kW PV System Cover Sheet
NOTE: 2016 CaliforniaResidential Code and 2016 California Electrical Code.
6.3 DC / 5.0 AC 10-30-19
As the home owner of the subject project, I certify that I requesting to install the solar photovoltaic system shown on these plans.
_______________________________ Home Owner Signature __________________________Home Owner’s Name (Printed)
1/16” = 1’ DRAWN BY
James Smith12345 E. Main St.
Anytown, AZ. 85268
12345 E. Main St.Anytown, AZ. 85268
**Utility requires 24hr access to the Utility Disconnect Switch,Utility Production Meter, Backup Load Production Meter,and Backup Load Disconnect Switch. N
S
NOTE: SYSTEM DESIGNEDIN ACCORDANCE WITH THE2017 N.E.C.
PHOTOVOLTAIC SYSTEM SIZE
RESIDENTIAL GROUND MOUNTED PHOTOVOLTAIC SYSTEMDC SYSTEM SIZE: 6.20kWAC SYSTEM SIZE: 5.0kW
PHOTOVOLTAIC SYSTEM COMPONENTS
ITEM DETAIL QTY
MODULE
INVERTER
RACKING SYSTEM
PEIMAR SG315MSOLAREDGE SE5000H-US
UNIRAC RACKING
201
1
VICINITY MAP
SITE MAP
AUTHORITY HAVING JURISDICTION
BUILDING AUTHORITY
ZONING/PLANNING AUTHORITY
ELECTRICAL UTILITY COMPANY
JEFFERSON COUNTY
JEFFERSON COUNTY
Xcel ENERGY
DESIGN CRITERIA
DESIGN WIND LOAD
ELEVATION
DESIGN SNOW LOAD
7,560 FT.
130 MPH
42.9 PSF
EXPOSURE CATEGORY B
12
13
14 Solar System Placards
1
2
3
4
5
6
7
Plant Location
Electrical 1 - Line
Electrical 3 - Line
PV Module Specs
Inverter Specs
8
Site Plan
9
Mounting Specs
10
Solar System Placards
11
Notes Page
Solar Module Layout
Derating Calculations
SHEET INDEX
Solar String Layout
Optimizer Specs
SAMPLE
DO NOT SCALE DRAWINGS
SIZE DRAWING NO.
SCALE REV. SHEET OFNA
ACODE INTENT NO.
DRAWN BY
CHECKED
ENGINEER
M.C.R.
LASTEST REV.
APPROVALS DATE
0002
N
S
JH
kW PV System Site Plan
SES
PVDisconnect
ToSolar
Modules Array (20)
30A
Inverter
1.91"
75” MAX.48” MIN.
6.3 DC / 5.0 AC
53’
53’
10-30-19
VALLE
Y
VALLEY
RID
GE
RID
GE
RIDGE
RID
GE
RID
GE
VALLEY
VALLE
Y
FIRE PATHWAY
Inve
rter
AC
Dis
conn
ect
Mai
n S
ervi
ceP
anel
DRIVEWAY
Property Line
Barn Owl Ct.
137’
63’
4’
4.6’
5’
14’
134’
DRAWN BY
Uplift and Load Calculations
Module Specifications Mount InformationPanel Brand: Peimar Model: SG315M-BF Brand: UniracPanel Square Foot (SF) : 17.92 SF Model: Tile HoofTotal Number of Panels : 20 Weight 39.7 LBS ea. Lag Bolt Length : 3 IN. 3 IN. Min. Total Panels Sq.Ft. : 358.4 SF No. of PV Mounts : 38Total Panels Weight : 794 LBS Pull Stength : 203 PSITotal Racking Weight : 127.1 LBS Mounts X Min. Length X Pull : 23142Wind Speed : 110 MPH
Wind Load x Total Panel Sq.Ft. : 10752.09 LBS Load
Distributed Load CalculationTotal Weight / SF : 2.571 PSF
Point Load Calculation Roof Mount DataTL Weight / # PV Mounts & Racking : 24.24 LBS per PV Mount Total PV Mounts : 38
Weight @ ea. Mount Point : 20.9 LBSROOF Weight per Sq.Ft. : 2.58 PSFRoofing Material : Tile RoofRoof Construc�on : 2" X 8" Trusses @ 24" CentersNo. Modules X Module Sg.Ft. : 358.41
Wind Load : 30 PSF
James Smith12345 E. Main St.
