owner’s manual ups/cp series 3000-6000.pdfŁ transients caused by switching and faults electrical...

58
Owner’s Manual

Upload: others

Post on 09-May-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

6 0

Owner's Manual

1Minuteman Continuous Power Series UPS

The following are examples of symbols used to alert the user toimportant information:

CAUTIONRISK OF ELECTRIC SHOCK

DO NOT OPEN

CAUTION TO REDUCE THE RISK OF ELECTRIC SHOCK,

DO NOT REMOVE COVER (OR BACK)

NO USER SERVICEABLE PARTS INSIDE

REFER SERVICING TO THE FACTORY

This symbol is intended to alert the user to the presence of uninsulated�dangerous voltage� within the product�s enclosure that may be of suffi-cient magnitude to constitute a risk of electric shock to persons.

This symbol is intended to alert the user to the presence of importantoperating and maintenance (servicing) instructions in the literature accom-panying the appliance.

WARNING Electrical Shock Hazard. The batteries contain HIGHVOLTAGES. To reduce the risk of electrical shock, usecaution when handling the units.

SAFETY Save these instructions. This manual containsINFORMATION important instructions that should be followed during

installation and maintenance of the UPS and batteries.

c m

cm

CONTENTS

SECTION 1. INTRODUCTION..........................................................................5Why is the Minuteman Continuous Power Series UPS One of the Best? ..............5How the Continuous Power Series Protects Your System.......................................8About the Manual....................................................................................................9

SECTION 2. PREPARATION..........................................................................10Unpacking the UPS...............................................................................................10Overview of the UPS.............................................................................................11

SECTION 3. INSTALLATION..........................................................................14Positioning the UPS..............................................................................................14Connecting the Hardwired UPS.............................................................................15Connecting the Plug and Play UPS.......................................................................24Installing the Optional Transformer........................................................................25Installing External Battery Packs...........................................................................32Installing a Customer Supplied External DC Source.............................................34Connecting Load Through Output Circuit Breaker Plate.......................................35Interface Ports.......................................................................................................36

SECTION 4. OPERATION............................................................................38Operation Mode and Configure Mode...................................................................38Operation Mode....................................................................................................38UPS Alerts.............................................................................................................40LED Indicators.......................................................................................................41Configure Mode.....................................................................................................43Using Communication Interfaces and Rear Panel Controls...................................45Using Options........................................................................................................46

SECTION 5. MAINTENANCE.........................................................................50Preventive Maintenance........................................................................................50Battery Life............................................................................................................50Battery Recharging................................................................................................50Storing the UPS.....................................................................................................50Maintenance..........................................................................................................51

SECTION 6. SPECIFICATIONS.......................................................................52Electrical Input.......................................................................................................52Electrical Output....................................................................................................52Internal Battery......................................................................................................52Physical.................................................................................................................52Model Specifications Table....................................................................................53

SECTION 7. TROUBLESHOOTING..................................................................54

SECTION 8. OBTAINING SERVICE.................................................................56

2

I N T R O D U C T I O N

Congratulations! By purchasing Minuteman's Continuous Power SeriesUninterruptible Power System (UPS), you now own superior powerprotection equipment. Your sensitive electrical equipment will be pro-tected from virtually any problem associated with AC power. The Con-tinuous Power Series UPS is designed to protect many types of electricalequipment including midsized networks, work stations, file servers, Point-of-Sale (POS) cash register systems, medical equipment, and telecom-munications equipment while providing outstanding performance andreliability.

WHY IS THE CONTINUOUS POWER SERIES UPS ONE OF THE BEST?DUAL CONVERSION ONLINE TECHNOLOGYDual conversion online technology makes the Continuous Power Seriesa true online system that delivers excellent voltage regulation and anextremely low input current distortion.

ADVANCED BATTERY MANAGEMENTThe Continuous Power Series has Minuteman's exclusive AdvancedBattery Management (ABM�) feature that doubles battery life andspeeds up recharge time to give you maximum battery reliability.

SOPHISTICATED COMMUNICATION INTERFACEThe Continuous Power Series communication interface features a relayinterface port and an RS-232 port. Both ports allow the user to monitorAC power conditions and the operational status of the UPS. The Con-tinuous Power Series is also fully compatible with Network Manager IIUPS management software.

START-ON-BATTERYThe Continuous Power Series has a start-on-battery option which allowsyou to start up your system via the internal battery in the event AC poweris not available.

TWO-PHASE FLEXIBILITYThe Continuous Power Series two-phase models have simultaneousmultiple output voltages (120/208 or 120/240) which improves utility loadbalance. This feature prevents overloading on a single line and enhancesoverall system stability.

3Minuteman Continuous Power Series UPS

Table 1-1. Continuous Power Series Standard Models

CP3000 Tower Hardwired 3.1 120v 23 x 6.8 x 16 125(58.4 x 17.2 x 40.6) (56.9)

CP3000-PP*2 Tower Plug & Play 3.1 120v 23 x 6.8 x 16 135(58.4 x 17.2 x 40.6) (61.2)

CPR3000 Rack Hardwired 3.1 120v 6.8 x 17.5 x 24 125(17.2 x 44.5 x 61) (56.9)

CPR3000-PP*3 Rack Plug & Play 3.1 120v 23 x 6.8 x 16 135(58.4 x 17.2 x 40.6) (61.2)

CP3200 Tower Hardwired 3.1 120/208 23 x 6.8 x 16 125120/240 (58.4 x 17.2 x 40.6) (56.9)

CP3200-PP*4 Tower Plug & Play 3.1 120/208 23 x 6.8 x 16 135120/240 (58.4 x 17.2 x 40.6) (61.2)

CPR3200 Rack Hardwired 3.1 120/208 23 x 6.8 x 16 125120/240 (58.4 x 17.2 x 40.6) (56.9)

CPR3200-PP*5 Rack Plug & Play 3.1 120/208 23 x 6.8 x 16 135120/240 (58.4 x 17.2 x 40.6) (61.2)

CP6000 Tower Hardwired 6 120/208 23 x 6.8 x 24 180120/240 (58.4 x 17.2 x 60.9) (86)

CP6000-PP* Tower Plug and Play 6 120/208 23 x 6.8 x 24 190120/240 (58.4 x 17.2 x 60.9) (90.3)

*1 All models are 50 & 60 Hz capable with auto-sensing.Standard plug and play model includes 4 each 5-15R receptacles and a L5-30P with inputline cord.

*2 Standard plug and play models includes 4 each 5-15R receptacles and a L5-30P with input linecord.

*3 Standard plug and play models include 4 each 5-15R, one L6-30R receptacles and a L14-30P withinput line cord.

*4 Standard plug and play model includes 4 each 5-15R, and one L6-30R receptacle and a L14-30Pwith input line cord.

*5 Standard plug and play models include 8 each 5-15R and one L6-30R receptacles and an L14-30Pwith input line cord.

Section 1 Introduction

6

VACVAC

VACVAC

VACVAC

VACVAC

VACVAC

VACVAC

1MODELS* STYLE

INPUT /OUTPUT

CONNECTION

DIMENSIONSIN / CM

(L X W X H)VOLTVAC

KVARATING

WEIGHT(LB/KG)

or

or

or

or

or

or

4

ON

24 in(61.0 cm)

6.8 in(17.2 cm)

16.0 in(40.6 cm)

2.1 & 3.1 KVA Rack-Mount

19.0 in(48.2 cm)

Including mounting wings

Figure 1-1. The Continuous Power Series Tower and Rack-Mount Models

ON

24.0 in(61.0 cm)

6.8 in(17.2 cm)

16.0 in(40.6 cm)

24.0 in(61.0 cm)

6.8 in(17.2 cm)

24.0 in(61.0 cm)

ON

5.0 & 6.0 KVATower

2.1 & 3.1 KVATower

5Minuteman Continuous Power Series UPS

HOW THE CONTINUOUS POWER SERIES PROTECTS YOUR SYSTEM

The Continuous Power Series UPS has two basic functions:

� Prevent AC line interruptions from disrupting your load (computernetwork, workstations, etc.)

� Condition poor quality AC power before it disrupts your load

AC power disturbances come in many forms, from full blackouts to radiotransmissions on a factory floor. The Continuous Power Series is designed torespond to these power problems before they affect the operation of yoursensitive electrical equipment. Various types of AC power disturbances in-clude:

� No voltage (blackout)

� Low voltage (brownout)

� High voltage

� Slow voltage fluctuation (voltage sag)

� Frequency variations

� Common mode noise

� Normal mode noise

� Transients caused by switching and faults

Electrical disturbances can damage software, hardware, and cause equipmentto operate erratically. The Continuous Power Series protects equipment bymaintaining a constant output voltage and by conditioning poor quality ACpower before it reaches sensitive electric equipment. Because the ContinuousPower Series is a true online UPS, it also provides instantaneous backuppower during a power failure with no interruption to your load(s). The blockdiagram in Figure 1-2 illustrates how the Continuous Power Series UPS isconnected to AC power and loads.

• Hard wire• Line cord

plug (optional)

Additional battery

INPUT AC/DC DC/AC

AUTO TRANSFER

SWITCH OUTPUT

• Redundancy• Auto retransfer

Front Panel

Utility Source

• Filter• Back feed protection

• Rectification• Amplification• Input current wave shaping• Input PF

correction• ABM

• Inverter• Output Voltage wave shaping

• Synchronizing

STD 5-15R +Hard wire

Receptacles (optional)MBS (optional)

Start-on-battery (optional)

RS-232 serial comm. port

Modem comm. port (optional)

Relay contacts

Remote emergency power OFF

X

X

• Input Voltage level• Battery level• Load level

• Alarms• Audio alarm silence• ON/OFF

Section 1 Introduction

Function Block Diagram

6

OPTIONSThe Minuteman Continuous Power Series is an option-rich UPS. Options arelisted below.

� Second RS-232 communication port for a modem board

� Start-on-battery

� Manual bypass switch

� Remote power warning interface kits

� External battery packs

� Optional output receptacles (see Appendix A for receptacle options)

� Remote distribution box

� Power management software

� Input transformer

ABOUT THE MANUAL

This manual contains information you need to install and operate the Continu-ous Power Series UPS. The information is intended for system administratorsor others with similar expertise in electronics. The field wiring instructions insection 3, Installation, are intended for qualified electricians and technicians.

SCOPEThe manual explains all the necessary information to unpack, install, andoperate the Continuous Power Series UPS. It also provides information aboutconfiguring, maintaining, and troubleshooting. Refer questions outside thescope of this manual to your Minuteman dealer or Para Systems TechnicalSupport Department.

