plate -fin-tube condenser performance

Upload: anonymous-lswzqlo

Post on 03-Jun-2018

229 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    1/255

    PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR

    REFRIGERANT R-410A AIR-CONDITIONER

    A Thesis

    Presented to

    The Academic Faculty

    By

    Monifa Fela Wright

    In Partial Fulfillmenof the Requirements for the Degree

    Master of Science in Mechanical Engineering

    Georgia Institute of Technolog

    May 2000

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    2/255

    ii

    PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR

    REFRIGERANT R-410A AIR-CONDITIONER

    Approved:

    ________________________________

    Samuel V. Shelton

    ________________________________

    James G. Hartley

    ________________________________Prateen Desa

    Date Approved____________________

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    3/255

    iii

    TABLE OF CONTENTS

    LIST OF TABLES vi

    LIST OF ILLUSTRATIONS vii

    NOMENCLATURE xii

    List of Symbols xiiList of Symbols with Greek Letters

    SUMMARY xxiii

    CHAPTER I: INTRODUCTION 1

    Research Objectives 4

    CHAPTER II: LITERATURE SURVEY 5

    Previous Studies on Variations of Heat Exchanger Geometric

    Parameters 5

    Previous Work in R-22 Replacement Refrigerants 8

    Two-Phase Flow Regime considerations in Condenser and

    Evaporator Design 13

    Two-Phase Flow Heat Transfer Correlations 16

    Two-Phase Flow Pressure Drop Correlations 19

    CHAPTER III: AIR-CONDITIONING SYSTEM AND COMPONENT

    MODELING 23

    Refrigeration Cycle 23

    System Component Models 25

    Compressor 25

    Condenser 28

    Condenser Fan 40

    Expansion Valve 40

    Evaporator 41

    Evaporator Fan 44

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    4/255

    iv

    Refrigerant Mass Inventory 45

    CHAPTER IV: REFRIGERANT-SIDE HEAT TRANSFER COEFFIECIENT

    AND PRESSURE DROP MODELS 51Single Phase Heat Transfer Coefficient 51

    Condensation Heat Transfer Coefficient 56

    Evaporative Heat Transfer Coefficient 61

    Pressure Drop in the Straight Tubes 62

    Pressure Drop In Tube Bends 70

    CHAPTER V: AIR-SIDE HEAT TRANSFER COEFFICIENT AND PRESSURE

    DROP MODELS 76Heat Transfer Coefficient 76

    Pressure Drop 81

    CHAPTER VI: DESIGN AND OPTIMIZATION METHODOLOGY 89

    Figure of Merit (Coefficient of Performance) 89

    System Design 94

    Optimization Parameters 94

    Operating Parameters 95

    Geometric Parameters 96

    Software Tools 97

    CHAPTER VII: OPTIMIZATION OF OPERATING PARAMETERS 98

    Effects of Air Velocity, Ambient Temperature, and Sub-Cool 100

    Effects on the Seasonal COP 109

    Range of Optimum Operating Parameter 111

    Effect of Operating Parameters on System Cost 111

    CHAPTER VIII: OPTIMIZATION OF GEOMETRIC DESIGN PARAMETERS

    FOR FIXED CONDENSER COIL COST 112Area Factor and Cost Facto 136

    Varying Number of Rows of Condenser Tubes 113

    Varying Condenser Tube Circuiting 115

    Varying Fin Pitch 124

    Varying Tube Diameter 137

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    5/255

    v

    Operating Costs 145

    CHAPTER IX: OPTIMIZATION OF GEOMETRIC DESIGN PARAMETERS

    FOR FIXED CONDENSER FRONTAL AREA 152Varying the Number of Rows of Condenser Tubes 153

    Varying Fin Pitch 159

    Varying Tube Diameter 163

    Operating Costs 170

    Varying the Base Configuration Frontal Area 179

    CHAPTER X: CONCLUSIONS AND RECOMMENDATIONS 185

    Conclusions 185

    List of Conclusions 188

    Recommendations 191

    Optimization Parameters and Methodology 191

    Computational Methods 193

    Refrigerant-Side Heat Transfer and Pressure Drop Models 196

    Economic Analysis 196

    APPENDIX A: AIR-CONDITIONING SYSTEM: EES PROGRAM 197

    REFERENCES 227

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    6/255

    vi

    LIST OF TABLES

    Table 2-1: List of Refrigerant R-22 Alternative Refrigerant Mixtures 12

    Table 5-1: Coefficients for the Euler Number Inverse Power Series 84

    Table 5-2: Staggered Array Geometry Factor 85

    Table 5-3: Correction Factors for Individual Rows of Tubes 87

    Table 6-1: Distribution of Cooling Load Hours, i.e. Distribution of Fractional

    Hours in Temperature Bins 91

    Table 8-1: Material Costs (London Metals Exchange, 1999) 114

    Table 8-2: Condenser Circuiting Configurations 124

    Table 8-3: Refrigerant Pressure Drop Distributions at 82F Ambient Temperature128

    Table 8-4: Seasonal COP and Area Factors for Varying Fin Pitch at Optimum Air

    Velocity and Sub-Cool for Fixed Condenser Material Cost 130

    Table 8-5: Condenser Tube Dimensions (www.aaon.com. AAOP Heating and Air-

    Conditioning Products web site) 138

    Table 8-6: Optimum Seasonal COPs and Area Factors for Varying Tube

    Diameters 141

    Table 9-1: Optimum Operating Conditions for Varying Number of Rows withFixed Condenser Frontal Area 154

    Table 9-2: Optimum Operating Conditions and Cost Factor for Varying Fin Pitch

    with Fixed Frontal Area 162

    Table 9-3: Optimum Operating Conditions and Cost Factor For Varying Tube

    Diameters with Fixed Frontal Area 166

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    7/255

    vii

    LIST OF ILLUSTRATIONS

    Figure 2-1: Typical Plate Fin-and-Tube Cross Flow Heat Exchange 5

    Figure 2-2: Horizontal Two-Phase Flow Regime Patterns 14

    Figure 3-1: The Actual Vapor-Compression Refrigeration Cycle 24

    Figure 3-2: Typical Cross Flow Heat Exchanger (fins not displayed) 30

    Figure 3-3: Hexagonal Fin Layout and Tube Array 37

    Figure 4-1: Refrigerant-Side Single Nusselt Number vs. Reynolds Numbe 55

    Figure 4-2: Condensation Heat Transfer Coefficient vs. Total Mass Flux Fo

    Refrigerant R-12 58

    Figure 7-1: Effect of Operating Conditions on Evaporator Frontal Area 99

    Figure 7-2: Effect of Air Velocity on COP for Various Ambient Temperatures and

    Optimum Degrees Sub-Cool 101

    Figure 7-3: Effect of Air Velocity on Compressor and Condenser Fan Power 13FSub-cool at 95F Ambient Temperature 103

    Figure 7-4: Effect of Ambient Temperature on COP for Varying Degrees Sub-Cool

    at 95F Ambient Temperature with an Air Velocity Over theCondenser of 8.5 ft/s 105

    Figure 7-5: Effect of Ambient Temperature on the Evaporator Capacity forVarying Degrees Sub-Cool at 95F Ambient Temperature with atOptimum Air Velocity 106

    Figure 7-6: Evaporator Capacity vs. Ambient Temperature for Various Sub-Cool

    conditions at 95F Ambient Temperature and Optimum Air Velocity108

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    8/255

    viii

    Figure 7-7: Effect of Air Velocity on the Seasonal COP for Varying Sub-cool

    Conditions 110

    Figure 8-1: Effect of Number of Rows on the Seasonal COP at Optimum AirVelocity and Varying Sub-Cool for Fixed Cost of Condenser Materials

    116

    Figure 8-2: Effect of Number of Rows on Compressor Power and Refrigerant

    Pressure Drop at Optimum Sub-Cool and Air Velocity for Fixed

    Condenser Material Cost at 82F Ambient Temperature 118

    Figure 8-3: Effect of Number of Rows of Tubes on Condenser Frontal Area fo

    Fixed Condenser Material Cost at Optimum Sub-Cool and Air Velocity

    119

    Figure 8-4: Effect of Number of Rows of Tubes on Condenser Fan Power and

    Airside Pressure Drop for Fixed Condenser Material Cost at 82FAmbient Temperature at Optimum Sub-Cool and Air Velocity 120

    Figure 8-5: Effect of Air Velocity on Seasonal COP for Varying Number of Rows at

    Optimum Sub-Cool for Fixed Condenser Material Cost 122

    Figure 8-6: Effect of Number of Rows on the Optimum Air Velocity and

    Volumetric Flow Rate of Air Over the Condenser at Optimum Sub-

    Cool for Fixed Condenser Material Cost 123

    Figure 8-7: Seasonal COP vs. Varying Condenser Tube Circuiting at Optimum

    Sub-Cool and Air Velocity for Fixed Condenser Material Cost 126

    Figure 8-8: Refrigerant-Side Pressure Drop for Various Circuiting at 82FAmbient Temperature and at Optimum Sub-Cool and Air Velocity fo

    Fixed Condenser Material Cost 127

    Figure 8-9: Seasonal COP vs. Air Velocity for Varying Fin Pitch at Fixed

    Condenser Material Cost and Optimum Sub-Cool 130

    Figure 8-10: Effect of Fin Pitch on the Seasonal COP at Optimum Sub-Cool and

    Air Velocity Over the Condenser for Fixed Condenser Material Cost131

    Figure 8-11: Air-side Pressure Drop vs. Fin Pitch for Fixed Condenser Material

    Cost at Optimum Sub-Cool and Air Velocity at 95F AmbientTemperature 133

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    9/255

    ix

    Figure 8-12: Power Requirements vs. Fin Pitch for Fixed Cost at Optimum Sub-

    Cool and Air Velocity and 95F Ambient Temperature 134

    Figure 8-13: Effect of Fin Pitch on Condenser Frontal Area at Optimum Sub-Cooland Air Velocity for Fixed Condenser Material Cost 136

    Figure 8-14: Optimum Seasonal COP for Varying Tube Diameter at Optimum Sub-

    Cool and Air Velocity for Fixed Condenser Material Cost 138

    Figure 8-15: Optimum Operating Parameters for Varying Tube Diameters at Fixed

    Condenser Material Cost 140

    Figure 8-16: Condenser Tube Length Allocation for Varying Tube Diameters at

    Optimum Air Velocity and Sub-Cool and 82 F Ambient Temperature

    for Fixed Condenser Material Cost 141

    Figure 8-17: Effect of Tube Diameter on Pressure Drop at Optimum Sub-Cool and

    Air Velocity at 82F Ambient Temperature for Fixed CondenserMaterial Cost 143

    Figure 8-18: Power Requirements for the Condenser Fan and the Compressor vs.

