nys dept. of taxation and finance rochester · the system will utilize multiple types of proximity...

17
Sheet No. Date Program Summary Reference 1 10/6/2017 N/A 2 10/6/2017 N/A 3 10/6/2017 N/A 4 10/6/2017 N/A 5 10/6/2017 S01-S05 6 10/6/2017 S06 7 10/6/2017 S07,S09, Workspaces(G) 8 10/6/2017 S08 9 10/6/2017 S10 10 10/6/2017 N/A 11 10/6/2017 S11,S12 12 Evidence Rms. 10/6/2017 S13 13 Lunch Rm. 10/6/2017 S14 14 10/6/2017 S15 15 10/6/2017 S16 16 10/6/2017 S17, Workspaces(C,D) 17 10/6/2017 Shared Facilities OGS Proj. No.: 19038 Dated: 10/6/2017 Server Rm. Specs. 1 All quantities and square footage amounts noted within the space forms and room data sheets are estimates only and should only be used as a guide. Actual quantities and square footage amounts will be determined during the Landlord's design process and are subject to OGS approval. Queue Area Private Offices NYS Dept. of Taxation and Finance Rochester Mail Rm. Open Office(incl. Copy/Fax/Printer,Hoteling Stations.) File Rms. Server Rm. Typical Requirements Sheet 4 of 4 Training Rm. Summary List Typical Requirements Sheet 1 of 4 Typical Requirements Sheet 2 of 4 Conference Rms. Employee Restroom Room Data Sheets for OGS Project No. 19038 Summary List Room Name Typical Requirements Sheet 3 of 4

Upload: trannguyet

Post on 29-Jul-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Sheet No. Date Program Summary Reference

1 10/6/2017 N/A

2 10/6/2017 N/A

3 10/6/2017 N/A

4 10/6/2017 N/A

5 10/6/2017 S01-S05

6 10/6/2017 S06

7 10/6/2017 S07,S09, Workspaces(G)

8 10/6/2017 S08

9 10/6/2017 S10

10 10/6/2017 N/A

11 10/6/2017 S11,S12

12 Evidence Rms. 10/6/2017 S13

13 Lunch Rm. 10/6/2017 S14

14 10/6/2017 S15

15 10/6/2017 S16

16 10/6/2017 S17, Workspaces(C,D)

17 10/6/2017 Shared Facilities

OGS Proj. No.: 19038 Dated: 10/6/2017

Server Rm. Specs.

1

All quantities and square footage amounts noted within the space forms and room data sheets are estimates only and should

only be used as a guide. Actual quantities and square footage amounts will be determined during the Landlord's design

process and are subject to OGS approval.

Queue Area

Private Offices

NYS Dept. of Taxation and Finance Rochester

Mail Rm.

Open Office(incl. Copy/Fax/Printer,Hoteling Stations.)

File Rms.

Server Rm.

Typical Requirements Sheet 4 of 4

Training Rm.

Summary List

Typical Requirements Sheet 1 of 4

Typical Requirements Sheet 2 of 4

Conference Rms.

Employee Restroom

Room Data Sheets for OGS Project No. 19038

Summary List

Room Name

Typical Requirements Sheet 3 of 4

X

X

X

X

Water Supply: (Hot & Cold)

X

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120vX

X

20

Indirect/Direct Recessed (LED) X

Narrow 4', 8' Recessed Slot LED

Recessed Round downlight LED

Decorative Susp. LED

Decorative wall sconce LED

Independently switched X

Dimmer switch(s) Number

X

typical

access

OGS Proj. No.: 19038

Pre-Action Dry Type Sprinkler

Semi-gloss Paint;

Acoustical Lay-in Tile

Ceiling Hgt: or specify other as appropriate Connect to UPS

Trim:

Chemical Fire SuppressionEggshell or Satin Paint;Walls:

Near: Direct Exhaust

No. of Spaces @ Net Sq. Ft.

Ventilation

9,100*

Away from:

To be determined during designNext to:

Cooling

Temperature Control

(Provide a description & number of occupants)

Section/Unit:

Relationship to Other Spaces: Humidification

HeatingEmployee spaces along with associated equipment for the purpose of

performing daily Agency office functions.

Carpetable Area is 14,213 sf. *

Utilities (place X as appropriate)Function of Space:

Various

Total Net Sq. Ft.

NYS Dept. of Taxation and Finance

Rochester

Low profile susp. Ind./Direct LED

Side Light:

(see individual RDS)

Amperes

Dedicated

Ceiling:

Lighting

Convenience

Type

Or As Required By Code

Keyed Lockset:Slab To Slab:

Ceiling High Solid: X

Single 36"

Connect to Emergency Generator

Other (specify size & no.)Double 36"

Doors Specify Type *Electric Power Receptacles:

Dry Type SprinklerCarpet Tiles

Wet Type Sprinkler(Indicate material, color to be selected at a later date)Finishes:

Rated:

as noted

Door Hardware: Specify Type

Hollow Metal:Solid Wood:

Duplex Quad

Floor:

Vinyl-Rubber

X

Wall Types:

Special Needs/Equipment Requirements: (Use 2nd sheet as needed)

Manual Pushpad:

Floor load:

Proximity readers

X

Projector Screen-Manual:

Electric Pushpad:

Partial Height:

Other:

Rated:

Sound Attenuation:

Other:

Passage Lockset:

10/06/17

Fiber Optics

Utilization of Space

Dated:

Sound System/Speakers

Sound Masking

Other: Wall Mounted Tack Strip:

A/V-Satellite Connection

2

See individual Room Data Sheets (RDS) for electric and data specifications beyond noted

here. 1.)Landlord shall distribute electrical and tel/data outlets as determined during design.

2.)For offices, workstations and work areas; computer receptacles shall be duplex and

uniquely identified by color. Maximum of 4 receptacles per 20 amp circuit. For each, provide

1-computer duplex receptacle, 2-combination tel/data receptacle box (2-ports each), and 2-

duplex convenience receptacles. Each of the two convenience receptacles shall be fed from

a different circuit. Maximum 8 convenience receptacles per 20 Amp circuit.