Anytown, AZ. 85268
SAMPLE
220.82 (A) Dwelling Unit
Single 120/240-volt 200 Amps Service.
220.82 (B) General Loads
The general calculated load shall be not less than 100 percent
of the first 10 Kva plus 40 percent of the remainder of the
following loads:
220.82 (B)(1)
3 volt-amperes/sq. ft. 3580 sq. ft. x 3 VA = 10740 VA
220.82 (B)(2)
1500 volt-amperes for each 2-wire, 20-ampere
small appliance branch circuit and each laundry
circuit.
Small Appliance 1 = 1500 VA
Laundry Circuit 1 = 1500 VA
TOTAL 13740 VA
= 10000 VA
= 800 VA
TOTAL 10800 VA
220.82 (B)(3)
The namaplate rating of the following:
a. All appliances that are fastened in place, permanently
connected, or located to be on a specific citcuit.
b. Ranges, wall-mounted ovens, counter-mounted
cooking units.
c. Clothes dryers that are not connected to the laundry
circuit specified on 220.80 (B)(2).
d. Water Heaters.
VA
6000 VA
4750 VA
7200 VA
VA
VA
VA
VA
VA
17950 VA
Smith Residential Load Calculations
WH
1500 VA x
1500 VA x
Appliance Name
Dryer
Range
TOTAL
100 % of the first 10 Kva
40 % of the remainde loads
220.82 (B)(4)
The nameplate ampere of Kva rating of all permanently
connected motors not included in 220.82 (B)(3)
VA
4950 VA
3500 VA
VA
VA
VA
VA
VA
VA
8450 VA
220.82 ( C ) Heating and Air-Conditioning Load
The largest of the following six selections (load in Kva)
shall be included:
(1) 100 percent of the nameplate rating(s) of the air conditioning
and cooling.
(2) 100 percent of the nameplate rating(s) for the heat pump when
the heat pump is used without any supplemental electric heating.
(3) 100 percent of the nameplate rating(s) of the hat pump compressor
65 percent of the supplemental electric heating for central
space-heating systems. If the heat pump compressor is prevented
from operating at the same time as the supplementary heat, it
does not need to be added to the supplementary heat for the
total central space heating load.
(4) 65 percent of the nameplate rating(s) of electric space heating if
less than four separately controlled units.
(5) 40 percent of the nameplate rating(s) of electric space heating if
four or more separately controlled untis.
(6) 100 percent of the nameplate ratings of electric thermal storage
and other heating systems where the usual load is expected to
be continuous at the full nameplate value. Systems qualifying
under this selection shall not be calculated uns any other
selection in 220.82 ( C ).
Percentage VA
VA
VA
0 VA
37200 VA
155 A
TOTAL
Total Computed Load =
Computed Load/240 V =
TOTAL
Load
Motor Loads
AC#1
AC#2
DO NOT SCALE DRAWINGS
SIZE DRAWING NO.
SCALE REV. SHEET OFNA
ACODE INTENT NO.
DRAWN BY
CHECKED
ENGINEER
M.C.R.
LASTEST REV.
APPROVALS DATE
0003
JH
kW PV System De-Rate6.3 DC / 5.0 AC 10-30-19
DRAWN BY
NOTES ON PAGE 7
James Smith12345 E. Main St.
Anytown, AZ. 85268
NOTES ON PAGE 8
De-Rating if required
SAMPLE
DO NOT SCALE DRAWINGS
SIZE DRAWING NO.
SCALE REV. SHEET OFNA
ACODE INTENT NO.
DRAWN BY
CHECKED
ENGINEER
M.C.R.
LASTEST REV.
APPROVALS DATE
0004
JH
kW PV System String Layout
Performance under standard test conditions (STC*)
Peimar SG315M-BF 315 Watt Solar Module
Maxium Power Pmax 315 Wp
Open Circuit Voltage Voc 40.93 V
Max. Power Point Voltage Vmp 33 V
Short Circuit Current Isc 9.82 A
Max. Power Point Current Imp 9.57 A
Solar Module Specifications
6.3 DC / 5.0 AC 10-30-19
DRAWN BY
ARRAY TO INVERTER
(2) PV SOURCE CIRCUITS(4) #10 AWG PV Wire (1) #8 AWG THWN-2 GND
PV SOURCE CIRCUITSTO FUSE COMBINER BOXDC DISCONNECT SWITCH(INTEGRAL TO INVERTER)
DO NOT GROUND PV NEGATIVE (-)
SolarEdge Optimizeradded to each panel perillustration.
G
+
-
+- +- +- +- +- +- +- +-+-
+
-
+- +- +- +- +- +- +- +-+-
+-
+-
James Smith12345 E. Main St.
Anytown, AZ. 85268
NOTES ON PAGE 8
SAMPLE
3’ Distanceto Ridge MIN.
Anchor Horizontal72” Spacing
Rail Ridge
Existing RafterLayout
Unirac PV Mount and Hardware System Diagram
Portrait PositionUnirac Mounting Hardwarefor 3 Arrays
Typical Layout: 1 of 3
SolarModule
3’ Distanceto Edge
Unirac 315168 Rails 10Splices 303018 6Mid 302030 34End 302035M 12FTRH9038-1 Tile Hook 38
Module Layout
DO NOT SCALE DRAWINGS
SIZE DRAWING NO.
SCALE REV. SHEET OFNA
ACODE INTENT NO.
DRAWN BY
CHECKED
ENGINEER
M.C.R.
LASTEST REV.
APPROVALS DATE
0005
JH
kW PV System Module Layout
SolarModule
West Side of Roof
3’ Distanceto Edge
3’ Distanceto Ridge
SolarModule
Rail
Existing RafterLayout
Ridge
Anchor Horizontal72” Spacing
South Side of Roof
6.3 DC / 5.0 AC 10-30-19
0.42"3’
ELEVATIONNTS
4x12 Roof Pitch
78
”
19.5’
MIN.
30.05°18.45 Degrees
26.6’
65
”
MIN
MIN
DRAWN BY
James Smith12345 E. Main St.
Anytown, AZ. 85268
NOTES ON PAGE 8
SAMPLE
DO NOT SCALE DRAWINGS
SIZE DRAWING NO.
SCALE REV. SHEET OFNA
ACODE INTENT NO.
DRAWN BY
CHECKED
ENGINEER
M.C.R.
LASTEST REV.
APPROVALS DATE
0006
JH
kW PV System 1 - Line6.3 DC / 5.0 AC 10-30-19
DRAWN BY
James Smith12345 E. Main St.
Anytown, AZ. 85268
Performance under standard test conditions (STC*)
Peimar SG315M-BF 315 Watt Solar Module
Maxium Power Pmax 315 Wp
Open Circuit Voltage Voc 40.93 V
Max. Power Point Voltage Vmp 33 V
Short Circuit Current Isc 9.82 A
Max. Power Point Current Imp 9.57 A
Solar Module Specifications
EXISTING UTILITYSERVICE
240VAC, 200A 1 PHASE
Note: Maximum recommended voltage drop
between inverters and Main AC Service Panel is1.5%. Exact sizes to be determined by
installer analysis including factors such asambient temperature, cable distance, max.
current, etc.
EXISTING LOADS(TYPICAL)
200A
CT RATEDBI-DIRECTIONALUTILITY METER
Backfeed breakerLoad side connection,
per NEC 690.64:(705.12 (D-5)
30A
FRAME GROUND ONLY
+ +MPPT
DC
AC+MPPT
4 - #10 AWGCU PV Wire
4 - #10 AWG CU THWN-2,1 - #8 CU GND
1” EMT CONDUIT(See Note)
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
Eaton Cutler DG221URB240VAC, NEMA 3R,
2 POLE, 30 AMP
or Suitable Substitute
3 - #8 AWG CU THWN-2 wire,L1, L2, Neutral
1 -#8 CU GEC GND1” EMT CONDUIT
(See Note)
5000 Watt Solaredge INVERTER
SE5000H-US
400 VDC to 240 VAC
NOTES ON PAGE 8
SAMPLE
DO NOT SCALE DRAWINGS
SIZE DRAWING NO.
SCALE REV. SHEET OFNA
ACODE INTENT NO.
DRAWN BY
CHECKED
ENGINEER
M.C.R.
LASTEST REV.
APPROVALS DATE
0007
JH
kW PV System 3 - Line
NOTES ON PAGE 8
SOLAR ARRAY20 - 315 watt panels2 Strings / 10 Panels
Note: Maximum recommended voltage drop
between inverters and Main AC Service Panel is1.5%. Exact sizes to be determined by
installer analysis including factors such asambient temperature, cable distance, max.
current, etc.
EXISTING UTILITYSERVICE
240VAC, 200A 1 PHASE
Earth Ground
+- G
4 - #10 AWG CU THWN-2,1 - #8 CU GND
3/4” EMT CONDUIT(See Note)
+- G
G
N
Main SES Panel(240Vac 1 Phase)
200A
EXISTING LOADS(TYPICAL)
30A
1 -#8 CU GEC
Ampacity correction factor for conductors:Free air per NEC table 310.15(B)(17)
#10 AWG THWN-2 55 Amps x .65 = 35.75 Amps#6 AWG THWN-2 105 Amps x .65 = 68.3 Amps#4 AWG THWN-2 140 Amps x .65 = 91 Amps
1 -#8 BARE CU GND1 -#8 BARE CU GEC
FRAME GROUND ONLY
L2
N
L1
DC
AC L1
L2
N
MPPT
G
-
+
.
.
.
IRREVSIBLE COMPRESSION-TYPECONNECTOR PER NEC 250.64 (C) (1)
3 - #8 AWG CU THWN-2 wire,L1, L2, Neutral
1 -#8 CU GEC GND1” EMT CONDUIT
(See Note)
Backfeed breakerLoad side connection,
per NEC 690.64:(705.12 (D-5)
5000 Watt Solaredge INVERTER
SE5000H-US
400 VDC to 240 VAC
Inverter Specifications
Recommended Max. PV Power (Module STC) 7,700WMax. DC Voltage 500VPeak Power Tracking Voltage 300 - 480VDC Max. Input Current @ 240VAC 16.5AAC Max. Output Current @ 240VAC 21APV Start Voltage (adjustable) 300VMax. AC Power Output @ (240VAC) 5000WNormal AC Power Output (240VAC) 5000WPeak Inverter Efficiency 98.3%CEC Weighted Efficiency 97.5%
SE5000H- US
SOLAREDGE
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
Eaton Cutler DG221URB240VAC, NEMA 3R,
2 POLE, 30 AMP
or Suitable Substitute
Performance under standard test conditions (STC*)
Peimar SG315M-BF 315 Watt Solar Module
Maxium Power Pmax 315 Wp
Open Circuit Voltage Voc 40.93 V
Max. Power Point Voltage Vmp 33 V
Short Circuit Current Isc 9.82 A
Max. Power Point Current Imp 9.57 A
Solar Module Specifications
6.3 DC / 5.0 AC 10-30-19
DRAWN BY
James Smith12345 E. Main St.
Anytown, AZ. 85268
SAMPLE
DO NOT SCALE DRAWINGS
SIZE DRAWING NO.
SCALE REV. SHEET OFNA
ACODE INTENT NO.
DRAWN BY
CHECKED
ENGINEER
M.C.R.
LASTEST REV.
APPROVALS DATE
0007
JH
kW PV System Notes
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
14
15
16
17
18
19
20
21
13.
6.3 DC / 5.0 AC 10-30-19
DRAWN BY
James Smith12345 E. Main St.
Anytown, AZ. 85268
SAMPLE
Via Creta 72, 25124 Brescia, ITALY � www.peimar.com • [email protected]
PEIMAR monocrystalline solar panels, produced using a combination of innovative production
processes and advanced engineering techniques, provide customers with maximum output and super
high performance (over 20% efficiency). This allows fewer panels to be used to generate more energy,
ideal if space is restricted or environmental conditions are challenging. Modern design, using matching
black cells and frames and a very long lifespan ensure this monochrystalline are a great option.
FRAME
BACKSHEET
JUNCTION BOX
CELLS
HIGH EFFICIENCY LINE
POSITIVE POWER OUTPUT TOLERANCE
HAILSTORM RESISTANCE
ANTI-REFLECTIVE GLASS
MODULE FIRE PERFORMANCE: CLASS I
QTY:
60 CELLS
TYPE:
MONO 5BB PERC TECHNOLOGY
DIMENSION:
156x156 mm / 6x6”∗Thanks to the use of PERC cells, PEIMAR modules are able to reach even higher efficiences,
as they facilitate the light imprisonment in close proximity to the rear surface and optimise the
electron capture.
30 YEAR LINEAR POWER WARRANTY ANNI
GARANZIA LINEARE PRODUZIONE
20 YEAR PRODUCT WARRANTY ANNI
GARANZIA PRODOTTO
60MONO
“MADE IN ITALY” MODULE
PERC TECHNOLOGY*Passivated Emitter and Rear Cell
ASSURED ENERGYProduct Liability Insurance QBE
SG315M (BF)
IP67IP67
Nominal Output (Pmax)
Flash Test Power Tolerance
Voltage at Pmax (Vmp)
Current at Pmax (Imp)
Open Circuit Voltage (Voc)
Short Circuit Current (Isc)
Maximum System Voltage
Maximum Series Fuse Rating
Module Efficiency
ELECTRICAL CHARACTERISTICS (STC)*
HIGH-EFFICIENCY LINE
MECHANICAL CHARACTERISTICS
Solar Cells
Solar Cells Size
Front Cover
Back Cover
Encapsulant
Frame
Frame finishing
Backsheet finishing
Diodes
Junction Box
Connector
Cables Length
Cables Section
Dimensions
Weight
Max. Load
60 (6x10) monocrystalline PERC
156x156 mm / 6x6”
3.2 mm / 0.12” thick, low iron tempered glass
TPT (Tedlar-PET-Tedlar)
EVA (Ethylene vinyl acetate)
Anodized aluminium alloy, double wall
Black
White
3 Bypass diodes serviceable
IP67 rated
MC4 or compatible connector
900 mm / 35.4”
4.0 mm² / 0.006 in²
1640x992x40 mm / 64.5x39x1.57”
18 Kg / 39.7 lbs
Certified to 5400 Pa
45±2 °C
-0.40 %/°C
-0.32 %/°C
0.047 %/°C
-40 °C ~ +85°C
1700x1200x1200 mm / 67x47x47”
27
516 Kg / 1138 lbs
TEMPERATURE CHARACTERISTICS
NOCT∗∗
Temperature Coefficient of Pmax
Temperature Coefficient of Voc
Temperature Coefficient of Isc
Operating Temperature
PACKAGING***
Pallet dimensions
Pieces per pallet
Weight
CERTIFICATIONS
CURRENT/VOLTAGE CHARACTERISTICSDIMENSIONS
***Pallets can be stacked up to two
*STC: (Standard Test Condition) Irradiance 1000W/m²; Module Temperature 25°C; Air Mass 1.5
**NOCT: (Nominal Operation Cell Temperature) Sun 800W/m²; Air 20°C; Wind speed 1m/s
It is important to point out, that all technical specifications, information and figures contained in this datasheet are estimated values.
Peimar reserves the right to change the technical specifications, information and figures contained in this document at any time without
notice.
US_VERS 1_05/2019
Fire Resistance Rating
Module fire performance
Class C (for ULC/ORD-C1703-01)
Type 1 (for UL 1703)
Values apply to modules: SG315M (BF)
315 W
0/+5 W
33 V
9.57 A
40.93 V
9.82 A
1500 V
15 A
19.36%
SG315M (BF)
INV
ER
TE
RS
www.solaredge.us
12-25
Single Phase Inverter with HD-Wave Technolo g yfor
North America
SE3000H-US / SE3800H-US / SE5000H-US /
SE6000H-US / SE7600H-US / SE10000H-US / SE11400H-US
Optimized installation with HD-Wave technology Speciically designed to work with power opimizers
Record-breaking e�ciency
Fixed voltage inverter for longer strings
Integrated arc fault protecion and rapid shutdown for NEC 2014 and 2017, per aricle 690.11 and 690.12
UL1741 SA ceriied, for CPUC Rule 21 grid compliance
Extremely small
Highre liability without any electrolyic capacitors
Built-in module-level monitoring
Outdoor and indoor installaion
Opional: Revenue grade data, ANSI C12.20 Class 0.5 (0.5% accuracy)
SE3000H-USSE3800H-USSE5000H-USSE6000H-USSE7600H-US SE10000H-USSE11400H-US OUTPUT
Rated AC Power Output 30003800 @ 240V3300 @ 208V
50006000 @ 240V5000 @ 208V
7600 10000 11400 VA
Max. AC Power Output 30003800 @ 240V3300 @ 208V
50006000 @ 240V5000 @ 208V
7600 10000 11400 VA
AC Output Voltage Min.-Nom.-Max. (183 - 208 - 229)
- 3 - 3 - - - Vac
AC Output Voltage Min.-Nom.-Max. (211 - 240 - 264)
