mrd1-t transformer differential protection system mrd - transformer differential protection relay 9...
TRANSCRIPT
MRD1-T - Transformer Differential Protection System
2 TB MRD1-T 10.01 E
Contents
1 Preface and Application
2 Features and Benefits
3 Design3.1 Relay front3.1.1 Display3.1.2 LEDs3.1.3 Push-buttons3.1.4 Parameter interface RS2323.2 Master module3.2.1 Interface RS4853.2.2 CAN-Bus (optionally)3.2.3 Function inputs and signal inputs
(optionally)3.3 Basic module and additional module3.3.1 Basic module NT 6I (MRD1-G,
MRD1-T2 and MRD1-T3)3.3.2 Additional module 3I (MRD1 T3)
4 Working principle4.1 Protective functions4.1.1 Transformer differential protection4.2 Analogue measured value detection4.2.1 Current measuring4.3 Digital signal processor4.4 Digital main processor4.5 Block diagram4.6 General functions4.6.1 Event-Recorder4.6.2 Fault-Recorder4.6.3 Self-test relay4.6.4 Self-test4.6.5 Output relay settings4.6.6 Parametrizing blocking
5 Operation5.1 General5.1.1 Data organization5.1.2 Parameter sets5.1.3 Key function5.1.4 LEDs5.1.5 VIEW mode / EDIT mode5.1.6 OFFLINE-TEST mode5.1.7 Reset (DEVICE RESET)5.1.8 Enter password5.1.9 Password forgotten
5.2 SYSTEM settings5.2.1 Selection5.2.2 Overview5.2.3 Time / Date5.2.4 Password change5.3 PARAMETER-pages5.3.1 Selection5.3.2 Overview5.3.3 Transformer ratings5.3.4 Protection parameters5.3.5 Relay-settings5.3.6 Setting of logic functions5.3.7 Blocking Setting5.3.8 Validity check5.4 DATA pages5.4.1 Selection5.4.2 Overview5.4.3 Measured and calculated data5.4.4 FAULT Recorder5.4.5 EVENT-Recorder5.4.6 Statistic data5.5 TEST-routines page (Self-test)5.5.1 Page selection5.5.2 Overview5.6 Parameter programming help
6 Relay Tests
7 Commissioning7.1 Check list7.2 C.T. connection
8 Technical Data8.1 MRD - Transformer Differential
Protection Relay
9 Tables / Connection diagrams9.1 Possible event messages9.2 View
10 Type code
This technical manual is valid for software versionV01-1.03.
TB MRD1-T 10.01 E 3
1 Preface and Application
MRD1 is a modular system to protect electrical appa-ratus and it is used for complex applications in theenergy distribution, primarily designed for transformer,generator, motor or line protection; additionally it canbe integrated into automation systems. Due to itsmodular design, the MRD1 can be adapted to indi-vidual applications without problem, with all imple-mented functions remaining combined in one singledevice. All vacant rack places in the basic unit can op-tionally be used for modules according to require-ments. The modules provide the necessary measuringinputs e.g. for two-winding or three-winding transform-ers as well as increase the number of output relays ordigital inputs according to requirements.
The high-performance digital technique of data calcu-lation makes complex mathematical algorithm formeasured value processing possible for the MRD1 aswell as utilization of the trip decision resulting from theindividual protection functions. The MRD1 software isalso of modular structure. Each protection function is al-located to a special program segment and so it ispossible to subsequently add further functions.
All essential parameters, measuring data or valuescalculated from these can be called off and are shownlocally on the display. The MRD1 is equipped with anEvent Recorder which stores all system signals, protec-tion activations or trip events. When trips occur a FaultRecorder records all fault data mesaured at the instantof the trip. Data of both recorders is provided with atime stamp and can be called off either at the displayor interface.
At present the following versions of MRD1 are avail-able :
• MRD1-T2 Transformer differential protection fortwo-winding transformers
• MRD1-T3 Transformer differential protection forthree-winding transformers
• MRD1-G Differential protection for generators andmotors
4 TB MRD1-T 10.01 E
2 Features and Benefits
Basic Unit
Standard equipment• Modular design
with automatic short circuiting C.T.-inputs• Signal and data processing in a separate digital
signal processor (32 samples per cycle)• Digital filtering of measured quantities• Three possibilities of parameter setting and data
calling:1) keyboard and display2) RS232 interface at the front (lap top)3) RS485 interface for integration into control systems at the rear
• Safety interlocking preventing parameter setting viadifferent ways at the same time
• extensive internal plausibility check of modified pa-rameters
• Event Recorder for recording system messages• Fault Recorder for recording measured fault data• Four programmable independent parameter sets• Non-volatile memory for parameter sets, events and
fault data• Indication of measured operational values and re-
sulting quantities• Wide-ranging automatic self-tests• Small relay size• Indication of relay functions optically or via sepa-
rate self supervision relay• Three possibilities for relay resetting• All data interfaces galvanical isolated• Rated frequency selectable: 50 Hz/60 Hz• Parameter setting protected by password
Functions which can be programmed by the user :• Protection and system parameters• Latched position or minimal signal duration for
each of the output relays
Optional equipment• CAN Bus• FO connection (fibre optic) for RS485 interface• Addition of further protection functions after installa-
tion of additional software modules
Transformer differential protection• Stabilization against transformer inrush and CT
saturation• Adaption to vector groups and transformation ratio
by means of software without additional interpos-ing CTs
• Compensation of tap changer position• Waveform recognition technique with a special
Fourier algorithm (inrush element)• No complete blocking of differential element but
only reduced sensivity• Independent High Set differential element for heavy
faults
TB MRD1-T 10.01 E 5
3 Design
This chapter informs briefly about operation elementsand indication elements of the MRD1. Name and po-sition of the individual modules are also described. Inchapter 5 operating of the relay and type specificfunctions are explained in more detail.
!NoteNoteNoteNoteFront view and rear view illustrations of the MRD1 aswell as connection diagrams can be found at the endof the manual.
3.1 Relay front
Display in Home Position
3.1.1 Display
The MRD1 is provided with a 16-digit, double-lineliquid crystal display (LCD), which is of alphanumericaldesign for an easy dialog. The figure above shows thebasic status of the display. Dependent on the mode se-lected, the following data can be shown on the dis-play:
• Date / Time / Relay type (Home Position)• Measured operational data• Measured fault data• System parameters and protection parameters• System signals and fault signals
3.1.2 LEDs
Additionally to the display there are max. 30 LEDs atthe front, indicating each of the operational status inthe MRD1. All LEDs are two-coloured (red/green) andarranged in two groups:
a) System and relay status indicationsThe 15 system indications are arranged underneaththe alphanumerical display. They are allocated to acertain function and show:
• Operational voltage available• Trip• OFFLINE TEST mode active• Edit mode active• Displayed parameter is modified but has not been
stored yet• Switch status of the 5 (optionally 10) output relays• Display of the relay function (self-test)
b) Status display of the 15 digital inputs (if provided)These 15 indications are shown at the left of the dis-play informing about the status of the digital inputs.
3.1.3 Push-buttons
All necessary MRD1 adjustments and inquiries can becarried out from the front of the relay by pressing therespective push-button (9 in total). Individual function ofthese push-buttons is explained in chapter Operating.
3.1.4 Parameter interface RS232
At the left of the relay front there is a 9-pole, D-SUBplug-and-socket connector for temporary lap-top con-nection. At this connection a serial interface RS-232 isprovided. A standard IBMTM compatible PC or port-able notebook can be connected to this PC interface.To connected MRD1 and PC a 1:1 modem-cable with9-pole plug-and-socket is used. By using SEG softwareHTLSOFT 3, which is WindowsTM compatible, MRD1parameters can comfortably be set. Additionally allmeasured operational and fault data can be read outof the relay integrated non-volatile memories.
6 TB MRD1-T 10.01 E
3.2 Master module
The master module is fitted right in the middle and con-tains componentries for data processing, the mainprocessor and the following connections:
3.2.1 Interface RS485
Interface RS485 at the rear of the relay is a permanentconnection between the MRD1 and the host computer.This interface operates at a constant transmission ratioof 9600 Baud if |SEG interface recorder "RS485pro"is used. Via RS485 interface all measured operationaland fault data as well as operational status indicationscan be read out - identical to RS232 interface. Remotesetting of parameters is also possible from the controlstation. The 8-pole plug-and-socket connector containsall necessary connections for this interface.
3.2.2 CAN-Bus (optionally)
This data interface is used for integrating the MRD1into special automation systems and for specific func-tion additions (e.g. temperature measuring module,graphic-display module). For the CAN Bus interfacestwo 9-pole D-SUB plug-and-socket connectors areused.
3.2.3 Function inputs and signal inputs(optionally)
These 15 digital inputs (contacts 1-15) are combinedon the 16-pole plug-and-socket connector. The six-teenth contact is the common return wire. Any incom-ing information
a) can direct be assigned to selectable output relays.This application method enables recording of the con-tact status (open or closed) of external protection de-vices (e.g. Buchholz relay at transformers)
b) can logically be interlinked with MRD1 internal pro-tection functions. The logical interlinking result can thanbe assigned to output relays.
An input can be considered active when a voltagequantity within the permissible high range (see Tecni-cal Data) is connected to the input contact and thecommon return wire. If the voltage is lower, the input isclassed as being inactive. Specific function of the indi-vidual inputs can be defined during programming (seechapter 6). Digital inputs are galvanical isolated fromthe relay electronics.
