pesgm2006-000045

Upload: sunitharajababu

Post on 04-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 PESGM2006-000045

    1/5

    The Short Circuit Current Ratings of

    Surge Protective Devices (SPDs)

    B.R. Cole,IEEE Member, K. Brown,IEEE Member, P.S. McCurdy,IEEE Member,

    T.E. Phipps,IEEE Member, and R. Hotchkiss,IEEE Member

    Abstract--This document examines the standards

    associated with the short circuit current ratings (SCCRs) for

    surge protective devices (SPDs). A review of the IEEE, UL, and

    NFPA documents is used to determine why SCCRs are required

    for SPDs and what is the correct methodology for determining

    the coordination of the SPD and the electrical distribution. An

    example is provided detailing the proper and improper applica-

    tion of the SPD as it relates to the SCCR. For improper applica-

    tions of an SPD, remedial actions are presented.

    Keywords AC circuit breakers, overvoltage protection, short

    circuit currents, surge protection

    I. INTRODUCTION

    Transient Voltage Surge Suppressors (TVSS), more

    commonly referred to as surge protective devices (SPDs),

    have been applied as part of an overall power quality strategy

    for more than three decades. As power and control systems

    become more complex through the utilization of semiconduc-

    tors used in electronic devices to control, process, and com-

    municate information, SPDs will continue to be recognized as

    an essential component of power quality. However, a large

    knowledge base regarding the proper application of SPDs

    does not exist; therefore, many issues cloud the safety, per-

    formance, and the correct application of the device.

    In particular, the short circuit current rating (SCCR)

    of the SPD is discussed within this paper. The SCCR of an

    SPD is defined as the suitability of the SPD for use on an AC

    power circuit that is capable of delivering not more than a

    declared rms symmetrical current at a declared voltage during

    a short circuit condition1. This paper will examine the

    standards, electrical codes, and application guidelines associ-

    ated with the installation of SPDs. Detail will be provided

    determining sufficient testing methodologies associated with

    obtaining the SCCR and the pass/fail criteria as determined by

    the listing agency. In addition, two examples will be provided

    that detail specific applications of an SPD, as related to

    coordinating the SCCR of the SPD to the power distribution

    system of the facility. One example will be a correct applica-

    tion. The second example will be an incorrect application of

    1UL 1449 3rdedition Draft, Underwriters Laboratories, Incorporated, dated

    2005 December 2005.

    This report has been developed by a task force of the Surge Protective

    Devices Committee Working Group 3.6.6 on the Applications of Low

    Voltage Surge Protective Devices and recommended for presentation at the

    PES General Meeting, 2006 July. Members and contributors of the task force

    included: B. Cole, K. Brown, P. McCurdy, T. Phipps, and R. Hotchkiss,

    the SPD, but will provide specific methods that will allow the

    application to be corrected.

    II. STANDARDS AND GUIDES

    In the United States, there are a small number of

    documents that have been produced to evaluate both the

    performance and safety attributes of a properly installed and

    coordinated SPD with the electrical distribution. These

    documents have been produced by telecommunication com-

    panies, by regulatory bodies, and independent organizations.

    The primary documents developed and addressed in this paper

    include those by the National Fire Protection Association(NFPA), Underwriters Laboratories, Incorporated (UL), and

    the Institute of Electrical and Electronic Engineers (IEEE).

    A. The NFPA

    The National Fire Protection Association (NFPA) is

    the primary sponsor of the National Electric Code (NEC), a

    top-level document detailing the guidelines for application of

    electrical and/or electronic equipment connected to low-

    voltage power distribution. The NEC is primarily concerned

    with the safety aspects of all electrical wiring and electri-

    cal/electronic devices, including SPDs. As an essential

    component of ensuring the safe application of an SPD, the

    NEC requires that virtually every component of the buildingwiring or device connected to the building wiring, including

