    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 1 OF 48 REVISION 2.1, SEP 2010

    PIPENET VISION SPRAY/SPRINKLER MODULE

    CHAPTER 1

    INTRODUCTION AND BASIC PRINCIPLES

    1. Introduction

    The Spray/Sprinkler Module of PIPENET VISION was specifically developed for the type offire protection systems that are used in process plants and similar plants, such as refineries,petrochemical plants, offshore plants, and terminals. Such systems are characterised bycomplex firewater ringmains, deluge systems, sprinkler systems, foam injection systems, etc.For these systems, it is usually necessary to perform calculations under several scenarios,such as different fire scenarios and different pump scenarios. With PIPENET VISION, it is

    simple and fast to perform these calculations. The objective is to ensure that pipes, pumps,hydrants, nozzles and other items perform satisfactorily. Where necessary, PIPENETVISION can be used to size orifice plates in order to balance or reduce the flow rates.

    The Spray/Sprinkler Module is a steady-state modelling program for designing systems, withthe objective being to ensure that the sizes of pumps, pipes, nozzles, etc. are adequate.

    The Spray/Sprinkler Module complies with the NFPA rules, which are the universal rulesgoverning the design of fire protection systems in the process plant industry, as far ashydraulic calculations are concerned.

    One of the differences between the Spray/Sprinkler Module and the other modules ofPIPENET VISION is that, with the Spray/Sprinkler Module, it is not possible to enter a networkuntil either (a) a Sunrise Data File (*.SDF) has been entered and saved or (b) an existingSunrise Data File is opened.

    In the suite of training manuals for the PIPENET VISION Spray/Sprinkler Module, Chapters 2and 3 are the core of the training course, whereas Chapters 1 and 4 provide useful readingmaterial.

    Most of the concepts and capabilities introduced in Chapter 1 User Interface of PIPENETVISION are relevant to this module and should be read prior to reading the training manuals

    for this module. In this document, the main concepts and features that are specific to theSpray/Sprinkler Module are described.

    2. Concepts

    2.1 Pressure Drop Model

    The pressure loss, P, in a pipe is described as

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    2/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 2 OF 48 REVISION 2.1, SEP 2010

    platelevfric PPPP ++=

    where

    Pfric is the pressure loss due to friction and fittings,Pelev is the pressure loss due to elevation change,Pplat is the pressure loss due to any orifice plate fitted.

    Full details of the equations that are used to calculate these pressure losses are describedbelow.

    2.1.1 Friction Pressure Losses Darcy

    Pfric is determined using the Bernoulli Equation, which is a theoretical equation that gives thepressure in pipes, ignoring frictional effects. The pressure drop due to friction effects can be

    found by comparing the theoretical results from the Bernoulli Equation with results obtained inexperiments. Based on the work of the French engineer Henri Darcy (180358) the followingequation is obtained.

    D

    uLLfP efric

    2)(2 +

    =

    where

    D is the internal diameter of the pipe,

    L is the pipe length,Le is the equivalent length of any pipe fittings,f is the Fanning friction factor,u is the fluid velocity,

    is the fluid density.

    The Fanning friction factor depends on the relative roughness of the pipe (i.e., pipe roughnessdivided by pipe diameter) and the Reynolds Number, Re, which is defined as

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    3/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 3 OF 48 REVISION 2.1, SEP 2010

    DuRe =

    where is the fluid viscosity. The standard values for f can be obtained from a graphicalrepresentation known as the Moody Diagram. The friction factor is represented in PIPENETVISION by the following empirical formulae (in which r is the surface roughness of the pipe).

    Laminar flow (Re < 2000):

    eRf

    16=

    Transitional flow (2000 < Re< 3000):

    The value of f is obtained by interpolating between the laminar value for Re = 2000 andthe turbulent value at Re = 3000.

    Turbulent flow (Re > 3000):

    +=

    fRD

    r

    f e

    252.127.0ln768.1

    1

    2.1.2 Friction Pressure Losses - Hazen-Williams Method

    With this method, the pipe C-factor is used in the calculations, and so the C-factor must besupplied.

    It should be noted that, for maximum flexibility, the user is allowed to override the roughnessor C-factor value of the pipe type when entering the individual pipe data. However, by default,the roughness or C-factor of each pipe will be determined by the pipe type of a particular pipe.

    The Hazen-Williams Equation is an empirical formula that gives an explicit expression for thefrictional pressure loss.

    SI Units

    The frictional losses are given by

    87.485.1

    85.15)(1005.6

    DC

    QLLP efric

    +=

    where

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    4/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 4 OF 48 REVISION 2.1, SEP 2010

    L is the pipe length in metres,Le is the equivalent length of any pipe fittings in metres,Q is the (volumetric) fluid flow rate in l/min,D is the pipe diameter in mm,

    C is the Hazen-Williams constant (or C-factor) for the pipe.

    Imperial Units

    The frictional losses are given by

    87.485.1

    85.1)(52.4

    DC

    QLLP efric

    +=

    where

    L is the pipe length in feet,Le is the equivalent length of any pipe fittings, in feet,Q is the (volumetric) fluid flow rate in UK gallons per minute,D is the pipe diameter in inches,C is the Hazen-Williams constant (or C-factor) for the pipe.

    2.1.3 Pressure Loss due to Elevation Change

    The pressure drop caused by the difference in elevation of the two ends of the pipe is givenby

    ZgPelev =

    in which

    g is the acceleration due to gravity,Z is the change in elevation.

    2.2 Pumps

    In the simple pump model, the pump performance curve is used. The user inputs the flowrate against head data at 100% rpm. PIPENET VISION can then calculate the performancecurve at other speeds, using the homologous relationships for pumps. This curve is normallyintended only for use only in the positive quadrant; in other words, when the flow and thehead are positive.

    Three options are available for defining pump curves:

    Quadratic function,

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    5/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 5 OF 48 REVISION 2.1, SEP 2010

    Cubic function,Cubic spline functions.

