Operation and Maintenance Manual

Upload: vonguyet

Post on 11-Jul-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

Operation and Maintenance Manual

9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

TTAABBLLEE OOFF CCOONNTTEENNTTSS

Warnings ............................................................................. 1 General Guidelines ............................................................. 2 Firmware Version ............................................................... 2 Environmental Conditions .................................................. 2 Electrical Specifications ...................................................... 2 NSF Suggested Operation Ranges ...................................... 3 Applicable Sensor Operation Ranges ................................. 3 Section A: Programming the Controller ............................ 4 

A – 1: Controller Options .............................................. 4 A – 2: The Program Menu ............................................. 4 

A – 2.1: Entering the Program Menu ......................... 4 A – 2.2: Selecting Language ...................................... 4 A – 2.3: pH High Alarm Point ................................... 4 A – 2.4: pH Low Alarm Point .................................... 4 A – 2.5: ORP High Alarm Point ................................ 4 A – 2.6: ORP Low Alarm Point ................................. 5 A – 2.7: Temperature High Alarm Point .................... 5 A – 2.8: Temperature Low Alarm Point .................... 5 A – 2.9: ORP/ppm Set point ...................................... 5 A – 2.10: ppm High Alarm ........................................ 5 A – 2.11: ppm Low Alarm ......................................... 5 A – 2.12: Exiting the Menu ........................................ 5 

Section B: Normal Operation ............................................. 6 B – 1: Set points ............................................................. 6 

B – 1.1: Displaying the Set points .............................. 6 B – 1.2: Modifying the Set points .............................. 6 

B – 1.2.1: pH Set Point .......................................... 6 B – 1.2.2: Chlorine Set Point ................................. 6 

B – 1.2.2.1: ORP Control ................................... 6 B – 1.2.2.2: ppm Control (Calculated) ............... 6 B – 1.2.2.3: ppm Control (Probe) ....................... 6 

B – 1.2.3: Booster Trigger Point ............................ 6 B – 1.2.4: Booster End Point .................................. 6 

B – 2: Single Point Calibration ...................................... 7 B – 2.1: Single Point Calibration - pH ....................... 7 B – 2.2: Single Point Calibration - Temp ................... 7 B – 2.3: Single Point Calibration – ppm .................... 7 

B – 2.3.1: Calculated ppm ...................................... 7 B – 2.3.2: ppm Probe ............................................. 7 

B – 2.4: Probe Error ................................................... 7 B – 3: Alarms ................................................................. 7 

B – 3.1: pH High/Low alarms .................................... 7 B – 3.2: ORP High/Low alarms ................................. 7 B – 3.3: ppm High/Low alarms .................................. 7 B – 3.4: Temperature High/Low alarms .................... 7 B – 3.5: No Flow Alarm............................................. 8 B – 3.6: Flow Restored Delay .................................... 8 B – 3.7: Cl/Br Lockout ............................................... 8 B – 3.8: pH Failsafe ................................................... 8 B – 3.9: Cl/Br Failsafe ............................................... 8 B – 3.10: Booster FAILSAFE .................................... 8 

B – 4: Resetting a Failsafe Alarm .................................. 8 Section C: Using the BECSysRCM3 ................................. 9 

C – 1: Monitoring a Controller ....................................... 9 C – 2: Downloading Data Logs ...................................... 9 

C – 2.1: Using a Flash Drive .................................... 10 C – 2.1.1: Importing Data Logs ............................ 11 

C – 3: Viewing Data Logs ............................................ 11 Section D: Troubleshooting .............................................. 12 

D – 1: BECSys3 ........................................................... 12 D – 1.1: Probe Error ................................................. 12 

D – 2: BECSysRCM3................................................... 12 D – 2.1: Problems Using A Flash Drive ................... 12 D – 2.2: Text Message Call-Out Test ....................... 12 

Section E: Maintenance .................................................... 13 E – 1: Potentiometric Sensors (pH and ORP) ............... 13 

E – 1.1: Electrode Cleaning: ..................................... 13 E – 1.2: Long-Term Storage: .................................... 13 

E – 2: CCS140 Free Chlorine Sensor ........................... 13 E – 2.1: Cleaning ...................................................... 13 E – 2.2: Long-Term Storage ..................................... 13 E – 2.3: Filling electrolyte ........................................ 13 

Section F: Feed Charts ..................................................... 14 F – 1: Spa Feed Charts ................................................. 14 F – 2: Pool Feed Charts ................................................ 15 

Section G: Installation Diagrams ...................................... 16 G – 1: Pressure Filter Installation ................................. 16 G – 2: Vacuum Filter Installation ................................. 16 

Section H: Replacement Parts .......................................... 17 Section I: Warranty .......................................................... 18 

Page 1 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

Warnings

Pay particular attention to the following warnings encountered in the pages of the BECSys3 Operation and Maintenance Manual:

Warning: Various other warning boxes may be found throughout the manual text.

Caution: Various other caution boxes may be found throughout the manual text.

Page 2 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

General Guidelines

Proper installation and use of the BECSys controller depends on the specific needs of the application. Read the manual completely before starting the installation and ensure all guidelines and recommendations are followed. All components should be mounted and the flow cell plumbing installed and pressure tested before wiring the controller. Ensure compliance with all applicable plumbing and electrical codes during the installation as well.

Firmware Version

This manual was written for firmware v2.08 & v2.09. If you received newer firmware but did not receive a copy of the manual covering that version of firmware, please contact your distributor.

Environmental Conditions

The BECSys3 is housed in a NEMA 4X (IP65) enclosure. It should not be used in explosive environments. The BECSys3 should be mounted so that adequate ventilation is provided around the enclosure, preventing general environmental specifications from being exceeded (see table below).

