nz3200 op manual - fire alarm engineers · 2015-01-12 · r67 m2 m3 sw9 br1-+ rn13 zd13 zd12 zd11...
TRANSCRIPT
Document No........................................................................MG059WO4
Issue No.................................................................................................3
Serial No...................................................................................................
Issue Date..................................................................10th February 2000
Software Version..................................................................................4.0
APPROVED TO:
NZS 4512:1997 Fire Alarm Systems in Buildings.AS/NZS 3548:1992 Electromagnetic Interference.
AMPAC TECHNOLOGIES PTY LTD
UNIT D, 33 PORANA ROADGLENFIELDAUCKLANDNEW ZEALAND
PH : 64-9-443 8072FAX : 64-9-443 8073
NOTE: INFORMATION CONTAINED IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUTNOTICE.
UNCONTROLLED DOCUMENT
NZ 3200AUTOMATIC FIRE ALARM SYSTEM
OPERATORS MANUAL
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 2
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
1 CONTENTS1 CONTENTS...............................................................................................................22 INTRODUCTION .......................................................................................................42.1 Unpacking And Inspection........................................................................................... 42.2 Anti Static Precautions................................................................................................. 43 SPECIFICATIONS ....................................................................................................44 SYSTEM DESCRIPTION ..........................................................................................51.1 General Description...................................................................................................... 5System Layout......................................................................................................................... 54.3 Main System Board API 708......................................................................................... 6
4.3.1 Detector Circuits....................................................................................................................74.3.2 Bell Circuits ............................................................................................................................74.3.3 Bell Isolate (Internal) .............................................................................................................74.3.4 Self Test ..................................................................................................................................74.3.5 Walk Test ................................................................................................................................84.3.6 Door Interlock.........................................................................................................................84.3.7 Fault Indicators ......................................................................................................................84.3.8 DBA Input ...............................................................................................................................84.3.9 Power Supply .........................................................................................................................94.3.10 Mains On Indicator ................................................................................................................94.3.11 Ancillary Power Output .........................................................................................................94.3.12 Fusing .....................................................................................................................................9
4.4 Zone Board - API 588.................................................................................................. 104.4.1 Detector Circuits..................................................................................................................10
4.5 Batteries ...................................................................................................................... 105 CONNECTING DEVICES........................................................................................115.1 Detectors ..................................................................................................................... 11
5.1.1 Detector Limitations ............................................................................................................115.2 Bells and Sounders .................................................................................................... 126 CONNECTING BRIGADE INTERFACES ...............................................................136.1 Connecting a Signal Generating Device (BD0678) ................................................... 137 SETTINGS...............................................................................................................147.1 Main System Board (API 708) Settings...................................................................... 14
7.1.1 Setting the number of zone cards......................................................................................147.1.2 Miscellaneous settings .......................................................................................................14
7.2 Setting zone bell output ............................................................................................. 157.2.1 Setting zone brigade call output ........................................................................................157.2.2 Setting zone configuration .................................................................................................15
7.3 Zone card (API 588) Settings. ................................................................................... 167.3.1 Setting the address of the zone cards...............................................................................167.3.2 Setting zone bell output ......................................................................................................177.3.3 Setting zone brigade call output ........................................................................................177.3.4 Setting zone configuration .................................................................................................17
8 INSTALLATION AND INITIAL OPERATION..........................................................198.1 Installing the NZ3200.................................................................................................. 19
8.1.1 Removing and reinstalling the index panel ......................................................................198.1.2 Initial operation ....................................................................................................................19
9 SYSTEM OPERATION............................................................................................209.1 Resetting the system.................................................................................................. 209.2 Isolating the Bells/Sounders...................................................................................... 209.3 Using the Walk Test facility........................................................................................ 209.4 Self Test Facility ......................................................................................................... 209.5 Trial Evacuation .......................................................................................................... 2010 OPTIONS ................................................................................................................2110.1 ASPI relay board ..................................................................................................... 21
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 3
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
11 TROUBLESHOOTING ............................................................................................2212 INDEX PANEL ENGRAVING..................................................................................2312.1 NZ3200/16 without DBA. For rear service F.I.P. .................................................... 2312.2 NZ3200/16 with DBA . For rear service F.I.P. ........................................................ 24NZ3200/16 For front service F.I.P. ........................................................................................ 2512.4 NZ3200/32 For Rear service F.I.P........................................................................... 2612.5 NZ3200/32 For Rear service F.I.P........................................................................... 2713 Appendix A. BATTERY CALCULATION. .............................................................2814 Appendix B. EXAMPLE BATTERY CALCULATION............................................2915 Appendix C. DETECTOR CIRCUIT LIMITATIONS................................................3016 Appendix D. COMPATIBLE OUTPUT DEVICES...................................................34
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 4
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
2 INTRODUCTION
2.1 Unpacking And Inspection
Carefully check packing before unpacking goods for any transit damage. Unpack the goods andcheck both externally and internally for any loose or damaged components that may affect theappearance, installation or operation of the goods. The index is supplied loose.
2.2 Anti Static Precautions
To prevent damage to panel components please ensure before touching or handling any of thewiring or printed circuit boards within the panel that you are correctly earthed.
3 SPECIFICATIONS
Size - 450H x 400W x 130D (NZ 3200/16)- 753H x 400W x 130D (NZ 3200/32)
Mains Supply - 230V AC ± 10% @ 0.5A
Power Supply Battery ChargerOutput Voltage 27VOutput Current(continuous) 1AOutput Current(peak) 1.8AQuiescent Current API708 0.045AQuiescent Current API588 0.053ABell Circuits 2 X 2AAuxiliary Relay Change Over Contacts @ 30V,5A
Detector CircuitsMaximum Cable Loop Impedance 50 Σ
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 5
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
4 SYSTEM DESCRIPTION
4.1 General Description
The NZ3200 is available in two standard formats - the NZ3200/16 and the NZ3200/32. TheNZ3200/16 accommodates the API708 Main System Board, and one, eight-zone circuit boards(API588) giving a total of 16 circuits. These circuits can operate with smoke detectors, heatdetectors and manual call points. The NZ3200/32 panel accommodates the API708 Main SystemBoard, and up to three eight-zone circuit boards (API 588) giving a maximum capacity of 32circuits.
