GES-TN11-Series – UPS External Wrap Around Bypass System
Operators Manual
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12
Note The instructions contained in this manual are not intended to cover all of the details or variations in equipment, or to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, please refer the matter directly to Always“On UPS Systems Inc. Any electrical or mechanical modifications to this equipment, without prior written consent of Always“On UPS Systems Inc, will void all warranties and may void UL/cUL/CSA listing. Unauthorized modifications can also result in personal injury, death, or destruction of the equipment.
UPS Bypass System Please complete the below information and return it to Always“On UPS Systems Inc. This will activate the warranty. If additional information or technical assistance is required call: Always On UPS Systems Inc Sales and Technical Support Line
Toll free at 1-877-259-2976 Ext. 451 or (250) 491-9777 Ext. 451 or Fax (250) 491-9775
Or E-mail at [email protected] or visit our web site at www.alwayson.com
Or write to
Always On UPS Systems Inc. #100 – 150 Campion Road,
Kelowna, BC, V1X 7S8, Canada
Please complete the following information for your records. Model Number: ______________________________________________________________ Serial Number: ______________________________________________________________ Date of Installation: ____________________________________________________________ Inspected By: ______________________________________________________________
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 i
Table of Contents 1. INTRODUCTION ......................................................................................................................................... 1 2. SYSTEM DIAGRAMS ................................................................................................................................. 2
2.1. FOR 208VAC INPUT, 240/120VAC OUTPUT ............................................................................................... 2 2.2. FOR 240VAC INPUT, 240/120VAC OUTPUT ............................................................................................... 4 2.3. FOR 120VAC INPUT, 120VAC OUTPUT ...................................................................................................... 5 2.4. FOR 208VAC INPUT, 120VAC OUTPUT ...................................................................................................... 7
3. LAYOUT ........................................................................................................................................................ 9 4. SITE PREPARATION ............................................................................................................................... 12
4.1. DELIVERY ................................................................................................................................................. 12 4.2. INSPECTION ............................................................................................................................................... 12 4.3. STORAGE ................................................................................................................................................... 12 4.4. LOCATION ................................................................................................................................................. 13
5. INSTALLATION ........................................................................................................................................ 14 5.1. BYPASS UNIT ............................................................................................................................................ 14 5.2. TN SERIES UPS ......................................................................................................................................... 14
6. OPERATION .............................................................................................................................................. 17 6.1. SYSTEM START UP .................................................................................................................................... 17 6.2. SYSTEM SHUTDOWN – LOAD WILL LOSE POWER ....................................................................................... 18 6.3. BYPASS PROCEDURES ............................................................................................................................... 18 ENTERING BYPASS MODE .............................................................................................................................. 18 RESTORING NORMAL OPERATION .................................................................................................................. 18
7. TROUBLESHOOTING ............................................................................................................................. 19 8. CONTACT INFORMATION .................................................................................................................... 20
8.1. ADDITIONAL PURCHASES OR UPGRADES ................................................................................................... 20 8.2. QA / WARRANTY QUESTIONS ................................................................................................................... 20 8.3. SOFTWARE QUESTIONS ............................................................................................................................. 20
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 ii
1. Introduction Thank-you for choosing the Always On UPS External Bypass System. It is designed to provide a high degree of protection for the critical loads connected. This manual is a guide to installing and using the Bypass System. It includes important safety instructions for operation and correct installation. Please read this manual in its entirety before setting up, installing and powering up the equipment. Use of the external Bypass allows for maintenance or repair of the UPS system without interruption of power to the critical loads, while maintaining isolation.
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 1
2. System Diagrams Section 2.1 is for bypass systems and UPS systems configured with a 208VAC input and a 120/240VAC output. Section 2.2 is for bypass systems and UPS systems configured with a 240VAC input and a 120/240VAC output. Section 2.3 is for bypass systems and UPS systems configured with a 120VAC input and a 120VAC output. All configurations are completed at factory. If alternate configurations or required contact the factory before proceeding as reconfiguring the system will void the warranty and possible damage the system.
