  • PD300

    Transformer, generator and motor protection

    Data sheet

  • DSE_PD300_eng_AP

    No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam Technology.

    One of the main aims of Ingeteam Technology lies in the continuous improvement of the companys equipment and, therefore, the information contained in this catalogue may be modified without prior notification.

    For further information, consult the corresponding manual or contact us directly.

  • INDEX

    Ingeteam Technology S.A.

    DSE_PD300_eng III

    MODEL CODE SELECTION ........................................................................................................... 4

    FUNCTIONS TABLE ..................................................................................................................... 5

    FUNCTIONAL DESCRIPTION AND CONFIGURATION ...................................................................... 6 General settings ........................................................................................................................................ 6 Protection settings .................................................................................................................................... 6

    AUTOMATISM FUNCTIONS ........................................................................................................ 12

    DATA ACQUISITION ................................................................................................................... 13

    MEASUREMENTS ...................................................................................................................... 13

    COMMUNICATION PROTOCOLS .................................................................................................. 14

    KEYPAD/LOCAL DISPLAY ........................................................................................................... 15

    TESTS ...................................................................................................................................... 15

    TECHNICAL SPECIFICATIONS .................................................................................................... 16

    ENVIRONMENTAL CONDITIONS ................................................................................................. 18

    CONSTRUCTION FEATURES ...................................................................................................... 18

    CONNECTION DIAGRAMS .......................................................................................................... 20

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 4

    MODEL CODE SELECTION

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 5

    FUNCTIONS TABLE

    Note: X: Available function O: Optional function

    PD300-2 PD300-3 PD300-G Protection functions

    Overexcitation (24) 5th harmonic or V/Hz 2 units. 5th harmonic 5th harmonic

    Undervoltage (27) X X

    Current unbalance (46) X X X

    Thermal image (49) X X X

    Instantaneous phase overcurrent (50) 2 units in each winding 2 units in each winding 2 units in each winding

    Time phase overcurrent (51) 1 unit in each winding 1 unit in each winding 1 unit in each winding

    Residual instantaneous overcurrent (50R) 2 units in each winding 2 units in each winding 2 units in each winding

    Residual time overcurrent (51R) 1 unit in each winding 1 unit in each winding 1 unit in each winding

    Instantaneous ground overcurrent (50G) 2 units in each winding 2 units in each winding

    Time ground overcurrent (51G) 1 unit in each winding 1 unit in each winding

    Breaker failure (50BF) X X X

    Overvoltage (59) X X

    Overfrequency (81M) 5 steps 5 steps

    Underfrequency (81m) 5 steps 5 steps

    Differential (87) In percentage and

    instantaneous

    In percentage and

    instantaneous

    In percentage and

    instantaneous

    Restricted earth (87G) X X

    Breaker monitoring X X X

    Trip and closure circuit surveillance (74TC/CC) X X X

    Power supply monitoring O O O

    External power supply monitoring O O O

    Temperature monitoring X X X

    Automatisms and commands

    Breaker and closure commands X X X

    Programmable logic X X X

    Breaker closure lock (86) X X X

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 6

    FUNCTIONAL DESCRIPTION AND CONFIGURATION

    GENERAL SETTINGS

    Setting Minimum Maximum Step Remarks Relay in operation YES/NO Breaker number 5 alphanum. characters

    PROTECTION SETTINGS

    Differential protection (87)

    Three-phase differential unit. Numeric ratio and connection group correction. Zero sequence component filter: Enables the elimination of the phase currents zero sequence component. Adjustable differential current instantaneous trip. 2nd, 2nd + 4th and 5th harmonic restraint, adjustable (Not available for PD300-G). Cross blocking (except in PD300-G).