4.2 System Layout
Figure 4.1 NZ3200/16 System Layout
CN6
TB1ZD1
G1
Z1
Z8
Z7
Z6
Z5
Z4
Z3
Z2
Z1
-
+
+
+
+
+
+
+
+
-
-
-
-
-
-
-
API 588 8 ZONE AZF
Z2
Z3
Z4
Z5
Z6
Z7
Z8
MAINSSWITCHBLOCK
TRANSFORMER
API 588
TRANSPONDERAREA
RELAY AREA
RELAY AREA
RELAY AREA
SW
9
SW1
SW
8S
W7
D2
8
TB2
D3
3D
38
D4
1D
47
D5
0D
53
D5
6D
59
D3
1D
37
D4
0D
44
D5
2
D5
5D
58
D3
6D
39
D4
3D
48
D5
1
D5
4D
57
CN10
LM
P1
BZ1
+
R10
RV1
CN3
U1
F5
F1
F4
D2
3D
24
D2
6D
18
D5
D8
D11
D15
D9
D16
D10
D6
D21D20 D22
TB5
R2
SW5
SW4
CN4
TB3
SW3
TB4
D1
CN5
CN1
D49
F2 F3
R21
RV2
SW2
SW6
TB
1
TB
6
R9
M1
25 Nov 1998
MIM
IC L
ED
Z8
Z7
Z6
Z5
Z4
Z3
Z2
Z1
-
-
-
-
-
-
-
-
+
+
+
+
+
+
+
+
POWER
LAMP
2A
2A
3A1A
VOLTAGE
CHARGER
SET
TRIM
V.SENSE
NORMAL
DEFECT
DBA
FIRE
Z5
Z6
Z7
Z8
Z4
Z3
Z2
Z1
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
-+
BE
LL
-+
BE
LL
Defects
Ext.
Bell
System
Battery
RESET
RESETTEST
BELL
ISOLATEMUTE
BUZZER WALKSELF
Mains On
NORMAL
AUXILARY
ISOLATE
3A
ACAC
LOCK
INTER-
DEFECT
EXT.DBA
COM
SWITCHES
N/C
N/O
AU
X
API 708
NZ3200 Main system board
0V 0VBAT+27V
OUTPUT
SG
D T
ype II
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 6
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
4.3 Main System Board API 708
The Main System Board provides most of the functions, common connections required by theNZ3200 system and the first eight zones.
The API 708 provides the following:Bell circuits.Transponder connections.Controls - Reset, Bell Isolate etc.System status indication.Power supply.Eight zone circuits.ASPI relay connection
Figure 4.2 API-708 Main System Board
R67
M2
M3
SW
9
BR1
-
+
RN13
ZD13
ZD12
ZD11
ZD10
ZD9
ZD8
ZD7
ZD6
CN7CN9
R63
C9+
C26
R22
R26
R29
CN8
C20
C38
C32
C25
C33
RN
7
RN
10
C16
+
SW1
SW
8
U9
R24
X1
U7
U17
U14
U16
U18
SW
7
M12
M18
M9
M13
M17
M16
M14
M7
M5
M11
M15
M19
C19
C23
C24
C29
C30
C34
C36
C39
RN11
C40
D28
C7
+
U10
U13
RN12
U11
U15
CN6
C21RN4
R64
D45
TB2
D33
D38
D41
D47
D50
D53
D56
D59
D31
D37
D40
D44
D52
D55
D58
D36
D39
D43
D48
D51
D54
D57CN10
LMP
1
R33
R35
R37
R38
R41
R43
R45
R47
R49
R51
R55
R56
R58
R59
R62
R65
R36
R39
R44
R48
R52
R57
R60
R66
M4
M6
M8
M10
D13
BZ1
+
C11
R14
R10
R4
R1
Q4
D4
RV1
CN3
U1
L1
C13
D19
ZD
4ZD3ZD2
R8R7
R6
F5
R20
F1
F4
RL2
///
N/C
C
N/O
D23
D24
D26
D18
D5
D8
D11
D15
D9
D16
D10
D6
TH
1
C1
+
RL1
C8
+
U4
D21D20 D22
TB5
R12
R11
R13
R2
ZD1
SW5
SW4
CN4
C3
TB3
D14
ZD5
RN3
SW3
TB4
C5C6
R5
D3R3
C4
D7
D2
D25
D1
D12
C2
C12
C17
C18
+
C10
+
C15
C14
+
C41
C35
C27 C28
C37
C22
+
C31
CN2
CN5
CN1
D29
D27
D34D35
D42
D46
D17
D30
D49
D32
F2 F3
L4
L3
L2
Q3
Q2Q1
Q5
R27
R30
R31
R19
R16R17
R18
R40
R15
R28
R23
R54
R25
R46
R53
R42
R50
R21
R61
R34
R32
RN1 RN
2
RN9
RN5
RN6
RN
8
RV2
SW2
SW6
TB
1
TB
6
U5
U3
U6
U8
U12
U2
R9
M1
D60
R68
R69
25 Nov 1998
MIM
IC L
ED
Z8
Z7
Z6
Z5
Z4
Z3
Z2
Z1
-
-
-
-
-
-
-
-
+
+
+
+
+
+
+
+
POWER
LAMP
2A
2A
3A1A
VOLTAGE
CHARGER
SET
TRIM
V.SENSE
EXT LED
NORMAL
DEFECT
DBA
FIRE
Z5
Z6
Z7
Z8
Z4
Z3
Z2
Z1
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
-+
BE
LL
-+
BE
LL
Defects
Ext.
Bell
System
Battery
RESET
RESETTEST
BELL
ISOLATEMUTE
BUZZER WALKSELF
AS
PI
Mim
ic
Mains On
NORMAL
AUXILARY
ISOLATE
3A
ACAC
LOCK
INTER-
DEFECT
EXT.DBA
COM
SWITCHES
N/C
N/O
AU
X
Z8Z1
API 708NZ3200 Main system board
0V 0VBAT+27V
0V 0VBAT+27V
AC AC
OUTPUT
SG
D T
ype
II
Power supply connetion
Interlock connection
External defect connection
Direct Brigade Alarm input
SGD Type II connection
Auxrelayoutput
AC input fuse
ExtendedLEDConnection
SwitchConnection
Zoned bell selection switchZoned fire brigade call selection switch
Fire zone configuration switch
BellOutput
DetectorZones
Remote mimic connection
ASPI relay connectionConnection to zone cards
Auxillary relay isolate switch
Lamp connectionSystemconfigu-ration
ExtendedLED connnectionzones 1-8
Resetswitch
Defectindicators
Zonedefectindicator
Zone fireindicator
Bellfuse
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 7
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
4.3.1 Detector Circuits
The API 708 provides connection to eight zone circuits. All of the detector circuits can beconfigured to accept smoke detectors, heat detectors, manual call points or a combination ofthese devices. Detectors or manual call point types used are subject to the compatibilitylimitations as described in section 4.
