target NE.1+0 ODU windowODU window (1+1 configuration)18ROI-S04060Monitored Items in the ODUFollowing items are monitored.TX PORTIONAlarmo TX INPUT: alarm occurs when the TX IFinput signal from the IDU is lostoTX POWER: TX RF Power decreases 3 to 6 dB from nominal value.ATPC Status(This portion of screen isonly active if ATPC is used.)Control Range*RX Threshold Level* Additional Attenuation*ODU ALM Mode *oo ooMeteringTX Power: The transmitted power of theODU in dBm.MTPC Status (This portion of screen is onlyactive if MTPC is used.)o MTPC Attenuation *o RX Threshold Level*o Additional Attenuation*RX PORTIONAlarmRX LEVEL: alarm occurs when the input level decreases by preset value from squelch level. (See Provisioning : RX Threshold)MeteringRX Level: The received level interpreted in dBm.COMMON PORTIONAlarmo APC this alarm occurs when the Local Oscillator is locked out.o CABLE this alarm occurs when the communication between the ODU and theIDU is lost.MeteringPower Supply: Display PS value (V)* For the detailed description of this items see 2.16 Equipment Setup and 2.17Provisioning.19ROI-S040602.13IDU TabThis function is to display the values and status of the monitored items of the IDU. This window only displays current settings and there are no control functions associated with this window.To set the ODU parameters see the chapters on Equipment Setup and Provisioning.2.13.1 IDU TabTo view the alarm and status of the IDU:1. Select the IDU tab in Link Summary window of the target NE. The figurebelow illustrates the difference between the IDU tab of a 1+0 and a 1+1 system.IDU window (1+0 configuration)For 10/100BASE-T Main INTFC onlyIDU window (for 1+1 configuration)20ROI-S04060Monitored ItemsFollowing items are monitored:MODULEAlarmoMAIN INTFC alarm occurs when the 150MB INTFC/OPT INTFC module fails.oSUB INTFC alarm occurs when the WS INTFC/LAN CARD fails.oMODEM alarm occurs if there is a modem failure.E-BER (MUX) BER in the MUXportion is worse than E-BERthresholdE-BER (DMR) BER in the radio portion is worse than thresholdSignal Degrade (MUX) BER (in MUX) is worse than the Signal Degrade threshold.Signal Degrade (DMR) BER (in the radio portion) is worse than the thresholdATPC X CTRL the status of the cable connection between the master and slave IDU modules.(XPIC system only)ooooTX PORTIONAlarmMOD - alarm occurs when the TX unit (modem)failed.oStatusSelectedMAIN INTFC(for 1+1 systems only)ALS *ALS Delay Time*RX PORTIONAlarmDEM alarm occurs when the RX unit(demodulator) fails or the IF signal is lost.STM-1 Output Control - STM-1output is shut off or not. **Link - Link failure in Port1/Port2 on the LAN occurs. **Collision - Collision condition inPort1/Port2 on the LAN occurs. **Mode - LAN Speed **Duplex - Full or Half Duplex **Link Down Control - 10/100BASE-Toutput is shut off or not. **ooXPIC PORTION (for XPIC system only)oAlarmX IF LEVEL - alarm occurs when the IF signal level of the cross polarization channel is lower thanrequired level.oo oStatusXPIC Reset the status of XPIC functionSub Baseband InterfaceSUB INTFC*WS INTFC*WS Line Length* AIS SENDAIS RCVCOMMON PORTIONAlarmMAIN INTFC LOS alarm occurs when theSTM-1 signal in the MUX is lost.MAIN INTFC LOF alarm occurs when the frame synchronization of the STM-1 input (MUX) is lost.SUB INTFC LOS alarm occurs when the WS INFC/LAN CARD signal is lostMDCPU alarm when there is a failure in the communication between modulesLOF (MUX) loss of frame occurred in theMUX.LOF (DMR) - loss of frame occurred in the radio portion.ooOH Assignment:Assignment*V11 1/2* VF-1/2*10BASE-T*oooMeteringBER: The current overall value of theBit-Error-Rateo.21ROI-S04060BER ALM Threshold (MUX)BER ALM Threshold (DMR)oSignal Degrade- the current value of the signal degraded threshold in the MUXoE-BER the current value of E-BER threshold in the MUXoSignal Degrade- the current value of the signal degrade threshold in the radio portion.oE-BER the current value of the E- BER threshold in the DMR side* For the detailed description of this items see 2.15 Equipment Setup and 2.17 Provisioning** For 10/100BASE-T Main INTFC only.2.14Auxiliary I/O Tab4-relay output and 6 optocoupler inputs are provided in the PNMT for external control and alarms. The setting for each relay output/optocoupler is available by clicking on the selected device in the Auxiliary I/O Monitor window.To monitor and set the Auxiliary I/O:1. Select the Aux. I/O tab in the Link Summary window2.14.1.1 Monitored ItemsFollowing items are monitored in this tab:1. Six (6) inputs (Input1 - Input6)2. Four (4)-relay outputs (Output1 - Output4)22ROI-S040602.14.1.2 Optocoupler Input SettingTo set the Optocoupler input:1.Click on the selected [Input-n] button in Aux. I/O tab.The input properties will be displayed in the ensuing window. The Input window has two tabs (1) Condition and (2) Name.2.2.14.1.3 Setting the selected Input to Alarm or Status1.Select the Alarm condition of the Input. You can select the event when thetarget Input will send the alarm signal to the PNMS/PNMT. Also you can preset the input to just send the Status of the input instead of an alarmsignal. The alarm input severity is defined in the X.733 recommendations. Select the Severity of the alarm, its type and probable cause by clicking on the pull-down arrow on the left-hand side of the field.Click on the Name tab.Enter the name of the Input in the Name field. A maximum of 32 characters can be usedClick on [Execute] button to activate the selected state of the device. Click on [Close] button when finished.2.3.4.5.23ROI-S040602.14.2 Relay output SettingTo set the relay output:1.Click [Output-n] button in Aux. I/O