Special Features & Remarks: (Use 2nd sheet as needed)

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

Cable TV

Chair Rail:

Security:

Casework:

X Communications

IntercomWhite Bd w/Presentation Rail:

# of Tel/Data receptacle boxes

Projector Screen-Electric:

Ceiling Mount Projector:

Glass: Side Light on Conf. Rms. Computer

Real Estate Planning & DevelopmentSpace Program Room Data Sheet

Office Of General Services

State Of New YorkTypical Space Requirements

Division:Project Name:

Fire Suppression per codeOther:

Voltage

Bureau:

115

Winter Cooling (24 hrs x 7 days)

Base:

Air/Steam/Oxygen/Vacuum

(Describe as appropriate)

Reception/Waiting Area

Conference Center

Press Room with Green Rooom

Mail & Copy Area

Work Room

Law Library

13Interview/Viewing Room

14 File Room / High Density File-Records Room

15Storage Rooms & Secure Storage Rooms

16Lunch Room

17Coat Closets18Collaborative Spaces19Forensics Lab

21

OGS Proj. No.: 19038 Dated:3

Project Name:

No. of Spaces @ Net Sq. Ft.

10/06/17

Office Of General Services

Space Program Room Data Sheet

State Of New York

Total Net Sq. Ft.

Special Features & Remarks - Continued

Bureau:

Section/Unit:

Division:

Typical Space Requirements

NYS Dept. of Taxation and Finance

Rochester

Real Estate Planning & Development

Practice Floor Conference Rooms

3)Additional electrical/telcom/data boxes checked in electrical section of room data sheets are to be provided over and above that required at each staff workstation/desk. 4) Provide up to an additional 18 dedicated 20A duplex receptacles and 18 telecom/data boxes placed as directed by OGS for copiers, printers, faxes, and other specialized office equipment. Provide access for 136 telecommunication/data cable points (i.e. core drilling with flush distribution boxes for powered panels, and/or raised access floor (6'' minimum), and/or inwall access with metal boxes, conduits of sufficient size and quantity as determined by design, bushings, and drag line extended to above ceiling and/or in floor wire distribution system, etc). Landlord to fire seal as required after installation of cabling by others. If powered modular furniture panels are used, Landlord to provide and install power to and final electrical connection to panels and associated equipment.5)Power poles will not be acceptable. Provide service to workstations/desks and office requirements by wall and/or floor outlets as directed by OGS.6) All agency and associated spaces including accessibility to and from the outside must be ADA compliant.o Tax and Finance must remain separate and secured from other building occupants(including, but not limited to:

bathrooms,elevators,stairwells,etc., within Tax's space.)7) Temperature Controls: Maximum of 1/1200sf. Plus additional controls as required to address exterior wall heat loss/gain along with controls as called out in Room Data Sheets. Private offices may be grouped 4/temperature control (unless noted otherwise) or less as required to address heat loads.8) Where sound attenuation is called out: walls, ceilings and doors shall be designed, specified and installed to meet or exceed required STC ratings & shall be addressed above ceiling and below raised access floor. Design parameters for rooms requiring sound attenuation shall meet sound transmission class (STC) ratings; large conference rooms, demising walls, toiletrooms STC 45-49. Executive offices, conference rooms of 4-8 occupants STC 40-44. Mechanical rooms adjacent to work areas STC 50-55. Enclosed break rooms STC 45-49. Open plan break rooms shall have provisions for reduced sound transmission at walls adjacent to work areas. . Specific rooms may require higher STC ratings as noted on Room Data Sheets. Design parameters for balanced noise criteria (NCB) utilizing recommended ANSI levels are: executive areas & conference rooms 25-30 NCB, open plan office areas 35-40 NCB, computer equipment rooms 38-43 NCB, main lobby areas 38-48 NCB & libraries 33-37 NCB.9) Sound masking in open office areas as required to achieve privacy levels.10) Each agency to have agency sub-master key under building master.(min. of 2 keys)11) Heating, ventilation and air conditioning (HVAC) systems must be capable of 24/7/365 operation. Tenant shall have ability to utilize HVAC as they deem necessary and shall request such services to the Landlord in advance. 12) Landlord to provide doors with keyed overide. Lock cylinders to be replaceable core.13) Landlord to provide door closers at all doors entering Agency space, secure areas and doors controlled by access card.14) Wiring for telephone-data lines to be done by Landlord's vendor. Landlord to provide conduit, junction boxes and drag lines. All Dept. of Tax and Finance cables and connections must be securely separated from other tenant cabling(no shared conduit). Network equipment cannot be co-located with other tenant equipment in order to meet IRS rules.15) A minimum of one convenience outlet is to be installed in corridors @ 20' O.C. for maintenance at landlord's expense.16) Provide window treatments on all exterior windows; Mechosystems Thermalveil, or equel approved by OGS. 17) In each IT Equipment Room and telcom and/or data closets provide grounding for tenant equipment: Wall mounted 1/4" x 4" x 10" Cu ground plate connected to building steel or suitable ground via # 4/0 Cu

CONT. ON NEXT PAGE

Conference Center

Press Room with Green Rooom

Mail & Copy Area

Work Room

Law Library

13Interview/Viewing Room

14 File Room / High Density File-Records Room

15Storage Rooms & Secure Storage Rooms

16Lunch Room

17Coat Closets

18Collaborative Spaces

19Forensics Lab

21

State Of New York

Total Net Sq. Ft.

Typical Space Requirements

NYS Dept. of Taxation and Finance

Rochester

No. of Spaces @ Net Sq. Ft.