    General settings Minimum Maximum Step Remarks Rated voltage winding 1(kV) 1 1000 0,1 Rated voltage winding 2(kV) 1 1000 0,1 Rated voltage winding 3(kV) 1 1000 0,1 C.T. ratio winding 1 1 10000 0,1 C.T. ratio winding 2 1 10000 0,1 C.T. ratio winding 3 1 10000 0,1 Connection type winding 1/2/3 Y/D/Z Phase shift 1-2 0 11 1 Phase shift 1-3 0 11 1 Function 86 enabled YES/NO Grounding 1 C.T. ratio 1 10000 0,1 Grounding 2 C.T. ratio 1 10000 0,1 VT ratio 1 10000 0,1 Maximum power capacity (MVA) 0,0 5000 0,1

    Tap winding 1 0,5 0,1

    100 20

    0,01 0,01

    In = 5A In = 1A and PD300-G

    Tap winding 2 0,5 0,1

    100 20

    0,01 0,01

    In = 5A In = 1A and PD300-G

    Tap winding 3 0,5 0,1

    100 20

    0,01 0,01

    In = 5A In = 1A

    Differential 2/3 windings 2wind. /3wind.

    Percentage charact. setting Minimum Maximum Step Remarks Enabled YES/NO Sensitivity (xTap) 0,15 2 0,01 Restraint current 1 (xTap) 0 2 0,01 Restraint current 2 (xTap) 0 20 0,01 1 (%) 5 100 1 2 (%) 5 200 1 Additional delay (s) 0 60 0,01

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 7

    Instantaneous differential setting Minimum Maximum Step Remarks Enabled YES/NO Trip (xTap) for PD300-2 and PD300-3 1,0 20 0,01 Trip (xTap) for PD300-G 0,60 4,00 0,01 Additional delay (s) 0 60 0,01 Harmonic restraint setting (disabled for PD300-G) Minimum Maximum Step Remarks

    2nd harmonic restraint enabled NO / 2nd PHASE / 2nd GLOBAL/ 2nd+4th PHASE / 2nd+4th GLOBAL

    2nd harmonic restraint threshold (%) 5 100 1 Differential threshold (xTap) 0,15 1 0,01 5th harmonic restraint enabled NO / PHASE / GLOBAL 5th harmonic restraint threshold (%) 5 100 1 Differential threshold (xTap) 0,15 1 0,01

    Restricted earth (87G) - Models PD300-2 and PD300-G

    This function is applicable when one of the transformers windings is grounded. The function compares the residual current with the current flowing through the grounded transformer. Should the difference between both currents, following the application of the corresponding transformation ratios, exceed the set threshold, a trip signal is issued. The direction is taken into account when allowing the trip.

    Phase overcurrent protection (50/51) - All models

    A back-up protection for external or internal transformer faults. In the event of such faults not being cleared by the primary protections, the overcurrent protection acts. Serious damage to the transformer would be produced in the absence of such protection. Each winding is equipped with two instantaneous levels and one timed level.

    Time charactistic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO

    Pick up (A) 0,1 0,02

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Curve type

    Definite time (TF) Inverse curve, very inverse, extremely inverse User curves

    Dial 0,05 0,5

    1,09 30,0

    0,01 0,1

    For IEC curves For ANSI curves

    Definite delay (s) 0,0 600,0 0,01 Instantaneous charactistic setting (low-level - 6 groups) Minimum Maximum Step Remarks Enabled YES/NO

    Pick up (A) 0,1 0,02

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Additional delay (s) 0,00 60,00 0,01

    Setting

    Minimum

    Maximum

    Step

    Remarks

    Enabled

    YES/NO

    Pick up (A)

    0,25

    0,05

    20

    4

    0,01

    0,01

    In = 5 A

    In = 1 A and Generator and motor

    Additional time (s)

    0 60 0,01

    Winding comparison Wind. 1, Wind. 2 or Autotransformer

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 8

    Instantaneous characteristic setting (high-level - -6 groups) Minimum Maximum Step Remarks Enabled YES/NO

    Pick up (A) 0,1 0,02

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Additional delay (s) 0,00 60,00 0,01

    Residual overcurrent protection (50/51R) - All models

    An overcurrent function that is applied to the directional sum of the three phases in order to detect earth faults. It is equipped with independent units for each of the windings.

