operating manual - alpha innotec
TRANSCRIPT
UK
Water/Water-Heat PumpsCompact
83050700fUK – Translation into English of the original German operating manual
Operating ManualWWC H/X – series
WWC X – series
2 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Please read firstThis operating manual provides important information on handling the unit. It is an integral part of the product and must be stored so that it is accessible in the immedi-ate vicinity of the unit. It must remain available through-out the unit's entire service life. It must be handed over to subsequent owners or users of the unit.
Read the operating manual before starting any work on or with the unit. Especially the chapter on safety. Follow all instructions in full and unreservedly.
It is possible that this operating manual may contain instructions that seem incomprehensible or unclear. In the event of any questions or if any details are unclear, contact the factory customer service department or the manufacturer's local partner.
Since this operating manual was written for several different models of the unit, always comply with the parameters for the respective model.
This operating manual is intended only for persons assigned to work on or with the unit. Treat all constitu-ent parts confidentially. They are protected by copy-right. They may not be reproduced, transmitted, copied, stored in electronic systems or translated into another language, either wholly or in part, without the express written permission of the manufacturer.
SymbolsThe following symbols are used in the operating manual. They have the following meaning:
Information for uers.
Information or instructions for qualified technicians.
DANGER! Indicates imminent danger, which results
in severe injuries or death.
WARNING! Indicates a potentially dangerous situa-
tion, which could result in severe injuries or death.
CAUTION! Indicates a potentially dangerous situation
that could result in moderate or slight injuries.
IMPORTANT Indicates a potentially dangerous situation, which
could result in property damage.
NOTE. Emphasized information.
€ ENERGY SAVING TIP Indicates advice, which helps to save energy, raw
materials and costs.
Reference to other sections of the operating manual.
Reference to other documents of the manufac-turer.
3Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Contents
INFORMATION FOR USERS AND QUALIFIED PERSONNEL
PLEASE READ FIRST ..................................................................2
SYMBOLS .....................................................................................2
INTENDED USE ..........................................................................4
DISCLAIMER................................................................................4
EC CONFORMITY .....................................................................4
SAFETY .........................................................................................4
CUSTOMER SERVICE ................................................................5
WARRANTY / GUARANTEE ....................................................5
DISPOSAL ....................................................................................5
OPERATING PRINCIPLE OF HEAT PUMPS ..........................5
AREA OF USE AND HEAT SOURCE REQUIREMENTS .....................................6
HEAT METERING .......................................................................7
OPERATION ................................................................................7
CARE OF THE UNIT ..................................................................7
MAINTENANCE OF THE UNIT ..............................................7Cleaning and flushing unit components .............................7
MALFUNCTIONS .......................................................................8
INSTRUCTIONS FOR QUALIFIED TECHNICIANS
SCOPE OF DELIVERY ................................................................8Main components ..................................................................9
INSTALLATION ..........................................................................9Installation room ...................................................................9Transport to installation location ....................................10Installation ............................................................................10
INSTALLING THE HYDRAULIC CONNECTIONS ...........12Safety assembly ...................................................................13Expansion vessel .................................................................13
DOMESTIC WATER HEATING ..............................................14
DOMESTIC HOT WATER TANK ..........................................14
ELECTRICAL CONNECTION WORK .................................14
FLUSHING AND FILLING THE SYSTEM .............................16Water quality of the fill and make-up water in
water heating systems according to VDI 2035 ........16Flush and fill the heating circuit and
the domestic hot water tank ...................................... 17
BLEEDING ..................................................................................18
INSULATING THE HYDRAULIC CONNECTIONS .......................................19
INSTALLING THE CONTROL PANEL .................................19
INSTALLATION AND REMOVAL OF THE SCREEN .........20
SET THE OVERFLOW VALVE .................................................21PUMP SETTINGS FOR
WWC 220HX AND WWC 280X .............................22
COMMISSIONING ...................................................................22Safety temperature limiter ................................................23
DISMANTLING .........................................................................23
TECHNICAL DATA / SCOPE OF DELIVERYWWC 100H/X – WWC 220H/X ....................................24WWC 280X – WWC 440X..............................................26
PERFORMANCE CURVESHeating capacity/COP / Power consumption / Heat pump pressure loss
WWC 100H/X ....................................................................28WWC 130H/X ....................................................................29WWC 160H/X ....................................................................30WWC 190H/X ....................................................................31WWC 220H/X ....................................................................32WWC 280X .........................................................................33WWC 440X .........................................................................34
DIMENSIONAL DRAWINGS AND INSTALLATION PLANSWWC 100H/X – WWC 220H/XDimensional drawings ........................................................35Installation plan ...................................................................36WWC 280XDimensional drawings ........................................................37WWC 440XDimensional drawings ........................................................38WWC 280X – WWC 440XInstallation plan ...................................................................39
HYDRAULIC INTEGRATIONWWC 100H/X – WWC 220H/XDefault ................................................................................. 40Separate buffer tank ...........................................................41WWC 280X – WWC 440XDefault ..................................................................................42Separate buffer tank ...........................................................43Legend Hydraulic integration ........................................... 44
TERMINAL DIAGRAMSWWC 100H/X – WWC 220H/X ....................................45WWC 280X – WWC 440X..............................................46
CIRCUIT DIAGRAMSWWC 100H/X ....................................................................47WWC 130H/X – 220H/X ..................................................50WWC 280X .........................................................................53WWC 440X .........................................................................56
EC DECLARATION OF CONFORMITY ..............................59
4 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Intended useThe unit is only to be used for its intended purpose. This means:
• for heating.
• for domestic water heating.
The unit may be operated only within its technical parameters.
Overview “Technical data / scope of delivery”.
NOTE. Notify the responsible power supply company of
the use of a heat pump or heat pump system.
DisclaimerThe manufacturer is not liable for any damage or losses resulting from use of the unit which is not its intended use.
The manufacturer's liability also expires:
• if work is carried out on the unit and its compo-nents contrary to the instructions in this operat-ing manual.
• if work is improperly carried out on the unit and its components.
• if work is carried out on the unit which is not described in this operating manual, and this work has not been explicitly approved by the manufac-turer in writing.
• if the unit or components in the unit have been altered, modified or removed without the explicit written consent of the manufacturer.
EC conformityThe unit bears the CE marking.
EC Declaration of Conformity
SafetyThe unit is safe to operate for its intended use. The con-struction and design of the unit conform to current state of the art standards, all relevant DIN/VDE regulations and all relevant safety regulations.
Every person who carries out work on the unit must have read and understood the operating manual before starting any work. This also applies if the person con-cerned has already worked with such a unit or a similar unit or has been trained by the manufacturer.
Every person who carries out work on the unit must comply with the relevant local accident prevention and safety regulations. This especially applies to the wearing of personal protective clothing.
DANGER! Risk of fatal electric shock! All electrical connection work must be
carried out by qualified electricians only. Before opening the unit, safely disconnect
the system from the power supply and prevent it from being switched back on!
WARNING! Only qualified personnel (trained heat-
ing, refrigerating system and refrigerant engineers and electricians) may carry out work on the unit and its components.
WARNING! Note and follow safety stickers on and in
the unit.
WARNING! Unit contains refrigerant! Leaking refrigerant could result in per-
sonal injury and environmental damage. Therefore:
– Switch off system.– Thoroughly ventilate installation
room.– Notify the manufacturer’s authorised
service centre.
IMPORTANT For safety reasons: Never disconnect the unit from the power sup-
ply, unless the unit is being opened.
5Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
IMPORTANT Only install the heat pump indoors.
Dimensioned drawing and installation plan for the respective unit model.
Customer serviceFor technical assistance, please contact your qualified technician or the manufacturer’s local service partner.
For a current list and additional partners of the manufac-turer, please visit
DE: www.alpha-innotec.de
EU: www.alpha-innotec.com
Warranty / GuaranteeFor warranty and guarantee provisions, please refer to your purchase documents.
NOTE. Please contact your dealer about all matters
concerning warranties and guarantees.
DisposalWhen withdrawing the old unit from service, always comply with the relevant local laws, guidelines, direc-tives and standards concerning the recovery, recycling and disposal of the operating materials and components of refrigerating units.
“Dismantling”.
Operating principle of heat pumps
Heat pumps operate on the same principle as a refriger-ator: same technology, only with reversed benefits. The refrigerator extracts heat from foods, which is released into the room through fins on the back.
The heat pump extracts heat from our environment: air, earth or ground water. The extracted heat is condi-tioned in the unit and supplied to the heating water. Even when it is extremely cold outside, the heat pump draws enough heat to heat a house.
Example: drawing of a brine/water heat pump with floor heating:
4/4 = usable energy approx. 3/4 = environmental energy approx. 1⁄4 = external electrical energy
6 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Area of use and heat source requirements
Taking into consideration the ambient conditions, limits of use and the relevant regulations, every heat pump can be used in new or existing heating systems.
“Technical data / scope of delivery” overview,
WATER TEMPERATURE / WATER QUANTITY
The water in the extraction well of the heat source system must have a minimum temperature of 7 °C all year round and may not exceed a temperature of 25°C. Depending on the heat output required or its cooling capacity as a relevant variable for dimensioning the heat source, a minimum water rate is required, which must be provided by the heat source as a continuous output. Before installing the water/water heat pump, a pump test should/must be carried out for at least 12 hours with verification of a quasi-constantly lowered water table (persistence) in order to provide information about the quantity of water available. For efficient operation of the well, during the initial start-up the nominal flow rate must be adjusted on the heat source side. Any appropriate components, which enable balancing are to be installed in the pipe network here. The material of the components used must be chosen according to the water quality. The necessary flow rate (heat source water rate) must meet the heat pump's requirements.
“Technical data/scope of supply” overview.
WATER QUALITY
In Germany the well must be designed and built to DIN 4021 and VDI 4640 (in other countries according to the corresponding regulations). Wells may only be drilled and built by drilling companies with a permit in accord-ance with DVGW W120. The water quality of the heat source is defined as normal groundwater. Ensure that the suction and return pipe always extends below the water level by sufficient depth, to ensure that oxygen is not added to the water (risk of iron oxide deposits). Please discuss the problem of iron oxide deposits with your well builder. During the planning the quality of the groundwater should be checked in advance as well as possible (e.g. by asking the competent water authority or searching for data on existing adjacent wells) and sub-sequently verified by water analysis in the built produc-tion well. The following table helps to assess the water quality.
IMPORTANT A water analysis and pump test must be carried
out before installing the water/water heat pump.
NOTE: Water analyses are prepared by water test labo-
ratories. Initial information about possible use of groundwater is available from your local water management authority. A pump test provides information as to whether a sufficient quantity / rate of water is available to cover the require-ments for the heating output of your unit. The minimum groundwater flow rate must at least be available as a continuous output.
“Technical data/scope of supply” overview, “Heat source flow rate” section.
EVALUATION OF THE WATER ANALYSIS
Water constituents - minimum requirement. The water should be analysed in advance for the test values listed below (table). An important criterion to be used for taking water samples is the DVGW Standard, Technical Notices, Leaflet W 112 and use of the technical rules listed in it (DIN, EN and ISO standards).
Designation LimitpH value > 6.8Iron level < 0.2 mg / lManganese level < 0.1 mg / lChloride level < 300 mg / lFree chlorine level < 3 mg / lTurbidity noneTechnical freedom from sand
< 0,1 ml sand per10 l pumped water
IMPORTANT If a value does not conform to the value listed
in the table, a water/water heat pump may not be used. Direct operation of the unit in conjunc-tion with surface water, wastewater, industrial wastewater or mixtures of water and alkali solu-tions, acids or chlorine is also not allowed.
7Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Heat meteringIn addition to proof of the system's efficiency, the EEWaermeG (German law on renewable energy heat) also requires heat metering (referred to in the follow-ing as WME). The WME is mandatory for air/water heat pumps. For brine/ water and water/water heat pumps, a WME must be installed for flow temperatures ≥ 35 °C. The WME must record the total thermal energy output (heating and domestic hot water) in the building. In the case of heat pumps with heat metering the analysis is carried out via the controller. This displays the thermal energy output into the heating system in kWh.
NOTE. Unit variants with or without heat metering are
available.
Operation
ENERGY SAVING USE OF THE HEAT PUMP HEATING
By deciding to purchase a heat pump or a heat pump sys-tem you are making a long-term contribution to protect-ing the environment through low emissions and reduced primary energy use.You can operate and control the heat pump system with the control panel of the heating and heat pump control-ler.
NOTE. Make sure that the control settings are correct.
Operating manual of the heating and heat pump controller.
To ensure that your heat pump or heat pump system operates efficiently and in an environmentally friendly way in heating mode, please pay particular attention to the following:
€ ENERGY SAVING TIP Avoid unnecessarily high flow temperatures. The lower the flow temperature on the heating
water side the more efficient the system.
€ ENERGY SAVING TIP Preferably use purge ventilation. Compared to
continuously open windows, this form of ventila-tion (fully opening windows for a short period, two to three times a day) reduces energy con-sumption and your heating bill.
Care of the unitYou can clean the outer surfaces of the unit with a damp cloth and proprietary household cleaning products.Do not use cleaning or care products that contain abra-sives, acids and/or chlorine. Such products would irrepa-rably damage the surfaces and could also cause technical damage to the unit.
Maintenance of the unitThe cooling circuit of the heat pump requires no regu-lar maintenance.
According to EU regulation (EC) 517/2014, leak inspections and maintenance of a log book are required by law for certain heat pumps!
Log book for heat pumps, Section “Information on use of the log book”.
The components of the heating circuit and the heat source (valves, expansion vessels, circulation pumps, fil-ters, dirt traps) should be tested and cleaned as needed, however, at least annually, by qualified personnel (heat-ing or refrigerating system fitters).It is best to arrange a maintenance agreement with a heating installation company. The company will arrange the necessary regular maintenance work.
CLEANING AND FLUSHING UNIT COMPONENTS
CAUTION! Unit components may be cleaned and
flushed only by customer service person-nel authorised by the manufacturer. Use only liquids recommended by the manu-facturer.
After flushing the condenser with chemi-cal cleaning agent, any residues must be neutralised and the system intensively flushed with water. Always note and follow the technical data of the respective heat exchanger manufacturer.
8 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
MalfunctionsIn the event of a malfunction, you can detect the cause of the malfunction via the diagnostics program of the heating and heat pump controller.
Operating manual of the heating and heat pump controller.
WARNING! Only customer service personnel author-
ised by the manufacturer may carry out service and repair work on the compo-nents of the unit.
