pesgm2006-000045
TRANSCRIPT
-
8/13/2019 PESGM2006-000045
1/5
The Short Circuit Current Ratings of
Surge Protective Devices (SPDs)
B.R. Cole,IEEE Member, K. Brown,IEEE Member, P.S. McCurdy,IEEE Member,
T.E. Phipps,IEEE Member, and R. Hotchkiss,IEEE Member
Abstract--This document examines the standards
associated with the short circuit current ratings (SCCRs) for
surge protective devices (SPDs). A review of the IEEE, UL, and
NFPA documents is used to determine why SCCRs are required
for SPDs and what is the correct methodology for determining
the coordination of the SPD and the electrical distribution. An
example is provided detailing the proper and improper applica-
tion of the SPD as it relates to the SCCR. For improper applica-
tions of an SPD, remedial actions are presented.
Keywords AC circuit breakers, overvoltage protection, short
circuit currents, surge protection
I. INTRODUCTION
Transient Voltage Surge Suppressors (TVSS), more
commonly referred to as surge protective devices (SPDs),
have been applied as part of an overall power quality strategy
for more than three decades. As power and control systems
become more complex through the utilization of semiconduc-
tors used in electronic devices to control, process, and com-
municate information, SPDs will continue to be recognized as
an essential component of power quality. However, a large
knowledge base regarding the proper application of SPDs
does not exist; therefore, many issues cloud the safety, per-
formance, and the correct application of the device.
In particular, the short circuit current rating (SCCR)
of the SPD is discussed within this paper. The SCCR of an
SPD is defined as the suitability of the SPD for use on an AC
power circuit that is capable of delivering not more than a
declared rms symmetrical current at a declared voltage during
a short circuit condition1. This paper will examine the
standards, electrical codes, and application guidelines associ-
ated with the installation of SPDs. Detail will be provided
determining sufficient testing methodologies associated with
obtaining the SCCR and the pass/fail criteria as determined by
the listing agency. In addition, two examples will be provided
that detail specific applications of an SPD, as related to
coordinating the SCCR of the SPD to the power distribution
system of the facility. One example will be a correct applica-
tion. The second example will be an incorrect application of
1UL 1449 3rdedition Draft, Underwriters Laboratories, Incorporated, dated
2005 December 2005.
This report has been developed by a task force of the Surge Protective
Devices Committee Working Group 3.6.6 on the Applications of Low
Voltage Surge Protective Devices and recommended for presentation at the
PES General Meeting, 2006 July. Members and contributors of the task force
included: B. Cole, K. Brown, P. McCurdy, T. Phipps, and R. Hotchkiss,
the SPD, but will provide specific methods that will allow the
application to be corrected.
II. STANDARDS AND GUIDES
In the United States, there are a small number of
documents that have been produced to evaluate both the
performance and safety attributes of a properly installed and
coordinated SPD with the electrical distribution. These
documents have been produced by telecommunication com-
panies, by regulatory bodies, and independent organizations.
The primary documents developed and addressed in this paper
include those by the National Fire Protection Association(NFPA), Underwriters Laboratories, Incorporated (UL), and
the Institute of Electrical and Electronic Engineers (IEEE).
A. The NFPA
The National Fire Protection Association (NFPA) is
the primary sponsor of the National Electric Code (NEC), a
top-level document detailing the guidelines for application of
electrical and/or electronic equipment connected to low-
voltage power distribution. The NEC is primarily concerned
with the safety aspects of all electrical wiring and electri-
cal/electronic devices, including SPDs. As an essential
component of ensuring the safe application of an SPD, the
NEC requires that virtually every component of the buildingwiring or device connected to the building wiring, including
SPDs, be provided with a means of over-current protection
[1]. In particular, Article 110-10 of the NEC states: The
over-current protective devices, the total impedance, the
component short-circuit current rating, and other characteris-
tics of the circuit to be protected shall be selected and coordi-
nated to permit the circuit-protective devices used to clear a
fault to do so without extensive damage to the electrical
components of the circuit. This fault shall be assumed to be
either between two or more circuit conductors. Listed prod-
ucts applied in accordance with their listing shall be consid-
ered to meet the requirements of this section.2
The NFPA 70 has added a new article to the 2002
codebook. Article 285 Transient Voltage Surge Suppressors
was added to address general, installation and connection
requirements for permanently installed Transient Voltage
Surge Suppressors. Prior to Article 285, the installation of
SPD systems was generally referenced under NEC Article 280
Surge Arresters. In the 2002 NEC, Article 280 continues to
address the general installation and connection requirements
2NEC 2002, National Fire Protection Association, Incorporated (NFPA) 70,2002.