    SPDs, be provided with a means of over-current protection

    [1]. In particular, Article 110-10 of the NEC states: The

    over-current protective devices, the total impedance, the

    component short-circuit current rating, and other characteris-

    tics of the circuit to be protected shall be selected and coordi-

    nated to permit the circuit-protective devices used to clear a

    fault to do so without extensive damage to the electrical

    components of the circuit. This fault shall be assumed to be

    either between two or more circuit conductors. Listed prod-

    ucts applied in accordance with their listing shall be consid-

    ered to meet the requirements of this section.2

    The NFPA 70 has added a new article to the 2002

    codebook. Article 285 Transient Voltage Surge Suppressors

    was added to address general, installation and connection

    requirements for permanently installed Transient Voltage

    Surge Suppressors. Prior to Article 285, the installation of

    SPD systems was generally referenced under NEC Article 280

    Surge Arresters. In the 2002 NEC, Article 280 continues to

    address the general installation and connection requirements

    2NEC 2002, National Fire Protection Association, Incorporated (NFPA) 70,2002.

    1-4244-0493-2/06/$20.00 2006 IEEE.

  • 8/13/2019 PESGM2006-000045

    2/5

    for Surge Arresters; however, this is beyond the scope of this

    technical report.

    Items in the 2002 NEC, the short circuit current rat-

    ing of the SPD are detailed in Article 285.5, and Article

    285.6. Article 285.5 states that the SPD shall be a Listed

    device [1]. Article 285.6 states that the SPD shall be marked

    with a short circuit current rating, which is obtained through

    an independent safety organization, and that the SPD shall beinstalled at point on the electrical distribution that does not

    exceed the rating of the SPD [1]. Listed products are those

    products that have been evaluated by an independent safety

    organization in accordance with OSHA 29 CFR 1910.7 [2].

    The predominate safety agency that provides product listings

    in the US is Underwriters Laboratories, Incorporated (UL).

    UL provides product Listing of SPDs in accordance with the

    Standard for Safety, Transient Voltage Surge Suppressor,

    number 1449, Second Edition, dated 1996 August. This

    standard will be discussed in greater detail later in this article.

    As detailed in Article 285.6, the code allows SPDs to

    be used at points within the electrical distribution system

    where the short circuit current rating of the SPD is greater

    than that of the system, but not where the short circuit current

    of the system is greater than that of the SPD SCCR. What the

    code does not address is the type of over-current protection

    that is required for the SPD to comply with these require-

    ments. It is the responsibility of the facility engineer to detail

    what the proper over-current protective device is and how the

    SPD is evaluated and determined to comply.

    B. UL Standards

    Within the United States, the UL Standards for

    Safety have long been considered the primary documents in

    assessing the safety of products. In Canada, the Canadian

    Standards Association is the primary safety assessment

    organization. There are also many other organizations that

    have been approved as independent safety assessors by

    OSHA.

    The UL Standard for Safety, Transient Voltage Surge

    Suppressors requires that the devices be subjected to many

    tests that determine the overall safety of the product. These

    tests include, but are not limited to dielectric withstand, surge

    testing, and the testing of the product to two-types of abnor-

    mal over-voltage scenarios: high current and limited-current.

    To meet the requirements of Article 285.6, UL util-

    izes the test procedure associated with abnormal over-voltages

    and high available fault currents. This is achieved by per-

    forming the full-phase voltage, high-current abnormal over-

    voltage test described in section 37.3 of UL 1449 [3]. The

    testing consists of applying an over-voltage with a specified

    available short circuit current to production representative

    SPDs. The applied over-voltage is the maximum phase

    voltage or twice the conductor pair voltage. For 120/240 Vac,

    single-phase, 3W+G system, the phase-to-neutral and phase-

    to-ground test voltages are 240 Vac. For a 120/208 Vac,

    three-phase wye, 4W+G system, the phase-to-neutral, and

    phase-to-ground test voltages are 208 Vac. In a 240 Vac,

    three-phase delta, 3W+G system, the phase-to-phase, and

    phase-to-ground test voltages are up to 480 Vac.