window.To open or close the relays click on the Event ON or Event OFF button respectively.Enter the desired strings for the open and close states of the Relay in the appropriate Even ON and Event OFF fields. A maximum of 32 characters can be used.Click on the Name tab.Enter the desired name on the Name,Event ON and Event OFF field. Amaximum of 32 characters can be used.Click on [Execute] button to carry out the command. Click on [Close] button when finished.2.3.4.5.6.7.2.14.3 Relay ConfigurationThere are 11 relays in the PASOLINK+ IDU. Consequently, 11 parallel alarms can be defined. Relays RL01, RL02 and RL03 have fixed alarms. Maintenance, PS ALM and CPU Alarm are outputted on RL01, RL02 and RL03 respectively.RL04 to RL11 are user-definable relays. If the HK-OUTs are enabled, RL08 to RL11 are allocated for Housekeeping (HK) alarms.The PNMT allows the user to configure the relays in a table format. The columns indicate the relays (RL01 to RL11) and the rows indicate the parallel alarms available in the PASOLINK+ IDU. The following indicators are used in the table:Out indicates that the alarm - in the corresponding row, is issued on the corresponding relay. HK Indicates that the corresponding relay is used for House Keeping.Mask Indicates that no alarm is issued in the corresponding relay when the maintenance mode is activated. Blank button not related to the corresponding alarm.24ROI-S04060To set the relay configuration:1.Click [Relay Configuration] button in Aux. I/O window.Select the HK-OUT used in the IDU. There are four (4) available HK-OUTs in the PASOLINK+ system. Selecting 1/2/3/4 button means all HK-OUTs will be enable; 1/2/3 means only HK-OUT 1, 2 and 3 will be enabled; and so on. If the HK-OUTs will not be used, select Disable button.The button(s) that corresponds to the target alarm(s) and relay (s).2.3.4.Click onClick on [Execute] button to apply the new relay configuration. Click on [Close] button when finished.5.2.15Control (CTRL) Tab2.15.1 The Control Module1. Select the CTRL tab in Link Summary window of the target NE.25ROI-S04060The following items can be monitored and controlled in the CTRL tab:Calendar AlarmDate/TimeCTRL ResetDownload Configuration FileDownload Program FileDownload Equipment Configuration FileUpload Configuration FileUpload Equipment Configuration Fileoo o o o o oo2.15.2 Setting the Date/TimeThe Date and Time stored in control module can be displayed and adjusted using this function.To set the Date/Time:1. Click on the [Date/Time] button in the CTRL tab.NOTETo set the value of the Date and Time field to the same value as that of the PNMT computer, check on the Display PC Time box.a) To check the Date and Time on the Control module:a)-1Select Get Date/Time in the Date/Time window.Click on [Execute] button.The current date and time in the control will be displayed in the Date and Time field.a)-2a)-3b). To set the Date and Time on the Control module:b)-1Select Set Date/Time in the Date/Time window.Click on [Execute] button.Click on [Close] button when finished.b)-2b-3)26ROI-S040602.15.3 CTRL ResetThe control module can be reset using this function.NOTEResetting the control module will not affect the traffic. The connection to the selected PASOLINK will be lost a few minutes and will be automatically re-connected.To reset the control module:1.Click on the [CTRL Reset] button in CTRL tab.You can select the with ROM(Ctrl Program) Switching option if you want to switch to a newly downloaded control module Program file.Click on [Execute] button to continue the control module reset operation.2.3.2.15.4 Downloading the Configuration Files to the Control ModuleThis function is used to download configuration files from the PNMT to the control module. The configuration file pp_network.cfg, contains the IP address of the NE as well as the IP address of the opposite station and the information about the PASOLINK network where the NE is located. The pp_mib.cfg contains the information about the equipment (i.e. name, pm type, etc.) and housekeeping (AUX I/O)To download new configuration file to the NE:27ROI-S040601.Click on [Configuration File] in the button in the CTRL tabsDownload (PC>>CTRL) section.2.3.Select the type of file to be downloaded in the Type list.Enter the location of the configuration file in the File field, or click on[Browse] to locate the file on the local hard disk or diskette.WARNING!!!Make sure that the correct configuration file is downloaded to the correct Control module. Incorrect configuration file will lead to Control module or network failure.4. Click on [Execute] button to start the operation.5. A message window indicating the status of the operation will appear. It will close automatically once the operation is finished.WARNING:Make sure that you have successfully downloaded the configuration file before doing Update. Otherwise the Control module will switch to an empty ROM that may cause Control module failure.6. Click on [Update] button to activate the new configuration file(s).Select the appropriate box for the type of configuration file that will be updated. One or more configuration file can be updated by checking the box opposite to the configuration file name. Click on [Execute] button to start the operation. The "with ROM (Ctrl Program) Switching" box is for switching to the ROM with the new CTRL Program and has the same function that was previously discussed in section 2.14.5 Downloading a new Program file to the Control Module.28ROI-S04060NOTEpp_network.cfgWhenupdatingfile,NE-to-NEcommunication will be lost when the Controlmodulere-initialisestothenewsystemconfiguration. This WILL NOT