    These functions are applicable to values of Q that lie between the specified minimum andmaximum values (namely, Qmin and Qmax respectively).

    2.2.1 Data Required for Entering a Pump Into the Library

    The standard method for entering pump data is to use points from the performance curve.These points are then used by PIPENET VISION to calculate the coefficients that define theappropriate curve (i.e., quadratic, cubic, or cubic spline).

    An alternative method, which is seldom used, is for the user to enter the coefficients A, B, andC that define the pump-performance curve. In this case, the minimum and maximum valuesfor the flow rate must also be given.

    2.2.2 Some Useful Tips

    If the user knows the performance coefficients for a pump, but does not wish to use a pumplibrary, the user can define the pump as a non-library pump, by supplying the values of A, B,C, Qmin, and Qmax.

    In order for the calculator to function correctly, it is necessary to ensure that there is only oneflow rate that corresponds to each pressure gain, and so the following restrictions apply:

    For flow rates between Qmin and Qmax, the slope of the performance curve must benegative or zero.

    For flow rates between Qmin and Qmax, there must not be a flow rate that gives nopressure change (that is, all flow rates must correspond to a non-zero pressurechange, and so the performance curve must not cross the horizontal axis).

    If a flow rate lies outside the range Qmin to Qmax, PIPENET VISION issues an appropriatewarning message, and then extrapolates the performance curve using the tangent to thecurve at either the minimum or maximum flow rate (whichever is appropriate).

    PIPENET VISION calculates the power required by a pump based on an efficiency value. Ifthis efficiency value is not supplied, the pump is assumed to be 100% efficient for the purpose

    of this calculation.

    2.2.3 Pumps - Coefficients Unknown

    In the PIPENET VISION Spray/Sprinkler Module, data for pumps and fans can be created in alibrary. In this case, PIPENET VISION performs a curve fit, and uses the curve coefficients inthe calculations. The input data must be in the form of data pairs, taken from theperformance curves.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    6/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 6 OF 48 REVISION 2.1, SEP 2010

    Typically, the units for the pump curves are not the same as the units in which pressure-dropcalculations are to be made. For example, it is usual to specify the pump curve in head offluid, rather than psi. For this reason, the pump/fan module accepts data in its own units.

    The dialog box for inputting a pump curve can be obtained by choosing Pumps Coeffs.

    unknown from the Libraries Menu (which is denoted by Libraries | Pumps Coeffsunknown in the PIPENET VISION training manuals). The resulting dialog box is shownbelow.

    PIPENET VISION takes into account the fact that the head generated by a pump isindependent of the density of the fluid, and so PIPENET VISION makes an appropriatedensity correction in converting the head into a pressure. Similarly, the pressure generatedby a pump depends on the fluid, and when the pump curve is defined in terms of pressure, anappropriate density correction is applied. This is the reason why, when the pump-performance curve is defined in terms of pressure, the performance curve is interpreted to bethat of water.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    7/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 7 OF 48 REVISION 2.1, SEP 2010

    Creating a New Pump

    1. Select the New Button, and provide a name and description.

    2. Select the desired flow-rate and pressure units from the drop-down menus.

    3. Provide minimum and maximum values of the flow rate.4. Provide at least three points for the curve.

    5. Select the type of curve to be fitted (from, quadratic, cubic and cubic spline).

    6. Click on the Apply Button to add the pump to the library.

    7. The coefficients are then calculated and displayed, along with the pump curve.

    Note that the definition of the pump curve is accepted only if at least three points are supplied,and that the slope of the calculated curve is negative everywhere between the minimum andmaximum values.

    Type of

    curve fitted

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    8/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 8 OF 48 REVISION 2.1, SEP 2010

    Editing an Existing Pump

    1. Select the name of the pump from the drop-down list.

    2. Make the required changes to the pump parameters.

    3. Click on the Apply Button to commit the changes.

    Deleting a Pump

    1. Select the name of the pump from the drop-down list.

    2. Click on the Delete Button.

    2.2.4 Pumps - Coefficients Known

    This capability is hardly ever used.

    In this case, the pump coefficients that define the performance curve can be obtained fromthe manufacturer. These coefficients are then entered into PIPENET VISION using Libraries| Pumps Coeff. Known, and a pump-performance curve is produced.

    2.3 Non-Return Valves

    Non-return valves allow unrestricted flow of fluid in a positive direction, and prevent all flow inthe reverse direction. Positive flowis taken to be in the direction from the valve's input node toits output node, in which case there is no pressure drop across the component. Cautionshould be exercised to avoid positioning a non-return valve such that it would isolate a portion

    of the network. If this were to happen, the calculator could report the error message networkcannot be solved".

    Note that, even if the solution to the problem involves the valve being open, PIPENET VISIONcan still generate this error message. Occasionally, a non-zero "leakage flow" may bereported through a closed valve. This flow, which arises from rounding errors that are smallerthan the requested convergence accuracy, is usually negligible.

    Modelling Equations

    Open valve:

    21PP =

    Fully closed valve:

    01 =Q

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    9/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 9 OF 48 REVISION 2.1, SEP 2010

    Continuity Equation:

    21 QQ =

    The following variables are used in the above equations.

    P1 is the inlet pressure,P2 is the outlet pressure,Q1 is the inlet flow rate,Q2 is the outlet flow rate.

    2.4 Filters

    Strainers are usually modelled as equipment items. However, if the user wishes to modelthem more accurately and the required data is available, the filter model can be used.

    Filters are used in most of the networks to collect residue and dirt particles from the flowmedium. The filters can also be generated in PIPENET VISION by supplying the values of thecoefficients, A and B, in the modelling equations.

    Modelling Equation

    The modelling equation is

    BQQAQP +=

    where

    P is the pressure increase from the inlet to the outlet,Q is the (volumetric) flow rate through the filter,A is a coefficient (which is less than or equal to zero),B is a coefficient (which is less than zero).