QUESTIONS?Minuteman is committed to excellence in dependability and customer satisfac-tion. If you have any questions or problems, please contact the TechnicalSupport Department at: 1-800-238-7272 or 214-446-7363 for more informa-tion.

7Minuteman Continuous Power Series UPS

P R E P A R A T I O N

The Preparation section is designed to familiarize you with your UPS. The firstpart explains unpacking the UPS, inspecting the unit, and safety precautions.The remaining sections describe front and rear panels and user controls. Studythis section to become familiar with your UPS before installing the unit.

UNPACKING THE UPSUnpack your UPS carefully to avoid damage. The following steps explain howto remove the UPS from its pallet.

1. Cut the strap holding the UPS box to the pallet.

2. Remove the cardboard box and packing material surrounding the UPS.

3. Using an appropriate number of people, lift the UPS off the pallet andset it down on its castors (3.1 KVA models come with small rubberpads. Attach the rubber pads to the underside of the UPS before settingthe unit on the floor).

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

The UPS weighs more than 125 pounds (56.7 kg). It is manda-tory that the necessary precautions be taken to lift, move,set, and position the UPS.

INSPECTING EQUIPMENTCheck your UPS for external damage. If any damage occurred during ship-ment, keep the shipping cartons and packing materials so the carrier or yourDeltec dealer can inspect them. The following instructions explain how to file adamage claim. If you discover damage after acceptance, file a claim for con-cealed damage.

To file a claim for shipping damage or concealed damage:

� File with the carrier within 15 days of receipt of the equipment

� Send a copy of the damage claim within 15 days to:

Para Systems, Inc.1455 LeMay DriveCarrollton, Texas 75007Attn: Customer Service Department

WARNING!

8

CHECKING PACKAGE CONTENTSThe following items should be included in your Continuous Power Seriespackage:

� 1 UPS unit

� 1 user�s manual

� 1 stabilizing bracket (6.0 KVA units only)

� Warranty Registration Card

� Platinum Protection Policy

If your UPS package does not contain these items contact your Minutemandealer. Optional equipment such as external battery packs are shipped inseparate containers. Contact your Minuteman dealer if the optional items youordered are not included in the shipment.

PRECAUTIONSPlease read all instructions before operating the equipment and save thismanual for future reference.

SAVE THESE INSTRUCTIONS. This manual contains importantinstructions that should be followed during installation andmaintenance of the UPS and batteries.

Electric Shock Hazard. The batteries contain high voltages.These voltages can damage equipment and injure or kill per-sonnel.

OVERVIEW OF THE UPSThe Minuteman Continuous Power Series has 10 standard models with powerratings from 3.1 to 6.0 KVA. The front panel LED indicators and control but-tons for tower and rack-mount models perform the same functions and indicatethe same information. The rear panels of each model vary depending onoptions. Figure 2-1 shows the standard rear panels for hardwired tower mod-els. Figure 2-2 shows the rear panel of the rack-mount hardwired model. Allmodels are also available with a plug and play option. Study these illustrationsto become familiar with your unit. The rear panels for plug and play units areshown with the plug and play instructions in section 3, Installation.

Section 2 Preparation

WARNING!

SAFETY INFORMASAFETY INFORMASAFETY INFORMASAFETY INFORMASAFETY INFORMATIONTIONTIONTIONTION

9Minuteman Continuous Power Series UPS

StandardRS-232 Port

RelayInterface

Port

Circuit Breakers

Ext. BatteryConnector

Terminal Blocks(located behind

rear panel plates) Rear Panel Plates

Conduit Hole

Conduit Hole

5-15RStandard Receptacles

REPO Port

Optional Start-On-Battery Switch

Manual BypassSwitch (optional)

Optional SecondRS-232

5-15RStandardReceptacles

CircuitBreaker

5.0 & 6.0 KVAModels

2.1 & 3.1 KVAModels

Figure 2-1. The Rear Panels of Tower Models

Optional2nd RS-232

StandardRS-232 Port

Relay Interface

Port

ConduitHole

Ext. Battery Connector

Terminal Blocks (behind rear panel plates)

Standard Receptacles

REPO Port

Optional Start-On- Battery Switch

CircuitBreaker

2.1 & 3.1 KVA Models

Figure 2-2. The Rear Panel of the Rack-Mount Model

1 0

Section 2 Preparation

FRONT PANEL CONTROL BUTTONSThe front panels of all models have the same control buttons. The controlbuttons allow you to operate the UPS and configure the unit�s parameters.Using the control buttons is explained in section 4, Operation.

FRONT PANEL LED INDICATORSThe front panel LED indicators (small colored lights) on all models indicatehow the UPS is functioning. On tower models the LEDs are placed verticallyon the front panel. On rack-mount models the LEDs are placed horizontally.There are LED indicators for AC input, battery charge, load, battery servicerequirement, and bypass mode. LEDs also indicate parameters when the UPSis in configure mode.

REAR PANELSThe rear panels of all models come standard with an RS-232 port and a relayinterface port, and a remote emergency power off (REPO) port. The RS-232port and cable are used to connect the UPS to a host computer and arecompatible with Minuteman Network Manager II software. The relay interfaceport supports AC line failure alarm, impending low battery alarm, summaryalarm, load-on-bypass alarm, and other dry-contact type devices. The REPOport supports standard REPO operation. The rear panel also includes standard5-15R receptacles, circuit breakers, and a battery pack connector for theoptional external battery pack.

1 1Minuteman Continuous Power Series UPS

I N S T A L L A T I O N

The Installation section explains positioning the UPS and connecting the ACinput and loads for both hardwired models and plug and play models. Thesection then explains how to connect the input transformers and the optionalexternal battery packs (if included). Installing the communication ports andother options are explained at the end of the section.

POSITIONING THE UPSWhen locating tower and rack-mount models consider the following guidelines:

TOWER� Avoid temperature and humidity extremes. To maximize the lifetime of

the batteries, an ambient temperature of 59°F to 77°F (15°C to 25°C) isrecommended.

� Provide shelter from the elements (especially moisture).

� make sure ventilation and space requirements are met. There shouldbe two inches (5 cm) of clearance at both sides and on top of the UPS.Four inches (10 cm) of clearance is needed at the rear of the UPS forventilation.

� Maintain clearance at the front of the UPS for user operations.

� Install the external battery pack next to the UPS.

RACK-MOUNT� The rack-mount UPS fits into a standard equipment rack (mounting

hardware is not provided).

� To maximize the life of the UPS internal batteries, avoid temperatureand humidity extremes.

� The ambient temperature should be kept around 59°F to 77°F(15°C to 25°C).

ATTACHING THE STABILIZING BRACKET6.0 KVA units come with a stabilizing bracket used to secure the unit once it isplaced. Follow the instructions below to attach the stabilizing bracket.

1. Remove the bottom two screws of the bottom rear panel plate.

2. Place the stabilizing bracket over the bottom of the plate, as shown inFigure 3-1, and attach it using the screws removed from the plate.

3

1 2

Figure 3-1. Attaching the Stabilizing Bracket to the UPS

CONNECTING THE HARDWIRED UPSHardwired units have input and output terminal blocks that connect directly tothe AC input source and load(s). The terminal blocks are located on the rearpanel, behind the rear panel plates as shown in Figure 3-2 and 3-3. Thissection explains how to select the wiring, locate the terminal blocks, andconnect your loads and AC input.

Please note that the first boldfaced sentence of each step explains the stepbriefly. The remaining text explains the step in greater detail.

Also note the following Pre-installation Considerations before beginning instal-lation procedures.

PRE-INSTALLATION CONSIDERATIONS

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

ELECTRICAL SHOCK HAZARD. The hardwired models must beinstalled by a qualified electrician or technician, or some otherqualified personnel. The UPS and batteries may contain HIGHVOLTAGES. These high voltages can injure or kill personneland damage equipment.

N ON ON ON ON O T ET ET ET ET E1. The UPS batteries are sealed, lead-acid, and mainte-

nance-free. These batteries are designed to give theirlongest service when used in an ambient temperatureof 77°F (25 °C).

2. Operate the UPS in a protected environment within atemperature range of 23°F to 104°F (0°C to 40°C) and arelative humidity of 0-95%, without condensation.

Section 3 Installation

WARNING

NOTE

1 3Minuteman Continuous Power Series UPS

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

The UPS weighs more than 125 pounds (56.7 kg). It is manda-tory that the necessary precautions be taken to lift, move,set, and position the UPS.

N ON ON ON ON O T ET ET ET ET E

Current limiting and mechanical disconnect devices, sup-plied by the customer, between the UPS and the input sourcemust be installed prior to operating a hardwired UPS. It is rec-ommended that current limiting and mechanical disconnectdevices also be installed between the UPS and the load.Follow the National Electric Code where applicable duringinstallation.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

To reduce the risk of fire or electric shock, install in a tem-perature and humidity controlled indoor area free of con-ductive contaminants.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

Do the following BEFORE CONNECTING ANY WIRING:

� TURN OFF the UPS by pushing the ON/OFF and OFF but-tons at the same time.

� TURN OFF all input power (AC and DC)

� TURN OFF the critical load (Any transformers or motors infront of the load are considered part of the load

� VERIFY WITH A METER that the power is removed

Conduit Hole

Terminal Blocks (behind rear panel plates)

Rack-Mount

Figure 3-2. Rear Panel of the Rack-Mount Models

WARNING!

NOTE

WARNING!

WARNING!

1 4

Terminal Blocks(located behind

rear panel plates) Rear Panel Plates

Conduit Hole

5.0 & 6.0 KVA Tower 2.1 & 3.1 KVA Tower

ConduitHole

Figure 3-3. Rear Panels for Standard Hardwired Models

1. If you are installing a transformer, it must be connected to ACinput before installing the UPS. See Installing the Transformer laterin this section for step-by-step instructions. If you are not installing a trans-former got to step 2.

2. Select the input and output wiring. The UPS has compression-type terminal blocks for input and output connections. The UPS uses#10 AWG wire torqued to 35 in-lb. Use the National Electrical CodeArticle 310, Table 310 (60° column only) to determine the appropriatewiring. Use only copper conductors and follow all pertinent local electri-cal codes when selecting wiring.