affect the radio link.During this time PNMT connection to the PASOLINKwill be lost but will automatically be reconnected after the Control module resets.7. Click on [Close] button when done.2.15.5 Downloading a new Program File to the Control ModuleThis function is used to update the application program on the Control module. This operation affects only the NMS communication but not the radio link, and will not disrupt communication.To download the program file to control module:1.Click on [Program File] in the button in the CTRL tabs Download(PC>>CTRL) section.29ROI-S040602. Check the CTRL button. If you tick the with Self Reset the controlmodule will be reset automatically after program file download is completed. In this case, you wont need to do steps 5 thru 8.3. Enter the appropriate location of the program file (*.out) in the File field.Otherwise, click [Browse] to locate the file.WARNING!!!Make sure that the correct program file is downloaded to the Control module. Incorrect program file will lead to failure.4. Click on [Execute] button to start the operation.5. A message window will appear displaying the status of the operation. The message window will close automatically once the download is completed.NOTEThis operation may take several minutes depending on the program file size.6.Click on [CTRL Reset] button to switch to the new program file.7.Check the with ROM(Ctrl Program) Switching box.Click on the [OK] button to complete the switch to the new program file.8.NOTEThe connection to the selected PASOLINK+ will be lost a few minutes and will automatically re-connect.30ROI-S040602.15.6 Downloading the Equipment Configuration Files to the Control ModuleThis function is used to download equipment configuration files from the PNMT to the control module. The Equipment configuration file contains the radio configuration data (i.e. frequency, main interface) and provisioning data (i.e. OH assignment, BER alarm threshold).To download new configuration file to the NE:1.Click on [Equipment Config. File] in the button in the CTRL tabsDownload (PC>>CTRL) section.2.click on [Browse] to locate the file on the local hard disk or diskette.WARNING!!!Make sure that the correct configuration file is downloaded to the correct Control module. Incorrect configuration file will lead to Control module or network failure.3.Click on [Execute] button to start the operation.A message window indicating the status of the operation will appear. It will close automatically once the operation is finished.4.WARNING:Make sure that you have successfully downloaded the configuration file before doing Update. Otherwise the Control module will switch to an empty ROM that may cause Control module failure.31ROI-S040605.Click on [Update] button to activate the new equipment configurationfile. Click on [Execute] button to start the operation.6.Click on [Close] button when done.2.15.7 Uploading Control Module Configuration file to PNMT PCThis function is used to upload the configuration file from the Control module of the selected PASOLINK to the PNMT PC.To upload configuration file from the Control module to the PNMT:1.Click on [Configuration File] in the button in the CTRL tabsUpload (CTRL>>PC) section.2.3.Select the type of file to be uploaded on the Type field.Click on the [Execute] button to start the operation.Enter the desired file name for the uploaded file. And select and the directory where the uploaded file will be saved.A message window indicating the status of the operation will appear. It will close automatically once the operation is completed.After the upload is finished click on [Close] button.Verify that the file was uploaded on the specified directory.4.5.6.7.32ROI-S040602.15.8 Uploading Equipment Configuration file to PNMT PCThis function is used to upload the Equipment configuration file from the Control module of the selected PASOLINK to the PNMT PC.To upload configuration file from the Control module to the PNMT:1.Click on [Equipment Config. File] in the button in the CTRL tabsUpload (CTRL>>PC) section.2.Click on the [Execute] button to start the operation.Enter the desired file name for the uploaded file. And select and the directory where the uploaded file will be saved.3.4.A message window indicating the status of the operation will appear. It willclose automatically once the operation is completed.After the upload is finished click on [Close] button.Verify that the file was uploaded on the specified directory.5.6.33ROI-S040602.16MaintenanceThere are ten maintenance control items that can be executed in the maintenance menu. The function of each control is as follows.MAINT : To switch Maintenance mode to ON TX Mute : To turn off TX powerCW(MOD Carrier): To turn on the Continuous Wave for measurements*These windows are not available when MAINT is OFF. (Switch to Maintenancemode first is displayed.)2.16.1 Maintenance menuTo go to maintenance window:1.Click Maintenance button in Link Summary window.Maintenance window(1+0configuration)Maintenance window(1+1 configuration)34ROI-S040602.16.2 Selecting Maintenance modeTo switch the PASOLINK to maintenance mode:1.Click [MAINT] button in Maintenance window.2.Select on ON/OFF depending on desired state.Click on [Execute] to carry out the command. Click on [Close] button when finished.3.4.2.16.3 Switching TX (for 1+1 system only)To control the TX switch manually:1.Click [TX Switch] button in Maintenance window.2.Select the system that you want to use for the TX portion of the radio. Thedefault value is Auto.Click on [Execute] button to switch the TX to the selected system. Click on [Close] button when