1-4244-0493-2/06/$20.00 2006 IEEE.
-
8/13/2019 PESGM2006-000045
2/5
for Surge Arresters; however, this is beyond the scope of this
technical report.
Items in the 2002 NEC, the short circuit current rat-
ing of the SPD are detailed in Article 285.5, and Article
285.6. Article 285.5 states that the SPD shall be a Listed
device [1]. Article 285.6 states that the SPD shall be marked
with a short circuit current rating, which is obtained through
an independent safety organization, and that the SPD shall beinstalled at point on the electrical distribution that does not
exceed the rating of the SPD [1]. Listed products are those
products that have been evaluated by an independent safety
organization in accordance with OSHA 29 CFR 1910.7 [2].
The predominate safety agency that provides product listings
in the US is Underwriters Laboratories, Incorporated (UL).
UL provides product Listing of SPDs in accordance with the
Standard for Safety, Transient Voltage Surge Suppressor,
number 1449, Second Edition, dated 1996 August. This
standard will be discussed in greater detail later in this article.
As detailed in Article 285.6, the code allows SPDs to
be used at points within the electrical distribution system
where the short circuit current rating of the SPD is greater
than that of the system, but not where the short circuit current
of the system is greater than that of the SPD SCCR. What the
code does not address is the type of over-current protection
that is required for the SPD to comply with these require-
ments. It is the responsibility of the facility engineer to detail
what the proper over-current protective device is and how the
SPD is evaluated and determined to comply.
B. UL Standards
Within the United States, the UL Standards for
Safety have long been considered the primary documents in
assessing the safety of products. In Canada, the Canadian
Standards Association is the primary safety assessment
organization. There are also many other organizations that
have been approved as independent safety assessors by
OSHA.
The UL Standard for Safety, Transient Voltage Surge
Suppressors requires that the devices be subjected to many
tests that determine the overall safety of the product. These
tests include, but are not limited to dielectric withstand, surge
testing, and the testing of the product to two-types of abnor-
mal over-voltage scenarios: high current and limited-current.
To meet the requirements of Article 285.6, UL util-
izes the test procedure associated with abnormal over-voltages
and high available fault currents. This is achieved by per-
forming the full-phase voltage, high-current abnormal over-
voltage test described in section 37.3 of UL 1449 [3]. The
testing consists of applying an over-voltage with a specified
available short circuit current to production representative
SPDs. The applied over-voltage is the maximum phase
voltage or twice the conductor pair voltage. For 120/240 Vac,
single-phase, 3W+G system, the phase-to-neutral and phase-
to-ground test voltages are 240 Vac. For a 120/208 Vac,
three-phase wye, 4W+G system, the phase-to-neutral, and
phase-to-ground test voltages are 208 Vac. In a 240 Vac,
three-phase delta, 3W+G system, the phase-to-phase, and
phase-to-ground test voltages are up to 480 Vac.
To either trip or open the over-current protective
device during the testing of the SPD, it is necessary that the
surge components conduct a significant amount of current.
The SPD may use either internal or external over-current
protective components. During and following the full-phasevoltage, high-current test, the SPD shall not create openings in
the enclosure, exhibit emission of flame, charring, glowing or
flaming of the cheesecloth wrapped around the product during
the test, or compromise the enclosure grounding of the SPD.
Once the SPD has successfully completed the testing,
the device shall be marked with its short circuit current
rating. The marking states that the SPD is suitable for use on
a circuit capable of delivering not more than (the nominal)
rms symmetrical amperes, (at tested) volts maximum3. The
short circuit current rating shall be one of the values indicated
in Table I, but not less than the amount detailed in Table II,
which is a reproduction of Table 61.3 and 12.1 respectively in
[3].TABLE I
LISTING OF AVAILABLE FAULT CURRENT RATINGS
FROM UL 1449, SECTION 61
Available Fault Current Rating RMS
Symmetrical Current
(Amperes)
5,000
10,000
14,000
18,000
22,000
25,00030,000
42,000
50,000
65,000
85,000
100,000
125,000
150,000
200,000
If the SPD requires an external fuse or circuit breaker
to pass the test at a specified SCCR, the device shall have an
additional marking as described: when protected by __A__class fuses and/or when protected by a __B__ circuit breaker
rated __C__ volts maximum. The interrupting rating of the
fuse or circuit breaker shall not be less than the available fault
current, whereAis Class CC, CD, G, H, J, L, R, T or K fuse,
Reference to Class H or Class K fuses shall not appear in the
marking if the indicated rms symmetrical fault current is
3Standard for Safety, Transient Voltage Surge Suppressors, UnderwritersLaboratories, Incorporated, UL 1449, 1996 August.