Open circuit operating devices will cause the panel to go into alarm within one second. Devicessuch as smoke detectors, which signal by increasing line current, can, when signalling, gothrough an optional Alarm Verification Facility (AVF). As such, when a detector goes into alarm, itis reset and not monitored for six to seven seconds, if an alarm is still present after this time, thesystem will latch into alarm. This function may be de-selected if desired in groups of two. Seesection 6 for details.
4.3.2 Bell Circuits
The NZ3200 provides a monitored bell circuit split to drive two x 2Amp circuits. These circuitseach require a 10K EOL resistor to give a system normal indication. If circuit is open or shorted, adefect signal is generated and the “Bells Fault” LED is illuminated.
See section 4 for connection details.
4.3.3 Bell Isolate (Internal)
This facility is set or reset by alternate pushes of the bell isolate switch. The yellow LED abovethe internal bell isolate switch indicates when the bell is isolated. When the bell is isolated, thebell relay will not respond to fire conditions thus enabling the system to be tested withoutdisturbing the building occupants. This switch is monitored, see section 4.2.6.
4.3.4 Self Test
Pressing the “Test” button twice activates this function. This causes the unit to test each zonesequentially by placing it into alarm and defect conditions. When it has completed this test, it willautomatically return to its normal mode of operation. This self-test may be terminated at any timeby another press of the switch.
During the self test the Fire, Defect and Bell outputs are inhibited.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 8
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
4.3.5 Walk Test
This function is initiated by pressing the “Test” button once on the Main System Board. When thisbutton is pressed a LED directly above the switch indicates. While the panel is in the walk testmode the detectors can be operated in the field and the panel will automatically reset them after aperiod of four seconds. During the test the bell output and brigade output will operate as normal.To prevent an unnecessary fire call it is recommended to isolate the brigade. To restore the panelto normal operation simply repress the switch and the walk test indicator will turn off. This switchis monitored, see section 4.2.6.
4.3.6 Door Interlock
If any of the monitored switches as listed below within the NZ3200 are not in their normal statewhen the door is closed the buzzer will sound to alert the operator to this condition. If thecondition is not rectified within two (2) minutes then a defect is signalled.
The following switches are monitored: Isolate, Test, AUX Relay Isolate, Walk Test and InternalBell Isolate. If the Walk Test or Internal Bell Isolate are active when the door is closed, theyautomatically return to their normal state after forty seconds.
Provision is also made for auxiliary switches to be wired into the door interlock warning systemvia the door interlock input on the Main System Board.
4.3.7 Fault Indicators
Fault indicators are provided on the Main System Board for the following.
(a) Battery Fault. This indicates if the battery voltage is below 24.3 volts.(b) Bell Fault. This indicates an open or short circuit on bell line/s.(c) System Fault. This indicates one of the following:
Communications fault.A module is disconnected.The door was closed with a switch not in its normal position. See section 4.2.6.
(d) External defect(e) Zone defects (eight of)
4.3.8 DBA Input
An input is provided for connection to any external device providing a Direct Brigade Alarm (DBA)output, eg sprinkler systems. A short circuit on this line will cause the DBA LED to light and thesystem bells to be energised. This input is monitored for normal condition with a 10K resistor. Anopen circuit will cause the DEFECT and SYSTEM LED to illuminate and the defect output to beenergised.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 9
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
4.3.9 Power Supply
The Main System Board has an on board switch mode power supply providing 27VDC at 1A forsystem power and charging the system batteries. The system incorporates a test function,controlled by the CPU on the API 708, which decreases the power supply output voltage for forty-five minutes, every forty eight hours to check the condition of the system batteries. If the batteryvoltage falls below 24.3V during the test period a defect signal is generated and the battery faultLED is illuminated.
The system checks that the battery is connected four times a minute using the same test asabove except the reduced voltage lasts for half a second.
4.3.10 Mains On Indicator
This LED is illuminated when the main power supply is connected and operational.
4.3.11 Ancillary Power Output
A fused power supply output is provided to power ancillary devices. The output is marked +27Vand 0V on TB1.
4.3.12 Fusing
The Main System Board has five fuses:F1 Power supply fuse 3 Amp M205F2 Power supply output fuse 1 Amp M205F3 Battery fuse 3 Amp M205F4 Bell circuit fuse 2 Amp M205F5 Bell circuit fuse 2 Amp M205
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 10
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
4.4 Zone Board - API 588
The API 588 Zone board provides all the necessary functions to control andmonitor eight (8) detector circuits. Up to three API 588 zone boards may be fittedto an NZ3200 system (NZ3200/32).
Figure 4.3 API-588 Zone Card
4.4.1 Detector Circuits
The API-588 zone board provides eight zone circuits, which operate identically to those providedon the API-708 board. See also section 3.2.1
4.5 Batteries
The NZ3200/16 system is designed to accept two x 12V, 7 AH sealed lead acid batteries. Theseare fitted into the shelf on the inside of the door.
The NZ3200/32 system will accommodate two x 12V, up to 12 AH sealed lead acid batteries.These sit in the base of the cabinet.
See also Appendix A for battery calculations.