Environmental SpecificationsSpecification RatingStorage Temperature -30 to 60 Deg CAmbient Operating Temperature -18 to 40 Deg CAmbient Humidity 95% non condensing maximum humidity

Electrical Specifications

The BECSys3 may be ordered in either an 115VAC model or a 230VAC model. Following are the electrical specifications for each model:

Controller Ratings 115VAC Model 230VAC Model Voltage: 115VAC 60Hz 230VAC 50Hz Phase: Single SingleCurrent: 9.25 Amps Full Load 4.625 Amps Full Load

(¼ Amp – Controller) (⅛ Amp – Controller) (9 Amps – Relay Outputs, 3A X 3) (4.5 Amps – Relay Outputs, 1.5A X 3)

Relay Output Ratings

115VAC Model 230VAC Model Relay 1 (K1) 115VAC (max) – 3 Amps 250VAC (max) – 1.5 Amps Relay 2 (K2) 115VAC (max) – 3 Amps 250VAC (max) – 1.5 Amps Relay 3 (K3) 115VAC (max) – 3 Amps 250VAC (max) – 1.5 Amps

Caution: The BECSys controller should not be installed where it is accessible to the public.

Caution: The BECSys controller should be sealed while under operation. All IO, power cables, and unused ports must be sealed using hardware rated NEMA4 or better. Damage to the controller caused by improper

sealing of the enclosure is not covered under warranty.

Page 3 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

NSF Suggested Operation Ranges

ORP 650mV to 850mVpH 6.8 to 8.2Free Available 0 to 10 ppmChlorine

Applicable Sensor Operation Ranges

Standard SensorspH 0.0 to 14.0 pHReed Flow Switch Switch Point (On): 2.0 gpmRotary Flow Switch Switch Point (On): 1.5 gpm

Optional SensorsTemperature 32°F to 212°F (0°C to 100°C)ORP -1500mV to 1500mVAmperometric ppm 0 ppm to 20 ppm

Page 4 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

Section A: Programming the Controller

A – 1: Controller Options Depending on how a particular controller is configured, not all of the options listed in this manual may be available.

If your controller is configured to monitor Free Cl, it may be either calculated or a probe may be attached.

A – 2: The Program Menu

A – 2.1: Entering the Program Menu To enter the program menu, press and hold both the Cal and Up key for three seconds. At the end of three seconds, one of two things will happen.

If access codes have been set, the unit will prompt you for an access code. Use the Arrow keys to change the current digit, and press the Set Points key to go to the next digit. Press the Enter key when you have finished entering your code. Once the access code has been entered, the controller will either display the first menu item or display "Access denied" if the code you entered is invalid.

When the LCD screen clears, release the keys and “Program Menu” should appear at the top of the display.

Once in the program menu, use the Arrow keys to scroll to the setting you wish to change. Press the Enter key to select the setting, and then use the Arrow keys to modify the value. Press the Enter key again to enter the new value and return to the menu. To exit the program menu, scroll to the “Exit menu” option and press the Enter key.

NOTE: After five minutes of no programming

activity, the Time-Out feature will automatically exit the programming menu.

A – 2.2: Selecting Language

The BECSys3 can be programmed to display in three different languages. Pressing the Enter key will display “Modify Value” and the current selected language. Use the Arrow keys to select between ENG (English), ESP (Spanish), and FRA (French), and press the Enter key to select the language you would like to use for the display.

A – 2.3: pH High Alarm Point

Pressing the Down Arrow displays pH High Alarm followed by the current pH high alarm point. To change this setting, press the Enter key, use the Arrow keys to input the value you would like, and then press the Enter key again to save the new value.

A – 2.4: pH Low Alarm Point

Pressing the Down arrow displays pH Low Alarm followed by the current pH low alarm point. To change this setting, press the Enter key, use the Arrow keys to input the value you would like, and then press the Enter key again to save the new value.

A – 2.5: ORP High Alarm Point

Pressing the Down arrow displays ORP High Alarm followed by the current ORP high alarm point. To change this setting, press the Enter key, use the Arrow keys to input the value you would like, and then press the Enter key again to save the new value.

Caution: Amperometric chlorine sensors require the use of a temperature sensor and a properly calibrated pH sensor. Refer to the instruction pamphlet included with the

sensor at the time of installation.

Page 5 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

A – 2.6: ORP Low Alarm Point

Pressing the Down arrow displays ORP Low Alarm followed by the current ORP low alarm point. To change this setting, press the Enter key, use the Arrow keys to input the value you would like, and then press the Enter key again to save the new value.

A – 2.7: Temperature High Alarm Point

Pressing the Down arrow displays Temp High Alarm followed by the current temperature high alarm point. To change this setting, press the Enter key, use the Arrow keys to input the value you would like, and then press the Enter key again to save the new value.

A – 2.8: Temperature Low Alarm Point

Pressing the Down arrow displays Temp Low Alarm followed by the current temperature low alarm point. To change this setting, press the Enter key, use the Arrow keys to input the value you would like, and then press the Enter key again to save the new value.

A – 2.9: ORP/ppm Set point

This option is only shown if the controller is configured for ppm control. Pressing the Down arrow displays ORP/ppm SP followed by the current setting. This option selects whether to use an ORP set point or a ppm set point for the main Cl/Br feed control. It is set to ORP by default. To change this setting, press the Enter key, use the Arrow keys to change between ORP and ppm, and then press the Enter key again to save the new value.

A – 2.10: ppm High Alarm

This option is only shown if the controller is configured for ppm control. Pressing the Down arrow displays ppm High Alarm. If the controller is configured with a ppm probe, the current ppm high alarm point will be displayed on the screen. If the controller is using calculated ppm, the current ppm high alarm point will be displayed using the LEDs. To change this setting, press the Enter key, use the Arrow keys to input the value you would like, and then press the Enter key again to save the new value.

A – 2.11: ppm Low Alarm

This option is only shown if the controller is configured for ppm control. Pressing the Down arrow displays ppm Low Alarm. If the controller is configured with a ppm probe, the current ppm low alarm point will be displayed on the screen. If the controller is using calculated ppm, the current ppm low alarm point will be displayed using the LEDs. To change this setting, press the Enter key, use the Arrow keys to input the value you would like, and then press the Enter key again to save the new value.

A – 2.12: Exiting the Menu

Pressing the down arrow displays Exit menu. Pressing the Enter key exits the menu.