    Tube Diameter at Optimum Air Velocity and Sub-Cool for Fixed

    Condenser Material Cost and 82F Ambient Temperature 144

    Figure 8-19: Operating Costs vs. Area Factor For Various Geometric Parameter

    at Optimum Sub-Cool and Air Velocity with Fixed Condenser

    Material Cost 146

    Figure 8-20: Seasonal COP at Optimum Sub-Cool and Air Velocity for Varying

    Condenser Tube Circuiting with Fixed Condenser Material Cost and

    5/16Tube Outer Diameter 149

    Figure 8-21: Comparison of the Effect of the Number of Tubes per Circuit on

    Seasonal COP for 5/16and 3/8Outer Tube Diameters at Optimum

    Sub-Cool and Air Velocity with Fixed Condenser Material Cost 150

    Figure 9-1: Effect of Air Velocity Over Condenser for Varying Numbers of Rows at

    Optimum Sub-Cool with Fixed Condenser Frontal Area 154

    Figure 9-2: Effect of the Number of Rows of Tubes on the Seasonal COP at

    Optimum Sub-Cool and Air Velocity for Fixed Condenser Frontal Area

    155

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    10/255

    x

    Figure 9-3: Refrigerant-Side Pressure Drop vs. Number of Rows with Fixed

    Condenser Frontal Area for Optimum Sub-Cool and Air Velocity at 82 F Ambient Temperatur 157

    Figure 9-4: Compressor and Condenser Fan Power for Varying Number of Rows

    with Optimum Sub-Cool and Air Velocity at 82F AmbientTemperature for Fixed Condenser Frontal Area 158

    Figure 9-5: Effect of Air Velocity on Seasonal COP for Varying Fin Pitch with

    Optimum Sub-Cool for Fixed Condenser Frontal Area 160

    Figure 9-6: Effect of Fin Pitch on the Seasonal COP at Optimum Sub-Cool and Air

    Velocity for Fixed Condenser Frontal Area 161

    Figure 9-7: Effect of Air Velocity For Varying Tube Diameter at Optimum Sub-Cool for Fixed Condenser Frontal Area 164

    Figure 9-8: Effect of Tube Diameter on the Seasonal COP for Fixed Condenser

    Frontal Area at Optimum Sub-Cool and Air Velocity 165

    Figure 9-9: Refrigerant-Side Pressure vs. Tube Diameter for Fixed Frontal Area at

    82F Ambient Temperature, Optimum Sub-Cool and Air Velocity 168

    Figure 9-10: Power Requirements for Varying Tube Diameters with Fixed

    Condenser Frontal Area at 82F Ambient Temperature, OptimumSub-Cool and Air Velocity 169

    Figure 9-11: Air-Side Pressure Drop vs. Tube Diameter for Fixed Condenser

    Frontal Area at 82F Ambient Temperature, Optimum Air Velocityand Sub-Cool 171

    Figure 9-12: Operating Cost Factor vs. Cost Factor of Condenser Materials for

    Varying Geometric Parameters with Fixed Condenser Frontal Area

    and Optimum Air Velocity and Sub-Cool 172

    Figure 9-13: Seasonal COP for Varying Condenser Tube Circuiting with Fixed

    Frontal Area and 5/16Tube Outer Diameter at Optimum Sub-Cool

    and Air Velocity 175

    Figure 9-14: Comparison of the Effect of the Number of Tubes per Circuit on th

    Seasonal COP for 5/16and 3/8Outer Tube Diameters with Fixed

    Frontal Area at Optimum Sub-Cool and Air Velocity 178

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    11/255

    xi

    Figure 9-15: Operating Cost Factor vs. Condenser Material Cost Factor for

    Varying Tube Diameter and Tube circuiting at Optimum Air Velocity

    and Sub-Cool 180

    Figure 9-16: Operating Cost Factor vs. Condenser Material Cost Factor for

    Varying Geometric Parameters and Various Fixed Frontal Areas at

    Optimum Air Velocity and Sub-Cool 182

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    12/255

    xii

    NOMENCLATURE

    List of Symbols

    a = Ratio of the transverse tube spacing to the tube diameter

    ast = Stanton Number coefficient in the Kays and London (1984)

    Correlation

    ax = Axial acceleration due to gravity

    A = Total heat transfer area

    Ac = Minimum free-flow cross sectional area

    Aci = Cross sectional area of the refrigerant-side of the tube

    Afin = Total fin surface area

    Afr,con = Frontal area of condenser

    Amin = Minimum free-flow area

    Ao = Total air-side heat transfer area including the fin and tube areas

    AF = Area Factor

    B = Buoyancy Modulus

    B = Two-phase flow refrigerant side pressure drop Coefficient for a tube bend odegrees

    bst = Stanton Number coefficient in the Kays and London (1984)

    Correlation

    b = Ratio of the tube spacing normal to the air flow, to the tube diameter

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    13/255

    xiii

    C = Heat capacity

    C1 = Constant of the Hiller-Glicksman refrigerant-side pressure drop

    Correlation

    C2 = Constant of the Hiller-Glicksman refrigerant-side pressure drop

    Correlation

    C3 = Constant of the Hiller-Glicksman refrigerant-side pressure drop

    Correlation

    cp = Specific heat at constant pressure

    cp,eff = Effective specific heat at constant pressure

    cp,l = Specific heat of fluid in the liquid phase

    Cmin = Minimum heat capacity between that of the air and the refrigeran

    Cmax = Maximum heat capacity between that of the air and the refrigerant

    Cr = Ratio of the minimum heat capacity to the maximum heat capacity

    Cz = Average row correction factor

    cz = Individual row correction factor

    CF = Cost factor

    COP = Coefficient of Performance

    COPseas = Seasonal Coefficient of Perfor mance

    Cost = Cost of materials for the heat exchangers

    CostAl = Cost per pound of Aluminu

    CostCu = Cost per pound of Copper

    D = Tube diameter

    Ddepc = Depth of condenser in the direction of air flow

    Dh = Hydraulic diameter

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    14/255

    xiv

    d( ) = Differential change in ( )

    Eu = Euler number

    Eucor = Corrected Euler number

    f = Friction factor

    fGO = Friction factor for fluid flowing as vapor onl

    fLO = Friction factor for fluid flowing as liquid only

    ffin = Fin friction factor

    fri = Fraction of temperature bin hours

    Fr = Froude number

    G = Mass flux

    Gmax = Mass flux of air through the minimum flow area

    gcs = Units conversion constant

    h = Specific enthalpy

    h1 = Specific enthalpy of refrigerant entering the compressor

    h2 = Actual specific enthalpy of refrigerant exiting the compressor

    h2s = Ideal specific enthalpy of refrigerant exiting the compressor

    h2a = Specific enthalpy of refrigerant exiting the superheated portion of the

    condenser

    h2b = Specific enthalpy of refrigerant entering the sub-cooled portion of the

    condenser

    h3 = Specific enthalpy of refrigerant entering the expansion valve

    h4 = Specific enthalpy of refrigerant exiting the expansion valve

    ha = Air-side heat transfer coefficien

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    15/255

    xv

    hevap = Two-phase refrigerant-side evaporative heat transfer coefficien

    hL = Liquid phase refrigerant side heat transfer coefficien

    hr = Refrigerant-side heat transfer coefficient

    hr,SP = Single phase refrigerant-side heat transfer coefficient

    hTP = Two-phase refrigerant-side heat transfer coefficient

    i = Temperature bin number

    j = Colburn factor

    JP = Parameter for the Colburn factor calculation

    k = Thermal conductivity

    k1 = Geometry factor for staggered tube array for the air-side pressure drop

    correlation

    kl = Liquid phase thermal conductivity

    kb, = Two-phase flow refrigerant side pressure drop Coefficient for a tube bend

    odegrees

    L = Length

    l = Integral variable evaporating tube length

    Lcon,sa = Tube length of the saturated portion of the condenser tubes

    Lcon,sc = Tube length of the sub-cooled portion of the condenser tubes

    Lcon,sh = Tube length of the superheated portion of the condenser tubes

    Levap,sat = Tube length of the saturated portion of the evaporator tubes

    Levap,sh = Tube length of the superheated portion of the evaporator tubes

    Lsat = Tube length of the saturated portion of the heat exchanger tubes

    Ltot = Total tube length of the heat exchanger tubes

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    16/255

    xvi

    m = mass

    m = mass flow rate

    ma,sat = mass of flow rate of air f owing over the saturated portion of the

    condenser

    ma,tot = total mass flow rate of air flowing over the condenser

    mair = mass flow rate of air flowing over heat exchanger

    mcon,sat = mass of refrigerant in the saturated portion of the condenser

    mcon,sc = mass of refrigerant in the sub-cooled portion of the condenser

    mcon,sh = mass of refrigerant in the superheated portion of the condenser

    mes = extended surface geometric parameter

    mevap,sat = mass of refrigerant in the saturated portion of the evaporator

    mevap,sh = mass of refrigerant in the superheated portion of the evaporator

    n = Blausius coefficien

    NTU = Number of transfer units

    NuD = Nusselt number based on the tube diameter

    P = Pressure

    pr = Reduced pressure

    Prat = Ratio of the condenser saturation pressure to the evaporator saturation

    pressure

    Pe = Perimeter

    PD = Compressor piston displacemen

    Pr = Prandtl number

    Q = Rate of total heat trans erred between the refrigerant and the air

    .

