    Module 4 : Programmable Logic Controllers

    Programmable Logic Controllers(PLC`S)

    Introduction :

    A PLC (i.e. Programmable Logic Controller) is a device that was invented to replace the necessary sequential relay circuits for machine control.

    The PLC works by looking at its inputs and depending upon their state, turning on/off its outputs. The user enters a program, usually via

    software, that gives the desired results.

    PLC Example :

    Let's assume that when a switch turns on we want to turn a solenoid on for 5 seconds and then turn it off regardless of how long the switch is

    on for.

    We can do this with a simple external timer. But what if the process included 10 switches and solenoids? We would need 10 external timers.

    What if the process also needed to count how many times the switches individually turned on? We need a lot of external counters.

    PLC - need :

    The bigger the process the more is need for a PLC.

    Simply program the PLC to count its inputs and turn the solenoids on for the specified time.

    The primary reason for designing PLC was eliminating the large cost involved in replacing the complicated relay based machine control systems.

    Inside PLC :

    The PLC mainly consists of :

    - A CPU,

    - Memory areas, and

    - Appropriate circuits to receive input/output data.

    We can actually consider the PLC to be a box full of hundreds or thousands of separate relays, counters, timers and data storage locations.

    INPUT RELAYS-(contacts) :These are connected to the outside world. They physically exist and receive signals from switches, sensors, etc.Typically they are not relays but rather they are transistors.

    INTERNAL UTILITY RELAYS-(contacts) :These do not receive signals from the outside world nor do they physically exist. They aresimulated relays and are what enables a PLC to eliminate external relays. There are also some special relays that are dedicated to performingonly one task. Some are always on while some are always off. Some are on only once during power-on and are typically used for initializing data

    that was stored.

    COUNTERS :These again do not physically exist. They are simulated counters and they can be programmed to count pulses. Typically thesecounters can count up, down or both up and down.

    TIMERS :These also do not physically exist. They come in many varieties and increments. The most common type is an on-delay type. Othersinclude off-delay and both retentive and non-retentive types. Increments vary from 1ms through 1s.

    OUTPUT RELAYS-(coils): These are connected to the outside world. They physically exist and send on/off signals to solenoids, lights, etc.They can be transistors, relays, or triacs depending upon the model chosen.

    DATA STORAGE : Typically there are registers assigned to simply store data. They are usually used as temporary storage for math or datamanipulation. They can also typically be used to store data when power is removed from the PLC. Upon power-up they will still have the same

    contents as before power was removed.

  • 8/13/2019 Plc in Detail for Process Control

    2/54

    PLC Operation :

    A PLC works by continually scanninga program. We can think of this scan cycle as consisting of 3 important steps.

    Step 1-CHECK INPUT STATUS :First the PLC takes a look at each input to determine if it is on or off. In other words, is the sensor connectedto the first input on? How about the second input? How about the third... It records this data into its memory to be used during the next step.

    Step 2-EXECUTE PROGRAM :Next the PLC executes program one instruction at a time. Maybe program said that if the first input was on thenit should turn on the first output. Since it already knows which inputs are on/off from the previous step it will be able to decide whether the first

    output should be turned on based on the state of the first input. It will store the execution results for use later during the next step.

    Step 3-UPDATE OUTPUT STATUS :Finally the PLC updates the status of the outputs. It updates the outputs based on which inputs were onduring the first step and the results of executing your program during the second step. Based on the example in step 2 it would now turn on the

    first output because the first input was on and your program said to turn on the first output when this condition is true. After the third step thePLC goes back to step one and repeats the steps continuously. One scan time is defined as the time it takes to execute the 3 steps listed above.

    PLC - Response :

    The total response time of the PLC is a fact we have to consider when purchasing a PLC.

    PLC takes a certain amount of time to react to changes. In many applications speed is not a concern, in others though...

    PLC Response Time Concern :

  • 8/13/2019 Plc in Detail for Process Control

    3/54

    Input 1 is not seen until Scan 2.

    Input 2 is not seen until Scan 3.

    Input 3 never seen by PLC.

    To avoid this we say that the input should be ON for at least 1 input delay time + one scan t ime.

    But what if it was not possible for the input to be on this long?Then the plc doesn't see the input turn on.

    Pulse Stretch Function :

    This function extends the length of the input signal until the plc looks at the inputs during the next scan.( i.e. it stretches the duration of the

    pulse.)

    Interrupt Function :

    This function interrupts the scan to process a special routine i.e. As soon as the input turns on, regardless of where the scan currently is, the

    PLC immediately stops what its doing and executes an interrupt routine.

    An interrupt routine can be thought of as a mini program outside of the main program. After its done executing the interrupt routine, it goes

    back to the point it left off at and continues on with the normal scan process.

  • 8/13/2019 Plc in Detail for Process Control

    4/54

    Relays :

    We understand how the PLC processes inputs, outputs, and the actual program.

    Now lets see How a relay actually works. After all, the main purpose of a PLC is to replace "real-world" relays.

    We can think of a relay as an electromagnetic switch.

    Apply a voltage to the coil and a magnetic field is generated. This magnetic field sucks the contacts of the relay in, causing them to make a

    connection.

    These contacts can be considered to be a switch. They allow current to flow between 2 points thereby closing the circuit.

    Relays a real example :

    Here we simply turn on a bell whenever a switch is closed.

    We have 3 real-world parts : A switch, a relayand a bell. Whenever the switch closes we apply a current to a bell causing it to sound.

    Replacing Relays :

    Lets use a PLC in place of the relay.

    The first thing that's necessary is to create what's called a Ladder Diagram.