Note that no fault is displayed if the safety temperature limiter on the electric heating element has triggered (depending on model).
“Commissioning”, “Safety temperature limiter” section.
Scope of deliveryExample layout of the scope of delivery:
1 Compact unit with hermetic compressor, all safety-relevant components for refrigeration circuit monitoring, installed sensors for recording the hot gas, heating water flow and return temperature, sensors for monitoring the heat source temperature, flow monitors for monitoring the water flow rate
2 Screen3 Safety assembly for the heating circuit4 Separate package (size 1: one box; size 2: two
boxes) with control panel, external tempera-ture sensor, dirt trap, Sylomer strips, seals
5 Vibration isolators for the heat-ing circuit and for the heat source
6 Expansion vessel for the heat-ing circuit with cap valve
Complete the following first:
Check the delivery for outwardly visible signs of damage…
Check to make sure that the delivery is complete… Any defects or incorrect deliveries must be
reported immediately.
NOTE. Note the unit model.
“Technical data / scope of delivery” overview.
9Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
FUNCTIONALLY NECESSARY ACCESSORIES
IMPORTANT Only use the manufacturer's original accessories.
If the unit is to be used for heating water, a 3-way switch-ing valve must be installed. This is not included with the unit and must be ordered separately.
MAIN COMPONENTS
1 evaporator2 compressor3 condenser
InstallationThe following applies to all work to be done:
NOTE. Always comply with the relevant local accident
prevention regulations, statutory regulations, guidelines and directives.
NOTE. Note the sound information for the respective
model.
“Technical data / Scope of delivery” overview, “Sound” section.
INSTALLATION ROOM
ATTENTION Install the heat pump only indoors. The installation room must be frost-free and
dry.
WARNING! Please note and follow the respective
relevant local standards, directives and regulations applicable, especially the minimum volume necessary depending on the refrigerant capacity of the relevant heat pump system (EN 378-1).
Refrigerant Limit
R 134a 0.25 kg/m³
R 404A 0.48 kg/m³
R 407C 0.31 kg/m³
R 410A 0.44 kg/m³
Overview “Technical data / scope of delivery”, “General unit data” section.
Minimum volume = Refrigerant capacity [kg]
Limit [kg/m³]
NOTE. If several heat pumps of the same type are instal-
led, only one heat pump must be considered. If several heat pumps of different types are in-
stalled, the heat pump with the largest refrige-rant capacity must be considered.
10 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
TRANSPORT TO INSTALLATION LOCATION
Always comply with the following safety information during transport:
WARNING! Several people are required to transport
the unit. Take into account the weight of the unit.
“Technical data / Scope of delivery” overview, “General unit data” section,
CAUTION! Wear safety gloves.
WARNING! The unit can tilt and tip over when being
removed from the wooden pallet and dur-ing transport. This can result in personal injury and damage to the unit.– Take suitable precautions to prevent
the risk of tipping over.
IMPORTANT Never use components and hydraulic connec-
tions on the unit for transport purposes.
IMPORTANT Do not tilt the unit more than a maximum of 45°
(in any direction).
To prevent transport damage, you should transport the unit to its final place of installation in its packed condi-tion (on the wooden pallet with packaging) using a pallet truck.If it is not possible to transport the unit to the final instal-lation location using a pallet truck, you can also transport the heat pump on a handcart.Before transporting with a handcart, we recommend removing the front panel in order to reduce the weight of the unit.
Remove packaging and set extra box aside (will be needed later on!)...
Remove angle bracket, transport and packaging material from the unit…
Dispose of angle bracket, transport and packaging material properly and in an ecologically compatible way...
Lift unit from the pallet…
Remove front panel of unit...
•
To do so, loosen the quick-release screws. Turn through 90° to the left…
•
Lift front panel and set aside in a safe place.
Push handcart under the rear side of the unit.
IMPORTANT If the handcart is pushed under the unit at the
rear panel, ensure you do not damage any con-nections during transport.
IMPORTANT Transport with a handcart on the front side of
the unit is not permitted.
IMPORTANT Do not tilt the unit more than a maximum of 45°
(in any direction).
INSTALLATION
CAUTION! Several people are required to install the
unit.
NOTE. Take into account the size of the unit.
“Technical data / Scope of delivery” overview, “General unit data” section.
NOTE. Always refer to and follow the installation plan
for the respective model. Note the size and minimum clearances.
Installation plan for the respective model.
11Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Proceed as follows at the installation location:
If you have no already done so, remove angle bracket, transport and packaging material from the unit. Set the extra box to the side and lift the unit from the wooden pallet...
“Transport to installation location”.
Dispose of angle bracket, transport and packaging material properly and in an ecologically compatible way...
Set unit on a stable, solid and level, preferably sound-insulated surface. Ensure that the floor is designed for the weight of the heat pump...
Set up the unit so that the switchbox side (= opera-tor side) is accessible at all times...
“Technical data/Scope of delivery” overview, “General unit data” section.
Use the Sylomer strips supplied to level out any minor unevenness.
The Sylomer strips give the heat pump additional stability. They absorb sound and vibrations transfer to the floor.
Place the Sylomer strips under the heat pump as fol-lows:
•
Tilt the unit to one side, slowly and carefully...
Secure unit in raised tilted position so that it cannot accidentally tip back into the original position.
IMPORTANT Do not tilt the unit more than a maximum of 45°
(in any direction).
CAUTION! Hands and fingers could be crushed during
the following work!
•
Position a Sylomer strip under the unit, flush with the respective outer edge...
•
Slowly and carefully tilt the unit back into its initial position.
Repeat steps • to • for the remaining sides of the unit.
Position Sylomer strips at right angles to each other, end-to-end:
Front side of unit (= operator side)
12 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Installing the hydraulic connections
NOTE. All materials used in the heat source circuit
(pipes, connections, sealing material…) must be corrosion resistant and suitable for the ground-water quality. Use suitable plastics or stainless steel.
IMPORTANT Connect the unit to the heating circuit accord-
ing to the hydraulic diagram for the respective model.
“Hydraulic connection” instructions.
IMPORTANT The heat source system must be designed
according to the specifications of the planning manual.
Planning manual and “Hydraulic connection” documents.
NOTE. Check to make sure that the cross-section and
lengths of the pipes for the heating circuit are adequately dimensioned. The free compression of the circulation pumps must be able to deliver at least the minimum throughput required for your model.
“Technical data /Scope of delivery” overview, “Heat source” and “Heating circuit” sections.
NOTE: Check whether the cross-sections and lengths
of the heat source pipes are adequately dimen-sioned.
NOTE: The heat source pump must be designed as a
constant speed pump. It must at least produce the minimum throughput required for your unit model. The heat source pump must be designed by performing a pipe network calculation.
“Technical data/Scope of delivery” overview, “Heat source” sections..
IMPORTANT Please note that the designed heat source pump
may only be used within its pump characteristic curve!
IMPORTANT When installing the connections, always secure
the connections on the unit against twisting, in order to prevent damage to the copper pipes inside the unit.
NOTE: Install the dirt trap included in the scope of
delivery in the well shaft (heat source inlet)
The connections for the heating circuit or the heat source are located at the rear of the unit:
For position of the connections, please refer to the dimensioned drawing for the respective model.
Install shut-off devices for the heating water outlet (flow) and heating water inlet (return) on the heat pump side…
Install shut-off devices for the heat source inlet and heat source outlet on the heat pump side…
NOTE. By installing the shut-off devices, the evaporator
and condenser of the heat pump can be flushed, if necessary.
Thoroughly flush the heating circuit and heat source circuit before connecting to the unit…
NOTE. Dirt and deposits in the heating circuit and heat
source can cause malfunctions.
Connect the fixed pipes of the heating circuit with the corresponding connections at the rear of the unit. Use vibration isolators and elbow unions (size 2 only)…
Vibration isolators must be installed to prevent structurally borne sound transfer
to the fixed pip-
ing.
Vibration isolators for the heating circuit are included with the unit; they have a zinced mesh and are marked in colour.
13Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Connect the fixed piping of the heat source with the relevant connections at the rear of the unit. Use vibration isolators and elbow unions (size 2 only)…
Vibration isolators must be installed to prevent structurally borne sound transfer
to the fixed pip-
ing.
Vibration isolators for the heat source are included with the unit and have a stainless steel mesh.
Lay vibration isolators in the quadrant, as shown by way of example in the following sketch:
Straight or extended hose laying of the vibration isola-tors is not permitted.
SAFETY ASSEMBLY
You must install the safety assembly for the heating circuit. The safety assembly for the heating circuit is included in the extra box.
The discharge from the heating water safety valve must be drained according to the relevant standards and regu-lations. Discharging the safety valve discharge into the sewers is allowed only if fed via a a funnel siphon, which must be accessible at all times.
The connection for the safety assembly is located on the outside at the top rear of the unit.
1 Heating circuit safety assembly connection
EXPANSION VESSEL
The expansion vessel for the heating circuit and the cor-responding cap valve are included in the scope of deliv-ery. They must both be integrated in the heating circuit on site in compliance with the relevant standards, guide-lines and directives.
IMPORTANT In conjunction with a multi-functional and/or
buffer tank with volume >200 l, always install an additional, adequately-dimensioned expansion vessel.
14 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Domestic water heatingIf the unit is to be used for domestic water heating, a 3-way changeover valve must be installed. This is not included with the unit and must be ordered separately.
IMPORTANT Only use the manufacturer’s original accessories.
Domestic water heating with the heat pump requires an additional heating water circuit (parallel) to the heating circuit. When connecting, make sure that the domestic hot water charge is not fed through a buffer tank in the heating circuit.
“Hydraulic connection” documents.
Domestic hot water tankIf the heat pump is to be used for domestic water heat-ing, you must integrate special domestic hot water tanks in the heat pump system. Choose a storage volume so that the required quantity of domestic hot water is avail-able even during a power failure.
NOTE: The heat exchanger surface of the domestic hot
water tank must be dimensioned so that the heating output of the heat pump is transferred with minimum spread.
You can choose a domestic hot water tank from our product range. They are optimally matched to your heat pump.
NOTE: Integrate the domestic hot water tank in the
heat pump system as shown in the hydraulic dia-gram for your system.
“Hydraulic connection” documents.
Electrical connection workThe following applies to all work to be done:
DANGER! Risk of fatal electric shock! All electrical connection work must be
carried out by qualified electricians only.
Before opening the unit, safely disconnect the system from the power supply and prevent it from being switched back on!
WARNING! During installation and when carrying out
electrical work, comply with the relevant EN-, VDE and/or local safety regulations.
Comply with technical connection require-ments of the responsible power supply company (if required by the latter)!
NOTE. All live cables must be stripped before they are
laid in the cable duct of the switchbox!
Open unit, if closed…
“Transport to the installation location”, and .
Open electrical switchbox inside the unit…
1 Cover plate of the switchbox2 Screw plugs
15Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Opened switch box size 1:
1 Controller board connections2 Power and control
cable connections
Opened switch box size 2:
1 Controller board connections2 Power and control
cable connections
Feed the load and control cables as well as the cables for sensors into the inside of the unit through the openings provided at the rear of the unit…
For positioning of the rubber grommets for feeding through the cables, see “dimensioned drawing” for the respective model.
Lay load and control leads in the cable duct inside the unit all the way to the switchbox.
Install electrical connections according to the ter-minal diagram and the circuit diagrams.
“Terminal diagrams” and “Circuit diagrams” for the respective model.
IMPORTANT Install electric connections only according to the
terminal diagram and the circuit diagrams that apply to your model.
IMPORTANT Ensure clockwise rotary field of the load power
supply (compressor). Operation with the incorrect rotary direction of
the compressor can cause serious, irreparable damage to the compressor.
IMPORTANT The power supply for the heat pump must be
equipped with a three-phase automatic circuit-breaker with at least 3mm contact spacing to IEC 60947-2.
Note the level of the tripping current.
“Technical data / Scope of delivery” overview, “Electrics” section.
E
D
C
B
www.alpha-innotec.deD - 95359 Kasendorf
Industriestraße 3Alpha-InnoTec GmbH
1
1Ers. d.Ers. f.
BenennungDurch�usssensor VFS5-100
603772-Zust. Änderungstext Datum
9.2.2009 HSVon
Blatt
von
Werksto� Gewicht-
Maßstab 1:2 Det. Maßstab
Datum NameErstelltGepr.Norm.
9.2.2009 Stenglein
toleranzAllgemein-
DIN ISO 2768 -c
Ober�ächen
ArtikelNr.
---
1 2 3 4
Schutzvermerk nach DIN 34 beachten
Blattformat: A4 hoch
IMPORTANT The sensor cable for heat quantity recording
may not be shortened!
NOTE. The control panel of the heating and heat pump
controller can be connected to a computer or network using a suitable network cable, enabling the heating and heat pump controller to be con-trolled remotely from there.
16 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
If this is required, install a shielded network cable (category 6, with RJ-45 connector) through the unit when installing the connections and run it through the front panel of the unit, parallel to the existing control cable of the heating and heat pump controller.
After completing all electrical installation work, close the switchbox inside the unit…
Screw on the front panel of the unit, if no further installation work inside the unit is to be carried out immediately.
Flushing and filling the system
IMPORTANT The system must be absolutely free from air
before commissioning.
WATER QUALITY OF THE FILL AND MAKE-UP WATER IN WATER HEATING SYSTEMS ACCORDING TO VDI 2035PART I AND II
Use of modern, energy-efficient heat pump systems is becoming increasingly widespread. Their ingenious technology enables these systems to achieve very good efficiencies. The decreasing space available for heat gen-erators has led to the development of compact units with increasingly smaller cross-sections and high capaci-ties. This means the complexity of the systems and the material diversity are also increasing, which plays an important role especially in their corrosion behaviour. The heating water not only affects the efficiency of the system, but also the life of the heat generator and the heating components of a system.
The guide values of VDI 2035 Part I and Part II must therefore be complied with as minimum requirements for proper operation of the systems. Our practical expe-rience has shown that the safest, most reliable and fault-free running is achieved with so-called low-salt operation.
VDI 2035 Part I provides important information and recommendations regarding scaling and its prevention in heating and domestic hot water heating systems.
VDI 2035 Part II primarily deals with the requirements for reducing heating water corrosion in hot water heat-ing systems.
PRINCIPLES OF PART I AND PART II
The occurrence of scaling and corrosion damage in hot water heating systems is low, if
- proper planning, design and commissioning is carried out
- the system is closed in corrosion terms
- adequately dimensioned pressurising is integrated
- the guide values for the heating water are complied with
- and regular servicing and maintenance are carried out.
