The Netbiter® MB100 Gateway connects serial Modbus RTU or Modbus ASCII devices with Ethernet and mobile networks. The gateway acts as a transparent bridge in both directions, translating Modbus TCP messages to serial Modbus RTU or Modbus ASCII messages. One common application is to connect one or more Modbus RTU serial devices to a supervisory SCADA or PLC that supports Modbus TCP Ethernet. The communication is done over the existing Ethernet LAN lines in the building, factory LAN or even over the Internet.By interfacing the RTU-TCP gateway with applications such as drives, power meters, temperature regulators, weigh scales, etc., it is possible to increase the distance between controller and application as well as making it easier to install a larger number of devices.
• Connects serial Modbus devices to Modbus TCP
• One gateway can link up to 31 Modbus devices
• Both RS-232 and RS-485 supported
• Connects with Ethernet or mobile networks
• 10/100 Mbit/s Ethernet
• Webbasedconfiguration
• DINrail/wallmounting
• LED Indicators for network, status etc
• Indicators for network and serial status
Netbiter® MB100
Ports and I/O’sThe Netbiter® MB100 gateway connects with serial Modbus devices over RS-232 or RS-485. Using RS-485 makes it possible to connect multiple devices through on RTU-TCP gateway, allowing up to 31 devices to be linked to one single gateway. The gateway can also handle up to 10 Modbus TCP connections simultaneously. There are also 2 digital inputs onboard that can be mapped to Modbus TCP registers and then accessible from a SCADA, PLC or similar.
AreliablesolutionThe Netbiter® MB100 Gateway is an off-the-shelf solution that is today installed in high volume in 40+ countries. It possible to integrate devices designed for serial Modbus communication with the control level networks without expensive engineering work and re-designs. This saves time and cost throughout the organization.
Orderinformation
Plastic housingP/N: MB100
Metal housingP/N: MB100-M
Userbenefits
This solution makes system integration easy and cost ef-ficient.
Serial field level devices can easily be integrated to super-visory SCADA PC tools and PLC’s using standard Ethernet cabling.
TechnicalSpecifications
IntellicomInnovationABLinjegatan 3DSE-302 50 HalmstadSweden
Phone: +46 35 18 21 70Fax: +46 35 18 21 99 Email: [email protected]: support.intellicom.se www.intellicom.se
Ethernet 10/100 Mbit/sSerial port #1 (DSUB) RS232
Serial port #2 (Terminal) RS232/RS485Serial Network Baud rate (Modbus RTU/ASCII) Up to 115,2 kbit/sI/O 2 digital inputs
PlasticHousing MetalHousingType of housing Norm, 4 modules, IP20 Metal, IP20DIN rail / Wall mounting YES / NO YES / YESMechanical Dimensions 90mm x 70mm x 58mm 92mm x 115mm x 25mmOperating Temperature -40 to +65 deg °C -40 to +75 deg °CPower Supply 9-24V AC/DC 9-24V DCPower Consumption 2W 2W