CPUAddress setting Mimic LED outputs
Connection from previous zone boardConnection to next zone board
Connection to auxiliary relay boards (ASPI) Configuration DIP switchFire selection DIP switchBell selection DIP switch
Lamp (fitted to rear of PCB)Detector zone connection
CN6
LMP
1
CN2
CN11AUX.POWER
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
TB1
D9R31
RN4
CN5
ULN
2804
74HC573
74HC573
U13LM7805
DEFECT
+
U12
ec
b
RN1
SW3
UDN2983
74H
C57
4
74HC573
74HC574
U2
+
SW2
SW1
CN3
MIMIC DATA
K1
C36
R25
CN12
CN1
CN4AUX DATA
OUTPUT
ON TO
MIM
IC L
ED
Z8Z1
ENABLE
SWITCH
CO
NFI
G
FIRE
BELL
Z1
Z8
Z7
Z6
Z5
Z4
Z3
Z2
Z1
-
+
+
+
+
+
+
+
+
-
-
-
-
-
-
-
API 588 8 ZONE AZF
Z2
Z4
Z5
Z6
Z7
Z8
ZONE
Z3
FIRE
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 11
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
5 CONNECTING DEVICES
5.1 Detectors
Devices such as heat detectors or manual call points which are normally closed, open circuitingfor the alarm condition will give a fire signal within one second of operating.
Devices, which increase the current in the detector line such as smoke detectors, may beoperated with Alarm Verification as per section 3.2.1 to eliminate false alarms due to transientconditions. See also section 6 for details on alarm verification settings.
Figure 5.1 Detector Wiring
Note: These detectors must not directly short the line as a short circuit gives a defect signal.Devices that have closing contact outputs, such as beam detectors, should have a resistor, in therange of 220 to 560Σ installed in series with the contacts.Each circuit must be terminated with an end of line resistor with a value of 6.8K (5% tolerance orbetter, power rating 1/4W)
5.1.1 Detector Limitations
Most detectors, with the exception of thermostatic heat detectors, draw a small monitoring currentand this limits the number detectors which can be connected to a given zone circuit. The totalquiescent current of all devices on a zone circuit must be less than 1.6mA @ 24V to ensurecorrect operation.
Appendix C lists the number of detector types, which may be fitted to a zone circuit.
+
-Z1
L1 OUT
L2
L1 IN
SMOKE DETECTOR(eg APOLLO SERIES60 DETECTOR)
MANUALCALLPOINT
EOLRESISTOR6.8K
HEAT DETECTOROPENING ONALARM
THIS DRAWING IS INDICATIVE OF WIRING ONLY.ANY COMBINATION OF DETECTORS AND MANUAL CALL POINTS
WITHIN SPECIFIED LIMITS IS PERMISSABLE.
560 OhmResistor
BEAMDETECTORCONTACTS
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 12
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
5.2 Bells and Sounders
Two bell/sounder circuits are provided, each capable of driving a 2 Amp load. These lines aremonitored using a small current in reverse polarity to normal. For this reason it is necessary toconnect the bells via diodes, 1N4004 diodes are recommended, as shown in Figure 4.2. Alsoobserve bell/sounder polarity.If required these lines can be split to provide three or four bell circuits total, as shown, however ifthis is done the end of line resistor must be changed. See table 4.2 for further detail.
Figure 5.2 Bell Sounder Connections
Table 4.2
Bell Output 1 Bell Output 2
First Circuit Second Circuit First Circuit Second Circuit
No ofCircuits
EOL CurrentAvailable
EOL CurrentAvailable
EOL CurrentAvailable
EOL CurrentAvailable
1 10K 2A - - *10K - - -
2 10K 2A - - 10K 2A - -
3 22K 1A 22K 1 10K 2A - -
4 22K 1A 22K 1 22K 1A 22K 1
* Note: For one bell circuit a 10K EOL is required on the panel on bell output 2.
B B
*EOL
+
-
BELLS
BELL O/P 1
B B
*EOL
1ST CIRCUIT
2ND CIRCUIT ON BELL OUTPUT 1 (OPTIONAL)
1N4004DIODES
BELLS
1N4004DIODES
S
S
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 13
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
6 CONNECTING BRIGADE INTERFACES
The NZ3200 system allows for connection to the brigade signalling network using a SignalGenerating Device (SGD Type II).
6.1 Connecting a Signal Generating Device (BD0678)
To install the SGD firstly mount the unit on standoffs within the cabinet as shown below.
Figure 5.1 Connecting a BD0678 SGD II
Connect SGD to the API708 as indicated. All signals required for the SGD brigade signalling arefound on connectors CN1. The BD0678 Signal Generating Device from AMPAC is supplied with aconnection cable. Simply connect one end of the cable to CN1 of the BD0678 and the other toCN1 of the API708.
MOUNT SGD ONSTAND OFFSPROVIDED INTHIS POSITION.
CONNECT CABLESTO CONNECTORS CN1.
CONNECT TO CN2
MAINSSWITCHBLOCK
TRANSFORMER
CN6
TB1ZD1
G1
Z1
Z8
Z7
Z6
Z5
Z4
Z3
Z2
Z1
-
+
+
+
+
+
+
+
+
-
-
-
-
-
-
-
API 588 8 ZONE AZF
Z2
Z3
Z4
Z5
Z6
Z7
Z8
API 588
SW
9
SW1
SW
8S
W7
D28
TB2
D33
D38
D41
D47
D50
D53
D56
D59
D31
D37
D40
D44
D52
D55
D58
D36
D39
D43
D48
D51
D54
D57
CN10
LM
P1
BZ1
+
R10
RV1
CN3
U1
F5
F1
F4
D23
D24
D26
D18
D5
D8
D11
D15
D9
D16
D10
D6
D21D20 D22
TB5
R2
SW5
SW4
CN4
TB3
SW3
TB4
D1
CN5
CN1
D49
F2 F3
R21
RV2
SW2
SW6
TB
1
TB
6
R9
M1
25 Nov 1998
MIM
IC L
ED
Z8
Z7
Z6
Z5
Z4
Z3
Z2
Z1
-
-
-
-
-
-
-
-
+
+
+
+
+
+
+
+
POWER
LAMP
2A
2A
3A1A
VOLTAGE
CHARGER
SET
TRIM
V.SENSE
NORMAL
DEFECT
DBA
FIRE
Z5
Z6
Z7
Z8
Z4
Z3
Z2
Z1
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
DEFECT
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
FIRE
-+
BE
LL
-+
BE
LL
Defects
Ext.
