Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com © 2015 Eaton All Rights Reserved Printed in USA June 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners. Electrical Sales and Distributor Training Product Comparison What’s the Difference? Medium Voltage Metal Enclosed Switchgear Medium Voltage Metal Clad Switchgear What You Need to Know and Look for in Specifications ANSI C37.20.2 for circuit breakers ANSI C37.20.3 for switchgear CSA C22.2 #31 ANSI C37.20.2 for circuit breakers CSA C22.2 #31 - M89 EEMAC G8 - 3.2 Features Front and rear access Shutters not required Compartmentalization not required Adjacent compartments can be open Bus and primaries can be uninsulated Fixed mounted switching and interrupting devices are allowed Must have front and rear access Shutters are required All live parts are compartmentalized Compartments isolated from each other Bus and primaries must be insulated Switching and interrupting devices are always drawout mounted Over Current Protection Device Types VCP-W or VCP-T vacuum circuit breaker Switches with or without fuses VCP-W vacuum circuit breaker 1200 amps through 4000 amps Over Current Protection Device Features Drawout circuit breakers with protective relays for overcurrent protection Maximum interrupting around 40 kA but varies by voltage and product class Switches have low duty cycle; varies by voltage and product class 100-750 no-load, 5-50 load-switching operations 3-4 fault close operations Fixed mounted fuses Suited for less demanding medium voltage applications Drawout circuit breakers with protective relays for overcurrent protection Up to 63 kA interrupting but varies by voltage class Breakers have high duty cycle; varies by voltage 5000-10,000 no-load or load switching operations 50-100 fault interruptions Especially suited for demanding medium voltage power distribution applications The Bottom Line Metal clad is metal enclosed but metal enclosed is not metal clad

Upload: boussaid-souheil

Post on 07-Jul-2016

219 views

Category:

Documents


1 download

TRANSCRIPT

Eaton1000 Eaton BoulevardCleveland, OH 44122 United StatesEaton.com

© 2015 EatonAll Rights ReservedPrinted in USAJune 2015

Eaton is a registered trademark.

All other trademarks are propertyof their respective owners.

Electrical Sales and Distributor Training

Product Comparison

What’s the Difference?

Medium Voltage Metal Enclosed Switchgear Medium Voltage Metal Clad Switchgear

What You Need to Know and Look for in Specifications

• ANSI C37.20.2 for circuit breakers

• ANSI C37.20.3 for switchgear

• CSA C22.2 #31

• ANSI C37.20.2 for circuit breakers

• CSA C22.2 #31 - M89

• EEMAC G8 - 3.2

Features

• Front and rear access

• Shutters not required

• Compartmentalization not required

• Adjacent compartments can be open

• Bus and primaries can be uninsulated

• Fixed mounted switching and interrupting devices are allowed

• Must have front and rear access

• Shutters are required

• All live parts are compartmentalized

• Compartments isolated from each other

• Bus and primaries must be insulated

• Switching and interrupting devices are always drawout mounted

Over Current Protection Device Types

• VCP-W or VCP-T vacuum circuit breaker

• Switches with or without fuses

• VCP-W vacuum circuit breaker

• 1200 amps through 4000 amps

Over Current Protection Device Features

• Drawout circuit breakers with protective relays for overcurrent protection

• Maximum interrupting around 40 kA but varies by voltage and product class

• Switches have low duty cycle; varies by voltage and product class

• 100-750 no-load, 5-50 load-switching operations

• 3-4 fault close operations

• Fixed mounted fuses

• Suited for less demanding medium voltage applications

• Drawout circuit breakers with protective relays for overcurrent protection

• Up to 63 kA interrupting but varies by voltage class

• Breakers have high duty cycle; varies by voltage

• 5000-10,000 no-load or load switching operations

• 50-100 fault interruptions

• Especially suited for demanding medium voltage powerdistribution applications

The Bottom Line

Metal clad is metal enclosed but metal enclosed is not metal clad