    .

    .

    .

    .

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    17/255

    xvii

    q = Amount of heat per unit mass transferred between the air and the

    refrigerant

    Qave,seas = Average cooling load of the system over all cooling load hours

    qcon,sat = Amount of heat per unit mass transferred between the air and the

    refrigerant in the saturated portion of the condenser

    qcon,sc = Amount of heat per unit mass transferred between the air and the

    refrigerant in the sub-cooled portion of the condenser

    qcon,sh = Amount of heat per unit mass transferred between the air and the

    refrigerant in the superheated portion of the condenser

    qcst = Empirical constant for the Euler number correlation

    Qe = Cooling capacity of the syste

    Qmax = Maximum possible amount of heat transferred between the refrigerant and

    the air

    r = Outer radius of tube

    rb = Radius of tube bend

    Rb = Tube bend recovery length

    rcst = Empirical constant for the Euler number correlati

    Rcv,PD = Ratio of clearance volume to the piston displacemen

    Re = Equivalent radius for a hexagonal fin

    Rf,r = Refrigerant-side heat exchanger fouling factor

    Rf,a = Air-side heat exchanger fouling factor

    rr = Relative radius of tube bend

    Rw = Tube wall thermal resistance

    Re = Reynolds number

    ReD = Reynolds number based on diameter

    .

    .

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    18/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    19/255

    xix

    Vol,Al,cond = Volume of the aluminum components of the condenser (fins)

    Vol,Al,eva = Volume of the aluminum components of the evaporator (fins)

    Vol,Cu,cond = Volume of the copper co ponents of the condenser (tubes)

    Vol,Cu,evap = Volume of the copper components of the evaporator (tubes)

    wa,com = Actual compressor work per unit mass of refrigeran

    Wave,seas = Average electricity required by the system over all cooling load hours

    Wcom = Compressor power

    Wf,con = Condenser fan power

    Wf,evap = Evaporator fan power

    ws,com = Isentropic compressor work per unit mass of refrigeran

    x = Vapor quality

    xe = Vapor quality at the exit of the heat exchanger

    xi = Vapor quality at the inlet of the heat exchanger

    Xl = Transverse tube spacing

    Xt = Tube spacing normal to air flow

    Xtt = Lockhart-Martinelli Parameter

    y = Equivalent length of tube bend

    z = Number of rows of tubes

    .

    .

    .

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    20/255

    xx

    List of Symbols with Greek Letters

    = Local void fraction.

    = Coefficient of the empirical relation for determining the equivalen circular radius for hexagonal fins

    hlat = Change in the latent enthalpy

    hsens = Change in the sensible enthalpy

    htot = Change in the total enthalpy

    p = Pressure drop

    p a,con = Pressure drop on the air-side of the condenser

    p b = Refrigerant-side pressure drop inside a tube bend

    p b,LO = Refrigerant-side pressure drop inside a tube bend with all fluid flowing as a liquid

    p b,SP = Single phase refrigerant-side pressure drop inside a tube bend

    p b,TP = Two-phase refrigerant-side pressure drop inside a tube bend

    pf = Friction component of the two-phase refrigerant-side pressure drop inside a straight tube

    pfins = Air-side pressure drop due to fins

    pm = Momentum component of the two-phase refrigerant-side pressure drop inside a straight tube

    p S,SP = Single phase refrigerant-side pressure drop inside a straight tube

    p S,TP = Two-phase refrigerant-side pressure drop inside a straight tube

    p tot,ac = Total air-side pressure drop

    p tubes = Air-side pressure drop due to tubes

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    21/255

    xxi

    x = Change in quality

    = Fin effectiveness

    pr = Pipe roughness

    = Fin parameter that is a function of the equivalent circular radius of a hexagonal fin

    b2 = Physical property coefficient for the refrigerant-side pressure drop determination inside a tube bend

    c = Compressor thermal efficienc

    f = Fin efficienc

    fan,con = Condenser fan efficiency

    s = Surface efficiency

    s,a = Air-side surface efficienc

    s,r = Refrigerant-side surface efficienc

    v = Compressor volumetric efficiency

    2b,LO = Two-phase multiplier for the refrigerant side pressure drop inside tube bends

    = Viscosity

    l = Viscosity of the fluid in the liquid phase

    m = Viscosity of the fluid evaluated at the mean fluid temperature

    s = Viscosity of the fluid evaluated at the temperature of the inner tube wall surface

    TP = Two-phase fluid viscosity

    v = Viscosity of the fluid in the vapor phase

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    22/255

    xxii

    = 3.14159..

    = Angle of tube bend

    = Density

    l = Density of the fluid in the liquid phase

    v = Density of the fluid in the vapor phase

    = Ratio of the minimum free-flow area to the frontal area of the hea exchanger

    = Coefficient of the empirical relation for determining the equivalen circular radius for hexagonal fins

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    23/255

    xxiii

    SUMMARY

    Current residential air-conditioners and heat pumps use the hydrochlorofluorocarbon

    refrigerant, R-22, as the working fluid. In accordance with the Montreal Protocol, a

    production ban of all equipment utilizing R-22 will begin in 2005, and a total ban on the

    production of R-22 is also impending. A binary zeotropic mixture, R-410a, is a strong

    candidate for R-22 replacement due to its many favorable performance characteristics;

    e.g., non-flammability, high working pressures, and good cycle efficiency.

    Since R-410a has significantly higher working pressure and vapor densities than R-

    22, current air cooled finned tube condenser designs are not appropriate. The optimum

    condenser and other high-pressure-side components are expected to employ smaller

    diameter tubes, which will affect other design parameters. At this time, there is limited

    information about condenser coil design and optimization using R-410a as the working

    fluid. Furthermore, the heat transfer and friction data are also limited.

    This work includes an examination of the available refrigerant-side two-phase flow

    heat transfer and pressure drop models for refrigerants. A model based on first principles

    is used to predict the performance of a unitary air-conditioning system with refrigerant R-

    410a as the working fluid. The seasonal coefficient of performance of the air-

    conditioning system is used as the figure of merit. The primary objective of this research

    was to provide guidelines for the design and optimization of the condenser coil for tw

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    24/255

    xxiv

    distinct criteria: (1) fixed condenser frontal area (size constraint), and (2) fixed

    condenser material cost (capital cost constraint).

    This study concludes that for both design criteria, the velocity of air flow over the

    condenser ranges between 7.5 ft/s and 8.5 ft/s while the optimum sub-cooling of the

    refrigerant exiting the condenser is approximately 15F. It is also concluded that

    condensers employing tubes of smaller diameters yield the best system performance.

    Recommendations for further research into the modeling of the in-tube condensation o

    refrigerant R-410a are outlined. An exhaustive search optimization study could not be

    performed due to computational speed limitations, therefore more advanced optimization

    search techniques are also recommended for further study.

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    25/255

    1

    CHAPTER I

    INTRODUCTION

    The decade of the 1990s has been a challenging time for the Heating Ventilation Air

    Conditioning and Refrigeration (HVAC&R) industry worldwide. Due to their role in the

    destruction of the stratospheric ozone layer, provisions of the Montreal Protocol and its

    various amendments required the complete phase-out of chlorine-containing refrigerant

    such as chlorofluorocarbons (CFCs) and hydrochlorofluorocarbons (HCFCs). These

    compounds have been used extensively as refrigerants in heat pumps, air conditioners

    and refrigeration systems (Ebisu and Torikoshi, 1998). CFCs, which are characterized by

    a high ozone-depletion potential (ODP), underwent a complete production phase-out in

    the United States in 1995. Because HCFC-22 (chlorodifluoromethane) has been readily

    available, inexpensive, and less harmful to the environment than CFCs, HCFC-22 has

    been widely used in the air-conditioning and heat pump industry, especially in residential

    unitary and central air-conditioning systems, for many years (Bivens et al., 1995).

    However, the 1992 revision of the Montreal Protocol stipulated the first producti

    ceiling for HCFCs starting in 1996 (Domanski and Didion, 1993). In the United States,

    regulations published by the Environmental Protection Agency (EPA) prohibit the

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    26/255

    2

    production of HCFC-22 after 2010 except for servicing equipment produced prior to

    2010. The deadline is much earlier in some European countries (Gopalnarayanan and

    Rolotti, 1999).