3. Provide an AC input line that meets the UPS electrical inputrequirements. Verify that the capacity of the UPS and the capacity ofthe input circuit are the same (the rating of the external circuit breakersmust match the AC input rating). Refer to Table 3-1 for the recom-mended circuit breaker size.

c SPECIAL CAUTION: THE CP3200 & CP6000, 2 PHASE UNITS, REQUIRE A 4 WIRE INPUT.THIS UNIT WILL BE DAMAGED, AND WILL NO LONGER FUNCTION IF THE INPUT ISINCORRECTLY WIRED. DO NOT ATTEMPT TO OPERATE UNIT UNLESS INSTALLEDCORRECTLY.

CONSULT WITH A QUALIFIED ELECTRICIAN IF THIS UNIT IS A PLUG AND PLAY (PP) UNITAND WALL OUTLET DOES NOT MATCH FOR A DIRECT CONNECTION.THE FOLLOWING MODELS ARE 2 PHASE UNITS:1. CP3200 2. CPR3200 3. CP3200-PP4. CPR3200-PP 5. CP6000 6. CP6000-PP

STEPS FOR FIELD WIRING

Section 3 Installation

1 5Minuteman Continuous Power Series UPS

4. Remove the rear panel plates at the back of the UPS as shownin Figure 3-4. The two sets of terminal blocks consist of seven(7) terminals each. Six (6) of the terminals on the AC input andbattery input block are used for connections. The remainingterminal is not connected. Follow the terminal block labelswhen connecting wires.

ExposedTerminal Blocks

RemovedRear Panel

Plates

Removed Plug Cap

Knockout from second conduit hole

Figure 3-4. Removing the Rear Panel Plates and Plug Cap

5. Remove plug cap and knockout and attach conduit. Removethe plastic plug cap from the conduit hole and attach flexiblewiring conduit to the conduit hole. Create a second conduithole by punching out a knockout from one of the rear panelplates, as shown in Figure 3-4, and attach a second conduit.

6. Route the input and output wiring. Route the wiring for the ACinput and loads through separate conduit to the terminalblocks.

C AC AC AC AC A U T I O NU T I O NU T I O NU T I O NU T I O N

Avoid damage. Do not remove, cut, or modify any of thewiring connected to the terminal blocks by the factory. Forinput wiring, connect only ONE WIRE to each terminal. Foroutput wiring, more than one wire may be connected to aterminal. The UPS or your load may be damaged if any ofthe factory-installed wiring is cut, broken, removed, or modi-fied in any way.

N ON ON ON ON O T ET ET ET ET E

The National Electrical Code requires that a current limitingdevice (provided by the customer) must be installed be-tween the input line to the UPS and between the UPS andthe output line when hard wired.

7. Connect a current limiting device between the AC input andthe UPS. Refer to Table 3-1 for the recommended circuitbreaker size for each model.

CAUTION!

NOTE

1 6

Table 3-1. Recommended AC Circuit Breaker Size

Recommended ACModel Circuit

Size (AMPS) Breaker

CP3000 20 A - 1 Pole

CP3000-PP 20 A - 1 Pole

CPR3000 30 A - 1 Pole

CPR3000-PP 30 A - 1 Pole

CP3200 15 A - 2 Pole

CP3200-PP 15 A - 2 Pole

CPR3200 30 A - 2 Pole

CPR3200-PP 30 A - 2 Pole

CP6000 30 A - 2 Pole

CP6000-PP 30 A - 2 Pole

8. Connect and secure the ground wires. Refer to Figure 3-5 forgrounding stud locations. There are two grounding stud loca-tions for each unit. Connect the AC input ground wire to theprimary grounding stud and the load ground wires to the sec-ondary grounding stud.

5.0 and 6.0 KVATower

GroundingStuds

2.1 and 3.1 KVATower

2.1 and 3.1 KVA Rack-Mount

GroundingStuds

Figure 3-5. Grounding Stud Locations for Tower and Rack-Mount Models

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

ELECTRICAL SHOCK HAZARD. The UPS may contain HIGH VOLT-AGES. These high voltages can damage equipment and in-jure or kill personnel.

N ON ON ON ON O T ET ET ET ET E

This symbol indicates primary equipment groundingpoint. This symbol indicates secondary equipmentgrounding point.

WARNING!

NOTE

6.0 KVA 3.1 KVA 3.1 KVA Tower Tower Rack-Mount

Section 3 Installation

1 7Minuteman Continuous Power Series UPS

9. Connect the AC input and output wiring according to the UPSInput and Output Wiring Tables and Figures. Table 3-2 andFigure 3-6 explain connecting single-phase units. Table 3-3 andFigure 3-7 explain connecting two-phase units. Check the UPS identifi-cation label to verify that the power rating for your load matches thepower rating of the UPS. Refer to the terminal block illustrations inFigure 3-9 and Figure 3-10 for the correct terminal locations. The blockdiagram in Figure 3-8 gives an overview of UPS connections.

N ON ON ON ON O T ET ET ET ET E

Input Line 2 (IL2) and Output Line 2 (OL2) on the terminalblocks are used for two-phase units only. These terminals arenot connected on single-phase units.

N ON ON ON ON O T ET ET ET ET E

If your UPS has an optional load circuit breaker plate, go toInstalling Output Circuit Breaker later in this section to con-nect loads through the output circuit breaker.

C AC AC AC AC A U T I O NU T I O NU T I O NU T I O NU T I O N

Utility neutral must be connected to the neutral terminal (IL3)on all hardwired units. Failure to connect the neutral candamage the unit.

Table 3-2. UPS Input and Output Wiring Chart for Single-Phase Models

AC Input to UPS Input (single-phase)

Connect this Wire To this Terminal in the UPS

Utility GROUND Grounding Stud

Utility Neutral IL3 (Neutral)

Utility Line 1 (hot) IL1 (Line 1)

Load to UPS Output (single-phase)

Connect this Wire To this Terminal in the UPS

Load Ground Grounding Stud

Load Neutral OL3 (Neutral)

Load Line 1 (hot) OL1 (Line 1)

SPECIAL CAUTION: THE CP3200 & CP6000, 2 PHASE UNITS, REQUIRE A 4 WIRE INPUT. THISUNIT WILL BE DAMAGED, AND WILL NO LONGER FUNCTION IF THE INPUT IS INCORRECTLYWIRED. DO NOT ATTEMPT TO OPERATE UNIT UNLESS INSTALLED CORRECTLY.

CONSULT WITH A QUALIFIED ELECTRICIAN IF THIS UNIT IS A PLUG AND PLAY (PP) UNIT ANDWALL OUTLET DOES NOT MATCH FOR A DIRECT CONNECTION.THE FOLLOWING MODELS ARE 2 PHASE UNITS:

1.CP3200 2.CPR3200 3.CP3200-PP

4.CPR3200-PP 5.CP6000 6.CP6000-PP

NOTE

NOTE

CAUTION!

1 8

UPS

Loads

Ground

Neutral

Line 1

Ground

Neutral

Line 1IL1

IL3

OL1

OL3

Utility

HotCB

1

1 Neutral must be connected. Failure to do so can damage the unit.

Figure 3-6. AC Input and Output Wiring Diagram for Single-Phase Models

Table 3-3. UPS Input and Output Wiring Chart for Two-Phase Models

AC Input to UPS Input (two-phase)

Connect This Wire To This Terminal in the UPS

Utility GROUND Grounding Stud

Utility Neutral IL3 (Neutral)

Utility Line 1 (hot) IL1 (Line 1)

Utility Line 2 (hot) IL2 (Line 2)

Load to UPS Output (two-phase)

Connect This Wire To This Terminal in the UPS

Load Ground Grounding Stud

Load Neutral OL3 (Neutral)

Load Line 1 (hot) OL1 (Line 1)

Load Line 2 (hot) OL2 (Line 2)

UPS

LoadsIL1

IL3

IL2 0L2

OL1

OL3

Utility

Hot

Ground

Neutral

Line 1

Line 2

Ground

Neutral

Line 1

Line 2

CB1

1 Neutral must be connected. Failure to do so can damage the unit.

Hot

Figure 3-7. AC Input and Output Wiring Diagram for Two-Phase Models

Section 3 Installation

1 9Minuteman Continuous Power Series UPS

Serial Comm. Port (Std.)

Dry Contacts (Std.)

REPO (Std.)

Modem Port (Option)

Start On Battery (Option)

Load

Di

strib

utio

n

3

AC Power Source

External DC PowerSource

HotHot

Neutral Ground

Line 1

Line 2

Neutral

Ground

Positive Negative

Neutral

CB-1

CB-2 (30A)

UPS (Field-Wired Models)

Line 1

Line 2

Neutral

Ground

NOTES:

All switchgear and connections outside of the UPS must be supplied by the customer. The National Electrical Code requires that an overcurrent and a disconnect device (provided by the customer) must be installed between the UPS and the AC input.

The National Electrical Code requires that a distribution system which contains an overcurrent and a voltage disconnect device (provided by the customer) must be installed between the UPS and the external DC source.

See Interface Ports later in this section for details about the User Interface Connectors.

The National Electrical Code requires that an overcurrent and a disconnect device (provided by the customer) must be installed between the UPS and the load.

Use for two-phase models only. Terminal is not connected on one-phase models.

2

1

2

3

4

4

AC INPUT

BATTERY INPUT

Ground

(+) (–)N

JL1JL2

OL1

OL2

OL3(N)

J2

J3

JA

JB

JC

J3O

J4

IL1

IL2

IL3(N)

Optional

Recep.

Plates

5-15R Duplex

TB1

1

5

55

Figure 3-8. UPS Wiring Diagram

2 0

Used only for two-phase units, dead on single-phase units.

Used only for two-phase units, dead on single-phase units.

Figure 3-9. Terminal Blocks for 3.1 KVA Units

Figure 3-10. Terminal Blocks for the 3.1 & 6.0 KVA Two-Phase Units

Section 3 Installation

2 1Minuteman Continuous Power Series UPS

10. Replace the rear panel plates and secure with the screws.Make sure the conduit is seated properly.

11. If you are not connecting external battery packs or an exter-nal DC source, installation is now complete. Go to section 4,Operation, for instructions about operating the UPS. To connect exter-nal battery packs see the Connecting the External Battery Packsinstructions later in this section. To connect external DC sources seeConnecting External DC Source later in this section.

CONNECTING THE PLUG AND PLAY UPSPlug and play power connections allow you to plug your UPS into an AC walloutlet and your loads into the output receptacles at the rear panel of the UPS.The steps below explain how. Figure 3-11 and 3-12 show the rear panels of theplug and play units.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

To reduce the risk of fire or electric shock install in a tempera-ture and humidity controlled indoor area free of conductivecontaminants.

