multimess D9-PQ class A network analyzer for low and medium voltage networks

One System. Best Solutions.

2

Other measuring devices call him „the Boss“

3

SI

GN

ALS

AN

D E

NER

GY

DAT

Amultimess D9-PQ

The novel multimess D9-PQ power quality analyzer and

fault recorder for low and medium voltage networks

is the main component of a system that can handle

all measuring tasks in electrical networks . The multi-

mess D9-PQ can be used as a power quality interface

in accordance withnetwork quality standards as well as

measuring device for all physically defined measured

values in alternating current networks.

Power quality network analyzer for low and medium voltage networks

multimess D9-PQ

Signals and Energy Data | multimess D9-PQ Power Quality Network Analyzer Class A

4

multimess D9-PQ

The novel multimess D9-PQ power quality analyzer and fault recorder for low and medium voltage networks is the main component of a system that can handle all measuring tasks in electrical networks .

The multimess D9-PQ can be used as a power quality interface with network quality standard as well as measuring device for all physically de-fined measured values in alternating current networks. Apart from standard evaluations, the

IEC61000-4-30 parameters Class A

Network frequency fulfilled

Accuracy of voltage measurement fulfilled

Voltage fluctuations fulfilled

Dips or rises in voltage fulfilled

Voltage interruptions fulfilled

Voltage asymmetry fulfilled

Voltage harmonics fulfilled

Voltage interharmonics fulfilled

Ripple-control voltage fulfilled

Upward or downward deviations fulfilled

Measurement accumulation intervals fulfilled

Synchronization fulfilled

Event tagging fulfilled

Number of interfering signal influences fulfilled

The multimess D9-PQ fulfills the requirements laid down in IEC 61000-4-30 (2008) for class A measuring devices to 100%.

multimess D9-PQ also features a high-speed fault recorder with a recording rate of 40.96kHz/10.24kHz and a 10ms RMS recorder. Thus, it allows for a detailed assessment of network interferences.

The unit is especially suitable for mon-itoring, recording and evaluating ref-erence qualities or quality agreements between the energy supplier and the customer and make them available for evaluation and storage.

Advanced voltage quality measuring devices work in accordance with the IEC 61000-4-30 (2008) standard. This standard defines the measuring meth-ods to provide users with a good basis for comparison.Devices from different manufacturers that comply with this standard have to deliver identical measuring results.

The standard distinguishes two measuring device classes:

class A measuring devices are mostly used for contract-relevant measurements in customer-sup-plier relationships.

class S measuring devices can be used to determine statistic quality values.

Application of the multimess D9-PQ

5

multimess D9-PQ

Design of the multimess D9-PQ

The multimess D9-PQ was designed for measurements in public networks and measurements in industrial envi-ronments with a measuring voltage of up to 690V (L-L).

No moving parts (fans, hard drive)

CAT IV

The user can expand the storage space to up to 32 GB with an SD card (this allows for many years of recording without having to con-nect the device to a database)

Optional: “IEC61000-4-7 - 2 kHz to 9 kHz” (B1)

Voltage and current frequency measurement of 2 kHz to 9 kHz in accordance with IEC 61000-4-7.

The multimess D9-PQ can be mounted on the wall (optional mounting rail), integrated into the switchboard (optional mounting frame) or in a mounting rail casing

Signals and Energy Data | multimess D9-PQ Power Quality Network Analyzer Class A

Power quality network analyzer for low and medium voltage networks

SI

GN

ALS

AN

D E

NER

GY

DAT

A

6

multimess D9-PQ Technical Data

Technical data

1.7 inch color display Keypad for basic configuration on the device 1 GB internal memory 20 kHz input channel bandwidth 4 voltage inputs measuring range end value: 480V L-N, accuracy < 0,1% 4 current inputs with 5 A rated current, measuring range end value: 10A, 100xIn impulse 1 ms Simultaneous processing of scanned and calculated voltages and currents Voltage and current oscillograph sampling rate: 40.96kHz/10.24kHz

Half-cycle recorder: Network frequency, effective voltage and current (RMS), voltage and current pointer, power recording rate: ~10ms (50Hz) /~8.33ms (60Hz)

Powerful triggers Online voltage and current streaming with a sampling rate of 40.96kHz.

IEC 61000-4-30, class A measured data processing

Recording of voltage quality events in accordance with DIN EN 50160; IEC61000-2-2; -2-12;-2-4.

Energy buffer for power failures of up to 2 seconds

2 kHz...9 kHz spectroanalysis, (35 frequency bands, BW = 200Hz) of voltage and currents in accordance with (IEC 61000-4-7)

Voltage and current harmonics n=2..50 2 digital inputs for general purposes with 2 input level options

2 relay outputs for safety monitoring and alarms

free WinPQ smart evaluation software

Option: Data analysis in a database with the WinPQ software package. Permanent communication with up to 500 devices.

Communications protocol

MODBUS RTUMODBUS TCP

IEC60870-5-104 (option P1)IEC61850 (option P2)

Time sync protocol(Receive / slave)

IEEE1344 / IRIG-B000..007

GPS (NMEA +PPS)

DCF77

NTP

PTP (IEEE1588)

Interfaces:

Ethernet 5 (10/100 Mbit)

2 * RS232/RS485at terminal

reversible

Dimensions (H x W x D)

160 x 90 x 58 mm

7

Technical Data multimess D9-PQ

Voltage inputs

Channels U1, U2, U3, UN/E/4

Electrical safetyDIN EN 61010

300V CAT IV600V CAT III

Input reference PE

Impedance -> PE 10 MΩ || 25pF

Rated input voltageUn

230 VAC

Measuring range end value ..480VAC L-E

Waveform e AC / DC

Maximum crest factor at Un 3

Bandwidth ...20kHz

Rated network frequency fn 0Hz/60Hz

Frequency range of thefundamental

fn ± 15%42.5..50..57.5Hz51.0..60..69.0Hz

Accuracy

Effective fundamental (RMS) ±0.1% Un (0°C...45°C)±0.2% Un (-25°C...55°C)@ 10%...150%Un

Fundamental, phase ±0.01°@ 10%...150%Un

Harmonic n = 2..50,effective (RMS)

±5% of the measured value@ Uh ≥ 1% Un±0.05% Un@ Uh < 1% Un

Harmonic n = 2..50, phase ±n∙0.01°@ Uh ≥ 1% Un

Interharmonics= 1..49, effective (RMS)

±5% of the measured value@ Uih = ≥ 1% Un±0.05% Un@ Uih < 1% Un

Network frequency 10mHz@ 10%...200%Un

Flicker meterDIN EN 61000-4-15:2011

Class F2

Residual voltage during voltage dip

±0.2% Un@ 10%..100%Un

Duration of voltage dip ±20ms@ 10%..100%Un

Residual voltage increase 0.2% Un@ 100%..150%Un

Duration of voltage increase 20ms@ 100%..150%Un

Duration of interruption ±20ms@ 1%..100%Un

Voltage asymmetry 0.15%@ 1%..5% of the measured value

Ripple-control voltage (< 3kHz) ±5% of the measured value@ Us = 3%..15% Un±0.15% Un@ Us = 1%..3% Un

Current inputs

Option C30 C31

Channels I2, I3, IN/4

Electrical safetyDIN EN 61010

300V CAT III

Input type Differential, isolated

Impedance ≤ 4mΩ

Rated input current In 5 AAC

Measuring range end value 10 AAC 100 AAC

Permanent overload capacity≤ 1s≤ 10ms≤ 1ms

10 A 30 A 100 A 500 A

Waveform Each AC

Maximum crest factor at In 4

Bandwidth Hz...20kHz

Accuracy

Fundamental, effective(RMS)

< 0.1% MW5%...100%

< 0.2% MW 5% ...10%

Fundamental, phase 0.1°5%...100% ±0.2° 5% ...10%

Harmonic n = 2..50,effective (RMS)

5%5%...100%

10% 5% ...10%

Harmonic n = 2..50,Phase

±n∙0.1°5%...100%

±n∙0.2° 5% ...10%

Interharmonics n= 1..49, effective (RMS)

±5%5%...100%

±10%5% ...10%

Storage of measured data

Internal memory 1024 MB

SD memory card 1 GB to 32 GB

Binary inputs (BI)

Range .250 VAC(/DC)

H levelL level

> 35 V< 20 V

Signal frequency C ... 70 Hz

Input resistance > 100kΩ

Electrical isolation Optocoupler,electrically isolated

Electrical safetyDIN EN 61010

300V CAT II

Signals and Energy Data | multimess D9-PQ Power Quality Network Analyzer Class A

SI

GN

ALS

AN

D E

NER

GY

DAT

A

8

Binary outputs (BO)

Contact specifications(EN60947-4-1, -5-1) :ConfigurationRated voltageRated currentRated load AC1Rated load AC15, 230VACInterrupting ratingDC1, 30/110/220 V

SPDT250VAC6A1500VA300VA

6/0,2/0,12A

Number of AC1 switch operations ≥ 60∙103 electrical

Electrical isolation insulated on all internalpotentials

Electrical safetyDIN EN 61010

300V CAT II

Power supply

Feature H1 H2

AC 90...264 V -

DC 100...300 V ...72 V

Power consumption ≤ 10 W

< 20 VA

≤ 10 Watts

Frequency 40...70Hz -

External fuse characteristics 6A

B

6A

B

Energy storage 2 seconds 2 seconds

Electrical safety

IEC 61010-1IEC 61010-2-030

Protection class 1

Contamination degree 2

Overvoltage category

Network supply option:

H0

H1

300V / CAT III

150V / CAT III

Measuring category 300V / CAT IV

600V / CAT III

Height 2000m

Electromagnetic compatibility

Immunity IEC 61000-6-5, environment G

Emissions CISPR22 (EN 55022) , class A

multimess D9-PQ Technical Data

Ambient parameters Transport and storage Operation

Ambient temperature:

Operation range limits

IEC 60721-3-1 / 1K5-40 ... +70°CIEC 60721-3-2 / 2K4-40 ... +70°C

IEC 60721-3-3 / 3K6-25 ... +55°C

Ambient temperature:

Nominal operation range

--- IEC 60721-3-3 / 3K5

mod. -10 ... +45°C

Relative humidity: 24 hour average

No condensation or ice

5...95 .95 %

Exposure to sunlight --- 700W/m2

Vibrations, jolts EC 60721-3-1 / 1M1

IEC 60721-3-2 / 2M1

IEC 60721-3-3 / 3M1

9

Technical Data multimess 4F96

Mechanical design The multimess D9-PQ can be mount-ed on the wall, integrated into the switchboard or in a mounting rail casing. All connections are accessible via phoenix terminals. Except for the voltage and current inputs, the con-nections are plug connections.An RJ 45 connector is available for the TCP/IP interface.

Color displayThe device's color display provides information on whether the measur-ing cables and measuring transducers were connected correctly and displays online data for voltage, current, total distortion factor (THD), power values and energy.The number of occurring PQ events, oscillograph and effective value re-cords of the last day, week and month are shown on the device's display.

Power supply 2 binary inputs

2 binary outputs

4 voltage inputs

4 current inputs

Signals and Energy Data | multimess D9-PQ Power Quality Network Analyzer Class A

SI

GN

ALS

AN

D E

NER

GY

DAT

A

10

multimess D9-PQ Measurements and Functions

multimess D9-PQ - automatic event detection and measurement standards: EN50160 (2013) / IEC61000-2-2 / IEC61000-2-12 /IEC61000-2-4 (class 1; 2; 3) / NRS048 / IEEE519 / IEC6 1000-4-30

Time interval Voltage 10/12T 150/180 10 min 2 h 1s N*s N*min

Network frequency Network frequency, 10s value (IEC61000-4-30)

Extremes, standard deviation of the network frequency (10s) Effective values (RMS) (IEC61000-4-30) Extremes, standard deviation of T/2- Ne dip [%], overvoltage [%] (IEC61000-4-30) Harmonic sub groups n=0..50 (IEC61000-4-7 Maximum values of 10/12 T harmonic sub groups n= 2..50 Interharmonic sub groups n=0..49 (IEC61000-4-7 Total distortion factor (THDS) (IEC61000-4-7) Partially weighted distortion factor (PWHD) Asymmetry, negative/positive sequence, sequence sign Asymmetry, zero-/positive sequence Positive, negative, zero sequence pointer Phase angles (fundamental) Flicker (IEC6100) Instantaneous value flicker (IEC61000-4-15) Ripple control voltages [%] (IEC61000-4-30) Phase angles ( zero crossings) of the phase voltage

Harmonics n=2..50 to the reference voltage fundamental

Frequency bands 1..35 , 2kHz..9kHz, effective value (RMS) (IEC61000-4-7)

Measurements and functionsClass A / IEC6: 1000-4-7 / IEC61000-4-15Continuous recording:Five fixed and two variable measurement intervals avail-able for continuous recording:10/12 T (200ms), 1 sec, n*sec, 150/180 T (3sec), n* min, 10 min, 2 h.

11

Measurements and Functions multimess D9-PQ

Time interval Current 10/12T 150/180 10 min 2 h 1s N*s N*min

Effective values (RMS) Extremes of T/2 values Harmonic sub groups n=0..50 (IEC61000-4-7 Maximum values of 10/12 T harmonic sub groups n= 2.50 Interharmonic sub groups n=0..49 (IEC61000-4-7) Total distortion factor (THD) (IEC61000-4-7) Total current harmonic Partially weighted distortion factor (PWHD) Weighted uneven harmonic currents (PHC) Distortion factors Asymmetry, negative/positive sequence, sequence sign Asymmetry, zero-/positive sequence Positive, negative, zero sequence pointer Phase angles (fundamental) Phase angles ( zero crossing) of the current harmonic

n=2..50 to the reference current fundamental

Frequency bands 1..35 , 2kHz..9kHz, effective value (RMS) (IEC61000-4-7)

Time interval Energy 10 min 2 h 1s N*s N*min

Active energy, phase Active energy, total Exported active energy, phase Exported active energy, total Imported active energy, phase Imported active energy, total (Inductive) reactive energy, phase (Inductive) reactive energy, total Exported (inductive) reactive energy, phase Exported (inductive) reactive energy, total Imported (inductive) reactive energy, phase Imported (inductive) reactive energy, total

Signals and Energy Data | multimess D9-PQ Power Quality Network Analyzer Class A

SI

GN

ALS

AN

D E

NER

GY

DAT

A

12

Time interval Power 10 min 2 h 1s N*s N*min

Active power, phase Active power, total Active power, extremes Reactive power, phase Reactive power, total Reactive power, extremes Apparent power, phase Apparent power, total Fundamental active power, phase Fundamental active power, total Fundamental active power, phase Fundamental reactive power (shift), total Fundamental apparent power, phase Phase angle of the fundamental apparent power, phase Fundamental apparent power, total Phase angle of the fundamental apparent power, total Distortion reactive power, phase Distortion reactive power, total Active power factors, phase, total Reactive power factors, phase, total COSφ + sign, phase, total SINφ + sign, phase, total COSφ + sign of the distortion reactive power, phase, total Capacitative, inductive scaling factor of COSφ (-1..0..+1) Triggered interval, medium active power, phase

Triggered interval, medium active power, total

Triggered interval, medium reactive power, phase

Triggered interval, medium reactive power, total

multimess D9-PQ Measurements and Functions

13

Measurements and Functions multimess D9-PQ

Recording rate: ~10ms (50Hz) or ~8.333ms (60Hz) max. record length: 6min (50Hz) or 5min (60Hz)

Oscillograph:

Half-cycle recorder: Network frequency

Effective voltage (RMS)

Effective current (RMS)

Active power, phase

Reactive power, phase

Active power, total

Fundamental reactive power, total

Phase angle of the fundamental apparent power, total

Phase angle voltage (fundamental)

Phase angle currents (fundamental)

Positive, negative, zero sequence voltage pointer

Positive, negative, zero sequence current pointer

Sampling rate: 40.96kHz or 10.24kHzMax. recording length: 4sec (40.96kHz) or 16sec (10.24kHz)T (3sec), n* min, 10 min, 2 h.

3 wire system 4 wire system

Phase earth conductor voltage Phase earth conductor voltage

Residual voltage Neutral conductor earth voltage

Phase-phase voltage

Phase currents

Total current Neutral conductor current

Signals and Energy Data | multimess D9-PQ Power Quality Network Analyzer Class A

Triggers:

Triggers lower upper step

Effective value (RMS) phase voltage (T/2) Effective value (RMS) Phase-phase voltage (T/2) Effective value (RMS) residual / neutral conductor - earth conductor voltage (T/2) Positive sequence voltage (T/2) Negative sequence voltage (T/2) Zero sequence voltage (T/2) Phase voltage phase (T/2) Phase voltage waveforms (wave shape trigger)

+/- threshold valuePhase-phase voltage waveforms (wave shape trigger)

Residual / neutral conductor - earth conductor voltage waveforms (envelope trigger)

Effective value (RMS) phase currents (T/2) Effective value (RMS) (total / neutral conductor current (T/2) Network frequency (T/2) Binary inputs (debounced) Rising, falling flank

Command external

SI

GN

ALS

AN

D E

NER

GY

DAT

A

14

multimess D9-PQ Measurements and Functions

PQ events:

Triggers lower upper

Voltage dip (T/2) Rise in voltage (T/2) Voltage interruption (T/2)

Fast change in voltage (T/2)

Filter for floating average

value

medium +/- threshold

average value

Change in voltage (10min) Voltage asymmetry (10min) Network ripple control voltage (150/180T) Voltage harmonic (10min) Total voltage distortion (THD) (10min) Short-term voltage fluctuations PST (10min) Long-term voltage fluctuations PST (10min) Network frequency (10s)

Online mode for direct readout:

Measurement/functions

Oscillograph

Performance cube for active, reactive, apparent and distortion power

Voltage and current harmonic n=2..50

Voltage and current interharmonics n=0..49

Phase of current harmonics n=2..50

Harmonic power n=2..50: ±Pn , ± Qn

Voltage and current frequency spectrums up to 20kHz

15

Signals and Energy Data | multimess D9-PQ Power Quality Network Analyzer Class A

Measurement and optimization technologyThe basis for contemporary energy management is the precise recording and processing of energy data. With its sophisticated measuring devices, energy meters and signal components, KBR creates the best conditions for greater transparency and efficiency when dealing with energy. Modular energy optimization reduces energy costs by optimizing power supply.

p Measurement data capture p Reducing load peaksp Lowering energy costsp Monitoring and documenting

voltage dips

Network analysisThe voltage quality is steadily decreasing. This is due to the widespread use of power electronics that create harmonics which influence the supply network. To be able to record and evaluate these disturbances, KBR offers the high-quality network analyzer multilog .

p Automatic evaluation in accordance with EN 50160 and IEC 61000

p More than 2,000 measured values in parallel, with a fault recorder ensuring consistency

p Highest possible measuring accuracy in accordance with IEC 61000-4-30, class A

p Recording time of up to a year

CompensationReactive power compensation and improvement of the network quality are essential aspects of KBR Power Quality. KBR develops and produces the components for the compensation systems in its own production facilities. Our Power Quality team offers network analyses, on-site troubleshooting and passive as well as active power filters in order to improve grid quality.

p Reducing reactive energy costs

p Increasing supply safety

p Increasing operational safety

p Competent consultation and service

p Seminars and workshopsp Power Quality - network

analysesp System integrationp Technical support

ServiceWe provide immediate professional assistance from a single agent without lengthy call waiting times. Support from experienced professionals for energy management. This is our service commitment!

KBR provides impulses and paves the way... www.kbr.de

POWER QUALITY

EDEP

RO01

16 0

812-

1ED

EPRO

0000

-000

0-0_

DE_

Mul

times

s D

9-PQ

Blin

dtex

t

Am Kiefernschlag 7 D-91126 Schwabach, Germany

T +49 (0) 9122 6373 - 0 F +49 (0) 9122 6373 - 83 E [email protected]

www.kbr.de www.visualenergy.de

KBR Kompensationsanlagenbau GmbH

1923

0_ED

EPRO

0178

-511

5-1_

EN