-
8/13/2019 PESGM2006-000045
3/5
greater than 10,000A,Bis the current rating of circuit breaker,
and Cis the nominal system voltage.
TABLE II
AVAILABLE FAULT CURRENT FROM SOURCE OF SUPPLY
FROM UL 1449, SECTION 12
TVSS (SPD) Rating Available Current in
Amperes
100A or less 5,000101 400A 10,000
Over 400A 25,000
UL 1449 states that an external circuit interrupting
device may be used and if one is employed in the test, then it
is required at installation [3]. When an SPD is marked for use
with an external over-current protective device, the test circuit
is to include that device: e.g. circuit breaker or fuse. Installing
an over-current protective device with an adequate interrupt-
ing rating in series with the SPD is required at installation.
With UL providing the test and marking requirements of the
SPD and the NEC providing the marking requirement of the
electrical system, an installation with the correct coordinationof the SPD and the power system available fault current is
obtainable. The coordination of power system, over-current
protective device and SPD are made easier as each is marked
with its appropriate short circuit current rating.
C. IEEE Guides
The IEEE is active in providing recommendations
and guidelines that help engineers correctly describe transient
environments, and help to identify the many attributes of a
correctly applied SPD. The most notable document on surge
environments and the anticipated waveforms at specific
locations within a facility are IEEE Guide on Surge Voltages
in Low Voltage AC Power Circuits, IEEE C62.41.1-2002,and IEEE Recommended Practice on Characterization of
Surges in Low Voltage AC Power Circuits, C62.41.2-2002.
While the aforementioned documents do provide an
overview of the surge environment, they do not provide any
input into how the SPD can, or should be coordinated to the
electrical distribution. Therefore, recommendations on the
performance, suitability, or best engineering practice for using
an over-current protective device in series with an SPD is
relegated to other industry standards.
III. APPLICATION EXAMPLE
Two main factors should be considered when select-ing over-current devices to be used with SPDs. First, the
ability to limit the available short-circuit energy to levels that
are compatible with an SPD during an end-of-service life
event. Second, the over-current device should not signifi-
cantly affect the ability of an SPD to divert transients within
the electrical distribution system. If an over-current protec-
tion device connected in line with an SPD disconnects during
a transient, the SPD is removed from the circuit when it is
needed most. In addition, it could be some time until this is
noticed, thereby making the SPD ineffective. Therefore,
careful attention should be made when coordinating series
connected over-current devices with SPDs to ensure not only
the safe end-of-service scenario, but additionally the maxi-
mum performance and reliability of the SPD.
An example is the best way to illustrate the correct
and incorrect application of an SPD in accordance with the
codes, conditions of acceptability, and guidelines of the NEC,
the UL, and the IEEE, respectively. In addition to providingan example of an incorrect application, the authors will also
present remedial methods, which engineers and installers can
use to bring the installation into compliance with the afore-
mentioned recommendations and guidelines.
As an example of a correct application, assume that
an SPD is going to be installed on the power distribution
system of a facility at a branch panel location. At this point in
the power distribution system, the available fault current
capability is 42,000 A. The available fault current at this
location, or any other within the power distribution system of
the facility, must be determined through a fault current analy-
sis by the supervising engineer. Assume that this SPD is
placed behind a circuit breaker with an SCCR of 42,000 A,
shown as in Figure 1. In addition, the SPD has obtained a
SCCR of 65,000 A. In this example, the SCCR of the SPD is
coordinated with that of the facilitys power distribution
system, resulting in correct and coordinated application. In
fact, as long as the SCCR of the SPD is equal to or exceeds
the point of application within the power distribution and the
preceding over-current protective device, the SCCR of the
SPD is correctly coordinated.
As an example of an incorrect application, assume
that a SPD has obtained a SCCR of 25,000 A from UL.
Assume that this particular SPD was placed behind a circuit
breaker with an SCCR of 65,000 A, as shown in Fig. 1.
Additionally, assume that the maximum SCCR available at
this particular location on the power distribution system is
42,000 A. As with the previous example, the supervising
engineer is responsible for determining the available fault
current at this particular point within the power distribution
system of the facility. In this particular example, the SPD is
incorrectly applied. Because the SPD has obtained an SCCR
rating of only 25,000 A, it might not be capable of withstand-
ing an interrupt current of 42,000 A.