    We have to create one of these because, unfortunately, a PLC doesn't understand a schematic diagram it only recognizes code.

    Most PLCs have software which convert ladder diagrams into code.

    Ladder Diagram :

    First Step :Translate all of the items we're using into symbols the PLC understands.

    Second step :We must tell the PLC where everything is located. In other words we have to give all the devices an address.

    Final step :We have to convert the schematic into a logical sequence of events.

  • 8/13/2019 Plc in Detail for Process Control

    5/54

    First Step :

    The PLC doesn't understand terms like switch, relay, bell, etc.

    It prefers input, output, coil, contact, etc.

    It doesn't care what the actual input or output device actually is. It only cares that its an input or an output.

    First we replace the battery with a symbol. This symbol is common to all ladder diagrams. We draw what are called bus bars.

    These simply look like two vertical bars. One on each side of the diagram. Think of the left one as being + voltage and the right one as being

    ground. Further think of the current (logic) flow as being from left to right.

    Next we give the inputsa symbol. In this basic example we have one real world input. (i.e. the switch).

    We give the input that the switch will be connected to the symbol shown below. This symbol can also be used as the contact of a relay.

    Next we give the outputsa symbol. In this example we use one output (i.e. the bell).

    We give the output that the bell will be physically connected to the symbol shown below. This symbol is used as the coil of a relay.

    The AC supply is an external supply so we don't put it in our ladder. The PLC only cares about which output it turns on and not what's physicallyconnected to it.

    Second Step :

    We must tell the PLC where everything is located. In other words we have to give all the devices an address.

    Where is the switch going to be physically connected to the PLC? How about the bell? We start with a blank road map in the PLCs town and give

    each item an address.

    Could you find your friends if you didn't know their address? You know they live in the same town but which house? The plc town has a lot of

    houses (inputs and outputs) but we have to figure out who lives where (what device is connected where).

    We'll get further into the addressing scheme later. The PLC manufacturers each do it a different way! For now let's say that our input will becalled "0000". The output will be called "500".

    Final Step :

    Convert the schematic into a logical sequence of events.

    The program we're going to write tells the PLC what to do when certain events take place.

    In our example we have to tell the plc what to do when the operator turns on the switch.

  • 8/13/2019 Plc in Detail for Process Control

    6/54

    Final converted diagram.

    We eliminated the real world relay from needing a symbol.

    Basic Instructions :

    Load :

    The load(LD) instruction is a normally open contact. It is sometimes also called examine if on (XIO).(as in examine the input to see if itsphysically on). The symbol for a load instruction is shown below.

    This is used when an input signal is needed to be present for the symbol to turn on.

    When the physical input is on we can say that the instruction is True.

    We examine the input for an on signal. If the input is physically on then the symbol is on.

    An on condition is also referred to as a logic 1 state.

    Load Bar :

    The Load bar instruction is a normally closed contact. It is sometimes also called LoaDNot or examine if closed( XIC)(as in examine the inputto see if its physically closed) The symbol for a loadbar instruction is shown below.

    This is used when an input signal does not need to be present for the symbol to turn on.

    When the physical input is offwe can say that the instruction is True.

    We examine the input for an off signal. If the input is physically off then the symbol is on.

    With most PLCs this instruction(Loador Loadbar) MUST be the first symbol on the left of the ladder.

  • 8/13/2019 Plc in Detail for Process Control

    7/54

    Out :

    The Out instruction is sometimes also called an Output Energize instruction. The output instruction is like a relay coil. Its symbol looks asshown below.

    When there is a path of True instructions preceding this on the ladder rung, it will also be True.

    When the instruction is True it is physically ON.

    We can think of this instruction as a normally open output.

    Out Bar :

    The Outbar instruction is sometimes also called an OutNot instruction.

    The Outbar instruction is like a normally closed relay coil. Its symbol looks like that shown below.

    A Simple Example :

    In the above circuit, the coil will be energized when there is a closed loop between the + and - terminals of the battery.

    We can simulate this same circuit with a ladder diagram.

  • 8/13/2019 Plc in Detail for Process Control

    8/54

    A ladder diagram consists of individual rungs just like on a real ladder.

    Each rung must contain one or more inputs and one or more outputs.

    The first instruction on a rung must always be an input instruction and the last instruction on a rung should always be an output (or itsequivalent).

    Notice in this simple one rung ladder diagram we have recreated the external circuit above with a ladder diagram.

    Here we used the Load and Out instructions.

    Some manufacturers require that every ladder diagram include an END instruction on the last rung. Some PLCs also require an ENDH

    instruction on the rung after the END rung.

    Next we'll trace the registers

    PLC Registers :

    In Previous example change switch 2 (SW2) to a normally closed symbol (loadbar instruction).

    SW1 will be physically OFF and SW2 will be physically ON initially. The ladder diagram now looks like this :

    We gave each symbol (or instruction) an address.

    This address sets aside a certain storage area in the PLCs data files so that the status of the instruction (i.e. t rue/false) can be stored.

  • 8/13/2019 Plc in Detail for Process Control

    9/54

    A Level Application :

    We are controlling lubricating oil being dispensed from a tank.

    This is possible by using two sensors.

    We put one near the bottom and one near the top, as shown in the picture.

    Here, we want the fill motor to pump lubricating oil into the tank until the high level sensor turns on. At that point we want to turn off the motor

    until the level falls below the low level sensor. Then we should turn on the fill motor and repeat the process.

    Here we have a need for 3 I/O (i.e. Inputs/Outputs) :

    2 are inputs (the sensors) and 1 is an output (the fill motor).

