plate -fin-tube condenser performance
TRANSCRIPT
-
8/12/2019 Plate -Fin-tube Condenser Performance
1/255
PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR
REFRIGERANT R-410A AIR-CONDITIONER
A Thesis
Presented to
The Academic Faculty
By
Monifa Fela Wright
In Partial Fulfillmenof the Requirements for the Degree
Master of Science in Mechanical Engineering
Georgia Institute of Technolog
May 2000
-
8/12/2019 Plate -Fin-tube Condenser Performance
2/255
ii
PLATE-FIN-AND-TUBE CONDENSER PERFORMANCE AND DESIGN FOR
REFRIGERANT R-410A AIR-CONDITIONER
Approved:
________________________________
Samuel V. Shelton
________________________________
James G. Hartley
________________________________Prateen Desa
Date Approved____________________
-
8/12/2019 Plate -Fin-tube Condenser Performance
3/255
iii
TABLE OF CONTENTS
LIST OF TABLES vi
LIST OF ILLUSTRATIONS vii
NOMENCLATURE xii
List of Symbols xiiList of Symbols with Greek Letters
SUMMARY xxiii
CHAPTER I: INTRODUCTION 1
Research Objectives 4
CHAPTER II: LITERATURE SURVEY 5
Previous Studies on Variations of Heat Exchanger Geometric
Parameters 5
Previous Work in R-22 Replacement Refrigerants 8
Two-Phase Flow Regime considerations in Condenser and
Evaporator Design 13
Two-Phase Flow Heat Transfer Correlations 16
Two-Phase Flow Pressure Drop Correlations 19
CHAPTER III: AIR-CONDITIONING SYSTEM AND COMPONENT
MODELING 23
Refrigeration Cycle 23
System Component Models 25
Compressor 25
Condenser 28
Condenser Fan 40
Expansion Valve 40
Evaporator 41
Evaporator Fan 44
-
8/12/2019 Plate -Fin-tube Condenser Performance
4/255
iv
Refrigerant Mass Inventory 45
CHAPTER IV: REFRIGERANT-SIDE HEAT TRANSFER COEFFIECIENT
AND PRESSURE DROP MODELS 51Single Phase Heat Transfer Coefficient 51
Condensation Heat Transfer Coefficient 56
Evaporative Heat Transfer Coefficient 61
Pressure Drop in the Straight Tubes 62
Pressure Drop In Tube Bends 70
CHAPTER V: AIR-SIDE HEAT TRANSFER COEFFICIENT AND PRESSURE
DROP MODELS 76Heat Transfer Coefficient 76
Pressure Drop 81
CHAPTER VI: DESIGN AND OPTIMIZATION METHODOLOGY 89
Figure of Merit (Coefficient of Performance) 89
System Design 94
Optimization Parameters 94
Operating Parameters 95
Geometric Parameters 96
Software Tools 97
CHAPTER VII: OPTIMIZATION OF OPERATING PARAMETERS 98
Effects of Air Velocity, Ambient Temperature, and Sub-Cool 100
Effects on the Seasonal COP 109
Range of Optimum Operating Parameter 111
Effect of Operating Parameters on System Cost 111
CHAPTER VIII: OPTIMIZATION OF GEOMETRIC DESIGN PARAMETERS
FOR FIXED CONDENSER COIL COST 112Area Factor and Cost Facto 136
Varying Number of Rows of Condenser Tubes 113
Varying Condenser Tube Circuiting 115
Varying Fin Pitch 124
Varying Tube Diameter 137
-
8/12/2019 Plate -Fin-tube Condenser Performance
5/255
v
Operating Costs 145
CHAPTER IX: OPTIMIZATION OF GEOMETRIC DESIGN PARAMETERS
FOR FIXED CONDENSER FRONTAL AREA 152Varying the Number of Rows of Condenser Tubes 153
Varying Fin Pitch 159
Varying Tube Diameter 163
Operating Costs 170
Varying the Base Configuration Frontal Area 179
CHAPTER X: CONCLUSIONS AND RECOMMENDATIONS 185
Conclusions 185
List of Conclusions 188
Recommendations 191
Optimization Parameters and Methodology 191
Computational Methods 193
Refrigerant-Side Heat Transfer and Pressure Drop Models 196
Economic Analysis 196
APPENDIX A: AIR-CONDITIONING SYSTEM: EES PROGRAM 197
REFERENCES 227
-
8/12/2019 Plate -Fin-tube Condenser Performance
6/255
vi
LIST OF TABLES
Table 2-1: List of Refrigerant R-22 Alternative Refrigerant Mixtures 12
Table 5-1: Coefficients for the Euler Number Inverse Power Series 84
Table 5-2: Staggered Array Geometry Factor 85
Table 5-3: Correction Factors for Individual Rows of Tubes 87
Table 6-1: Distribution of Cooling Load Hours, i.e. Distribution of Fractional
Hours in Temperature Bins 91
Table 8-1: Material Costs (London Metals Exchange, 1999) 114
Table 8-2: Condenser Circuiting Configurations 124
Table 8-3: Refrigerant Pressure Drop Distributions at 82F Ambient Temperature128
Table 8-4: Seasonal COP and Area Factors for Varying Fin Pitch at Optimum Air
Velocity and Sub-Cool for Fixed Condenser Material Cost 130
Table 8-5: Condenser Tube Dimensions (www.aaon.com. AAOP Heating and Air-
Conditioning Products web site) 138
Table 8-6: Optimum Seasonal COPs and Area Factors for Varying Tube
Diameters 141
Table 9-1: Optimum Operating Conditions for Varying Number of Rows withFixed Condenser Frontal Area 154
Table 9-2: Optimum Operating Conditions and Cost Factor for Varying Fin Pitch
with Fixed Frontal Area 162
Table 9-3: Optimum Operating Conditions and Cost Factor For Varying Tube
Diameters with Fixed Frontal Area 166
-
8/12/2019 Plate -Fin-tube Condenser Performance
7/255
vii
LIST OF ILLUSTRATIONS
Figure 2-1: Typical Plate Fin-and-Tube Cross Flow Heat Exchange 5
Figure 2-2: Horizontal Two-Phase Flow Regime Patterns 14
Figure 3-1: The Actual Vapor-Compression Refrigeration Cycle 24
Figure 3-2: Typical Cross Flow Heat Exchanger (fins not displayed) 30
Figure 3-3: Hexagonal Fin Layout and Tube Array 37
Figure 4-1: Refrigerant-Side Single Nusselt Number vs. Reynolds Numbe 55
Figure 4-2: Condensation Heat Transfer Coefficient vs. Total Mass Flux Fo
Refrigerant R-12 58
Figure 7-1: Effect of Operating Conditions on Evaporator Frontal Area 99
Figure 7-2: Effect of Air Velocity on COP for Various Ambient Temperatures and
Optimum Degrees Sub-Cool 101
Figure 7-3: Effect of Air Velocity on Compressor and Condenser Fan Power 13FSub-cool at 95F Ambient Temperature 103
Figure 7-4: Effect of Ambient Temperature on COP for Varying Degrees Sub-Cool
at 95F Ambient Temperature with an Air Velocity Over theCondenser of 8.5 ft/s 105
Figure 7-5: Effect of Ambient Temperature on the Evaporator Capacity forVarying Degrees Sub-Cool at 95F Ambient Temperature with atOptimum Air Velocity 106
Figure 7-6: Evaporator Capacity vs. Ambient Temperature for Various Sub-Cool
conditions at 95F Ambient Temperature and Optimum Air Velocity108
-
8/12/2019 Plate -Fin-tube Condenser Performance
8/255
viii
Figure 7-7: Effect of Air Velocity on the Seasonal COP for Varying Sub-cool
Conditions 110
Figure 8-1: Effect of Number of Rows on the Seasonal COP at Optimum AirVelocity and Varying Sub-Cool for Fixed Cost of Condenser Materials
116
Figure 8-2: Effect of Number of Rows on Compressor Power and Refrigerant
Pressure Drop at Optimum Sub-Cool and Air Velocity for Fixed
Condenser Material Cost at 82F Ambient Temperature 118
Figure 8-3: Effect of Number of Rows of Tubes on Condenser Frontal Area fo
Fixed Condenser Material Cost at Optimum Sub-Cool and Air Velocity
119
Figure 8-4: Effect of Number of Rows of Tubes on Condenser Fan Power and
Airside Pressure Drop for Fixed Condenser Material Cost at 82FAmbient Temperature at Optimum Sub-Cool and Air Velocity 120
Figure 8-5: Effect of Air Velocity on Seasonal COP for Varying Number of Rows at
Optimum Sub-Cool for Fixed Condenser Material Cost 122
Figure 8-6: Effect of Number of Rows on the Optimum Air Velocity and
Volumetric Flow Rate of Air Over the Condenser at Optimum Sub-
Cool for Fixed Condenser Material Cost 123
Figure 8-7: Seasonal COP vs. Varying Condenser Tube Circuiting at Optimum
Sub-Cool and Air Velocity for Fixed Condenser Material Cost 126
Figure 8-8: Refrigerant-Side Pressure Drop for Various Circuiting at 82FAmbient Temperature and at Optimum Sub-Cool and Air Velocity fo
Fixed Condenser Material Cost 127
Figure 8-9: Seasonal COP vs. Air Velocity for Varying Fin Pitch at Fixed
Condenser Material Cost and Optimum Sub-Cool 130
Figure 8-10: Effect of Fin Pitch on the Seasonal COP at Optimum Sub-Cool and
Air Velocity Over the Condenser for Fixed Condenser Material Cost131
Figure 8-11: Air-side Pressure Drop vs. Fin Pitch for Fixed Condenser Material
Cost at Optimum Sub-Cool and Air Velocity at 95F AmbientTemperature 133
-
8/12/2019 Plate -Fin-tube Condenser Performance
9/255
ix
Figure 8-12: Power Requirements vs. Fin Pitch for Fixed Cost at Optimum Sub-
Cool and Air Velocity and 95F Ambient Temperature 134
Figure 8-13: Effect of Fin Pitch on Condenser Frontal Area at Optimum Sub-Cooland Air Velocity for Fixed Condenser Material Cost 136
Figure 8-14: Optimum Seasonal COP for Varying Tube Diameter at Optimum Sub-
Cool and Air Velocity for Fixed Condenser Material Cost 138
Figure 8-15: Optimum Operating Parameters for Varying Tube Diameters at Fixed
Condenser Material Cost 140
Figure 8-16: Condenser Tube Length Allocation for Varying Tube Diameters at
Optimum Air Velocity and Sub-Cool and 82 F Ambient Temperature
for Fixed Condenser Material Cost 141
Figure 8-17: Effect of Tube Diameter on Pressure Drop at Optimum Sub-Cool and
Air Velocity at 82F Ambient Temperature for Fixed CondenserMaterial Cost 143
Figure 8-18: Power Requirements for the Condenser Fan and the Compressor vs.