TB MRD1-T 10.01 E 7
3.3 Basic module and additional module
Plug-in units 1 and 3 are intended for individual appli-cations and at our works they are equipped with mod-ules for measuring value detection in compliance withthe relay function. (see folding page)
!Important Note
The MRD1 must only be dismantled or opened by authorized staff .Removal of live modules entail severe danger for the person(s) involved because there can no sufficient protectionagainst accidental contact be guaranteed as soon as the relay has been opened. Furthermore there is the risk ofthe modules being damaged by electrostatic discharge (ESD/EGB) when handled improperly.
Identical modules must not be exchanged between different MRD1 basic versions....
Calibration of every MRD1 is done at work with regard to the specific features of that relay. A random changeof modules would lead to unreliable operation of the relay because the compatibility of the relay componentsamong each other would be in disorder and could not be guaranteed any longer.Any modification jobs on the MRD1, for instance, exchange of modules or software additions, are only allowedto be done at our works or by authorized agents.
3.3.1 Basic module NT 6I (MRD1-G,MRD1-T2 and MRD1-T3)
For generator, motor and transformer differential pro-tection, module NT-61 is plugged into the first space.
Measuring inputsThe module consists of six current measuring channelswhich are used for measuring the three conductor cur-rents of each winding. The CT start point must beformed outside the relay since all 12 CT connectionsare wired separately on terminals. In addition to othermeasuring or protection devices the MRD1 can belooped in to existing CT lines, assumed the CT beingable to carry the total burden.
Apart from further connections for voltage supply of therelay, the module is also provided with a digital inputfor remote resetting as well as connection facilities forthe five output relays. Four of these are free to be usedacc. to requirement, the fifth is assigned for Selftest Re-lay.
Input RESETIf a voltage is applied to terminals of the RESET input(C8-D8), the MRD1 is reset to its basic status. By thisprocedure possible alarms and trip signals are can-celled.The voltage applied for resetting must be within thepermissible high-range (see technical data), although itmust not necessarily be identical with the latter.
The input is galvanical isolated from the relay electron-ics. Contact D8 is also the neutral or minus for theblocking input.
Blocking InputIf a voltage is applied to the terminals of the blockinginput (D8-E8), all protection functions assigned to theoutput relays are blocked. Terminal D8 is also the neu-tral or minus for the reset input.
Alarm relaysPotential free outputs of the five alarm relays providedare at terminals C, D and E, series 1 to 7. Exact allo-cation can be taken from the connection diagram. Re-lay 5 is permanently assigned to Selftest Relay. Func-tion allocation of the remaining relays is free and canbe defined when programming (see chapter 5). Twoof these four relays are provided with two changeovercontacts each and the other two with one changeovercontact each.
3.3.2 Additional module 3I (MRD1 T3)
Module 3I is used for three-winding transformers andapplied to rack place 3. By this module the number ofmeasuring channels is increased by three currents forthe tertiary winding of the transformer and it providesalso five additional output relays.
8 TB MRD1-T 10.01 E
4 Working principle
In this chapter the individual functions and workingprinciple of the MRD1 are described.
4.1 Protective functions
4.1.1 Transformer differential protection
Term Explanation
ID Bias current This is the current flowing from the input side into the object to be protected, hav-ing a respective output current available at the output side. This current is repre-senting the normal load and the load at external faults.
Id Differential current The current resulting from the difference of incoming and outgoing conductor cur-rents when these were converted at one transformer side.In other words: The differential current is the component at the transformer inputcurrent which has no related output current.
Ia Pickup current If the differential current exceeds the pickup current, the relay trips.
Fault current due tooperational condi-tions
This kind of fault current is the component of the measured differential currentwhich, however, is not caused by a fault of the object to be protected but is ofsystematic nature
Stabilization Under this heading all measures are compiled which stabilize the differential relayagainst nuisance tripping. Stabilizing always means the pickup current is raisedand by this the differential relay becomes more intensitive, but is never completelyblocked.
IS Stabilizing current This current develops from the bias current and represents the extent of stabilizingmeasures necessary as result of the fundamental analysis. Parameters of the stabi-lizing characteristic can be set.
m Harmonic stabilizingfactor
This factor, derived from the analysis of the harmonic frequency, is apart from ISthe second stabilizing factor and in case of rush and saturation by following aspecial characteristic makes the differential relay stable against tripping errors.
d[Id] Characteristic Offset The characteristic curve is raised up by the value d[Id] immediately after a har-monic stabilization factor “m” is measured to be greater than zero. This is to givea basic stabilization after detection of inrush or ct-saturation during external faultby means of harmonic measurement.
Pickup characteristic In this characteristic both stabilizing quantities (stabilizing current and stabilizingfactor) are brought together and from this the pickup current is defined necessaryfor the operational condition of the object to be protected at that instant.
Table 1: Term definitions
TB MRD1-T 10.01 E 9
General idealized view
Differential protection is a strict selective object protec-tion and is based on the current measuring principle atthe input and output side of the object being pro-tected. Dependent on the earthing method used, theneutral can also be included in measuring and bal-ance.The area between input and output CTs of the objectis classed as protection zone supervised by theMRD1. Included in the protection zone are also CTsand CT connection wire to the relay.
protected area
transformer
MRD
I 1 I 2GRID GRID
Fig. 1: Definition of protection zone
The relay checks constantly if the incoming currents ofthe input side are met by respective outgoing currentsat the output side. If the balance of the conductor cur-rents shows a difference, this may suggest a faultwithin the protection zone. Especially where trans-formers are concerned it is necessary that all conductorcurrents are converted to one reference transformerside according to their transformation voltage ratioand to their vector group so that quantities and phasescan be compared.
To distinguish between faults occuring within (inter-nally) or outside (externally) of the protection zone isthe main purpose of the differential protection becauseat internal faults the differential protection relay musttrip, but not so at external faults.
Examples:
External fault
During a short circuit occuring at the right grid, thecomplete short circuit current flows through the trans-former. The difference between incoming and outgo-ing currents of all transformer terminals is small (in idealcases = zero) I1-I2 = 0. The differential protection relaydoes not trip. (Switching off in such cases probably tobe realized by an overcurrent relay).
protected area
transformer
MRD
I 1 I 2
short circuit current
GRID GRID
Fig. 2: External fault
Internal fault
When an internal fault occurs the current balance isdifferent. Dependent on the kind of fault a deficit in thetotal of incoming currents can be observed. A windingshort circuit, for instance, can be fed from both sides,even if with different intensity. But this short circuit doesnot go through the transformer, it is fed from both gridsinto the transformer. So therefore the current balanceshows a difference.
protected area
transformer
MRD
I 1 I 2
short circuit current
GRID GRID
Fig. 3: Internal fault (example of a short circuit fed fromtwo sides)
Due to the chosen direction of the reference arrow,current I2 flows here in negative direction.
The differential relays detects a current difference of I1-I2 = Id and trips when Id has exceeded the set thresh-old.
10 TB MRD1-T 10.01 E
Stabilizing
At first approximation this idealized view applies tostationary states only. In reality other effects, especiallydynamic processes, may cause the established currentdifference to rise, even if there is no internal fault. Insuch cases a simple static differential relay would mis-takenly trip and to prevent this stabilizing measureshave to be taken. Possible sources of measuring errorsare systematic and can be duly taken into account.Especial measures for detecting switching actions (in-rush), CT saturation or to counteract errors caused bytransformer tap changer position switches are here ref-ered to.
Stabilizing the MRD1 means always an action tomake the relay more insensitive. By the MRD1 two in-dependent stabilizing quantities are calculated fromthe fundamental oscillation and harmonic analysis (seefollowing paragraphs).
Fundamental analysis
Distortion factors for differential current measuring are:• Measuring errors of angle and value of the CTs
used• Poor adjustment of rated CT data to rated trans-
former data• Effects caused by no-load currents• Adverse effects caused by tap changer position
By these factors a fault current is caused which mainlydepends on the biasing current. This fault current is be-ing measured as a differential current, although atransformer fault must not necessarily have occured.When the pickup current is set at a very sensitivevalue, each of these static factors can cause unin-tended trippings. With increasing bias current thepickup current has to be corrected upwardly.The following pickup characteristic (exact characteris-tic) gives an detailed study of the individual fault fac-tors and the resulting fault current. In fig. 4 the ex-pected fault current versus tripping characteristic isshown.
If a real fault occurs, the measured differential currentexceeds the biasing current caused by operationalconditions. Therefore the pickup characteristic must ex-ceed the biasing current characteristic by the requiredsensitivity value. The exact course can be approxi-mated by a simplified characteristic consisting of twolinear sections (I and II). The higher the characteristicbegins, the higher the permissible differential current. Ifthe characteristic begins at a very low point this meansmaximum sensitivity. If the pickup characteristic is be-low the biasing characteristic, systematic effects cancause unintended trips.
Stabilisierungsstromstabilizing current Is / In
Differenzstromdifferential currentId / In
I
II
AUSLÖSUNGTRIP
KEINE AUSLÖSUNGNO TRIP
tatsächlicher Fehlerstromlinieexact fault characteristic
Angenäherte Kennlinieapproximated characteristic
Fig. 4: Typical pickup characteristic (without considering transient processes)
Calculation of the differential current and stabilizing current resulting from the fundamental oscillation of the inputand output currents (current of the negative and positive phase sequence system) produces a point on the charac-teristic. If this point is within the tripping range, the output relay picks up.
TB MRD1-T 10.01 E 11
Harmonic analysis
The analysis of harmonics allows detection of specialprocesses in the grid, which also distort ascertainteddifferential current values.