    Both of our inputs will be NC (normally closed) fiber-optic level sensors. When they are NOT immersed in liquid they will be ON. When they areimmersed in liquid they will be OFF.

  • 8/13/2019 Plc in Detail for Process Control

    10/54

    Program Scan :

    Initially the tank is empty. Therefore, input 0000 is TRUE and input 0001 is also TRUE.

    Gradually the tank fills because 500(fill motor) is on.

    After 100 scans the oil level rises above the low level sensor and it becomes open. (i.e. FALSE).

    Even when the low level sensor is false there is still a path of true logic from left to right. This is why we used an internal relay. Relay 1000 is

  • 8/13/2019 Plc in Detail for Process Control

    11/54

    latching the output (500) on. It will stay this way until there is no true logic path from left to right.(i.e. when 0001 becomes false).

    Since there is no more true logic path, output 500 is no longer energized (true) and therefore the motor turns off.

    Even though the high level sensor became true there still is NO continuous true logic path and therefore coil 1000 remains false!.

    After 2000 scans the oil level falls below the low level sensor and it will also become true again.

    At this point the logic will appear the same as SCAN 1 above and the logic will repeat as illustrated above.

    Latch Instruction :

  • 8/13/2019 Plc in Detail for Process Control

    12/54

  • 8/13/2019 Plc in Detail for Process Control

    13/54

    0000 and 0001 are both physically on.

    Next the PLC executes the program.

    Starting from the top left, input 0000 is true therefore it should set 0500.

    Next it goes to the next rung and since input 0001 is true it should reset 0500.

    The last thing it said was to reset 0500. Therefore on the last part of the scan when it updates the outputs it will keep 0500 off. (i.e. reset

    0500).

    Counters :

    A counter is a simple device intended to do one simple thing - count.

    There are up-counters(they only count up 1,2,3...). These are called CTU,(count up) CNT,C, or CTR.

    There are down counters(they only count down 9,8,7,...). These are typically called CTD (count down).

    To use Counters we must know 3 things :

    Where the pulsesthat we want to count are coming from. Typically this is from one of the inputs.(a sensor connected to input 0000 forexample).

    How many pulseswe want to count before we react. Let's count 5 widgets before we box them, for example.

    When/how we will reset the counter so it can count again. After we count 5 widgets lets reset the counter, for example.

    In this counter we need 2 inputs :

    - One goes before the reset line. When this input turns on the current (accumulated) count value will return to zero.- The second input is the address where the pulses we are counting are coming from.

    Cxxx is the name of the counter. If we want to call it counter 000 then we would put "C000" here.

    yyyyy is the number of pulses we want to count before doing something.

  • 8/13/2019 Plc in Detail for Process Control

    14/54

    Timers :

    TIMER :It is an instruction that waits a set amount of time before doing something.

    Type of Timers : On-Delay Timer and Off-Delay Timer.

    On-Delay Timer :

    Simply "delays turning on".

    After sensor (input) turns ON, wait x-seconds before activating a solenoid valve(output).

    This is the most common timer. It is often called TON(timer on-delay), TIM(timer) or TMR(timer).

    Off-Delay Timer :

    Simply "delays turning off".

    After sensor (input) sees a target it turn on a solenoid (output).

    When the sensor no longer sees the target it hold the solenoid on for x-seconds before turning it off.

    It is called a TOF (timer off-delay).

    Need to know 2 things :

    What will enable the timer :

    - Typically this is one of the inputs,(a sensor connected to input 0000 for example).

    How long we want to delay before we react.

    - Let's wait 5 seconds before we turn on a solenoid, for example.

    On-Delay Timer :

    Txxx :Timer Name.

    When the enable input is ON the timer starts to tick.

    When it ticks yyyyy(the preset value) times, it will turn on its contacts that we will use later in the program.

    Timer in Ladder Diagram :

  • 8/13/2019 Plc in Detail for Process Control

    15/54

    Wait for input 0001 to turn on.

    Timer T000 (a 100ms increment timer) starts ticking. It will tick 100 times. Each tick (increment) is 100ms so the timer will be a 10000ms (i.e.

    10 second) timer.

    100ticks X 100ms = 10,000ms.

    When 10 seconds have elapsed, the T000 contacts close and 500 turns on.

    When input 0001 turns off (false) the timer T000 will reset back to 0 causing its contacts to turn off (become false) thereby making output 500turn back off.

    One Shot :

    A one-shot is used to make something happen for ONLY 1 SCAN.

    Most manufacturers have one-shots that react to an off toon transition and a different type that reacts to an on tooff transition.

    Some names for the instructions could be DIFU/DIFD(differentiate up/down), SOTU/SOTD(single output up/down), OSR(one-shot rising)and others.

    Master Controls :

    Master controls can be thought of as "emergency stop switches".

    An emergency stop switch typically is a big red buttonon a machine that will shut it off in cases of emergency.

    The master control instruction typically is used in pairs with a master control reset.

    It is commonly abbreviated as MC/MCR(master control/master control reset).

    Timersshould not be used inside the MC/MCRblock.

    MCR in Ladder Diagram :

  • 8/13/2019 Plc in Detail for Process Control

    16/54

    In this example, rungs 2 and 3 are only executed when input 0000 is on (true).

    If input 0000 is not true the plc pretends that the logic between the MC and MCR instructions does not exist.

    Shift Registers :

    To store many previous events and act upon them later.

    We use a register or group of registers to form a train of bits (cars) to store the previous on/off status. Each new change in status gets stored

    in the first bit and the remaining bits get shifted down the train.

    SFT (ShiFT), BSL (Bit Shift Left), SFR (Shift Forward Register).