Page 6 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

Section B: Normal Operation

B – 1: Set points B – 1.1: Displaying the Set points

To display the set points, press the Set Points key briefly. The set points will be displayed for three seconds.

B – 1.2: Modifying the Set points To modify the set points press the Set Points key for three seconds. If the access codes have been set, the unit will prompt you for your access code, otherwise the display will change to pH Set Point followed by the current pH set point. For help entering your access code, see A - 1.1: Entering the Program Menu.

B – 1.2.1: pH Set Point

To change the pH Set Point, press the Enter key to enter the menu. Use the Arrow keys to input the desired value and then press the Enter key to save the value.

B – 1.2.2: Chlorine Set Point

B – 1.2.2.1: ORP Control

This option is shown if your controller is configured to use ORP as the Set point. The screen will display ORP Set Point followed by the current ORP set point. To change this setting, press the Enter key to enter the menu. Use the Arrow keys to input the new value and then press the Enter key to save the value.

B – 1.2.2.2: ppm Control (Calculated)

This option is only shown if the controller is configured for calculated ppm. The screen will display ppm Set Point and the current ppm set point on the LED bar graph will be flashing (the high and low alarms will be displayed by red LEDs). To change the calculated ppm set point, press the Enter key. Use the Arrow keys to adjust the value shown on the LED bar graph and press the Enter key to save the new value.

B – 1.2.2.3: ppm Control (Probe)

This option is only shown if the controller is configured for a ppm Probe. The screen will display ppm Set Point and the current ppm set point. To change the ppm set point, press the Enter key. Use the Arrow keys to adjust the value shown and press the Enter key to save the new value.

B – 1.2.3: Booster Trigger Point This option is only shown if your controller is configured for Cl/Br Booster feed. If relay 3 is configured for Cl/Br Booster control, the screen will display the current trigger point. To change this setting, press the Enter key. Use the Arrow keys to input the new value, and then press the Enter key to save the value.

B – 1.2.4: Booster End Point This option is only shown if your controller is configured for Cl/Br Booster feed. If relay 3 is configured for Cl/Br Booster control, the screen will display the current booster end point. To change this setting, press the Enter key. Use the Arrow keys to input the new value, and then press the Enter key to save the value.

Page 7 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

B – 2: Single Point Calibration To enter the calibration menu, press and hold the Cal key for three seconds. If the access codes have been set, the unit will prompt you for your access code, otherwise the display clears followed by Cal pH and the current pH reading. For help entering your access code, see A - 1.1: Entering the Program Menu. B – 2.1: Single Point Calibration - pH

The display should now read Cal pH followed by the current pH reading. To calibrate the pH, press the Enter key. Use the Arrow keys to adjust the displayed value to match your test kit reading, and then press the Enter key to save it.

B – 2.2: Single Point Calibration - Temp

This is only shown if the controller is configured to monitor temperature. Pressing the Down arrow key, the display will show Cal Temp followed by the current Temp reading. To calibrate the temperature, press the Enter key. Use the Arrow keys to adjust the displayed value to the measured value then press the Enter key to save it.

B – 2.3: Single Point Calibration – ppm

B – 2.3.1: Calculated ppm

This is only shown if the controller is configured for calculated ppm. Pressing the Down arrow key, the display will show Cal ppm and the ppm LED's will be flashing. To calibrate the ppm, press the Enter key. Use the Arrow keys to adjust the LED bar graph to match your test kit reading, and then press the Enter key to save the value.

B – 2.3.2: ppm Probe

This is only shown if the controller is configured for a ppm probe. Pressing the Down arrow key, the display will show Cal ppm followed by the current ppm reading. To calibrate the ppm, press the Enter key. Use the Arrow keys to adjust the displayed value to match your test kit reading, and then press the Enter key to save the value.

B – 2.4: Probe Error

Probe error indicates the value attempting to be calibrated is out of range. Contact your distributor for assistance.

B – 3: Alarms

During normal operation, the following alarms may be displayed. Some alarms will not be shown depending on the system's configuration. B – 3.1: pH High/Low alarms

This is displayed when the pH input has risen above/fallen below the pH high/low alarm point. These alarms will also trigger the Cl/Br Lockout alarm.

B – 3.2: ORP High/Low alarms These alarms are displayed if the controller is configured for ORP. This is displayed when the ORP input has risen above/fallen below the ORP high/low alarm point.

B – 3.3: ppm High/Low alarms These alarms are displayed if the controller is configured for ppm. This is displayed when the ppm input has risen above/fallen below the ppm high/low alarm point.

B – 3.4: Temperature High/Low alarms

These alarms are displayed when the controller is configured to monitor temperature. This is displayed when the Temperature input has risen above/fallen below the Temperature high/low alarm point.

Page 8 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

B – 3.5: No Flow Alarm This is displayed when the controller does not detect a flow signal. This alarm disables all chemical feeds.

B – 3.6: Flow Restored Delay This is displayed when flow is disrupted and then restored. The BECSys3 will delay restarting feeds for a programmed duration in order to prevent operating feeds based on readings from stagnant water.

B – 3.7: Cl/Br Lockout This is triggered whenever there is a pH high or low alarm. This message indicates that the Cl/Br feed (relay 2) and the optional Cl/Br Booster (relay 3) are disabled in order to prevent the Cl/Br feeds from driving the pH even further out of range.

B – 3.8: pH Failsafe This is displayed when the active pH feed (feed up or feed down) attempted to feed continuously for the selected failsafe duration. The active pH feed is disabled until one of the following conditions occurs: 1) The pH input reaches the programmed set

point. 2) Disruption of flow 3) User manually resets the failsafe.

B – 3.9: Cl/Br Failsafe

This is displayed when the Cl/Br feed attempted to feed continuously for the selected failsafe duration. The Cl/Br feed is disabled until one of the following conditions occurs: 1) The ORP/ppm input reaches the

programmed set point. 2) Disruption of flow 3) User manually resets the failsafe.