Tube Diameter at Optimum Air Velocity and Sub-Cool for Fixed
Condenser Material Cost and 82F Ambient Temperature 144
Figure 8-19: Operating Costs vs. Area Factor For Various Geometric Parameter
at Optimum Sub-Cool and Air Velocity with Fixed Condenser
Material Cost 146
Figure 8-20: Seasonal COP at Optimum Sub-Cool and Air Velocity for Varying
Condenser Tube Circuiting with Fixed Condenser Material Cost and
5/16Tube Outer Diameter 149
Figure 8-21: Comparison of the Effect of the Number of Tubes per Circuit on
Seasonal COP for 5/16and 3/8Outer Tube Diameters at Optimum
Sub-Cool and Air Velocity with Fixed Condenser Material Cost 150
Figure 9-1: Effect of Air Velocity Over Condenser for Varying Numbers of Rows at
Optimum Sub-Cool with Fixed Condenser Frontal Area 154
Figure 9-2: Effect of the Number of Rows of Tubes on the Seasonal COP at
Optimum Sub-Cool and Air Velocity for Fixed Condenser Frontal Area
155
-
8/12/2019 Plate -Fin-tube Condenser Performance
10/255
x
Figure 9-3: Refrigerant-Side Pressure Drop vs. Number of Rows with Fixed
Condenser Frontal Area for Optimum Sub-Cool and Air Velocity at 82 F Ambient Temperatur 157
Figure 9-4: Compressor and Condenser Fan Power for Varying Number of Rows
with Optimum Sub-Cool and Air Velocity at 82F AmbientTemperature for Fixed Condenser Frontal Area 158
Figure 9-5: Effect of Air Velocity on Seasonal COP for Varying Fin Pitch with
Optimum Sub-Cool for Fixed Condenser Frontal Area 160
Figure 9-6: Effect of Fin Pitch on the Seasonal COP at Optimum Sub-Cool and Air
Velocity for Fixed Condenser Frontal Area 161
Figure 9-7: Effect of Air Velocity For Varying Tube Diameter at Optimum Sub-Cool for Fixed Condenser Frontal Area 164
Figure 9-8: Effect of Tube Diameter on the Seasonal COP for Fixed Condenser
Frontal Area at Optimum Sub-Cool and Air Velocity 165
Figure 9-9: Refrigerant-Side Pressure vs. Tube Diameter for Fixed Frontal Area at
82F Ambient Temperature, Optimum Sub-Cool and Air Velocity 168
Figure 9-10: Power Requirements for Varying Tube Diameters with Fixed
Condenser Frontal Area at 82F Ambient Temperature, OptimumSub-Cool and Air Velocity 169
Figure 9-11: Air-Side Pressure Drop vs. Tube Diameter for Fixed Condenser
Frontal Area at 82F Ambient Temperature, Optimum Air Velocityand Sub-Cool 171
Figure 9-12: Operating Cost Factor vs. Cost Factor of Condenser Materials for
Varying Geometric Parameters with Fixed Condenser Frontal Area
and Optimum Air Velocity and Sub-Cool 172
Figure 9-13: Seasonal COP for Varying Condenser Tube Circuiting with Fixed
Frontal Area and 5/16Tube Outer Diameter at Optimum Sub-Cool
and Air Velocity 175
Figure 9-14: Comparison of the Effect of the Number of Tubes per Circuit on th
Seasonal COP for 5/16and 3/8Outer Tube Diameters with Fixed
Frontal Area at Optimum Sub-Cool and Air Velocity 178
-
8/12/2019 Plate -Fin-tube Condenser Performance
11/255
xi
Figure 9-15: Operating Cost Factor vs. Condenser Material Cost Factor for
Varying Tube Diameter and Tube circuiting at Optimum Air Velocity
and Sub-Cool 180
Figure 9-16: Operating Cost Factor vs. Condenser Material Cost Factor for
Varying Geometric Parameters and Various Fixed Frontal Areas at
Optimum Air Velocity and Sub-Cool 182
-
8/12/2019 Plate -Fin-tube Condenser Performance
12/255
xii
NOMENCLATURE
List of Symbols
a = Ratio of the transverse tube spacing to the tube diameter
ast = Stanton Number coefficient in the Kays and London (1984)
Correlation
ax = Axial acceleration due to gravity
A = Total heat transfer area
Ac = Minimum free-flow cross sectional area
Aci = Cross sectional area of the refrigerant-side of the tube
Afin = Total fin surface area
Afr,con = Frontal area of condenser
Amin = Minimum free-flow area
Ao = Total air-side heat transfer area including the fin and tube areas
AF = Area Factor
B = Buoyancy Modulus
B = Two-phase flow refrigerant side pressure drop Coefficient for a tube bend odegrees
bst = Stanton Number coefficient in the Kays and London (1984)
Correlation
b = Ratio of the tube spacing normal to the air flow, to the tube diameter
-
8/12/2019 Plate -Fin-tube Condenser Performance
13/255
xiii
C = Heat capacity
C1 = Constant of the Hiller-Glicksman refrigerant-side pressure drop
Correlation
C2 = Constant of the Hiller-Glicksman refrigerant-side pressure drop
Correlation
C3 = Constant of the Hiller-Glicksman refrigerant-side pressure drop
Correlation
cp = Specific heat at constant pressure
cp,eff = Effective specific heat at constant pressure
cp,l = Specific heat of fluid in the liquid phase
Cmin = Minimum heat capacity between that of the air and the refrigeran
Cmax = Maximum heat capacity between that of the air and the refrigerant
Cr = Ratio of the minimum heat capacity to the maximum heat capacity
Cz = Average row correction factor
cz = Individual row correction factor
CF = Cost factor
COP = Coefficient of Performance
COPseas = Seasonal Coefficient of Perfor mance
Cost = Cost of materials for the heat exchangers
CostAl = Cost per pound of Aluminu
CostCu = Cost per pound of Copper
D = Tube diameter
Ddepc = Depth of condenser in the direction of air flow
Dh = Hydraulic diameter
-
8/12/2019 Plate -Fin-tube Condenser Performance
14/255
xiv
d( ) = Differential change in ( )
Eu = Euler number
Eucor = Corrected Euler number
f = Friction factor
fGO = Friction factor for fluid flowing as vapor onl
fLO = Friction factor for fluid flowing as liquid only
ffin = Fin friction factor
fri = Fraction of temperature bin hours
Fr = Froude number
G = Mass flux
Gmax = Mass flux of air through the minimum flow area
gcs = Units conversion constant
h = Specific enthalpy
h1 = Specific enthalpy of refrigerant entering the compressor
h2 = Actual specific enthalpy of refrigerant exiting the compressor
h2s = Ideal specific enthalpy of refrigerant exiting the compressor
h2a = Specific enthalpy of refrigerant exiting the superheated portion of the
condenser
h2b = Specific enthalpy of refrigerant entering the sub-cooled portion of the
condenser
h3 = Specific enthalpy of refrigerant entering the expansion valve
h4 = Specific enthalpy of refrigerant exiting the expansion valve
ha = Air-side heat transfer coefficien
-
8/12/2019 Plate -Fin-tube Condenser Performance
15/255
xv
hevap = Two-phase refrigerant-side evaporative heat transfer coefficien
hL = Liquid phase refrigerant side heat transfer coefficien
hr = Refrigerant-side heat transfer coefficient
hr,SP = Single phase refrigerant-side heat transfer coefficient
hTP = Two-phase refrigerant-side heat transfer coefficient
i = Temperature bin number
j = Colburn factor
JP = Parameter for the Colburn factor calculation
k = Thermal conductivity
k1 = Geometry factor for staggered tube array for the air-side pressure drop
correlation
kl = Liquid phase thermal conductivity
kb, = Two-phase flow refrigerant side pressure drop Coefficient for a tube bend
odegrees
L = Length
l = Integral variable evaporating tube length
Lcon,sa = Tube length of the saturated portion of the condenser tubes
Lcon,sc = Tube length of the sub-cooled portion of the condenser tubes
Lcon,sh = Tube length of the superheated portion of the condenser tubes
Levap,sat = Tube length of the saturated portion of the evaporator tubes
Levap,sh = Tube length of the superheated portion of the evaporator tubes
Lsat = Tube length of the saturated portion of the heat exchanger tubes
Ltot = Total tube length of the heat exchanger tubes
-
8/12/2019 Plate -Fin-tube Condenser Performance
16/255
xvi
m = mass
m = mass flow rate
ma,sat = mass of flow rate of air f owing over the saturated portion of the
condenser
ma,tot = total mass flow rate of air flowing over the condenser
mair = mass flow rate of air flowing over heat exchanger
mcon,sat = mass of refrigerant in the saturated portion of the condenser
mcon,sc = mass of refrigerant in the sub-cooled portion of the condenser
mcon,sh = mass of refrigerant in the superheated portion of the condenser
mes = extended surface geometric parameter
mevap,sat = mass of refrigerant in the saturated portion of the evaporator
mevap,sh = mass of refrigerant in the superheated portion of the evaporator
n = Blausius coefficien
NTU = Number of transfer units
NuD = Nusselt number based on the tube diameter
P = Pressure
pr = Reduced pressure
Prat = Ratio of the condenser saturation pressure to the evaporator saturation
pressure
Pe = Perimeter
PD = Compressor piston displacemen
Pr = Prandtl number
Q = Rate of total heat trans erred between the refrigerant and the air
.