finished.3.4.35ROI-S040602.16.4 Switching RX (for 1+1 system only)To control the RX switch manually:1.Click [RX Switch] button in Maintenance window.2.Select the system that you want to use for the RX portion of the radio. Thedefault value is Auto.Click on [Execute] button to switch the TX to the selected system. Click on [Close] button when finished.3.4.2.16.5Main Signal Loopback -1 (STM-1 near-end loopback)This type loopback is created at the 150MB INFTC/OPT INTFC of the selected NE where you are currently connected.To set the STM-1 near-end loopback:7.Click on the [Main Signalwindow.Loopback 1] button in the Maintenance8.9.Select ON to activate the loopback.Click on [Execute] button to apply the loopback.10. Click on [Close] button when finished.36ROI-S040602.16.6 Main Signal Loopback -2 (STM-1 far-end loopback)This type loopback is created at the 150MB INFTC/OPT INTFC of the opposite NE. To set the STM-1 near-end loopback:1.Click on the [Main Signal Loopbackwindow.2] button in the Maintenance2.3.Select ON to activate the loopback.Click on [Execute] button to apply the loopback. Click on [Close] button when finished.4.2.16.7IF Loopback (STM-1 near-end loopback)This type loopback is created at the 150MB INFTC/OPT INTFC of the selected NE.To set the STM-1 near-end loopback:1. Click on the [IF Loopback 2] button in the Maintenance window.37ROI-S040602.3.Select ON to activate the loopback.Click on [Execute] button to apply the loopback. Click on [Close] button when finished.4.2.16.8 ALS RestartThis function is used to set the time of manual restart of the Automatic Laser Shutdown (ALS). When the optical input signal is off due to ALS, the IDU will emit laser signal from TX to RX at a preset value (2 sec or 90 sec), at this point, if the fault has been recovered then the ALS will be released and operation will return to normal. Otherwise, the laser emission will end immediately. (See PASOLINK + Instruction Manual for further details.)To set the ALS restart:1.Click on [ALS Restart] button in the Maintenance window.2.3.Select the timing in seconds of the laser emission for manual restart.Click on [Execute] button to apply the timing of the manual restart. Click on the [Close] button when finished.4.2.16.9 Selecting TX Mute statusTX power of the ODU is switched off when TX Mute is ON. This should be OFF in normal operation.To change the TX Mute status:1.Click [TX Mute] button in Maintenance windowNOTESwitch ON maintenance mode first before performing TX Mute.2.3.Select ON/OFF depending on the desired state.Click on [Execute] button to carry out the command. Click on [Close] button when finished.4.38ROI-S040602.16.10TX FrequencySets the RF transmitted frequency and consequently its pair receiving frequency.(See 2.17 Equipment Setup.)2.16.11RX FrequencyDisplays the current RF receiving frequency used by the ODU.(See 2.17 Equipment Setup.)2.16.12Selecting Carrier Wave statusWhen doing frequency measurements, the CW should be turned OFF to have anunmodulated signal. During normal operations this status should be ON.To change the CW (MOD Carrier) status:1.Click [CW (MOD Carrier)] button in Maintenance windowNOTESwitch ON maintenance mode first before performing CW.2.Click on ON/OFF button depending on desired state.Click on [Execute] button to carry out command. Click on [Close] button when finished.3.4.2.16.13ATPC ManualUsed when an optional transmitting power is required when the ATPC is in operation.To set the ATPC Manual:1. Click [ATPC Manual] button in Maintenance window39ROI-S040602.Select the whether to manually turn ON or OFF the ATPC manual and theATPC manual power that will be transmitted in dB.Click on [Execute] button to activate the new setting. Click on [Close] button when finished.3.4.2.16.14XPIC Forced Reset (for XPIC system only)XPIC function forcedly disabled.To set the XPIC Forced Reset1.Click [XPIC Forced Reset] button in Maintenance window.2.3.4.Click on Auto/Reset button depending on desired state.Click on [Execute] button to carry out command. Click on [Close] button when finished40ROI-S040602.17Equipment SetupMain signal, ODU and CTRL portion can be monitored and controlled in this window.2.17.1 Equipment Configuration WindowTo open the Equipment Configuration Monitor:1.Select Configuration Equipment Setup in the NE-specific menu bar.This window contains the setup information and control for the IDU and the ODU. The Equipment Setup window is shown below.2.41ROI-S040602.17.2 SetupTo setup the ODU and IDU parameters:1.Click on the [Setup] button in the Equipment Setup window.2.On the Setup window, the configurable items are shown and described in thetable below:42XPIC*XPIC sets the XPIC function mode to either. Master, Slave, or NotUsed (disabled).Adjacent Channel sets the adjacent channel to ACAP or ACCP modeNote: when an adjacent channel exists, ACAP must be selected.ODUTX Frequency sets the RF transmit frequency and consequently theRF receive frequency of the ODUIf frequency Channel file is previously registered, frequency setting by Channel name is available. Refer to Frequency Channel screen shown as below.TX Power Control method used by the ODU for power control functions can be set here. Either Automatic Transmit Power Control (ATPC) or Manual Transmit Power Control (MTPC) can be selected.ROI-S04060*: for XPIC system only3. Click on [Execute] button to apply the new set of values.CAUTION:Changing the TX/RX CH will interrupt the traffic.NOTE1. In the XPIC system, TX Power Control of slave equipment is not configurable.The slave equipment follows the TX Power Control setting of the master equipment.2. In the XPIC system, if TX Power Control