    Time characteristic settings (6 groups) Minimum Maximum Step Remarks Enabled YES/NO

    Pick up (A) 0,2 0,05

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Curve type

    Definite time (TF) Inverse curve, very inverse, extremely inverse User curves

    Dial 0,05 0,5

    1,09 30,0

    0,01 0,1

    For IEC curves For ANSI curves

    Definite delay (s) 0,0 600,0 0,01 Instantaneous characteristic settings (low-level -6 groups) Minimum Maximum Step Remarks

    Enabled YES/NO

    Pick up (A) 0,2 0,05

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Additional delay (s) 0,0 60,00 0,01 Instantaneous characteristic settings (high-level -6 groups) Minimum Maximum Step Remarks

    Enabled YES/NO

    Pick up (A) 0,2 0,05

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Additional delay (s) 0,0 60,00 0,01

    Current unbalance protection (46) - All models

    Protects the installation against current unbalances that occur as a consequence of anomalies in the power system, or against unbalanced loads. It is equipped with independent units for each of the windings.

    Time charactieristic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO

    Pick up (A) 0,2 0,05 160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Curve type

    Definite time (TF) Inverse curve, very inverse, extremely inverse User curves

    Dial 0,05 0,5

    1,09 30,0

    0,01 0,1

    For IEC curves For ANSI curves

    Definite time (s) 0,0 600,0 0,01 Instantaneous charactistic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO

    Pick up (A) 0,2 0,05

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Additional delay (s) 0,0 60,00 0,01

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 9

    Earth overcurrent protection (50/51G) - Models PD300-2 and PD300-G

    Is applied to the power transformers grounding in order to detect earth faults. It may also be applied as a tank protection.

    Timed charactistic settings (6 groups) Minimum Maximum Step Remarks Enabled YES/NO/Pickup/YES+Drop-out

    Pick up (A) 0,1 0,02

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Curve type Definite time (TF) Inverse curve, very inverse, extremely inverse User curves

    Dial 0,05 0,5

    1,09 30,0

    0,01 0,1

    For IEC curves For ANSI curves

    Definite time (s) 0,0 600,0 0,01 Delay if TF type Instantaneous charactistic setting Low-level (6 groups) Minimum Maximum Step Remarks Enabled YES/NO/ Pickup

    Pick up (A) 0,1 0,02

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Additional delay (s) 0,00 60,00 0,01 High level instantaneous characteristic settings (6 groups) Minimum Maximum Step Remarks Enabled YES/NO/ Pickup

    Pick up (A) 0,1 0,02

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Additional delay (s) 0,00 60,00 0,01

    Overvoltage protection (59) - Models PD300-2 and PD300-G

    This function protects the transformer against overvoltages, issuing a trip command when the voltage exceeds the set value during a set period.

    Time charactistic setting (6 groups) Minimum Maximum Step Remarks Enabled YES/NO Pick up (V) 10 200 0,1

    Curve type

    Definite time (TF) Inverse curve, very inverse, extremely inverse User curves

    Dial 0,05 0,5

    1,09 30,0

    0,01 0,1

    For IEC curves For ANSI curves

    Definite time (s) 0,0 600,0 0,01 Instantaneous charactic setting (6 groups) Minimum Minimum Step Remarks Enabled YES/NO Pick up (V) 10 200 0,1 Additional delay (s) 0,00 60,00 0,01

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 10

    Undervoltage protection (27) - Models PD300-2 and PD300-G

    Undervoltage may occur in the system during faults or similar situations.