A system log should be kept, in which the relevant plan-ning & design data is entered (VDI 2035).
DAMAGE THAT CAN OCCUR IN CASE OF FAILURE TO COMPLY WITH THE ABOVE
- Malfunctions and the failure of components (e.g. pumps, valves)
- Internal and external leaks (e.g. from heat exchangers)
- Cross-section reduction and blockaging of compo-nents (e.g. heat exchanger, pipes, pumps)
- Material fatigue
- Gas bubbles and gas cushion formation (cavitation)
- Negative effect on heat transfer (formation of coat-ings, deposits) and associated noises (e.g. boiling noises, flow noises)
LIMESCALE – THE ENERGY KILLER
Filling with untreated drinking water inevitably leads to the precipitation of all calcium as scale. The consequence: limescale deposits form on the heat transfer surfaces of the heating. The efficiency falls and the energy costs rise. A rule of thumb is that 1 millimetre of limescale deposit causes an efficiency loss of 10%. In extreme cases it can even cause damage to the heat exchangers.
WATER SOFTENING TO VDI 2035 – PART I
If the water is softened in accordance with the VDI 2035 guidelines before it is used to fill the heating system, no scale can form. This effectively and permanently prevents limescale deposits and the resulting negative effects on the entire heating system.
17Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
CORROSION – AN UNDERESTIMATED PROBLEM
VDI 2035, Part II, deals with the problem of corrosion. Softening the heating water can prove to be insufficient. The pH value can significantly exceed the limit of 10. pH values higher than 11 can set in, which even damage rub-ber seals. The VDI 2035, Part 1 guidelines are fulfilled; however, VDI 2035, Part 2 suggests a pH value between 8.2 and maximum 10.
If aluminium materials are used, which is the case in many modern heating systems, a pH value of 8.5 must not be exceeded! Because otherwise there is a threat of corrosion – aluminium is attacked without the presence of oxygen. Therefore, apart from softening the heating fill and make-up water, the heating water should also be appropriately conditioned. This is the only way to com-ply with the VDI 2035 requirements and the recommen-dations and installation instructions of the heat pump manufacturer.
Part 2 of VDI 2035 also refers to the reduction in total salt content (conductivity). The risk of corrosion is far lower if deionised water is used than is the case if the system is operated with salty, i.e. softened water.
Even if the water has been softened beforehand, it con-tains dissolved, corrosive salts, which act as electrolytes due to the use of different materials in the heating sys-tem and therefore accelerate corrosion processes. This can ultimately result in pitting.
ON THE SAFE SIDE WITH LOW-SALT OPERATION
The problems listed above do not occur at all with low-salt operation, as the heating water contains neither corrosive
salts such as sulphates, chlorides and nitrates nor alkalis-ing sodium hydrogen carbonate. The corrosive proper-ties of deionised water are very low and in addition, scale cannot form in the boiler. This is the ideal approach for closed heating circuits, in particular, because low oxygen input into the heating circuit can also be tolerated.
In general, when the system is filled with deionised water, the pH value sets itself within the ideal range due to “self-alkalinisation”. If necessary, a pH value of 8.2 can be very easily alkalised by adding chemicals. In this way, optimum protection of the entire heating system is achieved.
MONITORING
Analytical recording and monitoring of the relevant water values and the added active conditioning sub-stances is of decisive importance. Therefore, they should be monitored regularly using appropriate water test equipment.
FLUSH AND FILL THE HEATING CIRCUIT AND THE DOMESTIC HOT WATER TANK
Place a bleeder (vent) at the highest point of the heating circuit in the heating water outlet (flow)…
If necessary, place a bleeder at the highest point of the heating circuit in the heating water inlet (return)…
Open unit, if closed…
“Transport to the installation location”, and .
Flush and fill the unit via the filling and draining tap...
IMPORTANT Do not exceed a pressure of 2.5 bar when flush-
ing the unit. The drain line of the heating circuit safety valve must be closed before flushing and filling.
18 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Bleeding
VIEW OF INSIDE OF UNIT, SIZE 1
1 Electrical switchbox2 Overflow valve3 Electric heating element4 Circulation pump, heating circuit5 Fill and drain tap, heating circuit
VIEW OF INSIDE OF UNIT, SIZE 2
A B
A 28kW unitB 44kW unit
1 Electrical switchbox2 Overflow valve3 Circulation pump, heating circuit4 Fill and drain tap, heating circuit
BLEEDING THE UNIT
The unit is bled automatically if the bleeder (vent valve) of the safety assembly is open. If the heating circuit is filled or drained, the venting valve of the safety assembly opens.
BLEEDING THE CIRCULATION PUMP OF THE HEATING CIRCUIT
Unscrew the screw cover in the middle of the circulation pump until loose and close again after venting.
BLEEDING THE DOMESTIC HOT WATER TANK
To bleed the domestic hot water tank, the domestic hot water charge circuit must be flushed separately.
To do this, manually switch the domestic hot water changeover valve to domestic hot water charging. After bleeding, return it to the initial position.
19Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
NOTE: Once the heat pump, heating circuit and domes-
tic hot water charging circuit have been flushed, the bleeding program of the heating and heat pump controller must be started, after the con-trol panel has been installed.
If no further steps follow, install the front panel.
Insulating the hydraulic connections
NOTE. Insulate the heating circuit and the heat source
according to relevant local standards and guide-lines.
Check all hydraulic connections for leaks. Perform leak test…
Insulate all connections, vibration isolators, con-nections and pipes of the heating circuit and the heat source. Insulate the heat source so that it is vapour-diffusion tight.
Installing the control panelThere are 4 each recesses at different heights in the front panel of the unit for fastening the control panel:
1 four upper recesses2 four lower recesses
There are 4 hooks at the rear of the control panel, which are used to hook the control panel on the front panel of the unit:
Hook the control panel's hooks into the recesses of the front panel (either in the upper or lower recesses)...
Example:Control panel in upper recesses
20 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Push down the hooked in control panel, until it latches into place…
Push the control cable of the heating and heat pump controller into the right-hand socket on the underside of the control panel…
NOTE. A connection to a computer or a network can
be made via the left socket at the bottom of the control panel, thereby allowing the heating and heat pump controller to be controlled remotely from there. This requires a shielded network cable (category 6) to be laid through the unit during the electrical connection work.
Operating manual for the heating and heat pump controller, “Qualified technician” version, “Web server” section.
If this network cable is available, insert the network cable's RJ-45 connector into the left socket of the control panel.
NOTE. The network cable can be exchanged at any
time. In order to be able to connect it, the screen must first be removed.
Installation and removal of the screen
INSTALLING THE SCREEN
NOTE. The masking plate is provided in the as delivered
unit so that the control panel is inserted in the upper recesses of the front panel.
If the control panel has been inserted in the lower recesses of the front panel, you must first remove the masking plate's dummy cover and then reinsert it above the logo.
Screen at time of delivery:1 Recess for control panel2 Logo3 Dummy cover
First, insert the masking plate below in the slots provided in the front panel…
21Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Then, beginning on one side, latch the lugs on the masking plate from the bottom up into the slots provided in the front panel…
Then, on the opposite side, latch the lugs on the masking plate from the bottom up into the slots provided in the front panel…
Finally, press the upper latching lugs of the masking plate into the slots provided in the front panel.
DISMANTLING THE MASKING PLATE
In order to dismantle the masking plate, the latching lugs must be completely released on one side first by pushing towards the middle of the masking plate. Then release the lugs on the opposite side.
Set the overflow valve
REMARQUE The activities in this section are only necessary
for in-line tank integration. Complete the worksteps quickly, otherwise the
maximum return temperature can be exceeded and the heat pump switches to high-pressure fault.
Turn the adjusting knob at the overflow valve to the right to increase the temperature difference (the temperature drop), turn it to the left to re-duce it.
System is running in heating mode (ideally in cold condition).
In case of low heating curve: Set the system to “Forced heating”…
Operating manual of the heating and heat pump controller.
Shut off valves to the heating circuit…
Ensure that the total flow is routed via the overflow valve…
Read out the flow and return temperature at the heating and heat pump controller…
Operating manual of the heating and heat pump controller.
Turn the adjusting knob (2) of the overflow valve (1) until the temperature drop between the flow and return temperature is set as follows:
Heat source temperature Recommended settings10 °C 9 K
Open valves to heating circuit…
Reset the heating and heat pump controller.
22 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Commissioning
NOTE. The commissioning has to be in the heating
mode.
Carry out a thorough installation check and work through the general checklist…
Manufacturer’s homepage.
By checking the installation you prevent damage to the heat pump system, which could be caused by work carried out improperly.
Check that…
• clockwise rotary field of the load power supply (compressor) is ensured.
• The heat pump installation and assembly have been carried out according to the requirements of this operating manual.
• the electrical installation work has been completed properly.
• The power supply for the heat pump must be equipped with an all-pole automatic circuit-
breaker with at least 3 mm contact spacing to IEC 60947-2.
• The heating circuit is flushed, filled and thoroughly vented.
• All valves and shut-off devices of the heating circuit are open.
• All pipe systems and components of the system are leaktight.
Carefully fill out and sign the completion report for heat pump systems...
Manufacturer’s homepage.
Within Germany and Austria: Send completion report for heat pump systems
and general checklist to the manufacturer’s factory customer service department…
In other countries: Send completion report for heat pump systems
and general checklist to the manufacturer’s local partner…
The heat pump system is commissioned by customer service personnel authorised by the manufacturer. There is a fee for starting up!
PUMP SETTINGS FOR WWC 220HX AND WWC 280X
40 41
=
14
PP =
CP =
2 sec.
10 sec.Settings saved
PP CP
PP = Proportional Pressure short flashing
CP = Constant Pressure long flashing
Factory setting is Constant Pressure at Level 3.
For operation, the recirculation pump always has to be in the range „Constant Pressure“
.
23Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
INFORMATION FOR UNITS WITH INTEGRATED ELECTRIC HEATING ELEMENT
SAFETY TEMPERATURE LIMITER
A safety temperature limiter is installed in the electric heating element. If the heat pump fails or there is air in the system, check whether the reset button of this safety temperature limiter has sprung out. If necessary, push it back in again.
1 Safety temperature button on electric heating element
2 Reset button
Dismantling
DANGER! Risk of fatal electric shock! Electrical work may only be carried out by
qualified electricians.
Before opening the unit, safely disconnect the system from the power supply and prevent it from being switched back on!
WARNING! Only qualified heating or refrigerating
system personnel may dismantle the unit from the system.
IMPORTANT Recycle or ensure proper disposal of unit com-
ponents, refrigerants and oil according to the relevant regulations, standards and guidelines.
REMOVAL OF THE BUFFER BATTERY
IMPORTANT Before scrapping the heating and heat pump con-
troller, remove the buffer battery on the proces-sor board. The battery can be pushed out using a screwdriver. Dispose of battery and electronic components in an environmentally friendly way.
24 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Unit designationHeat pump type Brine/water ı Air/water ı Water/water • applicable ı — not applicable
Installation location Indoors ı Outdoors • applicable ı — not applicable
Conformity CE
Performance data Heating capacity/COP at
W10/W35 Standard point to EN14511 2 compressors 1 compressor
kW ı … kW ı …
W10/W45 Standard point to EN14511 kW ı …
W10/W35 Standard point acc. to EN255 2 compressors 1 compressor
kW ı … kW ı …
Limits of use Heating circuit °C
Heat source °C
additional operating points …
Sound Sound pressure level averaged at distance of 1m around the machine (in free field) dB(A)
Sound power level to EN12102 dB
Heat source Flow rate: minimum flow ı nominal flow ı maximum flow l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Recommended heat source pumpPower consumption of the heat source pump at nominal throughput kW
Nominal power / electricity consumption of heat source pump kW ı A
Total compression of the recommended heat source pump at nominal throughput bar
Dirt trap, to be installed upstream of the heat pump (included in additional box)Heating circuit Flow rate: minimum flow ı nominal flow ı maximum flow l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
General unit data Dimensions (see dimensioned drawing for the specified unit size) unit size
Total weight (including cooling) kg (kg)
Additional weight module 1 kg
Additional weight module 2 kg
Connections Heating circuit …
Heat source …
Refrigerant Refrigerant type ı Quantity … ı kg
Electrics Voltage code ı all-pole circuit breaker heat pump *) … ı A
Voltage code ı circuit breaker control voltage *) … ı A
Voltage code ı circuit breaker electric heating element *) ı A
Heat pump Effective power consumption in the standard point W10/W35 to EN14511: Power consumption ı current consumption ı cosφ kW ı A ı …
Maximum machine current within the use limits A
Starting current: direct ı with soft starter A ı A
Degree of protection IP
Output, electric heating element 3 ı 2 ı 1 phase kW ı kW ı kW
Components Circulation pump, heating circuit at nominal flow rate: Power consumption ı current consumption kW ı A
Circulation pump, heat source at nominal flow rate: Power consumption ı current consumption kW ı A
Passive cooling function Specification only for units with designator K: Cooling output at nominal flow rate (15°C heat source, 25°C heating water) kW
Safety equipment Safety component heating circuit ı Safety component heat source Incl. in scope of delivery: • yes — no
Heating and heat pump controller Incl. in scope of delivery: • yes — no
Electronic soft starter integrated: • yes — no
Expansion vessels Heat source: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Heating circuit: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Overflow valve integrated: • yes — no
Vibration decouplers Heating circuit ı heat source Incl. in scope of delivery: • yes — no
UK813241-a *) comply with local regulations n.d. = not detectable
Technical data / Scope of delivery
25Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
WWC220HX— ı — ı •
• ı —•
— 21,8 ı 5,7
——
21,8 ı 6,120 - 65 7 - 25
—4356
4400 ı 4400 ı 77000,23 ( —) ı 4400
—Grundfos SP 5A-6
0,540,55 ı 2,2
2,676/4“
1900 ı 3700 ı 4700—
0,61 ( —) ı 37001
235 (—)——
R 5/4“ AGR 5/4“ AG
R407c ı 4,53~/PE/400V/50Hz ı C13
1~/N/PE/230V/50Hz ı B103~/N/PE/400V/50Hz ı C16
3,82 ı 7,0 ı 0,7911,0
— ı 3020
9 ı 6 ı 30,18 ı n.n.