2.1. For 208VAC Input, 240/120VAC Output
NFB-2P2W+G
INPUT
UPS INPUT
BATTERIES
TN SERIES UPS
BYPASS
120/240VacTO LOAD3W+GN-G
BONDED
UPSELECTRONICS
OUTPUTBYPASS
UPS
BATTERY
ISO. TRANS.UTILITY
208Vac
208Vac2W+G
120/240Vac3W+G
Figure 2.1.1
Block Diagram of Bypass System
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 2
L1 L2 G
2P
240208
120
0120
00
L1
BYPASS SWITCH
L2 N
N
L1
L2
G
L1 L2 G
*N-G BONDED
*
208Vac 2W+G
120/240Vac3W+G
T1
TN SERIESUPS
ACINPUT
ACOUTPUT
RED BLK GRN
BLUE
RED
RED BLK GRN
GRN WHT BLK RED
RED
WHT
BLK
BLUE
WHT
WHTBLKRED
7
53
1
6
2
BLK
UPS INPUT
Figure 2.1.2
Wiring Diagram of Bypass Unit
208VacINPUT
L1
L2
G
B+
B-EXTERNAL
BATTERY
BATTERY
INPUT
EMI /SURGE
INTERNALBATTERIES
CHARGER
UPSELECTRONICS
SNMP OR AS400
RS-232/DRY CONTACT
EMI
MAINTBYPASSSWITCH
240208
0
12088
0120
0
L1
N
L2
120Vac
120Vac240Vac
OUTPUTTERM. BLOCK
OUTPUT
G
Figure 2.1.3 Wiring Diagram of UPS
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 3
2.2. For 240VAC Input, 240/120VAC Output
N_Series_Ext_Bypass_Manual V1.7 2012-06-12 4
NFB-2P 2W+G
INPUT
UPS INPUT
BATTERIES
TN SERIES UPS
BYPASS 120/240VacTO LOAD3W+GN-G
BONDED
UPSELECTRONICS
OUTPUTBYPASS
UPS
BATTERY
ISO. TRANS.UTILITY
240Vac
240Vac 2W+G 120/240Vac
3W+G
Figure 2.2.1 Block Diagram of Bypass System
L1 L2 G
2P
240208
120
0120
00
L1
BYPASS SWITCH
L2 N
N
L1
L2
G
L1 L2 G
*N-G BONDED
*
240Vac 2W+G
120/240Vac3W+G
T1
TN SERIESUPS
ACINPUT
ACOUTPUT
RED BLK GRN
BLUE
RED
RED BLK GRN
GRN WHT BLK RED
RED
WHT
BLK
BLUE
WHT
WHTBLKRED
7
53
1
6 2
BLK
UPS INPUT
Figure 2.2.2 Wiring Diagram of Bypass Unit
M0403_T
240Vac INPUT
L1 L2 G
B+ B- EXTERNAL
BATTERY BATTERY
INPUT EMI /
SURGE
INTERNAL BATTERIES
CHARGER
UPSELECTRONICS
SNMP OR AS400RS-232/DRY CONTACT
EMI
MAINTBYPASSSWITCH
240208
0
120 88
0 120
0
L1 N
L2
120Vac
120Vac240Vac
OUTPUTTERM. BLOCKOUTPUT
G
Figure 2.2.3
Wiring Diagram of UPS
2.3. For 120VAC Input, 120VAC Output
NFB-1P 2W+G
INPUT
UPS INPUT
BATTERIES
TN SERIES UPS
BYPASS
120Vac TO LOAD 2W+G
* N-G BONDED
UPS ELECTRONICS
OUTPUT BYPASS
UPS
BATTERY
120/120Vac
UTILITY 120Vac
240Vac 2W+G
120Vac 2W+G
TN SERIES EXT BYPASS
120/240Vac
*
Figure 2.3.1 Block Diagram of Bypass System
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 5
N_Series_Ext_Bypass_Manual V1.7 2012-06-12 6
Figure 2.3.2 Wiring Diagram of Bypass System
SNMP OR AS400
Figure 2.3.3
Wiring Diagram of UPS
240Vac INPUT
L1
L2
G
B+
B- EXTERNAL
BATTERY
BATTERY
INPUT
EMI / SURGE
INTERNAL BATTERIES
CHARGER
UPS ELECTRONICS
RS-232/DRY CONTACT
EMI
MAINT BYPASS SWITCH
240 208
0
120 88
0 120
0
L
N 120Vac
OUTPUT TERM. BLOCK
OUTPUT
G
L N G
2P
240208
120
0 120
0 0
BYPASS SWITCH
N L
N
L
G
L1 L2
*N-G BONDED
*
120 Vac 2W + G
I/P
T2
TNUP
ACINPUT
BLK WHT
RED
RED BLK
BLK
UPS INPUT
BLK120 Vac2W + GOUTPUT