Bell
System
Battery
RESET
RESETTEST
BELL
ISOLATEMUTE
BUZZER WALKSELF
Mains On
NORMAL
AUXILARY
ISOLATE
3A
ACAC
LOCK
INTER-
DEFECT
EXT.DBA
COM
SWITCHES
N/C
N/O
AU
X
API 708
NZ3200 Main system board
0V 0VBAT+27V
OUTPUT
SG
D T
ype II
K2
M4
R10
U7
C11
C10
BZ
1
+
M3
M1
C2
+
U1
C1
+
CN
1
CN
2
R1
X1
R6
C5
C4
R2
RN2
K1
C6
U3
C7
RN
1
R8
R9
R7
Q1
C8
C3
U4
R3
L1
ZD
1
L2
ZD
2
TB
1
M2
F1
D1
R5
U2
RN
3
R12
R11
R13
R14
U6
U5
R4
SW2
SW1 C9
AP
I 678
250m
A
7/8
/97D
OO
R
SW
ITC
H
FIR
E
SY
ST
EM
All lin
ks o
ff = 1
6
SG
D
AD
DR
ES
S
PO
LL
ISO
LA
TE
DE
FE
CT
FIR
E
NO
RM
AL24 18
TE
ST
ISO
LA
TE
NO
RM
AL
NO
RM
AL
B-+ A
BA
TC
H
TE
ST
ED
IIT
ype
SG
D AM
PA
C
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 14
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
7 SETTINGS
7.1 Main System Board (API 708) Settings
The main system board has four (4) banks of DIP switches which are used to set the following:
SW6 - Zone cards fitted, monitoring etc.SW7 - Zone bell setting.SW8 - Zone fire output setting.SW9 - Zone configuration.
Note: each switch bank has eight switches. In the following discussion the bank is nominated firstand the switch within that bank last. Thus SW6-2 would be the second switch on bank SW6.
7.1.1 Setting the number of zone cards
Switches 1 and 2 of switch bank SW6 set the number of zone cards fitted to the system as shownin the table below.
Number of zone cards SW6 - 1 SW6 - 2
0 OFF OFF
1 ON OFF
2 OFF ON
3 ON ON
7.1.2 Miscellaneous settings
The remaining six switches in switch bank SW6 set the functions as listed in the table below. Setthe switch to the on position to enable the function.
Switch Function
SW6-3 Direct Brigade Alarm
SW6-4 Bell monitoring
SW6-5 Sound buzzer for defects
SW6-6 Factory use only – Must be set to OFF.
SW6-7 Switch on auxiliary output during trial evacuation
SW6-8 Unused
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 15
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
7.2 Setting zone bell output
Each zone on the API708 may be selected to either sound or not sound the bells when in alarm.To set a zone to sound the bells set the DIP switch on bank SW7 to on. For example to set zonetwo (2) to sound the bells when in alarm set SW7- 2 to on.
7.2.1 Setting zone brigade call output
Each zone on the API708 may be selected to either call or not call the brigade when in alarm. Toset a zone to call the brigade set the DIP switch on bank SW8 to on. For example to set zone two(2) to sound the bells when in alarm set SW8- 2 to on.
7.2.2 Setting zone configuration
Zones on the API708 can be set to four different styles. The zones are set in pairs. SwitchesSW9-1 and SW9-2 set the operation of zones one and two, SW9-3 and SW9-4 set the operationof zones three and four and so on.
Zone 1 and 2 configuration.Zone style SW9-1 SW9-2
Heat only Off Off
Smoke only Off On
Combined (Heat and Smoke) On Off
Combined with Automatic Verification On On
Zone 3 and 4 configuration.Zone style SW9-3 SW9-4
Heat only Off Off
Smoke only Off On
Combined (Heat and Smoke) On Off
Combined with Automatic Verification On On
Zone 5 and 6 configuration.Zone style SW9-5 SW9-6
Heat only Off Off
Smoke only Off On
Combined (Heat and Smoke) On Off
Combined with Automatic Verification On On
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 16
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
Zone 7 and 8 configuration.Zone style SW9-7 SW9-8
Heat only (Heat and Smoke) Off Off
Smoke only Off On
Combined On Off
Combined with Automatic Verification On On
7.3 Zone card (API 588) Settings.
The zone card has three (3) banks of DIP switches which are used to set the following:
SW1 - Zone bell setting.SW2 - Zone fire output setting.SW3 - Zone configuration.
Also a set of four jumper pins is used to set the address
7.3.1 Setting the address of the zone cards.
For the zone card to function correctly the address must be set using the address jumpers whichare found immediately above the micro-controller. Each card in the system must have a uniqueaddress.
Address Setting
Address Setting
Address Setting
SettingAddress
1
2
3
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 17
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
7.3.2 Setting zone bell output
Each zone on the API588 may be selected to either sound or not sound the bells when in alarm.To set a zone to sound the bells set the DIP switch on bank SW1 to ‘ON’. For example to setzone two (2) to sound the bells when in alarm set SW1-2 to ‘ON’
7.3.3 Setting zone brigade call output
Each zone on the API588 may be selected to either call or not call the brigade when in alarm. Toset a zone to call the brigade set the DIP switch on bank SW2 to ‘ON’. For example to set zonetwo (2) to call the brigade when in alarm set SW2- 2 to ‘ON’.
7.3.4 Setting zone configuration
Zones on the API588 can be set to four different styles. The zones are set in pairs. SwitchesSW3-1 and SW3-2 set the operation of zones one and two, SW3-3 and SW3-4 set the operationof zones three and four and so on.
Zone 1 and 2 configuration.Zone style SW3-1 SW3-2
Heat only Off Off
Smoke only Off On
Combined (Heat and Smoke) On Off
Combined with Automatic Verification On On
Zone 3 and 4 configuration.Zone style SW3-3 SW3-4
Heat only Off Off
Smoke only Off On
Combined (Heat and Smoke) On Off
Combined with Automatic Verification On On
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 18
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
Zone 5 and 6 configuration.Zone style SW3-5 SW3-6
Heat only Off Off
Smoke only Off On
Combined (Heat and Smoke) On Off
Combined with Automatic Verification On On
Zone 7 and 8 configuration.Zone style SW3-7 SW3-8
Heat only Off Off
Smoke only Off On
Combined (Heat and Smoke) On Off
Combined with Automatic Verification On On
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 19
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
8 INSTALLATION AND INITIAL OPERATION
8.1 Installing the NZ3200
Do not apply power or connect batteries during this procedure.