    This equation is valid for values of Q whose modulus is less than a given maximum flow,Qmax. Note that filters are reversible (i.e., Q may be negative), in which case, since

    00

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    10/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 10 OF 48 REVISION 2.1, SEP 2010

    PKQ =

    where

    Q is the (volumetric) flow rate through the nozzle,P is the drop in pressure across the nozzle,K is a constant for the nozzle.

    This equation holds for values of P between specified minimum and maximum values (Pminand Pmax respectively). The range from Pmin to Pmax is known as the working pressure rangeof the nozzle.

    Note that the value of K depends on the units used for P and Q. When the K value of a nozzleis referred to, the standard units for P and Q are barand litres per minuterespectively.

    Data Required

    In the library, the following data is required.

    1. A nozzle descriptor to identify the type of nozzle (usually the manufacturers nozzlename is used).

    2. The nozzle K-factor.3. The values of Pmin and Pmax.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    11/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 11 OF 48 REVISION 2.1, SEP 2010

    The data for the input is as follows.

    1. The nozzle status (i.e., on or off). Note that, if a nozzle is off, there is a small solidcircle inside the nozzle symbol (in the schematic diagram), as indicated below.

    2. The nozzle label.3. The input node.4. The name of the nozzle in the library.

    5. The flow rate required through the nozzle.

    Notes

    1. Nozzles do not have to be stored in a library. Instead, they can be defined byspecifying the values of K, Pmin and Pmax. However, when there are several nozzles ofthe same type in the same network, it is easier to define the type in a library, asdescribed above.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    12/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 12 OF 48 REVISION 2.1, SEP 2010

    2. The flow rate required through a nozzle is used in the Design Facility of PIPENETVISION.

    2.6 Deluge Valves

    Typically, users prefer to model a deluge valve as an equipment item, since an equipmentitem requires only an equivalent length. This length value can be either calculated orobtained from the vendor of the deluge valve.

    For the sake of completeness, this section contains an introduction to the deluge valve model.

    Before a deluge valve can be added to a network, the valve must first be defined in theprivate data file (via Libraries | Deluge valves). The dialog box for this option contains a listof defined valve types.

    A descriptor, manufacturer supplied K-factor and X-factor, and bore must be supplied.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    13/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 13 OF 48 REVISION 2.1, SEP 2010

    Modelling Equation

    KQXP /=

    where

    P is the pressure drop across the valve,Q is the (volumetric) flow rate through the valve,K is a constant for the valve,X is a constant for the valve (with typical values being 1 and 2).

    Typical Performance Curves

    2.7 Overboard Dump Valves

    Overboard dump valves (or pressure safety valves) operate with a trigger pressure, PS. Whenthe pressure upstream of the valve is below the trigger pressure, PS, the valve remains shut;on the other hand, when the pressure rises above PS, the valve opens. Once the valve isopen, the upstream pressure stabilises at the trigger pressure, PS.

    In PIPENET VISION, an overboard dump valve is modelled as a special kind of outlet, andthere is no need to model the network downstream of the point at which the trigger pressureis measured.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    14/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 14 OF 48 REVISION 2.1, SEP 2010

    3. Rules Governing Specifications

    The rules that govern specifications in the Spray/Sprinkler Module are important. Thefollowing notes will help the user to understand them. These rules are mainly concerned withapplying specifications to firewater ringmains.

    Before a simulation can be performed, the user must provide PIPENET VISION withinformation about pressures and/or flow rates at a number of nodes in the network. Thesespecifications must obey the rules described in this section. PIPENET VISION runs thesimulation in two phases; namely, the Design Phase and the Calculation Phase.

    The aim of the Design Phase is to find suitable diameters for one or more pipes in thenetwork, so that the fluid velocity in each pipe and the pressure drop per unit length of piperemain within the design criteria. Even if all of the diameters are known, PIPENET VISIONstill performs this phase.

    In the Calculation Phase, PIPENET VISION performs the final analysis calculations.

    For both phases, the user must specify the pressure and/or flow rate in various parts of thenetwork. The user must also specify the input and output nodes in the network. There are twosets of specifications for each simulation: the design-phase specifications and thecalculation-phase specifications. So that the problem is mathematically solvable, these twosets of specifications must obey certain rules. It should be noted that, in some simulations,the user may not be interested in the results of one of the phases; however, both phases arestill run in PIPENET VISION, and so two sets of specifications need to be supplied.

    The specifications have to adhere to the following rules.

    1. There must always be at least one pressure specification. (If there is at least onenozzle in the system, PIPENET VISION will automatically set its outlet pressure to 0bar G, in which case a pressure need not be set by the user.)

    2. The actual number of specifications must obey the rules in the following table.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    15/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 15 OF 48 REVISION 2.1, SEP 2010

    Phase Np Nf

    Design 1 (set by PIPENET VISION) Nio 1

    Analysis Np Nio - Np

    The following parameters are used n the above table.

    Nio is the sum of the number of inputs and the number of outputs (ignoringnozzles),

    Np is the number of pressure specifications,Nf is the number of flow specifications.

    3.1 The Design Phase

    When a network is being designed, it is a general requirement that the velocity of the fluid ineach pipe does not exceed a given value (known as the design velocity of the pipe). Thevelocity of the fluid in a pipe depends on:

    The flow rate through the pipe, The diameter of the pipe.

    It is, therefore, important that all of the pipes are correctly sized, so that the fluid velocity doesnot exceed the design velocity. This problem is addressed in the design phase of thesimulation.

    Given the required flow rates in and out of the network, PIPENET VISION will find optimaldiameters for each pipe in the network, so that the velocity of the fluid does not exceed thedesign velocity. The user must supply the required flow rate for (a) all nozzles and (b) all butone of the input and output nodes in the network. PIPENET VISION can then determine theflow rates required throughout the network, and thus calculate optimal sizes for the pipes.

    The total number of Design Phase flow-rate specifications must be one less than the numberof input/output nodes. This point is especially important for firewater ringmains, as theytypically have more than one input/output node.