of master equipment is changed, the TX Power Control of the slave equipment is also changed. This will be displayed on the event log (two lines).2.17.2.1 Frequency Channel1.Click on [Browse] to locate the Channel plan file on the local hard disk.2.Select Channel and click on [OK], then TX and RX frequency corresponding to the channel will be set.43IDURedundancy This function Is available only for 1+1 systems Hot- Stand-By or Twin-Patch configuration can be set using this function.Main INTFC the main interface of IDU can be selected here. The available interfaces are STM-1(Optical), STM-1(Electrical) or STM-1(Optical SF).Frame ID used to synchronize the TX and RX frames of opposingNEs in the hop. The frame ID can be set from 1 to 8.ROI-S04060Frequency channel file format is csv, including channel name, TX frequency and RXfrequency.ExamplesCh1, 7442.000, 7603.000Ch2, 7603.000, 7442.0002.17.3 Editing the NE NameTo edit the NE name:1.Click [NE Name] button in Equipment Setup window.2.Enter new PASOLINK name in the NE Name dialog box. A maximum of 32characters can be used.Click on [Execute] button to change to new name. Click on [Close] button when finished.3.4.2.17.4 Editing the Note for NETo put an optional description on the current PASOLINK:1.Click [Note] button in Equipment Setup window.2.Enter the optional description for the specific PASOLINK in the Note dialog box. Amaximum of 100 characters can be used in this fieldClick on [Execute] button when finished. Click on [Close] button when finished.3.4.44ROI-S040602.18ProvisioningThe main interface (MAIN INTFC), overhead (OH), MTPC and ATPC can be set in this window.2.18.1 Provisioning WindowTo open the Equipment Configuration Monitor:1.Select Configuration Provisioning in the NE-specific menu bar.This window contains the setup information of the main INTFC, OH, MTPC and2.ATPC.The Provisioning window is shown below.45ROI-S040602.18.2 MAIN INTFCThis function enables you to set the ALS and its properties. The ALS or Automatic Laser Shutdown is a function available in the IDU that cuts the laser emission on the main interface after a certain period of time that the STM-1 LOS have been activated.2.18.2.1 Enabling the ALSWhen the ALS is enabled, the laser emission will be cut off after a certain period have elapsed after the IDU have issued an STM-1 LOS. If the ALS is disabled, the laser emission will be continuously outputted.To enable the ALS:1.Click on the [ALS] button on the Provisioning window.Select Enable on the ensuing window.2.3.Click on [Execute] button to enable the ALS.Click on [Close] button when finished.4.2.18.2.2Setting the ALS Delay Time (ALS Restart)This function allows you to set the time in seconds before the ALS will tryautomatically to release the laser lock-off. After the preset time have elapsed, the IDU will emit laser intermittently and if the fault have been corrected the ALS will be released and continue with the normal operation. Otherwise, the laser will beimmediately cut off.To set the ALS delay time:5.Click on the [ALS Delay Time] button on the Provisioning window.Select the time in seconds when the ALS will try to automatically release the lock-off in laser emission in the ensuing window.6.7.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.8.46ROI-S040602.18.2.3 Setting the PORT UsageThis function selects band width for Port1 and Port2. Sum of band width with Port1+Port2=150Mbps. When select usage of Port1=100Mbps and Port2=Not used, provisioning setting of following function for Port1 is only available.To set the PORT Usage:1.Click on the [PORT Usage] button on the Provisioning window.Select the combination of Port1 and Port2 usage.2.3.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.4.2.18.2.4 Setting the PORT 1This function is setting the Port1. Auto Negotiation corresponds to the LAN interface signal speed and mode. These choices are applicable only when Auto Negotiation is in OFF condition.1.2.Click on the [PORT 1] button on the Provisioning window.Select the Port1 setting.3.4.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.47ROI-S040602.18.2.5 Setting the PORT 2This function is setting the Port2. Auto Negotiation corresponds to the LAN interface signal speed and mode. These choices are applicable only when Auto Negotiation is in OFF condition.1.2.Click on the [PORT 2] button on the Provisioning window.Select the Port1 setting.3.4.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.2.18.2.6 Enabling the Far End Link DownWhen Link fault information is received from opposite site, release the LAN connection from interface. When it is detected Link fault, sends Link fault information to the opposite site and also release the LAN connection. Disable means that Far End Link Down control is not used.1.2.Click on the [Far End Link Down] button on the Provisioning window.Select Enable on the ensuing window.3.4.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.48ROI-S040602.18.2.7 Setting the Clock SourceInternal Clock means the timing source for synchronization applied from the inner system clock. DMR -> Internal Clock means the timing source for synchronization is applied from received clock via DMR.1.2.Click on the [Clock Source] button on the Provisioning window.Select the way to use the timing for synchronization.3.4.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.2.18.3 Overhead (OH) Assignment2.18.3.1 OH Assignment TypeThe OH can be either set at factory default (Easy) or customized (Custom) according to user requirements.To set the OH Assignment type:1.Click on the [Assignment] button in the Provisioning window.Select the type of OH assignment that will be employed.2.3.Click on [Execute] button to apply the setting.Click on [Close] button when finished.4.49ROI-S040602.18.3.2 DirectionTo set the direction:1.Click on the [Direction] button in the OH Assignment table.On the ensuing table, you will be able to select the direction for the V11-1 andV11-2 interface.2.3.