— ı ——
• ı —••
— ı — ı —• ı 50l ı 1,5
•• ı •
813237-g
Unit designationHeat pump type Brine/water ı Air/water ı Water/water • applicable ı — not applicable
Installation location Indoors ı Outdoors • applicable ı — not applicable
Conformity CE
Performance data Heating capacity/COP at
W10/W35 Standard point to EN14511 2 compressors 1 compressor
kW ı … kW ı …
W10/W45 Standard point to EN14511 kW ı …
W10/W35 Standard point acc. to EN255 2 compressors 1 compressor
kW ı … kW ı …
Limits of use Heating circuit °C
Heat source °C
additional operating points …
Sound Sound pressure level averaged at distance of 1m around the machine (in free field) dB(A)
Sound power level to EN12102 dB
Heat source Flow rate: minimum flow ı nominal flow ı maximum flow l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Recommended heat source pumpPower consumption of the heat source pump at nominal throughput kW
Nominal power / electricity consumption of heat source pump kW ı A
Total compression of the recommended heat source pump at nominal throughput bar
Dirt trap, to be installed upstream of the heat pump (included in additional box)Heating circuit Flow rate: minimum flow ı nominal flow ı maximum flow l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
General unit data Dimensions (see dimensioned drawing for the specified unit size) unit size
Total weight (including cooling) kg (kg)
Additional weight module 1 kg
Additional weight module 2 kg
Connections Heating circuit …
Heat source …
Refrigerant Refrigerant type ı Quantity … ı kg
Electrics Voltage code ı all-pole circuit breaker heat pump *) … ı A
Voltage code ı circuit breaker control voltage *) … ı A
Voltage code ı circuit breaker electric heating element *) ı A
Heat pump Effective power consumption in the standard point W10/W35 to EN14511: Power consumption ı current consumption ı cosφ kW ı A ı …
Maximum machine current within the use limits A
Starting current: direct ı with soft starter A ı A
Degree of protection IP
Output, electric heating element 3 ı 2 ı 1 phase kW ı kW ı kW
Components Circulation pump, heating circuit at nominal flow rate: Power consumption ı current consumption kW ı A
Circulation pump, heat source at nominal flow rate: Power consumption ı current consumption kW ı A
Passive cooling function Specification only for units with designator K: Cooling output at nominal flow rate (15°C heat source, 25°C heating water) kW
Safety equipment Safety component heating circuit ı Safety component heat source Incl. in scope of delivery: • yes — no
Heating and heat pump controller Incl. in scope of delivery: • yes — no
Electronic soft starter integrated: • yes — no
Expansion vessels Heat source: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Heating circuit: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Overflow valve integrated: • yes — no
Vibration decouplers Heating circuit ı heat source Incl. in scope of delivery: • yes — no
UK813241-a *) comply with local regulations n.d. = not detectable
WWC100HX— ı — ı •
• ı —•
— 11,0 ı 5,6
——
11,2 ı 5,720 - 65 7 - 25
—4053
2200 ı 2200 ı 41000,06 ( —) ı 2200
—Grundfos SP 3A-6
0,330,38 ı 1,4
3,005/4“
950 ı 1900 ı 2400—
0,34 ( —) ı 13501
213 (—)——
R 5/4“ AGR 5/4“ AG
R407c ı 2,953~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B103~/N/PE/400V/50Hz ı C10
1,96 ı 3,8 ı 0,745,9
30 ı —20
6 ı 4 ı 20,07 ı n.n.
— ı ——
• ı —•
—— ı — ı —• ı 25l ı 1,5
•• ı •
813233-e
WWC190HX— ı — ı •
• ı —•
— 18,6 ı 5,6
——
18,6 ı 5,720 - 65 7 - 25
—4053
3800 ı 3800 ı 65000,16 ( —) ı 3800
—Grundfos SP 3A-6
0,380,38 ı 1,4
1,765/4“
160 ı 3100 ı 3900—
0,52 ( — ) ı 22001
227 (—)——
R 5/4“ AGR 5/4“ AG
R407c ı 4,33~/PE/400V/50Hz ı C13
1~/N/PE/230V/50Hz ı B103~/N/PE/400V/50Hz ı C16
3,27 ı 6,0 ı 0,799,4
— ı 2820
9 ı 6 ı 30,17 ı n.n.
— ı ——
• ı —••
— ı — ı —• ı 35l ı 1,5
•• ı •
813236-d
WWC160HX— ı — ı •
• ı —•
— 14,7 ı 5,6
——
14,8 ı 5,720 - 65 7 - 25
—4053
3000 ı 3000 ı 52000,11 ( —) ı 3000
—Grundfos SP 3A-6
0,380,38 ı 1,4
2,575/4“
1300 ı 2500 ı 3100—
0,40 ( — ) ı 18001
219 (—)——
R 5/4“ AGR 5/4“ AG
R407c ı 3,953~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B103~/N/PE/400V/50Hz ı C16
2,6 ı 4,6 ı 0,817,5
— ı 2520
9 ı 6 ı 30,16 ı n.n.
— ı ——
• ı —••
— ı — ı —• ı 35l ı 1,5
•• ı •
813235-e
WWC130HX— ı — ı •
• ı —•
— 12,9 ı 5,5
——
12,7 ı 5,720 - 65 7 - 25
—4053
2600 ı 2600 ı 45000,1 ( —) ı 2600
—Grundfos SP 3A-6
0,380,38 ı 1,4
2,855/4“
1100 ı 2200 ı 2800—
0,46 ( —) ı 16001
216 (—)——
R 5/4“ AGR 5/4“ AG
R407c ı 3,53~/PE/400V/50Hz ı C10
1~/N/PE/230V/50Hz ı B103~/N/PE/400V/50Hz ı C10
2,35 ı 4,4 ı 0,776,9
— ı 2020
6 ı 4 ı 20,16 ı n.n.
— ı ——
• ı —••
— ı — ı —• ı 25l ı 1,5
•• ı •
813234-f
26 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Unit designationHeat pump type Brine/water ı Air/water ı Water/water • applicable ı — not applicable
Installation location Indoors ı Outdoors • applicable ı — not applicable
Conformity CE
Performance data Heating capacity/COP at
W10/W35 Standard point to EN14511 2 compressors 1 compressor
kW ı … kW ı …
W10/W45 Standard point to EN14511 kW ı …
W10/W35 Standard point acc. to EN255 2 compressors 1 compressor
kW ı … kW ı …
Limits of use Heating circuit °C
Heat source °C
additional operating points …
Sound Sound pressure level averaged at distance of 1m around the machine (in free field) dB(A)
Sound power level to EN12102 dB
Heat source Flow rate: minimum flow ı nominal flow ı maximum flow l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Recommended heat source pumpPower consumption of the heat source pump at nominal throughput kW
Nominal power / electricity consumption of heat source pump kW ı A
Total compression of the recommended heat source pump at nominal throughput bar
Dirt trap, to be installed upstream of the heat pump (included in additional box)Heating circuit Flow rate: minimum flow ı nominal flow ı maximum flow l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
General unit data Dimensions (see dimensioned drawing for the specified unit size) unit size
Total weight (including cooling) kg (kg)
Additional weight module 1 kg
Additional weight module 2 kg
Connections Heating circuit …
Heat source …
Refrigerant Refrigerant type ı Quantity … ı kg
Electrics Voltage code ı all-pole circuit breaker heat pump *) … ı A
Voltage code ı circuit breaker control voltage *) … ı A
Voltage code ı circuit breaker electric heating element *) ı A
Heat pump Effective power consumption in the standard point W10/W35 to EN14511: Power consumption ı current consumption ı cosφ kW ı A ı …
Maximum machine current within the use limits A
Starting current: direct ı with soft starter A ı A
Degree of protection IP
Output, electric heating element 3 ı 2 ı 1 phase kW ı kW ı kW
Components Circulation pump, heating circuit at nominal flow rate: Power consumption ı current consumption kW ı A
Circulation pump, heat source at nominal flow rate: Power consumption ı current consumption kW ı A
Passive cooling function Specification only for units with designator K: Cooling output at nominal flow rate (15°C heat source, 25°C heating water) kW
Safety equipment Safety component heating circuit ı Safety component heat source Incl. in scope of delivery: • yes — no
Heating and heat pump controller Incl. in scope of delivery: • yes — no
Electronic soft starter integrated: • yes — no
Expansion vessels Heat source: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Heating circuit: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Overflow valve integrated: • yes — no
Vibration decouplers Heating circuit ı heat source Incl. in scope of delivery: • yes — no
UK813241-a *) comply with local regulations n.d. = not detectable
Technical data / Scope of delivery
27Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
WWC280X— ı — ı •
• ı —•
— 27,0 ı 5,1
——
27,0 ı 5,220 - 60 7 - 25
—4760
5300 ı 5300 ı 93000,18 ( —) ı 5300
—Grundfos SP 8A-5
0,630,75 ı 2,3
2,406/4“
2300 ı 4600 ı 5800—
0,4 ( —) ı 46002
365 (—)——
R 6/4“ AGR 6/4“ AG
R407c ı 4,43~/PE/400V/50Hz ı C20
1~/N/PE/230V/50Hz ı B10— ı — ı —
5,29 ı 8,8 ı 0,8614,8
— ı 29,520
— ı — ı —0,22 ı n.n.
— ı ——
• ı —••
— ı — ı —• ı 50l ı 1,5
•• ı •
813238-e
Unit designationHeat pump type Brine/water ı Air/water ı Water/water • applicable ı — not applicable
Installation location Indoors ı Outdoors • applicable ı — not applicable
Conformity CE
Performance data Heating capacity/COP at
W10/W35 Standard point to EN14511 2 compressors 1 compressor
kW ı … kW ı …
W10/W45 Standard point to EN14511 kW ı …
W10/W35 Standard point acc. to EN255 2 compressors 1 compressor
kW ı … kW ı …
Limits of use Heating circuit °C
Heat source °C
additional operating points …
Sound Sound pressure level averaged at distance of 1m around the machine (in free field) dB(A)
Sound power level to EN12102 dB
Heat source Flow rate: minimum flow ı nominal flow ı maximum flow l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Recommended heat source pumpPower consumption of the heat source pump at nominal throughput kW
Nominal power / electricity consumption of heat source pump kW ı A
Total compression of the recommended heat source pump at nominal throughput bar
Dirt trap, to be installed upstream of the heat pump (included in additional box)Heating circuit Flow rate: minimum flow ı nominal flow ı maximum flow l/h
Pressure loss heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
Free compression heat pump ∆p (with cooling ∆pK) ı Flow rate bar (bar) ı l/h
General unit data Dimensions (see dimensioned drawing for the specified unit size) unit size
Total weight (including cooling) kg (kg)
Additional weight module 1 kg
Additional weight module 2 kg
Connections Heating circuit …
Heat source …
Refrigerant Refrigerant type ı Quantity … ı kg
Electrics Voltage code ı all-pole circuit breaker heat pump *) … ı A
Voltage code ı circuit breaker control voltage *) … ı A
Voltage code ı circuit breaker electric heating element *) ı A
Heat pump Effective power consumption in the standard point W10/W35 to EN14511: Power consumption ı current consumption ı cosφ kW ı A ı …
Maximum machine current within the use limits A
Starting current: direct ı with soft starter A ı A
Degree of protection IP
Output, electric heating element 3 ı 2 ı 1 phase kW ı kW ı kW
Components Circulation pump, heating circuit at nominal flow rate: Power consumption ı current consumption kW ı A
Circulation pump, heat source at nominal flow rate: Power consumption ı current consumption kW ı A
Passive cooling function Specification only for units with designator K: Cooling output at nominal flow rate (15°C heat source, 25°C heating water) kW
Safety equipment Safety component heating circuit ı Safety component heat source Incl. in scope of delivery: • yes — no
Heating and heat pump controller Incl. in scope of delivery: • yes — no
Electronic soft starter integrated: • yes — no
Expansion vessels Heat source: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Heating circuit: Scope of delivery ı Volume ı Initial pressure • yes — no ı l ı bar
Overflow valve integrated: • yes — no
Vibration decouplers Heating circuit ı heat source Incl. in scope of delivery: • yes — no
UK813241-a *) comply with local regulations n.d. = not detectable
WWC440X— ı — ı •
• ı —•
42,2 ı 5,3 21,3 ı 5,4
—42,2 ı 5,4 21,3 ı 5,5
20 - 60 7 - 25
—4760
8500 ı 8500 ı 147000,35 ( —) ı 8500
—Grundfos SP 8A-5
0,730,75 ı 2,3
2,06/4“
3600 ı 7200 ı 9000—
0,44 ( —) ı 52002
402 (—)——
R 6/4“ AGR 6/4“ AG
R407c ı 8,43~/PE/400V/50Hz ı C32
1~/N/PE/230V/50Hz ı B10— ı — ı —
2x 3,9 ı 2x 6,8 ı 0,832x 11,8
— ı 2220
— ı — ı —0,39 ı n.n.