These factors are:• Inrushes• Overexcitation of the transformer by overvoltage or
underfrequency• CT saturation at very high current load caused by:
- severe faults (external short circuit at high load)- start-up phases of big motor-operated drives- magnetizing currents of unloaded transformers- faults within the zone to be protected (short circuits)
We will explain the harmonic oscillation analysis moredetailed by taking the example "CT saturation" :In unstabilized transformer differential protection sys-tems instabilities can arise which may have grave con-sequences because the CT core is saturated due totransient processes. In this state the CTs, arranged ateither side of the zone to be protected, do not portraythe "right" secondary current (when compared to theprimary side). Through this constallation the differentialprotection relay detects at the secondary side of theCTs a differential current Id' which does, however, notexist at the primary side and this may cause unin-tended tripping.
In fig. 5 core saturation due to short circuit current is il-lustrated.Short circuit currents often contain a DC component.The high primary current arising during this kind of faultgenerates a magnetic B induction, causing saturationof the iron core.
The iron core keeps this high induction until the primarycurrent has reached zero. During the time the core issaturated, the secondary current is not in compliancewith the primary current, but becomes zero. During thetime the core is not saturated, the CT induces a currentwhich does not represent the real current for the entirecycle duration, its effective value is far too low.
Fig. 5 Core saturation of a CTa) primary current with DC componentb) induction in the corec) secondary current
Different saturation of CTs belonging to one protectionzone generate differential current Id' causing some un-stabilized relay to trip.For the harmonic analysis the MRD1 exploits thesecond, fourth and fith harmonic.
Important Note.For perfect functioning of the rush stabilization system itis essential that the MRD-T is connected in the correctphase sequence, i.e. that there is a positive rotatingfield. Refer also to page 11.
12 TB MRD1-T 10.01 E
Trip characteristic
The MRD1 identifies such factors by using the har-monic analysis and calculates a second dynamic stabi-lizing quantity, i.e. stabilzing factor m. Harmonicanalysis makes also detection of an inrush and trans-former saturation caused by overvoltage possible andare added to the calculation of the stabilizing factor.The MRD1 ascertains stabilizing factor m for thepresent situation with the effect of further lifting thecomplete characteristic. Calculation of m is definedand cannot be adjusted.m and IS each stabilize the relay entirely separate fromeach other, but never have a complete blocking effect.Both stabilizing quantities together define the pickupvalue in the trip characteristic.
A basic stabilization is performed by the parameterd[Id]. For all cases m>0 (rush current, single sided ct-saturation and external faults) the characteristic curve israised up for the minimum amount of d(Id). Anotheradditional raising is performed for raising m (moreservere rush, more severe ct-saturation).
The additionally adjustable parameter Idiff high set(Idiff >>) is a high current differential element. This set-ting value is not subjected to stabilization and specifiesthe highest permissible differential current. This pa-rameter defines characteristic sector III.
Tripping procedure
The protection program permanently checks the meas-urements that the DSP (digital signal processor) deliv-ers. When the DSP gives a new differential current theprotection task checks whether it lies within the trippinglimits. If this is the case the MRD1 is internally ener-gized. Tripping occurs when the calculated differencecurrent is consecutively three times within the trippinglimits. To prevent the energized state from being resettoo quickly, a hysteresis of 75 % is programmed. Thismeans that a newly calculated difference current mustbe smaller than 75 % of the present characteristic tripvalue in order for the energized condition to be reset.The total tripping time of the Relay is below 35 ms.
0Stabilisierungstromstabilizing current Is / In
Differenzstromdifferential currentId / In
I
II
III
AUSLÖSUNGTRIP
KEINE AUSLÖSUNGNO TRIP
m
Idiff >>(Für interne Fehler)(for internal faults)
d[Id]
Fig. 6: Dynamic stabilized trip characteristic (pick-up value).
TB MRD1-T 10.01 E 13
4.2 Analogue measured value detection
4.2.1 Current measuring
For measuring the relevant currents there is a separatetransducer for each of the existing measured quantities.This transducer provides galvanical isolation to the re-lay electronics. Adjustment to transformer vector groupand to the main CT rated currents is realized via thesoftware. The input signal is transmitted by internal CTsup to 64 times rated current linear. To achieve an ut-most accuracy there are two current measuring ranges,changeover of which is automatically.Each channel has its own sample-and-hold circuit. Allchannels are scanned simultaneously.
4.3 Digital signal processor
The digital signal processor (DSP) in the MRD1 ismainly used for processing measured values by con-trolling and monitoring data entry from the differentmeasuring channels. In addition all input signals aredigitally Fourier filtered. Among other values this proc-essor calculates RMS values and analyzes harmonicsby processing sampled data and stores digitalizedsignal sequences to the memory. Apart from datamanagement and processing the DSP keeps perform-ing wide-ranging self-tests.
4.4 Digital main processor
The main processors is the highest control elementwithin the MRD1 and processes the actual protectionprogram which interprets data obtained by the DSPand so refers to the operational status of the object tobe protected and to the own device. Special protec-tion mechanism enable the MRD1 to detect problemsin the own hardware. All communication betweenMRD1 and the outside world is also controlled by themain processor. This does not only mean control of in-dications or handling of key inputs but also harmoniz-ing the different data interfaces as well as control ofoutput relays.
14 TB MRD1-T 10.01 E
4.5 Block diagram
∩∩∩∩
∩∩∩∩
RS485
serialports
display and keyboard
CTs
real timeclock
CANBus1
CANBus2
LWL
CAN-con-tro-ller
faultmemory
programmemory
3
3
3
∩∩∩∩
anal
ogue
mea
sure
men
ts
PCMmemory card
serial PC-interfaceRS232
signal-processor
mainprocessor
central module
extension module
base module
mai
n pr
oces
sor b
us
optional
communi-cation
parameter-memory
blockinginput
supply
5outputrelays
SOFTWARERelaymatrix
∩∩∩ ∩
### #
RESETinput
dual portedmemory
5outputrelays
TB MRD1-T 10.01 E 15
4.6 General functions
4.6.1 Event-Recorder
The MRD1 is provided with an event recorder for re-cording events in a chronological order and thenstores them on a non-volatile memory. Any data entryhas a time stamp so that time of the event can al-ways be traced back. Data can be called off eithervia keys and display or data interfaces.Important events, such as trippings, are not only re-corded in the memory but also shown on the display.Pure informative events are stored in the recorderonly and are not displayed.
More details on calling off events and further infor-mation on the event recorder can be found in chap-ter 5.
The system messages are listed in chapter 9.1.
4.6.2 Fault-Recorder
At each tripping of the relays, the fault recorder rec-ords all measured data and resulting quantities. Anytripping event is automatically numbered consecu-tively in the recorder. Additionally to the measureddata the following details are also stored: the causefor tripping, serial number of the incident as well asdate and time at the instant of tripping.
The MRD1 is able to record several incidents in aFIFO memory. The longest stored data is overwrittenwhen a new incident occurs. Complete data of alto-gether 10 incidents can always be called off.More information on storage capacity and calling offrecorder data via keyboard can be found in chapter 5.
4.6.3 Self-test relay
The self-test relay (relay 5) is energized during nor-mal operation of the MRD1 and deenergized in thefollowing events:
• failure of aux. voltage• failure of internal partial power supply• processor failure detected by the internal watch-
dog• detection of an internal fault by software routines• when protection function of the output relays is
decoupled in OFFLINE TEST mode• when the default parameterset was loaded and
the device automatically switched in OFFLINETEST mode
• During power on initialisation• self-test of the output relays is performed
16 TB MRD1-T 10.01 E
4.6.4 Self-test
By pressing the TEST key several menu guided spe-cial test routines can be started in the MRD1 for in-ternal test purposes. Some tests disable the trans-former protection. These tests are locked by pass-word.
The following tests and information can be per-formed/is available :
Test / Inquiry Description Passwordre-quested
Protectionfunction
Software version number Number of version and date of software are in-quired no remains active
LED-Test • all LEDs light-up red f. 2s• all LEDs light up green f.2s no remains active
Test of output relays Sequence in one-second interval:• self-test relay de-energizes• all other relays de-energize• all relays energize one after the other (with LED)• relays return to actual position• self-test relay energizes
yes inactive during thetest
Memory test Test of software and memory by checking the pro-gram check sum no remains active
TB MRD1-T 10.01 E 17
4.6.5 Output relay settings
Reset time of the output relays:
With the exception of the self-supvervision relay, allexisting output relays are assigned to the differentialcurrent element. It is possible to define a proper resettime for each individual relay. For this period - fromthe moment of tripping - the relay remains in tripcondition even if the cause for the tripping does nomore exist.
!Note:If the time for which the relay has been energizedexceeds the adjusted reset time, the relay will releaseinstantaneously after trip condition is canceld. This isparticularly important for relay tests (test of the resettime) where the test current is not switched off imme-diately with tripping.
TRIP conditionAuslösebedingung
Relay energizedRelais angezogen
RESET TIMEMindestkommandozeit
t
RESET TIMEMindestkommandozeit
1
0
1
0
Fig.: Reset time
If a relay is to remain self-holding after tripping, thereset time has to be set to „exit“. Setting as per cus-tomer’s requirements can be noted down in the „se-lection“ line.
RelayBasic equipment Option
1 2 3 4 5 6 7 8 9 10Function Idiff
Idiff >>Idiff
Idiff >>Idiff
Idiff >>Idiff
Idiff >> STIdiff
Idiff >>Idiff
Idiff >>Idiff
Idiff >>Idiff
Idiff >>Idiff
Idiff >>
Pre-adjustment(in s) 0,20 0,20 0,20 0,20 • 0,20 0,20 0,20 0,20 0,20
Custom•
Setting range: 0 -...1,00 s or exit (=latching- contact un-til a DEVICE RESET is performed)ST=Self-Test relay• = no selection
18 TB MRD1-T 10.01 E
4.6.6 Parametrizing blocking
Blocking of protective function
The MRD1 offers a configurable blocking function.When applying a voltage to terminals D8-E8 all protec-tive functions are blocked that are configured for block-ing. In case of active blocking the output relays don’tact, but the device shows the fictive trip by means ofTrip-LED.
A minimum hold time can be set for the blocking. Duringthis time, starting from the begin of external blocking, allprotective functions are blocked, also in case the exter-nal blocking may was released. In case of longer con-tinuous external blocking the blocking can be stoppedafter a maximum hold time tmax for enabling the relay totrip in case of ongoing faults.
wirksame Blockierzeiteffective block. time
ext. Block. Eingangext. blockage input
tmin
t
tmax
!Note:Repeated impulse at the blocking time within tmin restartthe hold times.
Assignment of functions to output relays
The MRD1 offers 5 output relays. Relay number 5 ispreassigned to the selftest function of the relay and isworking with zero-signal current principle. Output relays1 – 4, and 6 – 10 are open-circuit relays and can beassigned to internal logic functions.
TB MRD1-T 10.01 E 19
5 Operation
5.1 General
5.1.1 Data organization
Data and settings in the MRD1 are subdivided into 4groups and each of those are allocated to one menukey or key combination. Related parameters or measur-ing data of one group are combined on individualpages. General settings can be made on the SYSTEMparameter page. Test routines are also on separatepages.
EVENTRecorder
PARAMETER measurementsdata recorder
PARAMETERpage 3
parameter 3.1parameter 3.2parameter 3.3.........
...
PARAMETERpage 2
parameter 2.1parameter 2.2parameter 2.3.........
...
PARAMETERpage 1
parameter 1.1parameter 1.2parameter 1.3...
TEST-routines
TESTroutines
software versionrelays testLED testmemory test
4 parameter sets
SYSTEM-parameter
SYSTEMPARAMETER
clock settingserial port optionswork set selectionOFFLINE TEST m.change passwordrestore default rated frequency
FAULTRecorder
...
...
...
+
DATApage 1
measurement1.1measurement 2.2measurement 3.3...
Statistic Data
Fig. 5.1: Data organization
20 TB MRD1-T 10.01 E
5.1.2 Parameter sets
MRD1 has access to four independent parametersets. Each of these data sets comprises a completeparameter set which makes individual setting of theMRD1 possible. If required by the operational pro-cedure several different settings can be stored andthen called off when needed.Data of SYSTEM parameters (e.g. rated frequency,slave address, date, time etc.) are not filled in thefour parameter sets, they do always apply.
EDIT-memory
display / keyboardserial interface
parameter set1
parameter set2
parameter set3
parameter set4
protection-program
output relay
messagedisplay / LED
measurement switch open in Offline Test Mode
SYSTEM-parameter
transformer
Fig. 5.1.2: Parameter sets, principle
For processing the selected set is loaded into theEDIT memory (switch: Set to Edit). After parametershave been changed, the EDIT memory is completelyrestored in the parameter set memory. All changesare then jointly read-in.Another switch (Work Set) defines on which of thedata sets the protection program is based. Allswitches are adjusted via software.
OFFLINE TEST mode is specified in chapter 5.1.6.
TB MRD1-T 10.01 E 21
5.1.3 Key function
KeyFunction short actuated long actuated (2s)
a) from HOME POSITION: View active parameter set (VIEW mode)
b) leaf to next PARA page
from HOME POSITION:" select one of the four parameter sets to edit (EDIT-mode)
++++
#
from HOME POSITION:" select SYSTEM-parameter page •
a) from HOME POSITION: View DATA pagesb) leaf to next DATA page
•
select the selftest routines page•
scrolling up / downsingle step
scrolling up / downfast
a) " change value. single stepb) move cursor
" change value, fast
a) confirm selection (YES)b) toggle setting in EDIT mode (yes/no ; on/off)
finish working in EDIT mode, perform parameter plausi-bility check and save (if check passed) all modifications
a) reject selection (NO)b) cancel modificationc) clear message
a) From HOME POSITION DEVICE RESETb) From Sub-Menu back to home position
• - no operation" - password protected# - press and hold down PARA, press UP in addition to PARA, release both
!NoteNoteNoteNoteIn the following paragraphs key symbols are mainlyused when explaining an operational procedure.Keys with the term "long" on them have to be pressedfor about 2s for actuating the function. If there isnothing stated, the respective key has only to bepressed briefly.
Fig.: Display in HOME POSITION
22 TB MRD1-T 10.01 E
5.1.4 LEDs
LEDs arranged at the relay front can light up in dif-ferent colours and can also either show permanentlight or flash in different frequencies.
LED lights up ON / OFF-ratio
green / redein / on
aus / off
green / red flashing a
green / red flashing b
t
Meaning of the LED-signals
LED name LED lights up Meaning
POWER green • Device OK
red flashing a • FAULT of an internal supply
off • Device OFF
TRIP off • Normal
red • Tripred flashing a • Energized
TEST off • Normal
red flashing a • OFFLINE-TEST-mode active
EDIT off • Normal, VIEW mode
red • EDIT mode after password access
MODIFIED off • Normal
red • EDIT mode: parameter modified
Relay off • Relays off
red
green
• Relays energized
• Relay-test
red flashing b • Relay off after energizing (until DEVICE RESET)
red flashing a • Relay blocked
SELFTEST green • Protection o.k. (selftest relay on)
red • System initialization (after power on)
red flashing a • OFFLINE TEST mode / Relay-TEST. no protec-tion, only messages
off • Internal fault. no protection
TB MRD1-T 10.01 E 23
5.1.5 VIEW mode / EDIT mode
There are two modes for selecting PARAMETERpages:A short press on the PARA-key activates the VIEW-mode. The EDIT-mode can be selected by pressingthe PARA-key for approx. 2 s (long press).• VIEW mode (viewing)
On pressing the key this mode only allows viewingthe active parameters
• EDIT mode (processing)Unlike in mode VIEW, in EDIT mode one of thefour parameter sets can be selected. That parame-ter set is then copied automatically into the EDITmemory and can be viewed there. At the first at-tempt of changing a parameter, the password isrequested. After entering the password (LED EDITlights up if the password was correct), the parame-ter can be changed. For any further change of pa-rameter(s) the password is not requested again. Incase the user does not know the password, thepassword entering mode can be cancelled andstill parameter sets be viewed but as explainedabove, they cannot be changed.
It is not necessary to acknowledge any changeseparately by pressing the ENTER key since at firsteverything is processed in the EDIT memory only.Each of the changes can be cancelled again. LEDMODIFIED indicates that the parameter displayedwas changed. If it should be set back to the initialvalue, only brief actuation of key RESET (cancelfunction) is needed. If the process is closed (with:ENTER, long), all the changes can be rejectedagain or be accepted. (Checkback: ARE YOUSURE?). Before the parameter set ist finally storedan internal plausibility check is performed to ensurethat all settings are conclusive. If the check routinedetects a irresolute combination of settings, theuser will be informed and the settings are notstored. e.g. an unsuitable combination of trans-former rated current (which is calculated from ratedvoltage and power capacity setting) an the settedCT primary rated current.
The protection program executed in the MRD1 at thetime is not effected by this procedure. Values of theactive parameter sets filed in the PARAMETER mem-ory are still being used until the complete EDIT mem-ory is recopied into the respective PARAMETERmemory. Only then all changes made taking effecttogether in the protection program.
!NoteNoteNoteNote
If during processing the aux. voltage fails, the com-plete EDIT memory is erased. After aux. voltage hasreturned, the protection program starts with those set-tings which were stored in the PARAMETER memorybefore the last processing operations. By this it is en-sured that the protection program does not work withincompletely changed data or meaningless data.
If due to the continously running check-sum test dataerror or loss of parameter memory is noted duringstart-up of the relay or during operation, a defaultparameter is loaded automatically. In such case therelay changes to the Offline mode (see next chapter)and the self-supervision relay de-energizes.
The EDIT-mode is left automatically if there is no inputlonger than 10 minutes (time out). Changed parame-ters wil not be stored.
24 TB MRD1-T 10.01 E
5.1.6 OFFLINE-TEST mode
For testing a parameter set the OFFLINE TEST modecan be activated. In this mode all output relays arebeing switched off. Now it can be changed over toanother parameter set for testing without risking nui-sance tripping. If the parameter set causes tripping,alarms are only shown on the MRD1 display or indi-cated via LEDs. The OFFLINE TEST mode is enabledor disabled on the SYSTEM SETTING page.
The OFFLINE TEST mode is indicated by:• Self-supervision relay de-energizes
(to inform the control system about the missingprotection function)
• Self-supervision LED flashes red (= no protection)• LED TEST flashes red (= TEST mode active)
!Important NotesImportant NotesImportant NotesImportant Notes
To prevent an unintended trip the OFFLINE TESTmode is activated as default setting on first commis-sioning. When the MRD1 recognizes a damagedparameter memory the default settings are loadedautomatically and the Offline mode is activated (withselftest relay unenergized).
During OFFLINE TEST mode the transformer is notprotected by the MRD1. Although a failure could bedetected during this mode, the MRD1 would not ini-tiate a trip of the transformer.
In order to prevent dangerous conditions, the trans-former must either have a sufficient backup protectionor has to be switched off.
After an intended OFFLINE TEST this mode must bedisabled so that protection is ensured again.