    The following points must be noted. By virtue of mass balance, the flow rates through all ofthe input/output nodes can be calculated if the flow rate at one input/output node is leftunspecified. Moreover, the pipe diameters must be sized adequately to handle the requiredflow rates, which is the reason why all the specifications during the design phase are flowrates.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    16/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 16 OF 48 REVISION 2.1, SEP 2010

    The following points should also be noted:

    If desired, the user can set the diameter of some (or all) pipes in the network.PIPENET VISION will then size only those pipes whose diameter has not been set.

    If the user wants certain pipes in the network to be given the same diameter, then thePipe Groupings facility should be used.

    When a pipe (or group of pipes) is being sized, PIPENET VISION will choose thesmallest pipe size that ensures that the design velocity is not exceeded by the fluid.

    In the design phase, it is assumed that all nozzles discharge at the minimum requiredrate. In most systems, there will be some nozzles that actually discharge at a rategreater than the minimum requirement, and so flow rates and velocities in the systemwill rise. Consequently, the velocity of the fluid may rise above the design velocity insome pipes in the system. These pipes will be identified during the calculation phase,

    and a warning will be issued. The user can resolve this problem by setting thediameters of these pipes to be slightly larger than the design diameters.

    In order to size all the pipes in a network, it may be necessary to perform more than onesimulation.

    3.2 The Calculation Phase

    In the calculation phase, all the diameters of the pipes are known, as they are either (a) set bythe user or (b) determined by PIPENET VISION during the design phase. PIPENET VISION

    simulates the behaviour of the network under the pressure and flow-rate conditions set by theuser. All nozzles in the network are assumed to discharge to atmospheric pressure. The usermust supply flow rates and/or pressures at various parts of the network by making CalculationPhase Specifications (which are described in the next section). PIPENET VISION will thencalculate the pressures and flow rates throughout the network.

    The total number of Calculation Phase flow-rate and pressure specifications must be equal tothe number of input/output nodes. This point is especially important for firewater ringmains,as they typically have more than one input/output node. Usually, the pressures at pump inletsare known and the flow rates at outlets are known. However, this is not a strict rule. Forexample, if a pump-selection case is to be run, the pressure and flow rate will typically be

    specified at the most remote output, and the input node would be left simply as an input (butwith no pressure or flow rate specified).

    Typically, the calculation phase is used for one or more of the following purposes:

    Determine what pressures are needed to produce the required flow rates. Select suitable pumps for the network. Check that all demands made on the network can be satisfied. (A warning is issued for

    any nozzle supplying at less than its required rate.)

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    17/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 17 OF 48 REVISION 2.1, SEP 2010

    Check that the fluid velocity in each pipe does not exceed the design velocity of thepipe. (A warning will be issued for any pipe for which the fluid velocity exceeds thedesign velocity.)

    4. The User Interface and the Design and Calculation Phases

    When a calculation is run, a pipe-sizing operation is performed if (a) there are unset pipesizes and (b) the user has requested that the Design Phase be run. However, the user willgenerally perform a pipe sizing-operation, possibly make some changes to the network, andthen perform another pipe-sizing operation, repeating these steps as required. Only when theuser is satisfied will he/she perform a calculation.

    The controls relating to the Design and Calculation Phases are located on the CalculationToolbar:

    The sequence of operations will typically proceed as follows:

    1. The two buttons D and C correspond to the Design and Calculation Phasesrespectively. If a Design Phase is required then the D Button is selected by defaultand the pipe-sizing button (i.e., the third button) is enabled.

    2. The user enters the network and, if he/she requires PIPENET VISION to perform aDesign Phase, then pipes may be entered with undefined bores.

    3. When the user has entered the network he/she will select the Pipe Sizing Button tosize the undefined pipes. The calculated pipe sizes are returned to the user, wherethey are displayed along with other pipe attributes. Note that, if another pipe-sizingoperation is performed, the sizes may change if changes are made to the network.

    4. Steps 2 and 3 are repeated as required.

    5. When the user is satisfied with the network, he/she should select the C Button (inwhich case, the Pipe Sizing Button is disabled) to fix the designed pipe sizes, and thenperform a calculation (by pressing the fourth button on the Calculation Toolbar).

    6. The user can revert to the Design Phase by selecting the D Button; however, the boresof pipes that were fixed in Step 5 do not become unset.

    4.1 Assumptions

    1. The input and output nodes of a network are those points where fluid enters or leavesthe network.

    2. Internal nodes are those nodes that are neither input nodes nor output nodes.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    18/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 18 OF 48 REVISION 2.1, SEP 2010

    3. Sub-networks may be created by the presence of breaks and/or blocks.4. If a node is at one end of a break then it is considered to have an attached pressure

    specification.5. If a node is at one end of a block then it is considered to have an attached flow

    specification.

    6. In the Design Phase, an arbitrary pressure of 50 bar is associated with one of thenodes. Therefore, a user-supplied pressure specification is not used in this phase.

    4.2 Design Phase

    1. There must be one (and only one) pressure specification, which may be applied at aninput node, an output node, or an internal node. This specification is automatically setin PIPENET VISION, and so the user does not need to input it.

    2. In a network, all but one of the input and output nodes must have a flow specification.

    4.3 Calculation Phase

    1. There must be at least one pressure specification.2. Pressure specifications may be applied to input nodes, output nodes, or internal nodes.3. The total number of pressure and flow specifications must be equal to the total number

    of input and output nodes (but note Points 4 and 5).4. If there is at least one nozzle present, a user-supplied pressure specification is not

    required in the Analysis Phase. The rule that the total number of specifications mustequal the total number of input and output nodes still holds.

    5. If the Most Remote Nozzle Option is selected, one flow specification is added to the

    Analysis Phase. Therefore, the user must only provide n - 1 pressure or flowspecifications, where n is the number of input and output nodes.

    4.4 Simple Example

    For a system with two inlets (pumps) and one outlet (deluge system), the specifications wouldbe as follows.