B – 3.10: Booster FAILSAFE This is displayed when the optional Cl/Br Booster feed attempted to feed continuously for the selected failsafe duration. The Cl/Br Booster feed is disabled until one of the following conditions occurs: 1) The ORP input reaches the Cl/Br Booster set

point. 2) Disruption of flow 3) User manually resets the failsafe.

B – 4: Resetting a Failsafe Alarm

To reset a failsafe alarm, press and hold the Up and Down arrow keys momentarily.

Page 9 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

Section C: Using the BECSysRCM3

C – 1: Monitoring a Controller The BECSysRCM3 maintains a connection to all of the BECSys2/BECSys3 controllers attached to it. By connecting to the BECSysRCM3, you may monitor any of the BECSys2/BECSys3 controllers attached to the BECSysRCM3. To monitor a particular controller, select the controller number from the left hand side of the menu tree. Here you can see information on the controller including the Product Number, Serial Number, and the Controller Name if it was provided. From here you can also view and change the controller settings including Set Points, Alarm Points, etc. You can also view the current state of the relay outputs.

C – 2: Downloading Data Logs The BECSysRCM3 allocates space for downloading data at midnight each day. If a controller is added during the day, logs will not be stored until midnight when the space is allocated. The BECSysRCM3 collects and stores data from the controllers that are connected to it. BECSys for Windows is used to view this data. To download the data logs, you may either download the site (as you would for a controller) using BECSys for Windows, or use a Flash Drive and import the data logs into BECSys for Windows later.

Page 10 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

C – 2.1: Using a Flash Drive Using the Flash Drive allows you to download the logs without having to go to a PC or connect with a Laptop. Plug your Flash Drive into the USB cable on the BECSysRCM3.

As soon as the Flash Drive is connected, the data transfer will start. There are three LEDs located on the side of the BECSys3 controller which indicate the transfer status.

The Flash Activity LED should be blinking any time there is data transfer between the Flash Drive and the BECSysRCM3. Once transfer is completed, either the Success (green) LED or the Error (red) LED should be illuminated. If the Error LED is illuminated, unplug the Flash Drive and then plug it in again. This will start the data transfer again. If the Error LED is illuminated again, there is some problem with the Flash Drive. The Flash Drive may be full or the BECSysRCM3 may not recognize it – see the troubleshooting section for more information on how to resolve this. Once the data transfer has been successful, take the Flash Drive to your PC and plug it in. Windows should recognize the Flash Drive and install drivers if necessary.

Page 11 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

C – 2.1.1: Importing Data Logs You may import the data logs from your Flash Drive into an existing BECSysRCM3 site, or a new site (the data logs will not import into any other sites). Select the site you wish to import the data logs into. Right click on the desired site and select “Import History File”. Once the data logs have been imported you may view them. If there were data logs previously downloaded, the new information will be added to those.

C – 3: Viewing Data Logs To view the data logs, select the BECSysRCM3 site from the list on the left and select “View Logs” from the buttons at the top. If this is the first time you have viewed the logs for this site, there will be a blank graph displayed. In order

to view the site data, you will need to configure the graph. Select the Graph Configuration button from the top of the window.

Under the Controller you can select which controller you want to graph including the BECSysRCM3 itself. Traces allow you to select what to show on the graph. Events are displayed below the graph.

Once you have selected which Traces and Events to display for the selected Controller, click the “OK” button, the graph will redraw adding the traces. The events will be displayed at the bottom of the screen. See the BECSys for Windows Manual (installed with BECSys for Windows) for more information.

Page 12 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

Section D: Troubleshooting

D – 1: BECSys3 D – 1.1: Probe Error

Probe error indicates the value attempting to be calibrated is out of range. Contact your distributor for assistance.

D – 2: BECSysRCM3 D – 2.1: Problems Using A Flash Drive If you have problems using a Flash Drive with the BECSysRCM3, make sure it is formatted either in the FAT or FAT 32 File System. To determine what File System the Flash Drive is formatted in, insert the Flash Drive in a PC. Once Windows has detected and assigned a drive letter to the Flash Drive, open Windows Explorer and find the drive letter assigned to the Flash Drive. Right click on the drive letter and select properties. A window will appear similar to the one below.

Next to File system should be listed either FAT or FAT32. If the Flash Drive is formatted using a different File System, it must be re-formatted before being used on the BECSysRCM3. To format a Flash Drive, right click on the Flash Drive in Windows Explorer and select Format. A window similar to the one shown below should appear:

Change the File System by clicking on the down arrow on the right hand side of the drop down menu for File System. Select either FAT or FAT32. Next check the Quick Format box at the bottom. Then click the Start button at the bottom of the screen. After a few minutes, a Format Complete window should appear. Click OK and close out the Format window. The Flash Drive is now configured for the proper File System for the BECSysRCM3.

D – 2.2: Text Message Call-Out Test

The BECSysRCM will not send out a test text message unless there is something to send. In order for a test message to be sent, an alarm must be generated (no flow for example).

Page 13 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

Section E: Maintenance

The BECSys3 requires no maintenance other than a periodic calibration check and sensor cleaning. E – 1: Potentiometric Sensors (pH and ORP)

E – 1.1: Electrode Cleaning: Slow response time and large offsets may indicate the electrode has become coated. The nature of the coating will dictate the type of cleaning technique that should be used. Soft coatings, like bacterial films, are best removed

using a squirt bottle or the water jet from a faucet. If this is not successful, then gently wipe with a soft wet cloth.

For a more severe coating, first try a strong detergent (something similar to Dawn liquid detergent) and warm water, using a soft brush (like a toothbrush). Isopropyl alcohol on a Q-tip is another good choice. Rinse the measuring end in distilled water before reinstallation.

Greasy and oily coatings are best removed with a detergent solution or a solvent that will not attack the sensor body. Methanol and isopropyl alcohol are good choices for solvents. Acetone, MEK, THF, or trichloroethane will irreparably harm the electrode.