— ı ——
• ı —••
— ı — ı —• ı 80l ı 1,5
•• ı •
813239-d
28 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Bezeichnung:
Seite: 1/1
Datei: 823201 Leistungs-Druckverlustkurve WWC100HX.xls
Leistungs-DruckverlustkurvenWWC100HX
Zeichnungsnummer: 823201
Änd./Ä.M./Ersteller/Datum
- / ÄM001-2007 / Neumann / 27.09.07
Legende: DE823000L
823201
“”
Freie Pressung Heizkreis
Volumenstrom Heizwasser
Volumenstrom Wärmequelle
Temperatur Wärmequelle
Heizleistung
Druckverlust Wärmequelle
“„
Temp„
Qh
Pe
COP
∆p”
∆p„
Leistungsaufnahme
Coeffiicient of performance / Leistungszahl
Qh (kW)
8
10
12
14
16
5 10 15 20 25 30
Temp„ (°C)
35°C
50°C
65°C
COP
1
2
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
Pe (kW)
0
1
2
3
4
5
5 10 15 20 25 30
Temp„ (°C)
∆p (bar)
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,0 0,5 1,0 1,5 2,0 2,5 3,0
“”
Δp”
∆p (bar)
0,0
0,1
0,2
0,3
0,4
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
“„
Δp„
Legend: UK823200
“” Heating water flow rate
“„ Heat source flow rate
Temp„ Heat source temperature
Qh Heating capacity
Pe Power consumption
COP Coefficient of performance / efficiency rating
∆p” Free compression, heating circuit
∆p„ Heat source pressure loss
CP Compressor
WWC 100H/X Performance curves
29Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbHBezeichnung:
Seite: 1/1
Leistungsaufnahme
Coeffiicient of performance / Leistungszahl
Temperatur Wärmequelle
Heizleistung
Druckverlust Wärmequelle
“„
Temp„
Qh
Pe
COP
∆p”
∆p„
Legende: DE823000L
823002-a
“”
Freie Pressung Heizkreis
Volumenstrom Heizwasser
Volumenstrom Wärmequelle
a /ÄM 013-2013 / Liška / 17.06.2013
Datei: 823202a Leistungs-Druckverlustkurve WWC130HX.xls
Leistungs-DruckverlustkurvenWWC130HX
Zeichnungsnummer: 823002-a
Änd./Ä.M./Ersteller/Datum
- / ÄM001-2007 / Neumann / 27.09.07
8
10
12
14
16
18
20
5 10 15 20 25 30
Temp„ (°C)
Qh (kW)
35°C
50°C
65°C
1
2
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
COP
0
1
2
3
4
5
5 10 15 20 25 30
Temp„ (°C)
Pe (kW)
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5
“”
∆p (bar)
∆p”
0,0
0,1
0,2
0,3
0,4
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
“„
∆p (bar)
∆p„
Legend: UK823200
“” Heating water flow rate
“„ Heat source flow rate
Temp„ Heat source temperature
Qh Heating capacity
Pe Power consumption
COP Coefficient of performance / efficiency rating
∆p” Free compression, heating circuit
∆p„ Heat source pressure loss
CP Compressor
Performance curves WWC 130H/X
30 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbHBezeichnung:
Seite: 1/1
Datei: 823203a Leistungs-Druckverlustkurve WWC160HX.xls
Leistungs-DruckverlustkurvenWWC160HX
Zeichnungsnummer: 823203-a
- / ÄM001-2007 / Neumann / 27.09.07
Legende: DE823000L
823203-a
“”
Freie Pressung Heizkreis
Coeffiicient of performance / Leistungszahl
Volumenstrom Heizwasser
Volumenstrom Wärmequelle
Temperatur Wärmequelle
Heizleistung
Änd./Ä.M./Ersteller/Datum
a /ÄM 013-2013 / Liška / 17.06.2013
Druckverlust Wärmequelle
“„
Temp„
Qh
Pe
COP
∆p”
∆p„
Leistungsaufnahme
12
14
16
18
20
22
5 10 15 20 25 30
Temp„ (°C)
Qh (kW)
35°C
50°C
65°C
1
2
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
COP
2
3
4
5
6
5 10 15 20 25 30
Temp„ (°C)
Pe (kW)
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0
“”
∆p (bar)
∆p”
0,0
0,1
0,2
0,3
0,4
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
“„
∆p (bar)
∆p„
Legend: UK823200
“” Heating water flow rate
“„ Heat source flow rate
Temp„ Heat source temperature
Qh Heating capacity
Pe Power consumption
COP Coefficient of performance / efficiency rating
∆p” Free compression, heating circuit
∆p„ Heat source pressure loss
CP Compressor
WWC 160H/X Performance curves
31Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbHBezeichnung:
Seite: 1/1
Änd./Ä.M./Ersteller/Datum
- / ÄM001-2007 / Neumann / 27.09.07
Legende: DE823000L
823204-a
a /ÄM 013-2013 / Liška / 17.06.2013
Datei: 823204a Leistungs-Druckverlustkurve WWC190HX.xls
Leistungs-DruckverlustkurvenWWC190HX
Zeichnungsnummer: 823204-a
“”
Freie Pressung Heizkreis
Volumenstrom Heizwasser
Volumenstrom Wärmequelle
Temperatur Wärmequelle
Heizleistung
Druckverlust Wärmequelle
“„
∆p”
∆p„
Leistungsaufnahme
Coeffiicient of performance / Leistungszahl
Temp„
Qh
Pe
COP
14
16
18
20
22
24
26
5 10 15 20 25 30
Temp„ (°C)
Qh (kW)
35°C
50°C
65°C
1
2
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
COP
2
3
4
5
6
7
5 10 15 20 25 30
Temp„ (°C)
Pe (kW)
0,00,10,20,30,40,50,60,70,80,91,0
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5
“”
∆p (bar)
∆p”
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5
“„
∆p (bar)
∆p„
Legend: UK823200
“” Heating water flow rate
“„ Heat source flow rate
Temp„ Heat source temperature
Qh Heating capacity
Pe Power consumption
COP Coefficient of performance / efficiency rating
∆p” Free compression, heating circuit
∆p„ Heat source pressure loss
CP Compressor
Legend: UK823200
“” Heating water flow rate
“„ Heat source flow rate
Temp„ Heat source temperature
Qh Heating capacity
Pe Power consumption
COP Coefficient of performance / efficiency rating
∆p” Free compression, heating circuit
∆p„ Heat source pressure loss
CP Compressor
Performance curves WWC 190H/X
32 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Bezeichnung:
Seite: 1/1
Datei: 823205a Leistungs-Druckverlustkurve WWC220HX.xls
Leistungs-DruckverlustkurvenWWC220HX
Zeichnungsnummer: 823205a a / ÄM007-2017 / Liska / 15.5.17
Legende: DE823000L
823205a
“”
Freie Pressung Heizkreis
Volumenstrom Heizwasser
Volumenstrom Wärmequelle
Änd./Ä.M./Ersteller/Datum
- / ÄM001-2007 / Neumann / 27.09.07
Druckverlust Wärmequelle
“„
Temp„
Qh
Pe
COP
∆p”
∆p„
Leistungsaufnahme
Coeffiicient of performance / Leistungszahl
Temperatur Wärmequelle
Heizleistung
18
20
22
24
26
28
30
5 10 15 20 25 30
Temp„ (°C)
Qh (kW)
35°C
50°C
65°C
1
2
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
COP
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
Pe (kW)
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0
“”
∆p (bar)
Δp”
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0
“„
∆p (bar)
Δp„
Legend: UK823200
“” Heating water flow rate
“„ Heat source flow rate
Temp„ Heat source temperature
Qh Heating capacity
Pe Power consumption
COP Coefficient of performance / efficiency rating
∆p” Free compression, heating circuit
∆p„ Heat source pressure loss
CP Compressor
WWC 220H/X Performance curves
33Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Bezeichnung:
Seite: 1/1
∆p”
∆p„
Leistungsaufnahme
Coeffiicient of performance / Leistungszahl
Temperatur Wärmequelle
Heizleistung
Änd./Ä.M./Ersteller/Datum
- / ÄM001-2007 / Neumann / 27.09.07
Druckverlust Wärmequelle
“„
Temp„
Qh
Pe
COP
Legende: DE823000L
823206a
“”
Freie Pressung Heizkreis
Volumenstrom Heizwasser
Volumenstrom Wärmequelle
Datei: 823206a Leistungs-Druckverlustkurve WWC280X.xls
Leistungs-DruckverlustkurvenWWC280X
Zeichnungsnummer: 823206a a / ÄM007-2017 / Liska / 15.5.17
22
24
26
28
30
32
34
36
38
5 10 15 20 25 30
Temp„ (°C)
Qh (kW)
35°C 50°C
1
2
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
COP
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
Pe (kW)
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
1,1
0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0
“”
∆p (bar)
Δp”
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0
“„
∆p (bar)
Δp„
Legend: UK823200
“” Heating water flow rate
“„ Heat source flow rate
Temp„ Heat source temperature
Qh Heating capacity
Pe Power consumption
COP Coefficient of performance / efficiency rating
∆p” Free compression, heating circuit
∆p„ Heat source pressure loss
CP Compressor
Performance curves WWC 280X
34 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Bezeichnung:
Seite: 1/1
Druckverlust Wärmequelle
“„
Temp„
Qh
Pe
COP
∆p”
∆p„
Leistungsaufnahme
Coeffiicient of performance / Leistungszahl
Volumenstrom Heizwasser
Volumenstrom Wärmequelle
Temperatur Wärmequelle
Heizleistung
Änd./Ä.M./Ersteller/Datum
- / ÄM001-2007 / Neumann / 27.09.07
Legende: DE823000L
823207
“”
Freie Pressung Heizkreis
Datei: 823207 Leistungs-Druckverlustkurve WWC440X.xls
Leistungs-DruckverlustkurvenWWC440X
Zeichnungsnummer: 823207
Qh (kW)
15
20
25
30
35
40
45
50
55
60
5 10 15 20 25 30
Temp„ (°C)
Vorlauf 35°C 2VD
Vorlauf 50°C 2VD
Vorlauf 35°C 1VD
Vorlauf 50°C 1VD
COP
2
3
4
5
6
7
8
5 10 15 20 25 30
Temp„ (°C)
Pe (kW)
2
4
6
8
10
12
5 10 15 20 25 30
Temp„ (°C)
∆p (bar)
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
1,1
1,2
0,0 1,0 2,0 3,0 4,0 5,0 6,0 7,0 8,0 9,0
“”
Δp”
∆p (bar)
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
1,1
1,2
0,0 2,0 4,0 6,0 8,0 10,0 12,0 14,0
“„
Δp„
Legend: UK823200
“” Heating water flow rate
“„ Heat source flow rate
Temp„ Heat source temperature
Qh Heating capacity
Pe Power consumption
COP Coefficient of performance / efficiency rating
∆p” Free compression, heating circuit
∆p„ Heat source pressure loss
CP Compressor
WWC 440X Performance curves
35Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
0
650
0
1550
1680
7
6
0
50
500565
0
658
14581380
0230
392
514
5
C
EA
1
2
3
4
87654321
www.alpha-innotec.deD - 95359 Kasendorf
Industriestraße 3Alpha-InnoTec GmbH
Schutz
verme
rk nach
DIN 3
4 beac
hten
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
BenennungMaßbildWWC 100H/X bis WWC 220H/X
819258 ba-Zust. Änderungstext
PEP 009/2006
ÄM 001/2007
ÄM 001/2007
Datum21.8.200621.5.20071.10.2007
DMVon
HaderdauerDM Blatt
von
Werkstoff Gewicht
Maßstab 1:15 Det. Maßstab
Datum NameErstelltGepr.Norm.
17.8.2006 Markieton2.10.2007 Markieton
toleranzAllgemein-
DIN ISO 2768 -c
Oberflächen
ArtikelNr.
Legend: UK819258bAll dimensions in mm.
A Front viewC Top viewE Rear view
Item Designation Dim.1 Heating water inlet (return); flat seat G 1 1/4"2 Heating water outlet (flow): flat seat G 1 1/4"3 Heat source inlet at the unit; flat seat G 1 1/4"4 Heat source outlet at the unit; flat seat G 1 1/4"5 Penetration for electric/sensor cables ---6 Safety assembly (in extra box) ---7 Control panel (in extra box) ---
Dimensional drawings WWC 100H/X – WWC 220H/X
36 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
RH
1690
1
OKF
> 25
0
2 2
800
>155
0
>800
FS
Legende: D819260a Technische Änderungen vorbehalten. Alle Maße in mm.
RH Raumhöhe min. 2000 OKF Oberkante Fertigfußboden FS Schraffierte Fläche Freiraum für Servicezwecke. 1 Geräteaufstellung auf Sylomerstreifen (im Beipack). 2 20 Abstand zum nächsten Objekt.
87654321
www.alpha-innotec.deD - 95359 Kasendorf
Industriestraße 3Alpha-InnoTec GmbH
Schutz
verme
rk nach
DIN 3
4 beac
hten
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
BenennungAufstellungsplanWWC 100H/X bis WWC 220H/X
819260 a-Zust. Änderungstext
PEP 009/2006
ÄM 001/2007
Datum18.8.20062.10.2007
DMVon
DM Blatt
von
Werkstoff Gewicht
Maßstab 1:25 Det. Maßstab
Datum NameErstelltGepr.Norm.
18.8.2006 Markieton2.10.2007 Markieton
toleranzAllgemein-
DIN ISO 2768 -c
Oberflächen
ArtikelNr.
Legend: UK819260aAll dimensions in mm.
RH Minimum room height 2000OKF Finished floor levelFS Shaded area = free space for service purposes
1 Unit installation on Sylomer strips (in extra box)2 20 Distance to next object
WWC 100H/X – WWC 220H/X Installation plan
37Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
0
650
0
1550
1680
7
6
0
50
500565
0
658
14581380
0230
392
514
5
C
EA
1
2
3
4
87654321
www.alpha-innotec.deD - 95359 Kasendorf
Industriestraße 3Alpha-InnoTec GmbH
Schutz
verme
rk nach
DIN 3
4 beac
hten
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
BenennungMaßbildWWC 100H/X bis WWC 220H/X
819258 ba-Zust. Änderungstext
PEP 009/2006
ÄM 001/2007
ÄM 001/2007
Datum21.8.200621.5.20071.10.2007
DMVon
HaderdauerDM Blatt
von
Werkstoff Gewicht
Maßstab 1:15 Det. Maßstab
Datum NameErstelltGepr.Norm.
17.8.2006 Markieton2.10.2007 Markieton
toleranzAllgemein-
DIN ISO 2768 -c
Oberflächen
ArtikelNr.
Legend: UK819258bAll dimensions in mm.
A Front viewC Top viewE Rear view
Item Designation Dim.1 Heating water inlet (return); flat seat G 1 1/4"2 Heating water outlet (flow): flat seat G 1 1/4"3 Heat source inlet at the unit; flat seat G 1 1/4"4 Heat source outlet at the unit; flat seat G 1 1/4"5 Penetration for electric/sensor cables ---6 Safety assembly (in extra box) ---7 Control panel (in extra box) ---
Dimensional drawings WWC 280X
38 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
0
1650
1780
0
750
7
6
0
50
650715
0
700
152014191344
0255
413
580
5
4
1
23
EA
C
87654321
www.alpha-innotec.deD - 95359 Kasendorf
Industriestraße 3Alpha-InnoTec GmbH
Schutz
verme
rk nach
DIN 3
4 beac
hten
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
BenennungMaßbildWWC 440X
819263 ba-Zust. Änderungstext
PEP 009/2006
ÄM 001/2007
ÄM 001/2007
Datum21.8.200621.5.20071.10.2007
DMVon
HaderdauerDM Blatt
von
Werkstoff Gewicht
Maßstab 1:20 Det. Maßstab
Datum NameErstelltGepr.Norm.
18.8.2006 Markieton2.10.2007 Markieton
toleranzAllgemein-
DIN ISO 2768 -c
Oberflächen
ArtikelNr.
Legend: UK819258bAll dimensions in mm.