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.4.2.18.3.3 Channel UsageThis function allows you to set the interface used on the available user channels (E1, F1, DSC, etc.) in the PASOLINK +. The user channels can be set as V11, VF or LAN (Ethernet) using this function.To set the channel usage:1. Click on the [Channel Usage] button in the OH Assignment table.2. On the ensuing window, the channel usage table will be displayed. You can assign a target channel to use a specific interface by plotting the channel (column) and the interface (row) on the table and clicking on the button that corresponds to the target channel and interface. Note that for each channel you can set only one interface.3. Click on [OK] button to apply the new settings.50ROI-S040602.18.4 Manual Transmit Power Control (MTPC) StatusWhen the MTPC is selected over ATPC the buttons on this section will become sensitive and the MTPC parameters can be set. The MTPC has four (4) parameters: MTPC TX Power RX Threshold Additional Attenuation And ODU ALM ModeThe procedure for setting these parameters will be presented in this section.NOTE1. In the XPIC system, MTPC status of slave equipment is not configurable.. The slave equipment follows the MTPC status setting of the master equipment.2. In the XPIC system, if MTPC status of master equipment is changed, of the MTPC status of slave equipment is also changed. This is shown in the event log (two lines). This is normal operation.2.18.4.1 MTPC TX PowerWhen the MTPC is in operation, the transmission power (dB) can be set using this function.To set the maximum transmission power in MTPC:1.Click on [MTPC TX Power] button in the Provisioning button.Set thepower (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right- hand corner of the field to increase or decrease the value shown in the input field.2.Click on [Execute] button to apply the maximum MTPC TX power.Click on [Close] button when finished.3.2.18.4.2RX ThresholdSets the threshold value of the receiving level. When the received level converge onthe preset value of the threshold the TX power is controlled by sending control signals in the Radio Frame Complementary Overhead (RFCOH).To set the RX threshold:1. Click on the [RX Threshold] button in the MTPC status section of theProvisioning window.51ROI-S040602.Set the power (dB) in the ensuing window. You can either highlight theinput field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field.3.Click on [Execute] button to apply the new preset value.Click on [Close] button when finished.4.2.18.4.3Additional AttenuationIf the transmission length of the radio section is short, additional span attenuatorscan be set in the ODU. The additional attenuation can be set from 0 to 5 dB.To set the additional attenuation:1.Click on the [Additional Attenuation] button in the MTPC statussection of the Provisioning window.Set the attenuation (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field2.3.Click on [Execute] button to apply the attenuation.Click on [Close] button when finished.4.2.18.4.4 ODU ALM ModeIn case wherein the ODU losses communication with the IDU due to failure of some sort, the response of the ODU can be preset using this function. Since the control function of the TX power is in the IDU, the ODU will be cut-off to this control when a failure in the communication between the ODU and the IDU occurs. In this case, the ODU either mutes the TX or Hold the current TX power, depending on the preset ODU ALM mode.52ROI-S04060To set the ODU ALM mode:1.Click on the [ODU ALM Mode] button in the MTCP status section of theProvisioning window.Select the action of the ODU in case of IDU communication failure. For MTPC, only Hold mode is available.2.3.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.4.2.18.5 Automatic Transmit Power Control (ATPC) StatusWhen the ATPC is selected over MTPC the buttons on this section will become sensitive and the ATPC parameters can be set. The ATPC has five (5) parameters: TX MAX Power TX MIN Power RX Threshold Additional Attenuation ODU ALM ModeThe procedure for setting these parameters will be presented in this section.NOTE1. In the XPIC system, ATPC status of slave equipment is not configurable.. The slave equipment follows the ATPC status setting of the master equipment.2. In the XPIC system, if ATPC status of master equipment is changed, of the ATPC status of slave equipment is also changed. This is shown in the event log (two lines). This is normal operation.53ROI-S040602.18.5.1 TX MAX PowerWhen the ATPC is in operation, the maximum transmission power (dB) can be set using this function.To set the maximum transmission power in ATPC:1.Click on [TX MAX Power] button in the Provisioning button.Set the power (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field.2.3.Click on [Execute] button to apply the maximum ATPC TX power.Click on [Close] button when finished.4.2.18.5.2TX MIN PowerWhen the ATPC is in operation, the minimum transmission power (dB) can be setusing this function.To set the maximum transmission power in ATPC:1. Click on [TX MIN Power] button in the Provisioning button.2. Set the power (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field.3. Click on [Execute] button to apply the minimum ATPC TX power.4. Click on [Close] button when