pcc1302 operator instructions

Upload: cuong-tran

Post on 13-Oct-2015

73 views

Category:

Documents


1 download

TRANSCRIPT

  • 5/23/2018 PCC1302 Operator Instructions

    1/34

    PowerCommandControl 1302Operator Instructions

  • 5/23/2018 PCC1302 Operator Instructions

    2/34

  • 5/23/2018 PCC1302 Operator Instructions

    3/34

    Table of Contents

    SECTION TITLE PAGE

    1 PCC 1302 Control Operation 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    PCC 1302 Features 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Local Status Output 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Operating Modes 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Off Mode 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Manual Run Mode 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Auto Mode 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Sleep Mode 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Configuring Sleep In Auto Mode 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installations with a Control Panel 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installations with a Manual Run/Off/Auto Switch 1-3. . . . . . . . . . . . . . . . . . . . . .

    Battle Short Mode 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installations with a Control Panel 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Installations without a Control Panel 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Control Panel 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Graphical Display 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Display Text / Symbolic Versions 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Display Menu Selection Buttons 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Previous Main Menu Button 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Off Button 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Not In Auto Indicator 1 7

  • 5/23/2018 PCC1302 Operator Instructions

    4/34

    Table of Contents (Continued)

    SECTION TITLE PAGE

    Selecting Auto, Manual Run, and Off Modes 1-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Entering the Mode Change Access Code 1-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Selecting Auto Mode 1-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Selecting Manual Run Mode 1-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Aborting the Transition to Auto or Manual Run Mode 1-19. . . . . . . . . . . . . . . . . . . .Selecting Off Mode 1-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Service Menus 1-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Status Menu 1-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Network Status Menus 1-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    History / About Menus 1-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    History Submenu 1-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .About Genset Submenus 1-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .About Control Submenu 1-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .About Display Submenu 1-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Fault History Menu 1-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Screen Adjust Menu 1-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Adjusting Values/Parameters 1-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Screen Adjust Menu 1-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 5/23/2018 PCC1302 Operator Instructions

    5/34

    1. PCC 1302 Control Operation

    TB15

    TB1

    J20

    DS1 LEDSTATUS

    INDICATOR

    J12

    J17

    J18

    J22

    J25

  • 5/23/2018 PCC1302 Operator Instructions

    6/34

    A PCC 1302 installation may also include the fol-lowing options.

    If a control panel is mounted on the genset(local display), one additional control panelcan be mounted up to 4000 feet from thegenset (remote displays). A setup menu inthe optional display panel is required to des-ignate a display as Local or Remote.

    Local status indicator lamp driver

    Remote and local emergency stop

    Four configurable inputs

    Annunciator fault inputs 1, 2, and 3 Theseoutputs can be used when an annunciator isinstalled as part of an PCCNet interface con-nected to TB1-2 and TB1-3. Grounding oneof these inputs on the annunciator activatesthe corresponding warning or shutdown se-quence.

    Three Customer Annunciator Text messagesubmenus are supplied to enter the event typeand description (see page 1-28).

    ECM CAN engine interface

    Local Status Output

    is flashed, followed by a half-second pauseand the third digit is flashed, followed by a half-second pause and then the fourth digit isflashed, followed by a two-second pause.

    NOTE: Only the last shutdown fault is flashed.

    OPERATING MODES

    The PCC 1302 works with a Manual Run/Off/Autoswitch, used to control genset operating modes.This capability is located either in the harness(switch) or is integrated into the optional control pan-

    el.

    Off Mode

    When in Off mode, the control does not allow thegenset to start. If the genset is already running andthe control is set to Off, it initiates a normal shut-down sequence.

    Manual Run Mode

    When in Manual Run mode, the genset starts andcontinues to run until the control is put into the Offmode. While in Manual Run mode, the remote startsignal is ignored.

  • 5/23/2018 PCC1302 Operator Instructions

    7/34

    Emergency Stop Mode

    When an optional emergency stop button is used, itimmediately shuts down the generator set, bypass-

    ing any time delay stop. If an optional emergencystop is not used, the local and remote E-stop sig-nals must be shorted to GND. The red ShutdownLED lights and one of the two emergency stop faultcodes (1433 Local Emergency Stopor 1434 Remote Emergency Stop) is either displayed(installations with a control panel) or flashed (instal-lations with a status indicator lamp), depending onwhich was activated last.

    To reset the control, close (disable) the activeemergency stop button(s) and perform a fault reset(see page 1-9).

    Sleep Mode

    The PCC 1302 control enters a low power (sleep)mode of operation where the current draw is not

    greater than 60 milliamps (DC) at normal batteryvoltage levels. The control is set to enter sleepmode after five minutes in Off mode or Auto mode,if configured. (Sleep mode can be disabled if a

    jumper is installed connecting TB15-1 to TB15-5.)

    The control will not enter the sleep mode if there are

    5. Disconnect the PCC 1302 from InPower.

    Installations with a Control Panel

    Sleep mode is automatically enabled on the controlpanel. The PCC 1302 control determines that itshould sleep when the display panel has had nokey presses for five minutes and wake-up signalsare inactive. The control system can be awakenedby pressing the keypad on the control panel or byactivating any wake-up input.

    Installations with a Manual Run/Off/Auto

    Switch

    For installations that utilize an Manual Run/Off/Autoswitch located in the harness, the control awakesfrom sleep mode if Manual Run mode is selected.The control will also wake up if Auto mode is se-lected and the control is configured to stay awakewhen in Auto mode, Wake-In-Auto = Enabled.

    Battle Short Mode

    The purpose of Battle Short is to satisfy local coderequirements, where necessary. To use this fea-ture, the necessary software must either beinstalled at the factory when the PCC 1302 is pur-chased or else installed by a customer service rep

  • 5/23/2018 PCC1302 Operator Instructions

    8/34

    Installations with a Control Panel

    Battle Short can be enabled or disabled (set to Ac-tive or Inactive) using the control panel.

    The PC service tool is required to enable theBattle Short mode feature. Contact an autho-rized service center for assistance.

    Before Battle Short can be used on installationswith the display panel, the Switch Input setting onthe Battle Short submenu must be set to OperatorPanel (see page 1-11). In addition, Battle Shortmode must be enabled (set to Active) in the Battle

    Short submenu (see page 1-11).When Battle Short mode is enabled, the Warningstatus indicator lights, and code 1131 Battle ShortActiveis displayed.

    When Battle Short mode is enabled and anoverrid-den shutdown fault occurs, the shutdown lamp re-mains lit even though the genset continues to run.Fault code 1416 Fail to Shut Downis displayed. If

    the , , or button is pressed to acknowledgethe fault, the fault message is cleared from the dis-play but remains in the Fault History file.