3 3 3 3 3 3 3 Vac
AC Frequency (Nominal) (1)59.3 - 60 - 60.5 HzMaximum Coninuous Output Current 208V
- 16 - 24 - - - A
Maximum Coninuous Output Current @240V
12.5 16 21 25 32 42 47.5 A
GFDI Threshold 1 AUility Monitoring, Islanding Protecion, Coun tryConigur ableThresho lds
Yes
INPUT Maximum DC Power @240V 4650 5900 7750 9300 11800 15500 17650 WMaximum DC Power @208V - 5100 - 7750 - - -Transformer-less, Ungrounded Yes
Maximum Input Voltage 480 VdcNominal DC Input Voltage 380 400 Vdc Maximum Input Current 208V - 9 - 13.5 - - -Maximum Input Current @240V 8.5 10.5 13.5 16.5 20 27 30.5 AdcMax. Input Short Circuit Current 45 AdcReverse-Polarity Protecion Yes
Ground-Fault Isolaion Detecion 600k Sensiivity
Maximum Inverter E�ciency 99 99.2 %CEC Weighted E�ciency 99 %Nigh�me Power Consumpion < 2.5 WADDITIONAL FEATURESSupported Communicaion Interfaces RS485, Ethernet, ZigBee (opional), Cellular (opional)Revenue Grade Data, ANSI C12.20 (2)OpionalRapid Shutdown - NEC 2014 and 2017 690.12
Automaic Rapid Shutdown upon AC Grid Disconnect
STANDARD COMPLIANCESafety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Grid Connecion Standards IEEE1547, Rule 21, Rule 14 (HI)
Emissions FCC Part 15 Class B INSTALLATION SPECIFICATIONS AC Output Conduit Size / AWG Range 3/4” minimum / 14-6 AWG 3/4” minimum /14-4 AWG
DC Input Conduit Size / # of Strings / AWG Range
3/4” minimum / 1-2 strings / 14-6 AWG3/4” minimum / 1-3 strings /
14-6 AWG
Dimensions with Safety Switch (HxWxD) 17.7 x 14.6 x 6.8 / 450 x 370 x 17421.3 x 14.6 x 7.3 / 540 x 370
x 185in / mm
Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 38.8 / 17.6 lb / kgNoise < 25 <50 dBACooling Natural Convecion Natural convecion
Operaing Temperature Range (3) (4)-13 to +140 / -25 to +60 (-40˚F / -40˚oCp ion) ˚F / ̊CProtecion Raing NEMA 3R (Inverter with Safety Switch)
Single Phase Inverter with HD-Wave Technology for North America SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/ SE7600H-US / SE10000H-US / SE11400H-US
(1) For other regional se�ngs please contact SolarEdge support P/N: SExxxxH-US000NNC2(2) (3) Revenue grade inverter For power de-raing informaion refer to: htps://www.solaredge.com/sites/default/iles/se-temperature-deraing-note-na.pdf
(4) -40 version P/N: SExxxxH-US000NNU4
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein
are trademarks of their respective owners. Date: 07/2018/V01/ENG NAM. Subject to change without notice.
PO
WE
R O
PT
IMIZ
ER
www.solaredge.us
SolarEdge Power Optimizer
Module Add-On
For North America
P300 / P320 / P400 / P405
Up to 25% more energy
Superior e�ciency (99.5%)
Miigates all types of module mismatch losses, from manufacturing tolerance to parial shading
Flexible system design for maximum space uilizaion
Fast installaion with a single bolt
Next generaion maintenance with module-level monitoring
Module-level voltage shutdown for installer and ireighter safety
PV power optimization at the module-level
USA - CANADA - GERMANY - ITALY - FRANCE - JAPAN - CHINA - AUSTRALIA - THE NETHERLANDS - UK - ISRAEL
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are
trademarks of their respective owners. Date: 12/2015 V.01. Subject to change without notice.
(2)
It is not allowed to mix P405 with P300/P400/P600/P700 in one string.