OptionalReceptacles

AC Line Cord

5 -15 StandardReceptacles

Ext. BatteryConnector

5.0 & 6.0 KVA Models 2.1 & 3.1 KVA Models

Figure 3-11. Rear Panel of Tower Models With Plug and Play Option

SPECIAL CAUTION: THE CP3200 & CP6000, 2 PHASE UNITS, REQUIRE A 4 WIREINPUT. THIS UNIT WILL BE DAMAGED, AND WILL NO LONGER FUNCTION IF THEINPUT IS INCORRECTLY WIRED. DO NOT ATTEMPT TO OPERATE UNIT UNLESSINSTALLED CORRECTLY.

CONSULT WITH A QUALIFIED ELECTRICIAN IF THIS UNIT IS A PLUG AND PLAY(PP) UNIT AND WALL OUTLET DOES NOT MATCH FOR A DIRECT CONNECTION.THE FOLLOWING MODELS ARE 2 PHASE UNITS:1. CP3200 2. CPR3200 3. CP3200-PP4. CPR3200-PP 5. CP6000 6. CP6000-PP

6.0 KVA Models 3.1 KVA Models

WARNING!

2 2

Section 3 Installation

Optional Receptacles

AC Line Cord

Standard 5-15Receptacles

Circuit Breaker

Figure 3-12. Rear Panel of Rack-Mount Models With Plug and Play Option

STEPS TO INSTALL PLUG AND PLAY POWER CONNECTIONS1. Plug in the optional transformer first. If you are not installing a transformer

go to step 2. If you are installing a transformer, it must be plugged into anAC outlet before installing the UPS. See Installing a Plug and Play Trans-former later in this section for step-by-step instructions.

2. Plug the UPS line cord into an AC outlet.

3. Plug your loads into the UPS using the receptacles at the rear panel.

N ON ON ON ON O T ET ET ET ET E

DO NOT plug laser printers into the UPS.

4. If you are not connecting external battery packs or an external DCsource, installation is now complete. Go to section 4, Operation, forinstructions about how to operate the UPS. To connect external batter-ies see the Installing the External Battery Packs instructions later in thissection. To connect external DC sources, see Connecting External DCSource later in this section.

INSTALLING THE OPTIONAL TRANSFORMER

The optional transformer has either hardwired or plug and play connectionsdepending on the model you have. Hardwired models have compression typeterminal blocks that connect directly to the AC input and loads. Plug and playmodels have a line cord that connects to a wall outlet and receptacles to plugloads into the UPS.

CONNECTING HARDWIRED TRANSFORMERThis set of instructions explains connecting the hardwired transformer andUPS. The instructions also explain how to install the transformer if the UPSis already connected. The first boldfaced sentence of each step explainsthe step briefly. The remaining text describes the step in greater detail.

NOTE

2 3Minuteman Continuous Power Series UPS

Please note the following Pre-installation Considerations before installingthe transformer and UPS.

PRE-INSTALLATION CONSIDERATIONS

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

ELECTRICAL SHOCK HAZARD. The hardwired models must beinstalled by a qualified electrician or technician, or some otherqualified personnel. The UPS and batteries may contain HIGHVOLTAGES. These high voltages can injure or kill personnel anddamage equipment.

N ON ON ON ON O T ET ET ET ET E1. The UPS batteries are sealed and maintenance-free.

These batteries are designed to give their longest ser-vice when used in an ambient temperature of 77°F (25°C).

2. Operate the UPS and transformer in a protected envi-ronment within a temperature range of 23°F to 104°F(0°C to 40°C) and a relative humidity of 0-95%, with-out condensation.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

The UPS and transformer each weigh more than 125 pounds(56.7 kg). It is mandatory that the necessary precautions betaken to lift, move, set, and position the UPS.

N ON ON ON ON O T ET ET ET ET E

Current limiting and mechanical disconnect devices betweenthe transformer and the input source must be installed prior tooperating a hardwired UPS and transformer. It is recommendedthat current limiting and mechanical disconnect devices alsobe installed between the UPS and the load. Follow the Na-tional Electric Code where applicable during installation.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

Do the following BEFORE CONNECTING or DISCONNECTINGANY WIRING:

� TURN OFF the UPS by pressing the ON/OFF and OFF but-tons at the same time.

� TURN OFF all input power (AC and DC).

� TURN OFF the critical load (Any transformers or motors infront of the load are considered part of the load.

� VERIFY WITH A METER that the power is removed.

WARNING!

NOTE

WARNING!

NOTE

WARNING!

2 4

STEPS FOR INSTALLING THE TRANSFORMER AND UPS1. Select the input and output wiring for the UPS and transformer. If the

UPS is already installed, go to step 3. The transformer and UPS use#10 AWG size wire torqued to 35 in-lb. Use only copper conductorsand follow all pertinent local electrical codes.

2. Provide an AC input line that meets both the UPS�s and transformer�selectrical requirements. Verify that the operation of the transformer andUPS does not exceed the rated capacity of the circuit (the rating of theexternal circuit breakers must match the AC input rating).

3. Remove the rear panel plates from the transformer and the UPS toexpose the terminal blocks.

4. If the UPS is already installed, disconnect the AC input from the UPSterminal blocks according to Table 3-4, UPS Disconnect Chart. If theUPS is not installed, go to step 6.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

ELECTRICAL SHOCK HAZARD. The hardwired transformers mustbe installed by a qualified electrician or technician, or someother qualified personnel. The UPS and batteries may containHIGH VOLTAGES. These high voltages can injure or kill personneland damage equipment.

Table 3-4. UPS Disconnect Chart

Disconnecting AC Input from the UPS

Disconnect This Wire From This Terminal on the UPS

Utility GROUND Grounding Stud

Utility Neutral IL3 (Neutral)

Utility Line 1 (hot) IL1 (Line 1)

Utility Line 2 (hot) two-phase only IL2 (Line 2) two-phase only

5. Remove the AC input wiring from the UPS conduit.

6. Remove the two knockouts from the rear panel plates of the transformerand attach flexible conduit to each hole.

7. Route the AC input and output wiring through each conduit to theterminal blocks of the transformer.

C AC AC AC AC A U T I O NU T I O NU T I O NU T I O NU T I O N

Avoid damage. Do not remove, cut, or modify any of thewiring connected to the terminal blocks by the factory. Forinput wiring, connect only ONE WIRE to each terminal. Foroutput wiring, more than one wire may be connected to aterminal. The UPS or your load may be damaged if any ofthe factory-installed wiring is cut, broken, removed, or modi-fied in any way.

Section 3 Installation

WARNING!

CAUTION!

2 5Minuteman Continuous Power Series UPS

N ON ON ON ON O T ET ET ET ET E

The National Electrical Code requires that a current limitingdevice (provided by the customer) must be installed be-tween the input line to the UPS when hardwired.

8. Connect a current limiting device between the AC input and the trans-former.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

ELECTRIC SHOCK HAZARD. A battery can present a risk ofelectric shock and high short circuit. BE CAREFUL when mak-ing connections to terminals. HIGH VOLTAGES may be presentwhich can injure or kill personnel and damage equipment.

N ON ON ON ON O T ET ET ET ET E

Attach the AC input and output grounds to the transformerbefore attaching any other wires.

9. Connect the AC input and output wiring to the transformer terminalblock according to the Transformer Wiring Chart, Table 3-5. The wiringdiagram in Figure 3-13 illustrates the wire connections. Figure 3-14shows the terminal block and label.

C AC AC AC AC A U T I O NU T I O NU T I O NU T I O NU T I O N

Utility neutral must be connected to the neutral terminal (IL3)on all hardwired units. Failure to connect the neutral candamage the unit.

Table 3-5. Transformer Wiring Chart

AC Input to Transformer

Connect This Wire To This Terminal in the Transformer

Utility GROUND Grounding Stud

Utility Neutral IL3 (Neutral)

Utility Line 1 (hot) IL1 (Line 1)

Utility Line 2 (hot) two-phase only IL2 (Line 2) two-phase only

Output to Transformer

Connect This Wire To This Terminal on the Transformer

Output Ground Grounding Stud

Output (Neutral) OL3 (Neutral)

Output Line 1 (hot) OL1 (Line 1)

Output Line 2 (hot) two-phase only OL2 (Line 2) two-phase only

c

NOTE

WARNING!

NOTE

CAUTION!

2 6

Utility

Transformer

Ground

Neutral

Line 1

Line 2IL1

IL3

IL2*

OL1

OL3

OL2*Hot

HotCB

Ground

Neutral

Line 1

Line 2

Output wiring

1 Neutral must be connected. Failure to do so can damage the unit.

Two-phase models only.

1 1

2 2

2

Figure 3-13. AC Input Transformer Wiring Diagram

Used only for two-phase units,

dead on single-phase units

Figure 3-14. Transformer Terminal Block

10. Remove the UPS plug cap and knockout and attach conduit to eachhole. Remove the plug cap from the conduit hole and a knockout from arear panel plate of the UPS. Attach conduit to both holes. If conduit isalready attached, go to step 11.

11. Route the transformer output wiring through the UPS conduit andconnect it to the UPS terminal block according to the TransformerOutput Wiring to UPS Chart, Table 3-6. The wiring diagram in Figure 3-15 shows how the transformer is connected to the UPS.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

ELECTRIC SHOCK HAZARD. A battery can present a risk ofelectric shock and high short circuit. BE CAREFUL when mak-ing connections to terminals. HIGH VOLTAGES may be presentwhich can injure or kill personnel and damage equipment.

C AC AC AC AC A U T I O NU T I O NU T I O NU T I O NU T I O N

Utility neutral must be connected to the neutral terminal (IL3)on all hardwired units. Failure to connect the neutral candamage the unit.

Section 3 Installation

c

WARNING!

CAUTION!