    Battle Short is suspended and a shutdown occursimmediately if:

    A f th f ll i h td f lt

    (see page 1-11) and select Inactive. Faultcode 1123 Shutdown After Battle Shortis then displayed.

    Installations without a Control Panel

    A Manual Run/Off/Auto switch must be installed ininstallations that do not include a control panel.Battle Short can be turned on or off with a customerinstalled external switch connected to one of thefour configured inputs.

    The PC service tool is required to enable theBattle Short mode feature and to enable the ex-

    ternal Battle Short switch using one of the fouravailable customer inputs. Contact an autho-rized service center for assistance.

    When Battle Short mode is enabled and an overrid-den shutdown fault occurs, the genset continues torun and the status indicator lamp flashes the shut-down fault code. See Local Status Output on page1-2 for information on interpreting the status indi-

    cator light.

    Battle Short is suspended and a shutdown occursimmediately if:

    Any of the following shutdown faults occurs.

    Overspeed Fault code 234

  • 5/23/2018 PCC1302 Operator Instructions

    9/34

    PREVIOUS MENU

    LEVEL BUTTON

    GRAPHICALDISPLAY

    OFF MODEBUTTON

    DISPLAY MENU

    SELECTION BUTTONS

    LEDINDICATORS

    HMI1211

    FIGURE 1-2. PCC 1302 OPTIONAL CONTROL PANEL

    CONTROL PANEL

    Figure 1-2 shows the front of the optional control

    TABLE 1-1. SYMBOLS

    SYMBOL DESCRIPTION

  • 5/23/2018 PCC1302 Operator Instructions

    10/34

    Display Menu Selection Buttons

    Four momentary soft-key buttons are used to stepthrough the various menus and to adjust parame-

    ters. These selection buttons are active when aword or symbol in the graphical display is shownabove the button. Some submenus do not includeany active buttons.

    The function of the four selection buttons varieswith each menu.

    When the symbol is displayed, theselection button can be used to switch to

    Automode.

    When the symbol is displayed, the selec-tion button can be used to switch to ManualRunmode.

    When the up and down triangles ( and )are displayed, the selection buttons are usedto navigate between a series of submenus.

    NOTE: When any Operator menu is dis-played, a series of Service menus canbe viewed by simultaneously pressingthe and selection buttons for twoseconds (see page1-20).

    tor menu that was displayed before the Autoor Manual Run mode was selected.

    When ADJUSTis displayed, the selection

    button is used to display an adjustablemenu. When the ADJUST button is pressed,the first adjustable parameter or value in thesubmenu is highlighted.

    When the symbol is displayed, theselection button is used to navigate to aneditable field within a menu.

    When the +and symbols are displayed,

    the selection buttons are used to increase ordecrease a parameter or value shown on thescreen.

    When changing values, pressing the buttonbelow the + symbol increase the value andpressing the button below the symbol de-creases the value.

    When SAVEis displayed, the selection but-ton is used to save changes made in a sub-menu. If the Previous Menu button ispressed before pressing SAVE, thechanges are not saved.

    Some menus include a list of numbered sub-

  • 5/23/2018 PCC1302 Operator Instructions

    11/34

    Previous Main Menu Button

    Press the button to view the previous mainmenu.

    NOTE: In the Screen Adjust menu, settings are not

    saved when the button is pressed.

    OFFBUTTON

    If the button is pressed during genset operation(manual or remote start), the engine immediatelyshuts down and the control enters the Off mode. Ifpossible, this hot shutdown should be avoided to

    help prolong the reliability of the genset.

    Not In Auto Indicator

    This red lamp is lit when the control is not in theAuto mode.

    Shutdown Indicator

    This red lamp is lit when the control detects a Shut-down condition. The generator set cannot bestarted when this lamp is on. After the condition iscorrected, the lamp can be reset by performing afault reset. When Battle Short mode is enabled andan overridden shutdown fault occurs, the Shut-down lamp is lit even though the genset continuesto run.

    Warning IndicatorThis yellow lamp is lit whenever the control detectsa warning condition. This lamp is automaticallyshut off when the warning condition no longer ex-ists.

    R S I di

  • 5/23/2018 PCC1302 Operator Instructions

    12/34

    CONTROL PANEL SYSTEM MESSAGES

    A system pop-up message is displayed when theevent it is displaying becomes active. These pop-

    up messages remain displayed until pre-empted byanother pop-up message or until the or thedisplay buttons is pressed or the event has expired.

    Once the or the button is pressed, the pre-vious screen is redisplayed.

    Communication Messages

    System messages are displayed for initial power-

    up or when there is a subsequent loss of commu-nications. Auto and Manual Run modes can also beselected when communication messages are dis-played (for more information, see page 1-18).

    Upon initial power-up, the message Establishingcommunication with control is displayed (see Fig-ure 1-4). This menu also displays the screens soft-ware number and version.

    SCRN PN03266796 V#.##

    until communications have been re-established(see Figure 1-5). The LEDs then return to the statedetermined by the control.

    FIGURE 1-5. RE-ESTABLISHINGCOMMUNICATIONS MESSAGE

    If either communication message remains dis-played (cannot view other menus), this is an in-dication that communications between thecontrol panel and the control board is lost. Con-tact an authorized service center for service.

    Event Messages

    When pre-set events (start or stop) are activated,Event messages are displayed showing the timeremaining until the event occurs (see Figure 1-6).

  • 5/23/2018 PCC1302 Operator Instructions

    13/34

    Status Messages

    Status messages for some events are displayed onthe optional control panel with a code number but

    are not announced with a lamp indicator. Text sta-tus messages include the event code, a short de-scription, and the time the event occurred. Symbol-ic status messages include the event code andsymbols to indicate the type of event that occurred.

    On Full Authority Electronic engines, the enginecontroller saves data after each run. During thistime, the display displays the message shown in

    Figure 1-7. The generator can still be started whilethe ECM Datasave is in progress.

    FIGURE 1-7. DATASAVE STATUS MESSAGE

    Shutdown faults can also be acknowledged whenin Auto mode by using an external customer-sup-plied remote fault reset switch. This ability must beenabled by setting the Remote Fault Reset En-

    abled trim to Enabled (disabled by default) usingInPower.

    The remote fault reset switch must be wired intoone of the four configurable inputs. The chosenconfigurable input should have its function mappedto the Fault Reset function. To reset the fault, theremote start command must be removed prior tothe remote fault reset switch being activated.

    Faults are removed from the display when they arecleared.

    NOTE: Pressing the or button also clears thefault from the front panel display.