    Time charactistic settings (6 groups) Minimum Maximum Step Remarks

    Enabled YES/NO

    Pick up (A) 10 200 0,1

    Curve type

    Definite time (TF) Inverse curve, very inverse, extremely inverse User curves

    Dial 0,05

    0,5

    1,09

    30,0

    0,01

    0,1

    For IEC curves

    For ANSI curves

    Definite time (s) 0,0 600,0 0,01

    Instantaneous charactistic setting (6 groups) Minimum Maximum Step Remarks

    Enabled YES/NO

    Pick up (V) 10 200 0,1

    Additional delay (s) 0,00 60,00 0,01

    Overexcitation protection (24) - All models

    This function prevents the transformers from working at a flux density higher to that for which they have been designed, thus avoiding overheating and the subsequent damage to the transformer resulting from overexcitation. It can be detected through 5th harmonic current level or through the V/f ratio.

    5th harmonic setting Minimum Maximum Step Remarks Enabled YES/NO

    Minimum operating current 0,50 0,1

    10 2

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Pick-up (%) 5 100 1 Additional delay (sec) 0 600 0,01 Setting for V/f (not available for PD300-3) Minimum Maximum Step Remarks Enabled YES/NO Minimum monitoring voltage (V) 50 150 1 Pick up (V/Hz) 1,00 4,00 0,01

    Curve type

    Definite time (TF) Inverse curve, very inverse, extremely inverse User curves

    Dial 0,05 0,5

    1,09 30,0

    0,01 0,1

    For IEC curves For ANSI curves

    Definite time (s) 0 600 0,01

    Frequency protection (81M/m) - Models PD300-2 and PD300-G

    The frequency unit provides protection against overexcitation. It may also be employed in subfrequency load-shedding schemes, assisting operation in the event of network instability, for which there are 5 steps.

    The settings, which are independent for each step, are individualized for each step (6 groups):

    Minimum Maximum Step Remarks Enabled YES/NO Pick up (Hz) 45 65 0,01 Additional delay (s) 0 600,00 0,01 Type Maximum/Minimum

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 11

    The common settings for all steps are as follows:

    Setting Minimum Maximum Step Remarks Minimum monitoring voltage (V) 40 200 1 N of frequency pick-up cycles 3 15 1

    Thermal image (49) All models

    Protects the unit against thermal overloads by calculating the temperature in accordance with the protected units current and recent load conditions.

    Setting Minimum Maximum Step Remarks Enabled YES/NO Heating time constant (min) 3 60 1 Cooling time constant (min) 3 180 1 Alarm threshold (%) 60 100 1

    Rated current (A) 0,2 0,04 0,04

    10,0 2 10,0

    0,01 0,01 0,01

    In = 5A In = 1A PD300-G

    Breaker failure protection (50BFI) - All models

    Verifies the correct operation of a breaker when clearing a fault. In case of an operation failure, the protection trips the adjacent breakers involved in the isolation of the area in fault.

    Setting Minimum Maximum Step Remarks Enabled YES/NO

    Phase restoration (A) 0,1 0,02

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Neutral restoration (A) 0,1 0,02

    160,0 32,0

    0,01 0,01

    In = 5 A In = 1A and PD300-G

    Definite retrip time (sec) 0,05 60,00 0,01 Definite trip time BF (sec) 0,05 60,00 0,01

    Breaker monitoring - All models

    A signal is generated when, following a trip, the kI2 counter exceeds the programmed threshold. The counter may be reset to the initial value by means of a command.

    Setting Minimum Maximum Step Remarks kI2 alarm threshold 0 65534 1 Initial kI2 value 0 65534 1

    Operating logic - All models

    Verifies the correct operation of the breaker.

    Setting Minimum Maximum Step Remarks Trip contact sealing YES/NO Closure sealing YES/NO Breaker opening failure timing (s) 0,02 5,0 0,01 Breaker closure failure timing (s) 0,02 5,0 0,01

    Coil monitoring - All models

    The monitoring of the trip and closure circuits allows to check the continuity of the trip and closure coil circuits to be monitored, both when the breaker is closed and when it is open.

