network operating division operating effectiveness transmission lines protection overview
TRANSCRIPT
NETWORK OPERATING DIVISION
Operating Effectiveness
Transmission Lines
Protection Overview
Transmission LinesLH1 Protection Overview
Operating Effectiveness
Training & Development
Hydro One Networks Inc49 Sarjeant Drive
Barrie, OntarioCanada, L4N 4V9
Phone (705) 719-3528
Revised: November 4, 2008
The information in this document is for reference and is to be used as a guide only. The OE Training Section makes no representation or warranty, expressed or implied, that the information contained within is current. The information included is subject to change. It is solely your responsibility to ensure that you are using up-to-date documents, prints and information. Please notify the HONOC Operating Effectiveness Training Section of required updates and/or modifications.
ObjectivesThrough the use of this presentation
participants will learn and understand Transmission Lines Protection.
Emphasis is on:– Functionality– Limitations– Instructions and Procedures– Support Services.
Cont…
Transmission Lines Protection
Transmission Lines Protection Overview.
This presentation will cover:
What transmission line protection is,
Why the need for line protection
Principles of Operation ( Impedance),
Different Operational zones
Various types or schemes
Exceptions and Anomalies
Transfer Trip Channels
Permissive Echo
Transmission Lines Protection Overview.
This presentation will cover:
LH1 configuration
Micro-wave communications
Power Line Carrier communications
Fibre-Optic Digital communications
Various types or schemes
Transmission Lines Protection Overview.
We first must understand what a transmission line is.
A transmission line is a high voltage circuit designed to carry a high amount of power over great distances between points.
In some cases, this could be simply between two points as shown.
Station ‘A’
Station ‘B’
Power flow
Transmission Lines Protection Overview.
In more complicated configurations there could be:
1. Multiple terminal stations
2. Multiple tap stations
3. Combinations of both
Station ‘A’
Station ‘B’
Power flow
Station ‘C’
Station ‘D’
Station ‘E’
Station ‘F’
Transmission Lines Protection Overview.
To begin, we will look at a simple two ended circuit
Station 'Z'Station 'Y'
Station 'Y' is a terminal that has two breakers on
the circuit.
Station 'Z' is also a two breaker terminal for the
circuit.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
The circuit that travels between Station 'Y' and Station 'Z' is a high voltage open air
transmission line and as such is vulnerable to external influences.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
A fault could develop anywhere along the circuit causing fault current to flow between
phases and/or to the ground.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
If there is no way of removing this faulted equipment from service, it will remain faulted
eventually causing danger to the public, damage to equipment or even lead to a system
wide disturbance.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
Protection systems will sense the fault
and clear the circuit removing it from service.
How does the protection system see the fault?
Transmission Lines Protection Overview.
Simple two ended circuit
There are many ways in which faults can be detected.
For transmission circuits the most common method is by using impedance .
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
At each end of the line there are both voltage sensing devices and current sensing devices
Voltage (CVT)
Current (CT)
Transmission Lines Protection Overview.
Simple two ended circuit
These sensing devices monitor line voltage and line current on a continuous basis.
Under normal circumstances, the current will be at expected normal values and the voltage
will be at the system normal.
Transmission Lines Protection Overview.
Simple two ended circuit
The Impedance is derived by placing the voltage and current into a ratio using OHMS
law.
Impedance =Voltage
Current
Voltage = 230,000 volts
Current = 2,000 amps
230,000
2,000= 115 ohms
Current = 50,000 amps
Transmission Lines Protection Overview.
Simple two ended circuit
If a fault occurs then these quantities will be disrupted causing the ratio to greatly change.
Impedance =150000
50000
Voltage = 230,000 volts
Current = 2,000 amps
230,000
2,000= 115 ohms= 3 ohms
Voltage = 150,000 volts
Trip Setting range
Normal Operating range
Transmission Lines Protection Overview.
Simple two ended circuit
The impedance is set to a certain range.
Anything outside of that set range is considered a fault and will trip the circuit.