Office Of General Services

Section/Unit:

Bureau:

Practice Floor Conference Rooms

OGS Proj. No.: 19038 Dated: 10/06/174

Special Features & Remarks - Continued

Project Name:

Real Estate Planning & DevelopmentSpace Program Room Data Sheet

Division:

18) Where needed all plywood will be 3/4" fire rated and painted to match wall. Mount plywood with bottom edge 3 ft. above finished floor.19) Landlord to provide connection to Cable TV (landlord submit vendor name).20) Landlord to provide blocking for wall mounted equipment/devices as specified by tenant. Placement to be determined during design. Landlord to install tenant provided monitors.21) Landlord to provide statement of existing generator availability and capacity for tenant's use.22) Landlord to install tenant provided AED cabinets, locations TBD.23) Tenant shall have access to the building 24/7. Landlord will contract with independent security contractor to provide and install security/access system at doors to access points into Tax spaces and doors as specified in the detailed room data sheets. System shall include:

Stand-Alone "non-web based proximity access control system with the following requirements:• HID Multi-Class iClass card compliant ,able to utilize current Tax issued HID Multi-Class iClass ID

cards.• Current cards are 35 bit encryption,2K class, standard programming,corporate 1000,software is

facility code enabled. The system will utilize multiple types of proximity devices, as well as a combination of "request to exit"

devices, including a doorbell video intercom with iClass radio frequency identification(RFID) reader, and electric strike (and/or) magnetic lock, Multi-Class iClass RFID prox reader with pin pad on peripheral doors, and Multi-Class iClass RFID prox readers w/o pin pad on internal doors.

One centralized, windows based platform PC system (single point of hardware/software configuration) for administration.

A windows-based PC that utilizes Win-Pak SE or PE software to act as database and storage, including desk mount card reader and all other peripheral devices configured for HID Multi-Class iClass FOBS of more than a single configuration.

The system must have a battery back-up that automatically activates during a total power failure and runs for 2 hours min.

The installed system must support multiple users' profiles,daylight savings, and holiday programming, etc...

If required by local code, and connected to a fire system, all doors must fail secure, but allow for egress. Secondary key lock to be placed on all peripheral doors to allow for the option of manual locking.

Overall security system design and all subsequent changes are subject to tenant approval, prior to installation.

o Landlord to coordinate cable runs with Landlord's locksmith,door vendor, security vendor, and construction contractor, etc...

o Security vendo to contract with tenant to provide a one year 24/7 on-site maintenance contract with maximum response time limit of two hours, renewed annually, for the proximity access control systemand all of its components (readers,software,auto door operators,etc.)

o Landlord to provide knox box located outside main facility doors for local fire department access to tenant space, in case of emergency.

o All external entry doors to be equipped with key lock deadbolt to be used as secondary means of securing tax space, in the event of extended power outage. All emergency exit doors to be fitted with panic hardware, and always secured from outside entry. Emergency exit doors to have local audible alarm with keyed reset. Multiple keys to be provided to designated Tax employees.

Conference Center

Press Room with Green Rooom

Mail & Copy Area

Work Room

Law Library

13Interview/Viewing Room

14 File Room / High Density File-Records Room

15Storage Rooms & Secure Storage Rooms

16Lunch Room

17Coat Closets

18Collaborative Spaces

19Forensics Lab

21

Special Features & Remarks - Continued

Practice Floor Conference Rooms

OGS Proj. No.: 19038 5 Dated: 10/06/17

NYS Dept. of Taxation and Finance

Rochester

Bureau:

Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

Project Name: Division:

Typical Space RequirementsState Of New York

Office Of General Services

Space Program Room Data Sheet Real Estate Planning & Development

Landlord to provide:a) Power, metal boxes, conduits of sufficient size as determined during design, bushings, and drag line

extended to above ceiling, and/or in floor wire distribution system, and for ceiling mounted cameras and access card readers (camersa and card readers by tenant). Number & placement to be determined by design.b) fire seal as required after installation of cabling by others.c) doors and frames to accept access system hardware & electric.d) electronic locks will be provided by security vendor.e) other type locks to be provided by landlord's locksmith as specified by tenant.

24) Video & Audio (& Wireless) conferencing equipment, presentation equipment, and ceiling & program speakers provided by tenant. Landlord to provide infrastructure, power, blocking, etc. where needed.25) All areas that are required to have manual lighting control, including rooms with single fixtures, shall incorporate an occupancy sensing device with override.26) Rooms calling for independent switch which have multiple doors must be provided with 3 or 4 way switching.27) Provide building common restrooms as required by building layout and code. 28) Landlord to identify availability and procedures for use for the freight elevator. Note availability for occasional transport of witnesses/offenders accompanied by investigators.29) All walls between tenant bureaus, hallways serving more than one bureau, and hallways facing public or other tenants shall be slab to slab in addition to those called for on Room Data Sheets.30) Noted specification sections within Room Data Sheets are to be used together with OGS Lease Materials Specifications for Leased Facilities. Noted specifications are the design intent for finish materials. Equal substitutions may be made with OGS and Tenant approval. 31) Program summary, concept drawings, stack diagram and room data sheets shall be used together. Concept drawings are guidelines based on generic floorplate. Landlord's design team shall provide design and construction documents per the lease.32) Landlord to provide non-yellowing corner guards on all wall outside corners.33) Landlord to supply all modular furniture, free standing furniture, conference room furniture, lunch/break room furniture, and queue area furniture as per tenant furniture specs. (documents attached)34) Landlord to provide recycling containers for kitchen/ break room, as well as individual under desk containers at desk cubicles, to meet local recycleing requirements.

X

X

X

X

Water Supply: (Hot & Cold)

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

X

X

X

20

Indirect/Direct Recessed (LED) X

X

X

X

X

OGS Proj. No.:

Conference Room(s) 175sf to 325sfState Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division:

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)

Multiple conference rooms of various sizes to accommodate staff.

* see program sheet for individual sizes.Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:

Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

6 various 1225*

Near: Direct Exhaust

Away from:

Other: Floor Drain

New York Metropolitan Transportation Council(Describe as appropriate) Humidification

Next to: To be determined during design Temperature Control

Base: Vinyl-Rubber Pre-Action Dry Type Sprinkler

Walls: Eggshell or Satin Paint; Chemical Fire Suppression

Finishes: (Indicate material, color to be selected at a later date) Wet Type Sprinkler

Floor: Carpet Tiles Dry Type Sprinkler

Ceiling Hgt: or specify other as appropriate Connect to UPS

Doors Specify Type *Electric Power Receptacles:

Trim: Semi-gloss Paint; Air/Steam/Oxygen/Vacuum

Ceiling: Acoustical Lay-in Tile Connect to Emergency Generator

Quad

Solid Wood: x Voltage

Single 36" Double 36" Other (specify size & no.) Type Duplex

Hollow Metal: Convenience

Rated: Dedicated

With Glass: Computer

Side Light: Amperes

Wall Types: Or As Required By Code Door Hardware: Specify Type Lighting

Ceiling High Solid: Passage Lockset:

Slab To Slab: Keyed Lockset: X Low profile susp. Ind./Direct LED

Partial Height: Manual Pushpad: Narrow 4', 8' Recessed Slot LED

Sound Attenuation: X Electric Pushpad: Recessed Round downlight LED

Rated: Proximity Reader: Decorative Susp. LED

Floor load: Projector Screen-Manual: Dimmer switch(s) Number

Security: Projector Screen-Electric: Communications

Folding Partition: Occupancy Notification: Decorative wall sconce LED

Special Needs/Equipment Requirements: (Use 2nd sheet as needed) Independently switched

Other: Wall Mounted Monitors: Cable TV

Special Features & Remarks: (Use 2nd sheet as needed) A/V-Satellite Connection

Casework: Ceiling Mount Projector: # of Tel/Data receptacle boxes

Chair Rail: White Bd w/Presentation Rail: Intercom

19038 6 Dated: 10/06/17

Flush mounted floor receptacle beneath conference table power/data. Minimum of two data lines

per room.Sound System/Speakers

Sound Masking

Fiber Optics

Utilization of Space

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

X

X

X

X

Water Supply: (Hot & Cold)

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

X

X

X

20

Indirect/Direct Recessed (LED) X

X

X

X

X

X

X

OGS Proj. No.: 19038 7 Dated: 10/06/17

Flush mounted floor receptacle - power/data. Landlord to provide commercial, ceiling mounted

projector and screen. Install (26) flush mounted floor receptacles for power/data(locations to be

determined by tenant.

Sound System/Speakers

Sound Masking

Fiber Optics

Utilization of Space

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

Other: Wall Mounted Monitors: Cable TV

Special Features & Remarks: (Use 2nd sheet as needed) A/V-Satellite Connection

Casework: Ceiling Mount Projector: # of Tel/Data receptacle boxes

Chair Rail: White Bd w/Presentation Rail: Intercom

Floor load: Projector Screen-Manual: Dimmer switch(s) Number

Security: Projector Screen-Electric: Communications

Folding Partition: Occupancy Notification: Decorative wall sconce LED

Special Needs/Equipment Requirements: (Use 2nd sheet as needed) Independently switched

Sound Attenuation: X Electric Pushpad: Recessed Round downlight LED

Rated: Proximity Reader: Decorative Susp. LED

Slab To Slab: Keyed Lockset: X Low profile susp. Ind./Direct LED

Partial Height: Manual Pushpad: Narrow 4', 8' Recessed Slot LED

Wall Types: Or As Required By Code Door Hardware: Specify Type Lighting

Ceiling High Solid: Passage Lockset:

With Glass: Computer

Side Light: Amperes

Hollow Metal: Convenience

Rated: Dedicated

Quad

Solid Wood: x Voltage

Single 36" Double 36" Other (specify size & no.) Type Duplex

Ceiling Hgt: or specify other as appropriate Connect to UPS

Doors Specify Type *Electric Power Receptacles:

Trim: Semi-gloss Paint; Air/Steam/Oxygen/Vacuum

Ceiling: Acoustical Lay-in Tile Connect to Emergency Generator

Base: Vinyl-Rubber Pre-Action Dry Type Sprinkler

Walls: Eggshell or Satin Paint; Chemical Fire Suppression

Finishes: (Indicate material, color to be selected at a later date) Wet Type Sprinkler

Floor: Carpet Tiles Dry Type Sprinkler

Near: Direct Exhaust

Away from:

Other: Floor Drain

New York Metropolitan Transportation Council(Describe as appropriate) Humidification

Next to: To be determined during design Temperature Control

Room to have Video Conferencing capability. Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:

Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

1 575 575

Training RoomState Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division:

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)

X

X

X

Water Supply: (Hot & Cold)

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

1

1

20

Indirect/Direct Recessed (LED) X

*1-2

X

OGS Proj. No.: 19038 8 Dated: 10/06/17

Special Features & Remarks: (Use 2nd sheet as needed) Sound System/Speakers Sound masking as required to comply with privacy level expections. *(2)

data lines needed in printer areas. (11) of the cubicles must be in close proximity

to the evidence room(s).

Sound Masking

Fiber Optics

Utilization of Space

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

Other: Wall Mounted Tack Strip: Cable TV

A/V-Satellite Connection

Casework: Ceiling Mount Projector: # of Tel/Data receptacle boxes

Chair Rail: White Bd w/Presentation Rail: Intercom

Floor load: Projector Screen-Manual: Dimmer switch(s) Number

Security: Projector Screen-Electric: *Communications

Other: Other: Decorative wall sconce LED

Special Needs/Equipment Requirements: (Use 2nd sheet as needed) Independently switched

Sound Attenuation: Electric Pushpad: Recessed Round downlight LED

Rated: Proximity Reader: Decorative Susp. LED

Slab To Slab: Keyed Lockset: Low profile susp. Ind./Direct LED

Partial Height: Manual Pushpad: Narrow 4', 8' Recessed Slot LED

Wall Types: Or As Required By Code Door Hardware: Specify Type Lighting

Ceiling High Solid: Passage Lockset:

With Glass: Computer

Side Light: Amperes

Hollow Metal: Convenience

Rated: Dedicated

Quad

Solid Wood: Voltage

Single 36" Double 36" Other (specify size & no.) Type Duplex

Ceiling Hgt: or specify other as appropriate Connect to UPS

Doors Specify Type *Electric Power Receptacles:

Trim: Semi-gloss Paint; Air/Steam/Oxygen/Vacuum

Ceiling: Acoustical Lay-in Tile Connect to Emergency Generator

Base: Vinyl-Rubber Pre-Action Dry Type Sprinkler

Walls: Eggshell or Satin Paint; Chemical Fire Suppression

Finishes: (Indicate material, color to be selected at a later date) Wet Type Sprinkler

Floor: Carpet Tiles Dry Type Sprinkler

Near: Direct Exhaust

Away from:

Other: Floor Drain

Relationship to Other Spaces: (Describe as appropriate) Humidification

Next to: To be determined during design Temperature Control

Open Office to contain workstations of various sizes distributed throughout

space. (81) @ 6x6, and (5) hoteling stations @ 7x7. (5) copy/fax/printer

stations @ 60sf placed near various work areas.

Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:

Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

91 see below 3,466

Open OfficeState Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division: All

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)

X

X

X

Water Supply: (Hot & Cold)

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

X

20

Indirect/Direct Recessed (LED) X

1 ea

X

OGS Proj. No.:

File Room(s)State Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division:

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)

File Storage. Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:

Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

3 250 750

Near: Direct Exhaust

Away from:

Other: Floor Drain

Relationship to Other Spaces: (Describe as appropriate) Humidification

Next to: To be determined during design Temperature Control

Base: Vinyl-Rubber Pre-Action Dry Type Sprinkler

Walls: Eggshell or Satin Paint; Chemical Fire Suppression

Finishes: (Indicate material, color to be selected at a later date) Wet Type Sprinkler

Floor: VCT Dry Type Sprinkler

Ceiling Hgt: or specify other as appropriate Connect to UPS

Doors Specify Type *Electric Power Receptacles:

Trim: Semi-gloss Paint; Air/Steam/Oxygen/Vacuum

Ceiling: Acoustical Lay-in Tile Connect to Emergency Generator

Quad

Solid Wood: Voltage

Single 36" Double 36" Other (specify size & no.) Type Duplex

Hollow Metal: X Convenience

Rated: Dedicated

With Glass: Computer

Side Light: Amperes

Wall Types: Or As Required By Code Door Hardware: Specify Type Lighting

Ceiling High Solid: X Passage Lockset:

Slab To Slab: Keyed Lockset: X Low profile susp. Ind./Direct LED

Partial Height: Manual Pushpad: Narrow 4', 8' Recessed Slot LED

Sound Attenuation: Electric Pushpad: Recessed Round downlight LED

Rated: Proximity Reader: Decorative Susp. LED

Floor load: TBD by LL Projector Screen-Manual: Dimmer switch(s) Number

Security: Projector Screen-Electric: Communications

Other: Other: Decorative wall sconce LED

Special Needs/Equipment Requirements: (Use 2nd sheet as needed) Independently switched

Other: Wall Mounted Tack Strip: Cable TV

A/V-Satellite Connection

Casework: Ceiling Mount Projector: # of Tel/Data receptacle boxes

Chair Rail: White Bd w/Presentation Rail: Intercom

19038 9 Dated: 10/06/17

Special Features & Remarks: (Use 2nd sheet as needed) Sound System/Speakers

Sound Masking

Fiber Optics

Utilization of Space

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

X

X

X

X

X

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish) X

9'

120v 220v

3

2 2

15 20 30

Indirect/Direct Recessed Fluor. X

X

1-54"

X

X

OGS Proj. No.: 19038 10 Dated: 10/06/17

Fiber Optics

Utilization of Space

24 hrs./day x 7 days/weekOther: Closer X

Special Features & Remarks: (Use 2nd sheet as needed)

IT Equipment Rooms rooms support carrier demarc connectivity, core network equipment, and any AV/Security sytem headend equipment.

Room to be served via 4" conduit from redundant/diverse points of entry (POE) in to the building for redundant/diverse circuit availability. Room

to be sized to accommodate three (3) carrier racks, four (4) system cabinets, and floor mounted HVAC units, estimated to be 20' x 20'.

Electrical systems for room to be served via redundant/diverse feeders from separate substations. Room to be served via a centralized UPS

system and individual circuits in room to be fed from diverse breaker panels. ER requires 24/7 continuous climate control. HVAC systems

should be designed to maintain an acceptable temperature range of of 64 degrees to 75 degrees F, and a relative humidity range of 30% - 55%.

Flooring shall consist of vinyl composite tile (VCT). 3/4" fire rated plywood to be installed on two (2) walls. No ceiling to be installed, cavity to be

encapsulated to eliminate flaking from fireproofing. Wall construction to meet a minimum of 2 hour fire rating for the room. Adequate lighting to

be installed and coordinated with equipment rack/ cabinet layout within room. Room can also serve as a TR for the same floor. Provisions to be

made to accommodate 4" conduits with innerduct and pull string as required to be installed on opposite sides of the room to accommodate

redundant/diverse backbone pathways to floor serving TRs. Telcommunications Grounding Busbar (TGB) to be installed in TR. Grounding riser

not required if building steel is continuous, #6 AWG grounding conductor to be installed from TGB to nearest building steel. Acoustical seals

recommended for doors. Security: Swipe-card access. Provide flood sensor monitoring that alarms to tenant as well as landlord. Landlord's

engineer shall confirm during design if additional structural support is required for consolidated UPS floor load.* Additional data and receptacle

box needed for stand-alone, off- TAX Network, access security system.

Cable TV

# of Tel/Data receptacle boxes*

Sound Attenuation: X Electric Pushpad:

Rated: Proximity Reader: X

Partial Height: Manual Pushpad:

Slab To Slab: X Keyed Lockset: X

Amperes

Wall Types: Or As Required By Code Door Hardware: Specify Type

Lighting

Rated: X

Independently switched

CommunicationsCeiling High Solid: Passage Lockset:

With Glass:

Side Light:

Computer

Solid Wood:

Voltage

Hollow Metal: X

Convenience

Doors Specify Type

Dedicated

Single 36" Double 36" Other (specify size & no.)

Type Duplex Quad

Ceiling: None

Connect to Emergency Generator

Ceiling Hgt: Enough to fit data racks ( )

Connect to UPS

Walls: Eggshell or Satin Paint;

Trim: Semi-gloss Paint;

Electric Power Receptacles

Floor: Anti-static VCT

Dry Type Sprinkler

Base: Vinyl-Rubber

Pre-Action Dry Type Sprinkler

Other:

Finishes: (Indicate material, color to be selected at a later date)

Chemical Fire Suppression

Air/Steam/Oxygen/Vacuum

Near: Direct Exhaust

Away From: Public access, sources of water

Relationship to Other Spaces: (Describe as appropriate) Humidification

Next to: Temperature Control

Wet Type Sprinkler

Centralized intake for outside vendor services to handoff to inside

business services. 3-4 Racks

Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

1 225 225

Server RoomState Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division:

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)

10/06/17

Equipment Room Specifications

Location: Located in a non shared tenant space, separated from EMI sources (Elevators, Switchgear

rooms, etc.)

