© ABB Group January 26, 2011 | Slide 1

POWERING SUBSEA LOADS OVER LONG DISTANCES

PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER SUBSEA TIE-BACK

Space optimiced multidirve Solutions

Page 2: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 2

Presentation Overview

• History

• Typical Subsea Consumers

• Electrical Configurations and

Characteristics

• Subsea Electrical Market Status

• Reference Projects

• Summary

Page 3: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 3

1980-present

ESP

More than 200

electrical systems

delivered

2000

SEPDIS

Subsea Frequency

Converter

2000-2003

TOPACIO & CEIBA

First systems with

subsea transformer

2006-2009

TYRIHANS

31km tie-back subsea

electrical system

2007-2010

ORMEN LANGE

20MVA Subsea

Transformer

2008-2011

ÅSGARD

Long Step-out Power

qualification, 15MVA,

47km, 200Hz

C o m p e t e n c e

System knowledge

Industry/Vendor collaboration

Project execution

Technology qualification

ABB Electrical Subsea History Developing with the industry

Page 4: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 4

Supply subsea base equipment with electric power

• Subsea Power Consumers

• Subsea Water Injection Pumps

• Subsea Multiphase Pumps

• Subsea Gas Compressors

• Subsea Downhole Pumps

• Subsea Booster Pumps

• Subsea Separation

• Pipe Heating

• New Field Developments: Marginal, Satellite and Deep Water

• Developments Without Platforms

• Long Distance Between Field and Platform/FPSO

• Extended use of Existing Infrastructure

Typical Subsea Consumers

Page 5: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 5

Typical Configuration – Short Distance - Single Consumer

REFERENCE PROJECTS:

• Lufeng by STATOIL

• Troll-Pilot by Norsk Hydro

• ESPs (more than 200 units

delivered worldwide)

STEP-OUT DISTANCE:

• Step-out distance up to 10-25

km, depending on load and

pump characteristics

CAPABILITY:

• 1-4 MVA

• Operating transmission voltage

typically 6 kV

TECHNOLOGY STATUS:

• All components qualified

Topside

Frequency Converter

TopsideStep-down three-winding transformer

Subsea Power Cable

HV Connector

AC Motor

Page 6: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 6

Subsea transformers and HV connectors

Typical Configuration – Long Step-Out

REFERENCE PROJECTS:

• Tyrihans by Statoil

• Topacio by Mobil

• Ceiba by Amerada Hess

• Åsgard MF Project VSD &

Long Step-out Power

qualification

STEP-OUT DISTANCE:

• Step-out distance up to

60km, depending on load,

frequency and pump

characteristics

CAPABILITY:

• Up to 15 MVA

• Operating transmission

voltage up to 50kV

OFFERING:

• Increased step-out

• Substantially reduced cable

cost due to high

transmission voltage

Topside

Frequency Converter

Topside Step-up Transformer

TopsideStep-down three-winding transformer

Bundled Subsea Power Cable

HV Connector

AC Motor

Subsea step-down transformer

Motor Connector

Subsea Power Cable Termination Head

Page 7: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

Hybrid Solution

• Supplying multiple consumers

• Competitive solution for Subsea drives

• Reduce cable cost (one cable from shore)

• Risk mitigation

• Maintanance access via helicopter

• Increased availability compared to using subea converters

• Utilize standard products

• Capability > 100MW @ 100km

Page 8: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

Considerations for Selecting Subsea Electrical Topology

© ABB Group January 26, 2011 | Slide 8

• Voltage • Number of consumers

• Power • Distance

Topside electrical

system

Topside electrical system with subsea transformer

Hybrid system

Complete subsea system

Cost &

Risk

Page 9: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

Capability Envelope – Topside Electrical Systems Current Technology

© ABB Group January 26, 2011 | Slide 9

0

5

10

15

20

Topside electrical system Topside with subsea transformer

Power/

MVA

Page 10: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 10

Presentation Overview

• Typical Subsea Consumers

• History

• Typical Configurations and Characteristics

• Subsea Electrical Market Status • Reference Projects

• Summary

Page 11: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

Subsea Market – Technology Steps

Page 12: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

Subsea gas compression system pilot

Subsea gas compression candidates Symbol size indicates total installed power

year indicates start benefit / possible start up

0

500

1000

1500

2000

2500

3000

0 50 100 150 200

step out for power (km)

wate

rdep

th (

m)

2008 Mikkel 10 MW

2008 Oseberg DSG-s 9 MW

2009 Corrib 8 MW

2013 Snøhvit compression 1 - 10 MW

2021 Snøhvit compression 1& 2 - 34 MW

2014 Tyrihans 15 MW

2016 Ormen Lange 50 MW

Jack & St Malo

Source Norsk Hydro

Page 13: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

Topside step-out stretch road map

??

Page 14: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

Why have subsea distribution and frequency converters not penetrated the market?

Subsea distribution system has be on the drawing

board for at least 15 years. Potential to save

platform costs by placing all equipment subsea.

So why has this not happened ?

Risk is the main reason

Risk mitigation is extreamly important – by placing

frequency converters topside, a major risk element

is removed from subsea, supply via long cables.