    Faults are re-announced if they are detected againafter being acknowledged.

    Fault= WARNINGor SHUTDOWN

  • 5/23/2018 PCC1302 Operator Instructions

    14/34

    FAULT/STATUS CODES

    Table 1-2provides a list of fault and status codes,types, displayed messages/symbols, descriptions,

    and fault categories (CTG).

    Category A Fault Codes:Pertain to engine or al-ternator shutdown faults that require immediate re-pair by trained and experienced service personnel(generator set non-operational). The control pre-vents the generator set from being restarted if ashutdown fault is not corrected.

    Category B Fault Codes:Consist of faults thatcan affect generator set performance or can cause

    engine, alternator, or connected equipmentdamage. Operate the genset only when it is power-ing critical loads and cannot be shut down. Catego-ry B faults require repair by trained and experi-

    enced service personnel.

    Category C Fault Codes:Consist of faults that arerepairable by site personnel. Service will be re-quired by trained and experienced service person-nel if site personnel cannot resolve the problem.

    Category D Fault Codes: Indicates non-criticaloperational status of generator set, external faults,

    or customer fault inputs. These faults require repairby trained and experienced service personnel.

    TABLE 1-2. FAULT AND STATUS CODES

    DISPLAYED MESSAGE/SYMBOLS

    CTG CODE LAMPTEXT VERSION

    SYMBOLICVERSION

    DESCRIPTION

    C 115**Shutdown

    HIGH COOLANTTEMP 115

    Indicates that the engine coolanttemperature is above normal and hasreached the shutdown trip point.

    A 121 Shutdown SPEED SIGNALLOST

    121Indicates that no magnetic pickup pulseswere sensed for a Loss of Speed delay. Ifa magnetic pickup is disabled, this fault isnot activated.

  • 5/23/2018 PCC1302 Operator Instructions

    15/34

    TABLE 1-2. FAULT AND STATUS CODES (CONT.)

    CTG DESCRIPTION

    DISPLAYED MESSAGE/SYMBOLS

    LAMPCODECTG DESCRIPTIONSYMBOLIC

    VERSION

    TEXT VERSIONLAMPCODE

    C 359 Shutdown FAIL TO START

    359The genset has failed to start after a setnumber of crank attempts. This indicates apossible fuel system problem (enginecranks but fails to start).

    A 415** Shutdown LOW OILPRESSURE 415

    Indicates the engine oil pressure hasdropped below normal and has reachedthe shutdown trip point.

    C 441** Warning LOW BATTERY

    441Indicates battery voltage supply to the

    control is approaching a low level at whichunpredictable operation can occur.

    C 442** Warning HIGH BATTERY

    442Indicates battery voltage supply to thecontrol is approaching a high level atwhich damage to the control can occur.

    B 1123*

    Shutdown SHUTDOWNAFTER BS 1123

    A shutdown fault occurred while the BattleShort mode was enabled.

    C 1131*

    Warning BATTLE SHORTACTIVE

    1131Indicates that the control is in Battle Shortmode

    used to bypass several fault

    shutdowns for genset operation duringemergencies.

    D 1311 Configur-able

    Customer FaultInput 1 1311

    The nature of the fault is an optionalcustomer selection.

  • 5/23/2018 PCC1302 Operator Instructions

    16/34

    TABLE 1-2. FAULT AND STATUS CODES (CONT.)

    CTG DESCRIPTION

    DISPLAYED MESSAGE/SYMBOLS

    LAMPCODECTG DESCRIPTIONSYMBOLICVERSION

    TEXT VERSIONLAMPCODE

    C 1435**

    Warning LOW COOLANTTEMP

    1435

    Indicates that the engine coolanttemperature is below the adjustedsetpoint. This may indicate that thecoolant heater is not operating or is notcirculating coolant.

    C 1438 Shutdown FAIL TO CRANK

    1438The genset has failed to sense rotation fortwo start attempts. This indicates apossible fault with the control, speed

    sensing, or the starting system.

    C 1442**

    Warning WEAK BATTERY 1442Indicates that the genset battery voltage isbelow battery thresholds during cranking.

    A 1446**

    Shutdown HIGH ACVOLTAGE

    1446

    Indicates that the one or more measuredAC output voltages has exceeded thethreshold for longer than a specified timelimit. The threshold and time limits are130% of nominal for 0 seconds or 110% of

    nominal for 10 seconds.

    A 1447**

    Shutdown LOW ACVOLTAGE

    1447

    Indicates that the measured AC outputvoltage is below the threshold for longerthan a specified time limit. The thresholdand time limits are 85% of nominal for 10seconds.

  • 5/23/2018 PCC1302 Operator Instructions

    17/34

    TABLE 1-2. FAULT AND STATUS CODES (CONT.)

    CTG DESCRIPTION

    DISPLAYED MESSAGE/SYMBOLS

    LAMPCODECTG DESCRIPTIONSYMBOLICVERSION

    TEXT VERSIONLAMPCODE

    D 1944 Warning ANNUNCIATOROUTPUT CON-FIGURATIONERROR

    1944Indicates a mismatch in the configurationof one of the annunciator relay outputs.

    A 2335 Shutdown EXCITATIONFAULT 2335

    Indicates that a loss of voltage orfrequency sensing from the generator hasoccurred.

    C 2676 Shutdown ALTERNATORFREQUENCYCONFLICT

    Indicates the measured alternator line

    frequency and measured alternatorexcitation frequency do not agree.

    B 2677 Shutdown FAIL TO STOP

    2677The genset continues to run afterreceiving a stop command from thecontroller.

    A 2972**

    Shutdown FIELDOVERLOAD 2972

    Indicates that the Field Voltage has beenabove 70V for 8 seconds.

    B 2678**

    Warning CHARGERFAILURE

    2678

    Indicates the battery charging alternatorhas not reached a acceptable voltagerange within the selected time period(default = 120 seconds).

    This warning is also displayed if youralternator is a type that does not supportthe controls charging alternator logic

  • 5/23/2018 PCC1302 Operator Instructions

    18/34

    ADJUSTING DEFAULT SETTINGS

    The optional control panel can be set up to displaywith SAE or SI units of measurement.

    For more information, see the Adjust Screen menushown on page 1-26.

    SAVING YOUR CHANGES

    All adjustments made to menus are temporary untilthe SAVEbutton is pressed. If the SAVE button ispressed and the engine is running, the adjustmentsare not saved until after the engine speed is zero. If

    power is lost to the control before a SAVE is execut-ed, all temporary adjustments are lost.

    Adjustments to the following are stored in flashmemory in the optional display panel.