2 7Minuteman Continuous Power Series UPS

Table 3-6. Transformer Output Wiring to UPS Chart

Transformer Output Wiring to UPS

Connect This Wire From the Transformer To This Terminal in the UPS

Output Ground Grounding Stud

OL3 Neutral IL3 (Neutral)

OL1 Line 1 (hot) IL1 (Line 1)

OL2 Line 2 (hot) two-phase only IL2 (Line 2) two-phase only

Transformer UPS

Ground

Neutral

Line 1

Line 2IL1

IL3

IL2

OL1

OL3

OL2

IL1

IL3

IL2

OL1

OL3

OL2

1

1 Neutral must be connected. Failure to do so can damage the unit.

Used for two-phase units only2

2

Figure 3-15. Transformer to UPS Wiring Diagram

12. Route the load wiring through the other UPS conduit and connect it tothe UPS terminal according to the Load to UPS Wiring Chart, Table 3-7. Figure 3-16 illustrates how the load wires connect to the UPS. Ifloads are already connected to the UPS, go to step 13.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

ELECTRIC SHOCK HAZARD. A battery can present a risk of elec-tric shock and high short circuit. BE CAREFUL when making con-nections to terminals. HIGH VOLTAGES may be present whichcan injure or kill personnel and damage equipment.

Table 3-7. Load to UPS Wiring Chart

Load to UPS

Attach This Wire To This Terminal on the UPS

Load Ground Grounding Stud

Load Neutral OL3 (Neutral)

Load Line 1 OL1 (Line 1)

Load Line 2 (two-phase only) OL2 (Line 2) (two-phase only)

c

WARNING!

2 8

Section 3 Installation

1 Used for two-phase units only.

UPS

Loads

Ground

Neutral

Line 1

Line 2IL1

IL3

IL2

OL1

OL3

OL21

Figure 3-16. Load to UPS Wiring Diagram

13. Replace the rear panel plates on both the transformer and UPS. Besure the conduit is sealed.

14. Installation is now complete. Go to section 4, Operation, for instructionsabout how to operate the UPS. To connect external batteries see theInstalling the External Battery instructions later in this section. Toconnect external DC sources see Connecting External DC Source laterin this section.

INSTALLING OPTIONAL PLUG AND PLAY TRANSFORMERThe instructions below explain installing transformers with plug and playconnections. Figure 3-17 shows how the plug and play transformer connectsto the UPS.

1. If the UPS is plugged into an AC outlet, turn the loads and the UPS off.If the UPS is not installed, go to step 3.

2. Unplug the UPS line cord from the AC outlet.

3. Plug the transformer line cord into the AC outlet.

4. Plug the UPS line cord into the output receptacle at the rear panel ofthe transformer.

5. If loads are already connected go to step 6. Plug your loads into thereceptacles at the rear panel of the UPS.

6. Installation is complete. You can now turn the UPS and loads on orrefer to section 4, Operation for information on how to operate the UPS.

2 9Minuteman Continuous Power Series UPS

Transformer UPS

UPS LineCord

Output Receptacle

AC UtilityOutlet

Figure 3-17. Installing a Plug and Play Transformer to the UPS

INSTALLING EXTERNAL BATTERY PACKS

Battery packs supplied by Minuteman have plug and play connections. Thefollowing instructions describe connecting the external battery packs to theUPS. The section also explains using the battery upgrade program toreconfigure the UPS for the external batteries. If you are using an alternateexternal DC source, see Installing Customer Supplied External DC Sourceslater in this section.

W A R N I N GW A R N I N GW A R N I N GW A R N I N GW A R N I N G

ELECTRICAL SHOCK HAZARD. Do not attempt to change thewiring in either the battery pack plug or battery pack recep-tacle. Attempting to alter plugs or receptacles wiring caninjury or kill personnel. If plugs and receptacles do not matchcall your Minuteman representative.

1. Plug the battery line cord into the external battery connector at the rearpanel of the UPS. Figure 3-18 shows the location of the connector.Push the battery pack plug into the connector quickly and firmly.

2. To connect more than one battery pack, connect the line cord of thesecond battery to the battery connector of the first battery. Repeat thisarrangement for each additional battery pack, as shown in Figure 3-18.

3. The external battery pack is now installed. Go to the next section toreconfigure the UPS for the external batteries.

WARNING!

3 0

External Battery External Battery

UPS

ExternalBattery

Line Cord

ExternalBattery

Connector

Ext. BatteryConnector

Figure 3-18. Connecting Battery Packs to the UPS

RECONFIGURING RUN TIME AND LOW BATTERY WARNINGAdding external batteries requires you to reconfigure the UPS�s battery runtime and low battery warning. To accomplish this, a program disk calledPWRS Battery Upgrade is included with your external battery pack(s).

System Requirements:

� DOS 2.0 or greater; or

� Windows 3.0 or greater.

After connecting the external battery pack(s), follow the steps below to use thePWRS Battery Upgrade program.

1. Connect the UPS to a host computer through the RS-232 port usingthe interface cable that accompanied your UPS.

2. Place the PWRS Battery Upgrade disk in the computer�s floppy drive.

3. If you are using DOS, type �Battery n� at the prompt (n= the number ofexternal battery packs connected to the UPS. For example, if you haveconnected 2 battery packs, enter �Battery 2�). Then press return.

4. If you are using Windows, select FILE from the Program Manager andchoose Run. At the command line enter �Battery n� (n= the number ofexternal battery packs. For example, if you are connecting 2 batterypacks, enter �Battery 2�). Then click OK.

5. The program takes several seconds to run. After the program has runthe UPS will calculate the correct battery run time and give an accuratelow battery warning. Save the disk for future upgrades.

Section 3 Installation

c

3 1Minuteman Continuous Power Series UPS

INSTALLING A CUSTOMER SUPPLIED EXTERNAL DC SOURCE

The following instructions explain how to connect an external DC source to theUPS. Note the warnings and cautions before installing.

W A R N I N G

ELECTRICAL SHOCK HAZARD. A voltage and over current pro-tection device MUST be installed between the external DCsource system and the UPS. The external backup system maycontain HIGH VOLTAGES. BE CAREFUL when making connec-tions to terminals labeled �BATT INPUT�. These high voltagescan damage equipment and injure or kill personnel.

W A R N I N G

To hard-wire an external DC source to the UPS terminal block,make sure the UPS is OFF by pressing the ON/OFF and OFFbuttons at the same time. Connect only one wire per termi-nal.

1. Disconnect the internal battery connector shown in Figure 3-19 beforeconnecting any wires to the terminal blocks.

2. Connect the external DC source according to the External DC SourceConnection Chart, Table 3-8.

W A R N I N G

ELECTRIC SHOCK HAZARD. The internal battery connectormust be disconnected to prevent electric shock when in-stalling an external DC source. Electric shock can injure orkill personnel.

W A R N I N G

The maximum available fault current must be limited to lessthan or equal to 5000 A from any DC source.

Internal Battery Connector

Figure 3-19. Disconnecting the internal battery connector

WARNING!

WARNING!

WARNING!

WARNING!

3 2

Table 3-8. External DC Source Connection Chart

External DC source to UPS

Attach This Wire To This Terminal on the UPS

External DC ground Grounding Stud

External DC negative (-) BATT Input (-)

External DC positive (+) BATT Input (+)

External DC neutral (N) BATT Input (-N-)

NOTE: ALL CONNECTORS MUST BE INSTALLED.

3. Reconnect the internal battery connector as shown in Figure 3-20.

4. Installation is complete. Go to section 4, Operation, for instructions on operat-ing the UPS.

Your UPS may have an optional output circuit breaker plate through whichsome loads can be connected. Follow the instructions to connect your loadsthough the output circuit breaker plate.

W A R N I N G

ELECTRICAL SHOCK HAZARD. The field-wiring must be per-formed by a qualified electrician or technician, or some otherqualified personnel. The UPS and batteries may contain HIGHVOLTAGES. These high voltages can injure or kill personneland damage equipment.

W A R N I N G

Do the following BEFORE CONNECTING or DISCONNECTINGANY WIRING:

� TURN OFF all input power (AC and DC).

� TURN OFF the UPS by pressing the ON/OFF and OFF but-tons at the same time.

� TURN OFF the critical load (Any transformers or motors infront of the load are considered part of the load.

� VERIFY WITH A METER that the power is removed.

cFigure 3-20. Reconnecting the internal battery connector

Section 3 Installation

CONNECTING LOAD THROUGH OUTPUT CIRCUIT BREAKER PLATE

WARNING!

WARNING!

Internal Battery Connector

3 3Minuteman Continuous Power Series UPS

1. Remove the circuit breaker plate from the UPS and punch out theknockout hole

2. Attach conduit to the conduit hole and route output wiring to the termi-nal block.

3. Connect the output wiring according to Table 3-9, Output CircuitBreaker Chart. Figure 3-21 shows the circuit breaker terminal blocklabels.

Table 3-9. Output Circuit Breaker Wiring Chart

Load to Circuit Breaker Plate

Connect This Wire To This Terminal on the Output Circuit Breaker

Output Ground Grounding Stud

Output Neutral N (Neutral)

Output Line 1 (hot) L1 (Line 1)

Output Line 2 (hot) L2 (Line 2)L2 L1 N

US

E C

U O

NLY

05143228 A

Figure 3-21. Output Circuit Breaker

4. Reattach the output circuit breaker plate to the UPS. Go to the section4, Operation, under Using Options for instructions about operating theload circuit breaker.

INTERFACE PORTS

The interface ports are located at the back of the UPS. They include a relayinterface port, an RS-232 port, and a remote emergency power off (REPO)switch port. This section describes the function and location of each port.Figure 3-22 shows each ports location.

RELAY INTERFACE PORTThe relay interface port has dry contacts that provide connections for a number ofremote status display and remote alarm devices. These devices include:

� AC line failure alarm

� Impending low battery alarm

� Summary alarm

� Load-on-bypass alarm

3 4

Refer to the installation/operation instructions that accompany these devicesfor operation and installation instructions.

RS-232 PORT AND CABLEThe RS-232 port can be used to connect to a host computer to monitor yourentire UPS system. The RS-232 is also fully compatible with all MinutemanNetwork Manager software.

N O T E

This RS-232 interface is a data channel only. The UPS will op-erate normally (protecting your load from power line prob-lems) with or without the RS-232 interface.

REMOTE EMERGENCY POWER OFFThe Remote Emergency Power Off (REPO) shuts down the UPS from aremote location by opening the closed REPO switch.

The REPO switch port, as shown in Figure 3-22, is located at the rear panel ofthe unit. To connect the REPO switch, remove the jumper wire from theREPO port and install a REPO cable. The maximum length of the cableshould not exceed 1000 feet (305 meters) for proper operation.

N O T E

The REPO connection is normally a CLOSED connection. Re-moving the jumper wire will cause the UPS to shut down.Turn the manual bypass switch to bypass (if available) whenconnecting a REPO device, or shut down loads.