    4.4.1 Specifications for the Two Inlets (Pumps)

    Suppose that both pumps have Design Phase flow rates of 0 and Analysis Phase pressuresof 0 barg.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    19/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 19 OF 48 REVISION 2.1, SEP 2010

    4.4.2 Specification for the One Output (Deluge System)

    For the output node, there are no Design Phase specifications and one Analysis Phase flow-rate specification.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    20/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 20 OF 48 REVISION 2.1, SEP 2010

    5. General Concepts of Fire Protection System

    Fire protection piping systems convey a fire-extinguishing substance from the source of

    supply to devices and equipment for applying it in fire fighting and fire protection.

    Water (owing to its effectiveness, availability, and low cost) is used most extensively as a fire-extinguishing material. Other substances that are piped for fire fighting special types of fireare foam, carbon dioxide (or other inert gases), vaporizing liquid, or dry chemicals in an inertgas carrier.

    The detailed procedures followed by fire-protection specialists in determining anticipatedwater flows, in establishing pipe sizes, and in planning pipe locations and arrangement forparticular private installations are too highly specialised and too limited in application to beallocated space for more than a brief mention here. Detailed information is available in the

    publications included in the references that appear later in this section.

    5.1 Standard, Rules and Regulations

    Some of the rules followed in fire protection systems are as follows.

    1. National Fire protection association rules (NFPA) - most universally used.2. Tariff Advisory Committee rules (TAC) - mostly followed in India.3. Oil Industry Safety Directorate rules (OISD) - for oil and gas industries in India.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    21/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 21 OF 48 REVISION 2.1, SEP 2010

    4. GB Standard - mostly followed in China.

    The generally recognized standards that cover fire-protection piping are those developed bythe National Fire Protection Association and by insurance organizations such as theAmerican Insurance Association, the Factory Mutual Engineering Corporation and the

    Factory Insurance Association.

    The general recognised standards that relate to fire protection piping are listed below. Notethat the fire protection hand books in References 1 and 2 contain much of the information inthe individual standards, and may provide all the information that is required.

    1. NFPA Handbook of Fire Protection, National Fire Protection Association, 60 BatteryMarch St., Boston, Mass. 02110.

    The following standards are all available in the National Fire Protection Association.

    2. Handbook of Industrial Loss Prevention, Factory Mutual Engineering Corporation.3. Standard for the installation of Sprinkler Systems, NFPA No. 13.4. Standard for the installation of Stand Pipe and Hose Systems, NFPA No.14.5. Standard for the installation of Water Tanks for Private Fire Protection, NFPA No. 22.6. Standard for the installation of Centrifugal Fire Pumps, NFPA No. 20.7. Standard for Carbon-dioxide Extinguishing Systems, NFPA No. 12.8. Standard for Foam Extinguishing Systems, NFPA No. 11.9. Standard for Dry Chemical Extinguishing Systems, NFPA No. 17.10. Standard for Outside Protection, NFPA No. 24.

    The following general references relate to certain aspects of the problems that are

    involved in the design and specification of the fire protection system.

    11. Automatic Sprinkler Hydraulic Data, by Clyde M. Wood. Automatic SprinklerCorporation of America.

    12. Hand Book of Cast Iron Pipes, Cast Iron Pipe Research Association, Chicago.13. Approved Equipment and Materials for Industrial Fire Safety, Factory Mutual

    Engineering Corporation.14. Fire Protection Equipment List, Underwriter Laboratories Inc, Chicago.15. List of Inspected Appliance and Equipment and Materials, Underwriter Laboratories

    of Canada.

    5.2 Tariff Advisory Committee

    The Tariff Advisory Committee has compiled rules to provide minimum requirements for fixedwater spray systems, based on good engineering practices. While formulating the rules, dueconsideration has been shown to the International Standards.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    22/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 22 OF 48 REVISION 2.1, SEP 2010

    According to the TAC Manual, full details on the Common Requirements to High VelocityWater Spray and Medium Velocity Water Spray Systems are explained in the TAC manual,and they are:

    1. Water supplies.

    2. Pumps - general requirements for electric driven, compression ignition engine drivenpumps, pump room, etc.

    3. Detection system.4. General requirements.5. Piping.6. Fittings.7. Deluge valves.8. Drainage.

    Similarly, high-velocity water-spray systems and medium-velocity water-spray systemsare also explained in TAC Manual.

    5.3 Oil Industry Safety Directorate (OISD)

    For Fire Protection Facilities for Petroleum Refineries & Oil/Gas processing plants,the Oil Industry Safety Directorate staffed from within the industry for formulating andimplementing a series of self regulatory measures aimed at removing obsolescence,standardizing and upgrading the existing standards to ensure safer operations. OISDconstituted a number of committees comprising of experts nominated from the industry todraw up standards and guidelines on various areas of concern.

    This standard covers the design criteria and the details of the various fire protection facilitiesto be provided in petroleum refineries and oil/gas processing plants.

    5.4 Classification of Petroleum Products

    5.4.1 General Classification of Petroleum Products

    Petroleum products are classified according to their closed-cup flash points, as follows:

    Class 'A' Petroleum: Liquids that have a flash point below 23 degrees C.

    Class 'B' Petroleum: Liquids that have a flash point of 23 degrees C or above, but below 65degrees C.

    Class 'C' Petroleum: Liquids that have flash point of 65 degrees C or above, but below 93degrees C.

    Excluded Petroleum: Liquids that have a flash point of 93 degrees C or above. Liquefiedgases, including LPG, do not fall under this classification but form a separate category.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    23/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 23 OF 48 REVISION 2.1, SEP 2010

    5.4.2 Classification for Heated Products

    At locations where the handling temperatures are higher than the flash point of the product incircumstances where the product handled is artificially heated to above its flash point, a class'C' product shall be considered as a Class 'B' product and a Class 'B' product shall be

    considered as a Class 'A' product.

    5.5 Classification Of Fires

    Class 'A' Fires: Fires involving combustible materials of organic nature, such as wood,paper, rubber and any plastics, etc., where the cooling effect of water is essential forextinction of such fires.