A Front viewC Top viewE Rear view
Item Designation Dim.1 Heating water inlet (return); flat seat G 1 1/4"2 Heating water outlet (flow): flat seat G 1 1/4"3 Heat source inlet at the unit; flat seat G 1 1/4"4 Heat source outlet at the unit; flat seat G 1 1/4"5 Penetration for electric/sensor cables ---6 Safety assembly (in extra box) ---7 Control panel (in extra box) ---
WWC 440X Dimensional drawings
39Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
RH
<179
0
1
OKF
>300
800
22
>175
0
> 800
FS
Legende: D819265a Technische Änderungen vorbehalten. Alle Maße in mm.
RH Raumhöhe min. 2000 OKF Oberkante Fertigfußboden FS Schraffierte Fläche Freiraum für Servicezwecke. 1 Geräteaufstellung auf Sylomerstreifen (im Beipack). 2 20 Abstand zum nächsten Objekt.
87654321
www.alpha-innotec.deD - 95359 Kasendorf
Industriestraße 3Alpha-InnoTec GmbH
Schutz
verme
rk nach
DIN 3
4 beac
hten
1
1
Ers. d. Ers. f.
A
B
C
D
E
F F
E
D
C
B
A
4321
BenennungAufstellungsplanWWC 280X bis WWC 440X
819265 a-Zust. Änderungstext
PEP 009/2006
ÄM 001/2007
Datum21.8.20062.10.2007
DMVon
DM Blatt
von
Werkstoff Gewicht
Maßstab 1:25 Det. Maßstab
Datum NameErstelltGepr.Norm.
18.8.2006 Markieton2.10.2007 Markieton
toleranzAllgemein-
DIN ISO 2768 -c
Oberflächen
ArtikelNr.
Legend: UK819260aAll dimensions in mm.
RH Minimum room height 2000OKF Finished floor levelFS Shaded area = free space for service purposes
1 Unit installation on Sylomer strips (in extra box)2 20 Distance to next object
Installation plan WWC 280X – WWC 440X
40 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
WWC 100H/X – WWC 220H/X Default
41Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Separate buffer tank WWC 100H/X – WWC 220H/X
42 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
WWC 280X – WWC 440X Default
43Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Separate buffer tank WWC 280X – WWC 440X
44 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Lege
nd h
ydra
ulic
dia
gram
m14
0304
1H
eat p
ump
51S
eper
atio
n ta
nkTA
/AE
xter
nal s
enso
r2
Und
erflo
or h
eatin
g / r
adia
tors
52G
as- o
r oil-
boile
rTB
W/B
Dom
estic
hot
wat
er s
enso
r3
Vib
ratio
n is
olat
ion
53W
ood
boile
rTB
1/C
Feed
wat
er s
enso
r mix
er c
ircui
ts 1
4S
ylom
er s
trip
mac
hine
und
erla
y54
Hot
wat
er c
ylin
der
DFl
oor t
mpe
ratu
re li
mite
r5
Clo
sure
and
dra
inag
e55
Brin
e pr
essu
re s
witc
hTR
L/G
Sen
sor e
xter
nal r
etur
n6
Exp
ansi
on v
esse
l pac
king
list
56S
wim
min
g po
ol h
eat e
xcha
nger
STA
Line
pre
ssur
e re
gula
tor v
alve
7S
afet
y va
lve
57G
eoth
erm
al h
eat e
xcha
nger
TRL/
HS
enso
r ret
urn
(hyd
raul
ic m
odul
e, d
ual)
8C
losu
re
58V
entil
atio
n sy
stem
9H
eatin
g ci
rcul
atio
n pu
mp
59P
late
hea
t exc
hang
er79
Mot
or v
alve
10N
on re
turn
val
ve/ o
ne w
ay v
alve
61C
oolin
g cy
linde
r80
Mix
ing
valv
e11
Indi
vidu
al ro
om re
gula
tion
65C
ompa
ct d
istri
buto
r81
Spl
it he
at p
ump
outd
oor u
nit
12O
verfl
ow v
alve
66Fa
ncoi
ls82
Spl
it he
at p
ump
indo
or u
nit
13S
team
tight
insu
latio
n67
Sol
ar/ s
ervi
ce w
ater
cyl
inde
r83
Circ
ulat
ion
pum
p14
Ser
vice
wat
er c
ircul
atio
n pu
mp
68S
olar
/ ser
vice
wat
er c
ylin
der
84S
witc
hing
val
ve15
Mix
er c
ircui
t thr
ee-w
ay m
ixer
(MK
1 di
scha
rge)
69M
ultif
unct
ion
tank
113
Con
nect
ion
2nd
heat
gen
erat
or
16
Exp
ansi
on v
esse
l sup
plie
d by
cus
tom
er71
Dua
l hyd
raul
ic m
odul
eB
T1O
utdo
or te
mpe
ratu
re s
enso
r18
Hea
ting
rod
(hea
ting)
72B
uffe
r tan
k w
all m
ount
edB
T2Fl
ow te
mpe
ratu
re s
enso
r 19
Mix
er c
ircui
t fou
r-w
ay m
ixer
(MK
1 ch
arge
)73
Pip
e le
ad-in
BT3
Ret
urn
tem
pera
ture
sen
sor
20H
eatin
g ro
d (S
W)
74V
ento
wer
BT6
Dom
estic
hot
wat
er te
mpe
ratu
re s
enso
r21
Mix
er c
ircui
t circ
ulat
ion
pum
p (F
P1)
75S
cope
of d
eliv
ery,
hyd
raul
ic to
wer
, dua
lB
T12
Flow
tem
pera
ture
liqu
efie
r23
Feed
circ
ulat
ing
pum
p (r
econ
nect
the
inte
grat
ed c
ircul
atin
g pu
mp
in th
e he
at p
ump)
76Fr
esh
wat
er s
tatio
nB
T19
Tem
pera
ture
sen
sor i
mm
ersi
on h
eate
r
24M
anifu
ld77
Sco
pe o
f sup
ply
wat
er/w
ater
boo
ster
BT2
4Te
mpe
ratu
re s
enso
r 2nd
hea
t gen
erat
or25
Hea
ting
circ
ulat
ion
pum
p78
Acc
esso
ries
wat
er/w
ater
boo
ster
opt
iona
l26
Sw
itchi
ng v
alve
(hea
ting/
serv
ice
wat
er)(
B =
norm
ally
ope
n)27
Hea
ting
elem
ent
28B
rine
circ
ulat
ion
pum
pC
omfo
rt bo
ard:
29D
irt-tr
ap 0
.6 m
m m
esh
15M
ixer
circ
uit t
hree
-way
mix
er (M
K2-
3 di
scha
rge)
30S
pill-
tray
für b
rine
mix
100
Roo
m th
erm
osta
t for
coo
ling
(opt
iona
l)17
Tem
pera
ture
diff
eren
ce re
gula
tor
31W
all b
reak
thro
ugh
101
Con
trols
sup
plie
d by
cus
tom
er19
Mix
er c
ircui
t fou
r-w
ay m
ixer
(MK
2 ch
arge
)32
Inle
t pip
e10
2D
ew-p
oint
mon
itor (
optio
nal)
21M
ixer
circ
uit c
ircul
atio
n pu
mp
(FP
2-3)
33B
rine
man
ifuld
103
Roo
m th
erm
osta
t for
refe
renc
e sp
ace
in p
acki
ng li
st22
Sw
imm
ing
pool
circ
ulat
ing
pum
p34
Gro
und
colle
ctor
104
Sup
ply
heat
pum
p44
Thre
e-w
ay m
ixer
val
ve (c
oolin
g fu
nctio
n M
K2)
35G
roun
d sl
inki
es10
5C
oolin
g ci
rcui
t mod
ule
box
rem
ovea
ble
for i
nsta
llatio
n47
C
hang
eove
r val
ve s
wim
min
g ba
th p
repa
ratio
n(B
= no
rmal
ly o
pen)
36G
roun
dwat
er s
prin
g pu
mp
106
Spe
cific
gly
cole
mix
ture
60C
hang
eove
r val
ve c
oolin
g op
erat
ion(
B =
norm
ally
ope
n)37
Wal
l bra
cket
107
Sca
ld p
rote
ctio
n / t
herm
osta
tic m
ixer
val
ve62
Hea
t met
er (o
ptio
nal)
38Fl
ow s
witc
h10
8S
olar
pum
p as
sem
bly
63C
hang
eove
r val
ve s
olar
circ
uit(B
= n
orm
ally
ope
n)39
Suc
tion
wel
l10
9O
verfl
ow v
alve
mus
t be
clos
ed64
Coo
ling
circ
ulat
ion
pum
p40
Inve
rted
wel
l11
0P
acki
ng li
st h
ydra
ulic
tow
er70
Sol
ar s
eper
atio
n m
odul
e41
Rin
se fi
tting
hea
ting
circ
uit
111
Mou
ntin
g fo
r add
ition
al h
eatin
g el
emen
tTB
2-3/
CFe
edw
ater
sen
sor m
ixer
circ
uits
2-3
42C
ircul
atio
n pu
mp
112
Min
imum
dis
tanc
e to
ther
mal
dec
oupl
ing
of th
e m
ixin
g va
lve
TSS
/ES
enso
r, te
mpe
ratu
re d
iffer
ence
con
trol (
low
tem
pera
ture
)43
Brin
e / W
ater
hea
t exc
hang
er (c
oolin
g fu
nctio
n)TS
K/E
Sen
sor,
tem
pera
ture
diff
eren
ce c
ontro
l (hi
gh te
mpe
ratu
re)
44Th
ree-
way
mix
er v
alve
(coo
ling
func
tion
MK
1)TE
E/F
Sen
sor e
xter
nal e
nerg
y so
urce
45C
ap v
alve
46Fi
ller a
nd d
rain
age
valv
e48
Dom
estic
hot
wat
er c
harg
ing
pum
p49
Dire
ctio
n of
gro
undw
ater
flow
50B
uffe
r sto
rage
Impo
rtant
not
ice
!
Thes
e hy
drau
lic d
iagr
ams
are
sche
mat
ic re
pres
enta
tions
and
are
for a
ssis
tanc
e on
ly. T
hey
do n
ot re
lieve
of t
he o
blig
atio
n to
car
ry o
ut a
ppro
pria
te p
lann
ing!
The
y do
not
incl
ude
all n
eces
sary
shu
t-off
valv
es, v
entil
ator
fit
tings
or s
afet
y de
vice
s. T
hese
mus
t be
inco
rpor
ated
in a
ccor
danc
e w
ith th
e st
anda
rds
and
regu
latio
ns a
pplic
able
to th
e re
spec
tive
inst
alla
tion.
All
coun
try-s
peci
fic s
tand
ards
, law
s an
d re
gula
tions
mus
t be
obse
rved
! The
tu
bes
have
to b
e di
men
sion
ed a
ccor
ding
to th
e no
min
al v
olum
e flo
w o
f the
hea
t pum
p re
sp. t
he fr
ee p
ress
ing
of th
e in
tegr
ated
circ
ulat
ing
pum
p. F
or d
etai
led
info
rmat
ion
and
advi
ce p
leas
e co
ntac
t our
loca
l sal
es p
artn
er!
45Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
M3
UV
WP
E
-M3
We
ll pum
p
-F12
-F10
-F11
A1
A2
Well pum
p
Flow
switch: Internally w
ired
3~N/PE/400V/50Hz
M3
AS
D
X7:P
E,N
,L1
ZW2/SST
X0-X
4
X7:P
E,N
,L1,L2,L3
3
X7:P
E,L1,L2,L3
X7
L3
Term
inals
Well pum
p
Auxiliary circulation pum
p
Auxiliary heating 3 x 400V
M
-X3
Pow
er supply compressor 3 x 400V
; Attention: R
ight-hand rot. field is mandatory!
TB1
N
ZU
P
ZW
1
3-pol. Cu
t out compressor; A
ttention: Right-hand
rot. field is mandatory!
Function
-X0
GND
Control signal of add
itional heat generator 1; internally w
ired
Term
inal strips on controller board (see sticker)
A1
VB
O
F11
VBO
Control 2
30VT
ermin
al strip in switchbox of hea
t pump; N
/PE
distribution for external 230V
units
A2
MA1
A3
N
A3
PE
TBW
5
MOT
Nam
e
Accessories: P
rocess water for cha
ngeover valve
L3
ZUP
N
2
F12
PE
A1
Cut out a
uxiliary heating
ZW
1
L2
ZW
2/SS
T
EV
U
L1S
ub-distribution unit internal installation
-X2
Wate
r Wate
r Co
mp
ac
t 10
- 22
kW
GND
N
L1T
BW
TA
PE
TBW
HU
P
L1
Heating circuit circulation pum
p; internally w
ired
FP1
BUP
Accessories: P
rocess water sensor/therm
ostat
A2
HUP
PEX
TA
L1
Sensor m
ixing circuit 1
3
N
MO
T
Charge/discharge 1 o
pen
TB1
Accessories: R
emote control
TRL
4
-X7
TA
Leg
en
d:
EVU
Overloa
d protection; internally wire
d
BU
P
PE
circulation pump
ZIP
TB
1
no function
ZIP
ZW
2C
ontrol signal of additional heat g
enerator 2 (alternative is general malfunction)
MZIP
1
3~PE/400V/50Hz
-X4
PE
Charge/discharge 1 closed
PE
X
2
MZ1
MIS
Term
inals in heat pum
p switchbox
PE
Pum
p for mixing circuit 1
L2
M
Energy supplier contact; close
d on release; bridge if no blocking inte
rval
RFV
FP
1
UK
83
1150a
PE
Controller board; A
ttention: I-max =
6A
/230VA
C
GND
BU
P
L1
N
External return sensor
RF
V
Cut out controller unit
L1
MZ
1/MIS
N
GND
ZW1
EV
U
ASD
GND
TR
L
MA
1/MIS
N
PE
PE
GND
External sensor
FP
1
1~N/PE/230V/50Hz
RFV
F10
18.0
2.2
016
1
Achim
Pfleg
er
10X281 - 1
0X2
85
-
1/1
Achim
Pfleg
er1
7.11.2
008
Term
inal diagram W
WC
100-220 H LU
X2
831150
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
aÄ
M 999/2016
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
Terminal diagram WWC 100H/X – WWC 220H/X
46 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
-F10
-F11
M3
UV
WP
E
-M3
Well pu
mp
A1
A2
ZIP
circulation pump
ZIP
M
X7
X0-X
4
X7:P
E,L1,L2,L3
Term
inals
AS
D
Control signal of add
itional heat generator 1; internally w
ired
Auxiliary circulation pum
p
MA1
ZW2/SST
-X0
Control signal of add
itional heat generator 2 (alternative is general m
alfunction)
ZU
P
2
Well pum
p
X7:P
E,N
,L1A
uxiliary heating 3 x 400VX
7:PE
,N,L1,L2,L3
Flow
switch: Internally w
ired
A1
A2
Leg
en
d:
Term
inal strips on controller board (see sticker)
GNDTA
GND
3-pol. Cu
t out compressor; A
ttention: Right-hand
rot. field is mandatory!