5.1.7 Reset (DEVICE RESET)
System messages in the display can be cancelledwith a short press on the RESET key. The message isnot removed at all but stored in the EVENT-memory.A trip will also cause a message which is also to becancelled with a short RESET press. After this allmeasured and calculated values can be recalledfrom the fault recorder. All output relays and LEDs (ifset to self-holding contact) will remain in energizedposition until a DEVICE RESET is initiated to theMRD1 by a long RESET press from home position.The DEVICE RESET can also be initiated by the ex-ternal reset input or via serial interface.
Info-messages do not need to be reset manually.They extinguish automatically after 5 s.
TB MRD1-T 10.01 E 25
5.1.8 Enter password
The MRD1 calls for a password if parameters are in-tended to be changed in the memory or other impor-tant functions to be activated. Nearly all data can becalled off by the user without entering a password,but for changing any data, the password is required.Some test functions can only be started after thepassword has been entered (see chapter 5.5).If a password is required this is indicated on the dis-play. The password consists of four digits and keycombination , has to be actuated.
Display Process Key
request to enter password
entering password
with every keypress a further willappear in the display
"
password correct.LED EDIT on
"
password incorrectLED EDIT remains off
Table: Procedure for entering a password
" Message appears for app. 2 s
!NoteAny process started can be stopped at any time bypressing key RESET:
The password entered at our works consists of key
sequence It is adviseable to change this password immediatelyto an individual one.
LED EDIT indicates if the password entered is cor-rect. In this state changes on MRD1 settings can bemade. When changing over to another function insome cases the password has to be entered again.Also after storing or cancelling, editing authority be-comes invalid. Hence it is very important that the re-lay is only left after LED EDIT has extinguished to pre-vent unauthorized change of settings.
5.1.9 Password forgotten
! ImportantIn case the password has been forgotten our workshave to be contacted to inquire about the measuresfor regaining access.
26 TB MRD1-T 10.01 E
TB MRD1-T 10.01 E 27
5.2 SYSTEM settings
5.2.1 Selection
On this page the general functions are shown whichare not stored in the four parameter sets. They arestored separately and always apply, irrespectively ofthe parameter set selected. The SYSTEM SETTINGScan only be selected from Home Display.
page select Display
+ "
" Starting at Home Display: press UP and hold, press PARA inaddition to, release both
SYSTEMparameterpage
line 1line 2line 3line 4...
select line
change value
password access
line 2[___________]
line 2[acual setting]
to change a value or start an operation :ENTER
to confirm or saveENTER
Fig.: System settings, principle
Note:
To change any setting or start an operation:• Select parameter or option with UP / DOWN• Press ENTER• Enter password if requested• If necessary: select setting with the +/- keys.
On setting date/time the arrow keys (up/down) are used to scroll to the next value.• Press ENTER to get new value valid.
28 TB MRD1-T 10.01 E
5.2.2 Overview
Key Existing lines Settings Range Default Actualsetting
scroll
Headline
change time and date see5.2.3
rated frequency in Hz 50 Hz60 Hz
50 Hz
select serial port disableRS232RS485CAN
RS485
Slave-address of RS485-interface 1-32 1
A...F Goup selectiont Time-/Date setting via
master
"
programming via interface enabledisable
disable
parameter set switch over via interface enabledisable
disable
activate Offline-TEST-Mode enabledisable
enable
select active parameter set 1 ... 4 1
change password see5.2.4
clear all parameter sets and set to defaultThe device switches to OFFLINE TESTmode automatically!
clear event recorder
clear fault recorder
Table: SYSTEM settings page, overview
" Select with cursor and
To change any setting or start an operation press
while shown in display.
TB MRD1-T 10.01 E 29
5.2.3 Time / Date
Key Display Remark Change value Setting range
Headline • Password input
scroll
change year 1980-2099
change month 1-12
change day 1-31(depends on year/month)
change hours 0-23
change minutes 0-59
change seconds 0-59
accept settings andstart new time / date
• •
cancel settings and restore oldtime / date
• •
• No selection possible
Table: Date /time-setting
!NoteNoteNoteNoteBoth arrow keys have the same function for this set-ting procedure. Both move the cursor always to thenext digit group. After reaching the SECOND col-umn, it is switched back to YEAR again. Digits for theyear and month have to be entered before digit(s) forthe day to enable the MRD1 to carry out correct cal-culation of intercalary days as well as the max. daysin a month. The internal clock does not stop duringthe setting procedure so that when cancelled byRESET key the actual time is not changed. Afterpressing ENTER the modified time becomes valid.
Date/time setting may be synchronized via serial in-terface (see setting "GROUP ADDRESS").
30 TB MRD1-T 10.01 E
5.2.4 Password change
The password in the MRD1 can be changed at anytime. For changing a password it is necessary toknow the present one. To rule out any typing errors,the password has to be entered twice. If the entriesare not identical, the password is not changed andthe previous one still applies. (Please see table be-low).
Display Step Key
Password change with ENTER
Request to enter old password
enter new password
enter new password again
" changing done
" The new password wouldn’t betyped 2 times identically
Try again " message appears for app. 2 s
Table: Password change, procedure
TB MRD1-T 10.01 E 31
5.3 PARAMETER-pages
5.3.1 Selection
This table gives an overview about all pages of aparameter set and the parameters belonging to.
Select PARAMETER-pages in VIEW- or EDIT mode
Key Display Remark
short
VIEW active parameter set continued at 5.3.2.
long
EDIT modeselect one of the four parameter setsto view or editconfirm with ENTER
e.g. set 2 was loaded and is nowready for editing
continued at 5.3.2.
PARApages
page 1page 2page 3page 4...
page 2
param 2.1param 2.2param 2.3param 2.4...
PARAMETER 2.3[ value ]
leaf to nextpage
select line
change value
password access
Fig: Parameter pages, organization
Possibilities after modifying a parameter:
• Keep modifications and scroll to next line (up/down)• Keep modifications and leaf to next page (PARA short)• Cancel modification of the displayed value (RESET short)• Finish working, accept all modifications and store (ENTER long)• Finish working and refuse all modifications, no store (RESET long)
32 TB MRD1-T 10.01 E
5.3.2 Overview
Key PagesHeadline
Parameter see
leaf to nextpage
or
Parameter pages active parameter ready for viewing(e.g. set 1)
selected set ready for viewing and editing(e.g. set 2)
Data of pro-tected device forall windingsW 1W 2W 3
Rated powerRated voltageCT primary currentConnection groupPhase shifttap ratioCT connection
5.3.3
parameter ofdifferential-protection
Difference current at Is=0 × InDifference current at Is=2 × InDifference current at Is=10 × Inmax. Difference current Idiff>>d[Id] Offset in case of harmonics
5.3.4
Parameter of lo-gic functions
Assignment of protective and logic functions(AND-logic)
Parameter ofoutput relays
Reset time or self-holding of the output relay 5.3.5
Parameter of ex-ternal blocking
Table: Parameter pages, overview
On the first attempt to change a setting with the+/- keys in a edit session the password is asked. Toview only parameter settings the PARA key is used toleaf to the next page and the UP/DOWN keys areused to select the parameter.
TB M
RD1-
T 1
0.01
E33
5.3
.3
Transf
orm
er r
atings
Key
Dis
play
Para
met
erA
vaila
ble
in M
RD1-
T2
T
3
Sele
ctSe
tting
rang
e
(• n
o se
lect
ion)
Def
ault
actu
al
Set 1
Set 2
Set 3
Set 4
Hea
dlin
e×
×no
ne•
••
••
•
rate
d ap
pare
nt p
ower
of
win
ding
1(H
igh-
volta
ge-si
de)
××
10 k
VA -
800
MVA
17.3
MVA
corre
spon
ding
to w
indi
ng 2
×10
kVA
- 80
0 M
VA17
.3 M
VA
corre
spon
ding
to w
indi
ng 3
×10
kVA
- 80
0 M
VA17
.3 M
VA
rate
d vo
ltage
of w
indi
ng 1
(pha
se to
pha
se v
olta
ge o
n hi
gh-
volta
ge-si
de)
××
100
V....
800
kV20
kVA
corre
spon
ding
to w
indi
ng 2
××
100
V....
800
kV6.
6 kV
corre
spon
ding
to w
indi
ng 3
×10
0 V.
...80
0 kV
6.6
kV
rate
d pr
imar
y cu
rrent
of p
hase
CT
win
ding
1×
×1.
....5
0.00
0 A
500
A
corre
spon
ding
to w
indi
ng 2
××
1....
.50.
000
A15
00 A
corre
spon
ding
to w
indi
ng 3
×1.
....5
0.00
0 A
1500
A
34TB
MRD
1-T
10.
01 E
Key
Dis
play
Para
met
erA
vaila
ble
in M
RD1-
T2
T
3
Sele
ctSe
tting
rang
e
(• n
o se
lect
ion)
Def
ault
actu
al
Set 1
Set 2
Set 3
Set 4
conn
ectio
n sy
stem
of w
indi
ng 1
××
wye
, del
ta, z
igza
g,w
ye+n
, zig
zag+
nw
ye +
n
corre
spon
ding
to w
indi
ng 2
××
wye
, del
ta, z
igza
g,w
ye+n
, zig
zag+
nw
ye +
n
phas
e sh
ift in
win
ding
2 i
n ×
30°
in re
latio
n to
win
ding
1×
×0-
110
conn
ectio
n sy
stem
in w
indi
ng 3
×w
ye, d
elta
, zig
zag,
wye
+n, z
igza
g+n
wye
+ n
phas
e sh
ift in
win
ding
3 i
n ×
30°
in re
latio
n to
win
ding
1×
0-11
0
volta
ge d
ispla
cem
ent b
y tra
nsfo
rmer
tap
chan
ger i
n w
indi
ng 1
××
- 20
%...
+ 20
%0,
0
Win
ding
1 C
T co
nnec
tion
in n
or-
mal
pol
arity
(lik
e co
nnec
tion
dia-
gram
) or i
nver
ted
(reve
rse
pola
rity)
"
××
norm
al,
inve
rted
norm
al
corre
spon
ding
to w
indi
ng 2
"×
×no
rmal
,in
verte
dno
rmal
corre
spon
ding
to w
indi
ng 3
"×
norm
al,
inve
rted
norm
al
" N
OTE
: The
Par
amet
er m
ust b
e se
t to
inve
rted
pola
rity,
if th
e di
rect
ion
of c
urre
nt fl
ow in
the
seco
ndar
y ci
rcui
t is
reve
rse
to th
e in
put t
erm
inal
s of
MRD
1 ac
cord
ing
to th
eco
nnec
tion
diag
ram
(Cha
pter
10)
.
TB MRD1-T 10.01 E 35
5.3.4 Protection parameters
Differential protection
The tripping characteristic of the MRD1 can be set with four parameters:
Idiff0: Error caused by no load current and error of the CTsIdiff2: Additional error by tap and linear error of the CTs (linear range of the CTs)Idiff10: Additional error by saturation of the CTsIdiff>>: maximum permitted difference currentd[Id]: raise up of characteristic curve by offset in case of characteristic harmonics
In: Transformer nominal current
0Stabilisierungsstromstabilizing currentIs / In
Differenzstromdifferential currentId / In
5
Idiff (Is/In=10)
10
Idiff >>
1
2
8
Einstellbereich der Kennliniesetting range of characteristic
2
8
I
II
III
Idiff (Is/In=2)Idiff (Is/In=0)
1
0,20,10,5
d[Id]
Fig: Possible setting range of the characteristic
36TB
MRD
1-T
10.
01 E
Key
Dis
play
Para
met
ers
of th
e ch
arac
teris
ticSe
lect
Setti
ng ra
nge
(• n
o se
lect
ion)
Pre-
adju
st-m
ent
actu
al
Set 1
Set 2
Set 3
Set 4
Hea
dlin
eno
ne•
••
••
•
diffe
rent
ial c
urre
nt Id
iff a
t sta
biliz
ing
curre
ntIs/
In=0
(s
ee p
ictu
re) #
0.1.
..0.5
× In
"0.
5
corre
spon
ding
to Is
/In
=2 #
0.2.
..1 ×
In"
1.0
corre
spon
ding
to Is
/In
=10 #
2.0.
..8.0
× In
8.0
max
imum
per
mitt
ed d
iffer
entia
l cur
rent
2.0.
..20.
0 ×
In20
.0
Offs
et o
f cha
ract
erist
ic c
urve
from
sta
tic b
asic
char
acte
ristic
cur
ve0.
0...8
.02.
0
Tabl
e: A
djus
tabl
e pr
otec
tion
para
met
er
" T
o ge
t no
nega
tive
slope
in th
e ch
arac
teris
tic p
art I
the
setti
ng Id
iff (I
s=2)
mus
t not
be
less
then
the
setti
ng Id
iff (I
s=0)
. The
MRD
1 w
ill ch
eck
the
inpu
ts on
this
mus
t.
# In
= T
rans
form
er n
omin
al c
urre
nt
TB M
RD1-
T 1
0.01
E37
5.3
.5
Rel
ay-s
ettings
Key
Dis
play
Setti
ngSe
lect
Setti
ng ra
nge
(• n
o se
lect
ion)
defa
ult
actu
al
Set 1
Set 2
Set 3
Set 4
head
line
none
••
••
•
Ass
ignm
ent o
f rel
ay 1
to lo
gic
func
tions
A...
P,O
R-lo
gic
[ ↵]
ABC
....P
AB.
...
corre
spon
ding
to re
lay
2
[ ↵]
ABC
....P
AB.
...
corre
spon
ding
to re
lay
3
[ ↵]
ABC
....P
AB.
...
corre
spon
ding
to re
lay
4
[ ↵]
ABC
....P
AB.
...
corre
spon
ding
to re
lay
6
[ ↵]
ABC
....P
AB.
...
corre
spon
ding
to re
lay
7
[ ↵]
ABC
....P
AB.
...
corre
spon
ding
to re
lay
8
[ ↵]
ABC
....P
AB.
...
corre
spon
ding
to re
lay
9
[ ↵]
ABC
....P
AB.
...
optio
-na
l
corre
spon
ding
to re
lay
10
[ ↵]
ABC
....P
AB.
...
38TB
MRD
1-T
10.
01 E
Key
Dis
play
Setti
ngSe
lect
Setti
ng ra
nge
(• n
o se
lect
ion)
defa
ult
actu
al
Set 1
Set 2
Set 3
Set 4
min
imun
Res
et ti
me
/la
tchi
ng ti
me
for r
elay
10.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
corre
spon
ding
to re
lay
20.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
corre
spon
ding
to re
lay
30.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
corre
spon
ding
to re
lay
40.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
ifeq
uippe
d
corre
spon
ding
to re
lay
6 (If
equ
ippe
d)0.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
corre
spon
ding
to re
lay
7 (If
equ
ippe
d)0.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
corre
spon
ding
to re
lay
8 (If
equ
ippe
d)0.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
corre
spon
ding
to re
lay
9 (If
equ
ippe
d)0.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
corre
spon
ding
to re
lay
10 (I
f equ
ippe
d)0.
00 ..
.. 1
.00s
/ex
it
"
0.2
s
Tabl
e: R
eset
tim
e of
the
outp
ut re
lays
" T
he re
set t
ime
ist th
e m
inim
um ti
me
the
rela
y ke
eps
ener
gize
d af
ter a
trip
. If t
he ti
me
is se
t to
exit
the
outp
ut re
lay
is co
nfig
urat
ed a
s a
latc
hing
con
tact
.
The
rela
y ke
eps
ener
gize
d af
ter a
trip
unt
il th
e M
RD1
is RE
SETe
d. (D
EVIC
E RE
SET)
39TB
MRD
1-T
10.
01 E
5.3
.6
Sett
ing o
f lo
gic
funct
ions
Taste
Dis
play
Setti
ngSe
lect
Setti
ng ra
nge
(• n
o se
lect
ion)
Def
ault
Act
ual
Set 1
Set 2
Set 3
Set4
Hea
der l
ine
Ass
ignm
ent o
f log
ic fu
nctio
ns A
to p
rote
ctiv
e fu
ncti-
ons
(her
e: p
rote
ctiv
e fu
nctio
n A
= Id
>)
Ass
ignm
ent o
f log
ic fu
nctio
ns B
to p
rote
ctiv
e fu
ncti-
ons
(her
e: p
rote
ctiv
e fu
nctio
n B=
Id>>
)
Ass
ignm
ent o
f log
ic fu
nctio
ns C
to p
rote
ctiv
e fu
nc-
tions
(her
e: p
rote
ctiv
e fu
nctio
n A
and
B)
Ass
ignm
ent o
f log
ic fu
nctio
ns P
to p
rote
ctiv
e fu
nc-
tions
(her
e: n
o pr
otec
tive
func
tion)
!N
ota
Not
aN
ota
Not
aFo
r MRD
1 th
ere
is th
e fo
llow
ing
defin
ition
:Pt
otec
tive
func
tion
A: D
iffer
entia
l pro
tect
ion
Id>
(Low
Set
)Pr
otec
tive
func
tion
B: Id
> (H
igh
Set)
40 TB MRD1-T 10.01 E
Scheme:
41TB
MRD
1-T
10.
01 E
5.3
.7
Blo
ckin
g S
etting
Key
Dis
play
Setti
ngSe
lect
Setti
ng ra
nge
(• n
o se
lect
ion)
Vor-
eins
tel-
lung
Sele
ct
Set 1
Set 2
Set 3
Set 4
Hea
der L
ine
Bloc
king
of p
rote
ctiv
e fu
nctio
ns(h
ere:
pro
tect
ive
func
tion
A a
nd B
)--,
AB
AB
Min
hol
d tim
e of
blo
ckin
g«e
xit»:
no m
in. h
old
time
0.0
... 6
0.0
exit
0.1s
Max
. blo
ccki
ng ti
me
whe
n co
ntin
uoui
ng b
lock
ing
si-gn
al «
exit»
: lat
ched
as
long
as
signa
l hol
ds0.
1 ...
60.
0ex
it2.
0s
42 TB MRD1-T 10.01 E
5.3.8 Validity check
The MRD1 is provided with a special parameterchecking facility as protection against wrong set-tings. However, to prevent that the actual settingrange is too much restricted , this facility can onlyprotect against gross setting errors. Before they arestored, changed settings are checked for their mu-tual validity. The procedure is such that firstly theparameters are compared to the calculated ratedcurrents IN (per winding) of the component, whichresult from the rated apparent power and ratedvoltage. Thereafter interrelation of the parameters ischecked.If there is a discrepancy when setting parametersvia the keyboard, either the MRD1 does not allowthe respective value to be further changed or refersto the inconsistent value
by issuing a clear text message when trying tostore the parameter. In this case the EDIT mode isnot left and the value can be corrected.When setting parameters via an interface, validityerrors are indicated by a spezial telegramm mes-sage.
