on line ups 6-10kva user manual

32
ON LINE UPS 6-10kVA USER MANUAL

Upload: dinhdiep

Post on 03-Jan-2017

329 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: ON LINE UPS 6-10kVA USER MANUAL

ON LINE UPS

6-10kVA USER MANUAL

Page 2: ON LINE UPS 6-10kVA USER MANUAL

Thanks for choosing EATON products!

All warnings and operation instructions in the manual and on the

machine should be strictly followed, and this user manual should

be kept for future reference.

Do not attempt to operate the UPS until reading through all

safety information and operating instructions of this manual

carefully.

Page 3: ON LINE UPS 6-10kVA USER MANUAL

Solemn Statement

Copyright Statement

EATON is dedicated to a continued effort of technological innovation and

provision of improved products and services to satisfy customers' needs.

Product design and technical specifications are subject to upgrading without

notice.

Page 4: ON LINE UPS 6-10kVA USER MANUAL

Safety Instruct ions

Operation Safety

1. Prior to the application, please read “Safety Instructions” carefully to ensure

correct and safe application. Please keep the user manual.

2. During operation, attention should be paid to all warning symbols and

operations should be followed strictly as required.

3. Equipment is not supposed to be used in environment that directly

exposed to sunlight or rain or in a humid environment.

4. The equipment should not be installed close to area of thermal sources or

any area where there is presence of devices such as electric heaters and

furnaces.

5. Make sure the safety space should be left for proper ventilation and

product maintenance when placing UPS. Refer to the instructions during

installation.

6. Dry and non-conductive items should be used for cleaning.

7. In case of a fire hazard, dry powder extinguisher should be used properly.

Using liquid fire extinguishers may result in electric shock hazard.

Electrical Safety

1. Before electricity is switched on, make sure earthing is properly done and

wire and battery polarity are correctly connected.

2. When UPS relocation or wire reconnection is necessary, AC and battery

should be switched off and UPS should be completely turned off, otherwise there

might be a danger of electric shock because output terminal might be still

electrified.

3. Please use EATON specified appendix devices and accessories.

4. To meet the requirement of EMC, the length of the output should be less than 10m.

Page 5: ON LINE UPS 6-10kVA USER MANUAL

Battery Safety

1. Battery service lifetime will be shortened as ambient temperature rises.

Replace batteries periodically to guarantee normal UPS performance and

sufficient back-up time.

2. Only personnel with proper expertise can carry out the maintenance of

accumulator batteries. Replacement of accumulator batteries requires a match of

same type and model with equal quantity.

3. As accumulator batteries may contain potential electric shock and short-circuit

current danger, to avoid accidents that might be thus resulted, the following

warnings should be observed during battery replacement:

A. Do not wear watches, rings or similar metallic items;

B. Use insulated tools;

C. Put on rubber shoes and gloves;

D. Do not place metallic tools or similar metallic parts on the batteries;

E. Switch off load connected to the batteries before dismantling battery

connection terminals.

4. Do not expose accumulator battery to fire in order to avoid possible

explosion that might endanger physical safety.

5. Non-professionals are not allowed to open or destroy accumulator

batteries for electrolytes in batteries contain strong acid and other dangerous

substances which will cause damages to both human skins and eyes. Should

electrolytes come into any contact with human body unintentionally, rinse with

clean water and seek medical advice.

6. Do not cause battery positive and negative polarity short circuit, otherwise,

electric shock or inflammation may occur.

Page 6: ON LINE UPS 6-10kVA USER MANUAL

Maintenance

1. Working environment and storage means can affect the service term and

reliability of this product to some extent. Therefore, the product is not suitable for

performance in the following environment:

A. Locations where temperature exceeds the maximum or goes below the

minimum temperature as required by technical specifications or humidity is

improper (temperature range: 0-40oC ; relative humidity range: 20%-90%).

B. Locations where vibration and impact are constant;

C. Locations where metallic dust, corrosive substances as well as

salts and inflammable gases are present.

2. For long-term inaction, UPS (without batteries) should be kept in dry

environment with temperature ranging from -25-55oC. Before start-up, ambient

temperature should be brought back to 0 or above for a certain period of time

(above 2 hours).