    BSR (Bit Shift Right) and SFRN (Shift Forward Register Not).

    Symbol needs 3 inputs and has some data inside the symbol : 1000: First Bit,

    1003 : Last Bit.Data :The data input gathers the true/false statuses that will be shifted down the train. When the data input is true the first bit (car) in theregister (train) will be a 1. This data is only entered into the register (train) on the rising edge of the clock input.

    Clock :The clock input tells the shift register to "do its thing". On the rising edge of this input, the shift register shifts the data one locationover inside the register and enters the status of the data input into the first bit. On each rising edge of this input the process will repeat.

    Reset :The reset input does just what i t says. It clears all the bits inside the register we're using to 0.

    Shift Registers - Application :

    Imagine an ice-cream cone machine. We have 4 steps :

  • 8/13/2019 Plc in Detail for Process Control

    17/54

    1. First we verify the cone is not broken.

    2. Next we put ice cream inside the cone.(turn on output 500).3. Next we add peanuts.(turn on output 501).

    4. Finally we add sprinkles.(turn on output 502).

    If the cone is broken we obviously don't want to add ice cream and the other items. Therefore we have to track the bad cone down our processline so that we can tell the machine not to add each item.

    We use a sensor to look at the bottom of the cone (input 0000). If its on then the cone is perfect and if its off then the cone is broken.

    An encoder tracks the cone going down the conveyor. (input 0001). A push button on the machine will clear the register. (input 0002).

    A good cone comes in front of the sensor (input 0000). The sensor (data input) turns on. 1000 will not turn on until the rising edge of the encoder

    (input 0001). Finally the encoder now generates a pulse and the status of the data input (cone sensor input 0000) is transferred to bit 1000. The

    register now looks like :

    As the conveying system moves on, another cone comes in front of the sensor. This time it's a broken coneand the sensor remains off. Now theencoder generates another pulse. The old status of bit 1000 is transferred to bit 1001. The old status of 1001 shifts to 1002. The old status of

    1002 shifts to 1003. And the new status of the data input (cone sensor) is transferred to bit 1000. The register now looks like :

  • 8/13/2019 Plc in Detail for Process Control

    18/54

    Since the register shows that 1001 is now on, the ladder says that output 0500 will turn on and ice cream is put in the cone. As the conveyingsystem continues to move on, another cone comes in front of the sensor. This time it's a good cone and the sensor turns on. Now the encoder

    generates another pulse. The old status of bit 1000 is transferred to bit 1001. The old status of 1001 shifts to 1002. The old status of 1002 shifts

    to 1003. And the new status of the data input (cone sensor) is transferred to bit 1000. The register now looks like :

    Since the register shows that 1002 is now on the ladder says that output 0501 wi ll turn on and peanuts are put on the cone. Since 1001 now

    holds the status of a broken cone, 500 remains off in the ladder above and no ice-cream is inserted into this cone.

    As the conveying system continues to move on, another cone comes in front of the sensor. This time it's also a good cone and the sensor turnson. Now the encoder generates another pulse.

    - The old status of bit 1000 is transferred to bit 1001.- The old status of 1001 shifts to 1002.

    - The old status of 1002 shifts to 1003.- And the new status of the data input(cone sensor) is transferred to bit 1000. The register now looks like :

    Since the register shows that 1003 is now on the ladder says that output 0502 will turn on and sprinkles are put on the cone.

    Since 1002 now holds the status of a broken cone, 501 remains off in the ladder above and no peanuts are put onto this cone.

    Since the register shows that 1001 is now on the ladder says that output 0500 will turn on and ice cream is put in that cone.

    As the conveying system continues to move on, another cone comes in front of the sensor. This time it's another broken cone and the sensor

    turns off. Now the encoder generates another pulse.

    The old status of bit 1000 is t ransferred to bit 1001.The old status of 1001 shifts to 1002.

  • 8/13/2019 Plc in Detail for Process Control

    19/54

    The old status of 1002 shifts to 1003.

    And the new status of the data input (cone sensor) is transferred to bit 1000.

    The register now looks like :

    As the conveying system continues to move on, another cone comes in front of the sensor. This time it's another broken cone and the sensor

    turns off. Now the encoder generates another pulse.

    The old status of bit 1000 is transferred to bit 1001.

    The old status of 1001 shifts to 1002.The old status of 1002 shifts to 1003.

    And the new status of the data input (cone sensor) is transferred to bit 1000.The register now looks like :

    Notice that the status of our first cone has disappeared.

    The shift register is most commonly used in conveyor systems, labeling or bottling applications, etc.

    Programming Languages :

    IEC 61131-3 defines FIVE programming languages for PLC.

    The languages can be mixed in any way within a PLC project.

    Machining process involved in Valve Production :

    - Two sensors are used to establish whether a work piece with correctly drilled holes is available at the machining position.

    - If the valve to be machined is of type A or type B (set via two selector switches).

    - The cylinder advances and presses the sleeve in to the drilled hole.

    Ladder Diagram (LD) :

    Graphical Programming language derived from the circuit diagram of directly wired relay controls.

    Functional Block Diagram (FBD) :

    Functions and function blocks are represented graphically and interconnected into networks.

    Originates from Logic diagrams.

  • 8/13/2019 Plc in Detail for Process Control

    20/54

    Instruction List (IL) :

    Textual Assembler-type language.

    Formulated from control instructions consisting of an operator and an operand.

    Structured Text (ST) :

    Structured text is high-level language based on Pascal, which consists of expressions and instructions.

    Sequential Functional Chart (SFC) :

    Language resource for the structuring of sequence oriented control programs. The elements of SFC are steps, transitions, alternative and

    parallel branching.

    Common Elements of Programming Languages :

    Resources of a PLC :

    -> Inputs, outputs and the memory.

    -> Directly addressed variables.

    Variables and data types :

    -> Representation of data.-> Data types.

    -> Variable declaration.-> Initialization.

    Program :

    -> Functions.

    -> Function blocks.

    Inputs, outputs and memory :

    Designation of resources :

    -> Inputs I.

    -> Outputs Q.

    -> Memory M.

    Data types :

    -> BOOL (X) 1 bit.

    -> BYTE (B) 8 bit.

    -> WORD (W) 16 bit.

  • 8/13/2019 Plc in Detail for Process Control

    21/54

    IX, QX, MX, IB, QB, MB, IW, QW, MW.

    Multiple resources :

    -> I1 Input 1.-> I15 Input 15.

    -> QW3 Output Word 3.-> MB5 Memory Byte 5.

    Directly addressed variables :

    -> Resource in control program addressed directly.

    -> Prefixed with the sign %.

    -> %I12 Input bit 12, %QB8 Output byte 8.

    Variables and Data Types :

    Representation of Numerical Data :

    -> Integers: 12, -8, 123_456, +751.

    -> Floating point: 0.123_4, -12.0, -8.0.

    -> Numbers to base 2: 2#1101_0011.

    -> Numbers to base 8: 8#323.

    -> Numbers to base 16: 16#D3.

    -> Boolean: 0, 1.

    Representation of Time Data :

    -> Time duration: T#18ms, TIME#18ms, t#3.5s.

    -> Date: D#2008-04-21, DATE#2008-04-21.

    -> Time of day: TOD#13:18:42.55.

    -> Date and Time: DT#2008-04-21:13:18:42.55.

    Representation of Strings :

    ->B character.

    -> warning string.

    Data Types :

    -> BOOL

    -> SINT, INT, DINT, UINT

    -> REAL

    -> TIME

    -> STRING

    -> BYTE

    -> WORD

    Controller program constructed into individual organization units :

    -> Configuration.

    -> Resources.

    -> Programs.

    -> Function blocks.

    -> Functions.

    All variables have specific position.

    All variable declaration starts with a keyword, which designate position of variable and end with keyword END_VAR

    VAR

    Temp : INT;

  • 8/13/2019 Plc in Detail for Process Control

    22/54

    Hand : BOOL;

    END_VAR

    Keywords for variable declaration :

    -> Input variables VAR_INPUT-> Output variables VAR_OUTPUT

    -> In/Output variables VAR_IN_OUT

    -> Local variables VAR

    -> Global variables VAR_GLOBAL-> External variables VAR_EXTERN

    Keyword ATis used to assign variables to the inputs and outputs of the controller.

    VAR

    Stop_button AT%I2 : BOOL;

    Temperature AT%IW3 : BOOL;

    END_VAR

    PROGRAM :

    Program for a controller is divided into individual organization units at the programming level :

    -> Programs.

    -> Function blocks.

    -> Functions.

    Functions :

    Function are software modules which, when invoked provide exactly one result.

    E.g. Addition of INT values or logic OR.

  • 8/13/2019 Plc in Detail for Process Control

    23/54

    Standard Functions :

    -> AND, OR, XOR, NOT.

    -> SHL, SHR, ROR, ROL.-> GT, GE, EQ, LE, LT, NE.

    -> ADD, MUL, SUB, DIV, MOVE.

    Function Blocks :

    Function blocks are software modules, which supply one or several result parameters.

    One important characteristic is possibility of instantiation.

    To use, a copy or instance must be created.

    The status information of the function block copy remains intact from one processing to the next.

    Example : Counters, Timers.

    CTU : incremental counter.

    Standard Function Blocks :

    CTU Incremental counter.

    CTD Decremental counter.

    TP Pulse.

    TON Switch-ON delay signal.

    TOF Switch-OFF signal delay.

    R_TRIG Edge detection: rising edge.

    F_TRIG Edge detection: falling edge.

    Programs :

    Consists of any language elements.

    Constructs necessary instructions to achieve the desired machine or process behavior by PLC.

    Stairwell Light Control Program :

    -> The stairwell light is switched ON for 3 min, if one of the two light switches on the apartment door or the front door is activated.

  • 8/13/2019 Plc in Detail for Process Control

    24/54

    Timers :

    IEC 61131-3 defines 3 types of timer function blocks :

    -> TPPulse Timing.-> TONOn-delay timing.-> TOFOff-delay timing.

    Time duration is specified by means of a defined character format :

    -> T#2h15m, T#20s.

    -> T#10m25s, t#3h_40m_20s.

    Timers TP Pulse Timer :

    TP is started by a shorter or longer 1-signal at input IN. A 1-signal now applies at output Q for the time specified at its input PT (preset time).

    The output signal Q has a fixed duration.

  • 8/13/2019 Plc in Detail for Process Control

    25/54

    TP Pulse Timer Example :

    Pressing of the start button S2 is to cause the piston of a cylinder to advance. This mechanism is used to clamp workpieces.

    When the piston advance fully, it is to remain in this position for 20 seconds.

    The cylinder then returns to its initial position.

  • 8/13/2019 Plc in Detail for Process Control

    26/54

    Timers Switch-On signal delay :

    TON is used to generate switch ON signal delays.

    After the start via a 1-signal at input IN, output Q does not assume value 1 until the time specified at input PT has expired, and retains this

    until input signal IN returns to 0.

    If the duration of input signal IN is shorter than the PT, the value of output remains at 0.