P300
(for 60-cell modules)
P320
(for high-power
60-cell modules)
P400
(for 72 & 96-cell modules)
P405
(for thin ilm
modules)
INPUT
Rated Input DC Power(1) 300 320 400 405 WAbsolute Maximum Input Voltage
(Voc at lowest temperature) 48 80 125 Vdc
MPPT Operaing Range 8 - 48 8 - 80 12.5 - 105 Vdc
Maximum Short Circuit Current (Isc) 10 11 10.1 Adc
Maximum DC Input Current 12.5 13.75 12.63 Adc
Maximum E�ciency 99.5 %
Weighted E�ciency 98.8 %
Overvoltage Category II
OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER)
Maximum Output Current 15 Adc
Maximum Output Voltage 60 85 Vdc
OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF)Safety Output Voltage per Power Opimizer
1 Vdc
STANDARD COMPLIANCE
EMC FCC Part15 Class B, IEC61000-6-2, IEC61000-6-3
Safety IEC62109-1 (class II safety), UL1741
RoHS Yes
INSTALLATION SPECIFICATIONS
Maximum Allowed System Voltage 1000 Vdc
Compaible inverters All SolarEdge Single Phase and Three Phase inverters
Dimensions (W x L x H)128 x 152 x 27.5 /
5 x 5.97 x 1.08128 x 152 x 35 /
5 x 5.97 x 1.37128 x 152 x 50 /
5 x 5.97 x 1.96mm / in
Weight (including cables) 760 / 1.7 830 / 1.8 1064 / 2.3 gr / lb
Input Connector MC4 Compaible
Output Wire Type / Connector Double Insulated; MC4 Compaible
Output Wire Length 0.95 / 3.0 1.2 / 3.9 m / t
Operaing Temperature Range -40 - +85 / -40 - +185 ˚C / ̊F
Protecion Raing IP68 / NEMA6P
Relaive Humidity 0 - 100 %(1) Rated STC power of the module. Module of up to +5% power tolerance allowed.
SolarEdge Power OptimizerModule Add-On for North America
P300 / P320 / P400 / P405
PV SYSTEM DESIGN USING
A SOLAREDGE INVERTER(2) SINGLE PHASE THREE PHASE 208V THREE PHASE 480V
Minimum String Length
(Power Opimizers) 8 10 18
Maximum String Length
(Power Opimizers)25 25 50
Maximum Power per String 5250 6000 12750 WParallel Strings of Diferent Lengths
or OrientaionsYes
Unirac PV Mount and Hardware
DISCONNECTS LOCATED AS SHOWN
FOR MARKING DC BACKUP SYSTEMS
Combiner Box /
Circuits / Conduit Combiner Box / Enclosures / EMT Enclosures
DC Disconnect / Breaker /
Recombiner Box
EMT / Conduit Raceways
*(Relective Material Required)
1 3 4
AC Disconnect / Breaker / Points of Connection
Production / Net Meter (Bi-directional)
7
6
NEC 690.31(G)(3)(4) / Roll: 596-00206 / 10-Pk: 596-00678
Building / Structure2
NEC 705.10 & NEC 690.56(B)
NEC 690.13(B) / Roll: 596-00878 10-Pk: 596-00893 / Metal 5-Pk: 596-00921
WARNINGELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B) / Roll: 596-00878 10-Pk: 596-00893 / Metal 5-Pk: 596-00921
WARNINGELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 110.27(C) & OSHA 1910.145(f)(7)Roll: 596-00499 / 10-Pk: 596-00664
Metal 5-Pk: 596-00832
NEC 690.13(B) / Roll: 596-0087910-Pk: 596-00894 / Metal 5-Pk: 596-00920
WARNINGELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
DC VOLTAGE IS ALWAYS PRESENTWHEN SOLAR MODULES
ARE EXPOSED TO SUNLIGHT
NEC 705.12(D)(3) & NEC 690.59 / Roll: 596-0049510-Pk: 596-09665 / Metal 5-Pk: 596-00833
WARNING DUAL POWER SOURCESECOND SOURCE IS PHOTOVO LTAIC SYSTEM
NEC 690.31(G)(1) / Roll: 596-00257