1. Unpack the NZ3200 system.2. Check for transit damage.3. Unplug CN1 from the Main System Board and battery leads from TB1.4. Using a screwdriver undo four (4) slotted nuts holding the internal panel into the cabinet.5. Withdraw the internal panel.6. Drill all cable access and mounting holes.7. Mount the unit into position.8. Feed cables into the unit.9. Install the engraved index with mounting provided.10. Install the internal panel and secure with slotted nuts.11. Install any option cards and/or transponder.12. Connect mains cabling to the mains switch. Ensure incoming Mains is properly earthedusing stud provided.13. Connect detector cabling.14. Connect ancillary cabling.15. Set DIP switches on the API 708 and API 588 as necessary, see section 6.
8.1.1 Removing and reinstalling the index panel
To remove the index panel with the panel installed and wired requires the following before theabove procedure can be performed.
1. Turn off mains power to the unit at the distribution board.2. Disconnect the batteries.3. Disconnect mains cabling from the switch block.4. Unplug TB1 from the API 588 and API708 boards. There is no need to undo the detectorcabling.5. Disconnect the cabling to the bells.6. Disconnect the battery cables from the batteries and unplug TB1.7. Remove any other cabling to the MAF by unplugging the terminal block/s.8. Repeat required steps above from step 4.
8.1.2 Initial operation
1. Switch on mains power to the unit.2. The internal buzzer will sound for approx one second. Battery defect LED should beilluminated.3. Connect batteries. Press ‘RESET’, Battery defect LED should extinguish.4. The unit is ready for operation.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 20
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
9 SYSTEM OPERATION
9.1 Resetting the system
To reset the system after a fire, press the ‘RESET’ button on the Main System Board. This willreturn the system back to its normal state. The buzzer will sound for confirmation.
9.2 Isolating the Bells/Sounders
Bells may be isolated by either pressing the Bell Isolate switch on the Main System Board, or byoperating the ‘Silence Alarms’ key switch on the outside of the cabinet.
Pressing Bell isolate on the Main System Board will cause the buzzer to beep and the LED abovethe switch to illuminate. To return Bells to normal press the switch again.
Note: Operating the key switch will cause a Defect signal to be sent.
9.3 Using the Walk Test facility
To start the walk test facility, press the ‘Test’ switch on the Main System Board. The buzzer willbeep once and the LED above the switch will illuminate. To avoid signalling the brigade isolatethe Signal Generating Device (SGD). If it is not desirable to operate the sounders then isolate thebell as detailed above. Do not close the door at this stage. See section 3.2.7.
The detectors can now be tested. As a detector is set into alarm the system will operate asnormal, except that after approximately four seconds the detectors on the circuit in alarm will bereset. After testing is complete, press the ‘Walk Test’ switch to return to normal. Return any otherswitches to normal before closing the door of the NZ3200.
9.4 Self Test Facility
To start the test, press the ‘Test’ button twice. The system will now place each zone into fire anddefect conditions sequentially. After each zone is tested, the system will flash the Defect and FireLED of each zone that operated correctly.
The test will terminate when finished. It may also terminated at any time by a another press of the‘Test’ switch.
9.5 Trial Evacuation
On the door of the NZ3200 a key switch is provided for Trial Evacuation, operating this key switchwill cause the system to operate the bells. This will override any other bell isolate or silencecondition.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 21
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
10 OPTIONS
10.1 ASPI relay board
The ASPI (AMPAC serial peripheralinterface) relay board will provide theNZ3200 system with a 5 Amp relay contactfor use by ancillary devices.
A fire zone or certain system functions canactivate the relay. Refer to table 9 below.
To install the API 593:
Power system down.
Mount the board on standoffs at the bottom or left side of the panel. Holes are already drilled toaccept these.
To connect a single ASPI board to an API 708, plug one end of the eight-way cable provided intoCN1 of the ASPI board and the other end into CN7 of the API 708. To add more than one ASPIboard onto an API 708 connect CN1 of the second ASPI board to CN2 of the first, etc. Amaximum of eight ASPI boards is permitted per API 708. ASPI relay boards may also beconnected to the API588. Only four ASPI relay boards may be fitted to a single API 588.
On the ASPI board there are a number of options available. Link K1 sets the address of theboard, only one address may be selected, only the API 708 board uses address 1. Link K3 setsthe conditions that will activate the relay. Any combination is allowable. Link K2 must be leftopen. For example if the relay needs to activate from a fire on zone 1 or 2 then K1 would be setto 4 and jumpers inserted in select 1 and 2.
Turn system on and test relay functions.
Table 9Select Address 4 Address 2 * Address 1
1 Zone 1 alarm Buzzer Zone 1 defect
2 Zone 2 alarm Bell † Zone 2 defect
3 Zone 3 alarm Defect Zone 3 defect
4 Zone 4 alarm Fire ‡(selectedzones)
Zone 4 defect
5 Zone 5 alarm Fire (any zone) Zone 5 defect
6 Zone 6 alarm Normal Zone 6 defect
7 Zone 7 alarm Zone 7 defect
8 Zone 8 alarm PSU shutdown Zone 8 defect
* API 708 only
C5
+
C4
+
RN1C3
R7
R1
R6
R5
K3
SELECT
R4
U3
LM78
L05
K1ADDRESS
CN2CN1
TB1
C2
C1
K2RTNRL1
JS1-12V
Q1
BD139
U2
74H
C59
5
U1
74H
C13
8
D11
D10
D9D8
D7D6
D5
D4
D3
D2
D1
R3
R2
D12
78
654321
7654321
N/O
COM
N/C
API 593
AS
PI
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 22
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
11 TROUBLESHOOTING
Problem Possible cause/s Suggested remedy/ action
Mains LED is off Mains supply is not operational.
AC Fuse on MAF blown.
Check mains supply.
Check and replace if necessaryF1 on MAF.
System signals fire. Fire LED ison, no zones in alarm.
Battery voltage below 19.2V. If Main is off, see above.
If Mains is on, disconnectbattery. If voltage rises, replacebatteries.
Bell circuits in defect. Diodes not fitted in series withbell.
End of line not fitted.
Fuses blown.
Fit diodes to bells as shown insection 4.2.
Fit end of line resistor as statedin table 4.2
Check fuses F4 and F5 on MAF.Replace if necessary.
Heat detector, opening contacts,will not signal fire.
Too many smoke or electronicheat detectors on detector line.