Hard coatings, like calcium or lime scale, are best removed with a solvent appropriate for the particular coating. A 5% solution of hydrochloric acid (HCl) would be a good choice for calcium scale. If unsure of the proper solvent to remove a hard mineral coating, then alternate between a 5% hydrochloric acid and a 4% sodium hydroxide (NaOH) for 10 minutes each. After treating the electrode with these strong acids or bases, rinse the electrode with water and soak it in a pH 4 buffer for at least 1/2 hour.

The platinum tip of an ORP sensor can be cleaned with an abrasive as a last resort. Gently scour the platinum with a 600 grit wet emery cloth, or preferably, a 1-3 micron alumina polishing powder.

E – 1.2: Long-Term Storage:

Save the wetting cap that came with the sensor for long-term storage. After removing the sensor from the flow-cell, clean it as in routine maintenance, and then store it in the wetting cap

using a pH 4 buffer saturated with potassium chloride (KCl). The potassium chloride will prevent electrolyte from leaching out of the sensors reference cell. The wetting cap only needs to be half full. If a number of sites are going to be serviced, for example, at the end of a season, then it might be a good idea to carry a pint of 4.0/KCl storage solution.

E – 2: CCS140 Free Chlorine Sensor Check the sensor measurement at regular intervals (at least once a month), and perform a recalibration if necessary. As a rule of thumb, refill the measuring cell with electrolyte once per season (or every 12 months). E – 2.1: Cleaning

If the sensor membrane is visibly soiled, then remove the sensor from the flow cell and clean the membrane with a gentle water jet, or soak the membrane for a few minutes in a 1% to 10% hydrochloric acid (HCl) solution. Avoid chemical additives as they may damage the membrane.

Replace a heavily soiled or damaged membrane. E – 2.2: Long-Term Storage

Save the yellow protective cap that came with the sensor for long-term storage. After removing the sensor from the flow cell, empty the measuring cell of electrolyte (particularly if dehydration of the membrane is possible). Rinse the measuring chamber and electrode shaft with cold water and let them dry. Then screw the measuring cell down loosely and not to the stop, so that the membrane remains unstressed. When the sensor is put back into service, it will have to be refilled with electrolyte and run through an initial polarization before calibration.

E – 2.3: Filling electrolyte

Unscrew the measuring chamber from the shaft.

Hold the measuring chamber at an angle and fill with approximately 7 to 8 ml electrolyte, up to approximately 1 cm under the top edge.

Tap the filled chamber several times on a flat surface to release any air bubbles. Screw the electrode shaft into the measuring chamber vertically from above, displacing all air from inside. Tighten slowly to the stop.

Warning: You may lightly blot the water On a pH sensor tip on a paper towel, but never vigorously rub or wipe the pH bulb because this may scratch the delicate outer layer on the pH

glass impairing its response.

Page 14 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

Section F: Feed Charts

Use the charts on the following pages to determine the correct amount of chemical to add to spa or pool water to achieve desired conditions. Choose which chart to use by the chemical indicated and the number of gallons to be treated. F – 1: Spa Feed Charts

Quantity of Muriatic Acid Needed to Lower Total Alkalinity

Desired Decrease In ppm

Gallons in Spa

100 150 250 500 750 1000 10 1.25 ts 2.00 ts 1.00 tb 2.00 tb 3.00 tp 0.25 cp20 2.50 ts 4.00 ts 2.00 tb 0.25 cp 0.33 cp 0.50 cp30 1.25 tb 2.00 tb 3.00 tb 0.33 cp 0.67 cp 0.75 cp40 5.00 ts 2.50 tb 0.25 cp 0.50 cp 0.75 cp 1.00 cp50 2.00 tb 3.00 tb 5.00 tb 0.67 cp 1.00 cp 1.33 cp60 2.50 tb 0.25 cp 0.33 cp 0.75 cp 1.00 cp 1.50 cp70 3.00 tb 0.25 cp 0.50 cp 1.00 cp 1.33 cp 1.75 cp80 3.50 tb 0.33 cp 0.50 cp 1.00 cp 1.50 cp 2.00 cp90 0.25 cp 0.33 cp 0.67 cp 1.00 cp 1.67 cp 2.33 cp100 0.25 cp 0.50 cp 0.67 cp 1.33 cp 2.00 cp 2.50 cp

ts = teaspoon tb = tablespoon cp = one cup (8 fl oz)

Quantity of Sodium Bisulfate Needed to Lower Total Alkalinity

Desired Decrease In ppm

Gallons in Spa

100 150 250 500 750 1000 10 1.50 ts 2.50 ts 1.00 tb 2.50 tb 0.25 cp 0.33 cp 20 1.00 tb 1.50 tb 2.50 tb 0.33 cp 0.50 cp 0.67 cp 30 1.50 tb 2.50 tb 0.25 cp 0.50 cp 0.75 cp 1.00 cp 40 2.00 tb 3.00 tb 0.33 cp 0.67 cp 1.00 cp 1.25 cp 50 2.50 tb 0.25 cp 0.50 cp 0.75 cp 1.25 cp 1.50 cp 60 3.00 tb 4.50 tb 0.50 cp 1.00 cp 1.50 cp 2.00 cp 70 0.25 cp 0.33 cp 0.50 cp 1.00 cp 1.67 cp 2.25 cp 80 0.25 cp 0.33 cp 0.67 cp 1.25 cp 2.00 cp 2.50 cp 90 0.33 cp 0.50 cp 0.75 cp 1.50 cp 2.25 cp 3.00 cp 100 0.33 cp 0.50 cp 0.75 cp 1.67 cp 2.50 cp 3.25 cp

ts = teaspoon tb = tablespoon cp = one cup (8 fl oz)