.
.
.
.
-
8/12/2019 Plate -Fin-tube Condenser Performance
17/255
xvii
q = Amount of heat per unit mass transferred between the air and the
refrigerant
Qave,seas = Average cooling load of the system over all cooling load hours
qcon,sat = Amount of heat per unit mass transferred between the air and the
refrigerant in the saturated portion of the condenser
qcon,sc = Amount of heat per unit mass transferred between the air and the
refrigerant in the sub-cooled portion of the condenser
qcon,sh = Amount of heat per unit mass transferred between the air and the
refrigerant in the superheated portion of the condenser
qcst = Empirical constant for the Euler number correlation
Qe = Cooling capacity of the syste
Qmax = Maximum possible amount of heat transferred between the refrigerant and
the air
r = Outer radius of tube
rb = Radius of tube bend
Rb = Tube bend recovery length
rcst = Empirical constant for the Euler number correlati
Rcv,PD = Ratio of clearance volume to the piston displacemen
Re = Equivalent radius for a hexagonal fin
Rf,r = Refrigerant-side heat exchanger fouling factor
Rf,a = Air-side heat exchanger fouling factor
rr = Relative radius of tube bend
Rw = Tube wall thermal resistance
Re = Reynolds number
ReD = Reynolds number based on diameter
.
.
-
8/12/2019 Plate -Fin-tube Condenser Performance
18/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
19/255
xix
Vol,Al,cond = Volume of the aluminum components of the condenser (fins)
Vol,Al,eva = Volume of the aluminum components of the evaporator (fins)
Vol,Cu,cond = Volume of the copper co ponents of the condenser (tubes)
Vol,Cu,evap = Volume of the copper components of the evaporator (tubes)
wa,com = Actual compressor work per unit mass of refrigeran
Wave,seas = Average electricity required by the system over all cooling load hours
Wcom = Compressor power
Wf,con = Condenser fan power
Wf,evap = Evaporator fan power
ws,com = Isentropic compressor work per unit mass of refrigeran
x = Vapor quality
xe = Vapor quality at the exit of the heat exchanger
xi = Vapor quality at the inlet of the heat exchanger
Xl = Transverse tube spacing
Xt = Tube spacing normal to air flow
Xtt = Lockhart-Martinelli Parameter
y = Equivalent length of tube bend
z = Number of rows of tubes
.
.
.
-
8/12/2019 Plate -Fin-tube Condenser Performance
20/255
xx
List of Symbols with Greek Letters
= Local void fraction.
= Coefficient of the empirical relation for determining the equivalen circular radius for hexagonal fins
hlat = Change in the latent enthalpy
hsens = Change in the sensible enthalpy
htot = Change in the total enthalpy
p = Pressure drop
p a,con = Pressure drop on the air-side of the condenser
p b = Refrigerant-side pressure drop inside a tube bend
p b,LO = Refrigerant-side pressure drop inside a tube bend with all fluid flowing as a liquid
p b,SP = Single phase refrigerant-side pressure drop inside a tube bend
p b,TP = Two-phase refrigerant-side pressure drop inside a tube bend
pf = Friction component of the two-phase refrigerant-side pressure drop inside a straight tube
pfins = Air-side pressure drop due to fins
pm = Momentum component of the two-phase refrigerant-side pressure drop inside a straight tube
p S,SP = Single phase refrigerant-side pressure drop inside a straight tube
p S,TP = Two-phase refrigerant-side pressure drop inside a straight tube
p tot,ac = Total air-side pressure drop
p tubes = Air-side pressure drop due to tubes
-
8/12/2019 Plate -Fin-tube Condenser Performance
21/255
xxi
x = Change in quality
= Fin effectiveness
pr = Pipe roughness
= Fin parameter that is a function of the equivalent circular radius of a hexagonal fin
b2 = Physical property coefficient for the refrigerant-side pressure drop determination inside a tube bend
c = Compressor thermal efficienc
f = Fin efficienc
fan,con = Condenser fan efficiency
s = Surface efficiency
s,a = Air-side surface efficienc
s,r = Refrigerant-side surface efficienc
v = Compressor volumetric efficiency
2b,LO = Two-phase multiplier for the refrigerant side pressure drop inside tube bends
= Viscosity
l = Viscosity of the fluid in the liquid phase
m = Viscosity of the fluid evaluated at the mean fluid temperature
s = Viscosity of the fluid evaluated at the temperature of the inner tube wall surface
TP = Two-phase fluid viscosity
v = Viscosity of the fluid in the vapor phase
-
8/12/2019 Plate -Fin-tube Condenser Performance
22/255
xxii
= 3.14159..
= Angle of tube bend
= Density
l = Density of the fluid in the liquid phase
v = Density of the fluid in the vapor phase
= Ratio of the minimum free-flow area to the frontal area of the hea exchanger
= Coefficient of the empirical relation for determining the equivalen circular radius for hexagonal fins
-
8/12/2019 Plate -Fin-tube Condenser Performance
23/255
xxiii
SUMMARY
Current residential air-conditioners and heat pumps use the hydrochlorofluorocarbon
refrigerant, R-22, as the working fluid. In accordance with the Montreal Protocol, a
production ban of all equipment utilizing R-22 will begin in 2005, and a total ban on the
production of R-22 is also impending. A binary zeotropic mixture, R-410a, is a strong
candidate for R-22 replacement due to its many favorable performance characteristics;
e.g., non-flammability, high working pressures, and good cycle efficiency.
Since R-410a has significantly higher working pressure and vapor densities than R-
22, current air cooled finned tube condenser designs are not appropriate. The optimum
condenser and other high-pressure-side components are expected to employ smaller
diameter tubes, which will affect other design parameters. At this time, there is limited
information about condenser coil design and optimization using R-410a as the working
fluid. Furthermore, the heat transfer and friction data are also limited.
This work includes an examination of the available refrigerant-side two-phase flow
heat transfer and pressure drop models for refrigerants. A model based on first principles
is used to predict the performance of a unitary air-conditioning system with refrigerant R-
410a as the working fluid. The seasonal coefficient of performance of the air-
conditioning system is used as the figure of merit. The primary objective of this research
was to provide guidelines for the design and optimization of the condenser coil for tw
-
8/12/2019 Plate -Fin-tube Condenser Performance
24/255
xxiv
distinct criteria: (1) fixed condenser frontal area (size constraint), and (2) fixed
condenser material cost (capital cost constraint).
This study concludes that for both design criteria, the velocity of air flow over the
condenser ranges between 7.5 ft/s and 8.5 ft/s while the optimum sub-cooling of the
refrigerant exiting the condenser is approximately 15F. It is also concluded that
condensers employing tubes of smaller diameters yield the best system performance.
Recommendations for further research into the modeling of the in-tube condensation o
refrigerant R-410a are outlined. An exhaustive search optimization study could not be
performed due to computational speed limitations, therefore more advanced optimization
search techniques are also recommended for further study.
-
8/12/2019 Plate -Fin-tube Condenser Performance
25/255
1
CHAPTER I
INTRODUCTION
The decade of the 1990s has been a challenging time for the Heating Ventilation Air
Conditioning and Refrigeration (HVAC&R) industry worldwide. Due to their role in the
destruction of the stratospheric ozone layer, provisions of the Montreal Protocol and its
various amendments required the complete phase-out of chlorine-containing refrigerant
such as chlorofluorocarbons (CFCs) and hydrochlorofluorocarbons (HCFCs). These
compounds have been used extensively as refrigerants in heat pumps, air conditioners
and refrigeration systems (Ebisu and Torikoshi, 1998). CFCs, which are characterized by
a high ozone-depletion potential (ODP), underwent a complete production phase-out in
the United States in 1995. Because HCFC-22 (chlorodifluoromethane) has been readily
available, inexpensive, and less harmful to the environment than CFCs, HCFC-22 has
been widely used in the air-conditioning and heat pump industry, especially in residential
unitary and central air-conditioning systems, for many years (Bivens et al., 1995).
However, the 1992 revision of the Montreal Protocol stipulated the first producti
ceiling for HCFCs starting in 1996 (Domanski and Didion, 1993). In the United States,
regulations published by the Environmental Protection Agency (EPA) prohibit the
-
8/12/2019 Plate -Fin-tube Condenser Performance
26/255
2
production of HCFC-22 after 2010 except for servicing equipment produced prior to
2010. The deadline is much earlier in some European countries (Gopalnarayanan and
Rolotti, 1999).
In addition, another international agreement, the Kyoto Protocol, has been initiated to
reduce the emission of greenhouse gases (GHGs) in order to lower the potential risk o
increased global warming. Representatives of more than 150 countries met in Kyoto,
Japan in December of 1997. As a result of this agreement, the nations agreed to roll back
emissions of carbon dioxide (CO2) and five other GHGs, including HFCs, to about 5.2%
below 1990 levels by 2010. Individual emissions targets were adopted for most
developed countries (Baxter et al., 1998). With CO2emissions tied directly to energ
use, the pressures for further HVAC&R equipment efficiency improvements will increase
in the early decades of the next century. At the same time, pressures from internationa
competition have continued unabated.
The choices for short-term and long-term replacements for R-22 are being driven by
environmental regulations, energy standard requirements, and the cost of implementation.
The differences in R-22 phase-out dates for the different countries seem to significantl
influence the choice of replacement refrigerants (Gopalnarayanan and Rolotti, 1999).
However, several programs are underway for evaluating R-22 alternatives. One such
industry program is the Alternative Refrigerants Program (AREP) initiated by the Air
Conditioning & Refrigeration Institute (ARI). The objective of this program is to provide
performance data on replacement refrigerants in compressors, air-conditioning syste
components and/or systems by conducting tests with participating member companies.
-
8/12/2019 Plate -Fin-tube Condenser Performance
27/255
3
Throughout the evaluation process, equipment manufacturers have made requests that the
alternatives meet several requirements. In order to meet these customer needs, a family
of alternatives has been developed for replacing R-22 (Bivens et al., 1995).
Unfortunately, no single-component HFCs have been discovered that have
thermodynamic properties close to that of R-22. Consequently, this has led to the
introduction of binary or ternary refrigerant mixtures. Several alternatives, including
binary and ternary blends of HFCs, as well as propane, are being considered as potential
R-22 replacement fluids (Gopalnarayanan and Rolotti, 1999). One very promising
replacement, from the viewpoint of zero ODP and non-flammability, is the binary
mixture, R-410a (Ebisu and Torikoshi, 1998). Note that R-410a is a near azeotropi
mixture consisting of 50% (wt%) R-32 and 50% R-125.
Besides the basic characteristics such as thermal properties and flammability, very
little heat transfer and pressure drop data for R-410a is available; although Wijaya and
Spatz (1995)have shown limited experimental data for heat transfer coefficients and
pressure drops for R-410a inside a horizontal smooth tube. Yet, knowledge of the
performance characteristics of air-cooled refrigerant heat exchangers with alternative
refrigerants is of practical importance in designing air-cooled heat exchangers required in
air-conditioning equipment. Therefore, more knowledge of the two-phase flow heat
transfer and pressure drops that occur in refrigerant R-410a heat exchangers is needed.
-
8/12/2019 Plate -Fin-tube Condenser Performance
28/255
4
Research Objectives
The primary objective of this current work is to study the design and optimization o
the operating conditions and the geometric design parameters for the air-cooled
condenser coil of a vapor compression residential air-conditioning system wit
refrigerant R-410a as the working fluid. The condenser and total system operating
conditions are varied so that the systems coefficient of performance can be evaluated as
a function of the heat exchanger design. Subsequently, it is also the intent of this stud
that the optimization methodology detailed in this work provide guidelines to the coil
designer for future design optimizations of this type. A secondary objective of this study
is to investigate various two-phase flow heat transfer and pressure drop evaluation
methods for refrigerant R-410a.
-
8/12/2019 Plate -Fin-tube Condenser Performance
29/255
5
CHAPTER II
LITERATURE SURVEY
Previous Studies on Variations of Heat Exchanger Geometric Parameter
The heat exchanger of interest for this present study is of the plate-fin-and-tube
configuration. A schematic of a typical plate-fin-and-tube heat exchanger is shown in
Figure 2-1.
Figure 2-1: Typical Plate Fin-and-Tube Cross Flow Heat Exchange
AirCrossFlow
Air CrossFlow
T= f(x,y)
Refrigerant
Flow
Refrigerant
Flow
-
8/12/2019 Plate -Fin-tube Condenser Performance
30/255
6
There have been several studies on heat exchangers of this type. Wang et al. (1999)
conducted an experimental study on the air-side performance for two specific louver fin
patterns and their plain plate fin counterparts. This study investigated the effects of fin
pitch, longitudinal tube spacing and tube diameter on the air-side heat transfer
performance and friction characteristics. This study found that for plain plate fin
configurations ranging from 8 to 14 fins per inch, the effect of longitudinal tube pitch on
the air-side was negligible for both the air-side heat transfer and pressure drop. However,
the heat transfer performance increased with reduced fin pitch.
Chi et al. (1998) conducted an experimental investigation of the heat transfer and
friction characteristics of plate fin-and tube heat exchangers having 7 mm diameter tubes.
In this study, 8 samples of commercially available plate-fin-and-tube heat exchangers
were tested. It was found that the effect of varying fin pitch on the air-side heat transfer
performance and friction characteristics was negligible for 4-row coils. However for 2-
row coils, the heat transfer performance increased with a decrease in fin pitch. This stud
used a plate-fin-and tube heat exchanger configuration with louver fin surfaces, which are
widely used in both automotive and residential air-conditioning systems. The transverse
fin spacing ranged from 21 mm to 25.4 mm and longitudinal fin spacing ranged from
12.7 mm to 19.05 mm
Wang et al. (1998) also collected experimental data on a plate-fin-and tube hea
exchanger configuration. They examined the effect of the number of tube rows, fin pitch,
tube spacing, and tube diameter on heat transfer and friction characteristics. This stud
found that the effect of fin pitch on the air-side friction pressure drop was negligibly
-
8/12/2019 Plate -Fin-tube Condenser Performance
31/255
7
small for air-side Reynolds numbers greater than 1000. It was also found that the hea
transfer performance was independent of fin pitch for 4-row configurations.
Furthermore, the results indicated that reducing the tube spacing and the tube diameter
produced an increase in the air-side heat transfer coefficient. The fin surfaces utilized in
this study were of the louver type, with transverse fin spacing ranging from 21 mm to
25.4 mm, and longitudinal fin spacing ranging from 12.7 mm to 19.05 mm. The
longitudinal tube spacing investigated for this studied ranged from 15 mm to 19 mm and
the tube diameters ranged from 7.94 mm to 9.52 mm.
One of the earliest and most complete investigations of heat exchanger heat transfer
and pressure drop characteristics was performed by Kays and London (1984). An
extensive amount of experimental heat transfer and friction pressure drop data were
complied for several different plate-fin-and-tube heat exchanger configurations as part of
this study. However, no optimization of the heat transfer surfaces and geometry was
performed.
Shepherd (1956) experimentally tested the effect of various geometric variations on
1-row plate fin-and-tube coils. He investigated the effects of varying the fin spacing, fin
depth, tube spacing, and tube location on the heat transfer performance of the coil. The
results of Shepherds study showed that as the fin pitch increased, the air-side hea
transfer coefficient, for a given face velocity, increased only slightly. He also found tha
as the fin depth and tube spacing increased, with all other variables constant, the air-side
heat transfer coefficient decreased. Rich (1973) studied the effect of varying the fin
spacing on the heat transfer and friction performance of multi-row heat exchanger coils.
-
8/12/2019 Plate -Fin-tube Condenser Performance
32/255
8
Rich found that over the range from 3 to 14 fins per inch, the air-side heat transfer
coefficient was independent of fin pitch. Neither Richs nor Shepherds investigations
involved the optimization of the heat exchanger operating conditions and geometric
parameters.
All of the above studies provide valuable insight into the effects of varying different
geometric parameters on the heat transfer and friction performance of plate-fin-tube heat
exchangers. However none of the above works investigated the effects that varying these
geometric parameters has on the optimization of a complete air-conditioning system
Previous Work in R-22 Replacement Refrigerants
Again, a major focus of this work is the study of the effect of the condenser plate-fin-
and-tube heat exchanger design parameters on the performance of a refrigerant R-410a
unitary air-conditioning system. However, as discussed in Chapter I, due to the
impending ban of refrigerant R-22 production, there is a pressing need for studies on the
performance characteristics of alternative refrigerants in air-conditioning and heat pump
systems. Therefore a survey of the previous investigations on R-22 replacemen
refrigerants in these systems is a very important part of this present study.
There has been a substantial amount of work done in the area of air-conditioning and
heat pump R-22 replacement refrigerants. Only some of the relevant studies are
mentioned here. Radermacher and Jung (1991) conducted a simulation study of potential
R-22 replacements in residential equipment. The coefficient of performance (COP) and
-
8/12/2019 Plate -Fin-tube Condenser Performance
33/255
9
the seasonal performance factor (SPF) were calculated for binary and ternary substitutes
for R-22. They found that for a ternary mixture of R-32/R-152a/R-124 with a weight
concentration of 20 wt%/20 wt%/60 wt%, the COP was 13.7% larger and the compressor
volumetric capacity was 23% smaller than the respective values for R-22. This stud
found that in general, based on thermodynamic properties only, refrigerant mixtures have
the potential to replace R-22 without a loss in efficiency. Efficiency gains are possible
when counterflow heat exchangers are used and additional efficiency gains are possible
when capacity modification is employed.