Zone configuration is set tosmoke only.
Reduce detectors on line tolimits in Appendix C.
Change zone settings.
Manual call point will not signalfire.
Too many smoke or electronicheat detectors on detector line.
Zone configuration is set tosmoke only.
Reduce detectors on line tolimits in table Appendix C.
Change zone settings.
Zone always in defect. Line is shorted. Check and remove short.
Zone always in fire. End of line not fitted. Fit 6K8 end of line.
System defect LED flashesevery 4 seconds.
Cable to CN4 of API708 isdisconnected.
Reconnect cable.
External defect operated but isnot connected.
Wire link not fitted to externaldefect input.
Fit wire link.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 23
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
12 INDEX PANEL ENGRAVING
The NZ3200 is supplied with a front index panel, which has been pre-drilled to accept all theLED's for the system. The NZ3200 can also be supplied as a rear service panel. The panelshould be engraved as shown in the following illustrations. When the DBA facility is not required,the top two LED's indicate fire (see section 6 for DIP switch settings), where the DBA is used thetop LED indicates fire and the second LED indicates DBA.
12.1 NZ3200/16 without DBA. For rear service F.I.P.
In the example below the zone information, defect and normal have been engraved in 3mm highlettering and fire in 6mm high. Note that ‘FIRE’ should be situated between the two LED's forclarity.
DEFECT
NORMAL
FIRE
GROUND FLOOR
FIRST FLOOR
SECOND FLOOR
STAIRWELL
PLANT ROOM
GROUND FLOOR
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
PLANT ROOM
STAIRWELL
THIRD FLOOR
RE
F
20
.0 m
m
47
.0 m
m
36
0.0
mm
38
0.0
mm
REF
15.1 mm
27.8 mm33.0 mm40.5 mm
53.2 mm
65.9 mm
78.6 mm
91.3 mm
104.0 mm
116.7 mm
129.4 mm
142.1 mm154.8 mm
167.5 mm
180.2 mm
192.9 mm
254.7 mm
267.4 mm
281.0 mm
292.8 mm
314.0 mm
280.1 mm
205.6 mm
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 24
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
12.2 NZ3200/16 with DBA . For rear service F.I.P.
In the example below all information is engraved in 3mm high lettering.
FIRE
DBA
DEFECT
NORMAL
GROUND FLOOR
FIRST FLOOR
SECOND FLOOR
STAIRWELL
PLANT ROOM
GROUND FLOOR
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
PLANT ROOM
STAIRWELL
THIRD FLOOR
RE
F
20
.0 m
m
47
.0 m
m
36
0.0
mm
38
0.0
mm
REF
15.1 mm
27.8 mm33.0 mm40.5 mm
53.2 mm
65.9 mm
78.6 mm
91.3 mm
104.0 mm
116.7 mm
129.4 mm
142.1 mm154.8 mm
167.5 mm
180.2 mm
205.6 mm
254.7 mm
267.4 mm
281.0 mm
292.8 mm
314.0 mm
280.1 mm
192.9 mm
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 25
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
12.3 NZ3200/16 For front service F.I.P.
30.8 mm
43.5 mm
56.2 mm
68.9 mm
94.3 mm
107.0 mm
119.7 mm
132.4 mm
145.1 mm
170.5 mm
183.2 mm
195.9 mm
208.6 mm
221.3 mm
269.8 mm
282.5 mm
295.2 mm
5.5
mm
22
.0 m
m
29
6.0
mm
RE
F
257.1 mm
29
0.5
mm
81.6 mm
157.8 mm
325.0 mm
314.5 mm
7.5 mm
55
.5 m
m
15
5.5
mm
162.5 mm
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 26
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
12.4 NZ3200/32 For Rear service F.I.P
7.5
0 m
m
43
.50 m
m
36
7.5
0 m
m
RE
F
37
5.0
0 m
m
-0.00 mm
27.40 mm
40.10 mm
52.80 mm
65.50 mm
78.20 mm
90.90 mm
103.60 mm
116.30 mm
129.00 mm
141.70 mm
154.40 mm
167.10 mm
179.80 mm
192.50 mm
205.20 mm
217.90 mm
230.60 mm
243.30 mm
256.00 mm
268.70 mm
281.40 mm
294.10 mm
306.80 mm
319.50 mm
332.20 mm
344.90 mm
357.60 mm
370.30 mm
383.00 mm
395.70 mm
408.40 mm
456.30 mm
469.00 mm
481.70 mm
494.40 mm
540.00 mm
68.50 mm
202.50 mm
470.50 mm
336.50 mm
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A B
A
A
A
A
A
A
A
A
14.70 mm
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 27
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
12.5 NZ3200/32 For Rear service F.I.P
561.50 mm
529.46 mm
542.16 mm
572.00 mm
516.76 mm
504.06 mm
468.30 mm
455.60 mm
442.90 mm
430.20 mm
417.50 mm
404.80 mm
392.10 mm
379.40 mm374.00 mm366.70 mm
354.00 mm
341.30 mm
328.60 mm
315.90 mm
303.20 mm
290.50 mm
277.80 mm
265.10 mm
252.40 mm
239.70 mm
227.00 mm
214.30 mm
201.60 mm197.00 mm188.90 mm
176.20 mm
163.50 mm
150.80 mm
138.10 mm
125.40 mm
112.70 mm
100.00 mm
87.30 mm
74.60 mm
8.00 mmREF
5.5
0 m
m
22
.00
mm
55
.50
mm
15
5.5
0 m
m
28
9.5
0 m
m2
95
.00
mm
RE
F
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 28
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
13 Appendix A. BATTERY CALCULATION.
Firstly calculate system quiescent current
Item Quantity Current each mA Current mAControl andIndicatingEquipment
Main system board API 708 1 45 45
Zone Cards API 588 53
ASPI relays 6
Detectorcircuits
Thermostatic Heat Detectors 0 0
Manual Call Points 0 0
Ionisation Detectors
Photo-electric Smoke Detectors
Electronic Heat Detectors
Beam Detectors
Signalling SGD Type II (API 678) 2
Ancillary load
Total system quiescent current IQ (mA)
Secondly calculate maximum system alarm current
Item Quantity Current each mA Current mAControl andIndicatingEquipment
Quiescent current - -
Total zones used 26
MAF additional load 34
ASPI relays 20
Alarm Circuits Bells
Sounders
Ancillary load
Total alarm current IA mA
Minimum battery requirement is given by.