Optional SecondRS-232

Relay Interface Port

RS-232

REPO Port

Start-On-Battery

Figure 3-22. UPS Communication Ports on the Rear Panel

Section 3 Installation

NOTE

NOTE

3 5Minuteman Continuous Power Series UPS

O P E R A T I O N

This section explains how to use the front panel control buttons and LEDindicators to operate the UPS in both operation mode and configure mode.The section also explains the audio alarm, self test, rear panel communicationports, and options.

N O T E

The control buttons and LED indicators perform the samefunctions and indicate the same information for both towerand rack-mount models

OPERATION MODE AND CONFIGURE MODE

The UPS front panel has two modes. Operation mode is the normal or defaultmode for the UPS. In this mode the front panel LEDs indicate informationabout the unit�s operation, and the control buttons manage UPS functions. Inconfigure mode, the LEDs and control buttons set the unit�s operation param-eters.

OPERATION PARAMETERSOperation parameters allow you to program various aspects of the UPS�soperation including frequency detection, nominal voltage, and alarms. Opera-tion parameters are set when the unit is in configure mode.

OPERATION MODE

AUTOMATIC STARTThe UPS starts automatically when the unit is connected to AC power. TheUPS can be configured to start manually. See Configuration Mode later in thissection for instructions. When output power is available to the receptacles/terminal blocks, the Output LED (ON LED) turns on. If output power is notavailable the Output LED (ON LED) turns off.

FRONT PANEL CONTROL BUTTONSThe front panel of the UPS has three control buttons used to operate the UPS.Buttons should be pressed for at least 0.5 seconds to activate unless otherwiseindicated. Figure 4-1 shows each control button and its specific function whenthe UPS is in operation mode.

ON/OFF Button ( )To manually start the UPS, push the On/Off button (see Configure Mode to turnoff auto-restart). When the UPS is on, power is available at the rear panel recep-tacles/terminal blocks.

Off Button ( )Push both the Off button and the On/Off button simultaneously to turn off power tothe rear receptacles/terminal blocks. The Output LED (ON LED) will turn off.When the unit is turned off, it can not be turned back on for 8 seconds.

4

m

NOTE

3 6

Press the Off button to place the UPS into bypass mode. Press the Off Buttonagain to place UPS back into operation mode.

N O T E

Because the UPS stays in bypass mode for 10 seconds, waitat least 10 seconds before placing UPS back into OperationMode.

Test/Reset Button ( )Pushing the Test/Reset button resets the audio alarm. Pushing theTest/Reset button for 3 seconds initiates the self test.

ON

Press once to turn UPS onmanually

Press both buttons to turn off power to rear

receptacles / terminal blocks

Press to reset alarm

Press once for 3 secondsto start self test

On/Offbutton

Test/Resetbutton

Offbutton

Press once to place UPS in bypass mode. Press again to

place UPS back into operational mode.

Figure 4-1. Control Button Functions for Operation Mode

SELF TESTThe UPS conducts a self test when the Test/Reset button is pushedfor 3 seconds. The self test performs diagnostics on various UPSfunctions to ensure the UPS is operating properly.

N O T E

If the batteries are not fully charged, the UPS will be unableto conduct a self-test.

UPS ALERTS

The audio alarm and LEDs alert the user to problems that may occur with theUPS, the AC input, or the loads when the unit is operating or conducting aself-test. During some events the alarm will sound in conjunction with anilluminated LED. Refer to the LED Indicator section later in this section or theTroubleshooting Guide for further information and instructions.

Section 4 Operation

NOTE

NOTE

3 7Minuteman Continuous Power Series UPS

FAILED SELF TESTIf the UPS fails its self test, the alarm will sound. Push the reset button for 3seconds to conduct another self test. If the alarm sounds again (indicating asecond failure), see section 7, Troubleshooting Guide, for instructions.

LINE FAILUREIf AC input fails, the audio alarm sounds and one of the LED above the ACinput icon turns red while the UPS switches to battery power. Press the Test/Reset button to turn off the audio alarm. The alarm resets when power returns.See section 7, Troubleshooting Guide, under the AC Input icon for instruc-tions.

OVERLOADWhen the UPS is overloaded on either line 1 or line 2 the audio alarm sounds andthe top LED on line 1 or line 2 (above the load icon) turns red. The unit will go intoauto bypass. Overloading occurs when loads attached to either line draw morecurrent than the UPS can provide. See section 7, Troubleshooting Guide, forinstructions about correcting an overload. Press the Test/Reset button to turn offthe alarm. The alarm automatically resets itself once overload problem is cor-rected.

OVERTEMPERATUREThe audio alarm sounds when the UPS is overheating. Turn off your loads first,then turn off the UPS. Check to see that the UPS has enough ventilationspace around the unit and that the ventilation grating on the rear panel is clearof dust and debris. If overheating continues see section 7, TroubleshootingGuide, for further instructions. Press the Test/Reset button to turn off thealarm. The alarm automatically resets itself.

SITE WIRING FAULTThe site wiring fault alarm is for single phase models. The alarm sounds andthe middle AC input icon flashes green if the UPS is not grounded properly,(Hot and Neutral are reversed). See section 7, Troubleshooting Guide, forfurther instructions about correcting a site wiring problem. Press the Test/Reset button to turn off the alarm. The alarm automatically resets itself.

LED INDICATORS

The LED indicators, shown in Figure 4-2, are located on the front panel of theUPS. They tell the user how the UPS is functioning in areas that include ACinput condition, battery level, and percentage of load capacity. There is also anON LED, a battery service LED, and a bypass LED. Figure 4-2 shows theinformation each LED indicates. See section 7, Troubleshooting Guide forexplanations and solutions for LEDs that indicate a problem.

3 8

ON Lit when power is present at rear output receptacles/terminals

AC INPUT LEDs

Output LED

Line voltage high, UPS on battery

red

green

red

UPS on AC input. If LED is not lit UPS is on battery power. LED flashes when a site wiring fault is detected

Line voltage low, UPS on battery

If all LEDs are solid, input frequency is outside selected frequency range

> 90%

Impendinglow battery

BATTERY LEVEL LEDs

green

green

green

green

red

LOAD LEDs

BATTERY SERVICE LED

Solid red if battery needs service

BYPASS LEDSolid red if in bypass mode

Line 1* Line 2*red

overloadgreen

75-100%green

50-75%green

25-50%green5-25%

* On single-phase units, the LEDs for Line 1 and 2 indicate the sameload information

ON

Figure 4-2. Exploded View of the UPS Front Panel

ON UPS Output LED

This LED is green when power is available to the receptacles/terminal blocks.

AC Input LEDs

There are three LEDs above the AC input icon that indicate the condition ofAC input.

Section 4 Operation

3 9Minuteman Continuous Power Series UPS

Top LED is red: Line voltage(s) is above acceptable limits. UPS on batterypower.

Middle LED is green: Line voltage(s) is at acceptable levels. If the LED isnot lit the UPS is on battery power.

Middle LED flashes green: A site wiring fault is detected. ConsultTroubleshooting Guide for details.

Bottom LED is red: Line voltage(s) is below acceptable input level. UPSis on battery power.

All three AC Input LEDs are on: Input frequency is outside the bypassrange but line voltage is within acceptable range. See Configuring theUPS later in this section for instructions on changing frequency range.

Battery Level LEDs

The battery level LEDs indicate the amount of approximate charge in thebattery. Adding external batteries will increase backup-times.

Bottom LED is red: Indicates impending low battery. The UPS has 2-5minutes battery backup left before shutdown.

Remaining Four LEDs: 4 LEDs are green: >90% charge

Load LEDs

There are two columns of LEDs above the load icon that indicate load levels.Load level is based on RMS current or watts, whichever is greater. On single-phase models, the first and second columns indicate the same load informa-tion. On two-phase models the first column shows the amount of power drawnfrom line 1 and the second column shows the amount drawn from line 2.

Top LED is red: Overload. Load is >100% of total load capacity.4 LEDs are green: 75-100% of total load capacity3 LEDs are green: 50-75% of total load capacity2 LEDs are green: 25-50% of total load capacity1 LED is green: 5-25% of total load capacity

Bypass LED

The bypass LED is red when the UPS is in bypass mode. This LED must beon before the MBS switch can be used.

Battery Service LED

The Battery service LED is solid red when the battery requires service. See theTroubleshooting Guide for details.

4 0

Configure ModeCONFIGURING UPS OPERATION PARAMETERSThe Continuous Power Series UPS has a set of operation parameters that areconfigured using the front panel control buttons and LEDs when the UPS is inconfigure mode. The control buttons place the UPS in configure mode, scrollthough parameters, and turn each parameter on and off. The LEDs on the frontpanel indicate which parameter you are working. Figure 4-3 shows the controlbuttons and indicates which LED on the front panel represents which parameter.Table 4-1, Parameter Configurations, explains each parameter.

Follow the steps below and use Figure 4-3, and Table 4-1 to set each opera-tion parameter.

1. Place the UPS in configure mode by pressing the On/Off button

( ) and Test/Reset button ( ) at the same time for 3

seconds. Then press the Off button ( ) to scroll to LED number 1.

This LED represents the first of 19 parameters.

2. Enable or disable each parameter by pressing the Test/Reset

button ( ) while in configure mode. Table 4-1 shows which

LED represents each parameter.

3. Scroll through each parameter by pressing the Off button ( ).

4. Set all parameters according to Table 4-1.

5. The UPS automatically returns to operation mode after scrollingthough the last LED.

N O T E

The UPS returns to Operation Mode after 90 seconds if noth-ing is entered while in Configure Mode. Changes made inConfigure Mode are automatically saved.

ON

Press to scroll through parameters while

in configure mode.

Press button once to enable or disable

each parameter while in configure mode.

(UPS returns to operation mode after scrolling through the last LED.)

Press both buttons for3 second to put

UPS in configure mode.

LED 8→ LED 7→ LED 6→ LED 5→ LED 4→

LED 13→LED 12→LED 11→

LED 10→ LED 9→

←LED 18

←LED 17

←LED 16

←LED 15

←LED 14←LED 19

LED 3→

LED 2→

LED 1→

m

Figure 4-3. Front Panel Control Buttons and LED Indicators When the UPS is in Configure Mode

Section 4 Operation

NOTE

4 1Minuteman Continuous Power Series UPS

N O T E

LEDs 15-19 are used to select specific output voltages for theUPS. The default voltage for single-phase units is 120 V nomi-nal. The default for two-phase units is 208 V or 240 V nominal.Enable only one voltage selection. If two conflicting voltagesare enabled the voltages will automatically return to thedefault.