Kondepudi (1993) performed experimental drop-in(unchanged system, same heat
exchangers) testing of R-32/R-134a and R-32/R-152a blends in a two-ton split-system air
conditioner. Five different refrigerant blends of R-32 with R-134a and R-152a were
tested as drop-inrefrigerants against a set of R-22 baseline tests for comparison. No
hardware changes were made except for the use of a hand-operated expansion device,
which allowed for a drop-incomparison of the refrigerant blends. Hence, other than
the use of a different lubricant and a hand-operated expansion valve, no form of
optimization was performed for the refrigerant blends. Parameters measured included
capacity, efficiency, and seasonal efficiency. The steady state energy efficiency ratio
(EER) and seasonal efficiency energy efficiency ratio (SEER) of all the R-32/R-134a and
R-32/R-152a blends tested were within 2% of those for a system using R-22. The 40
wt%/60 wt% blend of R-32/R-134a performed the best in a non-optimized system.
Fang and Nutter (1999) evaluated the effects of reversing valves on heat pump system
performance with R-410a as the working fluid. A traditional reversing valve enables a
-
8/12/2019 Plate -Fin-tube Condenser Performance
34/255
10
heat pump to operate in either the heating mode or cooling mode. It performs this
function by switching the refrigerant flow path through the indoor and out door coils,
thus changing the functions of the two heat exchangers. However, use of reversing
valves causes increased pressure drops, refrigerant leakage from the high pressure side to
the low pressure side, and undesired heat exchange. This study measured the overal
effects of a reversing valve on a 3-ton heat pump system using R-410a and made
comparisons to the same valves performance with R-22 as the working fluid. It was
found that changing from refrigerant R-22 to R-410a resulted in an increase in mass
leakage, but did not significantly change the effect that the reversing valve had on the
system COP.
Domanski and Didion (1993) evaluated the performance of nine R-22 alternatives.
The study was conducted using a semi-theoretical model of a residential heat pump with
a pure cross-flow representation of heat transfer in the evaporator and condenser
(Domanski and Mclinden, 1992). The models did not include transport properties since
they carried the implicit assumption that transport properties (and the overall heat transfer
coefficients) are the same for the fluids studied. Simulations were conducted for drop-
inperformance, for performance in a modified system to assess the fluidspotentials,
and for performance in a modified system equipped with a liquid line/suction-line hea
exchanger. The simulation results obtained from the drop-inevaluation predicted the
performance of candidate replacement refrigerants tested in a system designed for the
original refrigerant, with a possible modification of the expansion device. The drop-in
model evaluations revealed significant differences in performance for high-pressure
-
8/12/2019 Plate -Fin-tube Condenser Performance
35/255
11
fluids with respect to R-22 and indicated possible safety problems if those fluids were
used in unmodified R-22 equipment. The simulation results obtained from the constant-
heat-exchanger-loading evaluation corresponded to a test in a system modified
specifically for each refrigerant to obtain the same heat flux through the evaporator and
condenser at the design rating point. This simulation constraint ensures that the
evaporator pressures are not affected by the different volumetric capacities of the
refrigerants studied. The results for the modified system performance showed tha
capacity differences were larger for modified systems than for the drop-inevaluation.
However, none of the candidate replacement refrigerants exceeded the COP of R-22 at
any of the test conditions.
Bivens et al. (1995) compared experimental performance tests with ternary and binary
mixtures in a split system residential heat pump as well as a window air-conditioner.
This study investigated refrigerants R-407c, a ternary zeotropic mixture of 23 wt% R-32,
25 wt% R-125 and 52 wt% R-134a, and R-410b, a near azeotropic binary mixture
composed of 45 wt% R-32 and 55 wt% R-125 as working fluids. The heat pump used for
the evaluations was designed to operate with R-22 and was equipped with a fin-and-tube
evaporator with 4 refrigerant flow parallel circuits, and a spined fin condenser with 5
circuits and 1 sub-cooling circuit. It was found that R-407c provided essentially the same
cooling capacity as compared with R-22 with no equipment modification. R-410b
provided a close match in cooling capacity using modified compressor and expansion
devices. The energy efficiency ratio for R-407c versus R-22 during cooling ranged from
0.95 to 0.97. The energy efficiency ratio for R-410b versus R-22 during cooling ranged
-
8/12/2019 Plate -Fin-tube Condenser Performance
36/255
12
from 1.01 to 1.04. Window air-conditioner tests were conducted with R-407c in three
window air-conditioners ranging in size from 12,000 to 18,000 Btu/hr. The result
demonstrated equivalent capacity and energy efficiency ranging from 0.96 to 0.98
compared with R-22.
In summation, in the search for a replacement for refrigerant R-22 many refrigerants
have been studied. As discussed throughout this work, many of those studied are
refrigerant mixtures. A list of many of the refrigerant mixtures studied by the sources
sited in this literature survey is shown in Table 2-1.
Table 2-1: List of Refrigerant R-22 Alternative Refrigerant Mixtures
Refrigerant Weight Percent
R-410a R-32/50%, R-125/50%
R-407b R-32/45%, R-125/55%
R-407c R-32/23%, R-125/25%, R-134a/52%
Radermacher and Jung(1991)
R-132/20%, R-R-152a/20%, R-124/60%
Kondepudi (1993) R-32/40%, R-134a/60%
-
8/12/2019 Plate -Fin-tube Condenser Performance
37/255
13
As a result of many of the studies discussed in this literature survey, refrigerant R-410a
has emerged as the primary candidate to replace R-22 in many industrial and residential
applications. There is at least one commercially available air-conditioning system using
R-410a as the working fluid, which is made by Carrier. Therefore, as discussed in
Chapter I, R-410a is the refrigerant of interest for this current study.
Two-Phase Flow Regime Considerations in Condenser and Evaporator Design
The prediction of flow patterns is a central issue in two-phase gas-liquid flow in hea
exchangers. Design parameters such as pressure drop and heat and mass transfer are
strongly dependent on the flow pattern. Hence, in order to accomplish a reliable design
of gas-liquid systems such as pipelines, boilers and condensers, ana prioriknowledge of
the flow pattern is needed (Dvora et al., 1980).
Figure 2-2 shows one version of the commonly recognized flow patterns for two-
phase flow inside horizontal tubes. Description of these patterns is highly subjective, of
course, and there is some variation among researchers in the field concerning the
characterization of the various patterns. However, the essential situation is this: For
ordinary fluids under ordinary process conditions, two forces control the behavior and
distribution of the phases. These forces are gravity, always acting towards the center o
the earth, and vapor shear forces, acting on the vapor-liquid interface in the direction o
motion of the vapor. When gravity forces dominate (usually under conditions of low
vapor and liquid flow rates), one obtains the stratified and wavy flow patterns shown
-
8/12/2019 Plate -Fin-tube Condenser Performance
38/255
14
Figure 2-2: Horizontal Two-Phase Flow Regime Patterns
-
8/12/2019 Plate -Fin-tube Condenser Performance
39/255
15
in Figure 2-2. When vapor shear forces dominate (usually at high vapor flow rates), one
obtains the annular flow pattern (with or without entrained liquid in the core) shown on
the diagram. When the flow rates are very high and the liquid mass fraction dominates,
the dispersed bubble flow pattern is obtained, which is a shear-controlled flow of som
importance in boiler design but of very limited interest in condensers. Intermediate flow
rates correspond to patterns in which both gravitational and vapor shear forces are
important (Bell, 1988).
Although extensive research on flow patterns has been conducted, most of this
research has been concentrated on either horizontal or vertical flow. For horizontal flow
the earliest and perhaps the most durable, and best known of pattern maps for two-phase
gas-liquid flow was proposed by Baker (1954). Taitel and Dukler (1976) proposed a
physical model capable of predicting flow regime transition in horizontal and near
horizontal two-phase flow.
There are several points that need to be emphasized concerning the use of any flow
pattern map (Bell, 1988):
1. The definition of any two-phase flow pattern is highly subjective and differen
observers may disagree upon exactly what they are looking at. Adding to this
ambiguity are the various means of measuring two-phase flows and the resulting
different criteria that are used to characterize two-phase flows.
2. The boundaries drawn on a map as lines should be viewed as very broad
transition regions from one well defined flow pattern to another.
-
8/12/2019 Plate -Fin-tube Condenser Performance
40/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
41/255
17
assumed that the shear at the edge of the condensate film is directly proportional to the
pressure drop. This shear was expressed in terms of a constant friction factor and the
vapor velocity. Consequently, Nusselt succeeded in obtaining a correlation for the hea
transfer coefficient, which applies if the condensate is in laminar flow. However there
are significant discrepancies between Nusselts theory and the experimental data when
the condensate flow becomes turbulent or when the vapor velocity is very high (Soliman
et al., 1968).
Soliman et al. (1968) develop a model for two-phase flow heat transfer that includes
the contribution of the gravity, momentum and frictional terms to the wall shear stress.
In this work, a general correlation for the condensation heat transfer coefficient in the
annular flow regime was developed. The major assumption used in the development o
this correlation was that the major thermal resistance is in the laminar sublayer of the
turbulent condensate film. Experimental data for several fluids (including steam,
refrigerant R-22, and ethanol) was used to determine empirical coefficients and
exponents. This correlation predicts the experimental data within25%.
Yet another semi-empirical condensation heat transfer correlation for annular flow
was developed by Akers et al. (1959). Correlations for both the local and average values
of the condensation heat transfer coefficient were developed in the Akers study. The
Akers correlation predicts the experimental heat transfer coefficients generated b
Soliman et al. (1968), within 35%.