    TON Example :

    Cylinder 1A1 extends, if start button S1 is actuated.

    Once this has been extended for 2s, a second cylinder 2A1 move to its forward end position.

    Sensors 1B1 and 1B2 indicates the retracted and the forward end positions of cylinder 1A1.

  • 8/13/2019 Plc in Detail for Process Control

    27/54

  • 8/13/2019 Plc in Detail for Process Control

    28/54

  • 8/13/2019 Plc in Detail for Process Control

    29/54

    Decremental counter CTD :

    The decremental counter with preselect value PV is loaded with a 1-signal at input LD (load).

    During normal operation, each positive edge at input CD (count down) reduces the counter reading.

    Output Q of function block CTD is 0, until the counter reading CV becomes less than or = 0.

    CTD example :

    A cylinder is moved via a valve 1Y1.

    The position of cylinder is signaled via the sensors 1B1 (retracted) and 1B2 (extended).

    The cylinder is to advance, if push button S1 is pressed.

    When 10 strokes have been executed this way, lamp H1 is illuminated and the counter has expired.

  • 8/13/2019 Plc in Detail for Process Control

    30/54

    The counter must be re-loaded with the preset value, before any cylinder movements can be executed further. This is affected by means of

    actuating push button S2.

    Automation Control Systems :

    Automation control systems :

    These control systems are used in manufacturing plants of all types, and some other applications that you may not have considered.

    The control systems are built around special devices, designed to operate industrial machines, and processes. We call these devicesProgrammable Logic Controllers (PLC) and Programmable Automation Controllers (PAC).

    PLC and PAC Systems :

    PLCs were introduced in the early 1970s. The term PAC, was developed to differentiate those older systems from todays much morepowerful, and flexible devices.

    An analogy can be made between the VHS video tape, and a DVD. Both systems allow viewers to record TV programs for viewing at a latter

    time, but the DVD also can also be used to record music, data, and more.

    PLCs were designed to control machinery. PACs can be used for machine control, process, motion control, and other applications.

    We will use the term PLC generically to refer to both PLCs, and PACs.

    This section will explore the various components that comprise a PLC system.

  • 8/13/2019 Plc in Detail for Process Control

    31/54

    Basic Components of a PLC System :

    There are five basic componentsin a PLC system :

    The PLC processor, or controller.

    I/O (Input /Output) modules.

    Chassis or backplane.

    Power supply.

    Programming software that runs in a PC.

    In addition to these 5, most PLCs also have : A network interface. Lets look at each in more detail..

    Processor, Controller, or CPU :

    Stores the control program and data in its memory.

    Reads the status of connected input devices.

    Executes the control program.

    Commands connected outputs to change state based on program execution.- For example : Turn a light on, start a fan, adjust a speed, or temperature.

    Comes in various physical forms.

    I/O Modules :

    Physically connect to field devices.

    Input modules convert electrical signals coming in from input field devices such as pushbuttons, to electrical signals that the PLC canunderstand.

    Output modules take information coming from the PLC and convert it to electrical signals the output field devices can understand, such as a

    motor starter, or a hydraulic solenoid valve.

    I/O comes in various forms.

  • 8/13/2019 Plc in Detail for Process Control

    32/54

    Input modules interface directly to devices such as switches and temperature sensors.

    Input modules convert many different types of electrical signals such as 120VAC, 24VDC, or 4-20mA, to signals which the controller can

    understand.

    Input modules convert real world voltage and currents to signals the PLC can understand. Since there are different types of input devices, there

    is a wide variety of input modules available, including both digital and analog modules.

  • 8/13/2019 Plc in Detail for Process Control

    33/54

    Discrete vs. Analog Modules :

    DiscreteModules use only a single bit to represent the state of the device. For example, a switch is either open or closed. Therefore, the bit iseither a 0 (switch is open) or a 1 (switch is closed). Discrete modules are also known as Digital modules.

    AnalogModules use words to represent the state of a device. An analog signal represents a value.. For example, the temperature could be 5,9, 20, 100, etc degrees. Analog modules use a value, such as 52, rather than a 0 or 1 to represent the state of the device.

    Discrete Modules :

    Devices that are either on or off, such as a pushbutton, get wired to discretemodules. Discrete modules come in a variety of types, such as24VDC or 120VAC. You can buy discrete modules that allow you to typically connect anywhere from 2 to 32 devices, with the most popular being

    16 devices.

    Since it takes only 1 bit to represent the state of a device, a 16 point discrete module only requires 16 bits of memory in the controller to store

    the states of all the points on the module.

    Analog Modules :

  • 8/13/2019 Plc in Detail for Process Control

    34/54

    Devices that have a numberassociated with them, such as a temperature sensor, get wired to analogmodules. Analog modules come in avariety of types, such as 4 to 20 mA or 0 to 10 VDC. You can buy analog modules that allow you to connect anywhere from 2 to 16 devices.

    Since it takes 1 word to represent a number, a 16 point analog module requires 16 words of memory in the controller to store the value of all

    the numbers on the module. Each word in a PLC takes 16 or 32 bits (depending on the PLC), therefore it takes 16 or 32 times the amount of PLCmemory to store analog points vs. digital points.

    Output Modules :

    Output modules interface directly to devices such as motor starters and lights.

    Output modules take digital signals from the PLC and convert them to electrical signals such as 24VDC and 4 mA that field devices canunderstand.

    Output modules take a signal from a PLC and convert it to a signal that a field device needs to operate. Since there are different types of output

    devices, there is a wide variety of output cards available, including both digital and analog cards.