    In addition, another international agreement, the Kyoto Protocol, has been initiated to

    reduce the emission of greenhouse gases (GHGs) in order to lower the potential risk o

    increased global warming. Representatives of more than 150 countries met in Kyoto,

    Japan in December of 1997. As a result of this agreement, the nations agreed to roll back

    emissions of carbon dioxide (CO2) and five other GHGs, including HFCs, to about 5.2%

    below 1990 levels by 2010. Individual emissions targets were adopted for most

    developed countries (Baxter et al., 1998). With CO2emissions tied directly to energ

    use, the pressures for further HVAC&R equipment efficiency improvements will increase

    in the early decades of the next century. At the same time, pressures from internationa

    competition have continued unabated.

    The choices for short-term and long-term replacements for R-22 are being driven by

    environmental regulations, energy standard requirements, and the cost of implementation.

    The differences in R-22 phase-out dates for the different countries seem to significantl

    influence the choice of replacement refrigerants (Gopalnarayanan and Rolotti, 1999).

    However, several programs are underway for evaluating R-22 alternatives. One such

    industry program is the Alternative Refrigerants Program (AREP) initiated by the Air

    Conditioning & Refrigeration Institute (ARI). The objective of this program is to provide

    performance data on replacement refrigerants in compressors, air-conditioning syste

    components and/or systems by conducting tests with participating member companies.

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    27/255

    3

    Throughout the evaluation process, equipment manufacturers have made requests that the

    alternatives meet several requirements. In order to meet these customer needs, a family

    of alternatives has been developed for replacing R-22 (Bivens et al., 1995).

    Unfortunately, no single-component HFCs have been discovered that have

    thermodynamic properties close to that of R-22. Consequently, this has led to the

    introduction of binary or ternary refrigerant mixtures. Several alternatives, including

    binary and ternary blends of HFCs, as well as propane, are being considered as potential

    R-22 replacement fluids (Gopalnarayanan and Rolotti, 1999). One very promising

    replacement, from the viewpoint of zero ODP and non-flammability, is the binary

    mixture, R-410a (Ebisu and Torikoshi, 1998). Note that R-410a is a near azeotropi

    mixture consisting of 50% (wt%) R-32 and 50% R-125.

    Besides the basic characteristics such as thermal properties and flammability, very

    little heat transfer and pressure drop data for R-410a is available; although Wijaya and

    Spatz (1995)have shown limited experimental data for heat transfer coefficients and

    pressure drops for R-410a inside a horizontal smooth tube. Yet, knowledge of the

    performance characteristics of air-cooled refrigerant heat exchangers with alternative

    refrigerants is of practical importance in designing air-cooled heat exchangers required in

    air-conditioning equipment. Therefore, more knowledge of the two-phase flow heat

    transfer and pressure drops that occur in refrigerant R-410a heat exchangers is needed.

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    28/255

    4

    Research Objectives

    The primary objective of this current work is to study the design and optimization o

    the operating conditions and the geometric design parameters for the air-cooled

    condenser coil of a vapor compression residential air-conditioning system wit

    refrigerant R-410a as the working fluid. The condenser and total system operating

    conditions are varied so that the systems coefficient of performance can be evaluated as

    a function of the heat exchanger design. Subsequently, it is also the intent of this stud

    that the optimization methodology detailed in this work provide guidelines to the coil

    designer for future design optimizations of this type. A secondary objective of this study

    is to investigate various two-phase flow heat transfer and pressure drop evaluation

    methods for refrigerant R-410a.

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    29/255

    5

    CHAPTER II

    LITERATURE SURVEY

    Previous Studies on Variations of Heat Exchanger Geometric Parameter

    The heat exchanger of interest for this present study is of the plate-fin-and-tube

    configuration. A schematic of a typical plate-fin-and-tube heat exchanger is shown in

    Figure 2-1.

    Figure 2-1: Typical Plate Fin-and-Tube Cross Flow Heat Exchange

    AirCrossFlow

    Air CrossFlow

    T= f(x,y)

    Refrigerant

    Flow

    Refrigerant

    Flow

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    30/255

    6

    There have been several studies on heat exchangers of this type. Wang et al. (1999)

    conducted an experimental study on the air-side performance for two specific louver fin

    patterns and their plain plate fin counterparts. This study investigated the effects of fin

    pitch, longitudinal tube spacing and tube diameter on the air-side heat transfer

    performance and friction characteristics. This study found that for plain plate fin

    configurations ranging from 8 to 14 fins per inch, the effect of longitudinal tube pitch on

    the air-side was negligible for both the air-side heat transfer and pressure drop. However,

    the heat transfer performance increased with reduced fin pitch.

    Chi et al. (1998) conducted an experimental investigation of the heat transfer and

    friction characteristics of plate fin-and tube heat exchangers having 7 mm diameter tubes.

    In this study, 8 samples of commercially available plate-fin-and-tube heat exchangers

    were tested. It was found that the effect of varying fin pitch on the air-side heat transfer

    performance and friction characteristics was negligible for 4-row coils. However for 2-

    row coils, the heat transfer performance increased with a decrease in fin pitch. This stud

    used a plate-fin-and tube heat exchanger configuration with louver fin surfaces, which are

    widely used in both automotive and residential air-conditioning systems. The transverse

    fin spacing ranged from 21 mm to 25.4 mm and longitudinal fin spacing ranged from

    12.7 mm to 19.05 mm

    Wang et al. (1998) also collected experimental data on a plate-fin-and tube hea

    exchanger configuration. They examined the effect of the number of tube rows, fin pitch,

    tube spacing, and tube diameter on heat transfer and friction characteristics. This stud

    found that the effect of fin pitch on the air-side friction pressure drop was negligibly

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    31/255

    7

    small for air-side Reynolds numbers greater than 1000. It was also found that the hea

    transfer performance was independent of fin pitch for 4-row configurations.

    Furthermore, the results indicated that reducing the tube spacing and the tube diameter

    produced an increase in the air-side heat transfer coefficient. The fin surfaces utilized in

    this study were of the louver type, with transverse fin spacing ranging from 21 mm to

    25.4 mm, and longitudinal fin spacing ranging from 12.7 mm to 19.05 mm. The

    longitudinal tube spacing investigated for this studied ranged from 15 mm to 19 mm and

    the tube diameters ranged from 7.94 mm to 9.52 mm.

    One of the earliest and most complete investigations of heat exchanger heat transfer

    and pressure drop characteristics was performed by Kays and London (1984). An

    extensive amount of experimental heat transfer and friction pressure drop data were

    complied for several different plate-fin-and-tube heat exchanger configurations as part of

    this study. However, no optimization of the heat transfer surfaces and geometry was

    performed.

    Shepherd (1956) experimentally tested the effect of various geometric variations on

    1-row plate fin-and-tube coils. He investigated the effects of varying the fin spacing, fin

    depth, tube spacing, and tube location on the heat transfer performance of the coil. The

    results of Shepherds study showed that as the fin pitch increased, the air-side hea

    transfer coefficient, for a given face velocity, increased only slightly. He also found tha

    as the fin depth and tube spacing increased, with all other variables constant, the air-side

    heat transfer coefficient decreased. Rich (1973) studied the effect of varying the fin

    spacing on the heat transfer and friction performance of multi-row heat exchanger coils.

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    32/255

    8

    Rich found that over the range from 3 to 14 fins per inch, the air-side heat transfer

    coefficient was independent of fin pitch. Neither Richs nor Shepherds investigations

    involved the optimization of the heat exchanger operating conditions and geometric

    parameters.

    All of the above studies provide valuable insight into the effects of varying different

    geometric parameters on the heat transfer and friction performance of plate-fin-tube heat

    exchangers. However none of the above works investigated the effects that varying these

    geometric parameters has on the optimization of a complete air-conditioning system

    Previous Work in R-22 Replacement Refrigerants

    Again, a major focus of this work is the study of the effect of the condenser plate-fin-

    and-tube heat exchanger design parameters on the performance of a refrigerant R-410a

    unitary air-conditioning system. However, as discussed in Chapter I, due to the

    impending ban of refrigerant R-22 production, there is a pressing need for studies on the

    performance characteristics of alternative refrigerants in air-conditioning and heat pump

    systems. Therefore a survey of the previous investigations on R-22 replacemen

    refrigerants in these systems is a very important part of this present study.

    There has been a substantial amount of work done in the area of air-conditioning and

    heat pump R-22 replacement refrigerants. Only some of the relevant studies are

    mentioned here. Radermacher and Jung (1991) conducted a simulation study of potential

    R-22 replacements in residential equipment. The coefficient of performance (COP) and

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    33/255

    9

    the seasonal performance factor (SPF) were calculated for binary and ternary substitutes

    for R-22. They found that for a ternary mixture of R-32/R-152a/R-124 with a weight

    concentration of 20 wt%/20 wt%/60 wt%, the COP was 13.7% larger and the compressor

    volumetric capacity was 23% smaller than the respective values for R-22. This stud

    found that in general, based on thermodynamic properties only, refrigerant mixtures have

    the potential to replace R-22 without a loss in efficiency. Efficiency gains are possible

    when counterflow heat exchangers are used and additional efficiency gains are possible

    when capacity modification is employed.