    Class 'B' Fires: Fires involving flammable liquids, petroleum products, or the like, where ablanketing effect is essential.

    Class 'C' Fires: Fires involving flammable gases under pressure, including liquefied gases,where it is necessary to inhibit the burning gas at a fast rate with an inert gas, powder orvaporizing liquid for extinguishment.

    Class 'D' Fires: Fires involving combustible materials such as magnesium, aluminium, zinc,sodium, potassium, when the burning metals are reactive to water and water-containingagents, and in certain cases carbon dioxide, halogenated hydrocarbons and ordinary drypowders. Special media and techniques are required to extinguish these fires.

    5.6 Fire Protection Philosophy

    The Fire Protection Philosophy is based on Loss Prevention and Control. The importance ofadequate fire protection facilities for hydrocarbon processing plants need not be emphasised,as none of the plant is absolutely safe (because of the inherent hazard it carries). A fire in onepart/section of the plant can endanger other sections of the plant as well. If a fire breaks out, itmust be controlled/extinguished as quickly as possible, to minimize the loss to life andproperty and to prevent further spread of fire.

    5.6.1 Design Criteria

    The following shall be the basic design criteria for a fire protection system.

    1. Facilities should be designed on the basis that city firewater supply is not availableclose to the installation.

    2. Fire protection facilities shall be designed to fight two major fires simultaneously,anywhere in the installation. Fire-water requirements will be decided as per guidelinesgiven in the Annexure of OISD.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    24/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 24 OF 48 REVISION 2.1, SEP 2010

    5.6.2 Fire Water System

    Water is an essential medium for fire protection, and is the most important medium availablefor this purpose. Water is used for fire extinguishment, fire control, cooling of equipment andprotection of equipment and personnel from heat radiation. For these purposes, water is usedin various forms, such as straight jet, water fog, water curtain, water spray, deluge/sprinkler,for foam making, etc. The main components of the fire water system are fire water storage,fire-water pumps, and distribution piping network, along with hydrants and monitors.

    5.6.3 Design Basis

    The fire water system in an installation shall be designed to meet the fire water flowrequirement for fighting two fires simultaneously, requiring largest water demand.

    5.6.4 Fire Water DemandVarious areas that can be under fire shall be considered, and fire water demand for each areashall be calculated on the design basis.

    Consider different cases (for example, the fire water rate of five different cases), and calculatethe flow rate for each case. Then, the total design fire water rate is the sum of water rates forthe two major fires.

    6. Additional Information on the User Interface

    6.1 Spray Options

    The dialog box obtained from Options | Module options allows the user to control a numberof modelling and calculation options for the Spray/Sprinkler Module.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    25/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 25 OF 48 REVISION 2.1, SEP 2010

    6.1.1 Pressure Model

    The two main options for the pressure model are the Darcy Equation and the Hazen-WilliamsEquation.

    The Hazen-Williams Equation must be used for water and foam solution systems, and theDarcy Equation must be used for foam concentrate systems.

    6.1.2 Design Rules

    The fire protection systems follow norms including:

    NFPANFPA 96FOCOLDFOC

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    26/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 26 OF 48 REVISION 2.1, SEP 2010

    These norms are in-built into the Spray/Sprinkler Module.

    6.1.3 Spray or Sprinkler Mode

    There are two modes provided in this module. In the spray mode, all the nozzles input is open

    by default; and in the sprinkler mode, all the nozzles input are closed by default.

    6.2 Pipe Types

    In the Spray Module, all pipes in a network must be of a specified type. A pipe type isassociated with a pipe schedule, and this schedule must already exist before the pipe typecan be created. There is an optional lining definition, which may be provided by specifying thematerial and the lining thickness.

    Please note that, if no pipe type is defined, the Pipe Drawing Tool on the toolbar is disabled,

    and the message No Pipe Type appears in the status bar at the bottom of the screen. Thismessage will disappear when a pipe type is defined, in which case, the Pipe Button will beenabled.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    27/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 27 OF 48 REVISION 2.1, SEP 2010

    6.2.1 Creating a New Pipe Type

    Use the following procedure to create a new pipe type.

    1. Click on the New Button.

    2. Select the associated schedule from the drop-down list provided. Note that a nameand a description are supplied automatically.

    3. Provide a C-factor for the pipe schedule. The C-factor value will be taken intoconsideration when the Hazen-Williams Formula is selected for performing thecalculation.

    4. Supply velocities for all bores that are to be provided by the schedule. Bores can bemarked as available or unavailable by selecting the bore in the bottom right-handcorner of the window and clicking on the Use in design Button or Avoid in designButton as appropriate (and the default is for all valid bores to be marked as available).

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    28/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 28 OF 48 REVISION 2.1, SEP 2010

    5. Linings can also be provided using the drop-down menu (in which case, the thicknessof the lining must be given).

    6. Click on the Apply Button to complete the creation of the pipe type.

    6.2.2 Editing an Existing Pipe Type

    1. Select the pipe type from the top left-hand corner of the window.

    2. Make the required changes to the pipe-type parameters.

    3. Click on the Apply Button to commit the changes.

    6.2.3 Deleting a Pipe Type

    1. Select the pipe type from the top left-hand corner of the window.

    2. Click on the Delete Button.

    Note that a pipe type cannot be deleted if it is in use.

    6.3 Libraries

    Libraries are used for storing items that are to be used either (a) several times in the samenetwork or (b) in different networks.

    The library is associated with the data file, and is opened when the data file is open. For theSpray/Sprinkler Module, a library can contain the following items.

    1. Pipe schedules,2. Nozzles,3. Pumps (Coefficients Known and Coefficients Unknown),4. Linings,5. Deluge valves.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    29/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 29 OF 48 REVISION 2.1, SEP 2010

    There is only one local user library, which has the file extension .SLF, and replaces all of theseparate library files from previous modules. While a data file is open, entries can be added,deleted or edited using the Library Editor Dialog. PIPENET VISION automatically saves thelibrary file when the Sunrise Data File or .SDF file is stored. The name of the library file isderived from the name of the Sunrise Data File.