    Contrast

    Brightness

    Units

    Local or remote display

    Symbols or text displayed

    Access code required for mode change toAuto or Manual Run

    Auto / Manual Off switch status

    OPERATOR MENUS

    Figures 1-10and 1-11show block representationsof the following Operator menus.

    Engine Status

    Alternator Status

    Line-to-Line Voltage

    Line-to-Neutral Voltage

    Alternator Amperage

    To navigate between the Operator menus, press

    the buttons next to the and symbols in thegraphical display.

    The Operator menus can be used to select Auto orManual Run modes (see page 1-18).

    Engine Status Menu

    This menu displays the engine starting battery volt-age, engine coolant temperature, engine oil pres-

    sure, and hours of engine operation.

    Alternator Status Menu

    This menu displays genset load (in kVA), frequen-cy, and engine speed (RPM).

  • 5/23/2018 PCC1302 Operator Instructions

    19/34

    OPERATOR MENUS Text Version

    THREE PHASEONLY SINGLE

    PHASEONLY

  • 5/23/2018 PCC1302 Operator Instructions

    20/34

    OPERATOR MENUS Symbolic Version

    THREE PHASEONLY SINGLE

    PHASEONLY

  • 5/23/2018 PCC1302 Operator Instructions

    21/34

    SELECTING AUTO, MANUAL RUN, ANDOFF MODES

    Auto, Manual Run, and Off modes can be selected:

    From any of the Operator menus

    When the message Establishing commu-nication with control is displayed

    When the message Re-establishing com-munication with control is displayed

    Switching to Auto, Manual Run, or Off mode can be

    restricted to authorized personnel. If a control pan-el is set up with the mode change access code fea-ture enabled, an access code must first be enteredbefore the mode can be changed. The modechange access code feature is enabled through theDisplay Setup submenu (see page 1-14).

    The Auto or Off mode switch status is saved in non-volatile memory when it changes. When the control

    panel powers up (after sleeping or upon battery re-moval), the switch status is restored to its previoussaved state.

    Entering the Mode Change Access Code

    If th d h f t d i

    2. Press the arrow selection button to moveto the next numeric character.

    3. Press the button below the + or symbols untilthe value reads 2.

    4. Press the arrow selection button to moveto the next numeric character.

    5. Press the button below the + or symbols untilthe value reads 1.

    6. After you have completed entering the pass-word, press the arrow selection button .

    NOTE: If an incorrect password is entered,the Operator menu that was displayedbefore Auto, Manual Run, or Off modewas selected is redisplayed.

    TEXT VERSION

  • 5/23/2018 PCC1302 Operator Instructions

    22/34

    Selecting Auto Mode

    To switch to Auto mode (see Figure 1-13),

    1. Press the button on any of the Operator

    menus or the Establishing/Re-establishingcommunication with control menus.

    2. If the mode change access code feature is en-abled, the Mode Change Access Code menuis displayed. Enter the mode change accesscode as described above.

    3. A menu with alternating arrows is displayed

    above a second symbol. Press the sec-

    ond button. The Operator menu that wasdisplayed before Auto mode was selected isredisplayed.

    To disable Auto mode, press the button.

    NOTE: Manual Run mode can also be selected

    while in Auto mode.

    ALTERNATINGARROWS ARE

    DISPLAYED

    THIS MENU ISDISPLAYED ONLY IFTHE MODE CHANGE

    ACCESS CODE

    FEATURE IS ENABLED

  • 5/23/2018 PCC1302 Operator Instructions

    23/34

    Selecting Manual Run Mode

    To switch to Manual Run mode (see Figure 1-14),

    To switch to Manual Run mode,

    1. Press the button on any of the Operator me-nus or the Establishing/Re-establishing com-munication with control menus.

    2. If the mode change access code feature is en-abled, the Mode Change Access Code menu

    is displayed. Enter the mode change accesscode as described on the previous page.

    3. A menu with alternating arrows is displayed

    above a second symbol. Press the second

    button. The Operator menu that was dis-played before Manual Run mode was selectedis redisplayed.

    To disable Manual Run mode, press the button.

    NOTE:Auto mode can also be selected while inManual Run mode. Switching to Auto modemay result in the generator set shutting

    ALTERNATINGARROWS AREDISPLAYED

    THIS MENU ISDISPLAYED ONLY IFTHE MODE CHANGE

    ACCESS CODE

    FEATURE IS ENABLED

  • 5/23/2018 PCC1302 Operator Instructions

    24/34

    SERVICE MENUS

    Figure 1-15shows a block representation of themenus available from the Service Menus.

    The first Service Menu can be viewed from any ofthe Operator menus by simultaneously pressingthe and selection buttons for two seconds.The first Service Menu provides access to the fol-lowing menus:

    Setup Menus Used by Service personnel.Adjusting the Setup menus is restricted by apassword. To view the Setup menus only,

    press the VIEW button on the Setup pass-word menu.

    History / About see page1-22

    Screen Adjust see page 1-26

    To return to the Operator menu that was displayed

    prior to viewing the Service Menu, press thebutton.

    The second Service Menu can be viewed by press-ing the selection button on the first ServiceMenu. The second Service Menu provides accessto the following menus:

    Fault History see page 1-24

    The third Service Menu can be viewed by pressingthe selection button on the second ServiceMenu. The third Service Menu provides access tothe Network Status menus.

    Status Menu

    The Status menu is displayed when the (5)buttonis pressed on the second Service Menu. The Sta-tus menu shows the following:

    Voltage regulator (drive) level, in percentageof duty cycle

    Governor regulator (drive) level, in percent-age of duty cycle. This value is only dis-played if the governor is enabled.

    Network Status Menus

    The Network Status menus are displayed when the(7)button is pressed on the third Service Menu.

    Two menu are used to display the quantity of thefollowing devices that are connected to the net-work.

    Universal Annunciators

    Bar graphs

  • 5/23/2018 PCC1302 Operator Instructions

    25/34

    HISTORY / ABOUT MENUSSEE PAGE 1-22

    SETUP MENUSSEE PAGE 1-4

    SCREEN ADJUST MENUSEE PAGE 1-26

    1ST

    SERVICEMENU

  • 5/23/2018 PCC1302 Operator Instructions

    26/34

    HISTORY / ABOUT MENUS

    Figure 1-16shows a block representation of theHistory / About menu. The first History / About sub-menu is displayed when the (2)button is pressed

    on the Service Menu (see Figure 1-15).

    Press the buttons next to the and symbols inthe graphical display to navigate between the His-

    tory / About submenus. Press the button to re-turn to the Service Menu.

    History Submenu

    This submenu displays the number of enginestarts, hours of operation for the engine, and hoursof operation for the control.