230000 Volts
2000 Amps
115 ohms
150000 Volts
50000 Amps
3 ohms
Impedance is outside of preset range – Circuit will trip.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
The idea is to set the impedance such that for any fault on the line, the protections will see the changes in voltage, current and the ratio between them, covering 100% of the circuit.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
With this type of impedance detection, it would be very difficult to set the range to exactly
cover 100% of the circuit due to tolerances in measuring equipment.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
The settings could be set:
Too short. Under protected
Too long. Over protected
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
To correct this problem, specific zones of protection have been created.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
Zone 1 – Is set to cover 80-85% of the circuit and is instant.
Zone 1 – 80-85%
Zone 2 – Is set to cover 125-150% of the circuit but is generally a timed protection.
Zone 2 – 125-150%
Transmission Lines Protection Overview.
Zone 1 Protection
Station 'Z'Station 'Y'
Zone 1 – Is set to cover 80-85% of the circuit and is instant.
Zone 1 protection is generally known as Direct Direct UnderreachUnderreach
Zone 1 – 80-85%
Transmission Lines Protection Overview.
Zone 1 Protection
Station 'Z'Station 'Y'
This area Instantaneous
protection from Station 'Y' only.
This area Instantaneous
protection from Station 'Z' only.
This area overlaps and is
Instantaneous protection from
both Station 'Y' and Station 'Z'.
There is a limit to the protection when using Direct Direct
UnderreachUnderreach
Transmission Lines Protection Overview.
Zone 1 Protection
Station 'Z'Station 'Y'
If a fault occurs here, ‘Y’ Zone 1 will see it and
send a trip signal called…
To overcome this limit communication is used between
ends.
Transfer Transfer TripTrip
Transmission Lines Protection Overview.
Transfer TripTransfer Trip
Station 'Z'Station 'Y'
At Station 'Y' both Zone 1 and Zone 2 will see the fault.
Station 'Y' Zone 1 will trip instantly and send Transfer TripTransfer Trip
Station ‘Z' will receive Transfer TripTransfer Trip and trip its terminal breakers instantly.
1
2
T/T Rx
Transfer TripTransfer Trip
Communication is accomplished by a
variety of media but will not be discussed right
now.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
How do we protect this area from Station 'Z'?
How do we protect this area from Station 'Y'?
There is another limit to the protection when using
Direct UnderreachDirect Underreach
The answer is to use another zone designed to reach all the
way across the circuit.
Transmission Lines Protection Overview.
Simple two ended circuit
Station 'Z'Station 'Y'
The protection will overlook into adjacent zones and could cause erroneous trips for faults outside of the zone.
To prevent this Zone 2 protection is generally made to be timed.
Zone 2 is set to ‘see’ 125-150%125-150% of the circuit.
Zone 2Zone 2
Transmission Lines Protection Overview.
We will look at Zone 2 independent of Zone 1
Station 'Z'Station 'Y'
Although Zone 2Zone 2 is normally timed, there is a need for the Zone 2Zone 2 protection to be instantaneous in
order to satisfy rapid removal of the transmission circuit in a faulted condition.
Zone 2 is set to ‘see’ 125-150%125-150% of the circuit.
Zone 2Zone 2
Transmission Lines Protection Overview.
Zone 2 Protection
Station 'Z'Station 'Y'
The rapid removal will be by using Zone 2 in a:
Permissive OverreachPermissive Overreach scheme oror
Directional ComparisonDirectional Comparison scheme
Transmission Lines Protection Overview.
Permissive OverreachPermissive Overreach
Station 'Z'Station 'Y'
In Permissive OverreachPermissive Overreach each Station has a timedtimed Zone 2.
If a fault occurs outside of Station 'Z' Zone 1 as shown above, only the Station 'Z' Zone 2 will see it.
When the Zone 2 ‘sees’ the fault it starts a timer (400ms).
2
Zone 1 Limit
Transmission Lines Protection Overview.
Permissive OverreachPermissive Overreach
Station 'Z'Station 'Y'
At Station 'Y' both Zone 1 and Zone 2 will see the fault.