A setting is not regarded to be valid if one of thefollowing conditions are not met :
• CT mismatch for each winding1/8 × IN < IWPN < 2 × IN
• CT transformation ratio at MRD1 rated currentIWPN ≥ 5 A
• Relation of voltage levelsFor three-winding transformers (MRD1-T3)UN Winding 1 ≥ UN Winding 2 ≥ UN Winding 3
For two-winding transformers (MRD1-T2)UN Winding 1 ≥ UN Winding 2
• Tripping characteristicId(IS=0) ≤ Id(IS=2)i.e.gradient Sector I ≥ 0andgradient Sector I ≤ gradient Sector II
• Ext. Blockagetmin > tmax
minimum hold time is greater than maximum holdtime
Abbreviations :Abbreviations :Abbreviations :Abbreviations :
SN set rated vector powerUN set rated component voltage (phase-to-phase voltage)IN rated component current (IN = SN / √3 x UN)) calculated from UN and SN
IWPN set rated C.T. primary currentGradient characteristic gradient in the respective linear sector (see chapter 5.3.4)
TB MRD1-T 10.01 E 43
5.4 DATA pages
5.4.1 Selection
All measured, calculated and stored data canbe recalled on the data pages
Key Display
DATApage
page 1
Fault RecEvent Rec
page 1
meas. 1.1meas. 1.2meas. 1.3...
measurement 1 .3[ value ]
leaf to nextpage
select line
Data recorder (last but one)
time
FAULT EVENTI DIFF> TRIP
select a stored value
date event value 1 value 2 ...
DATA recorder
1 2 3 4 ....
Fig.: Data pages, organization
44 TB MRD1-T 10.01 E
5.4.2 Overview
Key PageHeadline
Data
leaf to nextpage
Data pages selected
Actual measurementsand calculated datas
Phase current (L1 L2 L3)Differential currentStabilizing current Is (fundamental oszillation analysis)Stabilizing factor m (harmonic analysis)
Recall stored trip datas Trip message, date / time ,measurementscalculated measurements
Recall event messages Message textdate / time
Recall statistic Data Operating hoursTrip counterAlarm counter
Table: Data pages, overview
TB MRD1-T 10.01 E 45
5.4.3 Measured and calculated data
Key Display Data
scroll
Headline
Actual measuring value of the phase current L1of winding 1 in A
corresponding to L2
corresponding to L3
...etc. Phase current in A (all phases, all windings)
calculated difference current (Idiff) "calculated stabilizing current (Irestr) "calculated stab. factor (harm restr.)
Table: Operational measured data
" related to the transformer nominal current
46 TB MRD1-T 10.01 E
5.4.4 FAULT Recorder
Key Display Value
scroll
Headline
see be-
low
Record 0 (last trip)Trip number date/timetrip reason,all stored data
Record 1 (last trip but one)Trip number date/timetrip reason,all stored data
for all existing registers Record n in chronological or-der
Trip number date/timetrip reason,all stored data
The display shows „“ at the end of the list or if no trips are stored.
Table: Fault-Recorder
Key Display Value
next value
Headline of the last trip (e.g.)
Trip number
Reason of the trip
Date of trip
Time of trip
Current L1 of winding 1 in A
etc. corresponding for all storeddatas
Table: Data of a fault recorder
TB MRD1-T 10.01 E 47
5.4.5 EVENT-Recorder
Key Display Value
scroll
headline
see below
Event 0event messagedate/timeof the last event
Event 1event messagedate/timeof the last trip but one(previous)
corresponding to all storedevents
Event nevent messagedate/timein chronological order
The display shows „“ at the end of the list.
Table: Event-Recorder
Key Display Value
next value
Event number and event mes-sage
e.g. last event
Date of event
Time of event
Table: Message and time / date
48 TB MRD1-T 10.01 E
5.4.6 Statistic data
Key Display Value
next value
Headline
MRD1 Operating hours
Trip counter
Alarm counter
Table: Statistic data
!NoteNoteNoteNoteThis statistic counters can not be resetted.
TB MRD1-T 10.01 E 49
5.5 TEST-routines page (Self-test)
5.5.1 Page selectionPage select Display
TEST-routines
test 1test 2test 3...
test 2
select testpassword access
start test
test is running
50 TB MRD1-T 10.01 E
5.5.2 Overview
Key Test Description execute
scroll
Headline
Display of version and date of the software onlydisplay
Test Test of the LEDs:
all LEDs will be illuminated green and red for twoseconds (no password needed)
Test Test of the output relays:
IMPORTANT: all relays will be energised in a 1 sinterval. The Selftest Relay keeps off for the durationof the test. After the test all relays will be set to thestate before.
"
Test Memory / program test:
This routine will test the memory and the programby calculating a checksum.
" NOTE: Password is needed, because the protection function is disabled during the test!
Table: Implemented test routines
TB MRD1-T 10.01 E 51
5.6 Parameter programming help
This chapter is a step by step help how to enter the first specific settings into the MRD1 by keyboard. Formore information about the parameter and its setting ranges see chapters: PARAMETER-pages andSYSTEM settings.
Step Key
1 select PARAMETER-page in EDIT-mode
long
2 if necessary: select the set No. to edit
3 confirm selection(set will be loaded in EDIT memory)
4 leaf to first parameter page
5 scroll to the first line of this page(first parameter)
6 if necessary:change displayed value
on first modification: enter password
For bit-wise parameter like system-parameter “Group Ad-dress” press [↵ ] shortly
7 scroll to next line(second parameter)
there is no need to confirm the modification of step 6with a separately ENTER press.
8 if necessary:change displayed value
repeat step 6 and 7 as long as needed
9 leaf to next page
continue at step 5
52 TB MRD1-T 10.01 E
Other operations Keyfinish working and store all modifications(EDIT-memory will be copied back to parameter memory)
long
abandon working and refuse all modifications(no storing)
long
cancel modification on the displayed parameter and reset to oldvalue.(if LED MODIFIED illuminated) short
edit another parameter set finish with ENTER long or RESET long andcontinue on step 1
!NoteNoteNoteNoteThere is no need to confirm any modification by pressing ENTER. All modifications are temporarily storedin the edit memory when scrolling with up/down keys. When pressing ENTER long all modifications in theedit memory will be stored in the parameter set memory after an ensurance request.
TB MRD1-T 10.01 E 53
6 Relay Tests
For testing the MRD1 the following has to be takeninto account:The test current source must supply a current free ofharmonics. Should this not be the case, measuringerrors may result from this if the reference ammeterused is an RMS instrument (which is common prac-tice).
Test circuits for differential current Idiff and stabilizingcurrent Is:
The rated value indication for differential currentand stabilizing current can be gathered from thefollowing table. Test current I should be in compli-ance with the transformer nominal current.
A B C DIdiff 2/3 × I 0 1× In 0Is 0 2/3 × I 0 1 × In
Value indications dependent on the test circuit used
I
MRD1
B3
B4
B5
B6
B7
B8
I
MRD1
A3
A4
A5
A6
A7
A8
W1
W2
W1
W2
B3
B4
B5
B6
B7
B8
A3
A4
A5
A6
A7
A8
A A
A) B)
MRD1
W1
W2
I
B3
B4
B5
B6
B7
B8
A3
A4
A5
A6
A7
A8
I
I L1
L2
L3
L1
L2L3
LFG1
A
A
A
D)
Symmetrisches Dreiphasensystemsymmetrical three phasesystem
MRD1
W1
W2
I
B3
B4
B5
B6
B7
B8
A3
A4
A5
A6
A7
A8
I
IL1
L2
L3
L1
L2L3
LFG1
A
A
A
C)
Symmetrisches Dreiphasensystemsymmetrical three phasesystem
NOTE for relay tests:• Stated accuracies apply to rated values• Currents must be free of harmonics• When a three-phase connection is used for the test, the current must form a symmetric system• Parameters W1 CT connection and W2 CT connection must be in normal position• Rated data parameters must be adjusted for a transformer of vector group Yy0• The settings of the primary nominal current of the CTs and the nominal voltages for all windings must be
the equal (transmission ratio 1:1).• LFG = |SEG-Power Function Generator
54 TB MRD1-T 10.01 E
7 Commissioning
7.1 Check list
Check Remark ok.Safety Measures Observe relevant safety regulationsAux. voltage range Prior to connection it has to be checked whether existing aux. voltage is
within the permissible range for MRD1Rated system data Secondary currents of CTs provided in the system have to be in compli-
ance with rated currents of the MRD1 (1 A or 5A) in the respective wind-ing
Connection Check MRD1 for correct connection in the switchboardEntry of rated systemdata
Has all rated system data correctly been programmed ?Are the indices of the vector group setted.Are the CTs connected normal or revers
Setting of parame-ters for protection
Have all parameters for protection correctly been programmed ?
Reset time Are the reset times set to all output relays?Selection of workparameter set
Has the right parameter set been selected as working set?
Protection function Does LED SELF-TEST light up green and is Selftest relay energized ?Device tests Selftest routines
- Lamptest- Test of the output relays- Checksum test- Test of the working parameter set in OFFLINE TEST mode
TB MRD1-T 10.01 E 55
7.2 C.T. connection
The right polarity of the C.T. is very important andso when the MRD1 is initially connected this has tobe checked carefully. Reverse polarity at even oneC.T. only is likely to cause trip errors. Whetherconnection of the MRD1 is correct can roughly beseen from the differential current indication, pro-vided the object to be protected operates trouble-free. To check the correct C.T. connection, firstlythe MRD1 should be operated at the object to beprotected in OFFLINE TEST mode.
! Important Note:In this operational mode, the object to be protectedmust have a sufficient back-up protection. Further-more it is assumed that the supervised componentis not faulty and all parameters are correct. Whenin OFFLINE TEST mode it is ensured that a CT withperhaps reverse polarity does not cause an unin-tended trip.
Now the supervised component can be switchedon while observing and interpreting the differentialcurrent indication. Interpretation of the indicatedvalue is always subject to local conditions (opera-tion related fault current) and can here only be de-scribed generally. The test circuits described inchapter 6 can be of help for fault identification.