    About Genset Submenus

    Two submenus display the generator set modelnumber, control number, and genset applicationfrequency rating.

    About Control Submenu

    This submenu displays the controls part number,serial number (up to 11 characters), software partnumber (up to 9 characters), and software version.

    About Display Submenu

    This submenu displays the optional control panelsoftware part number, software version, screenpart number, and screen version of the display.

  • 5/23/2018 PCC1302 Operator Instructions

    27/34

    HISTORY / ABOUT MENUS

  • 5/23/2018 PCC1302 Operator Instructions

    28/34

    FAULT HISTORY MENU

    Figure 1-18shows a block representation of theFault History menu. The first Fault menu is dis-played when the (4)button is pressed on the sec-

    ond Service Menu (see Figure 1-15). If there areany active fault submenus, an Active Fault head-ing is displayed for the most recent active fault. Allother fault submenus display a Fault Historyheading. Five of the most recent faults can beviewed. An example of how a fault code is dis-played is shown in Figure 1-17.

    Press the buttons next to the and symbols in

    the graphical display to navigate between menus.

    Press the button to return to the Service Menu.

    Information on faults is included in Table 1-2onpage 1-10.

    FAULTCODE

    FAULTDESCRIPTION

    TIME FAULTOCCURRED

    FIGURE 1-17. FAULT HISTORY MENU EXAMPLE

  • 5/23/2018 PCC1302 Operator Instructions

    29/34

    FAULT HISTORY MENU

    Fault 1

    Fault 2

    Active Fault

    OR

  • 5/23/2018 PCC1302 Operator Instructions

    30/34

    SCREEN ADJUST MENU

    Figure 1-19shows a block representation of theScreen Adjust menu. The Screen Adjust menu isdisplayed when the (3)button is pressed in the firstService Menu (see Figure 1-15).

    Adjusting Values/Parameters

    1. Press the ADJUSTselection button to selectthe first parameter or value to be changed.

    2. Press the+orselection buttons to adjust val-ues or select parameters.

    3. Press the arrow selection button to navi-gate to the next or previous adjustable value orparameter.

    4. After adjusting values/selecting parameters,press the SAVEbutton to save your settings.

    NOTE: If the Previous Menu button ispressed before pressing the SAVEbutton, the changes are not saved.

    5. Press the button to return to the Service

    Menu.

    Screen Adjust Menu

    This menu allows for adjusting the screens con-trast and brightness and for selecting the units ofmeasurement (SAE or SI) to be displayed.

    Contrast and Brightness: Press the + or selection buttons to adjust the screens con-

    trast and brightness. Changing the bright-ness setting also affects the brightness ofthe LEDs on the control panel.

    Units:Press the +or selection buttons toselect SAE (F, PSI) or SI (C, kPa) units ofmeasurement to be displayed.

    SCREEN ADJUST MENU

    No. 630-327Rev. SysPCC 1302 OEM Genset

    HMI2xxRun(Wakeup)

    Auto

    (C fi bl W k )

    J2510

    J2511

    J29 6

    J29 4

  • 5/23/2018 PCC1302 Operator Instructions

    31/34

    1-27

    Modified 7/2

    PCC1302 Baseboard

    Alternator

    Terminal Block

    PMG(optional)

    L1 L2 L3 LN

    ShuntApplications

    PMG Applications

    +

    LL600 VoltMax

    Field Winding

    20Amp

    ConfigurableInput

    #4, Fuel Level Switch(Wakeup)

    ECM Engine Connection

    Usealternatorcentertaps

    ora transformerifLL voltage>240 VAC

    J25 Display

    Battery

    +

    Fused B+

    B+Return

    Switches OEM

    connected OR

    Terminalblocks forcustomer connections

    FSOControl

    EstopB+

    Power

    J20 14

    Pilot Relay

    Starter

    Control

    EstopB+

    Power

    J20 15

    Switched B+

    (Run) Control

    EstopB+Power

    J20 3

    J20 1

    Chassis Ground

    BatteryChargingAlternator(ICRegulatorType/Kubota)

    Battery Charger

    AlternatorFlash/Failed J20

    22

    Lamp

    FailedOutput

    IC

    RegulatorPower

    BatteryChargingAlternator(NonICRegulatorType/Bosch)

    Battery ChargerAlternator

    Flash/FailedJ20 22Field

    Flash

    J20Genset

    J20 9

    J20 10

    J20 20

    J20 21

    J20 2

    J20 4

    J20 7

    J20 12

    J18 1

    J18 2

    J18 3

    10Amp

    P2

    P3

    P4

    J17 2

    J17 1

    J12 1

    J12 4

    J12

    2

    J12 5

    J12 3

    J12 6

    J22 1

    J22 2

    J22 3

    J22 4

    J12Genset Current

    J22Genset Voltage

    5A

    C T s ,

    Switched

    B+

    J20 11

    J20 18

    J20 6

    Input

    Return

    Configurable Input#3, Coolant Level

    Switch

    (Wakeup)

    J20 17

    J20 5

    Input

    Return

    OR

    OR

    KeyswitchControlJ11 21

    Pilot RelayEstopB+

    Power

    LS Out

    J11Engine

    J17AVR Control

    J18 AVR Power

    Switched

    B+

    LSOut

    LSOut

    LSOut

    DriverRating:

    4Amps

    Peak: 6

    Amps

    Relay B+ internally

    fusedat1.85AB.C.Alt. Flash

    internallyfused at1.5A

    ECM(PGI

    Compliant)

    Keyswitch

    (FSO

    optionally)

    Some ECMsintegratethe FSO withthe

    Keyswitch operation.

    Use adedicated FSO ifapplication s ECM does

    notprovide FSO

    operation.

    J1939 (+)

    J1939 ()

    J1939 (+)

    J1939 ()

    J1939(Shield)

    120

    Ohm120ohm terminated

    Only terminate shield

    ononeend

    J11 20

    J11 19

    J11 17

    UseL1/L2/N

    for1phaseapplications

    Don t connect

    N inDelta

    configuration

    HMI Fused B+ and

    Customer Fused B+

    share acommon 4.5Afuse.

    HMI FusedB+ is

    assumedto consumeno morethan 1.5A

    Partnumbers

    J11 Mate:03232161

    Sockets: 03232466

    PartnumbersJ25 Mate:03232445

    Sockets: 03232466

    PartnumbersJ20 Mate:03232446

    Sockets: 03232466

    Partnumbers

    J22Mate: 0323222603

    Partnumbers

    J12 Mate:03231932Sockets: 03231200

    Partnumbers

    J17 Mate:03232098Sockets: 03231200

    PartnumbersJ18 Mate:03232444

    Sockets: 03231200

    Partnumbers

    PCC1302: 0327161701

    Fused B+

    These signalsgotothe

    display but

    don t g o

    throughthePCC controller.