Station 'Y' Zone 1 will trip instantly
Station 'Y' Zone 2 will see the fault and will send PermissionPermission to Station 'Z' Zone 2 to trip instantly instead of timed.
1
2
2
Permissive SignalPermissive Signal
Zone 1 Limit
Transmission Lines Protection Overview.
Directional ComparisonDirectional Comparison
Station ‘Z’Station ‘Y’
In Directional ComparisonDirectional Comparison each Station has InstantInstant Zone 2 coverage.
If a fault occurs outside of Station ‘Z’ Zone 1 as shown above, only the Station ‘Z’ Zone 2 will see it.
When the Zone 2 ‘sees’ the fault it will trip instantly.
2
Zone 1 Limit
Transmission Lines Protection Overview.
Directional ComparisonDirectional Comparison
Station ‘Z’Station ‘Y’
This Instantaneous tripping, however, could pose a problem if the fault is outside of the protected circuit, but still inside the Zone 2 reach.
The fault will be seen by the Zone 2 protection and will cause the circuit to erroneously trip for this out of zone fault.
2
Zone 1 Limit
Transmission Lines Protection Overview.
Directional ComparisonDirectional Comparison
Station ‘Z’Station ‘Y’
For example: The fault is located on the adjacent circuit.
2
Station ‘Z’ Zone 2 ‘sees’ the fault and will trip instantly
Only the circuits breakers of the faultedfaulted circuit should trip
Zone 1 Limit
Transmission Lines Protection Overview.
Directional ComparisonDirectional Comparison
Station ‘Z’Station ‘Y’
To correct this a 3rd Zone is employed
2
This is the Directional ComparisonDirectional Comparison element which employs a relay known as an OM3 OM3 relay and is set to look backwardsIf a fault occurs out of zone it trips its local breakers.
The Zone 2 at Station ‘Z’ will also see the fault and try to trip its breakers instantly.
Block SignalBlock Signal
OM3
The OM3 will sense the fault as well and send a block signal to the opposite Zone 2 preventing it from
tripping instantly.
X
In some cases Zone 2 may be different in each Group, Group A Zone 2 could have Permissive Overreach where Group B could have Directional Comparison
Each Station has a Zone 1 Direct UnderreachDirect Underreach covering 80-85% of the circuit.
Each Station Zone 1 will send Transfer Trip Transfer Trip to opposite end station tripping its breakers.
Each Station has Zone 2 covering 125-150% of the circuit.
Zone 2 can be Permissive OverreachPermissive Overreach or Directional ComparisonDirectional Comparison
Permissive Overreach Permissive Overreach is Timed unless it receives a Permissive SignalPermissive Signal from the opposite end Zone 2
protection where it will then trip instantly.
Directional ComparisonDirectional Comparison is Instant unless it receives a Block Signal from the opposite end Zone 3 OM3 element
where it will then trip timed.
The protections will all have a Zone 1 Direct Under reach and Zone 2 will have either Permissive Overreach
or Directional Comparison but not both.
These protections are referred to as GroupsGroups. Each terminal will have duplication of each group and will be
known as Group AGroup A and Group BGroup B.Each Group AGroup A and Group B Group B are generally clones of each other with a Zone 1 Direct Underreach and a similar Zone 2.
Station ‘Y’ Zone 2
Station ‘Z’ Zone 2
Transmission Lines Protection Overview.
Protection review
Station 'Z'Station 'Y'
1
2
2
Block SignalBlock Signal
1OM3OM3
Transfer TripTransfer Trip
Permissive SignalPermissive Signal
Station ‘Y’ Zone 1
Station ‘Y’ Zone 3 OM3
Station ‘Z’ Zone 1
Block SignalBlock Signal
Transfer TripTransfer Trip
Permissive SignalPermissive Signal
Station ‘Z’ Zone 3 OM3
Station ‘Y’ Zone 2
Station ‘Z’ Zone 2
Transmission Lines Protection Overview.