Page 7: ON LINE UPS 6-10kVA USER MANUAL

Contents

C h a p t e r 1. B r i e f i n t r o d u c t i o n……………………………………... …..1

1.1 Frequently used symbols..................................................................................2

1.2 Front view……………………………………………………………………………2

1.3 Rear view…………………………………………………………………………….3

1.4 Technical data…………………………………………………………….…………4

C h a p t e r 2. I n s t a l l a t i o n

2.1 Unpacking inspection........................................................................................6

2.2 Wiring table.......................................................................................................7

2.3 Connection........................................................................................................8

2.4 Installation of external battery of long backup time model................................9

2.5 Connecting to computer interface....................................................................10

2.6 Parallel operation (option)...............................................................................11

2.7 Communication card installation......................................................................15

2.8 EPO.................................................................................................................16

2.9 Maintenance switch.........................................................................................17

2.10 Dustproof net (option)....................................................................................17

2.11 Transformer (option)......................................................................................17

C h a p t e r 3. C o n t r o l P a n e l…………………………………………………18

C h a p t e r 4. O p e r a t i o n ……………………………………………………….19

4.1 Start up............................................................................................................19

4.2 Shut down........................................................................................................21

C h a p t e r 5. B a t t e r y m a i n t e n a n c e……………………………………..22

C h a p t e r 6. Troubleshooting……………………………………………………….23

C h a p t e r 7. Warranty……………………………………………………………….25

Page 8: ON LINE UPS 6-10kVA USER MANUAL

Chapter 1 Br ief introduct ion

This On-Line-Series is an uninterruptible power supply incorporating double-

converter technology. It provides perfect protection specifically for computers,

communication equipment and so on. The double-converter principle

eliminates all mains power disturbances. A rectifier converts the alternating

current from the socket outlet to direct current. This direct current charges the

batteries and powers the inverter. On the basis of this DC voltage, the inverter

generates AC voltage, which permanently supplies the loads. When some

overload, inverter fault or rectifier fault occurs, the UPS will transfer to

Bypass mode.

This manual is designed for the EATON DX series product, include:

EDX6000H-LCD: 6kVA standard model with internal battery

EDX6000HXL-LCD: 6kVA long back up time model with external battery

EDX10KHXL-LCD: 10kVA long back up time model with external battery

1

Page 9: ON LINE UPS 6-10kVA USER MANUAL

1.1 Frequently used symbols

Symbol & Description

Symbol Description

Caution

Danger

Alternating Current

Direct current

Earth protection

Connection protection

Cycle

Do not place with sundries

Overload

Battery

On/off

1.2 Front view

EATON DX

ON/OFF TEST/

EATON DX

O N / O F F TE S T/

EDX6000H-LCD EDX6000HXL-LCD

& EDX10KHXL-LCD

Page 10: ON LINE UPS 6-10kVA USER MANUAL

1.3 Rear view

EDX6000H-LCD

EDX6000HXL-LCD & EDX10KHXL-LCD

NOTE:

1. For models with parallel card and maintenance switch, you should remove covers 4 and ⑥

to access the parallel card and maintenance switch.

3

1. Computer interface 2. Intelligent slot 3. Fan (2 Fans on 10kVA) 4. Parallel card (optional) cover 5. Input switch 6. Maintenance switch (optional) cover 7. Terminal block cover 8. Cable clamp 9. EPO (optional)

Page 11: ON LINE UPS 6-10kVA USER MANUAL

1.4 Technical data

4

Eaton E Series DX 1Ph 6kVA LCD UPS Technical Specification CONSTRUCTION

Model EDX6000H-LCD EDX6000HXL-LCD

Rating 6000VA / 4800W

Technology VFI, on-line double conversion

Dimensions: W x D*x H mm *Allow 150mm rear clearance for connections & air flow

248 x 500 x 616 240 x 500 x 460

Weight 60kg 20kg

ENVIRONMENTAL & SAFETY

Ambient service temperature

Power electronics part: 0 to 40C, Battery part: 5 to 25C without reducing battery life

Ambient storage temp. 0˚C to +45˚C

Maximum service altitude 1000m above sea level

Relative humidity 20 to 90%, no condensation allowed

Degree of protection IP21 (EN60529)