Since 2005 ABB has focused on step-out systems

with:

Longer distances

Higher power

Deeper water

© ABB Group January 26, 2011 | Slide 14

Page 15: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 15

Presentation Overview

• Typical Subsea Consumers

• History

• Typical Configurations and Characteristics

• Subsea Electrical Market Status

• Reference Projects • Summary

Page 16: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 16

Reference Project: Tyrihans

Field Operator: Statoil

Application: Subsea Raw Sea Water Injection

Capacity: 14 000 m3 untreated seawater/day

Pump Qty: 2

Tie-in distance: 31 km

Host platform: Kristin

Pump vendor: Aker Kvaerner Subsea

Project completion: 2009/2011

The project will add production worth > 1000 MUSD

Topside

FrequencyConverter

Topside Step-upTransformer

TopsideStep-downthree-windingtransformer

Bundled SubseaPower Cable

HV wet mateableconnector

AC Electrical PumpMotor

Subsea step-downtransformer

Pump motor wetmateable connector

Subsea PowerCable TerminationHead

Page 17: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 17

Reference Project: Tyrihans

ABB Scope of Supply

• 2 x Topside VSD System

• ACS1000 Water cooled converters

• Oil filled step-down/up transformers

•2 x Subsea Transformer

• 4000 kVA

• Insulation monitoring system on pump side

• Insulation monitoring system on umbilical

• System Design Report

• Time domain simulations

• Breakaway torque calculations

• Loadflow calculation

• Fault analysis

• THD calculations

Page 18: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 18

Frequency Converter

MV AC

Induction

Motor

Medium Voltage

Supply Bus

I>> Prot

Main Feeder

Breaker

& Protection

Converter Input

TransformerStep-Up

Transformer

4kV : 6.6kV

(example)

ACS 1000 MV DriveRect. DC-Link Inverter Output

Sine

Filter

•Water Cooled

•ACS- 600,800,1000,2000, 5000

•Sine filter

Page 19: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 19

Subsea Transformer

Mechanical solution – Subsea Transformer

Pressure compensator for volume

variation

Low voltage penetrators

Tank of special corrosion resistant steel

High voltage ”dry mateable” connection

Page 20: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 20

Åsgard Minimum Flow Project

Page 21: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 21

Åsgard MF Project VSD & Long Step-out Power qualification

Overall view of electrical test system

Phase 1

Phase 2

Key Design features:

Power system rated

for 15 MVA

Designed for 8MW

compressor shaft

power

Operating frequency

up to 200 Hz

Designed for direct

and long step-out

operation

Designed to test

different

compressors

(189/159/100Hz)

Designed with

advanced measuring

system

2007-2008

2008-2010

Page 22: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 22

Åsgard MF Project VSD & Long Step-out Power qualification

ABB scope of supply for Åsgard long step-out

qualification program

Equipment deliveries

Qualification tests

Simulations

Installation

Commissioning

System Testing

Page 23: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 23

Åsgard MF Project VSD & Long Step-out Power qualification

Technical challenges

World longest cable connected to

frequency converter output (47km)

Biggest power rating for step-out system

(Rated15MVA Transmission)

Highest supply frequency for long step-out

system (up to 200Hz)

Qualifying, building and testing

Detail simulation model of complete

system

Converter (15MVA/200Hz, for Long

Step-out Application)

Step-up Transformer (15MVA/200Hz)

Subsea Transformer (15MVA/200Hz)

Complete System testing

Zspectra test - 10 pi sections OC, phase 3

Zohms measured vs. model

0.00

100.00

200.00

300.00

400.00

500.00

600.00

40 190

628

1150

1250

2000

2500

3170

4000

4570

5350

6000

6410

6970

7560

8000

9000

f [Hz]

Z [

Oh

m]

Z ohms-measured

Z ohms-model

Page 24: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 24

Subsea Step-down Transformer

Key Design features:

Power rating 15 MVA

Insulation level 52 or 72.5 kV

Operating frequency up to 200 Hz

Qualified with current and voltage

measurement

Critical design parameters

Reliability

Achieved by:

Well established material

Normal operating temperatures

Natural cooling

Pressure compensation

Page 25: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 25

3-Phase Cable Simulator

Design 10 PI-sections with lumped

components

Fuse-less capacitors

Air-core inductors

Stainless steel resistors

Protection and monitoring

Outdoor installation

Operating voltage up to 52 kV

Loading up to 300 A

Operating frequency up to 200 Hz

Simulating features: Cable length from 20 to 47 km

Conductor size 150 or 240 mm2

Page 26: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 26

Conclusion K-Lab / Åsgard Activities

Advantages: • Minimizing big investments in new off-shore

production

• Use of known technology and products

optimized and adapted for this special

application is important for availability and

documented functionality

• VSD located on floating production units

(easy maintenance)

• Motor-friendly VSD due to 9-level output

voltages and Selected Harmonic Elimination

control method – no output VSD filter needed

despite long cables

Status: • Successful completion of system test

program

Page 27: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 27

Presentation Overview

• Typical Subsea Consumers

• History

• Typical Configurations and Characteristics

• Subsea Electrical Market Status

• Reference Projects

• Summary

Page 28: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

Summary

Subsea Electrical Configurations

Topside electrical system

Topside electrical system with subsea transformer

Hybrid system

Market and Technology Status:

Topside electrical systems with subsea transformers qualified up to 15MVA up to 60km, up to 200Hz, Year 2006-2010

Successfully qualified by Åsgard MF Project

High activity in qualifying systems for subsea compression

Long distances

Large powers

Subsea Drives –Tested and offered up to 3,5MVA, Year 2000

Market penetration slow

Developments In Works:

Qualify subsea transformers to 3000 meter

Page 29: PETRONAS - PETRAD - INTSOK CCOP DEEPWATER SUBSEA … · © ABB Group January 26, 2011 | Slide 1 POWERING SUBSEA LOADS OVER LONG DISTANCES PETRONAS - PETRAD - INTSOK – CCOP DEEPWATER

© ABB Group January 26, 2011 | Slide 29