SERIESS
ACOUTPUT
7 5 3 1
6
2 0 0 WHT
0DRE
110BLK
0 BLK
BLUE110
110DRET1
110 RED
BLK
BLUE
WHT RED
N. B. B.
WHT
BLK
BLK
BLK
RED
BLK
BLK
RED
RED
BLUE
M0403_T
2.4. For 208VAC Input, 120VAC Output
N_Series_Ext_Bypass_Manual V1.7 2012-06-12 7
Figure 2.4.1 Block Diagram of Bypass System
Figure 2.4.2 Wiring Diagram of Bypass System
M0403_T
3. Layout
L1AC INPUT
L2 L1 NTO UPSINPUT
L2FROM UPS
OUTPUT
L1 L2 N L1 L2GND GNDAC OUTPUT
Power Input and Output Terminal Strip + Ground Lugs
UPS Input Breaker
Maintenance Bypass Switch
5-6kVA
Figure 3.1 Back of the 6kVA Bypass Unit
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 9
L1AC INPUT
L2 L1 NTO UPSINPUT
L2FROM UPS
OUTPUT
L1 L2 N L1 L2GND GNDAC OUTPUT
Maintenance Bypass Switch
Power Input and Output Terminal Strip + Ground Lugs
8-10kVA
UPS Input Breaker
Figure 3.2
Back of the 8-10kVA Bypass Unit
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 10
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 11
12-15kVA
Figure 3.3 Back of the 12-15kVA Bypass Unit
Maintenance Bypass Switch
UPS Input Breaker
Power Input And Output Terminal Strip + Ground Lugs
4. Site Preparation
4.1. Delivery Upon receiving the Bypass Unit, inspect the packaging integrity and the physical condition of the cabinet carefully. In the event that physical damage is visible, the carrier must be informed immediately and a claim filed with them. Inform Always On as soon as the claim has been filed. A copy of the claim should be faxed to Always On at (250) 491-9775. A detailed report of the damage is necessary for carrier insurance claim.
4.2. Inspection Unpack the system carefully. Be sure to notice the packing method, and retain the box and packing material. If you must return the system at any time, you must repack it the way it was originally shipped. Visually inspect the system for damage that may have occurred during shipment. If there is damage, or anything is missing, contact the dealer from whom you purchased the unit, and save the packaging for future shipment. When the system has passed the initial inspection, record the installation date on the back panel of the unit and in the space provided towards the front of this manual. Included with Bypass System: User manual
4.3. Storage If the system is to be stored prior to installation, it should be placed in a dry area where it will not be exposed to dirt, moisture or other contaminants. Extreme storage temperatures are: -30ºC to +60ºC
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 12
4.4. Location The Bypass System is intended for installation in a temperature-controlled indoor area, free of conductive contaminants. Qualified individuals should conduct installation. Below is an example of one installation.