Size: Estimated at 15' x15'

Power Requirements:

Temperature & Humidity: 64-75 degrees F and 30%-55% Rel humidity maintained by supplemental 24/7

continuos HVAC.

Lighting: 50 foot-candles measured three feet above the finished floor

Miscellaneous: 4' x 8’ x 3/4" fire-rated plywood mounted to two walls

Flooring: Anti-static VCT

False Ceiling: The room shall not have a false ceiling, to permit maximum use of cable pathways both

vertically and horizontally. In such cases, where fire-proofing may be sprayed onto the

exposed ceiling, the fire-proofing shall be treated to mitigate airborne dust.

Wall Construction: All four (4) walls shall be floor to deck and have a 2-hour fire rating.

Cabling Specifications: 50 micron multimode fiber backbone cabling from ER to Floor TRs divesely

routed. Multipair copper backbone cabling capability between ER and TRs for low speed dedicated circuit

requirements. Coaxial cabling for CATV requirement is TBD

Connecting Hardware:

Conduits and Sleeves: Should extend 4"-6" into the Typical IT Closet. If the conduits or

sleeves are subject to water intrusion, they must drain away from the room and be

watertight. All conduits and sleeves must have the ends plugged upon installation to keep

debris from entering the conduits and sleeves. All penetrations shall be provided with

fire-stopping for openings through fire and smoke rated wall and floor assemblies. Cable

tray shall not be run through walls. Conduits and sleeves must have bushings installed at all ends and at all

pull boxes. Room to be available to receive diverse electrical and carrier service feeds.

OGS Proj. No.: 19038 11 Dated:

X

X

X

Water Supply: (Hot & Cold)

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

X

X

X

20

Indirect/Direct Recessed (LED) X

X

X

X

OGS Proj. No.: 19038 12 Dated: 10/06/17

Special Features & Remarks: (Use 2nd sheet as needed) Sound System/Speakers*Keyed separately - non shared lock. High security area - reverse hinges

required. Block wall preferred. Optional build - 3/4" plywood,covered by a layer of

5/8" drywall. Either option to be slab to slab.

Sound Masking

Fiber Optics

Utilization of Space

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

Other: Wall Mounted Tack Strip: Cable TV

A/V-Satellite Connection

Casework: Ceiling Mount Projector: # of Tel/Data receptacle boxes

Chair Rail: White Bd w/Presentation Rail: Intercom

Floor load: Projector Screen-Manual: Dimmer switch(s) Number

Security: Projector Screen-Electric: Communications

Other: Other: Decorative wall sconce LED

Special Needs/Equipment Requirements: (Use 2nd sheet as needed) Independently switched

Sound Attenuation: X Electric Pushpad: Recessed Round downlight LED

Rated: Proximity Reader: X Decorative Susp. LED

Slab To Slab: X Keyed Lockset: X* Low profile susp. Ind./Direct LED

Partial Height: Manual Pushpad: Narrow 4', 8' Recessed Slot LED

Wall Types: Or As Required By Code Door Hardware: Specify Type Lighting

Ceiling High Solid: Passage Lockset:

With Glass: Computer

Side Light: Amperes

Hollow Metal: X Convenience

Rated: Dedicated

Quad

Solid Wood: Voltage

Single 36" Double 36" Other (specify size & no.) Type Duplex

Ceiling Hgt: or specify other as appropriate ( ) Connect to UPS

Doors Specify Type *Electric Power Receptacles:

Trim: Semi-gloss Paint; Air/Steam/Oxygen/Vacuum

Ceiling: Acoustical Lay-in Tile Connect to Emergency Generator

Base: Vinyl-Rubber Pre-Action Dry Type Sprinkler

Walls: Eggshell or Satin Paint; Chemical Fire Suppression

Finishes: (Indicate material, color to be selected at a later date) Wet Type Sprinkler

Floor: Carpet Dry Type Sprinkler

Near: Direct Exhaust

Away from:

Other: Floor Drain

Relationship to Other Spaces: (Describe as appropriate) Humidification

Next to: To be determined during design Temperature Control

(1) @ 60sf, (1) @ 150sf.* Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:

Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

2 see below 210*

Evidence Room(s)State Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division:

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)

X

X

X

X

Water Supply: (Hot & Cold) X

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

X

X

20

Indirect/Direct Recessed (LED) X

X

X

X

X

OGS Proj. No.: 10/06/17

Chemical Fire Suppression

Eggshell or Satin Paint;

Floor Drain

Wet Type Sprinkler

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

19038

Decorative Susp. LED

Decorative wall sconce LED

Independently switched

13 Dated:

X

Wall mounted monitors

A/V-Satellite Connection

Other

Utilization of Space

White Bd w/Presentation Rail:

Single 36"

Casework: X

Floor load:

Sound Attenuation:

Partial Height:

Projector Screen-Electric:

Ceiling Mount Projector:

X

Other:

Proximity Reader:

Projector Screen-Manual:

Security:

Other:

Rated:

Intercom

Lighting

Computer

Amperes

Cable TV

Passage Lockset:

Manual Pushpad:

Electric Pushpad:

Recessed Round downlight LED

# of Tel/Data receptacle boxes

Communications

Chair Rail:

Other:

Special Needs/Equipment Requirements: (Use 2nd sheet as needed)

Ceiling High Solid:

Other (specify size & no.)