    6.4 Pipe Schedules

    Pipe schedules can be viewed using Libraries | Schedules. There are about eight built-inpipe schedules in PIPENET VISION. The user is also able to define other pipe schedules.

    On the left-hand side of the window is a list of available schedules, both built-in and user-defined. If you select any item in this list, the properties of the schedule are displayed on theright-hand side of the window.

    At the top right-hand corner, there are three fields common to all library editors:

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    30/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 30 OF 48 REVISION 2.1, SEP 2010

    1. The name of the schedule as it appears in pop-up menus (the length of this namebeing limited to 20 characters).

    2. An optional longer description.

    3. The source of the schedule, which may be one of the following: Built-in schedule provided with the Spray/Sprinkler Module - built-in schedules

    cannot be edited. Local user library - these items may be edited whilst a network is open. System library - these items can only be edited using the External System Library

    Editor.

    Below these three fields is a field that contains the roughness; and, below that field, is a gridshowing the standard nominal sizes and the corresponding internal diameters. If the nominaldiameter is "unset" then the corresponding nominal diameter is not included in the schedule.

    Nominal diameters are greyed-out, indicating that their value is fixed; however, if you scrolldown to the end of the grid, you can see 10 user-defined sizes (for which both the nominaland internal bores can be edited).

    The roughness value and the diameters are displayed in the user-specified units.

    6.4.1 Adding a New Schedule

    To add a new schedule, select the New Button in the bottom left-hand corner of the dialogbox, enter the desired values (if the Description Field is left empty, the description will becomethe same as the schedule name). Next, enter the roughness and the diameters, and thenselect either (a) the Apply Button, to accept the new schedule, or (b) the Cancel button, toabort.

    6.4.2 Editing an Existing Schedule

    From the left-hand side of the window, select the schedule that is to be edited, enter thedesired changes, and then select the Apply Button to accept the changes.

    6.4.3 Deleting an Existing Schedule

    Select the schedule to be deleted (on the left-hand side of the window), and then click on theDelete Button.

    6.5 Nozzles

    The nozzles in PIPENET VISION correspond to the spray or sprinkler nozzles, which areopen to the atmosphere. To set the nozzle attributes, the user can either enter the valuesdirectly in the schematic or obtain them from the library.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    31/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 31 OF 48 REVISION 2.1, SEP 2010

    The nozzle library dialog box can be accessed through Libraries | Nozzles.

    To view a library nozzle, select the required nozzle from the left-hand side of the window, andsee its properties on the right-hand side. To delete a nozzle, select the nozzle (in the left-handside of the window) and then click on the Delete Button.

    To add a new nozzle:

    1. Click on the New Button.

    2. Provide a unique name for the nozzle and an optional description.

    3. Enter the values for the K-factor, minimum pressure, and maximum pressure.

    4. Click on the Apply Button to add the nozzle to the library.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    32/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 32 OF 48 REVISION 2.1, SEP 2010

    6.6 Linings

    Linings for the pipes are provided to protect the inner surface of the pipe from corrosion,which is caused by the fluid medium. In most fire systems, fluid remains stagnant, resulting in

    a higher rate of corrosion. The linings can be concrete, epoxy, thermo setting plastic,asbestos, etc.

    To view a library lining, select the required lining from the left-hand side of the window (and its

    properties are displayed on the right-hand side). To delete a lining, select the lining, and thenclick on the Delete Button.

    To add a new lining:

    1. Click on the New Button.

    2. Provide a unique name for the lining and an optional description.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    33/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 33 OF 48 REVISION 2.1, SEP 2010

    3. Enter a value for the roughness.

    4. Click on the Apply Button to add the lining to the library.

    6.7 Deluge Valves

    Typically, deluge valves are modelled as equipment items. As mentioned earlier in thischapter, deluge valves still available in PIPENET VISION for historical reasons. Without thismodel, it might not be possible to open some older data files. For the sake of completeness,the method of inputting deluge valves is described below.

    To view a library deluge valve, select the required deluge valve from the left-hand side of thewindow, and see its properties on the right-hand side. To delete a deluge valve, select thedeluge valve, and then click on the Delete Button.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    34/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 34 OF 48 REVISION 2.1, SEP 2010

    To add a new deluge valve:

    1. Click on the New Button.

    2. Provide a unique name for the deluge valve and an optional description.

    3. Enter the values for the K-factor, X-factor and bore.

    4. Click on the Apply Button to add the deluge valve to the library.

    7. Other Useful Features of PIPENET VISION

    Any description of PIPENET VISION would be incomplete without the following features beingcovered.

    7.1 Global and Local Edit

    This functionality is applicable to the Data Window. It is best illustrated by an example.(Although the example itself is taken from the Standard Module, exactly the same principleapplies in the case of the Spray/Sprinkler Module.)

    Change the roughness of all pipes from 0.06 mm to 0.08 mm.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    35/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 35 OF 48 REVISION 2.1, SEP 2010

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    36/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 36 OF 48 REVISION 2.1, SEP 2010

    A local edit can be performed in a similar manner. In this case, the user must select the pipesto which the copied value is to be pasted.

    7.2 Sorting in Columns in the Data Window

    This invaluable feature can be used, for example, to determine the pipe with the maximumvelocity or the maximum pressure. This sorting can be performed in the data window.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    37/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 37 OF 48 REVISION 2.1, SEP 2010

    Select theResults Tab

    Click on the headingto sort the column

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    38/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 38 OF 48 REVISION 2.1, SEP 2010

    7.3 Copy/Paste to a Spreadsheet

    Copy the data using Edit/Copy as shown below.