Traviss et al. (1973) applied the momentum and heat transfer analogy to an annular
flow model using the von Karman universal velocity distribution to describe the liquid
-
8/12/2019 Plate -Fin-tube Condenser Performance
42/255
18
film. Since the vapor core is very turbulent in this flow regime, radial temperature
gradients were neglected, and the temperatures in the vapor core and at the liquid-vapor
interface were assumed to be equal to the saturation temperature. Axial heat conduction
and sub-cooling of the liquid film were also neglected. An order of magnitude analysis
and non-dimensionalization of the heat transfer equations resulted in a simple
formulation for the local heat transfer coefficient. The analysis was compared to
experimental data for refrigerants R-12 and R-22 in a condenser tube, and the results
were used to substantiate a general equation for forced convection condensation. Since
the heat transfer analysis assumed the existence of annular flow, the sensitivity of this
analysis to deviations from the annular flow regime is important. When the mass flux of
the refrigerant vapor exceeded 500,000 lbm/hr-ft2, there is appreciable entrainment of
liquid in the upstream portion of the condenser tube. Since the analysis assumed tha
annular film condensation exists and that all of the liquid is on the tube wall, analytical
predictions are below the experimental data in the dispersed or misty flow regime.
However, the entrainment of liquid is not very large because the main resistance to hea
transfer occurs in the laminar sublayer, and liquid removed from the turbulent zone di
not increase the heat transfer coefficient in direct relation to the amount of liquid
removed. Yet, according to the experimental data collected and analyzed by Singh et al.
(1996), the mean deviation for the Traviss correlation deviates by -%40 from the data.
The above correlations were developed for one specific flow regime (annular flow).
However, in many instances a correlation that is applicable to more than one flow regime
is needed. Shah (1979) developed a very simple dimensionless correlation, which he
-
8/12/2019 Plate -Fin-tube Condenser Performance
43/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
44/255
20
considerable uncertainty. Simpler forms or firmer theoretical bases for predictive
methods can only be achieved with a narrowing of the ranges of applicability (Beattie and
Whalley, 1982).
Early two-phase flow studies emphasized the development of overall pressure drop
correlations encompassing all types of flow regimes. Furthermore, most of the
experimental data were obtained from relatively small and short pipes (Chen and
Spedding, 1981). Hence, no satisfactory general correlation exists. For several years,
experimental pressure drop data have been collected for horizontal gas-liquid systems,
and many attempts have been made to develop, from the data, general procedures for
predicting these quantities. Errors of about 20% to 40% can be expected in pressure-drop
prediction, and even this range is optimistic if one attempts to use the various predictive
schemes without applying a generous measure of experience and judgment. A major
difficulty in developing a general correlation based on statistical evaluation of data is
deciding on a method of properly weighing the fit in each flow regime. It is difficult to
decide, for instance, whether a correlation giving a good fit with annular flow and a poor
fit with stratified flow is a better correlation than one giving a fair fit for both kinds o
flow (Russell et al., 1974).
Lockhart and Martinelli (1949) developed one of the first general correlations.
Although various other general correlations have since been proposed the original
Lockhart-Martinelli approach is still in many respects the best. As discussed by Chen
and Spedding (1981), this method continues to be one of the simplest procedures for
calculating two-phase flow pressure drop. One of the biggest advantages of thi
-
8/12/2019 Plate -Fin-tube Condenser Performance
45/255
21
procedure is that it can be used for all flow regimes. For this flexibility, however,
relatively low accuracy must be accepted. Detailed checks with extensive data have
shown that the correlation overpredicts the pressure drop for the stratified flow regime
(Baker, 1954); it is quite reasonable for slug and plug flow (Dukler et al., 1964); and for
annular flow, it underpredicts for small diameter pipes (Perry, 1963), but overpredicts for
larger pipes (Baker, 1954).
Souza et al. (1993) developed a correlation for two-phase frictional pressure drop
inside smooth tubes for pure refrigerants using the Lockhart-Martinelli parameter,Xtt (the
square root of the ratio between the liquid only pressure drop and the vapor only pressure
drop), the Froude number, Fr, and experimental data. The pressure drop due to
acceleration was calculated using the Zivi (1964) equation for void fraction. A single
tube evaporator test facility capable of measuring pressure drop and heat transfer
coefficients inside horizontal tubes was utilized, and pressure drop data were collected.
During the tests, the predominant flow pattern observed was annular flow. For lower
mass fluxes and qualities, stratified-wavy, and semi-annular flow patterns were also
observed. The resulting correlation of experimental data for refrigerants R-134a and R-
12 for turbulent two-phase flow predicted the pressure drop within 10%.
Chisolm (1973,1983) has published important results on pressure drop and has
improved several correlations that predicted the frictional pressure drop during two-phase
flow for many different fluids. According to the data collected by Souza et al. (1993),
Chisolms two-phase flow multipliers overpredicted the experimental data for low
qualities and slightly underpredited those for high qualities. Overall, Chisolms
-
8/12/2019 Plate -Fin-tube Condenser Performance
46/255
22
correlation for friction pressure drop predicts the experimental values within 30% with a
mean deviation of 14.7%.
Jung and Radermacher (1989) developed a correlation for pressure drop during
horizontal annular flow boiling of pure and mixed refrigerants. For this correlation, a
two-phase multiplier based on total liquid flow was introduced for the total pressure drop
(frictional and acceleration pressure drop) and was correlated as a function of the
Lockhart and Martinelli parameter, Xtt. However, Jung and Radermachers correlation
overpredicts the experimental data by an average of 29%.
In summary, the general correlation procedures yield fair predictions of pressure drop
for all flow regimes because they are based on a large amount of correlatable data.
However, when these correlations are applied to systems other than those used in their
development, or to flow over extended distances (fully established flow), predicted
pressure drops can be in error by as much as a factor of 2. For more reliable predictions
of pressure drop, correlations based on specific models for individual flow regimes are
preferable, yet difficult to model analytically without concrete knowledge of the quality
distribution throughout the tubes (Greslpvoch & Shrier, 1971).
-
8/12/2019 Plate -Fin-tube Condenser Performance
47/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
48/255
24
Figure 3-1: The Actual Vapor-Compression Refrigeration Cycle
SaturatedSub-cooled Superheated
2b 2a3
ExpansionValve
Saturated Superheated
4 4a
Compressor
Condenser
Evaporator
1
2
S
T
-
8/12/2019 Plate -Fin-tube Condenser Performance
49/255
25
temperature (State 2b), and then cooled to below the saturation point until only sub-
cooled liquid is present (State 3). The high pressure liquid is then forced through the
expansion valve into the evaporator (State 4). The refrigerant then absorbs heat from
warm indoor air that is blown over the evaporator coils. The refrigerant is completel
evaporated (State 4a) and heated above the saturation temperature before entering the
compressor (State 1). The indoor air is cooled and dehumidified as it flows over the
evaporator and returned to the living space.
System Component Models
Compressor
The purpose of the compressor is to increase the working pressure of the refrigerant.
The compressor is the major energy-consuming component of the refrigeration system,
and its performance and reliability are significant to the overall performance of the
HVAC system. In general there are two categories of compressors: dynamic compressors
and displacement compressors. Dynamic compressors convert angular momentum into
pressure rise and transfer this pressure rise to the vapor (McQuiston and Parker, 1994).
Positive displacement compressors increase the pressure of the vapor by reducing the
volume. For this study scroll type positive displacement compressors, which dominate
the residential air-conditioning industry, are utilized.
The amount of specific work (work per unit mass of refrigerant) done by an ideal
compressor can be expressed with the following:
-
8/12/2019 Plate -Fin-tube Condenser Performance
50/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
51/255
27
where Pratis the pressure ratioand Tratis the temperature ratio, which are defined by
the following relationships,
The coefficients in this correlation are based on saturated temperatures and not on the
actual temperatures at the inlet and outlet of the compressor.
The volumetric efficiency is another important consideration in selecting and
modeling compressors. The volumetric efficiency is the ratio of the mass of vapor that is
compressed to the mass of vapor that could be compressed if the intake volume were
equal to the compressor piston displacement. The volumetric efficiency is expressed as:
evapsat
condsat
ratP
PP
,
,= (3-4)
evapsat
condsat
ratTTT
,
,= (3-5)
-
8/12/2019 Plate -Fin-tube Condenser Performance
52/255
28
where vis the compressor volumetric efficiency, Rcv,pdis the ratio of clearance volume
to the piston displacement, and v is the specific volume. The volumetric efficiency is
also used to determine the mass flow rate of the refrigerant though the compressor, m, for
a given compressor size by the following expression,
where PD is the Piston Displacement (Threlkeld, 1970).
Condenser
The condenser is a heat exchanger that rejects heat from the refrigerant to the outside
air. Although there are many configurations of heat exchangers, finned-tube hea
= 1
v
v1
2
1,v pdcvR (3-6)
2v
PDm v
= (3-7)
.
-
8/12/2019 Plate -Fin-tube Condenser Performance
53/255
29
exchangers are the type most commonly used for residential air conditioning applications.
Refrigerant flows through the tubes, and a fan forces air between the fins and over the
tubes. The heat exchangers used in this study are of the cross-flow, plate-fin-and-tube
type. A schematic of this heat exchanger is shown in Figure 3-2. The plate fins are
omitted from the schematic for simplicity.