BATTERYPACK
"On"Always
Figure 4.1 Typical System Layout - Front View
N_Series_Ext_Bypass_Manual V1.7 2012-06-12 13
Figure 4.2 Typical System Layout - Rear View
M0403_T
5. Installation WARNING! The Bypass system should be installed by a qualified technician or personnel and wired in accordance with local and national electrical codes. Be sure the polarities and voltage match the rating of the unit. Check that the loads being protected are within the capacity of the system. Ensure no power has been applied to the systems and nothing has been turned on before proceeding.
5.1. Bypass Unit Note: All connections are available at the rear of the Bypass unit, See Figure 3.2 For a detailed wiring diagram, See Figure 5.1
1. Connect the critical loads to AC Output located on the Input/Output terminal block of the Bypass Unit.
2. Connect input cabling from the utility source to ‘AC Input’ located on the Input/Output terminal block of the Bypass Unit.
WARNING! Do NOT apply utility at this time. WARNING! Do NOT turn ON the UPS at this time.
5.2. TN Series UPS
1. If an optional Battery Bank has been purchased, connect the Battery Bank to the UPS. Refer to the Battery Bank Operators Manual for instructions.
2. Connect input cabling from ‘To UPS AC Input’ located on the Input/Output terminal block of the Bypass Unit to the UPS input terminal block.
3. Connect the output of the TN Series UPS to ‘From UPS AC Output’ located on the Input/Output terminal block of the Bypass Unit.
WARNING! Do NOT apply utility at this time. WARNING! Do NOT turn the UPS on at this time.
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 14
N_Series_Ext_Bypass_Manual V1.7 2012-06-12 15
OUTPUT I/P L2
INPUT TN SERIES UPS
I/P L1 B- B+
EXT BATT
GND O/P L2 O/P
L1 O/P N
O/PL2
ACINPUT
I/PL1
I/PL2
O/P N O/P
L1 GND
TO UPS AC INPUT
N I/P L2 I/P
L1 O/PL2
O/PL1
FROM UPS AC OUTPUT AC
OUTPUT
GND
INPUTUTILITY
L1GND L2 N TO LOAD
L1 L2
BYPASS UNIT
GND
TO OPTIONAL BATTERY CABINET(S)
B+ B-
Figure 5.1
External Wiring Diagram for the 208VAC and 240VAC system
120 VAC OUTPUT
I/P L2
240 VAC INPUT
TN SERIES UPS
I/P L1 B- B+
EXT BATT
GND O/P L O/P
N
ACINPUT
I/PL
I/PN
O/P N O/P
L1GND
240 VACTO UPS
AC INPUT
I/P N
I/P L O/P
L2O/PL1
120 VAC FROM UPS AC OUTPUT AC
OUTPUT
GND
120 Vac INPUTUTILITY
LGND N N TO LOAD120 VAC
L1
BYPASS UNIT
TO OPTIONAL BATTERY CABINET(S)
B+ B- GND
Figure 5.2 External Wiring Diagram for the 120VAC systems
M0403_T
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 16
Figure 5.3 External Wiring Diagram for the 208//120VAC systems
6. Operation 6.1. System Start Up
1. Ensure that all connections are secure and correct as per Installation Instructions.
2. Confirm that the Bypass Switch on the UPS is in the INV position. 3. Confirm that the Bypass Switch on the Bypass Unit is in the INV
position. 4. Confirm that the Battery Breaker on the UPS is in the OFF position. 5. Confirm that the Input Breaker on the UPS is in the OFF position. 6. Confirm that the UPS Input Breaker on the Bypass Unit is in the OFF
position. 7. Remove the cover plate on any Battery Cabinets (if applicable). 8. Switch all Battery Breakers on the Battery Cabinets to the ON position
(if applicable). 9. Switch the Battery Breaker on the UPS to the ON position. 10. Apply utility power to the system. 11. Switch the UPS Input Breaker on the Bypass Unit to the ON position. 12. Switch the Input Breaker on the UPS to the ON position. The UPS will enter Stand-By Mode. The LCD will become illuminated, and fans will start. 13. Press the ON/OFF Button on the front panel of the UPS to turn it ON
(hold the ON/OFF Button for 3 seconds or until the UPS beeps and displays “Ready On”).