finished.54ROI-S040602.18.5.3 RX ThresholdSets the threshold value of the receiving level. When the received level converge on the preset value of the threshold the TX power is controlled by sending control signals in the Radio Frame Complementary Overhead (RFCOH).To set the RX threshold:1.Click on the [RX Threshold] button in the ATPC status section of theProvisioning window.Set the power (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field.2.3.Click on [Execute] button to apply the new preset value.Click on [Close] button when finished.4.2.18.5.4Additional AttenuationIf the transmission length of the radio section is short, additional span attenuatorscan be set in the ODU. The additional attenuation can be set from 0 to 5 dB.To set the additional attenuation:1.Click on the [Additional Attenuation] button in the ATPC statussection of the Provisioning window.Set the attenuation (dB) in the ensuing window. You can either highlight the input field and enter the dB value using the keypad or use the arrows on the right-hand corner of the field to increase or decrease the value shown in the input field2.3.Click on [Execute] button to apply the attenuation.Click on [Close] button when finished.4.55ROI-S040602.18.5.5 ODU ALM ModeIn cases wherein the ODU losses communication with the IDU due to failure of some sort, the response of the ODU can be preset using this function. Since the control function of the TX power is in the IDU, the ODU will be cut-off to this control when a failure in the communication between the ODU and the IDU occurs. In this case, the ODU either mutes the TX or Hold the current TX power, depending on the preset ODU ALM mode.To set the ODU ALM mode:1.Click on the [ODU ALM Mode] button in the ATCP status section of theProvisioning window.Select the action of the ODU in case of IDU communication failure. For ATPC, MAX Hold, MIN Hold or Hold mode is available.2.3.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.4.2.18.6 SW Priority2.18.6.1 TX SW PriorityThe TX SW priority defines the channel that will be selected by the TX switch when both channels are normal.Non-priority: There is no priority.Priority No.1: Priority is given to No.1 channel.56ROI-S040602.18.6.2 RX SW PriorityThe RX SW priority defines the channel that will be selected by the RX switch when both channels are normal.Non-priority: There is no priority.Priority No.1: Priority is given to No.1 channel.2.18.7 Sub INTFCThere are 2 optional sub interfaces available in the PASOLINK + system. On this section, these sub-interfaces can be defined and specified accordingly.2.18.7.1 Defining the SUB INTFCTo set the type of sub interface mounted in the IDU:1.Click on the [SUB INTFC] button in the Provisioning window.Select the type of interface used from the ensuing window. If there are no WS andLAN card plugged-in in the IDU, Not used must be selected.2.3.Click on [Execute] button to apply the newly defined sub interface.Click on [Close] button when finished.4.57ROI-S040602.18.7.2 Defining the Wayside (WS) InterfaceTo specify the type of WS interface used:1.Click on the [WS INTFC] button in the Provisioning window.Select the type of WS interface on the ensuing window.2.3.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.4.2.18.7.3 WS Line LengthTo specify the WS line length:1.Click on the [WS Line Length] button in the Provisioning window.Select the line length in meters from the ensuing window. The WS line length can be set from 0 to 199.6 meters.2.3.Click on [Execute] button to apply the newly specified length.Click on [Close] button when finished.4.58ROI-S040602.18.8 BER ThresholdThe BER in the PASOLINK+ system is monitored in 3 sections (1) the MUX section, (2) the DMR section and the (3) Radio section. The Radio section is available 1+1 systems only and is used for switchover function. The figure below illustrates these sections:The MUX and DMR section BER is measured in terms of Signal Degrade and E-BER.Signal Degrade is triggered when the BER is worse than the preset threshold (1E-6,1E-7, etc.). Excessive BER (E-BER) occurs when the BER is worse than the preset threshold (1E-3, 1E-4, or 1E-5).The radio section, on the other hand, monitors the BER for switchover purposes. When the BER becomes worst than the preset value of the Low BER (RX Switch) the RX is switched to the other system in a 1+1 configuration. In a similar manner, when the BER becomes worse than the preset value for High BER, the switched to the other system.The preset value mentioned above is called the BER Threshold. The BER threshold can be set in 6 points: (1) Signal Degrade (MUX), (2) E-BER (MUX), (3) Signal Degrade (DMR), (4) E-BER (MUX), (5) Low BER, and (6) High BER. Low BER and High BER, however, are only available in 1+1 systems.59ROI-S040602.18.8.1 Signal Degrade (MUX)To set the threshold for signal degrade:1.Click on the [Signal Degrade (MUX)] button in the Provisioning window.Select the preset BER value that will trigger the signal degrade. The factory setting is 1E-6.2.3.Click on [Execute] button to apply the new threshold.Click on [Close] button when finished.4.2.18.8.2 E-BER (MUX)To set the E-BER Threshold for the MUX section:1.Click on the [E-BER (MUX)] button in the Provisioning window.Select the preset value wherein the E-BER will be triggered.2.3.Click on [Execute] button to apply the new threshold.Click on the [Close] button when finished.4.2.18.8.3 Signal Degrade (DMR)To set the threshold for signal degrade:1. Click on the [Signal Degrade (DMR)] button in the Provisioning window.2. Select the preset BER value that will trigger the signal degrade. The factory setting is 1E-6.60ROI-S040603. Click