When the refrigerant exits the compressor, it enters the condenser as a superheated
vapor and exits as a sub-cooled liquid. The condenser can be separated into three
sections: superheated, saturated, and sub-cooled. The amount of heat per unit mass o
refrigerant rejected from each section can be expressed as the difference between the
refrigerant enthalpy at the inlet and at the outlet of each section:
and
,22, ashcon hhq = (3-8)
,22, basatcon hhq = (3-9)
.32, hhq bsccon = (3-10)
-
8/12/2019 Plate -Fin-tube Condenser Performance
54/255
30
Figure 3-2: Typical Cross Flow Heat Exchanger (fins not displayed)
Horizontal
TubeSpacing
Air CrossFlow
Vertical TubeSpacing
Width
Depth
Height
row 1 row 2 row 3
1 Refrigerant FlowParallel Circuit
3 Tubes per Circuit
-
8/12/2019 Plate -Fin-tube Condenser Performance
55/255
31
The total heat rejected from the hot fluid, which in this case is the refrigerant, to the
cold fluid, which is the air, is dependent on the heat exchanger effectiveness and the hea
capacity of each fluid:
where is the heat exchanger effectiveness; Cminis the smaller of the heat capacities o
the hot and cold fluids, Chand Ccrespectively; Th,iis the inlet temperature of the hot
fluid; and Tc,iis the inlet temperature of the cold fluid. The heat capacity C, is expressed
as
where m is the mass flow rate of fluid and cpis the specific heat of the fluid. The hea
capacity, C, is the extensive equivalent to the specific heat, and it determines the amoun
of heat a substance absorbs or rejects when the temperature changes.
( )icih TTCQ ,,min = (3-11)
pcmC =(3-12)
.
-
8/12/2019 Plate -Fin-tube Condenser Performance
56/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
57/255
33
mass flow is separated into a number of discrete tubes and does not mix between fluids.
Furthermore, the plates of the heat exchanger prevent mixing of the air flowing over the
fins. Therefore, air at one end of the heat exchanger will not necessarily be the same
temperature as the air at the other end. For a cross flow heat exchanger with both fluids
unmixed, the effectiveness can be related to the number of transfer units (NTU) with the
following expression (Incropera & DeWitt, 1996):
where Cris the heat capacity ratio,
( ) ( )( )[ ] ,1exp1exp1 78.022.0
= NTUCNTU
Cr
r
(3-15)
.max
min
C
CCr= (3-16)
-
8/12/2019 Plate -Fin-tube Condenser Performance
58/255
34
In the saturated portion of the condenser, the heat capacity on the refrigerant side
approaches infinity and the heat capacity ratio, Crgoes to zero. When Cris zero, the
effectiveness for any heat exchanger configuration is expressed as
The NTU is a function of the overall heat transfer coefficient, U, and is defined as
where A is the heat transfer area upon which the overall heat transfer coefficient, U, is
based. The overall heat transfer coefficient accounts for the total thermal resistance
between the two fluids and is expressed as follows.
( ).exp1 NTU= (3-17)
,minC
UA
NTU=(3-18)
-
8/12/2019 Plate -Fin-tube Condenser Performance
59/255
35
where Rf,(a or r)is the fouling factor, Rwis the wall thermal resistance, s(a or r)is the
surface efficiency, andh is the heat transfer coefficient. There are no fins on the
refrigerant side of the condensing tubes; therefore, the refrigerant side surface efficiency
is 1. Neglecting the wall thermal resistance, Rw(this value is usually 3 orders o
magnitude lower than the other resistances), and the fouling factors, R f,(a or r), the overall
heat transfer coefficient reduces to:
The methodology for determining the refrigerant and air-side heat transfer coefficients
are discussed Chapter IV and Chapter V, respectively.
To determine the overall surface efficiency for a finned tube heat exchanger, it is firs
necessary to determine the efficiency of the fins as if they existed alone. For a plate-fin-
,111
,,
"
,
,
"
,
, rrrsrrs
rf
w
aas
af
aaas AhA
RR
A
R
AhUA ++++= (3-19)
.11
1
,
+=
rraaas AhAhUA
(3-20)
-
8/12/2019 Plate -Fin-tube Condenser Performance
60/255
36
and-tube heat exchanger with multiple rows of staggered tubes, the plates can be evenly
divided into hexagonal shaped fins as shown in Figure 3-3. Schmidt (1945) analyzed
hexagonal fins and determined that they can be treated as circular fins by replacing the
outer radius of the fin with an equivalent radius. The empirical relation for the equivalen
radius is given by
where r is the outside tube radius. The coefficients and are defined as
and
( ) ,3.027.1 2/1= rRe (3-21)
r
Xt
2=
(3-22)
,4
1
2/12
2
+= tl
t
XXX
(3-23)
-
8/12/2019 Plate -Fin-tube Condenser Performance
61/255
37
Figure 3-3: Hexagonal Fin Layout and Tube Array
Xt Tube Spacing
Normal to Air
Flo
Air Flow
Transverse Tube
Spacing
Xl
-
8/12/2019 Plate -Fin-tube Condenser Performance
62/255
38
where Xlis the tube spacing in the direction parallel to the direction of air flow, and X tis
the tube spacing normal to the direction of air flow.
Once the equivalent radius has been determined, the equations for standard circular
fins can be used. For this study, the length of the fins is much greater than the fin
thickness. Therefore, the standard extended surface parameter, escan be expressed as,
where hais the air-side heat transfer coefficient, k is the thermal conductivity of the fin
material, Pe is the fin perimeter, cis the fin cross sectional area, and t is the thickness o
the fin. For circular tubes, a parameter can be defined as
,2Pe
2/12/1
=
=
kt
h
kA
hm a
ces (3-24)
.ln35.011
+
=r
R
r
R ee (3-25)
-
8/12/2019 Plate -Fin-tube Condenser Performance
63/255
39
The fin efficiency, f, for a circular fin is a function of es, Re, and f, and can be
expressed as
The total surface efficiency of the fin, sis therefore expressed as
where Afinis the total fin surface area, Aois the total air-side surface area of the tube and
the fins.
( ).
tanh
ees
ees
fRm
Rm= (3-26)
( ),11 fo
fin
sA
A = (3-27)
-
8/12/2019 Plate -Fin-tube Condenser Performance
64/255
40
Condenser Fan
Natural convection is not sufficient to attain the heat transfer rate required on the air-
side of the condenser used in a reasonably sized residential air-conditioning system.
Therefore a fan must be employed to maintain the airflow at a sufficient rate of speed.
Although much of the power consumed by the total system is due to the compressor, the
condenser fan also requires a significant amount of power. The power required by the
fan is directly related to the air-side pressure drop across the condenser and to the
velocity of air across the condenser:
where Va,conis the air velocity over the face of the condenser, Pa,conis the air-side
pressure drop over the condenser, Afr,conis the frontal area of the condenser, and fan,conis
the condenser fan efficiency. Calculations for the air-side pressure drop are discussed in
Chapter V.
Expansion Valve
The expansion valve is used to control the refrigerant flow through the system
Under normal operating conditions, the expansion valve opens and closes in order to
confan
confrconacona
conf
APVW
,
,,,
,
= (3-28)
-
8/12/2019 Plate -Fin-tube Condenser Performance
65/255
41
maintain a fixed amount of superheat in the exit of the evaporator. In this study, the
superheat will be maintained at the typical 10F. Because the expansion valve can only
pass a limited volume of refrigerant, it cannot maintain the specified superheat at the
evaporator exit if the refrigerant is not completely condensed into liquid. If incomplete
condensation in the condenser occurs, the vapor refrigerant backs up behind the
expansion valve and the pressure increases until the refrigerant is fully condensed. As a
result, the expansion valve cannot regulate the refrigerant mass flow rate, and canno
maintain a fixed superheat at the evaporator exit. The energy equation shows that the
enthalpy is constant across the expansion valve.
Evaporator
The purpose of the evaporator is to transfer heat from the room air in order to lower
its temperature and humidity. Because the refrigerant enters the evaporator as a liquid-
vapor mixture, it is only divided into saturated and superheated sections. No sub-cooled
section is necessary. The analysis of the thermodynamic parameters of the evaporator is
43 hh =(3-29)
-
8/12/2019 Plate -Fin-tube Condenser Performance
66/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
67/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
68/255
44
where cpis the specific heat ratio for dry air and cp,effis the effective specific heat. To
maintain indoor humidity, the latent heat accounts for approximately 25% of the tota
enthalpy change of the air flowing over an evaporator. The effective specific heat can
thus be expressed in terms of the specific heat for dry air only,
Evaporator Fan
Because the evaporator is not the primary focus of this study, introducing wet coils
would present unwelcome complications in the overall analysis. In addition to affecting
the heat transfer, wet coils also have an effect on the air-side pressure drop. Although
there are correlations available for determining the pressure drop over wet coils, they are
cumbersome to use and again, the evaporator is not the primary focus of this
investigation.
After the air flows over the evaporator, it enters a series of ducts that then return the
air back inside the living space. The power required by the evaporator fan depends on
the losses in these ducts and can vary from configuration to configuration. Therefore, the
.33.1
75.0
25.0, p
tot
senslatpeffp c
h
h
T
hcc =
+= (3-33)
-
8/12/2019 Plate -Fin-tube Condenser Performance
69/255
45
default power requirement used by the Air-conditioning and Refrigeration Institute (ARI,
1989) of 365 Watts per 1000 ft3/minute of air will be used.
Refrigerant Mass Inventory
The degrees of sub-cooling at the condenser exit are controlled by the syste
operating conditions and the quantity of refrigerant mass in the system, as is discussed
further in Chapter VI. The mass of refrigerant in the tubes connecting the components is
neglected. Since the compressor contains only vapor, the mass of refrigerant in the
compressor is also neglected. Therefore the total mass of the system includes the mass o
refrigerant in the sub-cooled, saturated, and superheated portions of the condenser, and in
the saturated and superheated portions of the evaporator.