Acoustic Noise <55dBA@ 1m, Normal mode, typical load, battery fully charged

Standards

EMS & EMI: Complies with IEC61000-4-2 Level 4, IEC61000-4-3 Level 3, IEC61000-4-4 Level 4, IEC61000-4-4 Level 4, IEC62040-1, EN55022 Class B

Safety: Complies with GB4943-2001/IEC62040-1

POWER CONNECTIONS

Input Hardwired

Output Hardwired

USER INTERFACE

Display

LED mimic diagram + LCD Display with measurements (Input/Output/Bypass V & Hz, Battery V & % capacity & remaining time and level indicator, Load % & level

Indicator, Alarm codes)

Communication Ports 1 off Intelligent-Slot (Empty), 1 x RS232 DB9 Serial Port

Optional Intelligent Slot cards; AS400 Relay, Web/SNMP, Modbus

ELECTRICAL CHARACTERISTICS – INPUT

Rated input voltage 220V

Input voltage tolerance (with linear load)

185-274 @>90% load,

165-274 @70 - ≤90%,

150-274 @50 - ≤70% ,

120- 274 @≤50% load,

All values ±5V

Bypass Voltage Tolerance 165 – 253V (Default 187-253V user adjustable)

Operating Frequency 50/60Hz auto sensing; Tolerance (46/56 ±0.5) Hz Low, (54/64±0.5) Hz High

Input current distortion <10% THDi

Input power factor @ Pnom 0.99pf

Input Current (at rated load with fully charged battery)

25A

Input protection rating (MCB)

32A

ELECTRICAL OUTPUT CHARACTERISTICS – NORMAL MODE

Rated apparent/active power

6000VA / 4800W

Transfer–normal to stored energy

No break

Rated output voltage 220V

Output voltage variation ±2%

Crest factor 3:1

Eaton E Series DX 1Ph 6-10kVA LCD UPS Technical Specification CONSTRUCTION

Model EDX6000H-LCD EDX6000HXL-LCD EDX10KHXL-LCD

Rating 6000VA / 4800W 6000VA / 4800W 10000VA / 8000W

Technology VFI, on-line double conversion

Dimensions: W x D*x H mm *Allow 150mm rear clearance for connections & air flow

248 x 500 x 616 240 x 500 x 460 240 x 500 x 460

Weight 60kg 20kg 21kg

ENVIRONMENTAL & SAFETY

Ambient service temperature

Power electronics part: 0 to 40C, Battery part: 5 to 25C without reducing battery life

Ambient storage temp. 0˚C to +45˚C

Maximum service altitude 1000m above sea level

Relative humidity 20 to 90%, no condensation allowed

Degree of protection IP21 (EN60529)

Acoustic Noise <55dB @ 1m, Normal mode, typical load, battery fully charged

Standards

EMS & EMI: Complies with IEC61000-4-2 Level 4, IEC61000-4-3 Level 3, IEC61000-4-4 Level 4, IEC61000-4-4 Level 4, IEC62040-1, EN55022 Class B

Safety: Complies with GB4943-2001/IEC62040-1

POWER CONNECTIONS

Input Hardwired

Output Hardwired

USER INTERFACE

Display

LED mimic diagram + LCD Display with measurements (Input/Output/Bypass V & Hz, Battery V & % capacity & remaining time and level indicator, Load % & level

Indicator, Alarm codes)

Communication Ports 1 off Intelligent-Slot (Empty), 1 x RS232 DB9 Serial Port

Optional Intelligent Slot cards; AS400 Relay, Web/SNMP, Modbus

ELECTRICAL CHARACTERISTICS – INPUT

Rated input voltage 220V

Input voltage tolerance (with linear load)

185±5V - 274±5V @ >90% load,

165±5V - 274±5V @ 70 - ≤90%,

150±5V - 274±5V @ 50 - ≤70%,

120±5V - 274±5V @ ≤50% load,

Bypass Voltage Tolerance 165 – 253V (Default 187-253V user adjustable)

Operating Frequency 50/60Hz auto sensing; Tolerance (46/56 ±0.5) Hz Low, (54/64±0.5) Hz High

Input current distortion <10% THDi

Input power factor @ Pnom 0.99pf

Input Current (at rated load with fully charged battery)

25A 25A 41A

Input protection rating (MCB)