    Terminal

    BlockJ20Harness

    RemoteEstop

    PB (B)

    Basic

    Customer

    Fused B+

    These signalsgo to the

    engine but

    don t go

    throughthePCC controller.

    Terminal

    BlockJ20

    Harness

    Fused B+

    Thesesignals

    go to thegenset but

    don t go

    through thePCCcontroller.

    Terminal

    BlockJ11, J25Harness

    Basic

    Customer

    EstopB+Power

    Fused B+

    LocalEstop

    PB

    Input (Wakeuponopen)

    Return

    J25 2

    J25 6

    Remote EstopPB (B)

    A

    B

    Fused B+

    orHMI3xxDisplay

    HMI FuseB+

    B+Return

    PCCNetA(+)

    PCCNet B ()

    (ConfigurableWakeup)

    System Wakeup

    J254

    J253

    J255

    J2512

    J258

    UseShielded Twisted Pair forPCCNet

    Only terminate shield on one end

    Partnumbers

    HMI220:03006314

    HMI320:

    03006315J28 Mate:

    03232091

    J29 Mate:03232456

    Sockets: 03232466

    J29 1

    J29 2

    J29 3

    J28 1

    J28 2

    HMI 114Bargraph

    HMI Fuse B+

    B+Return

    PCCNetA (+)

    PCCNetB ()SystemWakeup

    J254

    J253J255

    J2512

    J258

    PartnumbersHMI114:

    0300????J1 &J6 Mate:

    03232011

    Sockets: 03232466

    J1 3

    J1 4J1 5

    J6 1

    J6 2

    Locate near

    mounting screw

    chassis.

    HMI211Display

    HMI Fuse B+

    B+Return

    PCC NetA (+)

    PCCNet B ()

    Manual (Wakeup)

    Auto (Config urable Wake up)J1 6

    J1 7

    System Wakeup

    J1 1

    J1 2

    J1 4

    J1 3

    J1 5

    J2510

    J2511

    J254

    J253

    J255

    J2512

    J258

    PartnumbersHMI211:

    03006014

    OR

    Local

    FIGURE 1-20. PCC 1302 WIRING (SHEEET 1 OF 4)

    No. 630-3270 Sh 1Rev. Sys: ProEM difi d 7/2006PCC 1302 OEM Genset

    HMI2xxRun (Wakeup)

    Auto

    (Configurable Wake up)

    J2510

    J2511

    J29 6

    J29 4

  • 5/23/2018 PCC1302 Operator Instructions

    32/34

    1-28

    Modified 7/2006

    LocalEstopPB

    PCC1302 Baseboard

    Alternator

    Terminal Block

    PMG(optional)

    L1 L2 L3 LN

    ShuntApplications

    PMG Applications

    +

    LL 600VoltMax

    Field Winding

    AUX 104GOVERNOR POWER STAGE

    Active OilPressureSender

    UseShielded Twisted Pair forMagPU

    OR

    20Amp

    ConfigurableInput

    #4, Fuel Level Switch(Wakeup)

    PCC 1302 OEM GensetHydromechanical Engine

    Connection

    Usealternatorcentertaps

    ora transformer

    i fLLvoltage>240 VAC

    J25 Display

    Input(Wakeup on open)

    Return

    J25 2

    J25 6

    Remote EstopPB(B)

    Battery

    +

    Fused B+

    B+Return

    Switches OEMconnected OR

    Terminalblocks forcustomer connections

    FSOControl

    EstopB+

    PowerJ20 14

    Pilot Relay

    Starter

    Control

    EstopB+

    Power

    J20 15

    Switched B+

    (Run) Control

    EstopB+Power

    J20 3

    J20 1

    Chassis Ground

    BatteryChargingAlternator(ICRegulatorType/Kubota)

    Battery Charger

    AlternatorFlash/Failed

    J2022

    Lamp

    FailedOutput

    ICRegulator

    Power

    BatteryChargingAlternator(NonICRegulatorType/Bosch)

    Battery ChargerAlternator

    Flash/FailedJ20 22Field

    Flash

    J20Genset

    J20 9

    J20 10

    J20 20

    J20 21

    J20 2

    J20 4

    J20 7

    J20 12

    J18 1

    J18 2

    J18 3

    10Amp

    P2

    P3

    P4

    J17 2

    J17 1

    J12 1

    J12 4

    J12 2

    J12 5

    J12 3

    J12 6

    J22 1

    J22 2

    J22 3

    J22 4

    J12Genset Current

    J22Genset Voltage

    5AC T s ,

    Switched

    B+

    J20 11

    J20 18

    J20 6

    Input

    Return

    Configurable Input

    #3, Coolant LevelSwitch

    (Wakeup)

    J20 17

    J20 5

    Input

    Return

    J11 1+5V

    J11 3Sense

    J11 2Return

    Passive OilPressureSender

    J11 3Sense

    J11 2Return

    Coolant

    TemperatureSensor

    (OnanType)

    J11 11Sense

    J11 12Return

    OR

    OR

    GlowPlug

    ControlJ11 7

    Pilot Relay

    Ignition

    ModuleControlJ11 7

    J11 6

    J11 6

    ORRelay B+

    Relay B+

    LS Out

    LS Out

    J11 9+

    J11 10

    J11 8Shield

    Mag

    Pickup

    J11Engine

    J11 4

    J11 5

    OR

    Governor PWM+

    GovernorPWM

    3rd Party

    FuelActuatorModule

    (20mAMax)

    J11 4

    J11 5 GovernorPWM+

    Governor PWM

    J1 2

    J1 1 J1 4 Act. LS Driver

    FuelActuator

    (6 AmpsMax)

    J1 3

    J1 5Gov PSPower

    J1

    GovPS

    A

    B

    J17AVR Control

    J18 AVRPower

    Switched

    B+

    LSOut

    LSOut

    LSOut

    Driver

    Rating:4Amps

    Peak: 6

    Amps

    Relay B+ internallyfusedat 1.85A

    OR

    Low Oil Pressure

    Switch

    J11 3

    J11 2

    Input

    Return

    Relay B+in ternally

    fusedat 1.85A

    B.C.Alt. Flash

    internally fused at

    1.5A

    UseL1/L2/Nfor1phase

    applications

    Don tconnect

    N inDeltaconfiguration

    HMI Fused B+andCustomerFused B+

    share acommon 4.5Afuse.