on [Execute] button to apply the new threshold.4. Click on [Close] button when finished.2.18.8.4 E-BER (DMR)To set the E-BER Threshold for the DMR section:1.2.Click on the [E-BER (DMR)] button in the Provisioning window.Select the preset value wherein the E-BER will be triggered.3.4.Click on [Execute] button to apply the new threshold.Click on the [Close] button when finished.2.18.8.5 High BER (Radio) [for 1+1 systems only]To set the threshold for High BER:1.2.Click on the [High BER] button in the Provisioning window.Select the preset BER value that will trigger the signal degrade. The factory setting is 3E-4.3.4.Click on [Execute] button to apply the new threshold.Click on [Close] button when finished.61ROI-S040602.18.8.6 Low BER (Radio) [for 1+1 systems only]To set the Low BER:1.2.Click on the [Low BER] button in the Provisioning window.Select the preset value wherein the E-BER will be triggered.3.4.Click on [Execute] button to apply the new threshold.Click on the [Close] button when finished.2.18.9 MS-AIS Generation2.18.9.1 MS-AIS GenerationThis setting is available only for the system which is provided with STM-1 INTFC and MS-AIS Generation. Enable means that Multiplexer Section AIS signal is generated when an AIS condition occurs. Disable means that function of the Multiplexer Section AIS signal generation is unavailable. When an AIS condition occurs, MS-AIS is not transmitted.1.2.Click on the [MS-AIS Generation] button in the Provisioning window.Select Enable on the ensuing window.3.4.Click on [Execute] button to apply the new setting.Click on [Close] button when finished.62ROI-S040602.19Link Performance MonitorThe following performance items can be monitored according to G.826 recommendation:Out of Frame Second (OFS) the total number of seconds the "out of frame" condition is generated in 15 minute-blocks.(OFS is applied to the Total only)"Errored Second (ES) the cumulative time in which more than one B1 error pulse per second was detectedSeverely Errored Second (SES) the cumulative time in which the BER of one-second period exceeded 10E-3.Unavailable Second (UAS) the cumulative time in which the unit remained inoperative Background Block Error (BBE) - the sum of the B1 background block errorRed color in Performance monitor window indicates the occurrence of performance items exceeding the threshold value. The threshold values can be set in Threshold window. The detailed daily performance data can be seen by clicking on the [Detail] button.2.19.1 Viewing Summary Link Performance MonitorTo view Summary Link Performance Monitor:1.Click on Link Performance Monitor in the NE-specific menu bar of thetarget PASOLINK the PASOLINK that you intend to monitor.Summary Link Performance Monitor63ROI-S040602.19.2 Threshold settingTo set the threshold values:1.Click on [Threshold] button in the Summary Link Performance Monitorwindow2.Select the performance item that is to be configured on the table shown above.The G.826 measure becomes available for setting when selected. The arrow buttons on the left-hand side of the field indicates this.Set the value when the alarm Occur and when the alarm Recover in the appropriate field. The measure will issue an alarm status when it reaches the alarm occur value or issue an alarm clear status when it reaches the recover value set in the threshold table.Click on [Execute] button to activate the new settings. Click on [Close] button when finished.3.4.5.64ROI-S040602.19.3 Link Performance Monitor (Daily Data) window.This window contains the Link Performance data of the current 8 days. To view the Link Performance Monitor (Daily Data) window:1.Click [Detail] button in Link Performance Monitor window.Link Performance Monitor window2.On this window a table presents the available data in the NE. The table ispresented as G.826 measure versus the Date. The date buttons on the right- hand side of the table is selectable. Moreover, the buttons reflect the summary alarm for that specific date.Click on the date buttons to display the detailed 15-min data for that date.3.65ROI-S040602.19.4 Link Performance Monitor (15 min Data) windowTo view the 15-min Data:1. Click button of the target date in Link Performance Monitor (Daily Date) window to display the detailed 15-min performance data.RefreshSaveLink Performance Monitor (15-min Data) window2.The data can be saved in text format by clicking on the save icon. Or can berefreshed by clicking on the refresh button.66ROI-S040602.20Event logThe Event Log Windows displays the date when the event or command was received, the equipment, item, and status.2.20.1 Event log monitor1.Click on Event Log in the NE-specific menu bar of the target PASOLINK thePASOLINK that you intend to monitor.A message window showing the progress of the uploading of the Event Log data will appear on the screen. Wait until the PNMT finishes the uploading of the data. The progress window will automatically close once the uploading is completed.The Event Log View will be displayed. The event log is presented in a table form showing the date of the event, the item that triggered the event and the status change.Sorting is possible for every column in Event Log window.The date shown in the Event Log window will be the format set up by OS.2.3.4.5.67ROI-S040602.21Version TabThe inventory information of the ODU and IDU can be viewed using this function.2.21.1 Version MonitorTo display version of ODU, IDU.1.2.Select the Version tab in Link Summary window.The version tab shows the Date of Manufacture, Software Version, Serial No. andCode No. of the ODU, IDU and.Version window for (1+0)Version window for (1+1)68