The UPS will automatically perform a self-test and then go to line mode. 14. Turn on loads sequentially as required.
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 17
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 18
6.2. System Shutdown – Load will lose power 1. Turn off loads sequentially as required. 2. Press the ON/OFF Button on the front panel of the UPS to turn it OFF
(hold the ON/OFF Button for 5 seconds or until the UPS beep stops and the LCD displays “Shutdown”). The UPS will shutdown. The LCD will display “UPS Off” for a few seconds and then switch to Stand-By Mode.
3. Switch the Input Breaker on the UPS to the OFF position, and wait 10 seconds before proceeding. The UPS will fully shutdown. The fans will stop, and the LCD will extinguish.
4. Switch the Battery Breaker on the UPS to the OFF position. 5. Switch the Battery Breakers on any attached Battery Cabinets to the
OFF position (if applicable). 6. Switch the UPS Input Breaker on the Bypass Unit to the OFF
position. 7. Remove utility power from the system.
The System is now completely shutdown.
6.3. Bypass Procedures This Bypass System provides the user with the ability to isolate the UPS from the utility power without disrupting power to the load. The UPS can be completely shutdown and even removed so that maintenance can be performed safely, without the load experiencing any downtime. Caution: Only operate the Bypass switch on the Bypass Unit when the UPS is in MAINTENANCE BYPASS mode.
Entering Bypass Mode
1. Put the UPS into Maintenance Bypass Mode by following the instructions found in the UPS Operators Manual.
2. Turn the Bypass Switch on the Bypass Unit to the BYPASS position. 3. Switch the UPS Input Breaker on the Bypass Unit to the OFF position. The UPS is now isolated from utility.
Restoring Normal Operation
1. Ensure the UPS is in MAINTENANCE BYPASS mode. 2. Switch the UPS Input Breaker on the Bypass Unit to the ON position. 3. Turn the Bypass Switch on the Bypass Unit to the NORMAL position. 4. Put the UPS into Normal Operation by following the instructions found in
the UPS Operators Manual. The system is now operating in Normal Mode.
7. Troubleshooting Problem Possible Cause Action to Take Cannot be switched to Bypass Mode
Utility not available at input of bypass system
• Confirm Utility supply and connection.
Cannot be switched to UPS Mode
UPS power not available • Confirm UPS supply and connection
Caution: Only operate the Bypass switch when the UPS is in MAINTENANCE BYPASS mode.
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 19
8. CONTACT INFORMATION
8.1. Additional Purchases or Upgrades Always On UPS Systems Inc. Bldg 1 – 150 Campion Road, Kelowna, BC, Canada, V1X 7S8 Phone: (250) 491-9777 Ext 451 Fax: (250) 491-9775 Email: [email protected] Website: www.alwayson.com
8.2. QA / Warranty Questions
Always On UPS Systems Inc. Bldg 1 – 150 Campion Road, Kelowna, BC, Canada, V1X 7S8 Phone: (250) 491-9777 Ext 209 Fax: (250) 491-9775 Email: [email protected] Website: www.alwayson.com
8.3. Software Questions
Always On UPS Systems Inc. Bldg 1 – 150 Campion Road, Kelowna, BC, Canada, V1X 7S8 Phone: (250) 491-9777 Ext 204 Fax: (250) 491-9775 Email: [email protected] Website: www.alwayson.com
M0403_TN_Series_Ext_Bypass_Manual V1.7 2012-06-12 20