Quantity of Bicarbonate of Soda Needed to Raise Total Alkalinity

Desired Increase In ppm

Gallons in Spa

100 150 250 500 750 1000 10 1.25 ts 2.00 ts 4.00 ts 2.50 tb 0.25 cp 0.33 cp 20 1.00 tb 1.50 tb 2.50 tb 5.00 tb 0.50 cp 0.50 cp 30 1.50 tb 2.00 tb 3.50 tb 0.50 cp 0.67 cp 1.00 cp 40 2.00 tb 3.00 tb 0.33 cp 0.50 cp 1.00 cp 1.00 cp 50 2.50 tb 3.50 tb 6.00 tb 0.75 cp 1.00 cp 1.50 cp 60 3.00 tb 0.25 tb 0.50 cp 1.00 cp 1.33 cp 1.75 cp 70 3.50 tp 0.35 cp 0.50 cp 1.00 cp 1.50 cp 2.00 cp 80 0.25 cp 0.33 cp 0.50 cp 1.25 cp 1.75 cp 2.50 cp 90 0.33 cp 0.50 cp 0.67 cp 1.33 cp 2.05 cp 2.75 cp 100 0.33 cp 0.50 cp 0.75 cp 1.50 cp 2.25 cp 3.00 cp

ts = teaspoon tb = tablespoon cp = one cup (8 fl oz)

Quantity of Calcium Chloride Needed to Increase Calcium Hardness

Desired Increase In ppm

Gallons in Spa

100 150 250 500 750 1000 10 1.25 ts 2.00 ts 1.00 tb 2.00 tb 3.00 tb 0.25 cp 20 2.50 ts 4.00 ts 2.00 tb 0.25 cp 0.33 cp 0.50 cp 30 1.25 tb 2.00 tb 3.00 tb 0.33 cp 0.67 cp 0.75 cp 40 4.00 ts 2.50 tb 0.25 cp 0.50 cp 0.75 cp 1.00 cp 50 2.00 tb 3.00 tb 5.00 tb 0.67 cp 1.00 cp 1.33 cp 60 2.50 tb 0.25 cp 0.33 cp 0.75 cp 1.00 cp 1.50 cp 70 3.00 tp 0.25 cp 0.50 cp 1.00 cp 1.33 cp 1.75 cp 80 3.50 tp 0.25 cp 0.50 cp 1.00 cp 1.50 cp 2.00 cp 90 0.25 cp 0.33 cp 0.33 cp 1.00 cp 1.67 cp 2.33 cp 100 0.25 cp 0.50 cp 0.67 cp 1.33 cp 2.00 cp 2.50 cp

ts = teaspoon tb = tablespoon cp = one cup (8 fl oz)

Quantity of Chlorine Compound Needed to Increase 1 ppm

Percent Chlorine In

Product

Gallons in Spa

100 150 250 500 750 1000 5 0.50 tb 2.00 ts 1.25 tb 2.50 tb 0.25 cp 0.33 cp 10 0.25 tb 1.00 ts 2.00 ts 1.25 tb 2.00 tb 2.50 tb 12 0.25 tb 1.00 ts 0.50 tb 1.00 tb 1.50 tb 2.00 tb 30 0.25 tb 0.33 ts 0.75 ts 1.25 ts 2.00 ts 2.50 ts 40 0.167 ts 0.25 ts 0.500 ts 1.00 ts 1.50 ts 2.00 ts 50 0.167 ts 0.25 ts 0.375 ts 0.75 ts 1.25 ts 1.50 ts 60 0.167 tb 0.200 ts 0.375 ts 0.50 ts 1.00 ts 1.25 ts 65 0.100 ts 0.167 ts 0.250 ts 0.50 ts 0.75 ts 1.00 ts

ts = teaspoon tb = tablespoon cp = one cup (8 fl oz)

Page 15 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

F – 2: Pool Feed Charts

Quantity of Muriatic Acid Needed to Lower Total AlkalinityDesired Decrease

In ppm Gallons in Pool

10,000 25,000 50,000 75,000 100,000 200,000 500,000 750,000 1,000,00010 1.30 pt 1.62 qt 3.25 qt 1.22 gl 1.62 gl 3.25 gl 8.13 gl 12.20 gl 16.25 gl20 1.30 pt 3.25 qt 1.62 gl 2.43 gl 3.25 gl 7.50 gl 16.20 gl 24.30 gl 32.50 gl30 1.95 qt 1.22 gl 2.44 gl 3.86 gl 4.98 gl 9.76 gl 24.40 gl 36.60 gl 48.80 gl40 2.80 qt 1.63 gl 3.25 gl 4.87 gl 6.50 gl 13.00 gl 32.50 gl 48.80 gl 65.00 gl50 3.25 qt 2.03 gl 4.07 gl 6.10 gl 8.14 gl 16.28 gl 40.70 gl 61.00 gl 81.40 gl60 3.90 qt 2.44 gl 4.88 gl 7.32 gl 9.76 gl 19.52 gl 48.80 gl 73.20 gl 97.80 gl70 1.14 gl 2.84 gl 5.69 gl 8.54 gl 11.38 gl 22.76 gl 56.90 gl 85.45 gl 113.80 gl80 1.30 gl 3.25 gl 6.50 gl 9.75 gl 13.00 gl 26.00 gl 65.00 gl 97.50 gl 138.00 gl90 1.48 gl 3.66 gl 7.31 gl 10.96 gl 14.82 gl 29.24 gl 73.10 gl 109.60 gl 146.20 gl100 1.63 gl 4.06 gl 8.12 gl 12.18 gl 16.24 gl 32.48 gl 81.20 gl 121.80 gl 162.40 gl120 1.96 gl 4.88 gl 9.76 gl 14.64 gl 19.52 gl 39.00 gl 97.80 gl 148.40 gl 196.20 gl150 2.44 gl 6.09 gl 12.18 gl 18.27 gl 24.40 gl 48.80 gl 121.80 gl 182.70 gl 244.00 gl200 3.25 gl 8.12 gl 18.24 gl 24.36 gl 32.50 gl 65.00 gl 162.40 gl 243.80 gl 325.00 gl

pt = one pt (16 fl oz) qt = one quart (32 fl oz) gl = one gallon (128 fl oz)

Quantity of Bicarbonate of Soda Needed to Raise Total Alkalinity

Desired Increase In ppm

Gallons in Pool10,000 25,000 50,000 75,000 100,000 200,000 500,000 750,000 1,000,000