    To either trip or open the over-current protective

    device during the testing of the SPD, it is necessary that the

    surge components conduct a significant amount of current.

    The SPD may use either internal or external over-current

    protective components. During and following the full-phasevoltage, high-current test, the SPD shall not create openings in

    the enclosure, exhibit emission of flame, charring, glowing or

    flaming of the cheesecloth wrapped around the product during

    the test, or compromise the enclosure grounding of the SPD.

    Once the SPD has successfully completed the testing,

    the device shall be marked with its short circuit current

    rating. The marking states that the SPD is suitable for use on

    a circuit capable of delivering not more than (the nominal)

    rms symmetrical amperes, (at tested) volts maximum3. The

    short circuit current rating shall be one of the values indicated

    in Table I, but not less than the amount detailed in Table II,

    which is a reproduction of Table 61.3 and 12.1 respectively in

    [3].TABLE I

    LISTING OF AVAILABLE FAULT CURRENT RATINGS

    FROM UL 1449, SECTION 61

    Available Fault Current Rating RMS

    Symmetrical Current

    (Amperes)

    5,000

    10,000

    14,000

    18,000

    22,000

    25,00030,000

    42,000

    50,000

    65,000

    85,000

    100,000

    125,000

    150,000

    200,000

    If the SPD requires an external fuse or circuit breaker

    to pass the test at a specified SCCR, the device shall have an

    additional marking as described: when protected by __A__class fuses and/or when protected by a __B__ circuit breaker

    rated __C__ volts maximum. The interrupting rating of the

    fuse or circuit breaker shall not be less than the available fault

    current, whereAis Class CC, CD, G, H, J, L, R, T or K fuse,

    Reference to Class H or Class K fuses shall not appear in the

    marking if the indicated rms symmetrical fault current is

    3Standard for Safety, Transient Voltage Surge Suppressors, UnderwritersLaboratories, Incorporated, UL 1449, 1996 August.

  • 8/13/2019 PESGM2006-000045

    3/5

    greater than 10,000A,Bis the current rating of circuit breaker,

    and Cis the nominal system voltage.

    TABLE II

    AVAILABLE FAULT CURRENT FROM SOURCE OF SUPPLY

    FROM UL 1449, SECTION 12

    TVSS (SPD) Rating Available Current in

    Amperes

    100A or less 5,000101 400A 10,000

    Over 400A 25,000

    UL 1449 states that an external circuit interrupting

    device may be used and if one is employed in the test, then it

    is required at installation [3]. When an SPD is marked for use

    with an external over-current protective device, the test circuit

    is to include that device: e.g. circuit breaker or fuse. Installing

    an over-current protective device with an adequate interrupt-

    ing rating in series with the SPD is required at installation.

    With UL providing the test and marking requirements of the

    SPD and the NEC providing the marking requirement of the

    electrical system, an installation with the correct coordinationof the SPD and the power system available fault current is

    obtainable. The coordination of power system, over-current

    protective device and SPD are made easier as each is marked

    with its appropriate short circuit current rating.

    C. IEEE Guides

    The IEEE is active in providing recommendations

    and guidelines that help engineers correctly describe transient

    environments, and help to identify the many attributes of a

    correctly applied SPD. The most notable document on surge

    environments and the anticipated waveforms at specific

    locations within a facility are IEEE Guide on Surge Voltages

    in Low Voltage AC Power Circuits, IEEE C62.41.1-2002,and IEEE Recommended Practice on Characterization of

    Surges in Low Voltage AC Power Circuits, C62.41.2-2002.

    While the aforementioned documents do provide an

    overview of the surge environment, they do not provide any

    input into how the SPD can, or should be coordinated to the

    electrical distribution. Therefore, recommendations on the

    performance, suitability, or best engineering practice for using

    an over-current protective device in series with an SPD is

    relegated to other industry standards.