    Kondepudi (1993) performed experimental drop-in(unchanged system, same heat

    exchangers) testing of R-32/R-134a and R-32/R-152a blends in a two-ton split-system air

    conditioner. Five different refrigerant blends of R-32 with R-134a and R-152a were

    tested as drop-inrefrigerants against a set of R-22 baseline tests for comparison. No

    hardware changes were made except for the use of a hand-operated expansion device,

    which allowed for a drop-incomparison of the refrigerant blends. Hence, other than

    the use of a different lubricant and a hand-operated expansion valve, no form of

    optimization was performed for the refrigerant blends. Parameters measured included

    capacity, efficiency, and seasonal efficiency. The steady state energy efficiency ratio

    (EER) and seasonal efficiency energy efficiency ratio (SEER) of all the R-32/R-134a and

    R-32/R-152a blends tested were within 2% of those for a system using R-22. The 40

    wt%/60 wt% blend of R-32/R-134a performed the best in a non-optimized system.

    Fang and Nutter (1999) evaluated the effects of reversing valves on heat pump system

    performance with R-410a as the working fluid. A traditional reversing valve enables a

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    34/255

    10

    heat pump to operate in either the heating mode or cooling mode. It performs this

    function by switching the refrigerant flow path through the indoor and out door coils,

    thus changing the functions of the two heat exchangers. However, use of reversing

    valves causes increased pressure drops, refrigerant leakage from the high pressure side to

    the low pressure side, and undesired heat exchange. This study measured the overal

    effects of a reversing valve on a 3-ton heat pump system using R-410a and made

    comparisons to the same valves performance with R-22 as the working fluid. It was

    found that changing from refrigerant R-22 to R-410a resulted in an increase in mass

    leakage, but did not significantly change the effect that the reversing valve had on the

    system COP.

    Domanski and Didion (1993) evaluated the performance of nine R-22 alternatives.

    The study was conducted using a semi-theoretical model of a residential heat pump with

    a pure cross-flow representation of heat transfer in the evaporator and condenser

    (Domanski and Mclinden, 1992). The models did not include transport properties since

    they carried the implicit assumption that transport properties (and the overall heat transfer

    coefficients) are the same for the fluids studied. Simulations were conducted for drop-

    inperformance, for performance in a modified system to assess the fluidspotentials,

    and for performance in a modified system equipped with a liquid line/suction-line hea

    exchanger. The simulation results obtained from the drop-inevaluation predicted the

    performance of candidate replacement refrigerants tested in a system designed for the

    original refrigerant, with a possible modification of the expansion device. The drop-in

    model evaluations revealed significant differences in performance for high-pressure

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    35/255

    11

    fluids with respect to R-22 and indicated possible safety problems if those fluids were

    used in unmodified R-22 equipment. The simulation results obtained from the constant-

    heat-exchanger-loading evaluation corresponded to a test in a system modified

    specifically for each refrigerant to obtain the same heat flux through the evaporator and

    condenser at the design rating point. This simulation constraint ensures that the

    evaporator pressures are not affected by the different volumetric capacities of the

    refrigerants studied. The results for the modified system performance showed tha

    capacity differences were larger for modified systems than for the drop-inevaluation.

    However, none of the candidate replacement refrigerants exceeded the COP of R-22 at

    any of the test conditions.

    Bivens et al. (1995) compared experimental performance tests with ternary and binary

    mixtures in a split system residential heat pump as well as a window air-conditioner.

    This study investigated refrigerants R-407c, a ternary zeotropic mixture of 23 wt% R-32,

    25 wt% R-125 and 52 wt% R-134a, and R-410b, a near azeotropic binary mixture

    composed of 45 wt% R-32 and 55 wt% R-125 as working fluids. The heat pump used for

    the evaluations was designed to operate with R-22 and was equipped with a fin-and-tube

    evaporator with 4 refrigerant flow parallel circuits, and a spined fin condenser with 5

    circuits and 1 sub-cooling circuit. It was found that R-407c provided essentially the same

    cooling capacity as compared with R-22 with no equipment modification. R-410b

    provided a close match in cooling capacity using modified compressor and expansion

    devices. The energy efficiency ratio for R-407c versus R-22 during cooling ranged from

    0.95 to 0.97. The energy efficiency ratio for R-410b versus R-22 during cooling ranged

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    36/255

    12

    from 1.01 to 1.04. Window air-conditioner tests were conducted with R-407c in three

    window air-conditioners ranging in size from 12,000 to 18,000 Btu/hr. The result

    demonstrated equivalent capacity and energy efficiency ranging from 0.96 to 0.98

    compared with R-22.

    In summation, in the search for a replacement for refrigerant R-22 many refrigerants

    have been studied. As discussed throughout this work, many of those studied are

    refrigerant mixtures. A list of many of the refrigerant mixtures studied by the sources

    sited in this literature survey is shown in Table 2-1.

    Table 2-1: List of Refrigerant R-22 Alternative Refrigerant Mixtures

    Refrigerant Weight Percent

    R-410a R-32/50%, R-125/50%

    R-407b R-32/45%, R-125/55%

    R-407c R-32/23%, R-125/25%, R-134a/52%

    Radermacher and Jung(1991)

    R-132/20%, R-R-152a/20%, R-124/60%

    Kondepudi (1993) R-32/40%, R-134a/60%

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    37/255

    13

    As a result of many of the studies discussed in this literature survey, refrigerant R-410a

    has emerged as the primary candidate to replace R-22 in many industrial and residential

    applications. There is at least one commercially available air-conditioning system using

    R-410a as the working fluid, which is made by Carrier. Therefore, as discussed in

    Chapter I, R-410a is the refrigerant of interest for this current study.

    Two-Phase Flow Regime Considerations in Condenser and Evaporator Design

    The prediction of flow patterns is a central issue in two-phase gas-liquid flow in hea

    exchangers. Design parameters such as pressure drop and heat and mass transfer are

    strongly dependent on the flow pattern. Hence, in order to accomplish a reliable design

    of gas-liquid systems such as pipelines, boilers and condensers, ana prioriknowledge of

    the flow pattern is needed (Dvora et al., 1980).

    Figure 2-2 shows one version of the commonly recognized flow patterns for two-

    phase flow inside horizontal tubes. Description of these patterns is highly subjective, of

    course, and there is some variation among researchers in the field concerning the

    characterization of the various patterns. However, the essential situation is this: For

    ordinary fluids under ordinary process conditions, two forces control the behavior and

    distribution of the phases. These forces are gravity, always acting towards the center o

    the earth, and vapor shear forces, acting on the vapor-liquid interface in the direction o

    motion of the vapor. When gravity forces dominate (usually under conditions of low

    vapor and liquid flow rates), one obtains the stratified and wavy flow patterns shown

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    38/255

    14

    Figure 2-2: Horizontal Two-Phase Flow Regime Patterns

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    39/255

    15

    in Figure 2-2. When vapor shear forces dominate (usually at high vapor flow rates), one

    obtains the annular flow pattern (with or without entrained liquid in the core) shown on

    the diagram. When the flow rates are very high and the liquid mass fraction dominates,

    the dispersed bubble flow pattern is obtained, which is a shear-controlled flow of som

    importance in boiler design but of very limited interest in condensers. Intermediate flow

    rates correspond to patterns in which both gravitational and vapor shear forces are

    important (Bell, 1988).

    Although extensive research on flow patterns has been conducted, most of this

    research has been concentrated on either horizontal or vertical flow. For horizontal flow

    the earliest and perhaps the most durable, and best known of pattern maps for two-phase

    gas-liquid flow was proposed by Baker (1954). Taitel and Dukler (1976) proposed a

    physical model capable of predicting flow regime transition in horizontal and near

    horizontal two-phase flow.

    There are several points that need to be emphasized concerning the use of any flow

    pattern map (Bell, 1988):

    1. The definition of any two-phase flow pattern is highly subjective and differen

    observers may disagree upon exactly what they are looking at. Adding to this

    ambiguity are the various means of measuring two-phase flows and the resulting

    different criteria that are used to characterize two-phase flows.

    2. The boundaries drawn on a map as lines should be viewed as very broad

    transition regions from one well defined flow pattern to another.

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    40/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    41/255

    17

    assumed that the shear at the edge of the condensate film is directly proportional to the

    pressure drop. This shear was expressed in terms of a constant friction factor and the

    vapor velocity. Consequently, Nusselt succeeded in obtaining a correlation for the hea

    transfer coefficient, which applies if the condensate is in laminar flow. However there

    are significant discrepancies between Nusselts theory and the experimental data when

    the condensate flow becomes turbulent or when the vapor velocity is very high (Soliman

    et al., 1968).

    Soliman et al. (1968) develop a model for two-phase flow heat transfer that includes

    the contribution of the gravity, momentum and frictional terms to the wall shear stress.

    In this work, a general correlation for the condensation heat transfer coefficient in the

    annular flow regime was developed. The major assumption used in the development o

    this correlation was that the major thermal resistance is in the laminar sublayer of the

    turbulent condensate film. Experimental data for several fluids (including steam,

    refrigerant R-22, and ethanol) was used to determine empirical coefficients and

    exponents. This correlation predicts the experimental data within25%.

    Yet another semi-empirical condensation heat transfer correlation for annular flow

    was developed by Akers et al. (1959). Correlations for both the local and average values

    of the condensation heat transfer coefficient were developed in the Akers study. The

    Akers correlation predicts the experimental heat transfer coefficients generated b

    Soliman et al. (1968), within 35%.