    Basic Components of a PLC System :

    Chassis/Backplane :

    All PLCs need some method of communicating between the controller, I/O and communications modules. Here are three ways used to accomplish

  • 8/13/2019 Plc in Detail for Process Control

    35/54

    this communications between the various components that make up the PLC system.

    Modules are installed in the same chassis as the PLC and communicate over the chassis backplane.

    Modules are designed to plug intoeach other. The interconnecting plugs form a backplane there is no chassis.

    Modules are built intothe PLC and modules come together in one physical block. The backplane in this case is transparent to the user.

    Below is an example of a backplane in a chassis based system. You can see the backplane in the area where the modules are not inserted. The

    modules have connectors that plug into the black connectors on the backplane. All of the connectors on the backplane are connected together

    electrically.

    Chassis and Backplane Examples :

    Benefits of the Different Forms :

    Great flexibility in choice of modules. Modules can be easily installed or removed without affecting other modules.

    Great flexibility in choice of modules. In some cases modules cannot be removed without breaking the chain and affecting all modules

    downstream no chassis cost.

    Low cost solution but limited flexibility, generally used in smaller, simpler systems.

  • 8/13/2019 Plc in Detail for Process Control

    36/54

  • 8/13/2019 Plc in Detail for Process Control

    37/54

    Network Interface :

    Most PLCs have the ability to communicate with other devices. These devices include computers running programming software, or collecting dataabout the manufacturing process, a terminal that lets an operator enter commands into the PLC, or I/O that is located in a remote location from

    the PLC. The PLC will communicate to the other devices through a network interface.

    Network Interface :

  • 8/13/2019 Plc in Detail for Process Control

    38/54

    PLC Control Panel :

    Typically, PLCs are installed in enclosures, on a panel.

    PLCs are part of a Control System :

  • 8/13/2019 Plc in Detail for Process Control

    39/54

    The PLC system is the center of a control system, but it is not the entire control system. There are several other key pieces that must be added to

    a PLC system to make a complete control system. Examples are :

    Operator terminals.

    Networks.

    Distributed I/O devices (I/O that is in a different location then the PLC).

  • 8/13/2019 Plc in Detail for Process Control

    40/54

    Module 4 : Programmable Logic ControllersPLC programming languages

    Programming a PLC :

    Every PLC has associated programming software that allows the user to enter a program into the PLC.

    Software used today is Windows based, and can be run on any PC.

    Different products may require different software: PLC5, SLC, and ControlLogix each require their own programming software.

    Before a PLC can perform any control task, it must be programmed to do so. The most popular language used to program a PLC is ladder logic.

  • 8/13/2019 Plc in Detail for Process Control

    41/54

    In a conveyor system, we have several requirements to accomplish; for example, timing and counting parts on the conveyor. Each of these

    requirements must be programmed into the PLC so that it knows how to respond to different events.

    The programmer develops the program, and connects their personal computer to the PLC through a network or cable and then downloads the programto the PLC.

    Ladder Logic Example :

  • 8/13/2019 Plc in Detail for Process Control

    42/54

  • 8/13/2019 Plc in Detail for Process Control

    43/54

    In this example, if the actual Start Button is on, then the value of all the XICs named Start Button, in the program will be true(also known as a one,or closed).

    If the start button is off (not on) then the value of the Start Button XICs will be false (also known as a zero, or open) .

    This instruction turns onif the logic to the left of the OTE is true. If the logic is false, then the output will be turned off. The OTE commands a physicaloutput located on a output module to turn either on or off.

    If there are multiple XICs on the rung,then all would have to be on for the rung to be true.

    If there are multiple OTEs on the rung, then all would be turned on or off based on the rung condition (true or false).

  • 8/13/2019 Plc in Detail for Process Control

    44/54

    The text above the XIC and OTE is the addressassociated with the instruction. PLC addresses may appear in many different ways depending on thePLC being used :

    -> Start_Button-> Local:2:I.Data[0].1

    -> I:020/2

    The address is used by the PLC to tell exactly which input to read or which output to command.

    I/O Addressing :

    Since a PLC will be controlling real devices down on a plant floor, it has to have some way of communicating to the correct device. All PLCs use some

    sort of method of I/O Addressingto perform this function.

    I/O addresses are a means to tie a physical I/O point to a location in PLC memory.

    An input address will represent the state of an input device, i.e. the switch is on or off.

    An output address will represent the commanded state for a device. i.e., turn the motor on or off.

    Often, a descriptive name of the device connected to the I/O point is used in addition to, or in place of the base I/O address which describes the

    physical location of the module in the rack.

    I/O Addressing vs. Data Addressing :

    I/O addresses are a means to tie a physical I/O point to a location in PLC memory. There are other addresses that do not connect to physical I/O, but

    are used to hold a value.

    Data addresses store a value used for functions like timers, counters, or calculations.

    In this example, parts on a conveyor are counted. The input, Part_detected looks at the I/O address of the actual sensor co unting the parts.

    The counter references a data address, and accumulates the counts in that location in memory.

    Each time the Part_detected switch closes, the counter adds one more count to the area of memory called part_count.

  • 8/13/2019 Plc in Detail for Process Control

    45/54

    Ladder Logic Example :

    Next, we will take a look at an actual segment of ladder logic code. The code will be the code used to control our conveyor from the first lesson. Before

    we do that, lets take a look at a few more ladder logic instructions :

    OTL - Output Latch - turns on the output and keeps it even if the rung goes false.

    OTU - Output Unlatch - turns off the output when the rung is true.

    TON - Timer On Delay - when the rung is true the timer will run.

    It will store the elapsed time in the Accum field (ac cumulator). As long as the rung remains true it will count until it reaches the preset value. If the

    preset value is hit the DN bit will go on (Don bit). When the rung goes false the timer will be reset.