    III. APPLICATION EXAMPLE

    Two main factors should be considered when select-ing over-current devices to be used with SPDs. First, the

    ability to limit the available short-circuit energy to levels that

    are compatible with an SPD during an end-of-service life

    event. Second, the over-current device should not signifi-

    cantly affect the ability of an SPD to divert transients within

    the electrical distribution system. If an over-current protec-

    tion device connected in line with an SPD disconnects during

    a transient, the SPD is removed from the circuit when it is

    needed most. In addition, it could be some time until this is

    noticed, thereby making the SPD ineffective. Therefore,

    careful attention should be made when coordinating series

    connected over-current devices with SPDs to ensure not only

    the safe end-of-service scenario, but additionally the maxi-

    mum performance and reliability of the SPD.

    An example is the best way to illustrate the correct

    and incorrect application of an SPD in accordance with the

    codes, conditions of acceptability, and guidelines of the NEC,

    the UL, and the IEEE, respectively. In addition to providingan example of an incorrect application, the authors will also

    present remedial methods, which engineers and installers can

    use to bring the installation into compliance with the afore-

    mentioned recommendations and guidelines.

    As an example of a correct application, assume that

    an SPD is going to be installed on the power distribution

    system of a facility at a branch panel location. At this point in

    the power distribution system, the available fault current

    capability is 42,000 A. The available fault current at this

    location, or any other within the power distribution system of

    the facility, must be determined through a fault current analy-

    sis by the supervising engineer. Assume that this SPD is

    placed behind a circuit breaker with an SCCR of 42,000 A,

    shown as in Figure 1. In addition, the SPD has obtained a

    SCCR of 65,000 A. In this example, the SCCR of the SPD is

    coordinated with that of the facilitys power distribution

    system, resulting in correct and coordinated application. In

    fact, as long as the SCCR of the SPD is equal to or exceeds

    the point of application within the power distribution and the

    preceding over-current protective device, the SCCR of the

    SPD is correctly coordinated.

    As an example of an incorrect application, assume

    that a SPD has obtained a SCCR of 25,000 A from UL.

    Assume that this particular SPD was placed behind a circuit

    breaker with an SCCR of 65,000 A, as shown in Fig. 1.

    Additionally, assume that the maximum SCCR available at

    this particular location on the power distribution system is

    42,000 A. As with the previous example, the supervising

    engineer is responsible for determining the available fault

    current at this particular point within the power distribution

    system of the facility. In this particular example, the SPD is

    incorrectly applied. Because the SPD has obtained an SCCR

    rating of only 25,000 A, it might not be capable of withstand-

    ing an interrupt current of 42,000 A.

    A few different approaches can be considered to

    rectify this particular example so that the SPD has been

    installed in accordance with the NEC, the IEEE recommenda-

    tions, and UL conditions of acceptability. The first approach

    would be to apply an SPD with an SCCR of 42,000 A or

    greater. Even though the circuit breaker preceding the SPD is

    greater than the SPD, the maximum short circuit current

    available at the panel is 42,000 A. Therefore, the SPD has an

    SCCR equal to the power distribution system at that point.

    The second approach is to utilize a current limiting

    circuit breaker that will limit the SCCR to the SPD to a value

    of 25,000 A or less. This option presents some complications.

  • 8/13/2019 PESGM2006-000045

    4/5

    In accordance with the NEC, the device must be applied in

    accordance with its safety agency listing requirements. The

    SPD must have been tested with a specified circuit breaker at

    a specified current rating. Using a circuit breaker produced

    by a different manufacturer, at a different SCCR, or even a

    different part number is not acceptable and is outside the

    scope of its safety agency listing. If the SPD is installed

    utilizing an untested or improperly tested current limiting

    circuit breaker, then it is the same as not utilizing a productevaluated by an independent safety agency, such as UL.

    The third approach would be to install a finite

    amount of impedance in the line prior to the panel. The

    amount of impedance would have to be high enough to limit

    the amount of SCCR to 25,000 A or less. One possible

    method to accomplish this is by installing a transformer in the

    power distribution system to lower the overall SCCR rating at

    that particular point. This option can be very expensive and

    might require additional space, but has some advantages in

    mitigating other power quality problems that might need to be

    addressed.