The following table can be considered as refer-ence when checking the connection. The statedvalues are based on symmetrical load I=IL1=IL2=IL3.Where loads are involved which are not 100 %symmetrical, the observed values may deviate fromthe table. All figures are to be understood as ap-proximate values and are a multiple of the loadcurrent.
Case Differential currentIdiff / In
Through currentIs / In
1 All CTs are correctly connected 0 12 One CT connect. with rev.polarity 1,33 0,663 Two CTs connect. with rev.polarity 2,0 04 Three CTs connect. with rev.polarity 2,0 0
Table: Recommended values for differential current and stabilizing current indication at the MRD1 with assumed faultlesscomponents and different numbers of CTs connected
1) Correct connection :All C.T.s are correctly connected. This case is iden-tical to that where all C.T.s are wrongly connectedor the direction of energy flow is reverse. Butchanges at the C.T. connection are not necessary.
2) One C.T. wrongly connectedIn this case the current balance is out of place.There is about 1/3 x I through current missing andthe MRD1 recognizes 2/3 x I differential currentinstead. Input and output currents in the phase withwrong polarity are interpreted by the MRD1 thatway as if 1/3 x I each flow into the faulty phase.Thus the resulting differential current is 2/3 x I.
3 / 4) Two or three C.T.s wrongly connectedIn these two cases the indication does not distin-guish between two or three C.T.s wrongly con-nected because of the internal calculation. If threeCTs are wrongly connected, the respective faultcan be eliminated by changing parameter "C.T.Connection" without having to change the wiring .
For locating all other faults either the complete C.T.wiring has to be checked after disconnection of thecomponent or the reversed connections to betraced by means of a suitable test current source.
56 TB MRD1-T 10.01 E
8 Technical Data
8.1 MRD - Transformer Differential Protection Relay
Common data
Rated frequency: 50 Hz, 60 HzDisplay: LED and LCD-Display (2 × 16 digits)
Voltage supply
Aux. voltage ranges Range Rated voltage RangeDC L 24 V 19-40 V
M 48/60 V 38-72 VH 110/125/220 V 88-264 V
AC on request
Power consumption stand-by 13 VAmaximum 16 VA
Permissible interruption of the max. 50 ms (at rated voltage)auxiliary voltage supply
Input CTa) Phase current CT
Rated current IN 1 A or 5 APower consumption in current path: at IN: < 0.1 VA
Thermal withstand capabilityin current circuit: 250 × IN (VDE 435, T303),
dynamical current withstand (half-wave)100 × IN for 1 s30 × IN for 10 s4 × IN continuously (VDE 435, T303)
linear range Low-Range 0.05...2 × INHigh-Range 2...64 × IN
Range setting automatical
Resolution 12 Bit per range
Failure < 0.1 % at IN< 0.1 % at 64 × IN
Accuracy 0.05×IN <2%(related to the measured value) 1×IN <1%
15×IN <2%
Operating time 25-30 msC.T. requirements: recommended min. requirements to expoit device accuracy 5P20
TB MRD1-T 10.01 E 57
Function- and signal inputs
Digital inputs
Thermal withstand capability max. 310 V DC, 265 V ACCoupling galvanically isolated with common return wireHigh-level U > 18 V DC/ACLow-level U < 12 V DC/AC
Reset and blocking input
Thermal withstand capability max. 310 V DC, 265 V ACCoupling galvanically isolated with common return wire (D8)High-level U > 18 V DC/AC function activatedLow-level U < 12 V DC/AC Function not activated
Communication serial interface RS232C
Data transmission rate 9600 BaudConnection 9-pin D-sub plugInsulation voltages DIN 19244 part 3 (IEC 870-3):
RS485
Data transmission rate 9600 BaudConnection plugged terminals
(RXT/TXD-P, RXT/TXD-N, Signal Ground, PE)Insulation voltages DIN 19244 part 3 (IEC 870-3):
Output relay
Contact class IIB DIN VDE 435 part 120max. breaking voltage: 250 VAC / 300 VDCmax. closing power: 1500 VA (250 V)max. breaking power: 11 VA (220 VDC) at L/R = 40 msmax. rating making current: 6 AShort circuit current: 20A / 16 msRated inrush current load: 64AReturning time: 20 ms (without minimum operating time!)Contact material: AgCdOContact life span: electrical: 2x105 switching points at 220V AC / 6A
mechanical: 30x106 switching points
Rated insulation voltage: 600 VAC (450V DC / 380 VAC) (VDE 435, T303)Air- and creeping distance VDE 0160
Insulation coordination: pollution degree 3 for terminals, pollution degree 2 for the electronic
58 TB MRD1-T 10.01 E
Temperature range forOperation: -5°C to +55°C (within class 3K3)Transport: -25°C to +70°C (class 1K4)Storage: -25°C to +70°C (class 2K3)
Insulation test voltage, inputs and outputs between themselves andto the relay frame as per IEC 255-5: 2.0 kV (RMS.) / 50 Hz.; 1 min.
Impulse test voltage, inputs andoutputs between themselves andto the relay frame as per IEC 255-5: 5 kV; 1.2 / 50 µs, 0.5 J
High frequency interference testvoltage, inputs and outputs betweenthemselves and to the relay frame asper IEC 255-22-1: 2.5 kV / 1 MHz
Electrical discharge (ESD)test as per VDE 0843, part 2IEC 77B(CO)21; IEC 255-22-2: 8 kV
Electrical fast transient (Burst)test as per DIN VDE 0843, part 4IEC 77B(CO)22; IEC 255-22-4: 4 kV / 2.5 kHz, 15 ms
Radio interference suppressiontest as per EN 55011: limit value class B
Radiated electromagnetic fieldtest as per ENV 50140: electric field strength: 10 V / m
Power frequency magnetic fieldimmunity test 100 A/m continuousIEC 1000-4-8 (EN 61000-4-8): 1000 A/m 3 s
Surge immunity test(asymmetrical / symmetrical)IEC 1000-4-5 (EN 6100-4-5): 4 kV
Mechanical test:
Shock: Class 1 as per DIN IEC 255 T 21-2Vibration: Class 1 as per DIN IEC 255 T 21-1Degree of protection: Front IP40Overvoltage class: III
Setting ranges: s. tables chapter 5 and 10
GL-Approbation: 99 360-97 HH
TB MRD1-T 10.01 E 59
9 Tables / Connection diagrams
9.1 Possible event messages
Display Event
Parameterset x is selected to active working set
Parameter setting via interface is active
Parameter setting via interface is not permitted
Default parameter settings reloaded
Manual DEVICE RESET is performed
External DEVICE RESET is performed
Software DEVICE RESET is performed
Blocking feature activated by external input
End of blocking
Difference current trip
Difference current trip released
Difference current high-set trip
Difference current high-set trip released
Change output relay state (except Selftest relay)
Selftest relay is energized
Selftest supervision relay is de-energized
Lamp test is finished
Test of the output is finished
Self-test is finished
Offline-Test-Mode is active
Offline-Test-Mode is not active
Fault recorder is cleared
Event recorder is cleared
System start / device initialization
Time/date setting was changed (old time)
Time/date setting was changed (new time)
60 TB MRD1-T 10.01 E
9.2 View
Frontpanel:
Rear panel
Module 3Extension module
Module 2Central module
Module 1Base module
digital inputs
CAN-Bus
RS-485-port
reset- and blocking input
auxiliary voltageandearth connection
measuring inputsB column: W3 (low voltage side)
output Relays
measuring inputsA column: W2 (low / medium voltage side)B column: W1 (high voltage side)
output Relays
2
3
4
5
6
7
8
9
C D E
A B
12
34
5
6
78
F
1
2
3
4
5
6
7
8
9
C D E
A B
12
34
5
6
78
F
1
CAN1
CAN2
12345678910111213141516
SEG MRD1 RWI D
RS485
GND
PEPE
P
N
GNDP
N
TB MRD1-T 10.01 E 61
Fig.: Connection diagram MRD1-T2 (2-winding transformer)
The System W1 is assigned to the high voltage side.
Important Note.For perfect functioning of the rush stabilization system it is essential that the MRD-T is connected in the cor-rect phase sequence, i.e. that there is a positive rotating field. Refer also to page 11.
62 TB MRD1-T 10.01 E
Fig.: Connection diagram MRD1-T3 (3-winding transformer)
The System W1 is assigned to the high voltage side.If the voltages in the systems W2 and W3 are differ-ent, the system W3 must be assigned to the lower voltage level.
Technical data subject to change without notice!
Important Note.For perfect functioning of the rush stabiliza-tion system it is essential that the MRD-T isconnected in the correct phase sequence,i.e. that there is a positive rotating field.Refer also to page 11.
TB MRD1-T 10.01 E 63
10 Type code
Transformer - Differential protection
MRD1- T A2-winding3-winding
23
Rated current primary 1 A5 A
15
secondary 1 A5 A
15
tertiary(for 3-winding)
1 A5 A
15
DC-Auxiliary voltage24 V (19 to 40 V DC).........................................................48V / 60V (38 to 72 V DC)................................................110V / 125V / 220V (88 to 264 V DC)...............................
LMH
Housing (42TE) additional MRD1-T2-HTL-3F42 for T2+G resp. MRD1-T3-HTL-3F42 forT3 available "
" necessary rack for the single components
!NoteNoteNoteNoteNormally the MRD1 is provided with one type of current transformer only (1A or 5A). Equipment with twoCTs of different current ratings in one relay only on request.
64 TB MRD1-T 10.01 E