A few different approaches can be considered to
rectify this particular example so that the SPD has been
installed in accordance with the NEC, the IEEE recommenda-
tions, and UL conditions of acceptability. The first approach
would be to apply an SPD with an SCCR of 42,000 A or
greater. Even though the circuit breaker preceding the SPD is
greater than the SPD, the maximum short circuit current
available at the panel is 42,000 A. Therefore, the SPD has an
SCCR equal to the power distribution system at that point.
The second approach is to utilize a current limiting
circuit breaker that will limit the SCCR to the SPD to a value
of 25,000 A or less. This option presents some complications.
-
8/13/2019 PESGM2006-000045
4/5
In accordance with the NEC, the device must be applied in
accordance with its safety agency listing requirements. The
SPD must have been tested with a specified circuit breaker at
a specified current rating. Using a circuit breaker produced
by a different manufacturer, at a different SCCR, or even a
different part number is not acceptable and is outside the
scope of its safety agency listing. If the SPD is installed
utilizing an untested or improperly tested current limiting
circuit breaker, then it is the same as not utilizing a productevaluated by an independent safety agency, such as UL.
The third approach would be to install a finite
amount of impedance in the line prior to the panel. The
amount of impedance would have to be high enough to limit
the amount of SCCR to 25,000 A or less. One possible
method to accomplish this is by installing a transformer in the
power distribution system to lower the overall SCCR rating at
that particular point. This option can be very expensive and
might require additional space, but has some advantages in
mitigating other power quality problems that might need to be
addressed.
Fig. 2 represents a SPD that includes the over-current
protection within the device itself. In this case, the SPD does
not require that the device be preceded with a circuit breaker.
However, the same rules apply. The SPD has a specified
SCCR, which has been evaluated by UL; it is marked either
on the product or in the accompanying installation instruc-
tions, and must be connected appropriately.
IV. RECOMMENDATIONS
To ensure that a short circuit current rating (SCCR)
of the SPD has been properly coordinated with the power
distribution system of the facility, the authors recommend the
following:
1. A fault current analysis of the power distribution sys-
tem be performed and documented at the time of new
construction,
2. A fault current analysis of the power distribution sys-
tem be updated and documented every time new dis-
tribution equipment is installed, e.g. power class
transformer, increase in size of electrical conductors,
etc.,
3. A fault current analysis of the power distribution sys-
tem be updated whenever there is a change in the
utility service,
4. A fault current analysis of the power distribution sys-
tem be updated and documented whenever an SPD is
installed or replaced and,
5. That the available fault current, as determined by the
engineer conducting the fault current analysis, be
marked on the distribution panel.
As part of these recommendations, it is imperative that
the SCCR of any SPD be coordinated with the power distribu-
tion system of the facility. This includes examining all
existing SPDs and ensuring that the SCCR of the SPD is
coordinated to the available fault current at these specific
application points.
V. CONCLUSION
As SPDs have become a common device in the over-all picture of a complete power quality strategy, their per-
formance and safety attributes have continued to be examined
and tested. One of the top attributes is the safe and correct
application, and coordination of an SPD to a power distribu-
tion system of the facility. Analysis is required for the short-
circuit current rating of the power distribution system, for any
over-current protective devices, and for the SPD itself.
The NEC has established rules determining the rela-
tionship between the interrupting rating of a device and the
over-current protective device required. An added clarifica-
tion was implemented by the second edition of UL 1449 by
testing SPDs to a particular set of conditions and providing
SPDs with a short circuit current rating. Additionally, contri-
butions made by the members of the IEEE on guidelines and
recommendations of a correctly installed SPD will help ensure
the correct application of an SPD. Responsibility for the
coordination of the SPD to the application rests on the speci-
fying engineer, the contractor or end-user installing the SPD
and the inspecting official.
In conclusion, the only set rule for determining the
short circuit current rating of an SPD is to examine the label-
ing, paperwork and installation instructions of that particular
SPD. Once the short circuit current rating of the SPD has
been determined, and a fault current analysis has been per-
formed on the power distribution system, the appropriate SPD
can be installed. Failure to ensure the proper application of
the SPD with the development of specifications, guidelines,
and standards can result in a potentially dangerous condition.
The inappropriate application of an SPD can no longer be
tolerated or excused.