    Traviss et al. (1973) applied the momentum and heat transfer analogy to an annular

    flow model using the von Karman universal velocity distribution to describe the liquid

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    42/255

    18

    film. Since the vapor core is very turbulent in this flow regime, radial temperature

    gradients were neglected, and the temperatures in the vapor core and at the liquid-vapor

    interface were assumed to be equal to the saturation temperature. Axial heat conduction

    and sub-cooling of the liquid film were also neglected. An order of magnitude analysis

    and non-dimensionalization of the heat transfer equations resulted in a simple

    formulation for the local heat transfer coefficient. The analysis was compared to

    experimental data for refrigerants R-12 and R-22 in a condenser tube, and the results

    were used to substantiate a general equation for forced convection condensation. Since

    the heat transfer analysis assumed the existence of annular flow, the sensitivity of this

    analysis to deviations from the annular flow regime is important. When the mass flux of

    the refrigerant vapor exceeded 500,000 lbm/hr-ft2, there is appreciable entrainment of

    liquid in the upstream portion of the condenser tube. Since the analysis assumed tha

    annular film condensation exists and that all of the liquid is on the tube wall, analytical

    predictions are below the experimental data in the dispersed or misty flow regime.

    However, the entrainment of liquid is not very large because the main resistance to hea

    transfer occurs in the laminar sublayer, and liquid removed from the turbulent zone di

    not increase the heat transfer coefficient in direct relation to the amount of liquid

    removed. Yet, according to the experimental data collected and analyzed by Singh et al.

    (1996), the mean deviation for the Traviss correlation deviates by -%40 from the data.

    The above correlations were developed for one specific flow regime (annular flow).

    However, in many instances a correlation that is applicable to more than one flow regime

    is needed. Shah (1979) developed a very simple dimensionless correlation, which he

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    43/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    44/255

    20

    considerable uncertainty. Simpler forms or firmer theoretical bases for predictive

    methods can only be achieved with a narrowing of the ranges of applicability (Beattie and

    Whalley, 1982).

    Early two-phase flow studies emphasized the development of overall pressure drop

    correlations encompassing all types of flow regimes. Furthermore, most of the

    experimental data were obtained from relatively small and short pipes (Chen and

    Spedding, 1981). Hence, no satisfactory general correlation exists. For several years,

    experimental pressure drop data have been collected for horizontal gas-liquid systems,

    and many attempts have been made to develop, from the data, general procedures for

    predicting these quantities. Errors of about 20% to 40% can be expected in pressure-drop

    prediction, and even this range is optimistic if one attempts to use the various predictive

    schemes without applying a generous measure of experience and judgment. A major

    difficulty in developing a general correlation based on statistical evaluation of data is

    deciding on a method of properly weighing the fit in each flow regime. It is difficult to

    decide, for instance, whether a correlation giving a good fit with annular flow and a poor

    fit with stratified flow is a better correlation than one giving a fair fit for both kinds o

    flow (Russell et al., 1974).

    Lockhart and Martinelli (1949) developed one of the first general correlations.

    Although various other general correlations have since been proposed the original

    Lockhart-Martinelli approach is still in many respects the best. As discussed by Chen

    and Spedding (1981), this method continues to be one of the simplest procedures for

    calculating two-phase flow pressure drop. One of the biggest advantages of thi

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    45/255

    21

    procedure is that it can be used for all flow regimes. For this flexibility, however,

    relatively low accuracy must be accepted. Detailed checks with extensive data have

    shown that the correlation overpredicts the pressure drop for the stratified flow regime

    (Baker, 1954); it is quite reasonable for slug and plug flow (Dukler et al., 1964); and for

    annular flow, it underpredicts for small diameter pipes (Perry, 1963), but overpredicts for

    larger pipes (Baker, 1954).

    Souza et al. (1993) developed a correlation for two-phase frictional pressure drop

    inside smooth tubes for pure refrigerants using the Lockhart-Martinelli parameter,Xtt (the

    square root of the ratio between the liquid only pressure drop and the vapor only pressure

    drop), the Froude number, Fr, and experimental data. The pressure drop due to

    acceleration was calculated using the Zivi (1964) equation for void fraction. A single

    tube evaporator test facility capable of measuring pressure drop and heat transfer

    coefficients inside horizontal tubes was utilized, and pressure drop data were collected.

    During the tests, the predominant flow pattern observed was annular flow. For lower

    mass fluxes and qualities, stratified-wavy, and semi-annular flow patterns were also

    observed. The resulting correlation of experimental data for refrigerants R-134a and R-

    12 for turbulent two-phase flow predicted the pressure drop within 10%.

    Chisolm (1973,1983) has published important results on pressure drop and has

    improved several correlations that predicted the frictional pressure drop during two-phase

    flow for many different fluids. According to the data collected by Souza et al. (1993),

    Chisolms two-phase flow multipliers overpredicted the experimental data for low

    qualities and slightly underpredited those for high qualities. Overall, Chisolms

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    46/255

    22

    correlation for friction pressure drop predicts the experimental values within 30% with a

    mean deviation of 14.7%.

    Jung and Radermacher (1989) developed a correlation for pressure drop during

    horizontal annular flow boiling of pure and mixed refrigerants. For this correlation, a

    two-phase multiplier based on total liquid flow was introduced for the total pressure drop

    (frictional and acceleration pressure drop) and was correlated as a function of the

    Lockhart and Martinelli parameter, Xtt. However, Jung and Radermachers correlation

    overpredicts the experimental data by an average of 29%.

    In summary, the general correlation procedures yield fair predictions of pressure drop

    for all flow regimes because they are based on a large amount of correlatable data.

    However, when these correlations are applied to systems other than those used in their

    development, or to flow over extended distances (fully established flow), predicted

    pressure drops can be in error by as much as a factor of 2. For more reliable predictions

    of pressure drop, correlations based on specific models for individual flow regimes are

    preferable, yet difficult to model analytically without concrete knowledge of the quality

    distribution throughout the tubes (Greslpvoch & Shrier, 1971).

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    47/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    48/255

    24

    Figure 3-1: The Actual Vapor-Compression Refrigeration Cycle

    SaturatedSub-cooled Superheated

    2b 2a3

    ExpansionValve

    Saturated Superheated

    4 4a

    Compressor

    Condenser

    Evaporator

    1

    2

    S

    T

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    49/255

    25

    temperature (State 2b), and then cooled to below the saturation point until only sub-

    cooled liquid is present (State 3). The high pressure liquid is then forced through the

    expansion valve into the evaporator (State 4). The refrigerant then absorbs heat from

    warm indoor air that is blown over the evaporator coils. The refrigerant is completel

    evaporated (State 4a) and heated above the saturation temperature before entering the

    compressor (State 1). The indoor air is cooled and dehumidified as it flows over the

    evaporator and returned to the living space.

    System Component Models

    Compressor

    The purpose of the compressor is to increase the working pressure of the refrigerant.

    The compressor is the major energy-consuming component of the refrigeration system,

    and its performance and reliability are significant to the overall performance of the

    HVAC system. In general there are two categories of compressors: dynamic compressors

    and displacement compressors. Dynamic compressors convert angular momentum into

    pressure rise and transfer this pressure rise to the vapor (McQuiston and Parker, 1994).

    Positive displacement compressors increase the pressure of the vapor by reducing the

    volume. For this study scroll type positive displacement compressors, which dominate

    the residential air-conditioning industry, are utilized.

    The amount of specific work (work per unit mass of refrigerant) done by an ideal

    compressor can be expressed with the following:

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    50/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    51/255

    27

    where Pratis the pressure ratioand Tratis the temperature ratio, which are defined by

    the following relationships,

    The coefficients in this correlation are based on saturated temperatures and not on the

    actual temperatures at the inlet and outlet of the compressor.

    The volumetric efficiency is another important consideration in selecting and

    modeling compressors. The volumetric efficiency is the ratio of the mass of vapor that is

    compressed to the mass of vapor that could be compressed if the intake volume were

    equal to the compressor piston displacement. The volumetric efficiency is expressed as:

    evapsat

    condsat

    ratP

    PP

    ,

    ,= (3-4)

    evapsat

    condsat

    ratTTT

    ,

    ,= (3-5)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    52/255

    28

    where vis the compressor volumetric efficiency, Rcv,pdis the ratio of clearance volume

    to the piston displacement, and v is the specific volume. The volumetric efficiency is

    also used to determine the mass flow rate of the refrigerant though the compressor, m, for

    a given compressor size by the following expression,

    where PD is the Piston Displacement (Threlkeld, 1970).

    Condenser

    The condenser is a heat exchanger that rejects heat from the refrigerant to the outside

    air. Although there are many configurations of heat exchangers, finned-tube hea

    = 1

    v

    v1

    2

    1,v pdcvR (3-6)

    2v

    PDm v

    = (3-7)

    .

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    53/255

    29

    exchangers are the type most commonly used for residential air conditioning applications.

    Refrigerant flows through the tubes, and a fan forces air between the fins and over the

    tubes. The heat exchangers used in this study are of the cross-flow, plate-fin-and-tube

    type. A schematic of this heat exchanger is shown in Figure 3-2. The plate fins are

    omitted from the schematic for simplicity.