32A 32A 63A

ELECTRICAL OUTPUT CHARACTERISTICS – NORMAL MODE

Rated apparent/active power

6000VA / 4800W 6000VA / 4800W 10000VA / 8000W

Transfer–normal to stored energy

No break

Rated output voltage 220V

Output voltage variation ±2%

Crest factor 3:1

Page 12: ON LINE UPS 6-10kVA USER MANUAL

Eaton E Series 1Ph 6-10kVA LCD UPS Technical Specification

EDX6000H-LCD EDX6000HXL-LCD EDX10KHXL-LCD

Rated output frequency 50Hz (default) or 60Hz

Output frequency regulation On Line Mode: Follows bypass frequency

Total output voltage distortion ≤2% Linear Load, ≤4% Non Linear Load

Frequency Slew Rate 1Hz/sec

Load power factor range 0.7 – 1.0

Number of output phases 1 Phase

Overload (Normal Mode, Resistive Load) 125% for 1 minute, 150% 30 seconds

Output voltage variation –

dynamic load

±6% max from 20%-100%-20% load step or vice versa

Recovery to nominal voltage ±10% within 60ms

ELECTRICAL OUTPUT CHARACTERISTICS – STORED ENERGY

Rated apparent/active power 6000VA / 4800W 6000VA / 4800W 10000VA / 8000W

Waveform Sine Wave

Rated output voltage 220V

Output voltage variation ±2%

Crest factor 3:1

Rated output frequency 50Hz (default) or 60Hz

Output frequency regulation ±0.05Hz

Total output voltage distortion ≤2% Linear Load, ≤4% Non Linear Load

Load power factor range 0.7 – 1.0

Number of output phases 1 Phase

Output Overload 125% for 1 minute, 150% 30 seconds

EFFICIENCY (Input/Output)

Efficiency at 100% linear load ≤90% (≤97% in ECO mode)

BATTERY

Internal Battery Type Valve Regulated Lead Acid, AGM, 3-5 year design life at 25oC

Charging voltage 2.275V/Cell ± 1%

Charger Capacity 220W ±5% 1000W ±5% 1000W ±5%

End V/Cell, >23% Load 1.6V 1.67V 1.67V

End V, ≤23% Load 1.83V 1.83V 1.83V

Internal Battery Re-charge time Internal Battery: <7 hours (6kVA) to recover 90% of capacity

External Battery: Dependant on battery capacity

Battery Nominal Voltage 192V (96 Cells) *240V / 120 Cells optional on XL Models

Internal Battery Configuration 16 x 12V 7.2Ah NA NA

Battery Circuit Protection Rating 30A 30A 60A

Battery Run Times

Internal battery Full / Half Load 4 / 12 mins NA NA

NOTE: Battery times are approximate and vary depending on age, temperature and load.

BYPASS CHARACTERISTICS

Type of bypass In-Built Automatic Relay Bypass

Transfer Time Online mode: <4ms, ECO Mode: ≤8ms

5

Eaton E Series 1Ph 6-10kVA LCD UPS Technical Specification

EDX6000H-LCD EDX6000HXL-LCD EDX10KHXL-LCD

Rated output frequency 50Hz (default) or 60Hz

Output frequency regulation On Line Mode: Follows bypass frequency

Total output voltage distortion

≤2% Linear Load, ≤4% Non Linear Load

Frequency Slew Rate 1Hz/sec

Load power factor range 0.7 – 1.0

Number of output phases 1 Phase

Overload (Normal Mode, Resistive Load)

125% for 1 minute, 150% 30 seconds

Output voltage variation –

dynamic load

±6% max from 20%-100%-20% load step or vice versa

Recovery to nominal voltage ±10% within 60ms

ELECTRICAL OUTPUT CHARACTERISTICS – STORED ENERGY

Rated apparent/active power 6000VA / 4800W 6000VA / 4800W 10000VA / 8000W

Waveform Sine Wave

Rated output voltage 220V

Output voltage variation ±2%

Crest factor 3:1

Rated output frequency 50Hz (default) or 60Hz

Output frequency regulation ±0.05Hz

Total output voltage distortion

≤2% Linear Load, ≤4% Non Linear Load

Load power factor range 0.7 – 1.0

Number of output phases 1 Phase

Output Overload (Battery Mode)