    Click here toselect the results

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    39/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 39 OF 48 REVISION 2.1, SEP 2010

    Open the Spreadsheet program and paste in the results.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    40/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 40 OF 48 REVISION 2.1, SEP 2010

    7.4 NFPA Style of Output

    Some fire engineers prefer to use the style of presentation shown in the NFPA rules. Thisstyle is available in PIPENET VISION, and is obtained (after a calculation) by using

    Calculation | Browse, and then selecting the NFPA Submittal Option.

    Extracts from such an output are shown below.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    41/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 41 OF 48 REVISION 2.1, SEP 2010

    SUMMARY VALUES

    Title

    Calculation date 29-Sep-2010 14:09

    Calculator PIPENET VISION Spray calculator, version 4.4

    Friction loss formula Hazen-Williams

    Design standard NFPA

    Total number of sprinkler heads 3

    Number of sprinkler heads on 3

    Total sprinkler discharge (l/min) 455.255

    Total non-sprinkler output flow (l/min) 0.000

    Total input flow (l/min) 455.255

    Highest fluid velocity (m/sec) 2.667

    Pressure at input nodes See NODE ANALYSIS table

    NODE ANALYSIS

    Node tag Elevation (m) Node Type Pressure (Bar G) Discharge (l/min) Notes

    1 0.00 Input 1.704 0.000

    2 0.00 1.701 0.000

    3 0.00 4.709 0.000

    4 5.00 4.151 0.000

    5 4.50 Sprinkler 4.190 153.527 Nozzle label: 201

    6 5.00 4.053 0.000

    7 4.50 Sprinkler 4.093 151.728 Nozzle label: 202

    8 5.00 3.960 0.000

    9 4.50 Sprinkler 4.000 150.000 Nozzle label: 203

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    42/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 42 OF 48 REVISION 2.1, SEP 2010

    PIPE INFORMATION

    Node 1

    Node 2

    Elev 1(m)

    Elev 2

    (m)

    K factor

    Pipe label

    Nozzle label

    Flow added (q)(l/min)

    Total flow (Q)

    (l/min)

    Nominal ID(milli.m.)

    Actual ID

    (mm)

    Fittings -quantity,type, andequivalentlength (m)

    L (m)

    F (m)

    T (m)

    C factor

    Pf per m

    (Bar)

    Pt (Bar G)

    Pe (Bar)

    Pf (Bar)

    Notes

    1

    2

    0.00

    0.00 1

    455.255

    455.255

    80

    73.990

    0.500

    0.000

    0.500

    120.0

    0.006

    1.701

    0.000

    0.003

    Vel = 1.765 m/sec

    3

    4

    0.00

    5.00 2 455.255

    80

    73.990

    1xE=2.13 10.000

    2.134

    12.134

    120.0

    0.006

    4.151

    -0.489

    0.068

    Vel = 1.765 m/sec

    4

    6

    5.00

    5.00 3 301.728

    50

    48.997

    5.000

    0.000

    5.000

    120.0

    0.020

    4.053

    0.000

    0.098

    Vel = 2.667 m/sec

    4

    5

    5.00

    4.50

    75.00

    4201

    153.527

    40

    37.973

    0.500

    0.000

    0.500

    120.0

    0.019

    4.190

    0.049

    0.010

    Vel = 2.259 m/sec

    6

    8

    5.00

    5.00 5 150.000

    40

    37.973

    5.000

    0.000

    5.000

    120.0

    0.019

    3.960

    0.000

    0.093

    Vel = 2.207 m/sec

    6

    7

    5.00

    4.50

    75.00

    6202

    151.728

    40

    37.973

    0.500

    0.000

    0.500

    120.0

    0.019

    4.093

    0.049

    0.009

    Vel = 2.233 m/sec

    8

    9

    5.00

    4.50

    75.00

    7203

    150.000

    40

    37.973

    0.500

    0.000

    0.500

    120.0

    0.019

    4.000

    0.049

    0.009

    Vel = 2.207 m/sec

    PIPE FITTINGS CODES

    HE Standard 45Elbow E Standard 90Elbow LE Long radius 90Elbow

    T Tee or Cross (Flow turned 90) G Gate Valve C Swing Check Valve

    NR Non-return Valve BV Ball Valve B Butterfly Valve

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    43/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 43 OF 48 REVISION 2.1, SEP 2010

    7.5 Elevation Error Correction

    Elevation mismatch errors in firewater ringmains are some of the most difficult problems toresolve. However, PIPENET VISION has tools to assist the user in resolving such problems.

    Let us consider the highlighted pipe in the following simple network.

    The attributes of this pipe are as shown in the Properties Window below.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    44/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 44 OF 48 REVISION 2.1, SEP 2010

    Let us suppose that the user has made an error, and has input an elevation of 1 metre(instead of 0 metres). We now change the elevation value to 1 metre, and then illustrate thetools in PIPENET VISION that can be used to resolve this elevation error.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    45/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 45 OF 48 REVISION 2.1, SEP 2010

    If we click on the Check Network Button, a diagnostic appears. However, in some cases,there is little information on the exact location of the error.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    46/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 46 OF 48 REVISION 2.1, SEP 2010

    We now double click on an error message (shown in red), which indicates an elevation error.All of the components in the loop in which the elevation error occurs now appear in red. Notethat the user must ensure that suitable colouration-display rules are selected; for example, ifNone is selected, it is possible to see the red loop; otherwise, the loop may not be colouredred.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    47/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 47 OF 48 REVISION 2.1, SEP 2010

    We now click on the Graphs Tab in a Data Window. The elevation profile along the loop isthen shown in the Data Window, starting and ending at Node 1. Note that the node numberscan be displayed on the profile.

  • 7/22/2019 Pipenet Vision Spraysprinkler Module

    48/48

    PIPENET VISION TRAINING MANUAL SPRAY: CHAPTER 1PAGE 48 OF 48 REVISION 2.1, SEP 2010

    Alternatively, we can click on the Common Height Errors Button on the Diagnostic Window.In this case, only the pipes common to more than one problem loop are shown.

    In some cases, this approach leads to fewer pipes for which the elevations need to bechecked.

    Common HeightErrors Button