    When the refrigerant exits the compressor, it enters the condenser as a superheated

    vapor and exits as a sub-cooled liquid. The condenser can be separated into three

    sections: superheated, saturated, and sub-cooled. The amount of heat per unit mass o

    refrigerant rejected from each section can be expressed as the difference between the

    refrigerant enthalpy at the inlet and at the outlet of each section:

    and

    ,22, ashcon hhq = (3-8)

    ,22, basatcon hhq = (3-9)

    .32, hhq bsccon = (3-10)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    54/255

    30

    Figure 3-2: Typical Cross Flow Heat Exchanger (fins not displayed)

    Horizontal

    TubeSpacing

    Air CrossFlow

    Vertical TubeSpacing

    Width

    Depth

    Height

    row 1 row 2 row 3

    1 Refrigerant FlowParallel Circuit

    3 Tubes per Circuit

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    55/255

    31

    The total heat rejected from the hot fluid, which in this case is the refrigerant, to the

    cold fluid, which is the air, is dependent on the heat exchanger effectiveness and the hea

    capacity of each fluid:

    where is the heat exchanger effectiveness; Cminis the smaller of the heat capacities o

    the hot and cold fluids, Chand Ccrespectively; Th,iis the inlet temperature of the hot

    fluid; and Tc,iis the inlet temperature of the cold fluid. The heat capacity C, is expressed

    as

    where m is the mass flow rate of fluid and cpis the specific heat of the fluid. The hea

    capacity, C, is the extensive equivalent to the specific heat, and it determines the amoun

    of heat a substance absorbs or rejects when the temperature changes.

    ( )icih TTCQ ,,min = (3-11)

    pcmC =(3-12)

    .

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    56/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    57/255

    33

    mass flow is separated into a number of discrete tubes and does not mix between fluids.

    Furthermore, the plates of the heat exchanger prevent mixing of the air flowing over the

    fins. Therefore, air at one end of the heat exchanger will not necessarily be the same

    temperature as the air at the other end. For a cross flow heat exchanger with both fluids

    unmixed, the effectiveness can be related to the number of transfer units (NTU) with the

    following expression (Incropera & DeWitt, 1996):

    where Cris the heat capacity ratio,

    ( ) ( )( )[ ] ,1exp1exp1 78.022.0

    = NTUCNTU

    Cr

    r

    (3-15)

    .max

    min

    C

    CCr= (3-16)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    58/255

    34

    In the saturated portion of the condenser, the heat capacity on the refrigerant side

    approaches infinity and the heat capacity ratio, Crgoes to zero. When Cris zero, the

    effectiveness for any heat exchanger configuration is expressed as

    The NTU is a function of the overall heat transfer coefficient, U, and is defined as

    where A is the heat transfer area upon which the overall heat transfer coefficient, U, is

    based. The overall heat transfer coefficient accounts for the total thermal resistance

    between the two fluids and is expressed as follows.

    ( ).exp1 NTU= (3-17)

    ,minC

    UA

    NTU=(3-18)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    59/255

    35

    where Rf,(a or r)is the fouling factor, Rwis the wall thermal resistance, s(a or r)is the

    surface efficiency, andh is the heat transfer coefficient. There are no fins on the

    refrigerant side of the condensing tubes; therefore, the refrigerant side surface efficiency

    is 1. Neglecting the wall thermal resistance, Rw(this value is usually 3 orders o

    magnitude lower than the other resistances), and the fouling factors, R f,(a or r), the overall

    heat transfer coefficient reduces to:

    The methodology for determining the refrigerant and air-side heat transfer coefficients

    are discussed Chapter IV and Chapter V, respectively.

    To determine the overall surface efficiency for a finned tube heat exchanger, it is firs

    necessary to determine the efficiency of the fins as if they existed alone. For a plate-fin-

    ,111

    ,,

    "

    ,

    ,

    "

    ,

    , rrrsrrs

    rf

    w

    aas

    af

    aaas AhA

    RR

    A

    R

    AhUA ++++= (3-19)

    .11

    1

    ,

    +=

    rraaas AhAhUA

    (3-20)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    60/255

    36

    and-tube heat exchanger with multiple rows of staggered tubes, the plates can be evenly

    divided into hexagonal shaped fins as shown in Figure 3-3. Schmidt (1945) analyzed

    hexagonal fins and determined that they can be treated as circular fins by replacing the

    outer radius of the fin with an equivalent radius. The empirical relation for the equivalen

    radius is given by

    where r is the outside tube radius. The coefficients and are defined as

    and

    ( ) ,3.027.1 2/1= rRe (3-21)

    r

    Xt

    2=

    (3-22)

    ,4

    1

    2/12

    2

    += tl

    t

    XXX

    (3-23)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    61/255

    37

    Figure 3-3: Hexagonal Fin Layout and Tube Array

    Xt Tube Spacing

    Normal to Air

    Flo

    Air Flow

    Transverse Tube

    Spacing

    Xl

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    62/255

    38

    where Xlis the tube spacing in the direction parallel to the direction of air flow, and X tis

    the tube spacing normal to the direction of air flow.

    Once the equivalent radius has been determined, the equations for standard circular

    fins can be used. For this study, the length of the fins is much greater than the fin

    thickness. Therefore, the standard extended surface parameter, escan be expressed as,

    where hais the air-side heat transfer coefficient, k is the thermal conductivity of the fin

    material, Pe is the fin perimeter, cis the fin cross sectional area, and t is the thickness o

    the fin. For circular tubes, a parameter can be defined as

    ,2Pe

    2/12/1

    =

    =

    kt

    h

    kA

    hm a

    ces (3-24)

    .ln35.011

    +

    =r

    R

    r

    R ee (3-25)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    63/255

    39

    The fin efficiency, f, for a circular fin is a function of es, Re, and f, and can be

    expressed as

    The total surface efficiency of the fin, sis therefore expressed as

    where Afinis the total fin surface area, Aois the total air-side surface area of the tube and

    the fins.

    ( ).

    tanh

    ees

    ees

    fRm

    Rm= (3-26)

    ( ),11 fo

    fin

    sA

    A = (3-27)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    64/255

    40

    Condenser Fan

    Natural convection is not sufficient to attain the heat transfer rate required on the air-

    side of the condenser used in a reasonably sized residential air-conditioning system.

    Therefore a fan must be employed to maintain the airflow at a sufficient rate of speed.

    Although much of the power consumed by the total system is due to the compressor, the

    condenser fan also requires a significant amount of power. The power required by the

    fan is directly related to the air-side pressure drop across the condenser and to the

    velocity of air across the condenser:

    where Va,conis the air velocity over the face of the condenser, Pa,conis the air-side

    pressure drop over the condenser, Afr,conis the frontal area of the condenser, and fan,conis

    the condenser fan efficiency. Calculations for the air-side pressure drop are discussed in

    Chapter V.

    Expansion Valve

    The expansion valve is used to control the refrigerant flow through the system

    Under normal operating conditions, the expansion valve opens and closes in order to

    confan

    confrconacona

    conf

    APVW

    ,

    ,,,

    ,

    = (3-28)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    65/255

    41

    maintain a fixed amount of superheat in the exit of the evaporator. In this study, the

    superheat will be maintained at the typical 10F. Because the expansion valve can only

    pass a limited volume of refrigerant, it cannot maintain the specified superheat at the

    evaporator exit if the refrigerant is not completely condensed into liquid. If incomplete

    condensation in the condenser occurs, the vapor refrigerant backs up behind the

    expansion valve and the pressure increases until the refrigerant is fully condensed. As a

    result, the expansion valve cannot regulate the refrigerant mass flow rate, and canno

    maintain a fixed superheat at the evaporator exit. The energy equation shows that the

    enthalpy is constant across the expansion valve.

    Evaporator

    The purpose of the evaporator is to transfer heat from the room air in order to lower

    its temperature and humidity. Because the refrigerant enters the evaporator as a liquid-

    vapor mixture, it is only divided into saturated and superheated sections. No sub-cooled

    section is necessary. The analysis of the thermodynamic parameters of the evaporator is

    43 hh =(3-29)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    66/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    67/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    68/255

    44

    where cpis the specific heat ratio for dry air and cp,effis the effective specific heat. To

    maintain indoor humidity, the latent heat accounts for approximately 25% of the tota

    enthalpy change of the air flowing over an evaporator. The effective specific heat can

    thus be expressed in terms of the specific heat for dry air only,

    Evaporator Fan

    Because the evaporator is not the primary focus of this study, introducing wet coils

    would present unwelcome complications in the overall analysis. In addition to affecting

    the heat transfer, wet coils also have an effect on the air-side pressure drop. Although

    there are correlations available for determining the pressure drop over wet coils, they are

    cumbersome to use and again, the evaporator is not the primary focus of this

    investigation.

    After the air flows over the evaporator, it enters a series of ducts that then return the

    air back inside the living space. The power required by the evaporator fan depends on

    the losses in these ducts and can vary from configuration to configuration. Therefore, the

    .33.1

    75.0

    25.0, p

    tot

    senslatpeffp c

    h

    h

    T

    hcc =

    += (3-33)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    69/255

    45

    default power requirement used by the Air-conditioning and Refrigeration Institute (ARI,

    1989) of 365 Watts per 1000 ft3/minute of air will be used.

    Refrigerant Mass Inventory

    The degrees of sub-cooling at the condenser exit are controlled by the syste

    operating conditions and the quantity of refrigerant mass in the system, as is discussed

    further in Chapter VI. The mass of refrigerant in the tubes connecting the components is

    neglected. Since the compressor contains only vapor, the mass of refrigerant in the

    compressor is also neglected. Therefore the total mass of the system includes the mass o

    refrigerant in the sub-cooled, saturated, and superheated portions of the condenser, and in

    the saturated and superheated portions of the evaporator.