125% for 1 minute, 150% 30 seconds

EFFICIENCY (Input/Output)

Efficiency at 100% linear load

≤90% (≤97% in ECO mode)

BATTERY

Internal Battery Type Valve Regulated Lead Acid, AGM, 3-5 year design life at 25oC

Charging voltage 2.275V/Cell ± 1%

Charger Capacity Continuous power

220W ±5% 1000W ±5% 1000W ±5%

End V/Cell, >23% Load 1.6V 1.67V 1.67V

End V, ≤23% Load 1.83V 1.83V 1.83V

Internal Battery Re-charge time

Internal Battery: <7 hours (6kVA) to recover 90% of nominal backup

External Battery: Dependant on battery capacity

Battery Nominal Voltage 192V (96 Cells) *240V / 120 Cells optional on XL Models

UPS Internal Battery Configuration

16 x 12V 7.2Ah NA NA

Battery Circuit Protection Rating

30A 30A 60A

Battery Run Times

Internal battery (H Models): Full Load / Half Load

4 / 12 mins NA NA

NOTE: Battery times are approximate and vary depending on age, temperature and load configuration.

BYPASS CHARACTERISTICS

Type of bypass In-Built Automatic Relay Bypass

Transfer Time Online mode: <4ms ECO Mode: ≤8ms

Page 13: ON LINE UPS 6-10kVA USER MANUAL

Chapter 2 Instal lat ion

DANGER: Ensure supply power is disconnected and the battery supply

is isolated.

CAUTION:

1. The installation as described in this chapter may only be carried out by

qualified personnel and must comply with the local regulations

2. The UPS is recommended for floor mounted installation only.

2.1 Unpacking inspection

1. Open the packing box of the UPS and take it out, check whether the UPS is

damaged during the process of transportation.

2. Should any damage be observed or parts be found missing, do not start the

machine. Contact the forwarder and distributor immediately.

Accessories:

1) User manual

RECYCLE: Please keep the packaging for future use.

2.2 Wiring table

CAUTION: Choice of the diameter and cross section of conductors depend

on the rated power of UPS, the installation and local regulations.

6

Page 14: ON LINE UPS 6-10kVA USER MANUAL

DX6K DX6K DX10K DX10 DX10K DX15K DX20K

XL XL KXL XL31 XL31 XL31

G 10AW 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

N 10AWG 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

L 10AWG 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

+ 10AWG 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

- 10AWG 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

G 10AWG 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

L 10AWG 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

N 10AWG 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

G 10AWG 10AWG 8AWG 8AWG 8AWG 6AWG 6AWG

(6mm2) (6mm2) (10mm2) (10mm2) (10mm2) (25mm2) (25mm2)

2.3 Connection

DANGER: The customer must install a suitably rated disconnection

switch in the mains supply to the UPS.

1. Choose appropriate cables for input and output to reference “wiring table”.

2. Remove the terminal block cover in the rear panel.

3. Connect the load to the output of the terminal block.

4. Connect the input power cable to the input of the terminal block. On XL model

connect the external battery cables.

5. Secure the cables to the cable clamps.

7

Page 15: ON LINE UPS 6-10kVA USER MANUAL

DANGER: Make sure the input and output cables are connected firmly.

Terminal block:

8

Input Output Inpu t Output

EDX6000HXL-LCD

EDX10KHXL-LCD

EDX6000H-LCD

Page 16: ON LINE UPS 6-10kVA USER MANUAL

7. Put the cover board back to the UPS and tighten the screws.

8. Before the input protection switch is being set in the “ON” position, supply

power source to the UPS.

Input Protection Switch

2.4 Installation of external battery of long backup time model

EATON DX has 16 batteries (20 batteries for special models) connected in

series as a 192VDC bank, and multiple of battery banks can be connected in

parallel; while 20 batteries for special models connected in series as a 240VDC

block and multiples of battery can be connected in parallel.

It is very important to follow the battery connecting procedures; otherwise, there

may be electric shock hazard. Please perform the connecting procedure according

to the following step strictly:

1. Make sure the battery switch in the “OFF” position and connect the 16

batteries in series.