V. REFERENCES1. National Fire Protection Association, National Electrical Code, 2002,
Ninth Edition, Quincy, MA.
2. US Department of Labor, Program Regulation (29 CFR 1910.7), [On-
line]. Available: http://www.osha.gov/dts/otpca/nrtl/nrtlregs.html.
3. Underwriters Laboratories, Incorporated, Standard for Safety, Transient
Voltage Surge Suppressors, Second Edition, 1996 August 15, Melville,
NY.
-
8/13/2019 PESGM2006-000045
5/5
Fig. 1. Connection of the SPD utilizing a dedicated circuit breaker Fig. 2. Connection of the SPD utilizing the main circuit breaker of the
panel.
Bryan Cole, NCE (M, 1993) is the President of
Technology Research Council, LLC, and former
Director of Engineering & Product Safety Officer for
Control Concepts Corporation. Bryan has been
involved with the R&D of one-port and two-port surgeprotection devices, electromagnetic interference (EMI)
filters, and harmonic filters, and product safety for
eighteen years. He a member of the IEEEs Power Engineering, Engineer-
ing Management, Product Safety, and EMC Societies, a member of UL
Standard Technical Panel for TVSS, temporary power taps, and Switchgear
and Panelboards, and member of the US National Committee to the IEC on
SPDs. Bryan is a NARTE Certified Engineer in product safety, has a
Bachelors degree in Electrical Engineering from Binghamton University, a
MBA from the University of Phoenix, and is a PhD student at Northcentral
University.
Kenneth Brown (M', 1996) is the Director of
Engineering for Power Quality Products at Leviton
Manufacturing Company. Ken has been involved
with the design and development of surge protection
devices for 8 years. Ken is presently chairman of thetechnical committee for the NEMA 5VS Section.
Ken is a member of the US National Committee to
the International Electro-technical Commission on
SPDs (37A) and he is a member of the IEEE Working Group's 3.6.4,
3.6.6, 3.6.9, and 3.6.10. Ken received an undergraduate degree in
Electrical Engineering from the Ohio Institute of Technology, and an
MBA from West Coast University.
Pat McCurdy (M, 1996) is the Product Marketing
Manager and technical specialist for Phoenix Con-
tacts North American Surge Protection division.
Patrick has worked for Phoenix Contact in various
technical, application, and management roles foreleven years. Patrick has a Bachelor of Science
Degree in Electrical Engineering Technology from
Penn State University and a Master in Business
Administration from Lebanon Valley College. Active
professional associations include: International Society of Measurements
and Control (ISA), Institute of Electrical and Electronic Engineers (IEEE),
American Gas Association (AGA), and National Electrical Manufacturers
Association (NEMA).
Thomas Phipps (M 2000) received the Manasseh
Cutler Scholarship at Ohio University in Athens,
Ohio while majoring in Electrical Engineering.
Tom has been involved in power quality engineer-
ing over the past seventeen years working in areasof Production, Applications, Test, and Research &
Development Engineering. His employment
experience includes the areas of power condition-
ing, power distribution, Rotary and Static UPS and for the past eleven
years TVSS. Tom has worked for several of the power conditioning
companies within the industry including Power Distribution, Incorpo-
rated, United Power, Incorporated, Power Systems & Controls and is
presently the Vice President of Engineering for Thor Systems, Incorpo-
rated located in Richmond, Virginia.
Ron Hotchkiss is the Vice President of Engineering
for Surge Technology. Ron has been involved in the
design, development and certification testing of one-
port and two-port surge protection devices for thirteen
years. Ron also manages engineering, safety agency,
compliance and quality operations. He is a member of
IEEEs Power Engineering Society and is an active
participant and contributor to several IEEE SPD
working groups and the Underwriters Laboratories
Standard Technical Panel for Transient Voltage Surge Suppressors. He is a
member of the balloting group for IEEE. Ron received his Electrical
Engineering degree with Honors from the University of South Florida in
Tampa.
Branch
Panel
Main
Circuit
Breaker
(Service
Entrance)
SPD
L1
L2
L3
N
G
L1
L2
L3
N
G
Ground Bar Neutral Bar
3-Phase
Circuit Breaker
Branch Panel
Main Circuit Breaker
Conductors to Other
Branch Panels
Branch
Panel
Main
Circuit
Breaker
(Service
Entrance)
SPD
L1
L2
L3
N
G
L1
L2
L3
N
G
Ground Bar Neutral Bar
Branch Panel
Main Circuit Breaker
Conductors to Other
Branch Panels