    The following text outlines the procedure for finding the refrigerant mass in the

    saturated portion of the evaporator. The same procedure is also used to determine the

    mass of refrigerant in the saturated portion of the condenser, however the boundary

    conditions are different

    The mass of refrigerant can be expressed as

    .v

    =L

    cidlAm (3-34)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    70/255

    46

    where, Aci is the cross sectional area of the refrigerant-side of the tube, and v is the

    specific volume, which at saturated conditions is a function of quality expressed as

    The boundary conditions for the saturated portion of the evaporator are

    and

    ( ) ( ) .v1vv vl xx += (3-35)

    ( ) ixlx == 0(3-36)

    1)( ==Llx (3-37)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    71/255

    47

    where lis integral variable evaporating tube length and L is the total evaporating tube

    length. Using the boundary conditions and assuming the quality varies linearly with tube

    length, the following expression results

    Substituting (3-38) into (3-35) yields an expression for the specific volume as a functi

    of length,

    For a uniform cross sectional area, substituting (3-39) into (3-34) yields

    ( ) .1

    ii xl

    L

    xlx +

    = (3-38)

    ( ) ( ) ( ).vv1

    vvvv lvi

    lvilL

    xlxl

    ++= (3-39)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    72/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    73/255

    49

    The mass of refrigerant in the superheated portions of the condenser and evaporator are

    expressed simply as:

    and

    Finally, the mass of refrigerant in the sub-cooled section of the condenser is expressed as

    shconcivshcon LAm ,, = (3-43)

    .,, shevapcivshevap LAm = (3-44)

    ( )( ) ( )

    .

    vvv

    vln

    vv1

    ,,

    +

    =llvi

    v

    lvi

    evapsatci

    evapsat

    xx

    LAm

    (3-42)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    74/255

    50

    .,, scconcivsccon LAm = (3-45)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    75/255

    51

    CHAPTER IV

    REFRIGERANT SIDE HEAT TRANSFER COEFFICIENT AND PRESSURE

    DROP MODELS

    Single Phase Heat Transfer Coefficient

    For a constant surface heat flux for single phase laminar flow, the Nusselt number can

    be approximated by the following expression.

    In the turbulent region, however, there are a number of expressions available for the

    Nusselt number. One of the more commonly used correlations for turbulent flow is the

    Dittus-Boelter equation. This correlation is valid for fully developed flow in circular

    36.4=DNu (4-1)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    76/255

    52

    tubes with moderate temperature variations (Incropera & DeWitt, 1996). For refrigeran

    cooling in a condenser, the Dittus-Boelter equation is expressed as

    This mathematical relation has been confirmed by experimental data for the following

    conditions:

    0.7 Pr 160

    ReD10,000

    L/D 10

    In the sub-cooled portion of the condenser in this study, the temperature difference at the

    inlet and exit is usually less than 20F, and the moderate temperature variation

    assumption is valid. However in the superheated portion of the condenser, the inlet and

    exit temperatures can differ by as much as 90F. Therefore, the temperature difference

    between the air flowing over the tubes and the refrigerant flowing inside the tubes is

    large. This causes the temperature difference between the inner surface of the tubes and

    the refrigerant to also be large in the superheated portion of the condenser. Thus, under

    these conditions, the Dittus-Boelter equation is less accurate.

    .PrRe023.0 3.08.0DDNu = (4-2)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    77/255

    53

    Yet another Nusselt number correlation for single phase turbulent flow has been

    developed by Sieder and Tate(1936). This correlation was developed for a large range of

    property variations based on the mean fluid temperature and the wall surface temperature,

    and is expressed as

    where all properties except for sare evaluated at the mean fluid temperature, and sis

    evaluated at the temperature of the inner tube wall surface. Again, since this model is

    developed for a large range of property variations, it is valid for larger temperature

    differences within the fluid flowing inside the tube.

    Kays and London (1984) have also developed a heat transfer correlation for single

    phase turbulent flow. This correlation was developed using empirical data taken from a

    variety of refrigerants in circular heat exchanger tubes under several thermodynamic

    conditions. Unlike most heat transfer correlations, Kays and London have developed the

    equations for the transition region between laminar and turbulent flow. The correlation is

    expressed as:

    ,PrRe027.0

    14.0

    3/18.0

    = sm

    DDNu

    (4-3)

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    78/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    79/255

    55

    Figure 4-1: Refrigerant-Side Single Nusselt Number vs. Reynolds Numbe

    0

    20

    40

    60

    80

    100

    120

    140

    0 5000 10000 15000 20000 25000

    Reynolds Number

    Nusse

    ltNumb

    er

    Laminar, ConstantHeat Flux

    Kays and Londo

    Dittus Boelter

    Sieder and Tate

    TransitionLaminar

    Turbulent

    Dittus-Boelter

    Sieder & Tate

    Kays &

    Londo

    Kays &

    Londo

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    80/255

    56

    tube diameter of 0.2885 in, with refrigerant R-410a flowing as superheated vapor at a

    mean temperature of 140 F and a pressure of 395 psia (conditions typically found in the

    superheated portion of the condenser for this study). In the turbulent region, the value o

    the Nusselt number calculated using the Kays and London correlation is on average about

    70% higher than the Nusselt numbers calculated using both the Dittus-Boelter and the

    Sieder and Tate correlations. This is due to the fact that both the Sieder and Tate and

    Dittus-Boelter equations have assumed a smooth pipe. However the Kays and London

    correlation was developed with experimental data taken from actual heat exchangers

    which employ tubes with rougher surfaces. Because the Kays and London relation is

    based on experimental data taken directly from heat exchangers similar to those

    investigated in this work, and because the issue of the transition from laminar to turbulent

    flow has been addressed, this correlation is used.

    Condensation Heat Transfer

    As discussed in Chapter II, the hea transfer coefficient in two-phase flow is

    dependent on the flow regimes that are present. Annular flow is generally assumed to be

    the dominant flow pattern existing over most of the condensing length during bot

    horizontal and vertical condensing inside tubes (Soliman et al., 1968). Baker (1954) and

    Gouse (1964) have derived flow pattern maps from numerous data, and have verified the

    validity of this assumption. In most cases, annular flow is established soon after

    condensation begins, and continues to very low quality. For horizontal condensing,

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    81/255

    57

    gravity-induced stratification exists at low quality, but this usually occupies only a small

    portion of the overall condensing length (Soliman et al., 1968). Annular flow is a

    particularly important flow pattern since for a wide range of pressure and flow

    conditions, and it occurs over a major part of the mass quality range, from 0.1 up to unity

    (Collier & Thome, 1996). Therefore, heat transfer correlations developed for annular

    flow, in addition to a correlation developed for all flow regimes, are considered for use in

    this present study.

    Two-phase flow heat transfer correlations developed by Traviss et al. (1973), Akers e

    al. (1959), and Shah (1979) are evaluated for this current work. The correlations o

    Akers et al. and Traviss et al. were developed for annular flow, while the Shah correlation

    is proposed to be applicable to all flow regimes. Figure 4-2 shows the condensation hea

    transfer coefficients for refrigerant R-12 calculated from the correlations of Shah, Traviss

    et al., and Akers et al., versus the total mass flux. The figure also shows experimenta

    condensation heat transfer coefficients for refrigerant R-12 taken from experimental data

    collected by Eckels and Pate (1991). Using the parameters designated by the Baker

    (1954) flow regime map, it is determined that for the experimental conditions of Eckels

    and Pate, a slug flow pattern exists for mass fluxes between 100 and 250 kg/m2-s, and an

    annular flow regime exists for mass fluxes greater than 250 kg/ 2-s. As Figure 4-2

    shows, the Traviss correlation overpredicts the experimental data for the entire range o

    mass fluxes shown. The Akers and Shah correlations slightly underpredict the

    experimental values for relatively low mass fluxes and slightly overpredict the

    experimental data at higher mass fluxes (annular flow).

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    82/255

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    83/255

    59

    The fact that the Traviss correlation greatly overpredicts the experimental data for

    when the flow regime is annular is surprising since this correlation was developed for

    annular flow. The Akers correlation predicts the experimental data to within an average

    14.3% while the Shah correlation predicts the experimental data to within an average o

    14.7%. Therefore the Shah and Akers correlations are in good agreement with each

    other, and are both more accurate than the Traviss correlation for the conditions

    investigated.

    Using the parameters of the Baker (1954) flow regime map, and the typical operating

    conditions of the condenser studied in this present work (mass fluxes approximately

    greater than or equal to 400 kg/ 2-s or 300,000 lbm/ft2-hr), it is determined that the

    dominant flow regime is indeed annular. However, this study also finds that for low

    qualities, stratified-wavy flow exists. As a result, the use of a general correlation that is

    valid for more than one flow regime is advantageous for the work of this investigation.

    Therefore, the correlations developed by Akers et al. and Traviss et al., are not used.

    Hence, the two-phase flow heat transfer correlation developed by Shah is used for this

    investigation.

    The two-phase flow heat transfer model developed by Shah is a simple correlation

    that has been verified over a large range of experimental data. In fact, experimental data

    from over 20 different researchers has been used in its development. The model has a

    mean deviation of about 15% and has been verified for many different fluids, tube sizes,

    and tube orientations.

  • 8/12/2019 Plate -Fin-tube Condenser Performance

    84/255

    60

    For this model, at any given quality, the two-phase heat transfer coefficient is defined

    as:

    wherehTPis the two-phase flow heat transfer coefficient, x is the quality,hLis the liquid

    only heat transfer coefficient, and p ris the reduced pressure. By integrating the

    expression (4-6) over the length of the tube, the mean