2. Connect the battery cable to the battery blocks. A disconnect

switch/protective device must be connected between the battery bank and the

UPS, the current and voltage specification of the switch shall be as follows:

- Standard 16 battery system: 192VDC, 34A

- Optional 20 battery system: 240V DC, 27A

9

Page 17: ON LINE UPS 6-10kVA USER MANUAL

DANGER: Do not connect the battery cable to the UPS first; otherwise, there

may be electric shock hazard.

3. Connect the battery cable to the battery terminal of UPS. Make the power

supply to the UPS, then set the battery block switch in the “ON” position, the

UPS will begin to charge the battery block.

CAUTION: The battery grounding of the UPS is located on the right of the

terminal block and marked with the icon " ".

2.5 Connecting to the Computer interface

Computer interface: standard RS232 communication port, use a RS232 cable to

connect the UPS with the computer.

1. Connect the RS232 communication cable to the serial port computer.

2. Connect the RS232 cable to the RS232 communication port of the UPS.

Communication Port

RS232 Cable

10

Page 18: ON LINE UPS 6-10kVA USER MANUAL

The PIN configuration of computer interface port on UPS is as follows:

2.6 Parallel operation (option)

1. Redundancy

N+X is currently the most reliable structure in power protection. N represents the minimum number of the UPS modules of the UPS system that the total load needs; X represents the number of the redundant UPS blocks of the UPS system, i.e. the number of faulty UPS modules that the system can handle simultaneously. The bigger X is, the higher the system reliability is. For occasions where reliability is highly depended on, N+X is the optimal mode.

The UPS system can be configured with up to three UPS modules. Use the parallel cables to connect the parallel UPS with each other to realise power redundancy.

2. Connection

The parallel function is optional and customers should purchase the necessary

accessories (including the parallel cables and parallel cards), then the customer

service engineers will help install them. Up to three UPS modules can be

paralleled; each must be supplied with a separate battery.

1) Remove the parallel card cover and connect the UPS parallel

communications cables.

11

Page 19: ON LINE UPS 6-10kVA USER MANUAL

2) Connect each output breaker to a main output breaker and then to the loads. Utility Input Switchboard

Output Switchboard

Load Load Load Load

CAUTION: Requirement of output wiring length:

When the lead from the output terminal of each set of UPS to the output

patch board is less than 20m, wire difference should be less than 20%;

When the lead from the output terminal of each set of UPS to the output

patch board is longer than 20m, wire difference should be less than 10%.

3) The wiring connection diagrams are as follows and the wiring requirements

follow the requirements of single UPS.

4) The parallel UPSs have been designed for use with separate batteries.

12

Page 20: ON LINE UPS 6-10kVA USER MANUAL

Output ground

Output neutral

Output line

Battery pack 3#

Battery pack 2#

Battery pack 1#

Input line

Input neutral

Input ground

13

Page 21: ON LINE UPS 6-10kVA USER MANUAL

3. Advantages of parallel configuration

This configuration improves the reliability of the power supply system

through the redundancy frame structure. Two UPSs equally share the load,

when one UPS fails, the other will take up full load itself.

It is designed to isolate the UPS from the AC source for maintenance; each

UPS has a manual maintenance bypass.

4. Operation

1) Please follow the single UPS operating guide to perform general operation.

2) Power on

Power on under mains: After you make sure that the power supply connection

is correct, press the “ON” button of any UPS continuously for more than 1

second, the units transfer to work under INV mode simultaneously as they

start up sequentially in line mode.

Power on under battery: Short press the "ON" button of each UPS to get

power sources, then press the “ON” button of one's continuously for more

than 1 second, the units work under battery mode simultaneously.

3) Power off

Press the “OFF” button of one set of UPS continuously for more than 4

seconds, all the UPSs will be shut down;

Press the “OFF” button of one set of UPS continuously for more than 1

second, no more than 4 seconds, this UPS will be shutdown alone.

CAUTION: Long-press is more than 1 seconds, short-press is less than

0.5 second.

2.7 Communication card installation

Intelligent slot is designed for the communication cards. You don’t need to

stop the UPS during the installation of communication card.

1. Remove the cover board of intelligent slot.

2. Insert the communication card into the slot.

3. Use the screws to tighten the card.

14

Page 22: ON LINE UPS 6-10kVA USER MANUAL

Intelligent slot

SNMP Card (option)

The intelligent slot with installation of SNMP card supplies the SNMP compliant data on

an RJ45 connector.