    Programming a PLC Conveyor example :

    Now lets take a look at a simple program for a conveyor application.

    When a box is placed on the conveyor in front of Photoeye 1, Light 1,and Motor 1 will turn on, causing the box to move down the conveyor to the left.

    When the box passes in front of Photoeye 2, Motor 1 and Light 1 will turn off, stopping the conveyor.

  • 8/13/2019 Plc in Detail for Process Control

    46/54

    Relay Ladder Logic Example :

    Heres the program for the conveyor: The first line of code turns on the motor and the light when a box is detected by photoeye1. Likewise, the motor

    and light are turned off when photoeye2 detects the box in the second line of code.

    The third line begins a timer when the box passes by photoeye1, and if the box does not pass by photoeye2 in 30 seconds (the timer counts in

    milliseconds), the motor and light are shut off by line 4. This is the indication of a jam condition.

    PLC Addressing Examples :

    Logix Controller sample addresses :

    1. Motor_start - Binary Tag

    2. Tank_temp - Integer Tag3. Local:5:I.Data.0 - Input Tag (Local - same chassis as processor, in slot 5, is an input, data bit 0)

    PLC-5 sample addresses :

    1. B3:0/2 - Binary File

    2. N7:0 - Integer File

    3. I:012/3 - Input file (Describes: Rack#, Group, Bit)

  • 8/13/2019 Plc in Detail for Process Control

    47/54

    SLC sample addresses :

    1. B3:0/2 - Binary File2. N7:0 - Integer File

    3. I:3.0/2 - Input file (Describes: Slot.word/bit)

    Other Programming Languages :

    While ladder logic is the oldest and most popular language used in PLCs today, many other l anguages are gaining in popularity and are in wide use.Examples are :

    Sequential Function Chart(SFC).

    Function Block.

    Structured Text.

    Higher level languages such as C.

    Architecture

    Control System Architectures :

    A complete control system is made up of a combination of PLCs, networks, I/O, terminals and software. All the components work together to form a

    complete control system.

  • 8/13/2019 Plc in Detail for Process Control

    48/54

    Within a control system architecture there are many subsystems and terms used to describe them. This section will go over some of the popularly usedterms to describe parts of control systems.

    Local I/O

    Distributed I/O

    Centralized I/O

    Centralized Control

    Distributed Control

    Control System

    Data Acquisition System

    Safety System

    I/O Systems :

    I/O systems are often referred to as local or distributed :

    Localrefers to the I/O being attached directly to the controller or on the same backplane as the Controller.

    Distributedrefers to I/O which is not on the same backplane as the Controller. Distributed I/O is connected using a network.

    The distributed input module sends the inputs across the backplane to the adapter. The adapter sends them over the I/O network to the PLC(Controller).

    I/O Architectures :

    I/O architectures are made up of I/O systems. The architectures are referred to as Centralized and Distributed :

  • 8/13/2019 Plc in Detail for Process Control

    49/54

    Centralizedrefers to the I/O being located near or in the same cabinet as the processor. Wires from field devices are brought back to the I/O, andcan be quite long.

    Distributedrefers to I/O that is located near the field devices. The wires from the field devices are short. The network cable i s run out to theDistributed I/O instead of running the field wires back to the I/O.

    Systems Vs. Architectures :

    I/O systems are part of an I/O architecture :

    -> If all the I/O is located near or in the same cabinet as the processor, it is a centralized architecture. Within the centralized architecture could beeither local or distributed I/O, or both.

    I/O systems are part of an I/O architecture :

    -> If some of the I/O is located remotely from the processor it is a distributed architecture. Within the distributed architecture is distributed I/O, or both

    local and distributed I/O.

  • 8/13/2019 Plc in Detail for Process Control

    50/54

  • 8/13/2019 Plc in Detail for Process Control

    51/54

    Advantages and disadvantages of centralized control :

    Advantages :

    1. The control program is all in one place.2. Easier to troubleshoot system problems.

    3. I/O performance throughout entire system.

    Disadvantages :

    1. Programs can get quite large.

    2. Related I/O performance slower compared to distributed control.

    3. Single PLC failure shuts down entire system.

    Distributed Control :

    Distributed control refers to a control system where multiple PLC controllers share the responsibility of controlling the sys tem. The PLCs usuallycommunicate frequently with each other.

  • 8/13/2019 Plc in Detail for Process Control

    52/54

  • 8/13/2019 Plc in Detail for Process Control

    53/54

    Data Acquisition System :

    The Data Acquisition system is generally responsible for collecting data about the control system, and storing it on master computers or servers, or

    displaying it on terminals. The data is often used later for reporting or charting purposes.

    Made up of devices and networks which are responsible for acquiring data about the process. Not responsible for direct control of the process.

    The network used for data acquisition is often Ethernet. While data acquisition devices can exist directly on the control network, a gateway is oftenused to separate network traffic between the data acquisition system and the control system.

    Safety System :

    The Functionof a Safety Systemis to monitor and controlconditions on a machine or process that arehazardousin themselves or, if no actionwere taken, may give rise to hazardous situations.

    The Safety System runs in parallel with the Control System. The Control System and Safety System may share components :

    -> Focus of Control System is Throughput.-> Focus of Safety System is Protection.

    A Safety system is designed to protect :

    -> People.

    -> Environment.

    -> Machinery.

  • 8/13/2019 Plc in Detail for Process Control

    54/54

    The safety system is often referred to as safetycontrol while the PLC system controlling the devices that produce the end product is often referredto as the standardcontrol.