    Fig. 2 represents a SPD that includes the over-current

    protection within the device itself. In this case, the SPD does

    not require that the device be preceded with a circuit breaker.

    However, the same rules apply. The SPD has a specified

    SCCR, which has been evaluated by UL; it is marked either

    on the product or in the accompanying installation instruc-

    tions, and must be connected appropriately.

    IV. RECOMMENDATIONS

    To ensure that a short circuit current rating (SCCR)

    of the SPD has been properly coordinated with the power

    distribution system of the facility, the authors recommend the

    following:

    1. A fault current analysis of the power distribution sys-

    tem be performed and documented at the time of new

    construction,

    2. A fault current analysis of the power distribution sys-

    tem be updated and documented every time new dis-

    tribution equipment is installed, e.g. power class

    transformer, increase in size of electrical conductors,

    etc.,

    3. A fault current analysis of the power distribution sys-

    tem be updated whenever there is a change in the

    utility service,

    4. A fault current analysis of the power distribution sys-

    tem be updated and documented whenever an SPD is

    installed or replaced and,

    5. That the available fault current, as determined by the

    engineer conducting the fault current analysis, be

    marked on the distribution panel.

    As part of these recommendations, it is imperative that

    the SCCR of any SPD be coordinated with the power distribu-

    tion system of the facility. This includes examining all

    existing SPDs and ensuring that the SCCR of the SPD is

    coordinated to the available fault current at these specific

    application points.

    V. CONCLUSION

    As SPDs have become a common device in the over-all picture of a complete power quality strategy, their per-

    formance and safety attributes have continued to be examined

    and tested. One of the top attributes is the safe and correct

    application, and coordination of an SPD to a power distribu-

    tion system of the facility. Analysis is required for the short-

    circuit current rating of the power distribution system, for any

    over-current protective devices, and for the SPD itself.

    The NEC has established rules determining the rela-

    tionship between the interrupting rating of a device and the

    over-current protective device required. An added clarifica-

    tion was implemented by the second edition of UL 1449 by

    testing SPDs to a particular set of conditions and providing

    SPDs with a short circuit current rating. Additionally, contri-

    butions made by the members of the IEEE on guidelines and

    recommendations of a correctly installed SPD will help ensure

    the correct application of an SPD. Responsibility for the

    coordination of the SPD to the application rests on the speci-

    fying engineer, the contractor or end-user installing the SPD

    and the inspecting official.

    In conclusion, the only set rule for determining the

    short circuit current rating of an SPD is to examine the label-

    ing, paperwork and installation instructions of that particular

    SPD. Once the short circuit current rating of the SPD has

    been determined, and a fault current analysis has been per-

    formed on the power distribution system, the appropriate SPD

    can be installed. Failure to ensure the proper application of

    the SPD with the development of specifications, guidelines,

    and standards can result in a potentially dangerous condition.

    The inappropriate application of an SPD can no longer be

    tolerated or excused.

    V. REFERENCES1. National Fire Protection Association, National Electrical Code, 2002,

    Ninth Edition, Quincy, MA.

    2. US Department of Labor, Program Regulation (29 CFR 1910.7), [On-

    line]. Available: http://www.osha.gov/dts/otpca/nrtl/nrtlregs.html.

    3. Underwriters Laboratories, Incorporated, Standard for Safety, Transient

    Voltage Surge Suppressors, Second Edition, 1996 August 15, Melville,

    NY.

  • 8/13/2019 PESGM2006-000045

    5/5

    Fig. 1. Connection of the SPD utilizing a dedicated circuit breaker Fig. 2. Connection of the SPD utilizing the main circuit breaker of the

    panel.