Pow
er supply compressor 3 x 400V
; Attention: R
ight-hand rot. field is mandatory!
Term
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
-X3
ZW
2/SS
T
A2
F11
Control 2
30V
VB
O
TB1
Accessories: P
rocess water sensor/therm
ostat
1
L1A3
Nam
e
Accessories: P
rocess water for cha
ngeover valve
N
L1
ZUPBU
P
2
N
PE
L1
ZW
1
TBW
MOT
A1
-X2
Heating circuit circulation pum
p; internally w
ired
TA
TB
W
M
Wate
r Wate
r Co
mp
ac
t 28
- 44
kW
GND
A3
L3
BUP
FP1
VBO
ZW
1
EV
U
ZW
2/SS
T
HUP
TBW
HU
P
MIS
GND
TB1
Sensor m
ixing circuit 1
PEX
3
Charge/discharge 1 o
pen
-X7
MA
1/MIS
TA
Accessories: R
emote control
L1
EVU
TRL
TR
L
Overloa
d protection; internally wire
d
PE
PE
3~PE/400V/50Hz
MO
T
PE
Well pum
p
ZIP
PE
M3
PE
N
PE
External return sensor
PE
X
Charge/discharge 1 closed
no function
TB
1
-X4
Pum
p for mixing circuit 1
F10
PE
M
RF
V
RFV
L1
UK
83
1151a
Energy supplier contact; close
d on release; bridge if no blocking inte
rval
FP
1
3
Sub-distribution unit intern
al installation
Controller board; A
ttention: I-max =
6A
/230VA
C
BU
P
L2
Term
inals in heat pum
p switchbox
Function
Cut out controller unit
N
PE
N
MZ
1/MIS
ASD
EV
U
4
MZ1
N
N
RFV
GND
External sensor
ZW1
GND
1~N/PE/230V/50Hz
FP
1
18.0
2.2
016
1
Achim
Pfleg
er
10X286 - 1
0X2
87
-
1/1
Achim
Pfleg
er1
7.11.2
008
Term
inal diagram W
WC
280-440 LUX
2831151
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
aÄ
M 999/2016
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
WWC 280X – WWC 440X Terminal diagram
47Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
L1
-X7
L2L3
NP
E
12
-K1
/2.3
34
M3
T1
T2
T3
PE
-M1
VD
1
56
12
-K3
/2.13
-X7
34
13
5
24
6-F
3
M3
UV
WP
E
-M3
Wellpum
p
56
PE
L1
-X7
L2L3
NP
E
12
-K5
/2.13
34
56
L1L2
L312
14
11
-B1
AS
D/2.1
DF
S/2.1
9596/2.6
3
BO
SU
P
Term
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
ws
sw
3~N
/PE
/400V/5
0Hz
Leg
en
d:
X7
-R1 br
Contactor w
ell pump
3~P
E/400V
/50Hz
br
R1
M3
Com
pressor 1
K1
Function
Pow
er supply compressor; right-hand rot. field is m
andatory!
K5
ZW
1
ZW
1
Wellpum
p
Motor protection sw
itch wellpum
p
1
sw
Phase sequence relay; if phase seque
nce in the ord
er of 11 +
14 is closed
br
B1
Contactor for auxiliary heating
VD
1
3
2 1
4w
s6 5
M1
VB
O
F3
3~N
/PE
/400V/50H
z
3~PE
/400V/50H
z
Operating m
aterials
VD
1
UK
81
7288c
sw
Auxiliary heating
Pow
er supply aux. heating
2
Contactor for com
pressor 1K
3
gr
WW
C 100H
LUX
2817288
Achim
Pfleg
er0
2.12.2
008
cÄ
M 013/2013
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516 1
/3
1
21.0
5.2
013
ÄM
033/2012b
Achim
Pfleg
er
10X481
Blatt-N
r.
Zusta
ndÄ
nde
rung
Bea
rb.
Datu
mN
ame
Bl vo
n An
z
Datu
m
Circuit diagram 1/3 WWC 100H/X
48 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
DF
S
AS
D
L-X
0
L
-X7
NN
PE
PE
N..
-X1
P+
-
b2c4a1
-F1
HD
P
HD.
VD1
-X1
A1
A2
-K1
VD
1
ND.
-X1
P-
+
c4b2a1
-F2
ND
P
L..
L-X
0L12
-F6D
FS
L
MOT
-X2
9596
-F3
/1.7
ASD
-X2
EVU
-X2
HUP
-X3
M1
LN
PE
-M4
HU
P
M1
brbl
PE
brblbk
-M5
HU
P
0-10V/3.13
GN
D/3.13
BUP
-X3
12
-Y1
VBO
-X3
A1
A2
-K3
VB
O
ZW1
-X3
ϑ
-ST
B
A1
A2
-K5
ZW
1
MA1
-X3
MZ1
M1
AZ
NP
E
-M16
MIS
12
/1.103
4/1.10
56
/1.10
12
/1.73
4/1.7
56
/1.7
12
/1.23
4/1.2
56
/1.2
Heating pum
p energy efficiency; installed in the Energy E
fficiency optionH
UP
M6
Operating m
aterials
Y1
2
Contactor for com
pressor 1
BU
P
Safety tem
perature limiter heating
element
sw
Accessories: P
rocess water for cha
ngeover valve
-A1
M16
VD
1
Leg
en
d:
Contactor for auxiliary heating
Controller supply
MIS
1
1~N/P
E/230V
/50Hz
Mixer; installed w
ith cooling option
K3
VB
O
Heating pum
p; not required in the En
ergy Efficiency option
Contactor w
ell pump
ST
B
3
bl
High-pressu
re switch
1~N
/PE
/230V/50H
z
UK
81
7288c
sw
1
Controller board; A
ttention: I-max =
6A
/230VA
C
2
ZW
1
F3
Function
X7
bl
M4
Term
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
F1
F6
Flow
rate switch
swsw
EV
U
Low-pressure sw
itchF
2
K5
ND
P
23
0V
AC
K1
A1
Motor protection sw
itch wellpum
p
2
1
EV
U
br
Energy supplier contact; close
d on release; bridge if no blocking inte
rvalH
DP
rt
HU
P
WW
C 100H
LUX
2817288
Achim
Pfleg
er1
7.05.1
999
cÄ
M 013/2013
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516 2
/3
2
21.0
5.2
013
ÄM
033/2012b
Esch
er F.
10X481
Blatt-N
r.
Zusta
ndÄ
nde
rung
Bea
rb.
Datu
mN
ame
Bl vo
n An
z
Datu
m
WWC 100H/X Circuit diagram 2/3
49Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
ϑ
RFV
-X4
-R1
0
RF
V
GND
ϑ
TB1
-X4
-R1
3
TB
1
GND
TR ϑ
TBW
-X4
-R9
TB
W
GND
ϑ
TA.
-X4
-R8
TA
GND
ϑ
TRL
-X5
-R4
TR
L
GND
ϑ
TVL
-X5
-R5
TV
L
GND
ϑ
THG
-X5
-R6
TH
G
GND
ϑ
TWA
-X5
-R11
TW
A
GND
CW.
-X5
-R12
GND
ϑ
TWE
-X5
-R7
TW
E
GND
AIn
-X6yellow
white
Green
Brown
-B2
Flow
sensor;
GND
AO1
0-10V/2.10
GN
D/2.10
AO2
-X6
GND
Flow
Sensor: insta
lled in the Energy E
fficiency optionA
nalogue output 2
AO
2B
2
Analo
gue inputA
InA
O1
Analo
gue output 1
R13
-A1
-A6
Operating m
aterials
BW
TT
B1
A1
R4
Leg
en
d:
CW
Y4
External sensor
R8
Function
Controller board; A
ttention: I-max =
6A
/230VA
C
-CW
TR
L
R11
TW
E
Dom
estic hot wate
r sensor
Return sensor
BW
TH
eat source input se
nsor
TV
L
Accessories: R
emote control
UK
81
7288c
Sensor m
ixing circuit 1; installed w
ith cooling option
-Y4
TW
A
A6
Com
fort board: installed in the Ene
rgy Efficiency option
RF
V
R12
TB
WT
A
Accessories: P
rocess water for therm
osta
t
R7
R9
Hot gas sensor
Heat source
output sensor
Flow
sensor
Encoding, heat pum
p; 3480 Ohm
TH
GR
6R
5
R10
WW
C 100H
LUX
2817288
Achim
Pfleg
er1
7.05.1
999
cÄ
M 013/2013
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516 3
/3
3
21.0
5.2
013
ÄM
033/2012b
Esch
er F.
10X481
Blatt-N
r.
Zusta
ndÄ
nde
rung
Bea
rb.
Datu
mN
ame
Bl vo
n An
z
Datu
m
Circuit diagram 3/3 WWC 100H/X
50 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
L1
-X7
L2L3
NP
E
12
-K1
/2.3
34
L1L2
L3
T1
T2
T3
-N1
M3
T1
T2
T3
PE
-M1
VD
1
56
12
-K3
/2.12
-X7
34
13
5
24
6-F
3
M3
UV
WP
E
-M3
Wellpu
mp 56
PE
L1
-X7
L2L3
NP
E
12
-K5
/2.13
34
56
L1L2
L312
14
11
-B1
AS
D/2.1
DF
S/2.1
9596/2.6
12
34
56
ws
brsw sw
B1
Phase sequence relay; if phase seque
nce in the ord
er of 11 +
14 is closed
gr
Contactor for auxiliary heating
3~N/P
E/400V
/50Hz
Leg
en
d:
33~P
E/400V
/50Hz
Function
Term
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
Com
pressor 1K
5
M3
3~N
/PE
/400V/50H
z
Wellpum
p
brsw
-R1
2
Pow
er supply compressor; right-hand rot. field is m
andatory!P
ower supply aux. he
ating
Auxiliary heating
M1
Motor protection sw
itch wellpum
p
UK
81
7289d
1
br
F3
ws
VB
O
3~P
E/400V
/50Hz
VB
OS
tarting current limit
K1
Contactor for com
pressor 1
R1
ZW
1
Operating m
aterials
VD
1
X7 N1
K3
VD
1
ZW
1C
ontactor well pum
p08.1
2.2
015
ÄM
013/2013
1
Achim
Pfleg
er
10X482 - 1
0X4
85;
c
1/3
Achim
Pfleg
er0
2.12.2
008
WW
C 130-220H
LUX
2817289
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
dÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
WWC 130H/X – 220H/X Circuit diagram 1/3
51Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
DF
S/1.15
AS
D/1.15
L-X
0
L
-X7
NN
PE
PE
N..
-X1
P+
-
b2c4a1
-F1
HD
P
HD.
VD1
-X1
A1
A2
-K1
VD
1
ND.
-X1
P-
+
c4b2a1
-F2
ND
PL..
L-X
0
12
-F6
DF
S
LL
9596
-F3
/1.8
MOT
-X2
ASD
EVU
HUP
-X3
M1
LN
PE
-M4
HU
P
M1
brbl
PE
brblbk
-M6
HU
P
0-10V/3.12
GN
D/3.12
BUP
-X3
12
-Y1
VBO
-X3
A1
A2
-K3
VB
O
ZW1
-X3
ϑ
-ST
B
A1
A2
-K5
ZW
1
MA1
-X3
MZ1
M1
AZ
NP
E
-M16
MIS
12
/1.113
4/1.11
56
/1.11
12
/1.73
4/1.8
56
/1.8
12
/1.43
4/1.4
56
/1.4
K3
1
Term
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
VD
1
Operating m
aterials
2sw
F3
MIS
Safety tem
perature limiter heating
element
Contactor for com
pressor 1
sw
F1
sw
UK
81
7289d rt
F6
VB
O
Mixer; installed w
ith cooling option
Flow
rate switch
ZW
1
K1
Contactor w
ell pump
M16
HU
P
Motor protection sw
itch wellpum
p
X7
HU
PM
6
bl
bl
Heating pum
p energy efficiency; installed in the Energy E
fficiency option
sw
3
Leg
en
d:
Function
br
1
Accessories: P
rocess water for cha
ngeover valveY
1B
UP
EV
U
1
1~N
/PE
/230V/50H
zC
ontroller supplyC
ontroller board; Attention: I-m
ax = 6
A/230V
AC
-A1
Heating pum
p; not required in the En
ergy Efficiency option
23
0V
AC
A1
2
K5
M4
ST
B
High-pressu
re switch
Energy supplier contact; close
d on release; bridge if no blocking inte
rval
2
HD
PE
VU
ND
PF
2
Contactor for auxiliary heating
1~N/P
E/230V
/50Hz
Low-pressure sw
itch08.1
2.2
015
ÄM
013/2013
2
Achim
Pfleg
er
10X482 - 1
0X4
85;
c
2/3
Achim
Pfleg
er0
2.12.2
008
WW
C 130-220H
LUX
2817289
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
dÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
Circuit diagram 2/3 WWC 130H/X – WWC 220H/X
52 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
ϑ
RFV
-X4
-R1
0
RF
V
GND
ϑ
TB1
-X4
-R13
TB
1
GND
TR ϑ
TBW
-X4
-R9
TB
W
GND
ϑ
TA.
-X4
-R8
TA
GNDϑ
TRL
-X5
-R4
TR
L
GND
ϑ
TVL
-X5
-R5
TV
L
GND
ϑ
THG
-X5
-R6
TH
G
GND
ϑ
TWA
-X5
-R11
TW
A
GND
CW.
