FLOW METER WITH DWE DISPLAY UNIT DWE-F... - Flow Sensor with DWE Smart Control Unit 4-digit LEDs for flow rate or total flow 2 switching outputs + 1 analog output Optional batch control p PNP / NPN configurable 2/3-wire 4...20mA optional; 1...5V/0...5V optional 2/3 wire 4...20mA optional; 1...5V/0...5V optional All-metal housing Rotatable indicator Rotatable indicator DWE F control unit displays flow rate as well as total flow 2 independent DWE-F control unit displays flow rate as well as total flow, 2 independent switching outputs are compatible with NPN/PNP output. Analog output can be d 2/3 i 4 20 A3 i 0 5V/1 5V Th ii bl programmed as 2/3-wire 4...20mA, 3-wire 0...5V/1...5V. The unit is able to use together with FPW100, FPW200, FGR200, FTB200 and FTS200. All metal housing design; LED display; Dual-key, user-friendly menu design; 330º rotatable indicator. Specifications Power Supply 12...30Vdc pp y Current Consumption 25mA(power supply 24Vdc, no-load) Switching Output Switching Output Output Push-pull (compatible with PNP / NPN) Current 500mA(power supply 24Vdc) Current 500mA(power supply 24Vdc) Current Analog Output Output 2/3 wire 4 20mA programable Output 2/3-wire 4...20mA programable Load RARA≤(Us-3V/0.02A Linearity ±0.5% of F.S. Voltage Analog Output Output 3-wire 0...5V/1...5V programable Load RARA5KLinearity ±0.5% of F.S. Accuracy ±0.5% of F.S. Stability(Drift/year) ±0.3% of F.S. Temperature Ambient -40...85Storage -40...85g Display 8mm height, red 4-digit LED Material Material Display Head Zinc alloy Housing 304 stainless steel Housing 304 stainless steel Protection Class IP67 El ti lC ti M12×1 l Electrical Connection M12×1plug Note: Parameters above are only for DWE-F control unit. FLOW F-61 NEXON www.nexonelectronic.com

Upload: others

Post on 04-Feb-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

  • FLOW METER WITH DWE DISPLAY UNIT

    DWE-F... - Flow Sensor with DWE Smart Control Unit

    4-digit LEDs for flow rate or total flow▼

    2 switching outputs + 1 analog outputOptional batch control

    ▼▼ p

    PNP / NPN configurable2/3-wire 4...20mA optional; 1...5V/0...5V optional

    ▼▼ 2/3 wire 4...20mA optional; 1...5V/0...5V optional

    All-metal housingRotatable indicator

    ▼▼

    ▼ Rotatable indicator▼

    DWE F control unit displays flow rate as well as total flow 2 independentDWE-F control unit displays flow rate as well as total flow, 2 independentswitching outputs are compatible with NPN/PNP output. Analog output can be

    d 2/3 i 4 20 A 3 i 0 5V/1 5V Th i i blprogrammed as 2/3-wire 4...20mA, 3-wire 0...5V/1...5V. The unit is able to usetogether with FPW100, FPW200, FGR200, FTB200 and FTS200.All metal housing design; LED display; Dual-key, user-friendly menu design;330º rotatable indicator.

    Specifications

    Power Supply 12...30Vdcpp yCurrent Consumption 25mA(power supply 24Vdc, no-load) Switching OutputSwitching Output

    Output Push-pull (compatible with PNP / NPN)Current 500mA(power supply 24Vdc)Current 500mA(power supply 24Vdc)

    Current Analog OutputOutput 2/3 wire 4 20mA programableOutput 2/3-wire 4...20mA programableLoad RA(Ω) RA≤(Us-3)V/0.02ALi i ≤ 0 5% f F SLinearity ≤±0.5% of F.S.

    Voltage Analog OutputOutput 3-wire 0...5V/1...5V programableLoad RA(Ω) RA≥5KΩLinearity ≤±0.5% of F.S.