Protection review
Station 'Z'Station 'Y'
1
2
2
Block SignalBlock Signal
1OM3OM3
Transfer TripTransfer Trip
Permissive SignalPermissive Signal
Station ‘Y’ Zone 1
Station ‘Y’ Zone 3 OM3
Station ‘Z’ Zone 1
Block SignalBlock Signal
Transfer TripTransfer Trip
Permissive SignalPermissive Signal
Station ‘Z’ Zone 3 OM3
This is what represents a basic line protection. Two Zones with a dual redundancy built in.
Station ‘Y’ Zone 2
Station ‘Z’ Zone 2
Transmission Lines Protection Overview.
Station 'Z'Station 'Y'
1
2
2
Block SignalBlock Signal
1OM3OM3
Transfer TripTransfer Trip
Permissive SignalPermissive Signal
Station ‘Y’ Zone 1
Station ‘Y’ Zone 3 OM3
Block SignalBlock Signal
Transfer TripTransfer Trip
Permissive SignalPermissive Signal
Station ‘Z’ Zone 3 OM3
The line switch at Station ‘Y’ is OPEN
As a result, Station ‘Y’ Protections no longer see the circuit.
Station ‘Z’ Zone 1
Lets look at when a terminal is Out of Service with its line disconnect open
Station ‘Z’ Zone 2
Transmission Lines Protection Overview.Lets look at when a terminal is
Out of Service
Station 'Z'Station 'Y'
2
1
Station ‘Z’ Zone 1
If a fault occurs within the Zone 1, both Zone 1 and Zone 2 protections will see the fault and the Zone 1 will high speed trip the terminal at Station ‘Z’.
Transfer TripTransfer Trip
Transfer Trip is Blocked to opposite terminal
breakers
Station ‘Z’ Zone 2
Transmission Lines Protection Overview.Lets look at when a terminal is
Out of Service
Station 'Z'Station 'Y'
2
1
Station ‘Z’ Zone 1
If a fault occurs outside of Zone 1, only Zone 2 protections will see the fault and will timed trip the terminal at Station ‘Z’.
To correct this, the Permissive Signal is returned or Echoed Echoed back to the sending terminal and it will then trip instantly. This signal is keyed on at all times.
Permissive SignalPermissive Signal
Permissive Echo SignalPermissive Echo Signal
‘B’ Pallets
Transmission Lines Protection Overview.
Communication
Station 'Z'Station 'Y'
2
1
In order for the Protection signals to travel from one station to another, a communications medium is required.
There are several types used today.
1
2
Powerline Carrier- Powerline Carrier- Wave TrapWave Trap
MicroWaveMicroWaveFibre-Optic Digital Fibre-Optic Digital
Tele-protectionTele-protection
Transmission Lines Protection Overview.
Micro-Wave CommunicationStation 'Z'Station 'Y'
A large microwave transmission tower is
built at each end of the circuit
Microwave signals are transmitted between
points.
These are known as Guard Tones
The Guard Tones typically consist of 4 4 Transfer Trip TonesTransfer Trip Tones and 2 Permissive / Blocking 2 Permissive / Blocking
TonesTones
We will call them…
Transmission Lines Protection Overview.
Micro-Wave CommunicationStation 'Z'Station 'Y'
Transfer Trip Channel #1Transfer Trip Channel #1
Transfer Trip Channel #2Transfer Trip Channel #2
Transfer Trip Channel #3Transfer Trip Channel #3
Transfer Trip Channel #4Transfer Trip Channel #4
Permissive / Block Channel #1Permissive / Block Channel #1
Permissive / Block Channel #2Permissive / Block Channel #2
Transmission Lines Protection Overview.Micro-Wave Communication
Station 'Z'Station 'Y' The question arises.
Why so many Tones?Why so many Tones?
Here’s why….
Microwave is:- influenced by external forces
- a line of sight communication
Transmission Lines Protection Overview.Micro-Wave Communication
Station 'Z'Station 'Y'
Microwave is a radio signal and uses air to travel through.
When the air changes properties, it distorts the path of the microwave.
This is known as-
MicrowaveMicrowave FadingFading
Transmission Lines Protection Overview.Micro-Wave Communication
Station 'Z'Station 'Y' Distortions Distortions in the air can be caused by changes in:
-Temperature
- Pressure
-Humidity
-Precipitation
-Fog
and many other atmospheric factors.