AS400 card (option)

This series UPS support AS400 card (an optional accessory) for intelligent slot. The

following is the pin assignment and description of DB-9 connector in AS400 card.

PIN Description

PIN1 UPS Fail

PIN2 Summary alarm

PIN3 GND (Ground)

PIN4 Remote shutdown

PIN5 Common

PIN6 Bypass

PIN7 Battery low

PIN8 UPS on

PIN9 Line loss

15

Page 23: ON LINE UPS 6-10kVA USER MANUAL

2.8 EPO

EPO (Emergency Power Off) is an optional green connector located on the

rear panel of the UPS. It performs emergency power off when the UPS is under

emergent condition. There are two connection methods as follows:

EPO

Switch

performs Emergency Power Off

EPO

Switch

1-2 connect with short wire, always keep connected

3-4 open- UPS perform Emergency power off

16

Page 24: ON LINE UPS 6-10kVA USER MANUAL

2.9 Maintenance switch

There are voltages present inside the UPS when it works under line mode, battery mode

or bypass mode, so you separate the UPS electronics from the utility via closing the

Maintenance switch to perform on-line maintenance. Maintenance switch

Utility input Output

Battery

Maintenance switch cover

2.10 Dustproof net (option)

Dustproof net is used to protect the UPS from dust and it is necessary to install a dustproof

net for the device at an environment with heavy dust or smog. Dustproof net should be

installed inside the UPS and at the back of the front panel. Please refer to the dustproof net

quick installation guide for details.

2.11 Transformer (option)

Please refer to the transformer quick installation guide for details.

17

Page 25: ON LINE UPS 6-10kVA USER MANUAL

①~④ LED:

① Utility power

② Battery

③ Bypass

④ Inverter

⑤ ON/OFF button

⑥ Function button

⑦ LCD

The alarm silence of the function button is valid only in battery mode and bypass mode. It

cannot silence other fault warning alarms of the UPS system.

The LCD has five parts as follows:

① Numerical display: show voltage, frequency, battery capacity, load capacity and fault

code.

② Configuration: show the connection configuration of part ① .

③ Load capacity icon: show the level of the load capacity.

④ Battery capacity icon: show the level of the battery capacity.

⑤ Alarm icon: when the UPS is abnormal, the icon will appear.

18

Chapter 3

Control panel

Page 26: ON LINE UPS 6-10kVA USER MANUAL

Chapter 4 Operat ion

4.1 Start up

The battery is fully charged before delivery. However, storage and

transportation will inevitably cause some charge loss. Therefore, it is advisable

to charge the battery for 12 hours before using it, so as to ensure adequate

battery autonomy.

Start with the utility power:

1. Power on the UPS, the Utility Power LED is lit, then press the “ON” Button to

start the UPS.

2. After few minutes, the normal operation begins, the utility power LED and the

inverter LED are lit and the LCD shows the main menu under normal mode.

3. UPS supplies power to the load.

4. Press the “Function” button to obtain the following information from LCD.

19

EATON DX

Page 27: ON LINE UPS 6-10kVA USER MANUAL

Hz

VAC

INPUT

5. Turn on the UPS, it will perform a self-test automatically and all of the “ ”

On the LCD are lit one by one from left to right. The inverter LED on and UPS is

under normal mode. If the utility power is abnormal, the UPS runs in battery mode.

Start without the utility power:

1. Press the “ON” button to start the UPS (connect the external battery first for the

long backup time models).

2. UPS starts up in battery mode, the battery LED and the inverter LED are on,

the LCD shows the main menu under battery mode.

20

L OAD

Page 28: ON LINE UPS 6-10kVA USER MANUAL

3. UPS supplies power to the load

4. Press the “Function” button to obtain the following information from LCD.

5. Buzzer beeps once every 4 seconds, which indicates the UPS run under

battery mode. Press the "Function” button for more than 2 seconds to silence the

buzzer.

4.2 Shut down

1. Press the “OFF” button to turn off the UPS.

2. The terminal still has live voltage via bypass; the line LED and the bypass LED

are on. The LCD shows the main menu under bypass mode.

3. The buzzer beeps once every 2 minutes, which indicates the UPS run under

bypass mode. Press the “Function” button for more than 2 seconds to silence the

buzzer.