10 1.50 lb 3.75 lb 7.50 lb 11.25 lb 15.00 lb 30.00 lb 75.00 lb 112.50 lb 150.00 lb20 3.00 lb 7.50 lb 15.00 lb 22.50 lb 30.00 lb 60.00 lb 150.00 lb 225.00 lb 300.00 lb30 4.50 lb 11.25 lb 22.50 lb 33.75 lb 45.00 lb 90.00 lb 225.00 lb 337.50 lb 450.00 lb40 6.00 lb 15.00 lb 30.00 lb 45.00 lb 60.00 lb 120.00 lb 300.00 lb 450.00 lb 600.00 lb50 7.50 lb 18.75 lb 37.50 lb 56.25 lb 75.00 lb 150.00 lb 375.00 lb 562.50 lb 750.00 lb60 9.00 lb 22.50 lb 45.00 lb 67.50 lb 90.00 lb 180.00 lb 450.00 lb 675.00 lb 900.00 lb70 10.50 lb 26.25 lb 52.50 lb 78.75 lb 105.00 lb 210.00 lb 525.00 lb 787.50 lb 1050.00 lb80 12.00 lb 30.00 lb 60.00 lb 90.00 lb 120.00 lb 240.00 lb 600.00 lb 900.00 lb 1200.00 lb90 13.50 lb 33.75 lb 67.50 lb 101.25 lb 135.00 lb 270.00 lb 675.00 lb 1012.50 lb 1350.00 lb100 15.00 lb 37.50 lb 75.00 lb 112.50 lb 150.00 lb 300.00 lb 750.00 lb 1125.00 lb 1500.00 lb

lb =pounds of dry chemical

Quantity of Calcium Chloride Needed to Increase Calcium Hardness

Desired Increase In ppm

Gallons in Pool10,000 25,000 50,000 75,000 100,000 200,000 500,000 750,000 1,000,000

lb oz lb oz lb oz lb oz lb oz lb lb oz lb oz lb10 1 4 3 2 6 4 9 6 12 8 25 62 8 93 12 12520 2 8 6 4 12 8 18 12 25 0 50 125 0 197 8 25030 3 12 9 6 18 12 28 2 37 8 75 187 8 281 4 37540 5 0 12 8 25 0 37 8 50 0 100 250 0 375 0 50050 6 4 15 10 31 4 46 14 62 8 125 312 8 468 12 62560 7 8 18 12 37 8 56 4 75 0 150 375 0 562 8 75070 8 12 21 14 43 12 65 10 87 8 175 437 8 658 4 87580 10 0 25 0 50 0 75 0 100 0 200 500 0 750 0 1,00090 11 4 28 2 56 4 84 6 112 8 225 562 8 843 12 1,125100 12 8 31 4 62 8 93 12 125 0 250 625 0 937 8 1,250150 18 12 46 14 93 12 104 10 187 8 375 937 8 1,406 4 1,875200 25 0 62 8 125 0 187 8 250 0 500 1,250 0 1,875 0 2,500

Quantity of Chlorine Compound Needed to Increase 1 ppm

Percent Chlorine In Product

Gallons in Pool10,000 25,000 50,000 75,000 100,000 200,000 500,000 750,000 1,000,000

5 3.2 cp 2 qt 1 gl 1.5 gl 2 gl 4 gl 10 gl 15 gl 20 gl10 1.6 cp 1 qt 2 qt 3 qt 1 gl 2 gl 5 gl 7.5 gl 10 gl12 1.33 cp 1.67 pt 1.517 qt 2.276 pt 3.33 qt 1.665 gl 4.163 gl 6.245 gl 8.326 gl30 0.278 lb 0.665 lb 1.390 lb 2.085 lb 2.780 lb 5.580 lb 13.900 lb 20.850 lb 27.800 lb40 0.209 lb 0.521 lb 1.043 lb 1.565 lb 2.086 lb 4.172lb 10.430 lb 15.645 lb 20.860 lb50 0.167 lb 0.417 lb 0.834 lb 1.251 lb 1.668 lb 3.336lb 8.340lb 12.511 lb 16.680 lb60 0.139 lb 0.348 lb 0.695 lb 1.043 lb 1.390 lb 2.780lb 6.950 lb 10.425 lb 13.900 lb65 0.128 lb 0.321 lb 0.642 lb 0.963 lb 1.284 lb 2.568lb 6.420 lb 9.630lb 12.840 lb70 0.119 lb 0.298 lb 0.596 lb 0.894 lb 1.192 lb 2.384lb 5.960lb 8.940 lb 11.920 lb75 0.111 lb 0.278 lb 0.556 lb 0.834 lb 1.112 lb 2.224 lb 5.560 lb 8.340 lb 11.120 lb80 0.104 lb 0.261 lb 0.521 lb 0.782 lb 1.042 lb 2.064 lb 5.210 lb 7.815 lb 10.420 lb85 0.096 lb 0.417 lb 0.491 lb 0.737 lb 0.982 lb 1.964 lb 4.910 lb 7.365 lb 9.829 lb90 0.093 lb 0.232 lb 0.463 lb 0.695 lb 0.926 lb 1.852 lb 4.630 lb 6.945 lb 9.260 lb100 0.083 lb 0.209 lb 0.417 lb 0.626 lb 0.634 lb 1..668 lb 4.170 lb 6.225lb 8.340 lb

cp = one cup (8 fl oz) pt = one pt (16 fl oz) qt = one quart (32 fl oz) gl = one gallon (128 fl oz) lb =pounds of dry chemical

Page 16 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

Section G: Installation Diagrams

G – 1: Pressure Filter Installation

G – 2: Vacuum Filter Installation

Page 17 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

Section H: Replacement Parts

Fuses 8140086 Main Fuse Time Lag 250mA 250V 9140088 Relays 1-3 Time Lag 3A 250V 8140059 RS485 Fuse Time Lag 250mA 250V 8320053 Fuse Cap

Sensors pH Sensors 9660013 BECSys pH Sensor (30” cable) [range: 0 to 14.0 pH] 9660010 BECSys pH Sensor (10’ cable) [range: 0 to 14.0 pH] ORP Sensors 9660022 BECSys ORP Sensor Platinum Band (30” cable)