Transmission Lines Protection Overview.
Micro-Wave Communication Station 'Z'
Station 'Y'
Microwave is also a “Line of SightLine of Sight” communications
Any type of physical obstruction will affect the path of the signal
BuildingsTrees
Transmission Lines Protection Overview.
Micro-Wave Communication Station 'Z'
Station 'Y'
To correct for these limits.
Pathways are carefully determined to minimize external influences.
Transmission Lines Protection Overview.
Micro-Wave Communication Station 'ZStation 'Y'
Bodies of Water Hills and Mountains
Tall Buildings
Pathways will go around avoiding large obstaclesAnother method to secure
transmission of the signal is sending along redundant
pathways
Main PathwayMain Pathway
Alternate PathwayAlternate Pathway
Transmission Lines Protection Overview.
Micro-Wave Communication Station 'ZStation 'Y'
Bodies of Water Hills and Mountains
Tall Buildings
Sometimes signals will be split.
2 T/T ch’s, 1 Perm on Main path
2 T/T ch’s, 1 Perm on Alt Path
Main PathwayMain Pathway
Alternate PathwayAlternate Pathway
T/T ch#1 T/T ch#2 Perm#1
T/T ch#3 T/T ch#4 Perm#2
Transmission Lines Protection Overview.
Transmission Circuit
Power Line Carrier - PLCPower Line Carrier - PLC
Power Line Carrier employs a high frequency signal injected into the transmission circuit.
At each end of the circuit, wave traps are employed which are tuned to trap the frequency and shunt it away to communications equipment.
Wave TrapWave Trap Wave TrapWave Trap
CVT shunts signal to communications
equipment
60hz passes, high hz does not
Transmission Lines Protection Overview.
Digital Tele-protection – Fibre OpticDigital Tele-protection – Fibre OpticDigital Tele-protection employs light signal injected into fibre optic cable.
The fibre could be buried or even in the sky wire of a transmission circuit.
Fibre Fibre OpticOptic Fibre Fibre
OpticOptic
SkywireSSkywireShield hield WiresWires
Digital Tele-protection had once utilized microwave tone equipment for the LH1 configuration but for the most part has since been replaced with all digital equipment.
This is a true Digital Tele-Protection scheme and is beyond the scope of this presentation.
Transmission Lines Protection Overview.
Micro-Wave CommunicationStation 'Z'Station 'Y'
T1 G1 T2 G2 T3 G3
T4 G4 T5 G5 T6 G6
R1 G1 R2 G2 R3 G3
R4 G4 R5 G5 R6 G6
TRIPTRIP
Frequency ShiftFrequency Shift
FaultFault
Relay/Microwave buildings
Watch carefully how this works
Trip #1
Guard #1
CH #1
Fail
Trip #2
Guard #2
CH #2
Fail
Trip #3
Guard #3
CH #3
Fail
Trip #4
Guard #4
CH #4
Fail
CH #2
CH #1
CH #3
CH #4
‘A’ Battery DC +
‘B’ Battery DC +
‘A’ Protection
‘B’ Protection
Guard #1
Fail
Permissive ‘A’ Logic
Fail
Permissive ‘B’ Logic
Perm #2
Guard #2
Transfer Trip ChannelsTransfer Trip Channels
Perm #1
Permissive ChannelsPermissive Channels
Disconnect Disconnect SwitchSwitch
CloseClose
Open
Disconnect Switch - ‘A’ Pallet Supervision
Trip CircuitTrip Circuit
Transmission Lines Protection Overview.
LH1 LH1 ConfigurationConfiguration
Click TheseClick These
To conclude you learned:• What a circuit is• What circuit protections are and why they are needed• The different zones of protection and how they work• Transfer Trip, Permissive & Block signals• Microwave, Power Line Carriers and Fibre-Optic Digital Tele-
Protections communications• LH1 configuration for protection tripping
Transmission Lines Protection Overview.
The End
Transmission Lines Protection Overview.