    Accuracy ≤±0.5% of F.S.Stability(Drift/year) ≤±0.3% of F.S.Temperature

    Ambient -40...85℃Storage -40...85℃g

    Display 8mm height, red 4-digit LEDMaterialMaterial

    Display Head Zinc alloyHousing 304 stainless steelHousing 304 stainless steel

    Protection Class IP67El t i l C ti M12×1 lElectrical Connection M12×1plug

    Note: Parameters above are only for DWE-F control unit.

    FLOW

    F-61

    NEXON

    www.nexonelectronic.com

  • FLOW METER WITH DWE DISPLAY UNIT

    Set Panel

    1 - LOGO2 - 8 state lights3 - 4-digit LED display window3 4 digit LED display window4 - Keys

    Press and hold for 2 seconds to entersetting mode/verification+S E setting mode/verification

    Shift down the menu/change values

    S

    S

    Shift up the menu/change values

    S

    E p / gE

    Menu

    Item Description Options

    unit Unit

    OptionsDisplay Item DescriptionDisplay

    Code for

    SP1

    unit Unit

    Set point of 2% ...100%EF

    Code forstarting thetotal flow code: 1001

    Reset point of lower limit 98%

    SP1

    High 4-digit of

    Set po t ooutput 1

    % 00%of F.S. menu

    Reset point ofoutput 1

    lower limit ... 98%of F.S.

    hysteresisNC/NO

    0-9999ACC2 High 4 digit ofthe totalrP1

    Middle 4 digit

    S t i t f 2% 100%

    out1 Output mode hysteresisNC/NOwindow NC/NO ACC1 0-9999

    L 4 di it f

    Middle 4-digitof the total

    SP2 Set point ofoutput 22% ...100%

    of F.S.

    f l l

    ACC0 Low 4-digit ofthe total 0-9999

    rP2 Reset point ofoutput 2lower limit …98%

    of F.S. clr rst / noClear total

    out2 Elimate thepeak 0~8 gradedAPOutput modehysteresisNC/NOwindow NC/NO

    sfun Outputfunction PNP / NPN Save Yes/NoSto

    A t

    Current analogoutput

    0…20mA or4…20mA

    AoutVoltage analog

    output0…5V

    or 1…5V

    Ast Analog outputstart pointlower limit

    …75% of F.S.

    AEd

    p

    Analog outputend point

    25%...100%of F Send point of F.S.

    FLOW

    F-62

    NEXON

    www.nexonelectronic.com

    LPM/GPM/MPHLPM/GPM/MPH

  • FLOW METER WITH DWE DISPLAY UNIT

    FlFunctional Specifications SP

    Flow rate

    Hysteresis Mode Hysteresis ModeThe hysteresis keeps the switching output stable if the flow rate

    rP

    tHysteresis Modey p g pfluctuates around the setpoint. Output switches when rising flowrate reaches set point (SP1); As flow rate falls the output switches

    1 0

    NO

    t

    rate reaches set point (SP1); As flow rate falls, the output switchesback only if the reset point (rP1) is reached.

    1 0 NC

    Fl

    Window Mode The window function allows the monitoring of a defined range If SP

    Flow rate

    Window ModeThe window function allows the monitoring of a defined range. Ifthe flow rate is between set point (SP1) and reset point (rP1), the

    rP

    toutput is activated (NO), otherwise it is deactivated(NC). tNO

    WiringNC

    Signal Plug CableU+

    BlueBrown

    U-13

    12

    Switching output 2BlackSwitching output 1 4

    2 White

    5

    43

    M12 plug

    Switching output 2Analog output

    (Current or Voltage) 5 Gray

    2 White 43

    M12 plug

    PNP output NPN output

    (Current or Voltage)