[range: 0 to 1000mV] 9660023 BECSys ORP Sensor Platinum Band (10’ cable)

[range: 0 to 1000mV] 9660038 BECSys ORP Sensor Solid Gold Band (30” cable)

[range: 0 to 1000mV] 9660040 BECSys ORP Sensor Solid Gold Band (10’ cable)

[range: 0 to 1000mV] pH/ORP Sensor Accessories 8500061 4/KCl solution (pint); for long-term storage of sensors 8680015 ½” Wetting Cap for pH and ORP sensors Temperature Sensors 9660016 Temperature Sensor (30” cable)

[range: 32°F to 212°F (0°C to 100°C)] 9660003 Temperature Sensor (10’ cable)

[range: 32°F to 212°F (0°C to 100°C)] Flow Switches 9660006 Reed flow switch [Switch Point (On): 2.0 gpm] 9660007 Rotary flow switch [Switch Point (On): 1.5 gpm] 9060547 Spring Check Valve 8680019 Rotary Flow Switch Replacement Kit includes: 1 Pin,

1 Cover, 1 Wheel, 1 O-ring 8060663 Rotary Flow Switch Replacement Pin 8060664 Rotary Flow Switch Replacement Cover 8060665 Rotary Flow Switch Replacement Wheel 8060666 Rotary Flow Switch Replacement O-Ring Amperometric ppm (Cl) 9660005 Amperometric Sensor only, no flow cell

[range: 0 to 20 ppm] 8680016 Replacement Membranes (2 pieces) for Chlorine

Sensor 9660005 8680017 Electrolyte (50 ml) for Chlorine Sensor 9660005

Boards 1200556 BECSys3 CPU PCB 1200407 BECSys3 Relay PCB 1200554 Free Chlorine (CCS140) Option Board 1200566 Free Chlorine (ECL6) Option Board

Software M000104 BECSys3 Firmware Upgrade IC

Documentation 8620044 BECSys3 Operator’s Manual 8620045 BECSys3 Installation/Technical Manual 8620046 BECSys3 (no ppm scale) Quick Reference Sheet 8620047 BECSys3 (0.2 – 16.0 scale) Quick Reference Sheet

Misc Enclosure Parts M000099 BECSys3 Lid Assembly no ppm scale M000101 BECSys3 Lid Assembly 0.2 – 16.0 ppm scale 8440199 BECSys3 Overlay no ppm scale 8440200 BECSys3 Overlay 0.2 – 16.0 ppm scale 9520027 Single BNC cable assembly 8060736 Small watertight cord grip PG-7 8060735 Large watertight cord grip NPT ½” Internal Components 8041102 2 Position Pluggable Terminal Block (Temperature) 8041103 3 Position Pluggable Terminal Block (Flow Switch,

RS485) 8380650 RS485 IC 9060533 Shield Screws 9520034 Ribbon Cable

Flow Cell Replacement Parts Round Flow Cell 1220210 Round Flow Cell Body 1220205 Acrylic Cover for Round Flow Cell 8060626 O-Ring for Round Flow Cell 1220207 PVC Mounting Plate for Round Flow Cell 8080625 Screws – Mounting Plate Rectangular Flow Cell 1220201 2-Sensor Rectangular Flow Cell Body 1220200 Acrylic Cover for 2-Sensor Rectangular Flow Cell 8060669 O-Ring for 2-Sensor Rectangular Flow Cell Common Flow Cell Components 9060189 Screws – Acrylic Cover 8060623 Elbow, 90° PVC 8060624 Elbow, 45° PVC 9060538 Plug, ¼” PVC 9060541 Nipple, ½” Close 8060621 Sample Valve, ¼” Ball Cock 9060546 Ball Valve ½” PVC 9060549 S80 Bushing, PVC ¾ x ½ 9060544 Pressure Gauge 8060673 Pressure Regulator Amperometric Flow Cell Components 1210255 Flow Cell for Amperometric Sensor (9660005) 8060671 Flow Meter used in Amperometric Flow Cell 1210253

Page 18 www.becs.com 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132

Operation and Maintenance Manual Rev: K12

Section I: Warranty

LIMITED WARRANTY BECS warrants the controller electronics, and flow cell against any defect in workmanship or materials for a period of five years from the date of shipment. BECS warrants the pH and ORP sensors against any defect in workmanship or materials for a period of two years from the date of shipment. In the event of a component failure due to any defect in workmanship or materials, BECS will repair, or if repair is not possible, replace the defective part or parts of the BECSys controller. BECS will have the sole right to determine whether to repair or replace a product. BECS will not be responsible for any expense associated with installation of repaired or replacement parts. LIMITATIONS AND EXCLUSIONS This is a LIMITED WARRANTY. BECS makes NO WARRANTIES other than those contained herein. The LIMITED WARRANTY replaces and is in lieu of any WARRANTIES of MERCHANTABILITY or of FITNESS FOR A PARTICULAR PURPOSE which are expressly DISCLAIMED. All GENERAL, SPECIAL, INDIRECT, INCIDENTAL AND/OR CONSEQUENTIAL DAMAGES ARE EXCLUDED AND DISCLAIMED. This Limited Warranty is governed by Missouri Law and all disputes related to or arising from this transaction or Limited Warranty shall be resolved in Circuit Court of St. Louis County, Missouri. Any claims under this Limited Warranty must be brought within ONE YEAR after the cause of action accrued.

Document Part Number: 8620045-K12

November 2012 9487 Dielman Rock Island Ind Dr, St. Louis, MO 63132 www.becs.com

Operation and Maintenance Manual Rev: K12

has been designing and manufacturing the industry’s most reliable water chemistry controller for over 20 years. Our 24,000 ft2 facility in Saint Louis, Missouri is home to an exceptional design team, and all manufacturing is performed onsite at this facility where we can personally assure the quality of our products. The BECS commitment to excellence drives the most innovative new products and unparalleled customer service.