4. Press the "Function" button to obtain the following information from LCD.

Hz

VAC

INPUT

5. To completely power down the UPS, disconnect the line input of the UPS.

21

LOAD

Page 29: ON LINE UPS 6-10kVA USER MANUAL

Chapter 5 Battery maintenance

The battery is key component of the UPS. The battery life depends on the ambient

temperature, charge and discharge times. High ambient temperature and deep

discharge will shorten the battery life.

1. When being connected to the utility whether the UPS has been turned on or not,

the UPS keeps charging the battery and also offers the protective function of

charging and discharging.

2. If the UPS has not been used for a long period, charging is recommended every

4 to 6 months. Charging should begin after the UPS shout down automatically in

the course of discharging. In the regions of hot climates, the battery should be

charged and discharged every 2 months. Moreover, the standard charging time

should be not less than 12 hours.

3. Under normal conditions, the battery life lasts 3 to 5 years. In case the battery is

found not in good condition, earlier replacement should be made. The battery

should only be replaced by qualified service personnel.

4. In replacement of battery, please use the same number and type of battery.

5. Batteries should not be replaced individually. All batteries should be replaced at

the same time following the instruction of the battery supplier.

6. Normally, the battery should be charged and discharged every 4 to 6 months.

The standard charging time should be not less than 12 hours.

22

Page 30: ON LINE UPS 6-10kVA USER MANUAL

Chapter 6 Troubleshoot ing

6.1 Understanding the UPS in alarm condition

If the Alarm icon is on and the LCD shows fault code, which indicates that the

operation is abnormal. Please refer to the "troubleshooting table" for details.

A. Fault code (fault menu)

The following items are displayed by the LCD via pressing the function button:

output voltage and frequency, input voltage and frequency, load level and battery

capacity. And the fault menu is the main menu.

B. Alarm code (alarm menu)

The following items are displayed by the LCD via pressing the function button:

parameters of output, input, load level, voltage, frequency and battery capacity.

And the alarm menu is the main menu.

23

Page 31: ON LINE UPS 6-10kVA USER MANUAL

6.2 Troubleshooting table

Fault code Description FAULT CODE TABLE

001 BUS soft start overtime 002 BUS voltage high 003 BUS voltage low 005 BUS short circuit 006 Inverter soft start overtime 007 Inverter voltage high 008 Inverter voltage low 010 R phase inverter voltage short circuit 017 R phase reverse power 021 Current balance fault 022 Overload 023 Over-temperature 025 INV Rly fault 026 Line input SCR fault 029 Rectifier fault 032 Communication wire disconnected 034 CAN communication wire fault 035 Synchronous signal wire fault 036 System power supply fault 042 Line input fuse fault 055 NTC fault 056 Parallel line fault 057 Battery fault 059 Battery overcharged

WARNING CODE TABLE EXTEND WARNING TABLE

100 Internal alarm 103 Line loss alarm 104 Input N wire disconnected 106 Reversed L, N connection 107 Bypass loss alarm 109 Battery disconnected 110 Battery voltage low alarm 111 Battery overcharged 113 Overload pre-alarm 114 Overload alarm 115 Fan failure 117 Charger failure 118 Address fault 119 Fail to meet power-on requirements 125 Temperature is too low 126 Temperature is too high 131 Slave board fail alarm

INTERNAL WARNING TABLE 200 Eeprom alarm 201 Address conflict 219 Fail to identify model 227 Parallel mode alarm

24

Page 32: ON LINE UPS 6-10kVA USER MANUAL

Chapter 7 Warranty

Our company promises: products to be offered free warranty service for one year

from the date of purchase. The local office or distributor may grant a warranty

period different to the above and refer to local terms of liability as defined in the

supply contract.

To obtain service under warranty via a valid guarantee offered by

dealers;

To obtain service under warranty via serial number.

The cost of delivery shall be borne by the customer, please contact the service

centre or distributor.

This limited warranty does not apply to conditions as follows:

Out of warranty;

The finished product of which the serial number is changed or lost;

Capacity dropped normally and external appearance damaged;

Some damage occurred during delivery, move;

Damage due to force disaster and man-made fault;

Disobeying provisions of operating/using the unit;

614-04506-IN