-X5
-R12
GND
ϑ
TWE
-X5
-R7
TW
E
GND
AIn
-X6yellow
white
Green
Brown
-B2
Flow
sensor;
GND
AO1
0-1
0V/2.10
GN
D/2.10
AO2
-X6
GND
AO
1
Com
fort board: installed in the Ene
rgy Efficiency option
R7
R4
UK
81
7289d
Analo
gue output 1
Return sensor
RF
V
Y4
Dom
estic hot wate
r sensor
Hot gas sensor
TB
W
TV
L
A6
Sensor m
ixing circuit 1
TA
Heat source
input sensor
Flow
sensor
R10
Encoding, heat pum
p; 3480 Ohm
TW
AA
ccessories: Rem
ote control
R5
TH
G
R9
Accessories: P
rocess water for therm
osta
t
R12
Analo
gue input
BW
T
-A6
TW
ER
6
R11
R13
AO
2F
low S
ensor: installed in the E
nergy Efficiency option
B2
External sensor
AIn
Analo
gue output 2
Heat source
output sensor
TR
L
Controller board; A
ttention: I-max =
6A
/230VA
CF
unction
-A1
Leg
en
d:
R8
-CW
TB
1C
W
Operating m
aterials
BW
T
-Y4
A1
08.1
2.2
015
ÄM
013/2013
3
Achim
Pfleg
er
10X482 - 1
0X4
85;
c
3/3
Achim
Pfleg
er0
2.12.2
008
WW
C 130-220H
LUX
2817289
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
dÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
WWC 130H/X – 220H/X Circuit diagram 3/3
53Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
L1
-X7
L2L3
NP
E
12
-K1
/2.3
34
L1L2
L3
T1
T2
T3
-N1
M3
T1
T2
T3
PE
-M1
VD
1
56
12
-K3
/2.13
-X7
I>I>
I> 1
35
24
6
-F3
34
M3
UV
WP
E
-M3
Wellpum
p
56
PE
9596/2.5
Motor protection sw
itch, wellpum
p
Term
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
K3
UK
81
7290d
F3
ZW
1X
7
12
Auxiliary heating
M3
Operating m
aterials
Pow
er supply compressor; right-hand rot. field is m
andatory!
VB
O
N1
VB
O
Contactor w
ell pump
VD
1
3~P
E/400V
/50Hz
3
Leg
en
d:
Starting current lim
it
Function
Wellpum
p
VD
1
R1
23
K1
Com
pressor 1M
1
Contactor for com
pressor 1
3~PE
/400V/50H
z
1
08.1
2.2
015
ÄM
013/2013
1
Achim
Pfleg
er
10X486;
c
1/3
Achim
Pfleg
er0
2.12.2
008
WW
C 280 LU
X2
817290
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
dÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
Circuit diagram 1/3 WWC 280X
54 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
L-X
0
L
-X7
NN
PE
PE
N..
-X1
P+
-
b2c4a1
-F1
HD
P
HD.
VD1
-X1
A1
A2
-K1
VD
1
ND.
-X1
P-
+
c4b2a1
-F2
ND
P
L..
L-X
0
9596
-F3
/1.7
LL
MOT
-X2
ASD
-X2
12
-F6DF
S
EVU
HUP
-X3
M1
LN
PE
-M4
M1
brbl
PE
brblbk
-HU
PM
6
0-10
V/3.13
GN
D/3.13
BUP
-X3
12
-Y1
VBO
-X3
A1
A2
-K3
VB
O
MA1
-X3
MZ1
M1
AZ
NP
E
-M1
6
MIS
12
/1.73
4/1.7
56
/1.7
12
/1.33
4/1.3
56
/1.3
Function
Controller supply
1~N
/PE
/230V/50H
z
-A1
bl
F2
SW
SW
1~N/P
E/230V
/50Hz
EV
UF
1
br
EV
U
ND
P
MIS
sw
Energy supplier contact; close
d on release; bridge if no blocking inte
rvalA
1
High-pressu
re switch
Leg
en
d:
Low-pressure sw
itch
1
HD
P
Controller board; A
ttention: I-max =
6A
/230VA
C
Heating pum
p; not required in the En
ergy Efficiency option
1
23
0V
AC
Term
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
2
Contactor w
ell pump
SW
M6
M16
F3
Contactor for com
pressor 1K
3
rtbl
UK
81
7290d
F6
Motor protection sw
itch, wellpum
p
Heating pum
p energy efficiency; installed in the Energy E
fficiency option
3
VB
O
Mixer; installed w
ith cooling option
Operating m
aterials
VD
1
HU
PM
4
K1
Flow
rate switch
X7
2
HU
P
08.1
2.2
015
ÄM
013/2013
2
Achim
Pfleg
er
10X486;
c
2/3
Achim
Pfleg
er0
2.12.2
008
WW
C 280 LU
X2
817290
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
dÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
WWC 280X Circuit diagram 2/3
55Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
ϑ
RFV
-X4
-R1
0
RF
V
GND
ϑ
TB1
-X4
-R13
TB
1
GND
TR ϑ
TBW
-X4
-R9
TB
W
GND
ϑ
TA.
-X4
-R8
TA
GND
ϑ
TRL
-X5
-R4
TR
L
GND
ϑ
TVL
-X5
-R5
TV
L
GND
ϑ
THG
-X5
-R6
TH
G
GND
ϑ
TWA
-X5
-R11
TW
A
GND
CW.
-X5
-R12
GND
ϑ
TWE
-X5
-R7
TW
E
GND
AIn
-X6yellow
white
Green
Brown
-B2
Flow
sensor;
GND
AO1
0-10V/2.10
GN
D/2.10
AO2
-X6
GND
Flow
Sensor: insta
lled in the Energy E
fficiency optionB
2A
nalogue output 2
AO
2
AIn
UK
81
7290d
Hot gas sensor
TV
L
RF
V
Analo
gue input
TW
A
-A1
R7
Sensor m
ixing circuit 1
TA
TB
W
Return sensor
TH
G
R4
Heat source
input sensor
R12
R10
Encoding, heat pum
p; 3480 Ohm
Flow
sensor
Accessories: R
emote control
R5
TW
E
BW
T
R9
Accessories: P
rocess water for therm
osta
t
-A6
CW
R13
TB
1
R6
Com
fort board: installed in the Ene
rgy Efficiency option
AO
1A
nalogue output 1
External sensor
-Y4
A6
A1
Leg
en
d:
R8
Function
Y4
Dom
estic hot wate
r sensor
R11
BW
T
Operating m
aterials
Heat source
output sensor
Controller board; A
ttention: I-max =
6A
/230VA
C
-CW
TR
L
08.1
2.2
015
ÄM
013/2013
3
Achim
Pfleg
er
10X486;
c
3/3
Achim
Pfleg
er0
2.12.2
008
WW
C 280 LU
X2
817290
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
dÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
Circuit diagram 3/3 WWC 280X
56 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
L1
-X7
L2L3
NP
E
12
-K1
/2.3
34
L1L2
L3
T1
T2
T3
-N1
M3
T1
T2
T3
PE
-M1
VD
1
562122
-K1
/2.3
12
-R20
12
-K2
/2.4
34
L1L2
L3
T1
T2
T3
-N2
M3
T1
T2
T3
PE
-M2
VD
2
562122
-K2
/2.4
12
-R2
1
L R
eg
/2.1N
Re
g/2.1
12
-K3
/2.14
-X7
I>I>
I> 1
35
24
6
-F3
34
M3
UV
WP
E
-M3
We
llpum
p
56
PE
9596/2.5
Sum
p heating for com
pressor 1
VD
2
R20
Com
pressor 2
2
K1
M2
3
Wellpum
p
3~P
E/400V
/50Hz
Contactor for com
pressor 1V
D2
Motor protection sw
itch, wellpum
p
3
X7
M3
Pow
er supply compressor; right-hand rot. field is m
andatory!
1
Pow
er supply aux. heating
1
K2
Contactor for com
pressor 2
VB
O
3~N
/PE
/400V/50H
z
3~PE
/400V/50H
zTerm
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
UK
81
7291c
2
R21
K3
Contactor w
ell pump
VB
O
Sum
p heating for com
pressor 2
3
12
M1
F3
Function
VD
1C
ompressor 1
VD
1
Leg
en
d:
Operating m
aterials
08.1
2.2
015
ÄM
008/2011
1
Achim
Pfleg
er
10X487;
b
1/3
Achim
Pfleg
er0
2.12.2
008
WW
C 440 LU
X2
817291
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
cÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
WWC 440X Circuit diagram 1/3
57Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
L R
eg
/1.11
N R
eg/1.11
L-X
0
L
-X7
NN
PE
PE
N..
-X1
P+
-
b2c4a1
-F1
HD
P
HD.
VD1.
A1
A2
-K1
VD
1
VD2.
-X1
A1
A2
-K2
VD
2
ND.
-X1
P-
+
c4b2a1
-F2
ND
P
L..
L-X
0
9596
-F3
/1.12
LL
MOT
-X2
ASD
12
-F6
DF
S
EVU
1314
-K69
M1
LN
PE
-M4
PE
HUP
-X3
1112
A1
A2
-K6
M1
brbl
PE
brwt
blbk
-M6
HU
P
GN
D/3.12
0-10V
/3.12
BUP
-X3
12
-Y1
VBO
-X3
A1
A2
-K3
VB
O
MA1
-X3
MZ1
M1
AZ
NP
E
-M1
6
MIS
12
/1.123
4/1.12
56
/1.12
1314
71
2/1.8
34
/1.85
6/1.8
2122
/1.9
12
/1.43
4/1.4
56
/1.521
22/1.5
F1
Contactor w
ell pump
F2
1
Mixer; installed w
ith cooling option
High-pressu
re switch
3
Controller board; A
ttention: I-max =
6A
/230VA
C
M6
VB
O
Leg
en
d:
K3
2
Operating m
aterials
-A1
VD
1
Function
SW
Controller supply
SW
F3
MIS
UK
81
7291c
M16
2
br
bl
1~N/P
E/230V
/50Hz
ND
P
23
0V
AC
Contactor for com
pressor 2
1
4
F6
Heating pum
p energy efficiency; installed with optional integrated hea
t quantity meter
3
SW
EV
U
K1
HU
P
Contactor for the
rmo contact o
n heating circulation pum
p; not applicable with option
al integrated heat quantity meter
WS
K
Contactor for com
pressor 1
Heating pum
p; not applicable w
ith optional integrated heat quantity m
eter
sw
PE
A1
1~N
/PE
/230V/50H
z
Motor protection sw
itch, wellpum
pF
low rate sw
itch
K6
Term
inal strip in sw
itchbox of heat pum
p; N/P
E distribu
tion for external 230V units
EV
U
bl
HD
P
M4
X7
VD
2
Energy supplier contact; close
d on release; bridge if no blocking inte
rval
rt
HU
P
Low-pressure sw
itch
K2
08.1
2.2
015
ÄM
008/2011
2
Achim
Pfleg
er
10X487;
b
2/3
Achim
Pfleg
er0
2.12.2
008
WW
C 440 LU
X2
817291
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
cÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
Circuit diagram 2/3 WWC 440X
58 Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
ϑ
RFV
-X4
-R10
RF
V
GND
ϑ
TB1
-X4
-R1
3
TB
1
GND
TR ϑ
TBW
-X4
-R9
TB
W
GND
ϑ
TA.
-X4
-R8
TA
GNDϑ
TRL
-X5
-R4
TR
L
GND
ϑ
TVL
-X5
-R5
TV
L
GND
ϑ
THG
-X5
-R6
TH
G
GND
ϑ
TWA
-X5
-R11
TW
A
GND
CW.
-X5
-R12
GND
ϑ
TWE
-X5
-R7
TW
E
GND
AIn
-X6yellow
white
Green
Brown
-B2
Flo
w se
nsor;
GND
AO1
0-10V/2.11
GN
D/2.11
AO2
-X6
GND
AIn
AO
2
TB
1
Hot gas sensor
External sensor
Analo
gue input
R5
Operating m
aterials
Accessories: P
rocess water for therm
osta
t
Heat source
input sensor
R13
A1
Analo
gue output 2
CW
-Y4
R11
Heat source
output sensor
Function
BW
T
Controller board; A
ttention: I-max =
6A
/230VA
C
-CW
TR
L
R8
Y4
-A1
BW
T
Leg
en
d:
-A6
RF
V
TV
L
Dom
estic hot wate
r sensor
R7
R4
TB
W
Analo
gue output 1
B2
Flow
sensor; installed with optiona
l integrated heat quantity meter
A6
Com
fort plate; installed with optional integrated heat quantity m
eter
AO
1
Sensor m
ixing circuit 1
R9
Flow
sensorR
eturn sensor
Accessories: R
emote control
R6
TA
R12
TW
A
TH
G
UK
81
7291c
Encoding, heat pum
p; 3830 Ohm
R10
TW
E
08.1
2.2
015
ÄM
008/2011
3
Achim
Pfleg
er
10X487;
b
3/3
Achim
Pfleg
er0
2.12.2
008
WW
C 440 LU
X2
817291
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516
cÄ
M 074/2015
Bl vo
n An
z
Nam
e
Datu
m
Zusta
nd
Blatt-N
r.
Bea
rb.
Datu
mÄ
nde
rung
WWC 440X Circuit diagram 3/3
59Subject to change without notice | 83050700fUK – Translation into English of the original German operating manual | ait-deutschland GmbH
IIA1
ait-deutschland GmbHIndustrie Str. 393359 KasendorfGermany
WWC 130H/X
Designation of the device(s)
NumberUnit modelNumber
100 486
2011/65/EG
confirms that the following designated device(s) as designed and marketed by us fulfill thestandardized EC directives, the EC safety standards and the product-specific EC standards.In the event of modification of the device(s) without our approval, this declaration shall becomeinvalid.
The undersigned
Heat Pump
100 484
WWC 100H/X
EC Declaration of Conformity in accordance with the EC Machinery Directive 2006/42/EC, Annex II A
2009/125/EG2010/30/EU
WWC 190H/X
Unit model
100 482100 481
2006/42/EG2006/95/EG2004/108/EG*97/23/EG
WWC 440X* 100 487
Company:
WWC 220H/X 100 485WWC 280X
Place, date: Kasendorf, 14.12.2015
EN 60529EN 378
Jesper StannowHead of Heating Development
EN 55014-1/-2
EC Directives Standardized EN
WWC 160H/X 100 483
EN 349
UK818132d
Signature:
Designated position:TÜV-SÜDIndustrie Service GmbH (Nr.:0036)
EN 60335-1/-2-40
EN ISO 13857 EN 61000-3-2/-3-3EN ISO 12100-1/2
Module
* Pressure equipment componentCategory
ait-deutschland GmbHIndustriestraße 3D-95359 Kasendorf
E [email protected] www.alpha-innotec.de
alpha innotec – an ait-deutschland GmbH brand
UK