NEC 690.13(B)Roll: 596-00238 / 10-Pk: 596-00854
Hand-writable 5-Pk: 596-00842
Engravable 5-Pk: 596-00858
NEC 690.13(B) / Roll: 596-00237 / 10-Pk: 596-00853
Hand-writable 5-Pk: 596-00841
Engravable 5-Pk: 596-00857
NEC 690.54 / Roll: 596-00892 / 10-Pk: 596-00882
PHOTOVOLTA IC AC DISCONNECT TED AC OUTPUT CURREN
RA T:
NOMINAL OPERATING AC VOLTA GE
PHOTOVOLTA IC AC DISCONNECT TED AC OUTPUT CURREN
RA T:
NOMINAL OPERATING AC VOLTA GE
Hand-writable 5-Pk: 596-00919
Engravable 5-Pk: 596-00923
Hand-writable 5-Pk: 596-00918
Engravable 5-Pk: 596-00922
NEC 690.53 / Roll: 596-00891 / 10-Pk: 596-00881
MAXIMUM VOLTA GEMAXIMUM CIRCUIT CURRENT
MAX RATED OUTPUT CURRENT OFTHE CHARGE CONTROLLEROR DC-TO-DC CONVERTER(IF INSTALLED)
MAXIMUM VOLTAGEMAXIMUM CIRCUIT CURRENT
MAX RATED OUTPUT CURRENT OFTHE CHARGE CONTROLLEROR DC-TO-DC CONVERTER(IF INSTALLED)
MAXIMUM VOLTAGEMAXIMUM CIRCUIT CURRENT
MAX RATED OUTPUT CURRENT OFTHE CHARGE CONTROLLEROR DC-TO-DC CONVERTER(IF INSTALLED)
Inverter5
NEC 690.54 / Roll: 596-00892 / 10-Pk: 596-00882
Hand-writable 5-Pk: 596-00919
Engravable 5-Pk: 596-00923
NEC 690.31(I) / Roll: 596-0932310-Pk: 596-09324 / Metal 5-Pk: 596-00924
WARNINGTHE DISCONNECTION OF THE GROUNDED CONDUCTOR(S)
MAY RESULT IN OVERVOLTAGEON THE EQUIPMENT
NEC 690.52 / Roll: 596-00252 / 10-Pk: 596-00855
Hand-writable 5-Pk: 596-00840
Engravable 5-Pk: 596-00862
596-00240POWER TO THIS SERVICE IS ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
CAUTION
Inverter& AC Disconnect
Main ServicePanel
PVARRAY
N
S
21
240
409
24
SAMPLE
NEC 690.13(B) / Roll: 596-00878 10-Pk: 596-00893 / Metal 5-Pk: 596-00921
WARNINGELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 690.13(B) / Roll: 596-00878 10-Pk: 596-00893 / Metal 5-Pk: 596-00921
WARNINGELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE ANDLOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
NEC 705.12(B)(3-4) & NEC 690.59 / Roll: 596-0049510-Pk: 596-00665 / Metal 5-Pk: 596-00833
WARNING DUAL POWER SOURCESECOND SOURCE IS PHOTOVO LTAIC SYSTEM
Breaker Panel / Pull Boxes8
NEC 690.15 (C) & NEC 690.33(E)(2)Roll: 596-00244 / 10-Pk: 596-00671
NEC 690.13 (F), NEC 705.12(B)(3-4) & NEC 690.59Roll: 596-00587 / 10-Pk: 596-00666
Metal 5-Pk: 596-00834
NEC 710.15(C) & 692.9 (C) / Roll: 596-0059110-Pk: 596-00699 / Metal 5-Pk: 596-00837
Main Service Disconnect9
NEC 690.13(B) / Roll: 596-0024310-Pk: 596-00675 / Metal 5-Pk: 596-00860
NEC 690.13(B) / Roll: 596-0024310-Pk: 596-00675 / Metal 5-Pk: 596-00860
Main Service Disconnect /
Utility Meter10
NEC 705.12 (B)(2)(c) / Roll: 596-0088310-Pk: 596-00884 / Metal 5-Pk: 596-00917
NEC 690.54 / Roll: 596-00892 / 10-Pk: 596-00882
PHOTOVOLTA IC AC DISCONNECT TED AC OUTPUT CURREN
RA T:
NOMINAL OPERATING AC VOLTA GE
Hand-writable 5-Pk: 596-00919
Engravable 5-Pk: 596-00923
NEC 110.27(C) & OSHA 1910.145(f)(7)Roll: 596-00499 / 10-Pk: 596-00664
Metal 5-Pk: 596-00832
NEC 110.27(C) & OSHA 1910.145(f)(7)Roll: 596-00499 / 10-Pk: 596-00664
Metal 5-Pk: 596-00832
WARNING
POWER SOURCE OUTPUTCONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE.
SAMPLE