Table 4-1. LED Parameters

LEDLED State Parameter

1 Blinking* Enable auto frequency detectionSolid Disabled

2 Blinking Enable forced 60 Hz frequency regardless of inputSolid* Disabled

3 Blinking Enable forced 50 Hz frequency regardless of inputSolid* Disabled

4 Blinking* Synch. frequency range A ± 3 HzSolid Disabled

5 Blinking Synch. frequency range B ± 1 HzSolid* Disabled

6 Blinking Synch. frequency range C ± 1/2 HzSolid* Disabled

7 Blinking 5minute impending low batterySolid* 2minute impending low battery

8 Blinking Disable auto restartSolid* Enable auto restart

9 Blinking Disable site wiring faultSolid* Enabled site wiring fault (only 1 phase unit)

10 Blinking Disable audio alarmSolid* Enabled audio alarm

11 Blinking Enable 2nd RS-232 port for modem (optional)Solid* Disabled

12 Blinking* Disable auto self testSolid Enable auto self test (select either 30 or 90 day test from LED 13

or 14. If none is selected, parameter returns to default)13 Blinking Enable every-30-day auto self test

Solid* Disable every-30-day auto self test14 Blinking Enable every-90-day auto self test

Solid* Disable every-90-day auto self test

15 Blinking Enable 100 V output (200 V output)** nominalSolid* Disabled

16 Blinking Enable 110 V output (220 V output)** nominalSolid* Disabled

17 Blinking Enable 115 V output (230 V output)** nominalSolid* Disabled

18 Blinking* Enable 120 V output (208/240 V output)** nominalSolid Disabled

19 Blinking Enable 127 V output (220/254 V output)** nominalSolid* Disabled

* Parameter default. ** Voltage in parenthesis ( ) are applicable for two-phase units.

NOTE

CAUTION! During configuration mode, "DO NOT" configure the LED #20 to blink. This is forfactory use only, and may damage the UPS. Failure to comply with this directive mayvoid your warranty!

4 2

USING COMMUNICATION INTERFACES AND REAR PANEL CONTROLS

The Continuous Power Series has several communication interfaces that allowthe user to monitor and control UPS functions through either remote monitor-ing devices or through a host computer. The Continuous Power Series alsohas several rear panel controls that are explained in this section.

Optional SecondRS-232

Relay Interface Port

RS-232

REPO Port

Start-On-Battery

Figure 4-4. The UPS Communication Ports

REMOTE EMERGENCY POWER OFFThe Continuous Power Series has a dedicated port for a Remote EmergencyPower Off (REPO) device. A REPO device, shown in Figure 4-4, is designedto shutdown the UPS from a remote location by opening a normally closedswitch. When the REPO switch is activated, power is turned off to the terminalblocks or receptacles at the back of the unit. For details about installing andoperating a REPO device, see the instructions that accompany the device.

W A R N I N G

REPO wiring should also trip the input breaker to the UPS tocompletely turn off the UPS.

RELAY INTERFACE PORTSThe relay interface port provides alarm signals on dry contacts. Table 4-2 andFigure 4-5 show the pin locations for each alarm. Alarms include a summaryalarm, bypass indicator, line failure indicator, and an impending low batteryindicator. For details about how to use the various remote status devices, readthe instructions that come with those devices.

Section 4 Operation

WARNING!

4 3Minuteman Continuous Power Series UPS

Table 4-2. Alarm Connections

Alarm Pin Number Connected To System State

Line Failure 1 - 2 Line OK 1 - 3 Line Failure

Impending Low Battery 4 - 5 Battery Normal4 - 6 Battery Low

Summary Alarm 7 - 9 UPS ON/OK7 - 8 UPS Alarm

UPS Bypassed 10 - 11 Inverter Supply10 - 12 Bypass Supply

Line Failure

ImpendingLow

Battery

Summary Alarm

UPS Bypassed

D—connector 15-pin

15 14 13 11 10 12 9 7 8 6 4 5 3 1 2

Figure 4-5. Pin Locations for Each Alarm

REAR PANEL CIRCUIT BREAKERSThe Minuteman Continuous Power Series has two types of output circuitbreakers on the rear panel. The push-button type circuit breaker protects eachstandard 5-15R duplex. When the push-button circuit breaker trips, it popsouts and a green ring appears. Push it in to reset.

C A U T I O N

Pushing in the push-button circuit breaker when it is nottripped, causes the circuit to open and your load to drop.

CAUTION!

4 4

Section 4 Operation

The branch-type circuit breaker protects both 5-15R duplexes. When thebreaker trips a red flag appears in the small window on the switch. To reset,move the switch to the OFF position then to the ON position.

USING OPTIONS

Your UPS may have several options including a second RS-232 port, trans-former, external batteries, a start-on-battery switch, and a manual bypassswitch. Each option is explained below.

SECOND RS-232 PORT WITH MODEM BOARD

The second RS-232 port on the rear panel of the UPS is used in conjunctionwith a modem board. The modem board allows the UPS to communicatepossible problems to a service center over the telephone lines. A modemboard allows both RS-232 ports to operate.

EXTERNAL BATTERY PACKS (RESERVE PACKS)Battery packs contain maintenance free batteries and have no user operations.External battery packs can be daisy chained together. See section 3, Installa-tion, for instruction on installing external battery packs.

START-ON-BATTERYThe start-on-battery switch option, shown in Figure 4-4, allows the user to turnon loads from the UPS during a power outage, provided that enough batterybackup is available. The switch is located at the rear panel of the UPS. To startthe UPS on battery, press and hold the start-on-battery switch for 20 secondsor until the UPS turns on.

MANUAL BYPASS SWITCHThe manual bypass switch (MBS) is on the rear panel of the UPS at thebottom as shown in Figure 4-6. Only use the manual bypass switch when thebypass mode LED is on. See Operation Mode under, �Off Button� earlier in thissection for instructions about how to place UPS in bypass mode. When theUPS is on bypass, AC input bypasses the UPS and goes directly to the load. Ifa power problem occurs while the UPS is on bypass, the unit does not switchto battery power.

C A U T I O N

Do not use the manual bypass switch unless the UPS is inbypass mode. When the UPS is in bypass mode, the bypassLED is on.

CAUTION!

4 5Minuteman Continuous Power Series UPS

Figure 4-6. The Optional Manual Bypass Switch

OUTPUT CIRCUIT BREAKER PLATEThe output circuit breaker, shown in Figure 4-7, trips when the load circuit isoverloaded. To reset the load circuit breaker, move the switch to the Onposition.

N O T E

If the breaker trips repeatedly, check connected loads. Dis-connect defective loads.

Figure 4-7. The Output Circuit Breaker Plate

NOTE

4 6

NOTES:

Section 4 Operation

4 7Minuteman Continuous Power Series UPS

M A I N T E N A N C E

This section explains UPS care and maintenance including preventive mainte-nance, battery care, and UPS storage.

PREVENTIVE MAINTENANCE

You can expect long, trouble-free operation from the Continuous Power SeriesUPS by taking a few preventive maintenance measures. Keep the area aroundthe UPS clean and relatively dust free. If the atmosphere is very dusty, cleanthe outside of the system periodically with a vacuum cleaner.

BATTERY LIFE

By keeping the UPS at an ambient temperature of 25°C (77°F), full battery lifecan be achieved, providing that battery usage is not abnormal.

BATTERY RECHARGING

While the UPS is on, the batteries are automatically recharged when powerreturns after a power failure. Complete recharging can take up to 24 hours.However, most charging is done in less than 8 hours. The battery does nothave to be fully charged to protect your system. The Continuous Power Seriesis designed to provide protection through multiple power outages as long asbattery power is available.

STORING THE UPSIf you plan to store the UPS, follow the guidelines below to protect thebatteries:

� Fully charge the batteries before you store the UPS.

� Turn the UPS OFF whenever it is being stored.

� Avoid storage temperatures above 27°C (80°F). The preferred storagetemperature is 21°C (70°F).

� Every 180 days, connect the UPS to an AC source, or plug the UPSinto an AC outlet (plug and play models), and operate the UPS for 12hours to charge the batteries. The batteries may suffer damage if notcharged every 180 days during storage.

� When moving, storing, or operating the UPS, you must keep it upright.

5

m

4 8

MAINTENANCE

The UPS requires no customer maintenance other than charging the battery ifthe UPS is stored for a long period of time. Repairs and maintenance must beperformed at the factory or factory-authorized service locations by qualifiedtechnicians. Maintenance agreements are available. Please contact Minute-man Technical Support Department at 1-800-238-7272 if you have any ques-tions or problems.

C A U T I O N

This product contains sealed lead batteries which must bedisposed of properly. For more information, contact your lo-cal recycling center or Minuteman representative.

Section 5 Maintenance

CAUTION!

4 9Minuteman Continuous Power Series UPS

S P E C I F I C A T I O N S

This section lists the electrical and physical specifications for all Continuous PowerSeries models. Table 6-1, Model Specifications, gives specific information for eachmodel.

ELECTRICAL INPUT

Power Ratings: 3.1, and 6.0 KVA;

Voltage: 120 VAC (nominal) for 3.1 KVA;120/208 or 120/240 VAC (nominal)for 3.1/6.0 KVA; -27 to +22%

Frequency: 50/60 Hz, ±3 Hz (auto-sensing)

Power Factor: >0.95 (active correction)

Connection: Hardwire to terminal strips standard. Line cord andplug option is available

ELECTRICAL OUTPUT

Voltage: 120 VAC (nominal) for 3.1 KVA;120/208 and 120/240 VAC (nominal)for 3.1/6.0 KVA

Regulation: ±2%

Overload Rating: 300% of full load for 10 cycles;150% of full load for 10 seconds;125% of full load for 20 minutes

Connections: Hardwired and 5-15R duplex receptacles standard

INTERNAL BATTERY

Type: Internal battery valve regulated, sealed lead-acidtype

Backup Time: 6-10 minutes at full load (standard internal batterypack)

Recharge Time: <3 hours to 90% capacity. Full 100% capacity: 8�24 hours

PHYSICAL

OperatingTemperature: 0-40°C. Recommended use at 25°C

OperatingHumidity: 0-95% non-condensing

Operating Altitude: 3000 meters (10,000 ft.)

Audio Noise: @ 25°C and 45% load, <49 dBA @ 1 meter (3 ft.)

UPS Dimension/

6

5 0

Section 6 Specifications

Weight: See Table 6-1, Model Specifications

Table 1-1. Continuous Power Series Standard Models

CP3000 Tower Hardwired 3.1 120v 23 x 6.8 x 16 125(58.4 x 17.2 x 40.6) (56.9)

CP3000-PP*2 Tower Plug & Play 3.1 120v 23 x 6.8 x 16 135(58.4 x 17.2 x 40.6) (61.2)

CPR3000 Rack Hardwired 3.1 120v 6.8 x 17.5 x 24 125(17.2 x 44.5 x 61) (56.9)

CPR3000-PP*3 Rack Plug & Play 3.1 120v 23 x 6.8 x 16 135(58.4 x 17.2 x 40.6) (61.2)

CP3200 Tower Hardwired 3.1 120/208 23 x 6.8 x 16 125120/240 (58.4 x 17.2 x 40.6) (56.9)

CP3200-PP*4 Tower Plug & Play 3.1 120/208 23 x 6.8 x 16 135120/240 (58.4 x 17.2 x 40.6) (61.2)

CPR3200 Rack Hardwired 3.1 120/208 23 x 6.8 x 16 125120/240 (58.4 x 17.2 x 40.6) (56.9)

CPR3200-PP*5 Rack Plug & Play 3.1 120/208 23 x 6.8 x 16 135120/240 (58.4 x 17.2 x 40.6) (61.2)

CP6000 Tower Hardwired 6 120/208 23 x 6.8 x 24 180120/240 (58.4 x 17.2 x 60.9) (86)

CP6000-PP* Tower Plug and Play 6 120/208 23 x 6.8 x 24 190120/240 (58.4 x 17.2 x 60.9) (90.3)

*1 All models are 50 & 60 Hz capable with auto-sensing.Standard plug and play model includes 4 each 5-15R receptacles and a L5-30P with inputline cord.

*2 Standard plug and play models includes 4 each 5-15R receptacles and a L5-30P with input linecord.

*3 Standard plug and play models include 4 each 5-15R, one L6-30R receptacles and a L14-30P withinput line cord.

*4 Standard plug and play model includes 4 each 5-15R, and one L6-30R receptacle and a L14-30Pwith input line cord.

*5 Standard plug and play models include 8 each 5-15R and one L6-30R receptacles and an L14-30Pwith input line cord.

6

VACVAC

VACVAC

VACVAC

VACVAC

VACVAC

VACVAC

1MODELS* STYLE

INPUT /OUTPUT

CONNECTION

DIMENSIONSIN / CM

(L X W X H)VOLTVAC

KVARATING

WEIGHT(LB/KG)

or

or

or

or

or

or

5 1Minuteman Continuous Power Series UPS

TROUBLESHOOTING

The Troubleshooting Guide describes various problems that may occur whileinstalling and operating the UPS, then suggests possible solutions. Problemsmay be indicated by front panels LEDs, the audio alarm, or both. The solutionsare simple steps that can be performed easily. If a problem is serious, theguide refers you to the Service Center.

Symptom Possible Cause What To Do

UPS will AC input not properly connected Consult the installation field-wiring instructions or maketo an AC outlet on plug and play sure to terminal block, or line cord line cord is connectedmodels not connected.

UPS is not turned on. Push the On/Off button on the front panel.

Wall socket is dead. Have qualified electrician repair the socket.

Alarm Sounds: UPS internal diagnostic test Press Test/Reset button to start self test again.Failed self test found a problem. If alarms continues, call Minuteman Technical Support.

Alarm Sounds: AC input has failed. UPS Save work and conduct an orderly shutdown ofAC line failure is in battery operation. your electrical equipment.

Alarm Sounds: Loads attached to line 1 Make sure loads are balanced between linesOverload or line 2 are drawing too 1 and 2 on two-phase models. See

much current. section 3, Installation, for more details.

Alarm Sounds: UPS is overheating. UPS on Make sure UPS is well ventilated.Over temperature auto bypass. (see Positioning the UPS in section 2, Preparation).

If overheating continues, call Minuteman TechnicalSupport.

Alarm Sounds: Ground wire or connection Have qualified electrician establish grounding.Site wiring fault does not exist in wall outlet.

Line and neutral wires are Have qualified electrician correct the wiring.reversed in wall outlet.

Line and neutral wires installed Have qualified electrician check hardwiring.incorrectly on hardwired units.

Alarm sounds Serious problems still exists. Turn UPS Off, then On. If alarm continues, contactafter reset button Minuteman Technical Support.is pushed

Battery Service LED Battery needs service. Contact Minuteman Technical Support.is RED

Battery service LED is Battery not charged. Keep UPS connected to AC input for at least 24RED during self test hours and then conduct self test.

Bottom LED above 2 to 5 minutes of battery Be prepared to lose battery power to your load(s).battery icon is RED backup left (with normal Save work and conduct orderly shutdown.

load and enough charge).

7

not turn on.

5 2

Section 7 Troubleshooting

Symptom Possible Cause What To Do

Top LED on line 1 Overload condition on line Determine if load(s) on line 1 is defective or if tooabove load icon is RED 1 (load drawing >100% of many loads are connected. Be sure loads are

available current/power). balanced on two-phase units.

Top LED on line 2 Overload condition on line Determine if load(s) on line 2 is defective or if tooabove load symbol is 2 (load drawing >100% of many loads are connected. Be sure loads areRED available current/power). balanced on two-phase units.

Top LED above AC Line voltage is too high. Correct input voltage if possible or be prepared toinput icon is RED, UPS on battery power. lose battery power to your load(s) after low battery alarm.middle LED off

Bottom LED above Line voltage is too Correct AC Input if possible or be prepared to loseAC input icon is RED, low (power failure) battery power to your load(s) after low battery alarm.

middle LED off UPS on battery.

Top and bottom LED Input freq. is outside See Configure Mode in section 4, Operation, toabove AC input icon bypass range. change frequency range.RED, middle LED green

Middle LED above AC Site wiring fault detected Plug and Play: Defective wall outlet. Have qualifiedicon is FLASHING electrician check outlet. Hardwired: Neutral and linegreen crossed. Have qualified electrican or technician check

wiring.

5 3Minuteman Continuous Power Series UPS

8. OBTAINING SERVICE

If the UPS requires service:

1. Use the TROUBLESHOOTING section 7 to eliminateobvious causes.

2. Verify that no circuit breakers are tripped. A tripped circuitbreaker is the most common problem.

3. Call your dealer for assistance. If you cannot reach yourdealer, or if he cannot resolve the problem, call or FAXMinuteman technical support at the following numbers:Voice phone (214) 446-7363, FAX line (214) 446-9011.Please have the following information available BEFOREcalling technical support.

A. Your Name and address.B. Where and when the unit was purchased.C. All of the model information on the rear of your unit.D. Any information on the failure, INCLUDING Error Codes or Error Messages shown on the front

panel.E. A description of the protected equipment, includ-

ing model numbers if possible.F. A technician will ask you for the above information

and, if possible, help solve your problem over thephone. In the event that the unit requires factoryservice, the technician will issue you a ReturnMaterial Authorization number (RMA #).

G. If the UPS is under warranty, the repairs will bedone at no charge. If not, there will be a chargefor repair.

4. Pack the UPS in its original packaging. If the original packaging is nolonger available, ask the technical support technician about obtaining anew set.

A. It is important to pack the UPS properly in order toavoid damage in transit. Never use Styrofoambeads for a packing material.

B. Include a letter with your name, address, daytimephone number, RMA number, a copy of your originalsales receipt, and a brief description of the trouble.

O B TA I N I N G S E RV I C E

5 4

5. Mark the RMA # on the outside of all packages. The factory cannot accept any package without the RMA # marked on the outside of the shipping box.

6. Return the UPS by insured, prepaid carrier to:

Minuteman, Para Systems Inc.455 LeMay Drive

Carrollton, Tx. 75007

NOTES:

O P T I O N A LP A N E L S

The illustrations below show rear panel plate options for each model.The panels in Figure A-1 are available for all models. The panels inFigure A-2 are only available for two-phase models. Each model hasthree plates on the rear panel. Each plate holds one type of receptacle.Plates may also come with a manual bypass switch (always located atthe bottom plate) or a blank plate.

L5-20R L5-30R 5-15R 5-20R

CSA 5-20R L5-15R

Figure A-1. Optional Receptacle Panels, Available for All Models

6-20R L6-15R L6-20R

L6-30R L14-20R L14-30R 6-15R

Figure A-2. Optional Receptacles Panels for Two-Phase Models

Appendix A ◆ Optional Panels

LIMITED PRODUCT WARRANTY

Para Systems Inc. (Para Systems) warrants this equipment, when properly applied andoperated within specified conditions, against faulty materials or workmanship for a period oftwo years from the date of original purchase by the end user. For equipment sites withinthe United States and Canada, this warranty covers repair or replacement of defectiveequipment at the discretion of Para Systems. Repair will be from the nearest authorizedservice center. Replacement parts and warranty labor will be borne by Para Systems. Forequipment located outside of the United States and Canada, Para Systems only coversfaulty parts. Para Systems products repaired or replaced pursuant to this warranty shall bewarranted for the unexpired portion of the warranty applying to the original product. Thiswarranty applies only to the original purchaser who must have properly registered theproduct within 10 days of purchase.

The warranty shall be void if (a) the equipment is damaged by the customer, is improperlyused, is subjected to an adverse operating environment, or is operated outside the limits ofits electrical specifications; (b) the equipment is repaired or modified by anyone other thanPara Systems or Para Systems-approved personnel; or (c) has been used in a mannercontrary to the product�s operating manual or other written instructions.

Any technical advice furnished before or after delivery in regard to use or application ofPara Systems�s equipment is furnished without charge and on the basis that it representsPara Systems�s best judgment under the circumstances, but it is used at the recipient�ssole risk.

EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRANTIES,EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY ANDFITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of im-plied warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser.

EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLEFOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGESARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSI-BILITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs, such aslost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss ofdata, cost of substitutes, claims by third parties, or otherwise. The sole and exclusive rem-edy for breach of any warranty, expressed or implied, concerning Para Systems�s productsand the only obligation of Para Systems hereunder, shall be the repair or replacement ofdefective equipment, components, or parts; or, at Para Systems�s option, refund of thepurchase price or substitution with an equivalent replacement product. This warranty givesyou specific legal rights and you may also have other rights which vary from state to state.

Longer term and F.O.B. job site warranties are available at extra cost. Contact Para Sys-tems (1-214-446-7363) for details.