The following text outlines the procedure for finding the refrigerant mass in the
saturated portion of the evaporator. The same procedure is also used to determine the
mass of refrigerant in the saturated portion of the condenser, however the boundary
conditions are different
The mass of refrigerant can be expressed as
.v
=L
cidlAm (3-34)
-
8/12/2019 Plate -Fin-tube Condenser Performance
70/255
46
where, Aci is the cross sectional area of the refrigerant-side of the tube, and v is the
specific volume, which at saturated conditions is a function of quality expressed as
The boundary conditions for the saturated portion of the evaporator are
and
( ) ( ) .v1vv vl xx += (3-35)
( ) ixlx == 0(3-36)
1)( ==Llx (3-37)
-
8/12/2019 Plate -Fin-tube Condenser Performance
71/255
47
where lis integral variable evaporating tube length and L is the total evaporating tube
length. Using the boundary conditions and assuming the quality varies linearly with tube
length, the following expression results
Substituting (3-38) into (3-35) yields an expression for the specific volume as a functi
of length,
For a uniform cross sectional area, substituting (3-39) into (3-34) yields
( ) .1
ii xl
L
xlx +
= (3-38)
( ) ( ) ( ).vv1
vvvv lvi
lvilL
xlxl
++= (3-39)
-
8/12/2019 Plate -Fin-tube Condenser Performance
72/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
73/255
49
The mass of refrigerant in the superheated portions of the condenser and evaporator are
expressed simply as:
and
Finally, the mass of refrigerant in the sub-cooled section of the condenser is expressed as
shconcivshcon LAm ,, = (3-43)
.,, shevapcivshevap LAm = (3-44)
( )( ) ( )
.
vvv
vln
vv1
,,
+
=llvi
v
lvi
evapsatci
evapsat
xx
LAm
(3-42)
-
8/12/2019 Plate -Fin-tube Condenser Performance
74/255
50
.,, scconcivsccon LAm = (3-45)
-
8/12/2019 Plate -Fin-tube Condenser Performance
75/255
51
CHAPTER IV
REFRIGERANT SIDE HEAT TRANSFER COEFFICIENT AND PRESSURE
DROP MODELS
Single Phase Heat Transfer Coefficient
For a constant surface heat flux for single phase laminar flow, the Nusselt number can
be approximated by the following expression.
In the turbulent region, however, there are a number of expressions available for the
Nusselt number. One of the more commonly used correlations for turbulent flow is the
Dittus-Boelter equation. This correlation is valid for fully developed flow in circular
36.4=DNu (4-1)
-
8/12/2019 Plate -Fin-tube Condenser Performance
76/255
52
tubes with moderate temperature variations (Incropera & DeWitt, 1996). For refrigeran
cooling in a condenser, the Dittus-Boelter equation is expressed as
This mathematical relation has been confirmed by experimental data for the following
conditions:
0.7 Pr 160
ReD10,000
L/D 10
In the sub-cooled portion of the condenser in this study, the temperature difference at the
inlet and exit is usually less than 20F, and the moderate temperature variation
assumption is valid. However in the superheated portion of the condenser, the inlet and
exit temperatures can differ by as much as 90F. Therefore, the temperature difference
between the air flowing over the tubes and the refrigerant flowing inside the tubes is
large. This causes the temperature difference between the inner surface of the tubes and
the refrigerant to also be large in the superheated portion of the condenser. Thus, under
these conditions, the Dittus-Boelter equation is less accurate.
.PrRe023.0 3.08.0DDNu = (4-2)
-
8/12/2019 Plate -Fin-tube Condenser Performance
77/255
53
Yet another Nusselt number correlation for single phase turbulent flow has been
developed by Sieder and Tate(1936). This correlation was developed for a large range of
property variations based on the mean fluid temperature and the wall surface temperature,
and is expressed as
where all properties except for sare evaluated at the mean fluid temperature, and sis
evaluated at the temperature of the inner tube wall surface. Again, since this model is
developed for a large range of property variations, it is valid for larger temperature
differences within the fluid flowing inside the tube.
Kays and London (1984) have also developed a heat transfer correlation for single
phase turbulent flow. This correlation was developed using empirical data taken from a
variety of refrigerants in circular heat exchanger tubes under several thermodynamic
conditions. Unlike most heat transfer correlations, Kays and London have developed the
equations for the transition region between laminar and turbulent flow. The correlation is
expressed as:
,PrRe027.0
14.0
3/18.0
= sm
DDNu
(4-3)
-
8/12/2019 Plate -Fin-tube Condenser Performance
78/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
79/255
55
Figure 4-1: Refrigerant-Side Single Nusselt Number vs. Reynolds Numbe
0
20
40
60
80
100
120
140
0 5000 10000 15000 20000 25000
Reynolds Number
Nusse
ltNumb
er
Laminar, ConstantHeat Flux
Kays and Londo
Dittus Boelter
Sieder and Tate
TransitionLaminar
Turbulent
Dittus-Boelter
Sieder & Tate
Kays &
Londo
Kays &
Londo
-
8/12/2019 Plate -Fin-tube Condenser Performance
80/255
56
tube diameter of 0.2885 in, with refrigerant R-410a flowing as superheated vapor at a
mean temperature of 140 F and a pressure of 395 psia (conditions typically found in the
superheated portion of the condenser for this study). In the turbulent region, the value o
the Nusselt number calculated using the Kays and London correlation is on average about
70% higher than the Nusselt numbers calculated using both the Dittus-Boelter and the
Sieder and Tate correlations. This is due to the fact that both the Sieder and Tate and
Dittus-Boelter equations have assumed a smooth pipe. However the Kays and London
correlation was developed with experimental data taken from actual heat exchangers
which employ tubes with rougher surfaces. Because the Kays and London relation is
based on experimental data taken directly from heat exchangers similar to those
investigated in this work, and because the issue of the transition from laminar to turbulent
flow has been addressed, this correlation is used.
Condensation Heat Transfer
As discussed in Chapter II, the hea transfer coefficient in two-phase flow is
dependent on the flow regimes that are present. Annular flow is generally assumed to be
the dominant flow pattern existing over most of the condensing length during bot
horizontal and vertical condensing inside tubes (Soliman et al., 1968). Baker (1954) and
Gouse (1964) have derived flow pattern maps from numerous data, and have verified the
validity of this assumption. In most cases, annular flow is established soon after
condensation begins, and continues to very low quality. For horizontal condensing,
-
8/12/2019 Plate -Fin-tube Condenser Performance
81/255
57
gravity-induced stratification exists at low quality, but this usually occupies only a small
portion of the overall condensing length (Soliman et al., 1968). Annular flow is a
particularly important flow pattern since for a wide range of pressure and flow
conditions, and it occurs over a major part of the mass quality range, from 0.1 up to unity
(Collier & Thome, 1996). Therefore, heat transfer correlations developed for annular
flow, in addition to a correlation developed for all flow regimes, are considered for use in
this present study.
Two-phase flow heat transfer correlations developed by Traviss et al. (1973), Akers e
al. (1959), and Shah (1979) are evaluated for this current work. The correlations o
Akers et al. and Traviss et al. were developed for annular flow, while the Shah correlation
is proposed to be applicable to all flow regimes. Figure 4-2 shows the condensation hea
transfer coefficients for refrigerant R-12 calculated from the correlations of Shah, Traviss
et al., and Akers et al., versus the total mass flux. The figure also shows experimenta
condensation heat transfer coefficients for refrigerant R-12 taken from experimental data
collected by Eckels and Pate (1991). Using the parameters designated by the Baker
(1954) flow regime map, it is determined that for the experimental conditions of Eckels
and Pate, a slug flow pattern exists for mass fluxes between 100 and 250 kg/m2-s, and an
annular flow regime exists for mass fluxes greater than 250 kg/ 2-s. As Figure 4-2
shows, the Traviss correlation overpredicts the experimental data for the entire range o
mass fluxes shown. The Akers and Shah correlations slightly underpredict the
experimental values for relatively low mass fluxes and slightly overpredict the
experimental data at higher mass fluxes (annular flow).
-
8/12/2019 Plate -Fin-tube Condenser Performance
82/255
-
8/12/2019 Plate -Fin-tube Condenser Performance
83/255
59
The fact that the Traviss correlation greatly overpredicts the experimental data for
when the flow regime is annular is surprising since this correlation was developed for
annular flow. The Akers correlation predicts the experimental data to within an average
14.3% while the Shah correlation predicts the experimental data to within an average o
14.7%. Therefore the Shah and Akers correlations are in good agreement with each
other, and are both more accurate than the Traviss correlation for the conditions
investigated.
Using the parameters of the Baker (1954) flow regime map, and the typical operating
conditions of the condenser studied in this present work (mass fluxes approximately
greater than or equal to 400 kg/ 2-s or 300,000 lbm/ft2-hr), it is determined that the
dominant flow regime is indeed annular. However, this study also finds that for low
qualities, stratified-wavy flow exists. As a result, the use of a general correlation that is
valid for more than one flow regime is advantageous for the work of this investigation.
Therefore, the correlations developed by Akers et al. and Traviss et al., are not used.
Hence, the two-phase flow heat transfer correlation developed by Shah is used for this
investigation.
The two-phase flow heat transfer model developed by Shah is a simple correlation
that has been verified over a large range of experimental data. In fact, experimental data
from over 20 different researchers has been used in its development. The model has a
mean deviation of about 15% and has been verified for many different fluids, tube sizes,
and tube orientations.
-
8/12/2019 Plate -Fin-tube Condenser Performance
84/255
60
For this model, at any given quality, the two-phase heat transfer coefficient is defined
as:
wherehTPis the two-phase flow heat transfer coefficient, x is the quality,hLis the liquid
only heat transfer coefficient, and p ris the reduced pressure. By integrating the
expression (4-6) over the length of the tube, the mean