    Setting Minimum Maximum Step Remarks Trip circuit monitoring enabled YES/NO Closure circuit monitoring enabled YES/NO

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 12

    AUTOMATISM FUNCTIONS

    External power supply monitoring

    Only available in models equipped with the Battery voltage measurement option.

    Setting Minimum Maximum Step Remarks Enabled YES/NO Minimum threshold (V) 20 220 1 Maximum threshold (V) 24 280 1

    Temperature monitoring

    Monitors the units temperature and generates an alarm when the temperature exceeds the set range.

    Setting Minimum Maximum Step Remarks Enabled YES/NO Minimum threshold () -40 0 1 Maximum threshold () 50 100 1

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 13

    DATA ACQUISITION

    Type Description Non-volatile memory capacity

    Events

    Date and time: Day/month/year hour/min/sec. m.sec. Description of the event Currents of each winding per phase, differential currents per phase, earth currents (PD300-2 and PD300-G) and voltage (PD300-2 and PD300-G)

    400 events

    Faults

    Date and time: day/month/year hour/min/sec. m.sec Description of the fault Detail:

    Available units Units tripped during the fault Units picked-up during the fault Fault start date and -time Trip date and time Fault end date and time Current opened by breaker Setting group active during the fault Fault and trip type Differential current Restraint current Fault and pre-fault phase current Neutral current Fault and pre-fault voltage (PD300-2 and PD300-G) Tripped phases Differential and restraint currents of each phase at the time of the trip Phase and neutral currents at the time of the trip Fault start and finish date and time

    20 faults

    Measurement historical reports

    Date and time recording Each recording contains the maximum and minimum average currents of each winding

    4000 recordings

    Statistical data kl2 sum (kA opened per breaker, squared) Opening counters for each breaker Trip counters for each breaker

    Oscillograph data recorder Up to 9 analog channels, the number of samples per analogical channel cycle is 32 Up to 32 digital channels

    1200 cycles. The number of cycles per disturbance can be programmed

    MEASUREMENTS

    Phase current for each winding (A) Average current per winding (A) Differential current (A) (1st, 2nd and 5th harmonic) Current maximeter (A) Ground current (A) (PD300-2 and PD300-G) Voltage (kV) (PD300-2 and PD300-G) Frequency (Hz) (PD300-2 and PD300-G) Device temperature measurement (optional) DC power supply voltage measurement (optional)

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 14

    COMMUNICATION PROTOCOLS

    Front serial port RS232

    PROCOME Equipped with one or two serial outputs, or one serial output and one Ethernet output.

    COM-1 rear serial port (RS232, RS485, G.F.O., P.F.O.)

    PROCOME

    COM-2 rear serial port (RS232, RS485, G.F.O., P.F.O)

    PROCOME DNP3.0 MODBUS IEC 870-5-101 (except with RS485) IEC 870-5-103

    Ethernet communication (only for models with Ethernet port)

    PROCOME encapsulated Peer to peer communications IEC 61850

    IEC 61850 communication options

    Single RJ45 Ethernet Single FOC Ethernet Double GFO or RJ45 Ethernet redundancy

    These IEC 61850 models (R-type box) for serial communication include:

    1 RS232 port Procome protocolCOM-6 1 GFO (unique option in case of double GFO or RJ45 Ethernet) or RS485 protocol DNP3.0.COM-2

    For more information of redundancy see DSS_IEC61850 document.

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 15

    KEYPAD/LOCAL DISPLAY

    TESTS

    16-KEY KEYBOARD

    LCD 2 LINES WITH 16 CHARACTERS

    7 RED LEDS AND 1 GREEN/RED

    RS232C connector

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 16

    TECHNICAL SPECIFICATIONS

    Auxiliary power supply 24-48 Vdc Range 18-60 Vdc Ripple 20 % over the rated value Burden 8W min/ 18W max 110-125-220 Vdc Range 86-280Vdc Ripple 20% over the rated value Burden 8W min/ 18W max Current circuits Thermal capacity for phase/neutral I Continuous 20 A Short term (1 s.) 500 A Very short term ( cycles) 1250 A Burden at I = 5 A