    HMIFusedB+isassumed to consume

    nomore than1.5A

    Partnumbers

    J25 Mate: 03232445Sockets: 03232466

    Partnumbers

    J11 Mate: 03232161Sockets: 03232466

    Partnumbers

    J20 Mate: 03232446Sockets: 03232466

    Partnumbers

    J12 Mate: 03231932Sockets: 03231200

    PartnumbersJ22Mate:0323 222603

    Partnumbers

    J17 Mate: 03232098Sockets: 03231200

    Partnumbers

    J18 Mate: 03232444

    Sockets: 03231200

    PartnumbersPCC1302:0327161701

    PartnumbersAux 104: 03271507J1Mate:0323 2216: Sockets: 03231200

    Fused B+

    These signals

    go to thedisplay but

    don tgo

    throughthe

    PCC controller.

    TerminalBlock

    J20Harness

    Remote Estop

    PB(B)

    Basic

    Customer

    Fused B+

    Fused B+

    These signals

    gototheenginebut

    don t go

    through thePCC controller.

    Terminal

    BlockJ20

    Harness

    B+ Return J20

    Harness

    Fused B+

    B+Return

    Gov PS PowerFused B+

    Fused B+

    These signals

    gotothegensetbut

    don t gothrough the

    PCC controller.

    TerminalBlock

    J11Harness

    B+Return

    J11,J25Harness

    BasicCustomer

    EstopB+ Power

    or HMI3xxDisplay

    HMI Fuse B+

    B+Return

    PCC NetA (+)

    PCC Net B ()

    (Configurable Wakeup)

    System Wakeup

    J254

    J253

    J255

    J2512

    J258

    UseShieldedTwistedPairfor PCC NetOnlyterminate shieldon one end

    Partnumbers

    HMI 220:03006314

    HMI 320:

    03006315J28 Mate:

    03232091J29 Mate:

    03232456

    Sockets: 03232466

    J29 1

    J29 2

    J29 3

    J28 1

    J28 2

    HMI 112Bargraph

    HMI FuseB+

    B+Return

    PCCNetA (+)

    PCCNetB ()SystemWakeup

    J254

    J253J255

    J2512

    J258

    Part numbers

    HMI 112:0300605002

    J1& J6 Mate:

    03232011Sockets: 03232466

    J1 3

    J1 4J1 5

    J6 1

    J6 2

    Locate near

    mounting screwchassis.

    HMI211Display

    HMI Fuse B+B+Return

    PCCNetA (+)

    PCCNetB()

    Manual(Wakeup)

    Auto (Confi gurable Wake up)J1 6

    J1 7

    System Wakeup

    J1 1

    J1 2J1 4

    J1 3

    J1 5

    J2510

    J2511

    J254

    J253

    J255

    J2512

    J258

    Part numbers

    HMI211:

    03006014

    OR

    Local

    FIGURE 1-20. PCC 1302 WIRING DIAGRAM (SHEET 2 OF 4)

    No. 630-327Rev. SysModified 7/2PCC 1302 Customer Connections:

    I npu t #1 I npu t #2Input #3 Input #4 Input #5 Input #6

    System Wakeup TB15 5

    RemoteStart TB110J1 7

    Remote

  • 5/23/2018 PCC1302 Operator Instructions

    33/34

    1-29

    Modified 7/2

    PCC1302

    Baseboard

    BatteryCharger

    Aux 101Remote I/O

    CustomerFused B+

    B+Return

    CustomerFused B+

    B+Return

    PCC Net A(+)

    PCCNetB ()

    SystemWakeup

    PCCNetA (+)

    PCCNetB()

    System Wakeup

    PCC Net Devices

    TB1 1

    TB1 2

    TB15 5

    TB1 5

    TB1 3

    TB1 1

    TB1 2

    TB15 5

    TB1 5

    TB1 3

    TB 1

    HMI2xxandHMI3xxDisplay

    CustomerFused B+

    B+Return

    PCC Net A(+)

    PCCNetB ()

    SystemWakeup

    TB1 1

    TB1 2

    TB15 5

    TB1 5

    TB1 3

    UseShieldedTwisted Pairfor PCC NetOnlyterminateshieldon one end,to

    prevent groundloops

    J1 3

    J1 4

    J1 5

    J14 1J14 2

    Discrete Input (Sense)

    Return

    Aux 101

    Relay 1Output

    J2 1

    J2 3

    Relay NO

    J2 2 Relay ComRelayNC

    Aux 101Relay 2

    Output

    J2 4

    J2 6

    Relay NO

    J2 5 Relay Com

    RelayNC

    Aux 101Relay 3

    Output

    J2 7

    J2 9

    Relay NO

    J2 8 Relay Com

    RelayNC

    Aux 101

    Relay 4Output

    J2 10

    J2 12

    Relay NO

    J2 11 Relay Com

    RelayNC

    Aux 101

    Relay 5Output

    J3 1

    J3 3

    Relay NO

    J3 2 Relay Com

    RelayNC

    Aux 101

    Relay 6

    Output

    J3 4

    J3 6

    Relay NO

    J3 5 Relay Com

    RelayNC

    Aux 101

    Relay 7Output

    J4 1

    J4 3

    Relay NO

    J4 2 Relay Com

    RelayNC

    Aux 101

    Relay8Output

    J4 4

    J4

    6

    Relay NO

    J4 5 Relay Com

    RelayNC

    J11 1

    J11 2

    AND/OR

    J11 3

    J11 4

    +/5V Analog

    Input

    Sense

    ReturnOil

    TemperatureRTD

    Sensor

    J11 5Sense

    J10 3Current source

    AND/OR

    J11 7

    J10 4

    p p

    J11 9

    J10 5

    p

    J11 11

    J10 6

    p

    J10 9Current return

    J11 6Sense return

    J10 10

    J11 8

    J10 11

    J11 10

    J10 12

    J11 12

    Exhaust Stack

    Temperature #1RTD

    Sensor

    Sense

    Current source

    Current return

    Sense return

    AmbientTemperature

    RTDSensor

    Sense

    Current source

    Current return

    Sense return

    FuelLevel

    Sensor

    RTDSensor

    Sense

    Current source

    Current return

    Sense return

    Intake Manifold

    TemperatureRTD

    Sensor

    SenseCurrent source

    Current return

    Sense return

    05VAnalog Input

    Sense

    Sense return

    038VAnalog

    InputJ11 13Sense

    J11 14Return

    AND/OR

    J11 15

    J11 16

    Input #7 Input #8

    Gnd must bewired in

    CustomerFused B+

    DiscreteInput(Sense)

    Return

    Gnd must be

    wired in

    OR

    OR

    OR

    OR

    OR

    OR

    OR

    DiscreteInput (Sense)