Wall Types: Specify Type

Keyed Lockset:

Double 36"

With Glass:

Solid Wood:

Slab To Slab:

X

Side Light:

Or As Required By Code Door Hardware:

Convenience

Hollow Metal:

Rated:

Acoustical Lay-in Tile

Ceiling Hgt: or specify other as appropriate

Doors Specify Type

*Electric Power Receptacles:

Duplex QuadType

Voltage

Dedicated

Ceiling:

Direct Exhaust

(Indicate material, color to be selected at a later date)

Away from data closetsAway from:

Other:

Air/Steam/Oxygen/VacuumTrim:

Pre-Action Dry Type Sprinkler

Dry Type SprinklerResilient FlooringFloor:

Base: Vinyl-Rubber

Semi-gloss Paint;

Finishes:

Walls:

Ventilation

Heating

Utilities (place X as appropriate)Function of Space:

Relationship to Other Spaces:

Next to:

Winter Cooling (24 hrs x 7 days)

Shared Kitchen space for all staff

(Provide a description & number of occupants)

To be determined during design

(Describe as appropriate) Humidification

Special Features & Remarks: (Use 2nd sheet as needed)

Provide solid surface countertop(min. length 8') for food and coffee prep. Countertop with full height backsplash,installed with

wall and base cabinets. Provide double bowl stainless steel sink, with goose neck faucet. Provide commercial grade microwave

oven. Provide commercial grade reach-in refrigerator, stainless steel exterior and interior, solid double door, 49 cf min. ETL

Sanitation listed and NSF compliant. Design space to accomodate tables and seating. Provide paper towel and liquid soap

dispenser. Room must meet ADA(accessible sink). Vent fan required. Non-motion sensor sink fixture, water line and electric for

landlord provided water filter stations.

Office Of General Services

State Of New York

300300

Total Net Sq. Ft.No. of Spaces @ Net Sq. Ft.

SharedSection/Unit:

Real Estate Planning & Development

Lunch Room

Space Program Room Data Sheet (Insert Room Name above)

Division:

Bureau:

Project Name:

NYS Dept. of Taxation and Finance

Rochester1

Near:

Temperature Control

Cooling

X

X

X

Water Supply: (Hot & Cold)

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

X

X

X

20

Indirect/Direct Recessed (LED) X

X

X

OGS Proj. No.:

Mail RoomState Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division:

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)

Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:

Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

1 225 225

Near: Freight Elevator Direct Exhaust

Away from:

Other: Floor Drain

Relationship to Other Spaces: (Describe as appropriate) Humidification

Next to: Temperature Control

Base: Vinyl-Rubber Pre-Action Dry Type Sprinkler

Walls: Eggshell or Satin Paint; Chemical Fire Suppression

Finishes: (Indicate material, color to be selected at a later date) Wet Type Sprinkler

Floor: VCT Dry Type Sprinkler

Ceiling Hgt: or specify other as appropriate ( ) Connect to UPS

Doors Specify Type *Electric Power Receptacles:

Trim: Semi-gloss Paint; Air/Steam/Oxygen/Vacuum

Ceiling: Acoustical Lay-in Tile Connect to Emergency Generator

Quad

Solid Wood: Voltage

Single 36" Double 36" Other (specify size & no.) Type Duplex

Hollow Metal: X Convenience

Rated: Dedicated

With Glass: Computer

Side Light: Amperes

Wall Types: Or As Required By Code Door Hardware: Specify Type Lighting

Ceiling High Solid: Passage Lockset:

Slab To Slab: X Keyed Lockset: X* Low profile susp. Ind./Direct LED

Partial Height: Manual Pushpad: Narrow 4', 8' Recessed Slot LED

Sound Attenuation: X Electric Pushpad: Recessed Round downlight LED

Rated: Proximity Reader: X Decorative Susp. LED

Floor load: Projector Screen-Manual: Dimmer switch(s) Number

Security: Projector Screen-Electric: Communications

Other: Other: Decorative wall sconce LED

Special Needs/Equipment Requirements: (Use 2nd sheet as needed) Independently switched

Other: Wall Mounted Tack Strip: Cable TV

A/V-Satellite Connection

Casework: Ceiling Mount Projector: # of Tel/Data receptacle boxes

Chair Rail: White Bd w/Presentation Rail: Intercom

19038 14 Dated: 10/06/17

Special Features & Remarks: (Use 2nd sheet as needed) Sound System/Speakers*Keyed separately(for override) - non shared lock. Minimum of 3 data lines. Sound Masking

Fiber Optics

Utilization of Space

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

X

X

X

X

Water Supply: (Hot & Cold) X

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

X

20

Indirect/Direct Recessed (LED) X

X

OGS Proj. No.: 19038 15 Dated: 10/06/17

Provide stainless steel partitions. Mens room to have stalls and urinals.

Both rooms to have one stall that is ADA compliant. Sinks are to be ADA

compliant. Outlets are to be GFI protected as per NEC.

Sound System/Speakers

Sound Masking

Fiber Optics

Utilization of Space

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

Other: Wall Mounted Tack Strip: Cable TV

Special Features & Remarks: (Use 2nd sheet as needed) A/V-Satellite Connection

Casework: Ceiling Mount Projector: # of Tel/Data receptacle boxes

Chair Rail: White Bd w/Presentation Rail: Intercom

Floor load: Projector Screen-Manual: Dimmer switch(s) Number

Security: Projector Screen-Electric: Communications

Other: Privacy Lockset: Decorative wall sconce LED

Special Needs/Equipment Requirements: (Use 2nd sheet as needed) Independently switched

Sound Attenuation: Electric Pushpad: Recessed Round downlight LED

Rated: Proximity Reader: Decorative Susp. LED

Wall Types: Or As Required By Code Door Hardware: Specify Type Lighting

Low profile susp. Ind./Direct LED

Partial Height: Manual Pushpad: Narrow 4', 8' Recessed Slot LED

Ceiling High Solid: Passage Lockset: X

Slab To Slab: x Keyed Lockset:

Rated: Dedicated

With Glass: Computer

Solid Wood: Voltage

Hollow Metal: X Convenience

Ceiling Hgt: or specify other as appropriate Connect to UPS

Doors Specify Type *Electric Power Receptacles:

Single 36" Double 36" Other (specify size & no.) Type Duplex Quad

Trim: Air/Steam/Oxygen/Vacuum

Ceiling: Connect to Emergency Generator

Base: Pre-Action Dry Type Sprinkler

Walls: Eggshell or Satin Paint; Chemical Fire Suppression

Vinyl-Rubber

Semi-gloss Paint;

Acoustical Lay-in Tile

Finishes: (Indicate material, color to be selected at a later date) Wet Type Sprinkler

Floor: VCT Dry Type Sprinkler

Away from:

Other: Floor Drain

Section/Unit:

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

2 225 450

Near: Direct Exhaust

Relationship to Other Spaces: (Describe as appropriate) Humidification

Next to: To be determined during design Temperature Control

Side Light: Amperes

Employee RestroomState Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division:

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)

Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:

X

X

X

Water Supply: (Hot & Cold)

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

X

20

Indirect/Direct Recessed (LED) X

X

OGS Proj. No.:

Independently switched

Dimmer switch(s) Number

Recessed Round downlight LED

Decorative Susp. LED

Projector Screen-Electric:

Ceiling Mount Projector:

Chair Rail:

Casework:

Security:

Partial Height:

Sound Attenuation:

Manual Pushpad:

Electric Pushpad:

Rated:

Special Needs/Equipment Requirements: (Use 2nd sheet as needed)

Other:

Floor load:

White Bd w/Presentation Rail:

Dated:

Cable TV

10/06/1719038 16

24 hrs./day x 7 days/weekWall Mounted Monitors:

7:00 AM - 7:00 PM

Sound Masking

Wall Mounted Tack Strip:

X Fiber Optics

Utilization of Space

Counters shall meet ADA standards.

Special Features & Remarks: (Use 2nd sheet as needed)

Wall Types: Or As Required By Code

xWith Glass:

Specify TypeDoor Hardware:

Side Light:

Rated:

Hollow Metal:

Amperes

Floor Drain

Convenience

x

Air/Steam/Oxygen/VacuumSemi-gloss Paint;

Acoustical Lay-in Tile

Ceiling Hgt: or specify other as appropriate

*Electric Power Receptacles:

Dedicated

Other (specify size & no.)

Trim:

Solid Wood:

Quad

Point of access for taxpayer transactions. Separated from employee area

by transaction counters with pass through windows(with blinds).

Adjacent entrance shall be secured with access control compatible with

HID iClass swipe card.

Duplex

Computer

Single 36"

Base:

No. of Spaces @ Net Sq. Ft.

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

Chemical Fire Suppression

(Describe as appropriate)

(Provide a description & number of occupants)

1

(Indicate material, color to be selected at a later date)

Pre-Action Dry Type Sprinkler

Away from:

Wet Type Sprinkler

Eggshell or Satin Paint;

Floor: VCT

Relationship to Other Spaces:

Type

Voltage

Double 36"

Vinyl-Rubber

Doors Specify Type

Proximity Reader:

Projector Screen-Manual:

Direct Exhaust

To be determined during design

Ceiling High Solid: Passage Lockset:

X

XKeyed Lockset:Slab To Slab:

# of Tel/Data receptacle boxes

Communications

Intercom

Other:

Dry Type Sprinkler

Lighting

Finishes:

Walls:

Ceiling:

Queue Area

Space Program Room Data Sheet (Insert Room Name above)

Humidification

Near: Elevators/Public Entrance

Function of Space:

State Of New York

Utilities (place X as appropriate)

225

Total Net Sq. Ft.

Office Of General Services

Division:

Temperature Control

225

Heating

Next to:

NYS Dept. of Taxation and Finance

Rochester

Real Estate Planning & Development

Project Name:

Bureau:

Section/Unit:

X

X

X

Water Supply: (Hot & Cold)

(1-coat primer, 2-coats finish)

(1-coat primer, 2-coats finish)

9'-0";

120v 120v

2

1

20

Indirect/Direct Recessed (LED) X

1

X

OGS Proj. No.: 19038 17 Dated: 10/06/17

Special Features & Remarks: (Use 2nd sheet as needed) Sound System/Speakers(3) of the offices must be in close proximity to the evidence room(s). Sound Masking

Fiber Optics

Utilization of Space

7:00 AM - 7:00 PM

24 hrs./day x 7 days/week

Other

Other: Wall Mounted Tack Strip: Cable TV

A/V-Satellite Connection

Casework: Ceiling Mount Projector: # of Tel/Data receptacle boxes

Chair Rail: White Bd w/Presentation Rail: Intercom

Floor load: Projector Screen-Manual: Dimmer switch(s) Number

Security: Projector Screen-Electric: *Communications

Other: Other: Decorative wall sconce LED

Special Needs/Equipment Requirements: (Use 2nd sheet as needed) Independently switched

Sound Attenuation: X Electric Pushpad: Recessed Round downlight LED

Rated: Proximity Reader: Decorative Susp. LED

Slab To Slab: Keyed Lockset: X Low profile susp. Ind./Direct LED

Partial Height: Manual Pushpad: Narrow 4', 8' Recessed Slot LED

Wall Types: Or As Required By Code Door Hardware: Specify Type Lighting

Ceiling High Solid: X Passage Lockset:

Glass: Computer

Side Light: x Amperes

Hollow Metal: Convenience

Rated: Dedicated

Quad

Solid Wood: x Voltage

Single 36" Double 36" Other (specify size & no.) Type Duplex

Ceiling Hgt: or specify other as appropriate Connect to UPS

Doors Specify Type *Electric Power Receptacles:

Trim: Semi-gloss Paint; Air/Steam/Oxygen/Vacuum

Ceiling: Acoustical Lay-in Tile Connect to Emergency Generator

Base: Vinyl-Rubber Pre-Action Dry Type Sprinkler

Walls: Eggshell or Satin Paint; Chemical Fire Suppression

Finishes: (Indicate material, color to be selected at a later date) Wet Type Sprinkler

Floor: Carpet Tiles Dry Type Sprinkler

Near: Direct Exhaust

Away from:

Other: Floor Drain

Relationship to Other Spaces: (Describe as appropriate) Humidification

Next to: To be determined during design Temperature Control

Standard stud and gypsum construction. 5@125sf, 1@150sf. Heating

Ventilation

Cooling

Winter Cooling (24 hrs x 7 days)

NYS Dept. of Taxation and Finance

Rochester

Bureau:

Section/Unit: Audit,CID,CED, Office of Counsel

No. of Spaces @ Net Sq. Ft. Total Net Sq. Ft.

6 125-150 775

Private OfficesState Of New York

Office Of General Services

Space Program Room Data Sheet (Insert Room Name above) Real Estate Planning & Development

Project Name: Division:

Function of Space: (Provide a description & number of occupants) Utilities (place X as appropriate)