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 17

    Auxiliary relay 7 (and 14) Carry (permanent) 5 A at 25 C Make and carry for 0.5 s 30 A Breaking capacity (L/R=40 ms)

    - 220 Vdc 0.15 A - 125 Vdc 0.3 A - 48 Vdc 0.5 A

    Breaking capacity (resistive) - 220 Vdc 0.2 A - 125 Vdc 0.4 A - 48 Vdc 0.2 A

    Performance time 8 ms. Frequency Programmable system frequency 50 or 60 Hz Operational range Fn 5 Hz Communications ports Front communication port RS232C connector DTE 9 pin D type female Cable length 3 m maximum Baud rate 600-38400 bps Insulation No Types of rear communication ports (COM-1 and COM-2) RS232

    - RS232C connector DTE 9 pin D type female - Cable type Shielded - Cable length 15 m max. - Insulation 500V

    RS485 - RS485 connector DTE 9 pin D type female - Cable type Shielded twisted pair - Cable length 1,000 m max. - Insulation 500V

    G.F.O. - Connector ST - Wavelength 820nm - Attenuation 8 db with 62.5 /125 m glass fibre - Glass fibre optic Multimode 62.5 /125 m - Maximum distance 1.5 Km

    P.F.O. - Connector HP standard - Wavelength 660 nm

    - Attenuation 24.7 db with 1mm plastic cable 22 db with 200 m silica cable

    - Maximum distance 115 m with 1mm plastic cable 1.9 Km with 200 m silica cable

    Ethernet RJ45 Connector RJ45 Female Cable type Shielded Cable length 100 m max. Insulation 500V Baud rate 10/100 Mbps G.F.O. Ethernet Connector ST Wavelength 1300nm Permitted attenuation 8 db with 62.5 /125 m glass fibre Multimode glass optical fibre 62.5 /125 m Maximum distance 1.5 Km

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 18

    IRIG-B port Input Demodulated Input level TTL Cable type 2-wire, shielded Insulation 500 V Maximum distance 1.5 Km Accuracy Accuracy Class 0.5 for V, I and P (up to 120% nominal) Accuracy in the protected range 3% Curve operation accuracy 5% or 30ms (the highest of the two values) Battery voltage monitoring (optional) 24-48 Vdc Range 18 to 60 Vdc 110-125-220 Vdc Range 86 to 280 Vdc Mechanical characteristics Weight 2.8 Kg Approx. weight with packaging and documentation 3.8 Kg Front IP IP40 Optional front IP IP54

    ENVIRONMENTAL CONDITIONS

    Operating temperature -20C to 75C Storage temperature -40C to 85C Relative humidity Up to 95% without condensation

    CONSTRUCTION FEATURES

    PD300-H model dimensions

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 19

    PD300-V model dimensions

    IEC61850 and TCP model dimensions

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 20

    CONNECTION DIAGRAMS

    2 winding, pin terminal models

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 21

    2 windings, closed-terminal models

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 22

    3 windings, pin-terminal models

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 23

    3 windings, closed-terminal models

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 24

    Generator, pin-terminal models

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 25

    Generator, closed-terminal models

  • TRANSFORMER, GENERATOR AND MOTOR PROTECTION

    Ingeteam Technology S.A.

    DSE_PD300_eng 26

    Ingeteam Technology, S.A.

    www.ingeteam.com

    Parque Tecnolgico de Bizkaia Edificio 110 48170 Zamudio, Bizkaia, Spain

    Tel + 34 944 039 600 Fax +34 944 039 679

    [email protected]

    Model code selectionFunctions tableFunctional description and configurationGeneral settingsProtection settings

    Automatism functionsData acquisitionMeasurementsCommunication protocolsKeypad/local displayTestsTechnical specificationsEnvironmental conditionsConstruction featuresConnection diagrams