    Bryan Cole, NCE (M, 1993) is the President of

    Technology Research Council, LLC, and former

    Director of Engineering & Product Safety Officer for

    Control Concepts Corporation. Bryan has been

    involved with the R&D of one-port and two-port surgeprotection devices, electromagnetic interference (EMI)

    filters, and harmonic filters, and product safety for

    eighteen years. He a member of the IEEEs Power Engineering, Engineer-

    ing Management, Product Safety, and EMC Societies, a member of UL

    Standard Technical Panel for TVSS, temporary power taps, and Switchgear

    and Panelboards, and member of the US National Committee to the IEC on

    SPDs. Bryan is a NARTE Certified Engineer in product safety, has a

    Bachelors degree in Electrical Engineering from Binghamton University, a

    MBA from the University of Phoenix, and is a PhD student at Northcentral

    University.

    Kenneth Brown (M', 1996) is the Director of

    Engineering for Power Quality Products at Leviton

    Manufacturing Company. Ken has been involved

    with the design and development of surge protection

    devices for 8 years. Ken is presently chairman of thetechnical committee for the NEMA 5VS Section.

    Ken is a member of the US National Committee to

    the International Electro-technical Commission on

    SPDs (37A) and he is a member of the IEEE Working Group's 3.6.4,

    3.6.6, 3.6.9, and 3.6.10. Ken received an undergraduate degree in

    Electrical Engineering from the Ohio Institute of Technology, and an

    MBA from West Coast University.

    Pat McCurdy (M, 1996) is the Product Marketing

    Manager and technical specialist for Phoenix Con-

    tacts North American Surge Protection division.

    Patrick has worked for Phoenix Contact in various

    technical, application, and management roles foreleven years. Patrick has a Bachelor of Science

    Degree in Electrical Engineering Technology from

    Penn State University and a Master in Business

    Administration from Lebanon Valley College. Active

    professional associations include: International Society of Measurements

    and Control (ISA), Institute of Electrical and Electronic Engineers (IEEE),

    American Gas Association (AGA), and National Electrical Manufacturers

    Association (NEMA).

    Thomas Phipps (M 2000) received the Manasseh

    Cutler Scholarship at Ohio University in Athens,

    Ohio while majoring in Electrical Engineering.

    Tom has been involved in power quality engineer-

    ing over the past seventeen years working in areasof Production, Applications, Test, and Research &

    Development Engineering. His employment

    experience includes the areas of power condition-

    ing, power distribution, Rotary and Static UPS and for the past eleven

    years TVSS. Tom has worked for several of the power conditioning

    companies within the industry including Power Distribution, Incorpo-

    rated, United Power, Incorporated, Power Systems & Controls and is

    presently the Vice President of Engineering for Thor Systems, Incorpo-

    rated located in Richmond, Virginia.

    Ron Hotchkiss is the Vice President of Engineering

    for Surge Technology. Ron has been involved in the

    design, development and certification testing of one-

    port and two-port surge protection devices for thirteen

    years. Ron also manages engineering, safety agency,

    compliance and quality operations. He is a member of

    IEEEs Power Engineering Society and is an active

    participant and contributor to several IEEE SPD

    working groups and the Underwriters Laboratories

    Standard Technical Panel for Transient Voltage Surge Suppressors. He is a

    member of the balloting group for IEEE. Ron received his Electrical

    Engineering degree with Honors from the University of South Florida in

    Tampa.

    Branch

    Panel

    Main

    Circuit

    Breaker

    (Service

    Entrance)

    SPD

    L1

    L2

    L3

    N

    G

    L1

    L2

    L3

    N

    G

    Ground Bar Neutral Bar

    3-Phase

    Circuit Breaker

    Branch Panel

    Main Circuit Breaker

    Conductors to Other

    Branch Panels

    Branch

    Panel

    Main

    Circuit

    Breaker

    (Service

    Entrance)

    SPD

    L1

    L2

    L3

    N

    G

    L1

    L2

    L3

    N

    G

    Ground Bar Neutral Bar

    Branch Panel

    Main Circuit Breaker

    Conductors to Other

    Branch Panels