    ReturnGnd must be

    wiredin

    Customer

    Fused B+

    Discrete Input (Sense)

    Return

    Gnd must bewiredin

    OR

    OR

    DiscreteInput (Sense)

    ReturnGnd must be

    wiredin

    CustomerFused B+

    Discrete Input (Sense)

    Return

    Gnd must bewiredin

    OR

    OR

    Aux 102Remote I/O

    J5

    J6

    J1

    Aux 102

    Relay 9Output

    J1

    1

    J3 1

    Relay NOJ2 1 Relay Com

    RelayNC

    Aux 102Relay 10

    Output

    J1 2

    J3 2

    Relay NO

    J2 2 Relay Com

    RelayNC

    Aux 102

    Relay 11Output

    J1 3

    J3 3

    Relay NO

    J2 3 Relay Com

    RelayNC

    Aux 102

    Relay 12

    Output

    J1 4

    J3 4

    Relay NO

    J2 4 Relay Com

    RelayNC

    Aux 102

    Relay13Output

    J1 5

    J3 5

    Relay NO

    J2 5 Relay Com

    RelayNC

    Aux 102

    Relay14

    Output

    J1 6

    J3 6

    Relay NO

    J2 6 Relay Com

    RelayNC

    Aux 102

    Relay15Output

    J1 7

    J3 7

    Relay NO

    J2 7 Relay Com

    RelayNC

    Aux 102Relay16

    Output

    J1 8

    J3 8

    Relay NO

    J2 8 Relay Com

    RelayNC

    J2

    J3

    Chassis Ground

    Mounting screw

    Maximumof 2Aux101 &

    102s canbe used

    pergenset

    J11

    J10

    J4

    J3

    J2

    TB 15

    Usea local,floating(nongrounded)DCpowersupplyifB+ linehashigh

    resistance(>1 ohm)due tolong runs,toprevent brief poweroutages during

    genset starts

    PCCNet must use a daisy chain

    topology only

    HMI 113Annunciator

    CustomerFused B+

    B+Return

    PCC Net A(+)

    PCCNetB ()

    TB1 1

    TB1 2

    TB1 5

    TB1 3

    HMI 112

    Bargraph CustomerFused B+B+Return

    PCC Net A(+)

    PCCNetB ()

    SystemWakeup

    TB1 1

    TB1 2

    TB15 5

    TB1 5

    TB1 3

    J23

    J24

    TB116

    TB115

    J15

    J13

    J1

    4J61

    J62

    J4

    J4 1

    J4 2

    Input

    ReturnInput #9

    J4 3

    J4 4ReturnInput #10

    Input

    J4 5

    J4 6ReturnInput #11

    Input

    J4 7

    J4 8ReturnInput #12

    InputJ10 7

    J10 95VDCSupply#1

    (20mA max)

    +

    Return

    J10 8

    J1010

    5VDCSupply #2(20 mAmax)

    +

    Return

    J10

    Part numbersAux 101:

    03271536

    Part numbersAux 102:

    03271265

    Partnumbersw/oenclosure:

    300592901w/enclosure:

    300592902

    PartnumbersHMI 112:0300605002

    Aux 102

    Relay OutputRatings:

    2A,30VDC,

    250VAC

    Aux 101Relay Output

    Ratings:30VDC,

    250VACNO: 5A

    NC: 3A

    AND/OR

    AND/OR

    PartnumbersAux 101 mates:

    J1: 0323219204J14:0323167802

    Others: comew/ boardAux 102 mates:

    J1, J2, J3:0323167808J4: 0323167807

    Others: comew/ board

    Refer to the PCCNetSpec Sheet for

    further detailson PCCNet

    HMI211CustomerFused B+

    B+Return

    PCC NetA (+)

    PCC Net B ()

    TB1 1

    TB1 2

    TB1 5

    TB1 3

    J1 4J1 1J1 2

    J1 3J1 5

    Remote

    Part numbers

    HMI211:03006014

    J29 3

    J29 1

    J29 2

    J28 1

    J28 2

    FIGURE 1-20. PCC 1302 WIRING (SHEEET 3 OF 4)

    No. 630-3270 Sh 1Rev. Sys: ProEModified 7/2006

    PCC 1302 Customer Connections:

  • 5/23/2018 PCC1302 Operator Instructions

    34/34

    1-30

    Modified 7/2006

    PCC 1302 Baseboard

    Relay Output

    Ratings:3.5A,

    30VDC,

    250VAC

    Customer

    Output#1

    TB1 6 Relay NO

    TB1 7 Relay Com

    See Application Notessection for high level

    Estopcircuit

    TB1 Basic

    TB1 11

    TB1 10

    Input

    Return

    Remote

    Start

    (Wakeup)TB1

    12

    TB1 13ReturnCustomer

    Input #1

    Input

    TB1 14

    TB1 15ReturnCustomer

    Input #2

    Input

    TB1 5

    TB1 10

    Customer fused

    Battery Supply

    (3Amax)

    +

    Return

    Customer

    Output#2

    TB1 8 Relay NO

    TB1 9 Relay Com

    Battery

    +

    RemoteEstop

    PB(Remove jumper

    if not used)

    Input (Wakeuponopen)

    Return

    TB1 16

    TB1 15

    EstopB+Power

    A

    B

    Local EstopPB(B)

    PCC NetDevices(See Customer

    PCC Net page)

    PCCNetA (+) RS485

    PCCNetB () RS485

    TB1 1

    TB1 2

    PCC NetB ShieldTB1 3

    TB1 4Ready To

    LoadOutputLowSide Driver

    Itemsin dashed lines

    represent internal

    PCC circuitry.

    SystemWakeupTB15 5

    TB15 Modbus/PC Tool

    Modbus

    SystemWakeup:

    Groundif the PCC

    control system is to

    always stayawake.

    (+)

    ()

    RS485 (+)

    RS485 ()

    Shield

    120

    Ohm120 ohmterminated

    Only terminateshield

    onone end

    TB15 3

    TB15 4

    TB15 1

    PCC NetDevices(See Customer PCC Net page)

    PCTool HarnessPC Tool

    OR

    Partnumbers

    TB15 Mate: 0323219204

    Partnumbers

    TB 8 Mate:0323232503

    Partnumbers

    TB1 Mate: 03232434

    Part numbers

    PCTool Harness kit:05411199

    EstopB+Power

    These signals

    go to the

    customer but

    don t go

    through the

    PCC controller.

    Terminal

    BlockJ20

    Harness

    Local EstopPB

    (B)

    J25

    Harness

    FIGURE 1-20. PCC 1302 WIRING DIAGRAM (SHEET 4 OF 4)