    PNP output NPN output

    FLOW

    F-63

    NEXON

    www.nexonelectronic.com

    2x PNP +

    analog output

    2x NPN +

    analog output

  • P0SITIVE DISPLACEMENT FLOW METER

    DWE-FGR200 - Positive Displacement Flow Meter with DWE Smart Control UnitDWE FGR200 Positive Displacement Flow Meter with DWE Smart Control Unit

    Dimensions in inches (mm) Fig 1 : G≤3/4''Dimensions in inches (mm) Fig. 1 : G≤3/4

    Dimensions in inches (mm) Fig 2 : G≤1-1/4''Dimensions in inches (mm) Fig. 2 : G≤1 1/4

    Dimension Table inch (mm)

    BAPulse Number/L SizeGFEDC2 172 99 2 831 730 47

    2 173 32 R f t

    G1/4'' 2.17 (55) 2.99 (76)14000

    0 47

    2.83(72)M6

    1.73 (44)

    0.47 (12)

    3 151 73 2.17 (55)

    3.32 (84.4)4200

    Refer toFig.1

    66

    0.47 (12)

    3.15 (80)M6

    1.73 (44) G1/4''

    G3/4''4.69 (119 )M8 2.36 (60)

    0.75 (19)

    4.21 (107)

    4.92 (125)470

    420 SAE1-1/4''-- 3.22 (81.8) 2.59

    (65.8) 5.5

    (139)213(8.4) Refer to Fig.

    7 (178)

    213(8.4)210

    2.59 (65.8) SAE1-1/4''--

    3.22 (81.8)

    2

    * Thread connection of NPT is optional.

    FLOW

    F-69

    NEXON

    www.nexonelectronic.com

    1.47(37.44)

    3 )1.46

    ( 37)

    2.72

    (69

    .03

    B

    C

    GG

    M14X1.5mm.TAPERED

    BOTTOM HOLEF

    BOTTOM HOLEFOR SES

    SENSORS

    2x M4x0.7mm

    A

    D

    Lit

    Gal

    M3

    S2

    S1

    S E

    E M6=10mm DEEPM8=16mm DEEP

    G

    S E

    1.47(37.44)

    2 03)

    1.46( 37)

    2.72

    (69

    .0

    B

    A10X1/2-13

    G

    Lit

    Gal

    M3

    S2

    S1

    S E

    D C

  • P0SITIVE DISPLACEMENT FLOW METER

    Order Code

    DWE-FGR : Positive displacement flow meter with DWE smart control unitDWE FGR : Positive displacement flow meter with DWE smart control unit200 : Series #N : NPT threadN : NPT threadG : BSP thread14 Thread si e 1/4“ (corresponding meas ring range 3L/7 5L)14 : Thread size- 1/4“ (corresponding measuring range 3L/7.5L) 34 : Thread size- 3/4“ (corresponding measuring range 75L) 114 Th d i 1 1/4“ ( di i 225L/450L)114: Thread size- 1-1/4“ (corresponding measuring range 225L/450L)

    DWE-FGR 200 G 3L3L14 A2 T S DDWE FGR 200 G 3L3L14 A2 T S D

    A2 : 2-wire current output (4…20mA)V3 : 3-wire voltage output (0…10V)A3 : 3-wire current output (4…20mA)pT : TotalizerB : Batch controlB : Batch controlS : Stainless steel bodyA : Aluminum bodyA : Aluminum bodyMeasuring range (see technical data for details) :

    3L : 0 02 3 0L/min3L : 0.02—3.0L/min7.5L : 0.05—7.5L/min75L : 0 5 75 0L/min75L : 0.5—75.0L/min225L : 2.0—225.0L/min450L 4 0 450 0L/ i450L : 4.0—450.0L/min

    Flow direction detection :D : Yes(only for M12X1plug connection and pulse output)- : None

    Note 1: Refer to FGR200 for details.Note 2: For flow direction detectable product, please set OUT1 as the flow direction detection output.

    FLOW

    F-70

    NEXON

    www.nexonelectronic.com

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles false /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice