msc in ref

Upload: mostafa-hassanain

Post on 24-Feb-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Msc in Ref

    1/36

    1

    CHAPTER (1)

    INTRODUCTION

    HCFC22 has been predominantly used in residential air conditioners

    and heat pumps for the past few decades and its sales volume has been the

    largest among various refrigerants. Even though the ozone depleting potential

    of HCFC22 is not as high as CFCs, it still contains ozone depleting chlorine.

    Due to its ozone depleting effect, Montreal Protocol and its amendments have

    set the phase-out deadlines on HCFC22in different countries and areas.

    The Montreal Protocol sets limits (cap) for the HCFC consumption,

    defined as production plus imports less exports and specified destruction: in

    1996 (freeze at calculated cap), 2004 (65% of cap), 2010 (25%), 2015 (10%),

    and 2020 (0.5%) with full consumption phase-out by 2030 in non-Article 5

    countries. Aprea et al ( 2011) reported that the schedule for Article 5 countries

    like Egypt begins with a freeze of the amount of HCFC in 2013 (based on

    2010 production and consumption levels) with declining limits starting in

    2015 (90%), 2020 (65%), 2025 (32.5%), and 2030 (2.5%) followed by phase-

    out in 2040. Exports from Article 5 countries into non-Article 5 countries are

    effectively restricted to meet the more stringent non-Article 5 schedules to

    avoid separate domestic and export products and to exploit newer

    technologies derived from joint ventures and licensing agreements.

    Park and Jung (2006) sated that various alternatives for HCFC22 have

    been proposed and tested in an effort to comply with the Montreal protocol in

    the past years,. At this time, HFC refrigerant mixtures such as R-410A and R-

    407C are used in some countries to replace R-22. R-410A is a near azeotropic

    mixture with a gliding temperature difference (GTD) of less than 0.2C. Its

    vapor pressure is roughly 50% higher than that of HCFC22 and hence the

    capacity increases significantly with R-410A. Due to high pressure,

  • 7/25/2019 Msc in Ref

    2/36

    2

    compressors need to be redesigned completely and also the heat exchangers

    needs to be optimized to accommodate lower volumetric flow rates associated

    with the use of R-410A. Even though a simple thermodynamic cycle analysis

    shows that the cycle COP of R-410A is somewhere lower than that of

    HCFC22, the actual energy efficiency of R-410A is similar to that of

    HCFC22 due to the improved compressor efficiency and reduced energy

    losses in some components of the refrigeration system. On the other hand,

    R407C is a non-azeotropic refrigerant mixture (NARM) whose GTD is

    roughly 6 C. Its vapor pressure is similar to that of HCFC22 and hence it is

    expected that R-407C may be used in existing equipment without major

    changes. Since it is a NARM, however, fractionation may occur in case of the

    leak in the system. At the same time, many companies expend much effort to

    develop their own alternatives for R-22. Especially, refrigerant mixtures

    composed of environmentally safe pure refrigerants have gotten a special

    attention from the industry with the expectation of possible energy efficiency

    without major changes in the system.Limitations of both R-410A and R-407c lead many researchers to

    search about the best R-22 replaced refrigerant in both for old equipment and

    new one. Strategy of R-22 replacement has three mechanisms available to

    eliminate this substance. First, especially for old equipment with remaining

    life, a drop-in process is recommended. This involves the pure exchange of

    the refrigerant without any modifications to the refrigerating plant and

    keeping the existing lubricant oil. The second option is to undertake a

    retrofitting process. This is understood as an active adaptation of the

    refrigeration plant to the new refrigerant, which could also entail the

    replacement of the lubricant oil, the expansion valves and certain other

    elements of the system. Finally, the last option, although only possible for

    new equipment, is to design new plants with long-term refrigerants, such as

  • 7/25/2019 Msc in Ref

    3/36

    3

    hydrocarbons, ammonia or carbon dioxide as reported by Mohanraj et al

    (2009).

    A number of R-22 alternatives for vapor compression residential air

    conditioners and heat pumps systems have been proposed in the literature

    based on thermodynamic property data. Thus, the objectives of the present

    work are studying investigation the performance characteristics of water

    chiller work with R-22, R-438A and R-422A respectively. Comparison

    between performance characteristics of the air conditioning system using

    R-22 and its alternatives. Indicate the best drop-in replacement refrigerant for

    old systems.

    The present thesis consists of six chapters and five appendices. Chapter

    (1) gives a brief introduction. Chapter (2) deals with an overview of the

    literature related to performance characteristics of compression residential air

    conditioners and heat pumps working with R-22 alternatives. Chapter (3)

    describes the experimental test rig including instrumentation, test procedure

    and data reduction. Results of experimental investigations are discussed inChapter (4). Conclusion of experimental investigations are given in Chapter

    (5). Specification of water chiller system components, specification of the

    instrumentation devices, instruments calibration and uncertainty analysis are

    given in appendices (A), (B), (C), and (D), respectively.

  • 7/25/2019 Msc in Ref

    4/36

    4

    CHAPTER (2)

    LITERATURE SURVEY

    2.1 Introduction

    R-22 has been widely used for many decades in vapour compression

    refrigeration system. It is generally accepted and most suitable refrigerant for

    air-conditioners and in medium and low temperature applications for

    commercial and industrial refrigeration. Unfortunately, it belongs to the

    family of hydro-chlorofluorocarbon (HCFC) refrigerants, which considered as

    harmful working fluids to the environment. Due to their stratospheric ozone

    layer depletion, they are now being controlled substances by the Montreal

    protocol. Montreal Protocol and its amendments have set the phase-out

    deadlines on R-22 in different countries and areas. EU and Japan have banned

    the import of R-22 systems since 2004, and the USA has prohibited the use of

    R-22 as refrigerant in new equipment from 2010. In accordance with the

    Montreal Protocol, all developing countries will freeze R-22 consumption at

    its level in 2015, and will ban the use of R-22 in A/C industry from 2030.

    With increasingly understanding the consequences caused by the ozone

    depletion, many countries and areas have accelerated the phase-out process of

    R-22.

    2.2 Environmental Impacts

    In general, the atmosphere is divided into five layers, which are defined

    by distance above the surface of the earth. They are; troposphere (0-15km);

    stratosphere (15-50km); mesosphere (50-85km); thermosphere and

    ionosphere (above 85km).

    HCFC refrigerants are a family of chemical compounds derived from

    the hydrocarbons (methane and ethane) by substitution of chlorine and

    fluorine atoms for hydrogen. The emission of chlorine and fluorine atoms

  • 7/25/2019 Msc in Ref

    5/36

    5

    present in HCHC refrigerants is responsible for the major environmental

    impacts. The two important ones are ozone depleting and greenhouse.

    2.2.1 Ozone depletion

    Ozone (O3) is a triatomic allotrope of oxygen composed naturally

    through a process called photochemical analysis where the sunlight has an

    impact on oxygen molecules, the ozone exists throughout the year over the

    equatorial belt, and moves toward the polar regions by the movements of air

    in the stratosphere that is filled by ozone on the altitudes ranging from 20 to

    35 kilometers, Its thickness ranges between 2 to 8 km as reported in (MSEA-

    EEAA, 2009).

    It is an extremely rare component of the Earths atmosphere; in every

    ten million molecules of air, only about three are ozone. Most of the ozone

    (90%) is found in the upper atmosphere (UNEP, 2000).

    HCFCs, CFCs and halons are stable chemicals, which persist for many

    years in the atmosphere. They eventually break down in the stratosphere torelease halogens; chlorine in the case of HCFCs, CFCs and bromine in the

    case of halons. Chlorine and bromine can destroy ozone but are not destroyed

    themselves during this process. Thus one halogen atom can destroy thousands

    of molecules of ozone.

    Ozone layer is the natural filter and preventive shield surrounding Earth

    to protect all creatures against harmful UV-B rays effects coming from the

    sun to earths surface. Effects include human skin cancer and eye cataract;

    effect on photosynthesis in green plants, reducing plant growth and affecting

    agricultural crops; and impact on marine ecosystems, all of which leads to an

    unbalanced general system of nature and life on earth, which, in turn, affects

    the global climate change; hence, threatening human health and environment

    safety.

  • 7/25/2019 Msc in Ref

    6/36

    6

    2.2.2 Greenhouse

    The greenhouse effect is caused by absorption of long wave radiation

    from earths surface by carbon dioxide, and the other naturally occurring

    "greenhouse gases", in the troposphere (0-15 km). Short wave radiation from

    the sun has most of its harmful components filtered out by the ozone layer.

    The rest of the short wave radiation heats the surface of the earth and the seas.

    These surfaces give off long wave radiation, which can be trapped by a

    variety of greenhouse gases, which act like an insulating blanket. There is

    thus a tendency for global warming.

    The environmental effects are measured by ozone depletion potential

    (ODP), global warming potential (GWP) and total equivalent warming impact

    (TEWI). ODP is a relative index indicating the extent to which a chemical

    may cause ozone depletion. The reference level of 1 is the potential of R11 to

    cause ozone depletion. GWP is also a relative index indicating the extent to

    which a chemical may cause greenhouse effect. To combine the impact ofdifferent greenhouse gases released into the atmosphere, TEWI has been

    defined as the equivalent amount of carbon dioxide (CO2) that would give

    approximately the same integrated radiative forcing over a particular

    integration time horizon (ITH). TEWI takes into account contributions from

    the substance itself (direct) and the data on energy consumption of the

    equipment during its operation (indirect) that may contribute to global

    warming.

    TEWI is expressed as the sum of contributions from direct and indirect

    global warming potentials as:

  • 7/25/2019 Msc in Ref

    7/36

    7

    TEWI = (GWP x Lx n)+ (GWP x m (1- (recovery) +(n x Eannual x)

    Leakage Recovery losses Energy consumption-

    direct global warming potential indirect global

    Warming potential

    Where, GWP is the global warming potential (CO2-related), L is the leakage

    rate per year (kg), is the system operating time (years), m is the refrigerant

    charge (kg), recovery is the recycling factor, E annual is the energy

    consumption per year (kWh) and is the CO2-emission per kWh. The ODP

    values of pure CFC and HCFC refrigerants are shown pictorially are shownpictorially in Fig. 2.1.The GWP values of pure and mixed refrigerants are

    illustrated in Fig. 2.2 and Fig. 2.3 .

    Fig. (2.1) Ozone depletion potential of pure CFCs and HCFCs refrigerants

    (Calm and Hourahan, 2001).

    0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1

    R11 R12 R113 R114 R115 R22 R123 R124 R141B R438A R422A

    1

    0.82

    0.90.87

    0.40.36

    0.03

    0.08 0.11

    0 0

    ODP

    Refrigerants

  • 7/25/2019 Msc in Ref

    8/36

    8

    Fig. (2.2) Global warming of pure CFC and HCFC refrigerants (Calm and

    Hourahan, 2001).

    Fig. (2.3) Global warming of HFC mixtures (Dupont,2009)

    0

    2000

    4000

    6000

    8000

    10000

    12000

    R11 R12 R113 R114 R115 R22 R123 R124 R141B R142B

    4800

    10900

    6000

    9700

    6800

    2000

    400

    1000 1100

    2200

    GWP

    Refrigerants

    0

    500

    1000

    1500

    2000

    2500

    3000

    3500

    4000

    R404A R407A R407B R407C R438A R410A R410B R417A R422D R422A

    3650

    2000

    2600

    1750 1684

    2100 2200

    2300

    2729

    2530

    GWP

    Refrigerants

  • 7/25/2019 Msc in Ref

    9/36

    9

    2.3 International Efforts

    The efforts can be sorted in two directions.

    2.3.1 Ozone layer depletion

    Molina and Rowland studied of ozone layer depletion since 1974 for

    first time then the scientific confirmation of the depletion of the ozone layer

    prompted the international community to establish a mechanism for

    cooperation to take action to protect the ozone layer. This was formalized by a

    treaty called the Vienna Convention for the protection of the ozone layer,

    which was adopted and signed by 28 countries on 22 March 1985 in Vienna.

    This led in September 1987 to the drafting of the Montreal Protocol on

    substances that deplete the ozone layer. The Protocol was signed by 24

    countries and by the European Economic Community and entered into force

    on 1 January 1989. The treaty states that the Parties to the Montreal Protocol

    recognize that worldwide emissions of ozone-depleting substances (ODSs)

    significantly deplete and otherwise modify the ozone layer in a manner that islikely to result in adverse effects on human health and the environment. The

    Parties previously agreed to an extended phase-out schedule, with final phase-

    out in developed countries by 2030 and in developing countries by 2040.

    These schedules have now been brought forward. The September 2007

    adjustments to the Montreal Protocol oblige Article 5 countries to take action

    as soon as possible to freeze their baselines in respect of HCFC production

    and consumption levels (average consumption and average production for the

    years 2009-2010) in 2013, and as a first step, to reduce their production and

    consumption of HCFCs by 10 per cent by 2015 ( UNIDO,2009).

  • 7/25/2019 Msc in Ref

    10/36

    10

    2.3.2 Climate change

    The United Nations Framework Convention on Climate Change

    (UNFCCC) was agreed in 1992 in Rio de Janeiro and ratified thereafter.

    Many countries joined the international treaty to begin to consider what could

    be done to reduce global warming and to work on adaptation strategies to

    cope with whatever temperature increases are inevitable. More recently, a

    number of nations approved an addition to the treaty, the Kyoto protocol,

    which has more powerful (and legally binding) measures. The UNFCCC

    secretariat supports all the institutions involved in the international climate

    change political process. The Kyoto protocol is an international agreement

    linked to the United Nations framework convention on climate change. It was

    adopted in Kyoto, Japan, on 11 December 1997, and entered into force on 16

    February 2005. To date, 180 nations have ratified the treaty. The detailed

    rules for the implementation of the Protocol were adopted at the Seventh

    Conference of the Parties in Marrakesh in 2001 ( UNIDO,2009).

    2.4 Egyptian Strategy for Phasing Out Use of HCFCs Substances

    Egyptian Meteorological Authority (EMA) measures ozone for

    monitoring ozone layer change above Egypt, especially above Aswan (above

    the tropical area where ozone is naturally generated). Figure (2.4) show that

    Ozone measurement changes above Cairo and Aswan Straight lines

    demonstrate that there is no clear tendency for change.

    MSEA is currently conducting an amendment and updating legislations and

    regulations related to the use and importation of HCFC substances; in

    addition to developing a strategy for phasing out use of such substances in

    various fields. Table (2-1) shows the timetable of phasing out the use of the

    ozone depleting HCFCs in "Article 5" countries (including Egypt) that applies

    to Montreal Protocol (Egypt State of Environment Report, 2009).

  • 7/25/2019 Msc in Ref

    11/36

    11

    Table (2.1): Timetable for phasing out use of HCFCs (UNIDO, 2009)

    Substance Base Level Production/Consumption Rate Control

    First Group

    HCFC

    substances

    Average

    Consumption

    Rate in

    2009-2010

    Freezing production/consumption

    levels (1st January, 2013)

    10% reduction (1st January ,2015)

    35% reduction (1st January , 2020)

    67.5% reduction (1st January ,2025)

    100% reduction (1st January, 2030) with a

    possible exemptions for necessary uses.

    Fig. (2.4) Ozone measurement changes above Cairo and Aswan (MSEA-

    EEAA.,2009)

  • 7/25/2019 Msc in Ref

    12/36

    12

    2.5 R-22 Replacement

    From precession R-22 must be phased-out and it must be replaced in

    both for old equipment and new one. Strategy of R-22 has three mechanisms

    available to eliminate this substance, which are schematized in Fig. (2.5).

    First, especially for old equipment with remaining life, a drop-in process is

    recommended. This involves the pure exchange of the refrigerant without any

    modifications to the refrigerating plant and keeping the existing lubricant oil.

    The second option is to undertake a retrofitting process. This is understood as

    an active adaptation of the refrigeration plant to the new refrigerant, which

    could also entail the replacement of the lubricant oil, the expansion valves and

    certain other elements of the system. Finally, the last option, although only

    possible for new equipment, is to design new plants with long-term

    refrigerants, such as hydrocarbons, ammonia or carbon dioxide.

    Fig. (2.5) Mechanisms and some refrigerant options to substitute R22 in

    medium and low temperature applications. (Llopis et al., 2012)

  • 7/25/2019 Msc in Ref

    13/36

    13

    2.6 Experimental and Theoretical Studies

    A large number of experimental and theoretical studies are found in literature

    pertaining to HC, HFC and their mixtures as alternatives to halogenated

    refrigerant by researchers from various parts of the world. A brief summary of

    these results is given in the following sections

    (Mohanraj et al., 2009)

    2.6.1 Hydrocarbons refrigerants as R22 alternatives

    Choi et al. (1996) evaluated the performance of flammable refrigerants

    as R22 alternative for water-to-water residential heat pump applications at

    different compressor speeds. The results showed that based on the capacity

    R32/R152a was found to be the best performer due to good glide matching in

    the heat exchangers and have good thermodynamic and transport properties.

    The HC mixture (R290/R600a) is found to have the highest COP with a loss

    in the system capacity.Purkayastha and Bansal (1998) experimented with R290 and LPG

    (R290 98.95%, R170 1.007%, R600a 0.0397%) as substitute for R22 in

    a 15 kW heat pump. It has been reported than COP of HC refrigerants (R290

    and LPG mixture) were respectively 18% and 12% higher compared to that of

    R22. However volumetric refrigeration capacity and condenser are highly

    lower by 16% and 14% and 13% and 10%.

    Chang et al.(1999) measured the performance characteristics of heat

    pump system using hydrocarbon refrigerants (propane, isobutane, butane and

    propylene) and binary mixtures of propane/ isobutene and propane/butane as

    alternative to R-22 They concluded that The cooling and heating capacities of

    R290 are slightly smaller than those of R-22 with a slightly higher COP than

    that of R-22. The capacity and COP of R-1270 are slightly greater than that of

  • 7/25/2019 Msc in Ref

    14/36

    14

    R-22, which is an indication of a possible alternative for air conditioning and

    heat pumping applications. When zeotropic refrigerant mixtures of R-290=R-

    600a and R-290=R-600 are used, the cooling and heating capacities increase

    almost linearly with respect to mass fraction of R290. COPs for the mixtures

    are higher than linearly interpolated values based on those of pure

    components. The COP of hydrocarbon mixtures for the cooling condition is

    higher than that of R-22 for a wide range of the mixture compositions.

    Hydrocarbon refrigerants have a higher thermal conductivity and a lower

    viscosity in the liquid phase than R-22, which is a potential for higher heat

    transfer coefficients in the evaporator and condenser. When considering

    average heat transfer coefficient, it is concluded that hydrocarbons heat

    transfer performance is comparable to R-22. Zeotropic mixtures show heat

    transfer degradation due to composition difference between vapor and liquid

    phases.One thing to keep in mind is the flammability of hydrocarbon

    refrigerant. Leak-free design of a system, or indirect heating or cooling design

    using the secondary heat transfer fluid can be a possible solution. Safetyshould be considered when using hydrocarbon as a refrigerant.

    Chang et al. (2000) investigated with R290, R1270, R600, and R600a

    and binary mixtures of R290/R600a and R290/R600 as R22 alternatives in a

    heat pump. It has been reported that cooling and heating capacity of R290

    were smaller and COP was slightly higher than that of R22. The capacity and

    COP of the R1270 were slightly greater than R22. The COP of the zeotropic

    mixture R290/R600a with 50% mass percentage of R290 was enhanced by

    7% and R290/R600 at composition of 75:25 (by mass percentage) showed

    11% improved performance. It has been found that system is degraded for

    zeotropic HC mixtures due to composition variation in phase change.

    Granryd (2001) reviewed the HC refrigerants for different

    applications. He compared R290 with R22 and reported that R290 gave lower

  • 7/25/2019 Msc in Ref

    15/36

    15

    capacity by 315% than that of R22. The heat transfer coefficient of R290 in

    condenser was also found to be lower than that of R22.

    In 2001 Devotta and Waghmare use NIST CYCLED has been used for

    the comparative thermodynamic analysis for the comparative thermodynamic

    analysis. and they found that the characteristics of HC 290 are very close to

    those of HCFC-22, and compressors require very little modification.

    Therefore, HC-290 is a potential candidate provided the risk concerns are

    mitigated as had been accomplished for refrigerators.

    Urchuegua et al. (2004) reported the experimental characterization of

    two commercial scroll and reciprocating compressors working with R22 and

    R290 with same mineral oil as lubricant. His experiments reported that the

    refrigerating capacity in both types of units was reduced 1320% due to the

    use of propane but at the same time COP was increased by 13%.

    Chaichana et al. (2003) studied the options of using natural working

    fluids (R717, R744, R290, R600, R600a and R1270) as substitutes for R22 in

    solar boosted heat pumps based on thermo-physical properties and the thermalperformance. Their results indicate that R744 is not suitable for solar boosted

    heat pumps because of its low critical temperature and high operating

    pressure values. R717 seems to be more appropriate in terms of operating

    parameters and performance which requires major changes in the system.

    Condensing pressure values of R600 and R600a are 5070% less than R22.

    Hence R600 and R600a cannot be used as drop in substitute for R22. R290

    and R1270 have close saturation pressure values compared to that of R22.

    The performance of R22, R290 and R1270 was comparable. Hence, R290 and

    R1270 were identified as direct drop in substitutes for R22.

    Thermodynamic analysis of refrigerant mixtures for possible replacements

    for CFCs by an algorithm compiling property data was reported by

    Arcaklioglu et al (2006). To achieve this aim the point properties of the

  • 7/25/2019 Msc in Ref

    16/36

    16

    refrigerants are obtained from REFPROP where appropriate. According to his

    calculations using the current systems the best mixtures, which can either fit

    or provide better performance for the CFC based refrigerants, are as follows

    For R12, R290/R600a (56/44) mixture provides 0.4% better COP. For R-22,

    R32/R125/R134a (32.5/5/62.5) mixture provides 0.8% better COP. For R502,

    R32/R125/R134a (43/5/52) mixture provides 2% better COP.

    Park and Jung. (2006) studied the thermodynamic performance of two

    hydrocarbon refrigerants and seven mixtures composed of R1270, R290,

    RE170 and R152a as alternatives for R22 in residential air conditioning

    applications. It has been reported that all the pure and mixed fluids tested

    have low GWP of 358 as compared to that of R22. Also their test results

    showed that expect R1270, all the other refrigerants have higher COP with

    lower discharge temperature and similar refrigeration capacity.

    Park and Jung. (2007) studied performances of two pure

    hydrocarbons and seven mixtures composed of propylene, propane,

    HFC152a, and dimethylether were measured to substitute for HR-22 inresidential air-conditioners and heat pumps. The pure and mixed refrigerants

    tested have greenhouse warming potentials (GWPs) of 358 as compared to

    that of CO2 and the mixtures are all near-azeotropic having the gliding

    temperature difference (GTD) of less than 0.6 0C .The following conclusions

    were drawn. COPs of these fluids are similar to, or better than, that of R-

    22.45%R1270/ 40%R290/15%DME mixture showed the highest COP which

    is 5.7% higher than that of R-22.Capacities of propane (R-290) and

    20%R1270/80%R290 are lower than that of R-22 by 11.5 and 6.6%,

    respectively, while other fluids showed a similar capacity to that of R-

    22.Compressor-discharge temperatures of all fluids tested were lower than

    that of R-C22 by 1117 0C. This indirectly indicates that these fluids would

    show long-term stability and reliability. The refrigerant charge for all

  • 7/25/2019 Msc in Ref

    17/36

    17

    refrigerants tested was reduced up to 55% as compared to R-22 due to their

    lower density.

    Thermodynamic performance of R-433A (30% propylene and 70%

    propane)and R-22 is measured in a heat pump bench tester under air

    conditioning and heat pumping conditions was studied by Park et al

    (2008).He concluded that The COP of R-433A is 4.97.6% higher than that of

    R-22.The capacity of R-433A is 1.05.5% lower than that of R-22.The

    compressor discharge temperature of R433A is 22.627.9 _C lower than that

    of R-22.The amount of charge for R-433A is 57.057.7% lower than that of

    R-22 due to its low density.R-433A is a good long term environmentally

    friendly alternative refrigerant to replace R-22 in residential air-conditioners

    and heat pumps due to its excellent thermodynamic and environmental

    properties with minor changes.

    Ki-Jung Park (2009) back to study thermodynamic performance of R-

    432A (80% propylene (R1270) and 20% dimethylether (RE170)) and R-22 is

    measured in a heat pump bench tester under both air-conditioning and heatpumping conditions. He concluded that the COP of R-432A is 8.58.7%

    higher than that of R-22.The capacity of R-432A is 1.96.4% higher than that

    of R-22.The compressor discharge temperature of R432A is 14.1 17.3oC

    lower than that of R-22.The amount of charge for R-432A is 50% lower than

    that of R-22 due to its low density.R-432A is a good long term drop-in

    environmentally friendly alternative refrigerant to replace R-22 in residential

    air conditioners and heat pumps due to its excellent thermodynamic and

    environmental properties.

    Cleland et al. (2009) studied the using of hydrocarbons as drop-in

    replacements for R-22 in on-farm milk cooling equipment and he concluded

    that Drop-in replacement of R-22 by the hydrocarbon refrigerant Care-50 in a

    farm milk silo refrigeration system gave about 6% lower energy use, and had

  • 7/25/2019 Msc in Ref

    18/36

    18

    no noticeable effect on milk cooling capacity. The conversion was very

    simple and potentially cost-effective because, apart from the change in

    refrigerant (and associated labeling and documentation), no other alterations

    or adjustments to the system were made. Both the laboratory and farm trials

    showed that hydrocarbons are attractive alternatives R-22 for on-farm milk

    cooling equipment.

    Teng et al (2012) studied investigates the feasibility of replacing R-22

    window air conditioners with hydrocarbon refrigerants (propane, R290) for

    various charged masses (25 70%), and analyzes the performance at different

    outside air temperatures (26, 29, 32 oC)Results show that the best charged

    mass for replacing R-22 with R290 refrigerant is approximately 50 55% of

    the R-22 refrigerant for various outside air temperatures. In addition, a

    comparison of R-22 and R290 refrigerants shows that the EER of R290

    refrigerant exhibits an upward trend as the outside air temperature increases,

    improving the EER by approximately 20% in the ideal situation. The

    refrigerant in a window air conditioner can be changed from R-22 toR290refrigerant, and the ODP and GWP differences are negligible. Results

    show that R290 refrigerant is suitable for use in higher outdoor temperature

    and higher EER values of R290 air conditioner, and simultaneously helps

    combat global warming and reduce carbon emissions.

    2.6.2 Carbon dioxide as an alternative

    Brown et al. (2002) compared the performance of CO2 and R-22 in a

    residential air conditioning system using semi-theoretical vapor compression

    and trans critical cycle models. The simulated R22 system has conventional

    component configuration, while CO2 system includes liquid-line/suction-line

    heat exchanger. It has been reported that COP of the CO2 system is 10% less

    and power consumption is 38% higher than that of R22. The cooling

  • 7/25/2019 Msc in Ref

    19/36

    19

    capacities of both the systems were identical at 35 o C ambient temperatures

    and will decrease linearly with increase in the ambient temperature.

    2.6.3 HFC mixtures as alternatives

    Knig. (1997) compared propane as R-22 replacements with R-410A,

    R-407C. Theoretical comparison of these replacements showed that only

    slight difference in terms of COP and capacity.

    Jung et al. (2000) studied the performance of HFC and hydrocarbon

    mixtures as alternatives to R-22. It has been reported that COP of ternary

    mixtures composed of R-32, R-125, R-134a is 45% higher than that of R-22.

    The COP of binary mixture composed of R-32 and R134a is 7% higher and

    capacities are similar to R-22 and COP of binary azeotrope of R-290 and

    R134a is 35% higher than R-22. Compressor dome temperature and

    discharge temperature were found to be lower than that of R-22 and hence the

    system reliability and fluid stability with these mixtures would be better than

    that of R-22.Motta and Domanski (2000) reported the simulation results of R-22

    and its alternatives R-410A and R-407C at high outdoor temperatures. Their

    results indicate that R-410A has more pronounced performance degradation

    than R-22 and R-407C because of low critical temperature. R410A has the

    highest COP degradation. The change of COP for R-22 and R-407C is similar

    because their critical temperatures are within 10 K of each other. The

    presence of liquid-line/suction-line heat exchanger will improve the capacity

    and COP of all refrigerants studied.

    Devotta et al. (2001) NIST CYCLED has been used for the

    comparative thermodynamic analysis. Among the refrigerants studied (HFC-

    134a, HC-290, R-407C, R-410A, and three blends of HFC-32, HFC-134a and

    HFC-125) and they found that. HFC-134a offers the highest COP, but its

  • 7/25/2019 Msc in Ref

    20/36

    20

    capacity is the lowest and requires much larger compressors. For retrofitting,

    R-407C is probably the best candidate.

    Kim (2002) reported an experimental assessment of performance tests

    for R-22 and four alternative fluids (R-134a, R-32/134a (30/70%), R-407C,

    and R-410A) at operating conditions typical for a residential air conditioner .

    The zeotropic mixtures, R-407C and R-32/134a (30/70), have the closest

    performance characteristics to R-22, with R-32/134a having a slightly better

    COP. The important operating parameters (evaporator and condenser

    pressures and compressor discharge temperature) did not deviate significantly

    from the R-22 values. Also, the low-pressure R-134a had a COP comparable

    to the R- 22 COP, but it had a much lower capacity. The binary near-

    azeotrope, R-410A, displayed a 44% higher capacity than R-22 when tested at

    the same compressor rpm. At a reduced compressor speed at which R-410A

    capacity matched that of R-22, the COP of R-410A was 22% better than the

    COP of R-22. However, it has to be realized that this COP improvement

    resulted from significantly lower pressure losses (especially in the evaporator,suction line, and at compressor valves), and from reduced friction losses in

    the compressor running at a lower speed.

    Payne and Domanski (2002) tested with R-410A in a R-22 based split

    air-conditioning systems with outdoor temperature ranging from 27 to 55 oC.

    The capacity and efficiency of both systems decreased linearly with

    increasing outdoor temperature. The capacities of both systems were

    approximately equal at 35 oC whereas at 55 oC outdoor temperature, the R-

    410A capacity was reduced by 9% compared to that of R-22. The

    performance of R-410A was degraded more than R-22 when ambient

    temperature gets increased more than 68 0C due to its lower critical

    temperature.

  • 7/25/2019 Msc in Ref

    21/36

    21

    Li et al. (2002) studied the performance of high temperature hot water

    heat pump with non-azeotropic refrigerant mixture R-22/R-141b. the results

    shows that the coefficient of performance is maximum when the molar

    component of R22 is about 75%. It is shown that the maximum pressure of

    the system is under 2.5 MPa after taking R-22/R-141b as working fluids, even

    though the highest cooling water temperatures is about 80 oC

    Rakhesh et al. (2003) experimentally studied the performance of R-

    407C and R-407A as alternatives for R-22 in a heat pump. The results

    reported that R-22 gives highest overall COP at all condensing and evaporator

    temperatures. The overall COP of R-407C is slightly higher than R-407A. At

    low evaporator temperature, the performance of R-407C and R-407A are

    comparable. The isentropic efficiency is highest for R-22 and lowest for R-

    407A. The volumetric efficiency of the compressor is highest for R-22 and

    lowest for R-407C. The heating capacity is highest with R-22 followed by R-

    407C and R-407A. The variation of cooling capacity is highest with R22 and

    lowest with R-407A at all temperatures.Aprea and Greco (2003) reported that Performance evaluation of R22

    and R407C in a vapour compression plant with reciprocating compressor. The

    investigation has revealed that R22 performs better than R407C mainly

    because of a better compression process due to a number of factors, including

    the facts that the isoentropic and volumetric efficiencies of the semi-hermetic

    compressor are better than that of R407C.

    Calm and Domanski (2004) reported that R-410A and R-407C are the

    leading replacements for R-22 in unitary air conditioners and heat pump

    applications.

    Spatz and Motta (2004) made a thermodynamic analysis, comparison

    of heat transfer and pressure drop characteristics, system performance

    comparisons using a validated detailed system model, safety issues, and

  • 7/25/2019 Msc in Ref

    22/36

    22

    determination of the environmental impact of refrigerant selection. Three

    potential alternatives to the R-22 were studied: two HFCs (R-404A and R-

    410A) and one HC (R-290). He concluded that R-410A was shown to be

    an efficient refrigerant in this application due in large part to its thermal

    properties resulting in improved heat transfer and pressure drop

    characteristics .The R-290 systems efficiency was also quite good. Using the

    assumptions stated in this paper and in a similar system. The enhanced

    R404A system also shows favorable efficiency characteristics especially at

    average operating conditions.

    Thorough examinations of all the fluid properties of R-290 lead to the

    conclusion that systems employing this refrigerant would have comparable or

    slightly better efficiency (

  • 7/25/2019 Msc in Ref

    23/36

    23

    mode operation in order to improve heating capacity. For cooling mode

    operation, it is desirable to adjust the refrigerant composition to in order to

    obtain the highest COP and to reduce the energy consumption.

    The performance of an air to water vapor compression heat pump has

    been investigated experimentally. The main purpose of this study was to

    investigate the possibilities of using R134a as a working fluid to replace R-22

    for vapor compression heat pumps. Pure R-22, pure R134a and some binary

    mixtures of R-22/R134a were considered as working fluids by Karagoz

    (2004). His results indicated that the COP of pure R134a is higher than that

    pertaining to pure R-22.The mixture ratio has the greater effect on the COP

    values. Generally, minimum COP occurs at a zero mass ratio of R134a, and as

    the concentration of R134a increases, the COP increases until the mixture

    ratio of 50/50% R134a/R-22. The maximum COP occurs at a mixture ratio of

    around 50/50% R134a/R-22.The COP increases with increasing evaporator

    source inlet temperature for the pure refrigerants and refrigerant

    mixtures.R134a and zeotropic mixtures of R134a/R-22 can be a substitute forR-22.

    Szen et al. (2004) predicted the performance of the heat pump was

    using a fuzzy-logic controller under various working-conditions and mixing

    ratios of R12/R22 refrigerant mixtures, instead of requiring an expensive and

    time consuming experimental. Fuzzy-logics linguistic terms provide a

    feasible method for defining the performance of the heat pump. Input data for

    the fuzzy logic are mixing ratio, evaporator inlet temperature and condenser

    pressure. In the comparison of performance, results obtained via analytic

    equations and by means of the fuzzy-logic controller, the coefficient of

    performance (COP), and rational efficiency (RE) for all working situations

    differ by less than 1.5% and 1%, respectively. The statistical coefficient of

    multiple determinations (R2-value) equals to 0.9988 for both the COP and the

  • 7/25/2019 Msc in Ref

    24/36

    24

    RE. With these results, we believe that fuzzy logic can be used for the

    accurate prediction of the COP and the RE of the heat pump.

    Cabello et al. (2004) reported an experimental evaluation of a vapour

    compression plant performance using R-134a, R-407C and R-22 as working

    fluids. The conclusion was the mass flow rate evolution becomes the most

    important influence on the refrigerating capacity behavior. With reference to

    the electrical power consumption, the refrigeration plant consumption

    working with R22 tends to decrease more slowly with increasing compression

    ratios than using the other working fluids. This fact is transferred to the COP,

    obtaining a smaller value of the COP using R22 than using R407C for high

    compression ratios.

    Aprea et al. (2004) reported An analysis of the performances of a

    vapour compression plant working both as a water chiller and a heat pump

    using R22 and R417A.The experimental verified experimentally that the COP

    and the exergetic efficiency of the plant, when the R22 is used as working

    fluid, are higher than the COP and the exergetic efficiency obtainedconsidering as working fluid the R417A, both when the plant operates as a

    heat pump and as a water chiller. In particular, the efficiency defects of

    R417A are always higher than the defects of R22 of about 6% related to the

    valve and the heat exchangers, and of about 10% referring to the compressor.

    Moreover, it has been experimentally verified that the COP of R22 is higher

    than that of R417A also of about 18% related to the water chiller system and

    of about 15% referring to the heat pump.

    Because of the potential variation of the fluid composition, lots of

    designers are concerned by the use of zeotropic refrigerant mixtures in

    refrigeration and air-conditioning systems. Idrissi et al. (2005), reported a

    local simulation model of a water-to-water heat pump is proposed by adopting

    a modular approach. Thus, the overall model consists of the association of an

  • 7/25/2019 Msc in Ref

    25/36

    25

    elementary model for each basic component, namely the compressor,

    condenser, evaporator and receiver. Implemented with a ternary zeotropic

    blend R-134a/R-125/R-32. The numerical results show that, compared to the

    nominal composition of R-407C (R- 134a/R-125/R-32; 52/25/23%), the

    circulating composition in the machine is low in the less volatile component

    R-134a (-3% absolute variation) and rich in the most volatile component R-32

    (+3% absolute). In the regions of condensation beginning and evaporation

    end, the local composition is noticeably different from both the circulating

    and nominal compositions. In these regions, the local mass composition of R-

    134a increases (+4/+10% absolute) whereas the local mass composition of R-

    125 and R-32 are in deficit (-3/-6% absolute).

    Devotta et al. (2005) reported that retrofitting R22 systems with

    R407C is a better option to extend the life of R22 systems even though the

    performance is slightly lower.

    Han et al. (2007) investigated with ternary mixture composed of

    R32/R125/R161 as an alternative to R407C. It has been reported that,pressure ratio, power consumption are found to be lower than R407C. The

    above mixture has high refrigeration capacity and coefficient of performance

    compared to R407C. The discharge temperature also was found to be slightly

    higher than R407C.

    The exergetic method of analysis is a useful tool in explaining the various

    energy flows in a process and in the final run helps to reduce losses occurring

    in the system. Arora et al. (2008) explained the method of carrying out an

    exegetic analysis of an actual vapour compression refrigeration (VCR) cycle.

    A computational model has been developed for computing coefficient of

    performance (COP), exergy destruction, exergetic efficiency and efficiency

    defects for R502, R404A and R507A. The present investigation has been

    done for evaporator and condenser temperatures in the range of -50 0C to 0C

  • 7/25/2019 Msc in Ref

    26/36

    26

    and 40 0C to 550C, respectively. The results indicate that R507A is a better

    substitute to R502 than R404A. The efficiency defect in condenser is highest,

    and lowest in liquid vapour heat exchanger for the refrigerants considered.

    Assaf et al. (2011) presented Modelica-based modelling and simulation

    of dry-expansion shell-and-tube evaporators working with alternative

    refrigerant mixtures. The model is experimentally validated using a standard

    shell-and-tube evaporator working with HFC-134a.he It is concluded that the

    effect of the temperature profile of any refrigerant mixture can be substantial

    on the relative performance of a particular heat exchanger configuration

    compared to counter-flow configuration.

    An experimental research was carried out to investigate the

    performance of R-22 and its ozone-friendly alternative refrigerants (R404A

    and R507) in a window air-conditioner by Bolaji (2011). He concluded that

    R-22 had the lowest pressure ratio and discharge temperature closely followed

    by R507. The average discharge temperature obtained using R507 and R404A

    were 4.2% and 15.3% higher than that of R-22, respectively. The lowestcompressor power and energy consumption were obtained from R507

    retrofitted system. Also, the highest refrigeration capacity and coefficient of

    performance (COP) were obtained using R507 in the system. The average

    refrigeration capacities of R507 and R404A were 4.7% higher and 8.4%

    lower than that of R-22, respectively, while the average COP of R507

    increased by 10.6% and that of R404A reduced by 16.0% with respect to that

    of R-22. Generally, the investigation has revealed that R507 can be used

    successfully as a retrofitting refrigerant in existing window air-conditioners

    originally designed to use R-22 in the event of HCFC phased out.

  • 7/25/2019 Msc in Ref

    27/36

    27

    2.6.4 HFC/HC mixtures as alternative

    Kim et al. (1994) experimented with two azeotropic mixtures of

    R134a/R290 (45/55 by mass percentage) and R134a/R600a (80:20 mass

    percentage). The performance characteristics of the azeotropes are compared

    with that of R12, R290, R134a and R22. The cooling and heating capacity of

    R290/R134a was greater than that of R22 and COP was found to be lower

    than that of R22 and R290. The COP of the R134a/600a mixture is higher

    than R12 and R134a. The cooling capacity is also found to be higher than

    R134a and R600a. The discharge temperature of the azeotropic mixtures

    studied are found be lower than that of R22 and R12.

    Maczek et al. (1997) investigated with ternary zeotropic mixture

    composed of R744/R32/R134a as an alternative for R22 in a heat pump. It has

    been reported that above mixture with mass fraction (7:31:62) showed an

    increase in capacity and COP by 18.6% and 2.5% respectively. This mixture

    was found to be promising alternative only for low temperature heat pump

    applications because of its excessive condensing temperature.Payne et al. (1998) compared the performance of R22, R290 and the

    flammable zeotropic mixtures R32/R290 and R32/R152a in a residential

    water-to-water heat pump. In cooling mode at constant capacity R32/ R290

    (50:50) mixture produced 8% higher COP than R22. In heating mode, the

    COP of R32/R290 was 13% lower and the COP of R290 was 1% higher than

    that of R22 in the water to air system. R290 shows the best performance

    compared to the other fluids due to its zero environmental impacts, thermo

    physical properties and oil solubility.

    Yang et al. (1999) investigated with HFC/HC ternary mixtures

    (R32/R125/R152a and R32/R125/R290) and binary mixtures (R125/R290 and

    R32/ R290) as alternatives to R22. Their experimental investigations reported

  • 7/25/2019 Msc in Ref

    28/36

    28

    that performance of R32/R125/R152a mixture was found to be close to R22

    over wide range of operating conditions and also have better efficiency.

    Aprea et al. (2004) made performance study of vapor compression

    plant working as water chiller and heat pump using R22 and its substitute

    R417A. It has been reported that R417A does not require a change of

    lubricant and it is quite compatible with mineral oil, alkyl-benzene and ester

    oils. The compression ratio of R417A is higher than R22 in both the cases.

    The COP of the R22 is higher than that of R417A of about 18% in the case of

    water chiller and 15% in the case of heat pump applications. The discharge

    temperature of R417A was also found to be lower than R22 in both chiller

    and heat pump applications. It is observed that the exergy destroyed in the

    components of the plant working with R417A as working fluid are greater

    than the exergy destroyed while using R22 on an average of about 14%.

    Experimental investigation with R407C with 10% and 20% HC blend

    composed of 45% of R290 and 55% of R600a (by weight) as an alternative in

    window air conditioners without changing the mineral oil.Jabaraj et al. (2006) it has been reported that 19% increase in

    condenser tube length is required to suit the mixtures as compared to R22.

    The experimental results reported that R407C with 20% HC blend was found

    to be the promising alternative to R22 in window air conditioners without

    changing the mineral oil.

    Calm (2006) has investigated 28 different pure refrigerants for chiller

    applications. The results reported that R123 remains the best current option to

    reduce the substantial global warming contributions from chiller and air

    conditioning applications. R123 has low ODP and very low GWP, very short

    atmospheric lifetime and the highest energy efficiency of all the current

    options.

  • 7/25/2019 Msc in Ref

    29/36

    29

    A review reported by Mohanraj et al. (2009).about the various

    experimental and theoretical studies carried out around the globe with

    environment friendly alternatives such as hydrocarbons (HC),

    hydroflurocarbons (HFC) and their mixtures, which are going to be the

    promising long-term alternatives. In addition, the technical difficulties of

    mixed refrigerants and future challenges of the alternatives are discussed. The

    problems pertaining to the usage of environment friendly refrigerants are also

    analyzed. he concluded that the Researchers from various parts of the world

    reported the experimental and theoretical results with environment friendly

    alternatives. Based on the results regarding the performance, it can be

    understood that HC mixtures and R152a are found to be better substitutes for

    R12 and R134a in domestic refrigeration sector. R290, R1270, R290/R152a,

    R744 and HC/HFC mixtures are found to be the best long-term alternatives

    for R-22 in air conditioning and heat pump applications. R123 was found to

    be an attractive alternative to R11, R12 and R-22 in chiller applications.

    R152a and HC mixtures are found to be a best option for automobile airconditioners. The use of low environmental impact refrigerants like the

    natural refrigerants (R290, R1270 and R744) and HC/HFC refrigerants in air

    conditioning and heat pump applications play a vital role in the developing

    countries India for reducing the environmental impact of halogenated

    refrigerants.

    Torrella (2010) presented an on-site experimental study of the R-22

    replacement by two possible substitutes, the HFC-417A and the HFC-422D,

    in a water chiller in which the energy performance was evaluated. This chiller

    is part of the centralized HVAC system of a lecture room building at the

    Jaume I University of Castellon, Spain. This communication compares and

    analyses main operation parameters of the chiller when operating with each

    refrigerant in real conditions. From the experimental measurements, it was

  • 7/25/2019 Msc in Ref

    30/36

    30

    observed that the evaporating and condensing temperatures were different

    when working with each refrigerant. Accordingly, this difference in pressures

    and compression ratios must be taken into account for more accurate

    comparisons. It was observed a drop-in cooling capacity and in compressor

    power consumption with regard to the operation with R-22 when the chiller

    worked with any of the substitute refrigerants. That fact is also to be

    considered in the R-22 substitution process.

    An experimental investigation of the global environmental impact of

    the R-22 retrofits with R422D by Aprea and Maiorino (2011).They

    concluded that the storage investigation have demonstrated that for each test

    the R-22 retrofit with R422D leads to an increase of the energy consumption

    up to 28.9%.Since the GWP of R422D is much higher than that of R-22 and

    even if the charge of R422D is 8% lower than that of R-22, the direct effect of

    the R422D is 42% higher than that of R-22.As a consequence of the retrofit

    with R422D, the plant investigated has shown an increase of TEWI up to

    36.8%.The performance investigation highlighted that the operation withR422D is less efficient than that with R-22. In particular, the difference

    between the COP for R-22 and that for R422D is, on average, 20%, and it

    grows with the raising of the air temperature of cold reservoir.R-22 retrofit

    with R422D leads to an increase of the condensing Pressure, which indicates

    that the heat exchange surface of the condenser is insufficient to reject the

    thermal power, worsening the efficiency. To improve the energy performance

    and then to reduce the indirect effect, we proposed two ways: increasing the

    heat exchange surface and adoption of electronic expansion valves. Based on

    theoretical considerations it is possible to obtain a 20% reduction of energy

    consumption.

    Experimental evaluation of HCFC-22 replacement by the drop-in fluids

    HFC-422A and HFC-417B for low temperature refrigeration applications

  • 7/25/2019 Msc in Ref

    31/36

    31

    carried by Llopis et al (2011). A double stage vapour compression plant with

    sub cooler, in an evaporating temperature range from -31 and 17oC and in a

    condensing temperature range from 30 and 48oC was used. The experimental

    results showed that when using any of the drop-in fluids there is an important

    increment on the refrigerant mass flow rate through the plants, which in some

    cases would need to readjust the expansion valves. However, with the

    substitutes there is an important reduction of the specific refrigerating effect,

    which tends to reduce the cooling capacity. Regarding the energy

    performance with the R-22 drop-in fluids it has been measured a reduction in

    the capacity in the plant, being this reduction higher than expected from a

    theoretical analysis. Furthermore, regarding the COP in medium and low

    evaporating temperatures, the reduction with the R-22 substitutes is important

    and higher to the values predicted with a theoretical analysis.

    La Rocca and Panno (2011). presented an experimental analysis

    comparing the performance of a vapour compression refrigerating unit

    operating with R-22, and its performance in comparison to a new HFC fluid,R-417A, R-422A and R-422D. Results revealed that R-22 was energetically

    more efficient than the other fluids. R-417A, R-422A and R-422D are

    characterized by ODP = 0 and in the existing installations they can easily

    replace R-22 without having to change the lubricant, or renewing the

    refrigeration circuits and the accessories. This makes replacement a

    particularly easy operation that can be carried out without any special

    technical equipment and at a very low cost. Change in energy performance as

    a result of a R-422D retrofit.

    An experimental analysis for a vapor compression refrigeration plant

    for a walk-in cooler was studied by Aprea et al. (2011). The results

    demonstrated that the cooling capacity for R422D was lower than for R-22,

    while the electrical power absorbed with R422D was higher than that with

  • 7/25/2019 Msc in Ref

    32/36

    32

    R-22. As consequence, the COP of R422D was lower than that of R-22.

    Furthermore, technical proposals are introduced with the aim of retrofitted

    with R422D.

    Llopis et al. (2012) R-22 replacement with two drop-in fluids (R-

    422A, R-417B) and a retrofit refrigerant (R-404A) in a two-stage refrigeration

    plant for low temperature. The experimental measurements showed that when

    using any of the substitute fluids there is an important incremental difference

    in the refrigerant mass flow rate through the plant, which in some cases would

    make it necessary to readjust the expansion valves of the system. An

    important reduction in the capacity has been measured when using the drop-in

    fluids R4-22A and R-417B, whereas, for the retrofit refrigerant R-404A the

    capacity is enhanced to an important degree. Regarding the COP of the plant,

    the reduction in COP with any of the tested fluids is important and is greater

    than the values predicted by a theoretical analysis.

  • 7/25/2019 Msc in Ref

    33/36

    33

    2.8 Physical Environmental and Safety Characteristics of R-22 , R-438A and

    R-422A

    Table (2-2) shows composition and main thermodynamic properties of

    R-22 and its substitutes fluids considered in this work R-438A and R-422A

    while their p-h diagrams are shown in Fig. (2.6-a) and Fig. (2.6-b),

    respectively. The pressure levels of R-43a and R-422A are higher than

    corresponding pressures in R-22 higher and medium temperatures. Hence,

    R-438A andR-4 22A are better to replace R-22 for air conditioning

    applications than lower temperature applications. Furthermore, R-438A and

    R-422A have a temperature glide, which makes them unsuitable for flooded

    evaporators. Another important difference is that there is an important

    reduction in the latent heat of phase change (h fg) as compared to R22, which

    will tend to reduce the capacity provided by the plants.

  • 7/25/2019 Msc in Ref

    34/36

    34

    Table (2.2): Physical Environmental and Safety Characteristics of R-22 , R-

    438A and R-422A (Elgendy et al.,2014)

    R-422AR-438AR-22

    85.1% R-1258.5% R-322CHCIFComposition (%wt)

    11.5% R-

    134a

    45% R-125

    3.4% R-60044.2% R-134a

    1.7% R-600

    0.6% R-610a

    113.699.186.47Molecular weight (g mol-1)

    -44.03-42.33-40.81Normal boiling point (C)71.7385.2796.14Critical temperature (C)

    37.464349.9Critical pressure (bar)

    2.466.190Glidea (C)

    167.44203.7226.81hfg (T=-30C)

    140.6176.9200.9hfg (T = 5C)

    104.8140.3166.60hfg (T = 40C)

    0.08620.1430.135g (T=-30C) (m3 kg-1)

    0.02480.03860.0403g (T=5C) (m3 kg-1)

    000.05ODP

    310022651810GWP (100 years)

    A1A1A1ASHRAE Safety group

  • 7/25/2019 Msc in Ref

    35/36

    35

    Fig. (2.6-a) Pressure -enthalpy diagram of the R-22 and its drop-in R-438A.

    Fig. (2.6-b) Pressure -enthalpy diagram of the R-22 and its drop-in R-422A.

    100 200 300 400 500

    Specific enthalby (kJ/kg)

    1

    10

    100

    Pressure(bar)

    R-22

    R-438A

    T=40C

    T=-25C

    T=5C

  • 7/25/2019 Msc in Ref

    36/36

    2.8 Concluding Remarks

    The literature survey revealed that although many investigations were

    carried out on airconditioner working with R22 alternatives, Both R-410A

    and cant be consider as a drop-in and a little work was conducted on an air

    conditioner running with R-422A and no investigation was carried for R-

    438A to evaluate its performance at various operating conditions. Moreover,

    previous investigators did not explore its effect even for water to water chiller

    using R-422A and R-438A. However, there is a lack of information on the

    performance characteristics of water to water chiller using R-422A and R-

    438A.Therefore, the present work aimed at evaluating the performance

    characteristics of a vapor compression water chiller for various operating

    conditions. A comparison, based on energy points of view, is considered

    among R-22 alternatives as working fluids in water chiller. An experimental

    apparatus was designed, constructed and equipped with necessary

    instrumentation. R-22, R-422A or R-438A is used as a primary working fluid

    and water is adopted as the secondary heat transfer fluid at both the condenserand evaporator. Influences of evaporator water inlet temperature, condenser

    water inlet temperature and condenser water flow rate on the performance

    characteristics of the system is experimentally investigated.