over-support splice adaptor

4
• Place splices directly over supports • No additional support required Over-Support Splice Adaptor (Beam Installation) Over-Support Splice Adaptor T&B ® Cable Tray Systems

Upload: others

Post on 16-Nov-2021

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Over-Support Splice Adaptor

• Place splices directly over supports

• No additional support required

Over-SupportSplice Adaptor(Beam Installation)

Over-Support Splice Adaptor

T&B® Cable Tray Systems

Page 2: Over-Support Splice Adaptor

12

3

4

6

Over-Support Splice AdaptorBeam Installation – ABW46-OSS-B

12

3

4

6

21

6

3

4

35

4

Over-Support Splice AdaptorBeam Installation – ABW46-OSS-B

Required on hold down joint only

Required on expansionjoint only

BOTTOM VIEW

1. Bonding jumper2. Splice plate3. Over-support splice adaptor4. Beam clamp

5. Hold down clamp6. Structural beam7. Strut (see right page)

Installation Components

Standard 1/4 Span Typical InstallationBased on NEMA VE2

Supports are placed at 1/4 span (25%).

Supports should be located within 2 feet of each side of expansion splice plates.

T&B Over-Support Installation method

Supports are placed right under the joints of the installation.

The splice adaptor allows a wider distribution of the support, therefore minimizing the stress and deflection of the assembly.

Over-SupportSplice Adaptor

25% Span 25% Span

ExpansionSplice Plate

StandardSplice Plate

StandardSplice Plate

Span

Span

Page 3: Over-Support Splice Adaptor

12

3

4

6

12

3

4

6

Over-Support Splice AdaptorStrut Installation – ABW46-OSS-S

12

3

4

6

12

3

5

7

12

3

4

6

5

Over-Support Splice AdaptorStrut Installation – ABW46-OSS-S

Required on expansionjoint only

INSIDE VIEW

Extra Supports Required

Over-SupportSplice Adaptor

Over-SupportSplice Adaptor

25% Span 25% Span

StandardSplice Plate

ExpansionSplice Plate

StandardSplice Plate

NEMA VE2: Splice joints should be designed and placed so as to maximize the rigidity of the cable tray over support. Splice plates and adaptors are part of a system specifically designed for placement directly over supports.

• For gap setting at expansion joint, refer to NEMA chart on the back cover.

Cable Tray Installation• Every over-support joint must have a pair of

over-support splice adaptors (both standard splices and expansion splices).

Required on hold down joint only

Page 4: Over-Support Splice Adaptor

Atlantic ProvincesThomas & Betts Limited Tel.: (902) 450-1307 Toll Free: 1-877-862-4357 Fax: (902) 450-1309

QuebecThomas & Betts Limited Tel.: (450) 466-1102 Toll Free: 1-800-465-1399 Fax: (450) 466-1163

OntarioThomas & Betts Limited Tel.: (905) 858-1010 Toll Free: 1-877-291-7771 Fax: (905) 858-1080

Manitoba/SaskatchewanThomas & Betts Limited Tel.: (604) 598-9811 Toll Free: 1-866-540-8220 Fax: (604) 598-9840

AlbertaThomas & Betts Limited Tel.: (780) 424-7092 Toll Free: 1-888-664-5666 Fax: (780) 424-7093Toll Free: 1-866-424-4082

British ColumbiaThomas & Betts Limited Tel.: (604) 598-9811 Toll Free: 1-866-540-8220 Fax: (604) 598-9840

Expansion Plate Gap Chart

Gap Settings in. (mm)

Metal Temperature at Time for Installation

© 2017. Thomas & Betts Limited. All rights reserved. Printed in Canada. 09/17/5000. Order No. OVERSUPPORT-E2

ABW46-OSS-BOver-Support Splice Adaptor – Beam Installation

Expansion over support beam 29 in. 2SHWCTC, Heavy-duty hold down clamp (complete with mounting hardware) 2ABWCHGC, Combination Hold Down / Expansion Guide Clamp 2E142-3/8X100EG, 3/8 in. – 16 x 1 in. hex cap screws 2AC100-3/8EGC, 3/8 in. strut nut 2NOTE: Every expansion joint requires the use of a bonding jumper such as FBD16-1 (16 in., 600 A)

ABW46-OSS-SOver-Support Splice Adaptor – Strut Installation

Expansion over support beam 29 in. 2ABWCHGC, Combination Hold Down / Expansion Guide Clamp 4E142-3/8X100EG, 3/8 in. – 16 x 1 in. hex cap screws 4AC100-3/8EGC, 3/8 in. strut nut 4NOTE: Every expansion joint requires the use of a bonding jumper such as FBD16-1 (16 in., 600 A)

Over-Support Splice Adaptor – Safe Working Load

Cable Tray Series Safe Load Rating When Used with ABW46-OSS at 20-ft. Span

AH36 80 lb./ft.

AH46 100 lb./ft.

AH56 120 lb./ft.

AH66 165 lb./ft.

83