See appendix B for an example.
BATTERY SIZE =(24 x IQ) + (0.5 X IA)
1000=
(24 x ___) + (0.5 X ___) 1000
= AH
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 29
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
14 Appendix B. EXAMPLE BATTERY CALCULATION
Firstly calculate system quiescent current
Item Quantity Current each mA Current mAControl andIndicatingEquipment
Main system board API 708 1 45 45
Zone Cards API 588 1 53 53
ASPI relays 1 6 6
Detectorcircuits
Thermostatic Heat Detectors 40 0 0
Manual Call Points 3 0 0
Ionisation Detectors 53 .045 2.385
Photo-electric Smoke Detectors 0 - 0
Electronic Heat Detectors 11 .057 0.627
Beam Detectors 0 - 0
Signalling SGD Type II (API 678) 1 2 2
Ancillary load 0
Total system quiescent current IQ (mA) 109.01
Secondly calculate maximum system alarm currentItem Quantity Current each mA Current mA
Control andIndicatingEquipment
Quiescent current - - 109.01
Total zones used 16 26 416
MAF additional load - 34 34
ASPI relays 1 20 20
Alarm Circuits Bells 40 15 600
Sounders 5 100 500
Ancillary load 0
Total alarm current IA mA 1679.01
BATTERY SIZE =(24 x 109) + (0.5 X 1679)
1000= 3.45 AH
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 30
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
15 Appendix C. DETECTOR CIRCUIT LIMITATIONS.
Detector Type Quiescent Current Circuit Limit
Thermal Detector(opening on alarm)
0µA No limit
Manual Call Point 0µA No limit
Apollo Series 60 Heat Detector(55000-105)
57µA 28
Apollo Series 60 Heat Detector(55000-106)
57µA 28
Apollo Series 60 Heat Detector(55000-107)
57µA 28
Apollo Series 60 Heat Detector(55000-108)
57µA 28
Apollo Series 60 Ionisation SmokeDetector (55000-200)
45µA 35
Apollo Series 60 Photoelectric SmokeDetector (55000-300)
45µA 35 *
Hochiki America SIH 24F IonisationSmoke Detector
40µA 40
Hochiki America SLK 24FPhotoelectric Smoke Detector
45µA 35
Fenwal CDP7051Ionization Smoke Detector
45µA 35
Fenwal CDP7155Photoelectric Smoke Detector
55µA 29 *
*Software version 2.0 or greater. Due to turn on surge/delay, this type of detector should be used withAlarm Verification (gating) switched off if used with combined circuits with manual call points. Seeoperators manual for details.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 31
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
Appendix C. DETECTOR CIRCUIT LIMITATIONS.
Detector Type Quiescent Current Circuit Limit
Thermal Detector(opening on alarm)
0µA No limit
Manual Call Point 0µA No limit
Apollo Series 60 Heat Detector(55000-105)
57µA 28
Apollo Series 60 Heat Detector(55000-106)
57µA 28
Apollo Series 60 Heat Detector(55000-107)
57µA 28
Apollo Series 60 Heat Detector(55000-108)
57µA 28
Apollo Series 60 Ionisation SmokeDetector (55000-200)
45µA 35
Apollo Series 60 Photoelectric SmokeDetector (55000-300)
45µA 35 *
*Software version 2.0 or greater. Due to turn on surge/delay, this type of detector should be used withAlarm Verification (gating) switched off if used with combined circuits with manual call points. Seeoperators manual for details.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 32
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
Appendix C. DETECTOR CIRCUIT LIMITATIONS.
Detector Type Quiescent Current Circuit Limit
Thermal Detector(opening on alarm)
0µA No limit
Manual Call Point 0µA No limit
Apollo Series 60 Heat Detector(55000-105)
57µA 28
Apollo Series 60 Heat Detector(55000-106)
57µA 28
Apollo Series 60 Heat Detector(55000-107)
57µA 28
Apollo Series 60 Heat Detector(55000-108)
57µA 28
Apollo Series 60 Ionisation SmokeDetector (55000-200)
45µA 35
Apollo Series 60 Photoelectric SmokeDetector (55000-300)
45µA 35 *
*Software version 2.0 or greater. Due to turn on surge/delay, this type of detector should be used withAlarm Verification (gating) switched off if used with combined circuits with manual call points. Seeoperators manual for details.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 33
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
Appendix C. DETECTOR CIRCUIT LIMITATIONS.
Detector Type Quiescent Current Circuit Limit
Thermal Detector(opening on alarm)
0µA No limit
Manual Call Point 0µA No limit
Apollo Series 60 Heat Detector(55000-105)
57µA 28
Apollo Series 60 Heat Detector(55000-106)
57µA 28
Apollo Series 60 Heat Detector(55000-107)
57µA 28
Apollo Series 60 Heat Detector(55000-108)
57µA 28
Apollo Series 60 Ionisation SmokeDetector (55000-200)
45µA 35
Apollo Series 60 Photoelectric SmokeDetector (55000-300)
45µA 35 *
Hochiki America SIH 24F IonizationSmoke Detector
40µA 40
Hochiki America SLK 24FPhotoelectric Smoke Detector
45µA 35
Fenwal CDP7051Ionization Smoke Detector
45µA 35
Fenwal CDP7155Photoelectric Smoke Detector
55µA 29 *
*Software version 2.0 or greater. Due to turn on surge/delay, this type of detector should be used withAlarm Verification (gating) switched off if used with combined circuits with manual call points. Seeoperators manual for details.
AMPAC TECHNOLOGIES PTY LTDNZ3200 OPERATORS MANUAL
Page 34
DOC NO:G0059W04 DIR: VOL1 \..\G0059 DATE: 11/5/00 REVISION: 3
16 Appendix D. COMPATIBLE OUTPUT DEVICES.
Product Code Description
206-0002 Bell 24VDC Red 150 mm.
205-0008 Sounder with AS2220 Evac tone 9-28VDC 18mA.
209-0018 Sounder with LED and mute facility.
205-0006 Horn Siren 24VDC 200mA Red.
205-0002 AS2W Flush sounder White 12/24V 15mA .
205-0001 AS2R Flush sounder Red 12/24V 15mA.